VA WCHCS Bldg 33 Oneline Report 23.pdf
PDF 53 KB Posted
- Attached to
- H263--Fire Protection Services Federal contract opportunity
- Solicitation number
- 36C25925Q0190
About this file
This is a fire protection systems testing report conducted by ALARMSpecialists, Inc. at VA Hospital WCHCS Building 33 on March 21, 2023, documenting required periodic testing of fire safety devices per EC.02.03.05 standards.
The report details testing results for multiple fire protection system components: 2 pull stations, 5 smoke detectors, 3 tamper switches (tested at 1-4 turns), 1 water flow switch (tested at 25 seconds), 4 strobe zones, and 1 speaker zone. All devices were located in Building 33 across various rooms (100-103) and areas. Every tested device passed inspection, with all components being on Node 7, Loop 1. The testing complied with requirements for 12-month testing of detectors and manual fire alarm boxes, 6-month testing of water flow devices and valve tamper switches, and 12-month testing of visual/audible alarms.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by ALARMSpecialists, Inc
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 5
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Pull Station IT BUILDING EXIT BUILDING 33 N 7 L 1 M 3 Pass March 21, 2023 Pull Station FACP IN ROOM 100 BUILDING 33 N 7 L 1 M 5 Pass
EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
VA Hospital - WCHCS - Bldg 33 - Device List - March 23
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 5
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Smoke Detector ROOM 100 BUILDING 33 N 7 L 1 D 1 Pass March 21, 2023 Smoke Detector ROOM 101 BUILDING 33 N 7 L 1 D 3 Pass March 21, 2023 Smoke Detector FACP IN ROOM 100 BUILDING 33 N 7 L 1 D 4 Pass March 21, 2023 Smoke Detector ROOM 102 BUILDING 33 N 7 L 1 D 2 Pass March 21, 2023 Smoke Detector RISER ROOM 103 BUILDING 33 N 7 L 1 D 5 Pass
VA Hospital - WCHCS - Bldg 33 - Device List - March 23 EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 5
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Tamper Switch TAMPER CONTROL VALVE BUILDING 33 N 7 L 1 M 2 Pass 4 TURNS March 21, 2023 Tamper Switch UPPER TAMPER BLDG 33 N 7 L 1 M 10 Pass 1 TURN March 21, 2023 Tamper Switch LOWER TAMPER BLDG 33 N 7 L 1 M 12 Pass 1 TURN
VA WCHCS - Bldg 33 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 4 of 5
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Water Flow Switch WATERFLOW BUILDING 33 N 7 L 1 M 1 Pass 25 SEC
VA WCHCS - Bldg 33 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note 2: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 5 of 5
Date Tested Device Floor Room # / Corridor Location / Description No de Lo op De vice Label Status Comments March 21, 2023 Strobe Zone STROBE CKT Q-1 IN FACP CAB Building 33 N 7 L 1 M 71 Pass March 21, 2023 Strobe Zone STROBE CKT Q-2 IN FACP CAB Building 33 N 7 L 1 M 72 Pass March 21, 2023 Strobe Zone STROBE CKT Q-3 IN FACP CAB Building 33 N 7 L 1 M 73 Pass March 21, 2023 Strobe Zone STROBE CKT Q-4 IN FACP CAB Building 33 N 7 L 1 M 74 Pass March 21, 2023 Speaker Zone BLDG 33 SPEAKERS IN FACP CAB Building 33 N 7 L 1 M 95 Pass
VA WCHCS - Bldg 33 - Audibles - Device List - March 23
EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.
File details come from the government source that posted it. Updated .