VA WCHCS Bldg 22 Oneline Report 23.pdf
PDF 48 KB Posted
- Attached to
- H263--Fire Protection Services Federal contract opportunity
- Solicitation number
- 36C25925Q0190
About this file
This is a March 2023 fire safety device testing report prepared by ALARMSpecialists, Inc. for Building 22 at the VA WCHCS (Veterans Affairs Western Colorado Health Care System) facility. The report documents required testing of fire safety devices in accordance with hospital standards EC.02.03.05.
The testing, conducted on March 21, 2023, covered multiple device types: pull stations in the warehouse area and pharmacy cache, smoke detectors in the same locations, a water flow switch (tested at 8 seconds), and audible/visual notification devices including a strobe zone in the chiller room and a speaker/strobe at the main entrance. All tested devices passed inspection. The testing documentation complies with requirements for 12-month testing of manual fire alarm boxes, smoke detectors, and visual/audible alarms, as well as 6-month testing for water flow devices and valve tamper switches. Each device is identified with specific location codes and device numbers (e.g., N3 L4 M1) for tracking purposes.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by ALARMSpecialists, Inc
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 4
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Pull Station WAREHOUSE AREA BUILDING 22 N 3 L 4 M 1 Pass March 21, 2023 Pull Station PHARMACY CACHE BUILDING 22 N 3 L 4 M 2 Pass
EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
VA Hospital - WCHCS - Bldg 22 - Device List - March 23
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 4
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Smoke Detector WAREHOUSE AREA BUILDING 22 N 3 L 4 D 1 Pass March 21, 2023 Smoke Detector PHARMACY CACHE BUILDING 22 N 3 L 4 D 2 Pass
VA Hospital - WCHCS - Bldg 22 - Device List - March 23 EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 4
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Water Flow Switch WATERFLOW BUILDING 22 N 3 L 4 M 3 Pass 8 SEC
VA WCHCS - Bldg 22 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note 2: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 4 of 4
Date Tested Device Floor Room # / Corridor Location / Description No de Lo op Device Label Status Comments March 21, 2023 Strobe Zone BLDG 22 STROBES CHILLER ROOM Building 22 N 3 L 1 M 84 Pass March 21, 2023 Speaker/Strobe Main Entrance Building 22 N 3 L 4 x x 49798252 Pass
VA WCHCS - Bldg 22 - Audibles - Device List - March 23
EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.
File details come from the government source that posted it. Updated .