VA WCHCS Bldg 35 Oneline Report 23.pdf
PDF 55 KB Posted
- Attached to
- H263--Fire Protection Services Federal contract opportunity
- Solicitation number
- 36C25925Q0190
About this file
This is a fire protection system inspection report from March 21, 2023, documenting testing of various fire safety devices in Building 35 of a VA Hospital (WCHCS facility). The report, prepared by ALARMSpecialists Inc., includes test results for three categories of devices: manual fire alarm boxes (pull stations), water flow devices, and visual/audible alarms.
The inspection covered a pull station at the north exit, a water flow switch (tested at 35 seconds), and multiple notification devices including a strobe zone circuit, a speaker/strobe unit (label #49798289), and a strobe unit (label #49798288) near Room 108. All devices passed their respective tests. The report references Joint Commission standard EC.02.03.05, which requires testing of duct detectors, heat detectors, and manual fire alarm boxes every 12 months, water flow devices every 6 months (mechanical devices quarterly), and visual/audible alarms every 12 months.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by ALARMSpecialists, Inc
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 3
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Pull Station NORTH EXIT BUILDING 35 N 6 L 2 M 2 Pass
EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
VA Hospital - WCHCS - Bldg 35 - Device List - March 23
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 3
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Water Flow Switch WATERFLOW BUILDING 35 N 6 L 2 M 4 Pass 35 SEC
VA WCHCS - Bldg 35 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note : Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 3
Date Tested Device Floor Room # / Corridor Location / Description No de Lo op Device Label Status Comments March 21, 2023 Strobe Zone CKT R-2 BLDG 35 IN FACP CAB Building 35 N 6 L 1 M 72 Pass March 21, 2023 Speaker/Strobe By Rm 108 Building 35 N 6 L 2 x x 49798289 Pass March 21, 2023 Strobe Rm 108 Building 35 N 6 L 2 x x 49798288 Pass
VA WCHCS - Bldg 35 - Audibles - Device List - March 23
EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.
File details come from the government source that posted it. Updated .