This is a building testing and inspection report dated March 22, 2023, documenting the testing of fire protection and life safety systems in Building 37 of the VA WCHCS (Veterans Affairs Western Colorado Health Care System) facility.
The report details testing results for multiple systems including: pull stations at various building exits, tamper switches for sprinkler control valves (requiring 1-3 turns), a dry system waterflow device, supervisory pressure devices for the dry pipe system, and visual/audible notification devices including strobe zones and speaker/strobes throughout the facility. All tested devices passed inspection, with specific locations noted including the Wellness Center, Winter Sports Clinic, and Recreational Service areas. The testing was performed by ALARMSpecialists, Inc. of Centennial, CO and follows various EC.02.03.05 testing requirements for hospitals, including quarterly, semi-annual and annual testing intervals depending on device type. One action item noted was to relocate an ICON to room B106 Onyx.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by ALARMSpecialists, Inc
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 6
Date Tested Device Location No de Lo op Device Status Comments March 22, 2023 Pull Station B104 SOUTHEAST EXIT BUILDING 37 N 10 L 2 M 1 Pass March 22, 2023 Pull Station B104 WEST EXIT BUILDING 37 N 10 L 2 M 2 Pass March 22, 2023 Pull Station A108 EAST EXIT BUILDING 37 N 10 L 2 M 6 Pass March 22, 2023 Pull Station A100 WEST EXIT BUILDING 37 N 10 L 2 M 7 Pass March 22, 2023 Pull Station Wellness Center Hallway By Exit N 10 L 2 M 12 Pass
EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
VA Hospital - WCHCS - Bldg 37 - Device List - March 23
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 6
Date Tested Device Location No de Lo op Device Status Comments March 22, 2023 March 22, 2023 BY FIRE POWER SUPPLY BLDG 37 N 10 L 2 D 1 Pass Relocate ICON to B106 Onyx
VA Hospital - WCHCS - Bldg 37 - Device List - March 23 EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 6
Date Tested DEVICE LOCATION STATUS COMMENTS March 22, 2023 Tamper Switch TAMPER CONTROL #1 BUILDING 37 N 10 L 2 M 4 Pass 1 TURN March 22, 2023 Tamper Switch TAMPER CONTROL #2 BUILDING 37 N 10 L 2 M 5 Pass 2 TURNS March 22, 2023 Tamper Switch DRY SYSTEM TAMPER BLDG 37 N 10 L 2 M 8 Pass 2 TURNS March 22, 2023 Tamper Switch BUILDING 37 PIV BUILDING 37 N 10 L 2 M 11 Pass 3 TURNS
VA WCHCS - Bldg 37 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note 2: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 4 of 6
Date Tested DEVICE LOCATION STATUS COMMENTS March 22, 2023 Dry System MAIN WATERFLOW DRY SYSTEM BUILDING 37 N 10 2 M 10 Pass
VA WCHCS - Bldg 37 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 5 of 6
Date Tested DEVICE LOCATION No de Lo op De viceSTATUS COMMENTS March 22, 2023 Dry System DRY SYST LOW AIR BUILDING 37 N 10 L 2 M 3 Pass
VA WCHCS - Bldg 37 - Supervisory List (Pressure Devices) - March 23 EC.02.03.05 EP 1 At least quarterly, the hospital tests supervisory signal devices on the inventory (except valve tamper switches). The results and completion dates are documented.
Note 1: Supervisory signals include the following: control valves; pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure; water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 6 of 6
Date Tested Device Floor Room # / Corridor Location / Description No de Lo op De vice Label Status Comments March 22, 2023 Strobe Zone STROBE CIRCUIT S-1 IN ROOM B103 Building 37 N 10 L 2 M 71 Pass March 22, 2023 Strobe Zone STROBE CIRCUIT S-2 IN ROOM B103 Building 37 N 10 L 2 M 72 Pass March 22, 2023 Strobe Zone STROBE CIRCUIT S-3 IN ROOM B103 Building 37 N 10 L 2 M 73 Pass March 22, 2023 Strobe Zone STROBE CIRCUIT S-4 IN ROOM B103 Building 37 N 10 L 2 M 74 Pass March 22, 2023 Speaker/Strobe Wellness Center Building 37 N 10 L 2 x x 49799124 Pass March 22, 2023 Speaker/Strobe Winter Sports Clinic Building 37 N 10 L 2 x x 49799128 Pass March 22, 2023 Speaker/Strobe Recreational Service Building 37 N 10 L 2 x x 49799130 Pass March 22, 2023 Speaker/Strobe Wellness Center Work Area Building 37 N 10 L 2 x x 49799131 Pass March 22, 2023 Strobe Wellness Center Restroom Building 37 N 10 L 2 x x 49799123 Pass March 22, 2023 Strobe Recreational Service Restroom Building 37 N 10 L 2 x x 49799126 Pass
VA WCHCS - Bldg 37 - Audibles - Device List - March 23
EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.