VA WCHCS Bldg 20 Oneline Report 23.pdf

PDF 79 KB Posted

Attached to
H263--Fire Protection Services Federal contract opportunity
Solicitation number
36C25925Q0190
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

This is a fire safety device inspection report prepared by ALARMSpecialists, Inc. documenting testing conducted on March 21, 2023 at VA WCHCS Building 20. The report details the inspection and testing of multiple fire safety systems including pull stations, smoke detectors, duct detectors, tamper switches, water flow switches, strobe/speaker devices, and door control/releasing devices throughout the facility.

The report indicates all devices passed inspection, with specific locations and device IDs documented for each component. Key details include testing of 4 pull stations, 13 smoke detectors, 4 duct detectors with shutdown verification, 3 tamper switches (requiring 1-4 turns), 1 water flow switch (24 second response), 19 strobe/speaker devices, and 27 door control/releasing devices. The testing was conducted in compliance with standard EC.02.03.05 which requires various fire safety devices to be tested either every 6 or 12 months, with all results and completion dates documented.

View the file

Other files for this federal contract opportunity

Other files attached to H263--Fire Protection Services, newest first.
File Type Posted
VA WCHCS Device List 23.pdf PDF
VA WCHCS Bldg 46 Oneline Report 23.pdf PDF
VA WCHCS Bldg 36 Oneline Report 23.pdf PDF
VA WCHCS Bldg 35 Oneline Report 23.pdf PDF
VA WCHCS Bldg 22 Oneline Report 23.pdf PDF
VA WCHCS Bldg 5 Oneline Report 23.pdf PDF
VA WCHCS Bldg 1 Oneline Report 23.pdf PDF
VA WCHCS Off-Premises Monitoring EP5 Report 23.pdf PDF
VA WCHCS Bldg 12 Oneline Report 23.pdf PDF
VA WCHCS Bldg 9 Oneline Report 23.pdf PDF
VA WCHCS Bldg 8 Oneline Report 23.pdf PDF
36C25925Q0190 0002_1.docx DOCX document
VA WCHCS Bldg 37 Oneline Report 23.pdf PDF
VA WCHCS Bldg 34 Oneline Report 23.pdf PDF
VA WCHCS Bldg 13 Oneline Report 23.pdf PDF
36C25925Q0190 0002.docx DOCX document
VA WCHCS Bldg 45 Oneline Report 23.pdf PDF
VA WCHCS Bldg 33 Oneline Report 23.pdf PDF
VA WCHCS Bldg 14 Oneline Report 23.pdf PDF
VA WCHCS Bldg 7 Oneline Report 23.pdf PDF
VA WCHCS Bldg 6 Oneline Report 23.pdf PDF
36C25925Q0190 0001_1.docx DOCX document
36C25925Q0190 0001.docx DOCX document
Table 1 Task list by TJC EPs and Frequency 112624.xlsx XLSX spreadsheet
36C25925Q0190_1.docx DOCX document
36C25925Q0190.docx DOCX document
Previous Solicitation Questions and Answers.docx DOCX document
Show all 27

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Prepared by ALARMSpecialists, Inc

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 7

Date Tested Device Location NodeLo op Device Status Comments March 21, 2023 Pull Station CLC MAIN ENTRY BLD 20 FLR 1 N 1 L 9 M 11 Pass

March 21, 2023 Pull Station BY CLC RAMP BLD 20 FLR 1 N 1 L 9 M 12 Pass

March 21, 2023 Pull Station EXIT BY ROOM 146 BLD 20 FLR 1 N 1 L 9 M 2 Pass

March 21, 2023 Pull Station EXIT BY ROOM 116 BLD 20 FLR 1 N 1 L 9 M 1 Pass

EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory.

The results and completion dates are documented.

VA WCHCS - Bldg 20 - Device List - March 23

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 7

Date Tested Device Location NodeLo op Device Status Comments March 21, 2023 Smoke Detector DINING HALL BLD 20 FLR 1 N 1 L 9 D 14 Pass

March 21, 2023 Smoke Detector DINING HALL BLD 20 FLR 1 N 1 L 9 D 15 Pass

March 21, 2023 Smoke Detector BY CLC RAMP BLD 20 FLR 1 N 1 L 9 D 16 Pass

March 21, 2023 Smoke Detector HALLWAY TO CLC BLD 20 FLR 1 N 1 L 9 D 17 Pass

March 21, 2023 Smoke Detector HALL BY ROOM 151 BLD 20 FLR 1 N 1 L 9 D 12 Pass

March 21, 2023 Smoke Detector HALL BY ROOM 116 BLD 20 FLR 1 N 1 L 9 D 1 Pass

March 21, 2023 Smoke Detector HALL BY ROOM 119 BLD 20 FLR 1 N 1 L 9 D 2 Pass

March 21, 2023 Smoke Detector HALL BY ROOM 109 BLD 20 FLR 1 N 1 L 9 D 3 Pass

March 21, 2023 Smoke Detector HALL BY ROOM 129 BLD 20 FLR 1 N 1 L 9 D 4 Pass

March 21, 2023 Smoke Detector HALL BY OFFICE 149 BLD 20 FLR 1 N 1 L 9 D 9 Pass

March 21, 2023 Smoke Detector HALL BY ROOM 137 BLD 20 FLR 1 N 1 L 9 D 7 Pass

March 21, 2023 Smoke Detector HALL BY ROOM 140 BLD 20 FLR 1 N 1 L 9 D 5 Pass

March 21, 2023 Smoke Detector BOTTOM OF RAMP CLC BLD 20 FLR 1 N 1 L 9 D 13 Pass

VA WCHCS - Bldg 20 - Device List - March 23 EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory.

The results and completion dates are documented.

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 7

Date Tested DEVICE LOCATION Node Lo op De vice SHUTDOWN STATUS COMMENTS March 21, 2023 Duct Detector AHU-20 SUPPLY BLDG 20 FLR 1 N 1 L 9 D 6 Yes Pass Change message March 21, 2023 Duct Detector AHU-20 RETURN BLDG 20 FLR 1 N 1 L 9 D 8 Yes Pass March 21, 2023 Duct Detector AHU-21 RETURN BLD 20 FLR 1 N 1 L 9 D 10 Yes Pass March 21, 2023 Duct Detector AHU-21 SUPPLY BLD 20 FLR 1 N 1 L 9 D 11 Yes Pass

EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

EC.02.03.05 EP 19 Every 12 months, the hospital tests automatic smoke-detection shutdown devices for air-handling equipment. The results and completion dates are documented.

VA - WCHCS - BLDG 20 - DUCT DETECTION - March 23

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 4 of 7

Date Tested DEVICE LOCATION STATUS COMMENTS Building 20 N 0 L 0 M 0

March 21, 2023 Tamper Switch SOUTH PIV BLDG 20 N 1 L 9 M 13 Pass 4 Turns March 21, 2023 Tamper Switch MECH RM TAMPER 1 BLD 20 FLR 1 N 1 L 9 M 4 Pass 3 Turns March 21, 2023 Tamper Switch MECH RM TAMPER 2 BLD 20 FLR 1 N 1 L 9 M 6 Pass 1 Turn

VA WCHCS - BLDG 20 - Sprinkler - March 23

EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Note 2: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 5 of 7

Date Tested DEVICE LOCATION STATUS COMMENTS Building 20 N 0 L 0 M 0

March 21, 2023 Water Flow Switch MECH RM WATERFLOW BLD 20 FLR 1 N 1 L 9 M 5 Pass 24 Sec

VA WCHCS - BLDG 20 - Sprinkler - March 23

EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 6 of 7

Date Tested Device Room # / Corridor Location / Description No de Lo op De vice Scan # Status Comments N 0 L 0 M 0

March 21, 2023 Strobe Zone A/V J-1 ELEC RM 133 Building 20 N 1 L 9 M 71 Pass March 21, 2023 Strobe Zone A/V J-2 ELEC RM 133 Building 20 N 1 L 9 M 72 Pass March 21, 2023 Strobe Zone A/V J-3 ELEC RM 133 Building 20 N 1 L 9 M 73 Pass March 21, 2023 Strobe Zone A/V J-4 ELEC RM 133 Building 20 N 1 L 9 M 74 Pass March 21, 2023 Speaker/Strobe Hallway From pharmacy Building 20 N 1 L 9 x x 49797546 Pass March 21, 2023 Strobe By Nurse Break Room Building 20 N 1 L 9 x x 49797570 Pass March 21, 2023 Speaker/Strobe Rm 100 Building 20 N 1 L 9 x x 49797542 Pass March 21, 2023 Speaker/Strobe By 100 Building 20 N 1 L 9 x x 49797543 Pass March 21, 2023 Speaker/Strobe By Rm 122 Building 20 N 1 L 9 x x 49797654 Pass March 21, 2023 Speaker/Strobe By Rm 122 Building 20 N 1 L 9 x x 49797672 Pass March 21, 2023 Speaker/Strobe By Rm 127 Building 20 N 1 L 9 x x 49797673 Pass March 21, 2023 Strobe Rm 130 Building 20 N 1 L 9 x x 49797677 Pass March 21, 2023 Strobe In room 131 Building 20 N 1 L 9 x x 49797706 Pass March 21, 2023 Speaker/Strobe By Rm 132 Building 20 N 1 L 9 x x 49797540 Pass March 21, 2023 Speaker/Strobe By Rm 135 Building 20 N 1 L 9 x x 49797571 Pass March 21, 2023 Speaker/Strobe By Rm 140 Building 20 N 1 L 9 x x 49797587 Pass March 21, 2023 Strobe Rm 148 Building 20 N 1 L 9 x x 49797534 Pass March 21, 2023 Speaker/Strobe By 153 Building 20 N 1 L 9 x x 49797545 Pass March 21, 2023 Strobe Rm 153 Building 20 N 1 L 9 x x 49797544 Pass

VA WCHCS - BLDG 20 - Audibles - Device List - March 23

EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 7 of 7

Date Tested Device Room # / Corridor Location / Description No de Lo op De vice Scan # Status Comments N 0 L 0 M 0

March 21, 2023 Door Control Relay FCPS DOOR MAG RELAY

ELEC RM 134 Building 20 N 1 L 9 M 71 Pass

March 21, 2023 Door Control Relay ACCESS CONTROL BLDG 20

Building 20 N 1 L 9 M 72 Pass

March 21, 2023 Releasing Device in hallway to bldg 20 Building 20 N 1 L 9 M 73 49797568 Pass March 21, 2023 Releasing Device in hallway to bldg 20 Building 20 N 1 L 9 M 74 49797569 Pass March 21, 2023 Releasing Device in room 106 Building 20 N 1 L 9 x x 49797705 Pass March 21, 2023 Releasing Device in room 109 Building 20 N 1 L 9 x x 49797704 Pass March 21, 2023 Releasing Device in room 110 Building 20 N 1 L 9 x x 49797703 Pass March 21, 2023 Releasing Device Rm 111 Building 20 N 1 L 9 x x 49797653 Pass March 21, 2023 Releasing Device Rm 113 Building 20 N 1 L 9 x x 49797665 Pass March 21, 2023 Releasing Device Rm 115 Building 20 N 1 L 9 x x 49797655 Pass March 21, 2023 Releasing Device Rm 116 Building 20 N 1 L 9 x x 49797656 Pass March 21, 2023 Releasing Device Rm 118 Building 20 N 1 L 9 x x 49797666 Pass March 21, 2023 Releasing Device Rm 119 Building 20 N 1 L 9 x x 49797667 Pass March 21, 2023 Releasing Device Rm 121 Building 20 N 1 L 9 x x 49797668 Pass March 21, 2023 Releasing Device Rm 122 Building 20 N 1 L 9 x x 49797669 Pass March 21, 2023 Releasing Device Rm 125 Building 20 N 1 L 9 x x 49797670 Pass March 21, 2023 Releasing Device Rm 126 Building 20 N 1 L 9 x x 49797671 Pass March 21, 2023 Releasing Device Rm 129 Building 20 N 1 L 9 x x 49797674 Pass March 21, 2023 Releasing Device By Rm 130 Building 20 N 1 L 9 x x 49797675 Pass March 21, 2023 Releasing Device By Rm 130 Building 20 N 1 L 9 x x 49797676 Pass March 21, 2023 Releasing Device in room 133 Building 20 N 1 L 9 x x 49797664 Pass March 21, 2023 Releasing Device in room 138 Building 20 N 1 L 9 x x 49797661 Pass March 21, 2023 Releasing Device Rm 140 Building 20 N 1 L 9 x x 49797576 Pass March 21, 2023 Releasing Device Rm 141 Building 20 N 1 L 9 x x 49797572 Pass March 21, 2023 Releasing Device Rm 142 Building 20 N 1 L 9 x x 49797573 Pass March 21, 2023 Releasing Device Rm 143 Building 20 N 1 L 9 x x 49797574 Pass March 21, 2023 Releasing Device Rm 144 Building 20 N 1 L 9 x x 49797575 Pass

VA WCHCS - BLDG 20 - Door Control - Device List - March 23

EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.

File details come from the government source that posted it. Updated .