07 22 00 - ROOF AND DECK INSULATION.pdf
PDF 47 KB Posted
- Solicitation number
- 36C25026B0011
About this file
This is Section 07 22 00 (Roof and Deck Insulation) of the specifications for a roof replacement project at Columbus VAMC Building 1A, issued as Addendum #01 on April 27, 2026, under contract #757-21-101.
The section specifies requirements for roof and deck insulation, vapor retarders, and cover boards on both existing concrete and metal deck substrates. The insulation thermal performance requirement is RSI-57 (R-33) minimum for new systems, with rehabilitation areas matching existing conditions. Polyisocyanurate board insulation per ASTM C1289 (Type II, Class 1, Grade 2) with glass fiber reinforced cellulosic felt facers is required, with rigid foam containing minimum 9 percent recycled content. The vapor retarder system consists of ASTM D 6163 Grade S, Type III glass-fiber-reinforced, SBS-modified asphalt sheet applied with cold-applied adhesive containing 24% bio-based content and ultra-low VOC formulation. Cover board shall be glass-mat, water-resistant gypsum roof board per ASTM C1177/C1177M at 6 mm thick, factory primed. Insulation surface burning characteristics must comply with ASTM E84, with flame spread rating of 75 maximum and smoke developed rating of 150 maximum. Installation requires adhered insulation using bead-applied or full-spread urethane adhesives with staggered joints minimum 150 mm between layers, cant strips at vertical junctures, and cover boards offset minimum 150 mm from insulation joints. All products must comply with sustainable construction requirements including VOC limits per Section 01 81 13 and support for bio-based and recycled content materials. The installer must be the same as the Division 07 roofing section installer, and all work must comply with NRCA Manual-15 recommendations.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum #01 April 27, 2026 Columbus VAMC – Replace Roof Building 1A
#757-21-101
01-01-21
ROOF AND DECK INSULATION
07 22 00 - 1
SECTION 07 22 00
ROOF AND DECK INSULATION
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
B. Roof and deck insulation, vapor retarder, and cover board on both existing concrete and metal deck substrates ready to receive roofing or membrane.
C. Repairs and alteration work to existing roof insulation.
1.2 RELATED WORK
A. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS: Non-Flooring
Adhesives and Sealants VOC Limits.
B. Section 06 10 00, ROUGH CARPENTRY: Wood Cants, Blocking, and Edge
Strips.
C. Section 07 01 50.74 REHABILITATION OF EXISTING MEMBRANE ROOFING:
membrane rehabilitation system.
D. Section 07 52 16.11 COLD ADHESIVE STYRENE-BUTADIENE-STYRENE MODIFIED
BITUMINOUS MEMBRANE ROOFING Membrane base flashings and stripping.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. American Society of Civil Engineers
ASCE 7-16...............Minimum Design Loads and Associated Criteria for Buildings and Other Structures
C. American Society of Heating, Refrigeration and Air Conditioning
(ASHRAE):
Standard 90.1-13........Energy Standard for Buildings Except Low-Rise
Residential Buildings.
D. ASTM International (ASTM):
C208-12(2017)e2.........Cellulosic Fiber Insulating Board.
C1177/C1177M-17.........Glass Mat Gypsum Substrate for Use as
Sheathing.
C1278/C1278M-17.........Fiber-Reinforced Gypsum Panel.
C1289-19................Faced Rigid Cellular Polyisocyanurate Thermal
Insulation Board.
C1396/C1396M-17.........Gypsum Board.
E84-20..................Surface Burning Characteristics of Building
Materials.
F1667-18a...............Driven Fasteners: Nails, Spikes, and Staples.
01-01-21
ROOF AND DECK INSULATION
07 22 00 - 2
E. National Roofing Contractors Association (NRCA):
Manual-15...............The NRCA Roofing Manual: Membrane Roof Systems-
2019.
F. UL LLC (UL):
Listed Online Certifications Directory.
G. U.S. Department of Agriculture (USDA):
USDA BioPreferred Program Catalog.
H. U.S. Department of Commerce National Institute of Standards and
Technology (NIST):
DOC PS 1-19.............Structural Plywood.
DOC PS 2-18.............Performance Standard for Wood-Based
Structural-Use Panels.
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and installation details.
a. Nailers, cants, and terminations.
b. Layout of insulation showing slopes, tapers, penetrations, and edge conditions.
C. Manufacturer's Literature and Data:
1. Description of each product.
D. Samples:
1. Roof insulation, each type.
2. Fasteners, each type.
E. Sustainable Construction Submittals:
1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.
2. Biobased Content:
a. Show type and quantity for each product.
3. Low Pollutant-Emitting Materials:
a. Show volatile organic compound types and quantities.
b. Certify each product contain no added urea formaldehyde.
F. Qualifications: Substantiate qualifications meet specifications.
1. Installer.
1.5 QUALITY ASSURANCE
A. Installer Qualifications: Same installer as Division 07 roofing section installer.
01-01-21
ROOF AND DECK INSULATION
07 22 00 - 3
1.6 DELIVERY
A. Comply with recommendations of NRCA Manual.
B. Deliver products in manufacturer's original sealed packaging.
C. Mark packaging, legibly. Indicate manufacturer's name or brand, type, and manufacture date.
D. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.7 STORAGE AND HANDLING
A. Comply with recommendations of NRCA Manual.
B. Store products indoors in dry, weathertight facility.
C. Protect products from damage during handling and construction operations.
1.8 FIELD CONDITIONS
A. Environment: Install products when existing and forecasted weather permit installation according to manufacturer's instructions.
1.9 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
B. Manufacturer's Warranty: Warrant substrate board, vapor retarder, insulation, and cover board against material and manufacturing defects as part of Division 07 roofing system warranty.
PART 2 - PRODUCTS
2.1 SYSTEM PERFORMANCE
A. Insulation Thermal Performance:
1. Match existing for Rehabilitation areas
2. New System Overall Average R-Value: RSI-57 (R-33), minimum.
B. Fire and Wind Uplift Resistance: Provide roof insulation complying with requirements specified in Division 07 roofing section.
C. Insulation on Decking: UL labeled indicating compliance with one of the following:
1. UL Listed.
2. Insulation Surface Burning Characteristics: When tested according to
ASTM E84.
a. Flame Spread Rating: 75 maximum.
b. Smoke Developed Rating: 150 maximum.
2.2 PRODUCTS - GENERAL
A. Provide each product from one manufacturer.
B. Sustainable Construction Requirements:
01-01-21
ROOF AND DECK INSULATION
07 22 00 - 4
1. Insulation Recycled Content:
a. Rigid Foam: 9 percent total recycled content, minimum.
2. Low Pollutant-Emitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:
a. Non-flooring adhesives and sealants.
b. Composite wood and agrifiber.
3. Bio-Based Materials: Where applicable, provide products designated by USDA and meeting or exceeding USDA recommendations for bio-based content, and products meeting Rapidly Renewable Materials and certified sustainable wood content definitions; refer to www.biopreferred.gov.
2.3 ADHESIVES
A. Primer: Water based primers where required.
B. Modified Asphaltic Insulation Adhesive: Insulation manufacturer's recommended modified asphaltic, asbestos-free, cold-applied adhesive formulated to adhere roof insulation to substrate or to another insulation layer.
C. Bead-Applied Urethane Insulation Adhesive: Insulation manufacturer's recommended bead-applied, low-rise, one- or multicomponent urethane adhesive formulated to adhere roof insulation to substrate or to another insulation layer.
D. Full-Spread Applied Urethane Insulation Adhesive: Insulation manufacturer's recommended spray-applied, low-rise, two-component urethane adhesive formulated to adhere roof insulation to substrate or to another insulation layer.
2.4 ROOF AND DECK INSULATION
A. Roof and Deck Insulation, General: Preformed roof insulation boards approved by roofing manufacturer.
B. Polyisocyanurate Board Insulation: ASTM C1289, Type II, Class 1, Grade
2, faced with glass fiber reinforced cellulosic felt facers on both major surfaces of the core foam.
1. Match existing thickness and taper.
2.5 INSULATION ACCESSORIES
A. Cants and Tapered Edge Strips:
1. Insulation Cant Strips: ASTM C208, Type II, Grade 1, cellulosic-fiber insulation board.
01-01-21
ROOF AND DECK INSULATION
07 22 00 - 5
2. Tapered Edge Strips: 1/12 (1 inch per 12 inches), from 0 mm
(0 inches), 300 mm to 450 mm (12 inches to 18 inches) wide.
a. Cellulosic Fiberboard: ASTM C208.
b. Mineral Fiberboard: ASTM C726.
c. Perlite Board: ASTM C728.
2.6 VAPOR RETARDER MEMBRANE SYSTEM
1. Ply Sheet: ASTM D 6163, Grade S, Type III, glass-fiber-reinforced, SBS-modified asphalt sheet smooth surfaced, suitable for application specified.
2. Cold-Applied Adhesive: Roofing system manufacturer's standard one-or two-part, 24% Bio Based, 100% solids, asbestos-free, ultra low
VOC, cold-applied adhesive specially formulated for compatibility and use with roofing membrane sheets.
2.7 COVER BOARD:
1. Glass-Mat, Water-Resistant Gypsum Roof Board: ASTM C1177/C1177M, 6 mm (1/4 inch) thick per moisture survey of existing conditions, factory primed.
2.8 ACCESSORIES
A. Fasteners: Corrosion-resistant carbon steel fasteners and galvalume-coated steel or plastic round plates for fastening substrate board and insulation to roof deck.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Comply with requirements of Division 07 roofing section.
3.2 PREPARATION
A. Examine and verify substrate suitability for product installation.
B. Protect existing construction and completed work from damage.
3.3 INSTALLATION - GENERAL
A. Install products according to manufacturer's instructions.
1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.
B. Comply with requirements of UL for insulated steel roof deck.
C. Attach substrate board and other products to meet requirements of
Division 07 roofing section.
3.4 VAPOR RETARDER INSTALLATION
A. Vapor Retarder Installation, General:
1. Install continuous vapor retarder on roof decks where indicated.
01-01-21
ROOF AND DECK INSULATION
07 22 00 - 6
2. At vertical surfaces, turn up vapor retarder to top of insulation or base flashing.
3. Seal penetrations through vapor retarder with roof cement to prevent moisture entry from below.
B. Cast in Place Concrete Decks, Except Insulating Concrete:
1. Prime deck as specified.
2. Apply one ply per manufacturer requirements into uniform application of adhesive.
3. Roll membrane into adhesive and heat weld all laps.
3.5 INSULATION INSTALLATION
A. Insulation Installation, General:
1. Cant Strips: Install preformed insulation cant strips junctures of roofing system with vertical construction.
2. Use same insulation as existing for roof repair and alterations unless specified otherwise.
B. Insulation Thickness:
1. Thickness of roof insulation shown on drawings is nominal. Provide thickness required to comply with specified thermal performance.
2. Insulation on Metal Decks: Provide insulation thickness to match existing conditions.
3. When actual insulation thickness differs from drawings, coordinate alignment and location of roof drains, flashing, gravel stops, fascias and similar items.
4. Where tapered insulation is used, maintain insulation thickness at high points and roof edges shown on drawings.
a. Low Point Thickness: Minimum 38 mm (1-1/2 inches).
5. Use minimum two layers of insulation when required thickness is
68 mm (2.7 inch) or greater.
C. Lay insulating units with close joints, in regular courses and with end joints staggered.
1. Stagger joints between layers minimum 150 mm (6 inches).
D. Lay units with long dimension perpendicular to the rolled
(longitudinal) direction of the roofing felt.
E. Seal cut edges at penetrations and at edges against blocking with bitumen or roof cement.
F. Cut to fit tightly against blocking or penetrations.
G. Cover all insulation installed on the same day; comply with temporary protection requirements of Division 07 roofing section.
01-01-21
ROOF AND DECK INSULATION
07 22 00 - 7
H. Installation Method:
1. Adhered Insulation:
a. Prime substrate as required.
b. Set each layer of insulation firmly in ribbons of bead-applied insulation adhesive.
c. Set each layer of insulation firmly in uniform application of full-spread insulation adhesive.
3.6 COVER BOARD INSTALLATION
A. Install cover boards over insulation with long joints in continuous straight lines with staggered end joints.
B. Offset cover board joints from insulation joints 150 mm (6 inches), minimum.
C. Secure cover boards according to "Adhered Insulation" requirements.
- - E N D - -