VA WCHCS Bldg 33 Oneline Report 23.pdf

PDF 53 KB Posted

Attached to
H263--Fire Protection Services Federal contract opportunity
Solicitation number
36C25925Q0190
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

This is a fire protection systems testing report conducted by ALARMSpecialists, Inc. at VA Hospital WCHCS Building 33 on March 21, 2023, documenting required periodic testing of fire safety devices per EC.02.03.05 standards.

The report details testing results for multiple fire protection system components: 2 pull stations, 5 smoke detectors, 3 tamper switches (tested at 1-4 turns), 1 water flow switch (tested at 25 seconds), 4 strobe zones, and 1 speaker zone. All devices were located in Building 33 across various rooms (100-103) and areas. Every tested device passed inspection, with all components being on Node 7, Loop 1. The testing complied with requirements for 12-month testing of detectors and manual fire alarm boxes, 6-month testing of water flow devices and valve tamper switches, and 12-month testing of visual/audible alarms.

View the file

Other files for this federal contract opportunity

Other files attached to H263--Fire Protection Services, newest first.
File Type Posted
VA WCHCS Off-Premises Monitoring EP5 Report 23.pdf PDF
VA WCHCS Bldg 12 Oneline Report 23.pdf PDF
VA WCHCS Bldg 9 Oneline Report 23.pdf PDF
VA WCHCS Bldg 8 Oneline Report 23.pdf PDF
36C25925Q0190 0002_1.docx DOCX document
VA WCHCS Bldg 45 Oneline Report 23.pdf PDF
VA WCHCS Bldg 20 Oneline Report 23.pdf PDF
VA WCHCS Bldg 14 Oneline Report 23.pdf PDF
VA WCHCS Bldg 7 Oneline Report 23.pdf PDF
VA WCHCS Bldg 6 Oneline Report 23.pdf PDF
VA WCHCS Device List 23.pdf PDF
VA WCHCS Bldg 46 Oneline Report 23.pdf PDF
VA WCHCS Bldg 36 Oneline Report 23.pdf PDF
VA WCHCS Bldg 35 Oneline Report 23.pdf PDF
VA WCHCS Bldg 22 Oneline Report 23.pdf PDF
VA WCHCS Bldg 5 Oneline Report 23.pdf PDF
VA WCHCS Bldg 1 Oneline Report 23.pdf PDF
VA WCHCS Bldg 37 Oneline Report 23.pdf PDF
VA WCHCS Bldg 34 Oneline Report 23.pdf PDF
VA WCHCS Bldg 13 Oneline Report 23.pdf PDF
36C25925Q0190 0002.docx DOCX document
36C25925Q0190 0001_1.docx DOCX document
36C25925Q0190 0001.docx DOCX document
Table 1 Task list by TJC EPs and Frequency 112624.xlsx XLSX spreadsheet
Previous Solicitation Questions and Answers.docx DOCX document
36C25925Q0190_1.docx DOCX document
36C25925Q0190.docx DOCX document
Show all 27

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Prepared by ALARMSpecialists, Inc

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 5

Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Pull Station IT BUILDING EXIT BUILDING 33 N 7 L 1 M 3 Pass March 21, 2023 Pull Station FACP IN ROOM 100 BUILDING 33 N 7 L 1 M 5 Pass

EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

VA Hospital - WCHCS - Bldg 33 - Device List - March 23

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 5

Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Smoke Detector ROOM 100 BUILDING 33 N 7 L 1 D 1 Pass March 21, 2023 Smoke Detector ROOM 101 BUILDING 33 N 7 L 1 D 3 Pass March 21, 2023 Smoke Detector FACP IN ROOM 100 BUILDING 33 N 7 L 1 D 4 Pass March 21, 2023 Smoke Detector ROOM 102 BUILDING 33 N 7 L 1 D 2 Pass March 21, 2023 Smoke Detector RISER ROOM 103 BUILDING 33 N 7 L 1 D 5 Pass

VA Hospital - WCHCS - Bldg 33 - Device List - March 23 EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 5

Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Tamper Switch TAMPER CONTROL VALVE BUILDING 33 N 7 L 1 M 2 Pass 4 TURNS March 21, 2023 Tamper Switch UPPER TAMPER BLDG 33 N 7 L 1 M 10 Pass 1 TURN March 21, 2023 Tamper Switch LOWER TAMPER BLDG 33 N 7 L 1 M 12 Pass 1 TURN

VA WCHCS - Bldg 33 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 4 of 5

Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Water Flow Switch WATERFLOW BUILDING 33 N 7 L 1 M 1 Pass 25 SEC

VA WCHCS - Bldg 33 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Note 2: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 5 of 5

Date Tested Device Floor Room # / Corridor Location / Description No de Lo op De vice Label Status Comments March 21, 2023 Strobe Zone STROBE CKT Q-1 IN FACP CAB Building 33 N 7 L 1 M 71 Pass March 21, 2023 Strobe Zone STROBE CKT Q-2 IN FACP CAB Building 33 N 7 L 1 M 72 Pass March 21, 2023 Strobe Zone STROBE CKT Q-3 IN FACP CAB Building 33 N 7 L 1 M 73 Pass March 21, 2023 Strobe Zone STROBE CKT Q-4 IN FACP CAB Building 33 N 7 L 1 M 74 Pass March 21, 2023 Speaker Zone BLDG 33 SPEAKERS IN FACP CAB Building 33 N 7 L 1 M 95 Pass

VA WCHCS - Bldg 33 - Audibles - Device List - March 23

EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.