This is a fire protection system inspection and testing report conducted by ALARMSpecialists, Inc. at VA Hospital WCHCS Building 12 on March 21, 2023, documenting compliance with EC.02.03.05 requirements.
The report details testing of multiple fire protection system components: three pull stations in office/workroom and shop areas, a tamper switch control valve (2 turns), a water flow switch (28 second response), and six audio/visual notification devices including strobe zones, speaker/strobes, and horn/strobes in various locations throughout Building 12. All tested devices passed inspection according to required standards, with specific device labels and locations documented. The testing follows Joint Commission requirements for 12-month testing of manual fire alarm boxes and smoke detectors (EP 3), 6-month testing of water flow devices and valve tamper switches (EP 2), and 12-month testing of visual and audible fire alarms (EP 4).
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by ALARMSpecialists, Inc
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 3
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Pull Station OFFICE/WORKROOM BUILDING 12 N 3 L 5 M 3 Pass March 21, 2023 Pull Station SHOP AREA ROOM 102 BUILDING 12 N 3 L 5 M 4 Pass March 21, 2023 Pull Station SHOP AREA ROOM 103 BUILDING 12 N 3 L 5 M 5 Pass
EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
VA Hospital - WCHCS - Bldg 12 - Device List - March 23
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 3
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Tamper Switch TAMPER CONTROL VALVE BUILDING 12 N 3 L 5 M 1 Pass 2 TURNS March 21, 2023 Water Flow Switch WATERFLOW BUILDING 12 N 3 L 5 M 2 Pass 28 SEC
VA WCHCS - Bldg 12 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 3
Date Tested Device Floor Room # / Corridor Location / Description No de Lo op Device Label Status Comments March 21, 2023 Strobe Zone BLDG 12 STROBES CHILLER ROOM Building 12 N 3 L 1 M 82 Pass March 21, 2023 Speaker/Strobe Pipe Fitting Rm Building 12 N 3 L 5 x x 49798255 Pass March 21, 2023 Speaker/Strobe Paint Rm Building 12 N 3 L 5 x x 49798257 Pass March 21, 2023 Speaker/Strobe Rm 100A Storage Building 12 N 3 L 5 x x 49798259 Pass March 21, 2023 Horn/Strobe O/S North Side Building 12 N 3 L 5 x x Pass March 21, 2023 Speaker/Strobe Rm 100 Storage Building 12 N 3 L 5 x x 49798262 Pass
VA WCHCS - Bldg 12 - Audibles - Device List - March 23 EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented. Note: For additional guidance on performing tests, see NFPA 72-2010: Table 14.4.5.