EL0.2+Add+1.pdf

PDF 134 KB Posted

Attached to
Y1DA--552-CSI-162: Site Prep for PET CT Federal contract opportunity
Solicitation number
36C25021B0001
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This pre-solicitation notice describes a federal construction contract opportunity for site preparation work related to a PET/CT replacement project. The Department of Veterans Affairs will be soliciting proposals for site prep for PET-CT Replacement under project number 552-CSI-162 at the Dayton VA Medical Center in Dayton, Ohio. Offerors must be verified as Service-Disabled Veteran-Owned Small Businesses. The contractor will demolish existing structures and prepare the site for building operations. The performance period is 245 calendar days from notice to proceed. The solicitation documents will be posted on November 9, 2020 on SAM.gov, with proposals due approximately 30 days later. The estimated value is between $1,000,000 and $5,000,000 under NAICS code 236220 with a small business size standard of $39.5M. The SDVOSB must perform a minimum of 25% of the construction work. Bid, payment and performance bonds will be required.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--552-CSI-162: Site Prep for PET CT, newest first.
File Type Posted
36C25021B0001 A00007.pdf PDF
36C25021B0001 A00006.pdf PDF
JA - GOJO toilet accessories 2-18-2021_Redacted (1).pdf PDF
Bid Opening Instructions.pdf PDF
36C25021B0001 A00004.docx DOCX document
JA - Tork toilet accessories 2-18-2021_Redacted.pdf PDF
Pre-Bid RFI Responses Add No 2.pdf PDF
G100 - Cover Sheet - Add 2 (1).pdf PDF
2019-1206_C301 (DETLS) (1).pdf PDF
image001 (3).png PNG image
275223 - Nurse Call and Code Blue Systems - Add 2 (1).pdf PDF
2019-1206_C300 (DETLS) (1).pdf PDF
36C25021B0001 A00005 (1).pdf PDF
CBLH Addendum 1 Narrative.pdf PDF
102800ToiletAccessoriesADDNo1.pdf PDF
18111DVAMCPETCTGeotechReport.pdf PDF
18111DVAMCPETCTGeotechAddendumNo1.pdf PDF
36C25021B0001A00003.docx DOCX document
090600ScheduleofFinishesAddNo1.pdf PDF
EL2.3+Add+1.pdf PDF
EL3.4+Add+1+.pdf PDF
AS400EXTERIORELEVATIONSADDNo1.pdf PDF
BidOpeningInstructions.docx DOCX document
Pre-BidRFIResponsesAddNo2-19-2021.pdf PDF
Nu.+12+-+Site+Plan+Add+No+1.pdf PDF
AS522DETAILSADDNo1.pdf PDF
230711HVACandBoilerPlantInsulationAddNo1.pdf PDF
EL4.3+Add+1.pdf PDF
EL2.0+Add+1.pdf PDF
552-CSI-162 Site Visit Sign In.pdf PDF
36C25021B0001 A00002.docx DOCX document
Bid Opening Instructions.docx DOCX document
Site Visit Sign-In Sheet .xlsx XLSX spreadsheet
36C25021B0001 A00001.docx DOCX document
Valcom - ja_Redacted.pdf PDF
Masonry Veneer-JA_Redacted.pdf PDF
Fire Alarm-ja_Redacted.pdf PDF
Corbin Russwin Locksets-ja_Redacted.pdf PDF
18111 - DVAMC PETCTPart-4.pdf PDF
18111 - DVAMC PETCTPart-1.pdf PDF
Wage Determination.pdf PDF
18111 - DVAMC PETCTPart-3.pdf PDF
Patient Lifts-ja_Redacted.pdf PDF
Chicago Faucets-ja_Redacted.pdf PDF
18111 - DVAMC PETCTPart-2.pdf PDF
18111 - DVAMC PETCT PM VOL 1 of 2.pdf PDF
36C25021B0001_1.docx DOCX document
Beldon - Homestead - masonry brick-ja_Redacted.pdf PDF
18111 - DVAMC PETCTPart-5.pdf PDF
18111 - DVAMC PETCT PM VOL 2 of 2.pdf PDF
Show all 50

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LIGHTING CONTROL GENERAL NOTES

1. REFER TO FLOOR PLANS FOR QUANTITIES, WIRING AND SWITCHING ARRANGEMENTS.

2. REFER TO OCCUPANCY SENSOR MANUFACTURER'S WIRING DIAGRAMS FOR INSTALLATION DRAWINGS.

3. FOR ALL OCCUPANCY SENSORS, TIME DELAY DIP SWITCH SETTINGS SHALL BE FOR 15 MINUTES, UNLESS DIRECTED OTHERWISE. WALL MOUNTED DEVICES SHALL HAVE DIP SWITCH SETTINGS FOR

MANUAL ON.

4. OCCUPANCY SENSORS SHALL BE PROVIDED AS SPECIFIED BY SENSOR SWITCH. EQUALS SHALL BE MANUFACTURED BY WATTSTOPPER, TOUCHÉ CONTROLS, OR LEVITON. ALL EQUIVALENT SYSTEMS SHALL PROVIDE ALL DEVICES, WIRING, AND COMPONENTS FOR A COMPLETE INSTALLATION COMPARABLE TO

WATTSTOPPER.

5. EC IS RESPONSIBLE FOR PROPER COMMISSIONING OF ALL OCCUPANCY SENSORS. COMMISSIONING SHALL BE PERFORMED ONCE ALL SPACES ARE OCCUPIED AND HVAC SYSTEM IS PROPERLY BALANCED FOR AIR FLOW AND TEMPERATURE. COMMISSIONING SHALL INCLUDE A ROOM-BY-ROOM 100% TEST OF EACH SENSOR IN A SHORT TIME-OUT TEST MADE TO ENSURE SENSOR DETECTS HUMAN MOVEMENTS, NO AIR INTERFERENCE IS PRESENT, AND SENSOR CANNOT DETECT MOVEMENT OUTSIDE OF CONTROLLED

SPACE. INCLUDE ALL ADJUSTMENTS TO SETTINGS AND MINOR RELOCATION OF DEVICES.

LIGHTING CONTROL DIAGRAM #2

N.T.S.

SYMBOL " "

B

120V

WHITE

GROUND

NEUTRAL

NEUTRAL

GREEN

RED

BLACK

WHITE

(SEE INSTALLATION

INSTRUCTIONS)

120V GROUND

OC

Primary Load

SENSORSWITCH: PASSIVE

INFRARED WALL SWITCH

SENSOR #WSX-PDT.

BLK

WHT

120V

NEUTRAL

RED/EM 277V

YLW/EM 120V

BLU/EM MVOLT

WHT-RED/EM NEUTRAL

VLT DIM COMMON

GRY DIM POSITIVE

BLU LINE OUTGRN

CAT 5e

LIGHTING CONTROL DIAGRAM #5

N.T.S.

J

SYMBOL " "

E

SENSORSWITCH:

#nPODM-DX-WH

SINGLE CHANNEL

DIMMER SWITCH.

SYMBOL

SENSORSWITCH:

#nPP16-D POWER

PACK WITH MVOLT

INPUT.

SS

PP

A

LIGHTING CONTROL TAG DETAIL

LIGHTING CONTROL

TAG FOR ROOM OR

SPACE.

PANEL

CIRCUIT #

N.T.S.

LIGHTING CONTROL DIAGRAM #4

D

BLK

WHT

120V

NEUTRAL

CAT 5e

RED/EM 277V

YLW/EM 120V

BLU/EM MVOLT

WHT-RED/EM NEUTRAL

VLT DIM COMMON

GRY DIM POSITIVE

BLU LINE OUTGRN

CAT 5e

CAT 5e CAT 5e nCM-PDT-10

OCCUPANCY SENSOR

SENSOR SWITCH

J nCM-PDT-10

OCCUPANCY SENSOR

SENSOR SWITCH

FOR ADDITIONAL

POWER PACKS (IF

REQUIRED) IN WORK

SPACE, SEE PLANS

SYMBOL

SENSORSWITCH:

#nPP16-D POWER

PACK WITH MVOLT

INPUT.

SS

SENSORSWITCH:

#nPODM-DX-WH

SINGLE CHANNEL

DIMMER SWITCH.

OC1OC1

PP

N.T.S.

OR

Refer to floor plans for exact quantity and types of switches required.

A

LIGHTING CONTROL DIAGRAM #1

Lighting Load

Neutral White

Unswitched Hot Black

Lighting Load

Unswitched Hot Black

N.T.S.

BLK

WHT

120V

NEUTRAL

CAT 5e

RED/EM 277V

YLW/EM 120V

BLU/EM MVOLT

WHT-RED/EM NEUTRAL

RED/EM

YLW/EM

BLU/EM

WHT-RED/EM

VLT DIM COMMON

GRY DIM POSITIVE

BLU LINE OUT

VLT DIM COMMON

GRY DIM POSITIVE

BLUGRN

GRN

CAT 5e

CAT 5e a,b

LIGHTING CONTROL DIAGRAM #3

N.T.S.

C

J

J

SENSORSWITCH:

#nPODM-2P-DX-WH

TWO

CHANNEL DIMMER

SWITCH.

SYMBOL

SENSORSWITCH:

#nPP16-D POWER

PACK WITH

MVOLT

INPUT.

FOR ADDITIONAL

POWER PACKS (IF

REQUIRED) IN WORK

SPACE, SEE PLANS

a,b

SENSORSWITCH:

#nPODM-2P-DX-WH

TWO

CHANNEL DIMMER

SWITCH.

CAT 5e

SS

PP

SS

PP

SIGNATURE DATE

HATHAWAY

STATE OF O

H IO

P R

O F

ESS IO N

AL E N G

I N

E E

R

R E G I S T E RE D

E-61777

MARLON

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C :\U se rs

\M Ky ag ab a\ D oc um en ts

\1

_M

EP

_C

EN

TR

AL

F

IL

E_ m ky ag ab a@ sb m ce

.c om

.rv t

2/

/2

3:

:5

PM

EL0.2

LIGHTING FIXTURE SCHEDULE AND

DETAILS

SITE PREP FOR PET/CT

REPLACEMENT

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020 MCH

BID AND CONSTRUCTION

(REVISED)18111

09/16/2020

1. ALL FLUORESCENT FIXTURES SHALL BE PROVIDED WITH MVOLT ELECTRONIC BALLASTS WITH 10% TOTAL HARMONIC DISTORTION OR LESS UNLESS NOTED OTHERWISE. REFER TO SPECIFICATIONS FOR ACCEPTABLE BALLAST MANUFACTURERS

2. "NL" SUBSCRIPT INDICATES THAT THE FIXTURE IS CONNECTED TO AN UNSWITCHED CIRCUIT FOR "NIGHT LIGHT"

ILLUMINATION.

3. "EM" SUBSCRIPT INDICATES THAT THE FIXTURE IS CONNECTED TO AN EMERGENCY POWER SOURCE FOR EMERGENCY

ILLUMINATION.

4. EC TO USE BRAND NAME OR EQUAL.

5. VERIFY CEILING TYPE WITH ARCHITECTURAL REFLECTED CEILING PLAN. PROVIDE MOUNTING TYPE AS REQUIRED TO ACCOMMODATE THE CEILING. (i.e. FLANGE OR GRID MOUNT).

6. CONFIRM ALL MOUNTING HEIGHTS WITH ARCHITECT.

NOTES:

LIGHTING FIXTURE SCHEDULE

SYMBOL CATALOG NUMBER DESCRIPTION MOUNTING LAMP(S)

POWER

REQUIREMENT

0 VA

D1 LDN4-35/05-L04-AR-LSS-MVOLT-EZ1 LITHONIA: 11 3/16" x 9 7/16" x 5 11/16" DEEP LED FIXTURE WITH 4" APERATURE, 3500K, 523.6 LUMEN OUTPUT, 5.74W, MVOLT, WHITE FINISH AND ONE (1) 0-10V DIMMING LED DRIVER.

RECESSED INTEGRAL 6 VA

P1 ZL1D-L48-7000LM-FST-120-35K-80CRI

-WH

LITHONIA: 2.234"x4'x2.9882" DEEP LED FIXTURE WITH STEEL CONSTRUCTION, SNAP ON/SNAP OFF LENS, 7480 LUMEN OUTPUT, 120V, 3500K COLOR TEMPERATURE, 33W, WHITE FINISH AND (1) LED DRIVER.

PENDANT INTEGRAL 59 VA

R1 2BLT2-33L-ADP-EZ1-LP835 LITHONIA: 2'x2'x2-3/4" DEEP LED FIXTURE WITH ALUMINUM FRAM HOUSING, ACRYLIC LENS, 3300 LUMENT OUTPUT, 3500K, 82

CRI, 26W, WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 26 VA

R2 2BLT2-20L-ADP-EZ1-LP835 LITHONIA: 2'x2'x2-3/4" DEEP LED FIXTURE WITH ALUMINUM FRAM HOUSING, ACRYLIC LENS, 2000 LUMENT OUTPUT, 3500K, 82

CRI, 17W, WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 17 VA

R3 2BLT2-40L-ADP-EZ1-LP835 LITHONIA: 2'x2'x2-3/4" DEEP LED FIXTURE WITH ALUMINUM FRAM HOUSING, ACRYLIC LENS, 4041 LUMENT OUTPUT, 3500K, 82

CRI, 31.73W, WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 32 VA

W1 WAL14-LED4-LO-4-P-TMW-SC-UNV-W

M-DM10

PURDENTIAL LTG: 4'X7"X4" DEEP WALL MOUNT LED FIXTURE, 770LM/FT, 28W, MVOLT, WHITE FINISH AND 1- (ONE) 0-10V DIMMING

DRIVER.

WALL MOUNT INTEGRAL 20 VA

W2 LE-P-W-1-R-120/277-SW16 LITHONIA: "X-RAY IN USE" SIGN, WHITE HOUSING, RED LETTER COLOR, DUAL VOLTAGE. CEILING/WALL

SURFACE

INTEGRAL 3 VA

W3 070442-35K-PHC PERFORMANCE IN LIGHTING: 8.9"x8.6" LED EXTERIOR WALL MOUNT FIXTURE, ALUMINUM HOUSING, 3500K COLOR TEMPERATURE, TYPE 3 DISTRIBUTION, 18.5W, ALUMINUM METALLIC FINISH, INTEGRAL PHOTOCELL AND ONE (1) 0-10V LED

DIMMING DRIVER. FIXTURE TO BE MOUNTED 10' AFF UNLESS SPECIFIED OTHERWISE BY ARCHITECT.

WALL MOUNT INTEGRAL 19 VA

X1 EDGR-R LITHONIA: 13"x8"x1-3/4" DEEP LED EXIT SIGN WITH ACRYLIC HOUSING WITH BRUSHED ALUMINUM FACE, RED LETTERS DUAL VOLTAGE, NICKEL CADMIUM BATTERY AND MOUNTING, FACES & CHEVRONS AS INDICATED ON PLANS.

UNIVERSAL INTEGRAL 3 VA

Revisions: Date:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

BID AND CONSTRUCTION (REVISED) 07-13-2020

SOLE SOURCE REVISION 09-16-2020

ADDENDUM NO. 1 02-16-2021

File details come from the government source that posted it. Updated .