This is a fire alarm and sprinkler system test report for Building 36 at the VA WCHCS (Veterans Affairs Western Colorado Health Care System) conducted by ALARMSpecialists, Inc. on March 21, 2023.
The report documents the testing of multiple fire safety devices throughout Building 36, including: three pull stations at building exits (South, West, and East), one smoke detector above the FACP, three tamper switches (one post indicator valve and two control valves), one water flow switch (tested at 28 seconds), and ten visual/audible notification devices (strobe zones, strobes, and speaker/strobes) in various rooms and corridors. All devices were tested as part of required periodic inspections - pull stations, smoke detectors, and audible/visual devices tested annually; water flow devices and tamper switches tested semi-annually. Every device tested received a "Pass" status with no failures noted.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by ALARMSpecialists, Inc
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 5
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Pull Station SOUTH EXIT BUILDING 36 N 6 L 1 M 1 Pass March 21, 2023 Pull Station WEST EXIT BUILDING 36 N 6 L 1 M 2 Pass March 21, 2023 Pull Station EAST EXIT BUILDING 36 N 6 L 1 M 5 Pass
EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
VA Hospital - WCHCS - Bldg 36 - Device List - March 23
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 5
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Smoke Detector SMOKE ABOVE FACP BUILDING 36 N 6 L 1 D 1 Pass
VA Hospital - WCHCS - Bldg 36 - Device List - March 23 EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 5
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Tamper Switch POST INDICATOR VALVE BUILDING 36 N 6 L 1 M 6 Pass 3 TURNS March 21, 2023 Tamper Switch TAMPER CONTROL VALVE BUILDING 36 N 6 L 1 M 4 Pass 1 TURN March 21, 2023 Tamper Switch TAMPER CONTROL VALVE BUILDING 36 N 6 L 1 M 7 Pass 1 TURN
VA WCHCS - Bldg 36 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note 2: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 4 of 5
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Water Flow Switch WATERFLOW BUILDING 36 N 6 L 1 M 3 Pass 28 SEC
VA WCHCS - Bldg 36 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 5 of 5
Date Tested Device Floor Room # / Corridor Location / Description No de Lo op Device Label Status Comments March 21, 2023 Strobe Zone CKT R-3 BLDG 36 IN FACP CAB Building 36 N 6 L 1 M 73 Pass March 21, 2023 Strobe Zone CKT R-4 BLDG 36 IN FACP CAB Building 36 N 6 L 1 M 74 Pass March 21, 2023 Strobe Rm 110 Building 36 N 6 L 1 x x 49798278 Pass March 21, 2023 Strobe Rm 111 Building 36 N 6 L 1 x x 49798277 Pass March 21, 2023 Strobe Rm 120 Building 36 N 6 L 1 x x 49798284 Pass March 21, 2023 Strobe Rm 121 Building 36 N 6 L 1 x x 49798285 Pass March 21, 2023 Speaker/Strobe Above 128 Building 36 N 6 L 1 x x 49798286 Pass March 21, 2023 Speaker/Strobe Above 133 Building 36 N 6 L 1 x x 49798283 Pass March 21, 2023 Speaker/Strobe Above 151 Building 36 N 6 L 1 x x 49798280 Pass March 21, 2023 Speaker/Strobe Above 155 Building 36 N 6 L 1 x x 49798281 Pass
VA WCHCS - Bldg 36 - Audibles - Device List - March 23
EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.