VA WCHCS Bldg 6 Oneline Report 23.pdf
PDF 56 KB Posted
- Attached to
- H263--Fire Protection Services Federal contract opportunity
- Solicitation number
- 36C25925Q0190
About this file
This is a fire protection device inspection report dated March 21, 2023, for Building 6 at the VA Hospital WCHCS, conducted by ALARMSpecialists, Inc. The report documents mandatory testing of fire safety devices as required by hospital standards EC.02.03.05.
The inspection covered multiple fire protection systems including: six pull stations located throughout the building (all passed), one smoke detector above the FACP (passed), one water flow switch (passed at 32 seconds), two tamper switches (passed at 3 turns and 1 turn respectively), and 17 strobe/speaker devices including four strobe circuits and various individual strobe and speaker/strobe units throughout the building's rooms and corridors (all passed inspection). All devices were tested on Node 10, Loop 1. The testing complies with requirements for 12-month testing of manual fire alarm boxes, smoke detectors, and visual/audible alarms, as well as 6-month testing of water flow devices and valve tamper switches.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by ALARMSpecialists, Inc
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 5
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Pull Station EAST EXIT BUILDING 6 N 10 L 1 M 12 Pass March 21, 2023 Pull Station CONFERENCE HALL EXIT BUILDING 6 N 10 L 1 M 10 Pass March 21, 2023 Pull Station CONFERENCE HALL EXIT BUILDING 6 N 10 L 1 M 11 Pass March 21, 2023 Pull Station BASEMENT STAIRWELL BUILDING 6 N 10 L 1 M 14 Pass March 21, 2023 Pull Station CONFERNCE RM SOUTH BUILDING 6 N 10 L 1 M 15 Pass March 21, 2023 Pull Station 1ST FLOOR STAIRWELL BUILDING 6 N 10 L 1 M 13 Pass
EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
VA Hospital - WCHCS - Bldg 6 - Device List - March 23
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 5
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Smoke Detector SMOKE ABOVE FACP BUILDING 6 N 10 L 1 D 1 Pass
VA Hospital - WCHCS - Bldg 6 - Device List - March 23 EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 5
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Water Flow Switch WATERFLOW BUILDING 6 N 10 L 1 M 1 Pass 32 SEC
VA - WCHCS - Bldg 6 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 4 of 5
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Tamper Switch POST INDICATOR VALVE BUILDING 6 N 10 L 1 M 2 Pass 3 TURNS March 21, 2023 Tamper Switch UPPER SPRINKLER TAMPER BLDG 6 N 10 L 1 M 4 Pass 1 TURN
VA - WCHCS - Bldg 6 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 5 of 5
Date Tested Device Floor Room # / Corridor Location / Description No de Lo op De vice Label Status Comments March 21, 2023 Strobe Zone STROBE CIRCUIT N-1 IN FACP CAB. Building 6 N 10 L 1 M 71 Pass March 21, 2023 Strobe Zone STROBE CIRCUIT N-2 IN FACP CAB. Building 6 N 10 L 1 M 72 Pass March 21, 2023 Strobe Zone STROBE CIRCUIT N-3 IN FACP CAB. Building 6 N 10 L 1 M 73 Pass March 21, 2023 Strobe Zone STROBE CIRCUIT N-4 IN FACP CAB. Building 6 N 10 L 1 M 74 Pass March 21, 2023 Speaker/Strobe By Rm 108 Stairwell Building 6 N 10 L 1 x x 49798218 Pass March 21, 2023 Speaker/Strobe Training Rm Building 6 N 10 L 1 x x 49798250 Pass March 21, 2023 Strobe Training Rm Building 6 N 10 L 1 x x 49798249 Pass March 21, 2023 Strobe Outside Building Building 6 N 10 L 1 x x 49799071 Pass March 21, 2023 Speaker/Strobe Rm 101A Building 6 N 10 L 1 x x 49799074 Pass March 21, 2023 Strobe Rm 102A Building 6 N 10 L 1 x x 49799072 Pass March 21, 2023 Speaker/Strobe By Rm 105 Building 6 N 10 L 1 x x 49798244 Pass March 21, 2023 Strobe By Rm 109 Building 6 N 10 L 1 x x 49798245 Pass March 21, 2023 Speaker/Strobe By Rm 112 Building 6 N 10 L 1 x x 49798247 Pass March 21, 2023 Strobe Rm 112 Building 6 N 10 L 1 x x 49799073 Pass March 21, 2023 Strobe Rm 120A Building 6 N 10 L 1 x x 49798246 Pass March 21, 2023 Speaker/Strobe By Rm 121A Building 6 N 10 L 1 x x 49798266 Pass March 21, 2023 Strobe By Rm 121A Building 6 N 10 L 1 x x 49798265 Pass
VA WCHCS - Bldg 6 - Audibles - Device List - March 23
EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.
File details come from the government source that posted it. Updated .