VA WCHCS Bldg 37 Oneline Report 23.pdf

PDF 57 KB Posted

Attached to
H263--Fire Protection Services Federal contract opportunity
Solicitation number
36C25925Q0190
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

This is a building testing and inspection report dated March 22, 2023, documenting the testing of fire protection and life safety systems in Building 37 of the VA WCHCS (Veterans Affairs Western Colorado Health Care System) facility.

The report details testing results for multiple systems including: pull stations at various building exits, tamper switches for sprinkler control valves (requiring 1-3 turns), a dry system waterflow device, supervisory pressure devices for the dry pipe system, and visual/audible notification devices including strobe zones and speaker/strobes throughout the facility. All tested devices passed inspection, with specific locations noted including the Wellness Center, Winter Sports Clinic, and Recreational Service areas. The testing was performed by ALARMSpecialists, Inc. of Centennial, CO and follows various EC.02.03.05 testing requirements for hospitals, including quarterly, semi-annual and annual testing intervals depending on device type. One action item noted was to relocate an ICON to room B106 Onyx.

View the file

Other files for this federal contract opportunity

Other files attached to H263--Fire Protection Services, newest first.
File Type Posted
VA WCHCS Bldg 45 Oneline Report 23.pdf PDF
VA WCHCS Bldg 33 Oneline Report 23.pdf PDF
VA WCHCS Bldg 20 Oneline Report 23.pdf PDF
VA WCHCS Bldg 14 Oneline Report 23.pdf PDF
VA WCHCS Bldg 7 Oneline Report 23.pdf PDF
VA WCHCS Bldg 6 Oneline Report 23.pdf PDF
VA WCHCS Bldg 34 Oneline Report 23.pdf PDF
VA WCHCS Bldg 13 Oneline Report 23.pdf PDF
36C25925Q0190 0002.docx DOCX document
VA WCHCS Off-Premises Monitoring EP5 Report 23.pdf PDF
VA WCHCS Bldg 12 Oneline Report 23.pdf PDF
VA WCHCS Bldg 9 Oneline Report 23.pdf PDF
VA WCHCS Bldg 8 Oneline Report 23.pdf PDF
36C25925Q0190 0002_1.docx DOCX document
VA WCHCS Device List 23.pdf PDF
VA WCHCS Bldg 46 Oneline Report 23.pdf PDF
VA WCHCS Bldg 36 Oneline Report 23.pdf PDF
VA WCHCS Bldg 35 Oneline Report 23.pdf PDF
VA WCHCS Bldg 22 Oneline Report 23.pdf PDF
VA WCHCS Bldg 5 Oneline Report 23.pdf PDF
VA WCHCS Bldg 1 Oneline Report 23.pdf PDF
36C25925Q0190 0001_1.docx DOCX document
36C25925Q0190 0001.docx DOCX document
Previous Solicitation Questions and Answers.docx DOCX document
36C25925Q0190_1.docx DOCX document
36C25925Q0190.docx DOCX document
Table 1 Task list by TJC EPs and Frequency 112624.xlsx XLSX spreadsheet
Show all 27

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Prepared by ALARMSpecialists, Inc

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 6

Date Tested Device Location No de Lo op Device Status Comments March 22, 2023 Pull Station B104 SOUTHEAST EXIT BUILDING 37 N 10 L 2 M 1 Pass March 22, 2023 Pull Station B104 WEST EXIT BUILDING 37 N 10 L 2 M 2 Pass March 22, 2023 Pull Station A108 EAST EXIT BUILDING 37 N 10 L 2 M 6 Pass March 22, 2023 Pull Station A100 WEST EXIT BUILDING 37 N 10 L 2 M 7 Pass March 22, 2023 Pull Station Wellness Center Hallway By Exit N 10 L 2 M 12 Pass

EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

VA Hospital - WCHCS - Bldg 37 - Device List - March 23

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 6

Date Tested Device Location No de Lo op Device Status Comments March 22, 2023 March 22, 2023 BY FIRE POWER SUPPLY BLDG 37 N 10 L 2 D 1 Pass Relocate ICON to B106 Onyx

VA Hospital - WCHCS - Bldg 37 - Device List - March 23 EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 6

Date Tested DEVICE LOCATION STATUS COMMENTS March 22, 2023 Tamper Switch TAMPER CONTROL #1 BUILDING 37 N 10 L 2 M 4 Pass 1 TURN March 22, 2023 Tamper Switch TAMPER CONTROL #2 BUILDING 37 N 10 L 2 M 5 Pass 2 TURNS March 22, 2023 Tamper Switch DRY SYSTEM TAMPER BLDG 37 N 10 L 2 M 8 Pass 2 TURNS March 22, 2023 Tamper Switch BUILDING 37 PIV BUILDING 37 N 10 L 2 M 11 Pass 3 TURNS

VA WCHCS - Bldg 37 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Note 2: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 4 of 6

Date Tested DEVICE LOCATION STATUS COMMENTS March 22, 2023 Dry System MAIN WATERFLOW DRY SYSTEM BUILDING 37 N 10 2 M 10 Pass

VA WCHCS - Bldg 37 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 5 of 6

Date Tested DEVICE LOCATION No de Lo op De viceSTATUS COMMENTS March 22, 2023 Dry System DRY SYST LOW AIR BUILDING 37 N 10 L 2 M 3 Pass

VA WCHCS - Bldg 37 - Supervisory List (Pressure Devices) - March 23 EC.02.03.05 EP 1 At least quarterly, the hospital tests supervisory signal devices on the inventory (except valve tamper switches). The results and completion dates are documented.

Note 1: Supervisory signals include the following: control valves; pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure; water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory.

6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 6 of 6

Date Tested Device Floor Room # / Corridor Location / Description No de Lo op De vice Label Status Comments March 22, 2023 Strobe Zone STROBE CIRCUIT S-1 IN ROOM B103 Building 37 N 10 L 2 M 71 Pass March 22, 2023 Strobe Zone STROBE CIRCUIT S-2 IN ROOM B103 Building 37 N 10 L 2 M 72 Pass March 22, 2023 Strobe Zone STROBE CIRCUIT S-3 IN ROOM B103 Building 37 N 10 L 2 M 73 Pass March 22, 2023 Strobe Zone STROBE CIRCUIT S-4 IN ROOM B103 Building 37 N 10 L 2 M 74 Pass March 22, 2023 Speaker/Strobe Wellness Center Building 37 N 10 L 2 x x 49799124 Pass March 22, 2023 Speaker/Strobe Winter Sports Clinic Building 37 N 10 L 2 x x 49799128 Pass March 22, 2023 Speaker/Strobe Recreational Service Building 37 N 10 L 2 x x 49799130 Pass March 22, 2023 Speaker/Strobe Wellness Center Work Area Building 37 N 10 L 2 x x 49799131 Pass March 22, 2023 Strobe Wellness Center Restroom Building 37 N 10 L 2 x x 49799123 Pass March 22, 2023 Strobe Recreational Service Restroom Building 37 N 10 L 2 x x 49799126 Pass

VA WCHCS - Bldg 37 - Audibles - Device List - March 23

EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.

File details come from the government source that posted it. Updated .