275223 - Nurse Call and Code Blue Systems - Add 2 (1).pdf
PDF 152 KB Posted
- Attached to
- Y1DA--552-CSI-162: Site Prep for PET CT Federal contract opportunity
- Solicitation number
- 36C25021B0001
About this file
This is a pre-solicitation notice for site preparation work for a PET-CT replacement project at the Dayton VA Medical Center. The Department of Veterans Affairs seeks to prepare the site for building operations, including demolition and removal of existing structures. The project is set aside for service-disabled veteran-owned small businesses and has a value between $1,000,000 and $5,000,000. Interested offerors should register at SAM.gov by November 9, 2020 to receive the solicitation, which will require bid, payment and performance bonds. A site visit will be scheduled, and amendments will be posted to SAM.gov. The work must be completed within 245 calendar days of notice to proceed. The North American Industry Classification System code is 236220 and the small business size standard is $39.5 million. The service-disabled veteran-owned small business must perform a minimum of 25% of the construction work.
View the file
Other files for this federal contract opportunity
Show all 50
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
10-01-18
VA PROJECT NO. 552-CSI-162
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 1
SECTION 27 52 23
NURSE CALL AND CODE BLUE SYSTEMS
PART 1 - GENERAL
1.1 SECTION SUMMARY
A. Work covered by this document includes design, engineering, labor, material and products, equipment warranty and system warranty, training and services for, and incidental to, the complete installation of new and fully operating National Fire Protection Association (NFPA) – Life
Safety Code 101.3-2 (a) Labeled and (b) Listed, Emergency Service
Nurse-Call and/or Life Safety listed Code Blue Communication System and associated equipment (here-in-after referred to as the System) provided in approved locations indicated on the contract drawings. These items shall be tested and certified capable of receiving, distributing, interconnecting and supporting Nurse-Call and/or Code Blue communications signals generated local and remotely as detailed herein.
B. Work shall be complete, Occupational Safety and Health Administration
(OSHA), National Recognized Testing Laboratory (NRTL – i.e.
Underwriters Laboratory [UL]) Listed and Labeled; and VA Central
Office (VACO), Telecommunications Voice Engineering (TVE 005OP3B) tested, certified and ready for operation.
C. The System shall be delivered free of engineering, manufacturing, installation, and functional defects. It shall be designed, engineered and installed for ease of operation, maintenance, and testing.
D. The term “provide”, as used herein, shall be defined as: designed, engineered, furnished, installed, certified, tested, and warranty by the Contractor.
E. Specification Order of Precedence: In the event of a conflict between the text of this document and the Project’s Contract Drawings outlined and/or cited herein; THE TEXT OF THIS DOCUMENT TAKES PRECEDENCE.
HOWEVER, NOTHING IN THIS DOCUMENT WILL SUPERSEDE APPLICABLE EMERGENCY
LAWS AND REGULATIONS, SPECIFICALLY NATIONAL AND/OR LOCAL LIFE AND
PUBLIC SAFETY CODES. The Local Fire Marshall and/or VA Public Safety
Officer are the only authorities that may modify this document’s
EMERGENCY CODE COMPLIANCE REQUIREMENTS, on a case by case basis, in writing and confirmed by VA’s Project Manager (PM), Resident Engineer
(RE) and TVE-005OP3B. The VA PM is the only approving authority for
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 2 other amendments to this document that may be granted, on a case by case basis, in writhing with technical concurrencies by VA’s PM, RE, TVE-005OP3B and identified Facility Project Personnel.
F. The Original Equipment Manufacturer (OEM) and Contractor shall ensure that all management, sales, engineering and installation personnel have read and understand the requirements of this specification before the system is designed, engineered, delivered and provided. The Contractor shall furnish a written statement stating this requirement as a part of the technical submittal that includes each name and certification, including the OEMs. The Contractor is cautioned to obtain in writing, all approvals for system changes relating to the published contract specifications and drawings, from the PM and/or the RE before proceeding with the change.
1.2 RELATED SECTIONS
A. 01 33 23 – Shop Drawings, Product Data and Samples.
B. 07 84 00 – Firestopping.
C. 26 05 19 – Low – Voltage Electrical Power Conductors and Cables (600
Volts and Below).
D. 26 41 00 – Facility Lightning Protection.
E. 27 05 11 – Requirements for Communications Installations.
F. 27 05 26 – Grounding and Bonding for Communications Systems.
G. 27 05 33 – Raceways and Boxes for Communications Systems.
H. 27 10 00 – CONTROL, COMMUNICATION AND SIGNAL WIRING.
I. 27 15 00 – Communications Structured Cabling.
L. 27 51 16 – Public Address & Mass Notification System (PA)
1.3 DEFINITION
A. Provide: Design, engineer, furnish, install, connect complete, test, certify and warranty.
B. Work: Materials furnished and completely installed.
C. Review of contract drawings: A service by the engineer to reduce the possibility of materials being ordered which do not comply with contract documents. The engineer's review shall not relieve the
Contractor of responsibility for dimensions or compliance with the contract documents. The reviewer's failure to detect an error does not constitute permission for the Contractor to proceed in error.
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 3
D. Headquarters (aka VACO) Technical Review, for National and VA
Communications and Security, Codes, Frequency Licensing Standards, Guidelines and Compliance:
Office of Telecommunications
Special Communications Team (005OP3B)
1335 East West Highway – 3rd Floor
Silver Spring, Maryland 20910,
(O) 301-734-0350, (F) 301-734-0360
E. Engineer: Scheeser Buckley Mayfield LLC
F. Owner: VAMC Dayton
G. General Contractor (GC): Contractor; you; successful bidder.
H. Contractor: Systems Contractor; you; successful bidder.
1.4 REFERENCES
A. The installation shall comply fully with all governing authorities, laws and ordinances, regulations, codes and standards, including, but not limited to:
1. United States Federal Law:
a. Departments of:
1) Commerce, Consolidated Federal Regulations (CFR), Title 15 –
Under the Information Technology Management Reform Act (Public
Law 104-106), the Secretary of Commerce approves standards and guidelines that are developed by the:
a) Chapter II, National Institute of Standards Technology
(NIST – formerly the National Bureau of Standards). Under
Section 5131 of the Information Technology Management
Reform Act of 1996 and the Federal Information Security
Management Act of 2002 (Public Law 107-347), NIST develops
– Federal Information Processing Standards Publication
(FIPS) 140-2—Security Requirements for Cryptographic
Modules.
b) Chapter XXIII, National Telecommunications and Information
Administration (NTIA – aka ‘Red Book’) Chapter 7.8 / 9;
CFR, Title 47 Federal communications Commission (FCC) Part
15, Radio Frequency Restriction of Use and Compliance in
“Safety of Life” Functions & Locations.
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 4
2) FCC - Communications Act of 1934, as amended, CFR, Title 47 –
Telecommunications, in addition to Part 15 – Restrictions of use for Part 15 listed Radio Equipment in Safety of Life /
Emergency Functions / Equipment/ Locations (also see CFR, Title 15 – Department of Commerce, Chapter XXIII – NTIA):
a) Part 15 – Restrictions of use for Part 15 listed Radio
Equipment in Safety of Life / Emergency Functions /
Equipment/Locations.
b) Part 58 – Television Broadcast Service.
c) Part 90 – Rules and Regulations, Appendix C.
3) Health, (Public Law 96-88), CFR, Title 42, Chapter IV Health &
Human Services, CFR, Title 46, Subpart 1395(a)(b) JCAHO “a hospital that meets JCAHO accreditation is deemed to meet the
Medicare conditions of Participation by meeting Federal
Directives:”
a) All guidelines for Life, Personal and Public Safety; and, Essential and Emergency Communications.
4) Labor, CFR, Title 29, Part 1910, Chapter XVII - Occupational
Safety and Health Administration (OSHA), Occupational Safety and Health Standard:
a) Subpart 7 - Definition and requirements (for a NRTL – 15
Laboratory’s, for complete list, contact
(http:www.osha.gov/dts/otpca/nrtl/faq_nrtl.html):
1) UL:
a) 44-02 – Standard for Thermoset-Insulated Wires and
Cables.
b) 65 – Standard for Wired Cabinets.
c) 83-03 – Standard for Thermoplastic-Insulated Wires and Cables.
d) 467-01 – Standard for Electrical Grounding and
Bonding Equipment
e) 468 – Standard for Grounding and Bonding Equipment.
f) 486A-01 – Standard for Wire Connectors and Soldering
Lugs for Use with Copper Conductors
g) 486C-02 – Standard for Splicing Wire Connectors.
h) 486D-02 – Standard for Insulated Wire Connector http://www.osha.gov/dts/otpca/nrtl/faq_nrtl.html
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 5
Systems for Underground Use or in Damp or Wet
Locations.
i) 486E-00 – Standard for Equipment Wiring Terminals for
Use with Aluminum and/or Copper Conductors.
j) 493-01 – Standard for Thermoplastic-Insulated
Underground Feeder and Branch Circuit Cable.
k) 514B-02 – Standard for Fittings for Cable and
Conduit.
l) 1069 – Hospital Signaling and Nurse Call Equipment.
m) 1449 – Standard for Transient Voltage Surge
Suppressors.
n) 1479-03 – Standard for Fire Tests of Through-
Penetration Fire Stops.
o) 1666 – Standard for Wire/Cable Vertical (Riser) Tray
Flame Tests.
p) 1863 – Standard for Safety, Communications Circuits
Accessories.
q) 2024 – Standard for Optical Fiber Raceways.
r) 60950-1/2 – Information Technology Equipment –
Safety.
2) Canadian Standards Association (CSA): same tests as for
UL.
3) Communications Certifications Labatory (CCL): same tests as for UL.
4) Intertek Testing Services NA, Inc. (ITSNA formerly
Edison Testing Laboratory [ETL]): same tests as for UL.
b) Subpart 35 – Compliance with NFPA 101 – Life Safety Code.
c) Subpart 36 - Design and construction requirements for exit routes.
d) Subpart 268 - Telecommunications.
e) Subpart 305 - Wiring methods, components, and equipment for general use.
5) Department of Transportation, CFR, Title 49 (Public Law 89-
670), Part 1, Subpart C – Federal Aviation Administration
(FAA):
a) Standards AC 110/460-ID & AC 707 / 460-2E – Advisory
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 6
Circulars for Construction of Antenna Towers.
b) Forms 7450 and 7460-2 – Antenna Construction Registration.
6) Veterans Affairs (Public Law No. 100-527), CFR, Title 38, Volumes I & II:
a) Office of Telecommunications:
1) Handbook 6100 – Telecommunications.
a) Spectrum Management FCC & NTIA Radio Frequency
Compliance and Licensing Program.
b) Special Communications Proof of Performance Testing, VACO Compliance and Life Safety Certification(s).
b) Office of Cyber and Information Security (OCIS):
1) Handbook 6500 - Information Security Program.
2) Wireless and Handheld Device Security Guideline Version
3.2, August 15, 2005.
c) VA’s National Center for Patient Safety – Veterans Health
Administration Warning System, Failure of Medical Alarm
Systems using Paging Technology to Notify Clinical Staff, July 2004.
d) VA’s Center for Engineering Occupational Safety and Health, concurrence with warning identified in VA Directive 7700.
e) Office of Construction and Facilities Management (CFM):
1) Master Construction Specifications (PG-18-1).
2) Standard Detail and CAD Standards (PG-18-4).
3) Equipment Guide List (PG-18-5).
4) Electrical Design Manual for VA Facilities (PG 18-10), Articles 7 & 8.
5) Minimum Requirements of A/E Submissions (PG 18-15):
a) Volume B, Major New Facilities, Major Additions; and
Major Renovations, Article VI, Paragraph B.
b) Volume C - Minor and NRM Projects, Article III, Paragraph S.
c) Volume E - Request for Proposals Design/Build
Projects, Article II, Paragraph F.
6) Mission Critical Facilities Design Manual (Final Draft –
2007).
7) Life Safety Protected Design Manual (Final Draft –
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 7
2007).
8) Solicitation for Offerors (SFO) for Lease Based Clinics
– (05-2009).
b. Federal Specifications (Fed. Specs.):
1) A-A-59544-00 - Cable and Wire, Electrical (Power, Fixed
Installation).
2. National Codes:
a. American Institute of Architects (AIA): Guidelines for Healthcare
Facilities.
b. American National Standards Institute/Electronic Industries
Association/Telecommunications Industry Association
(ANSI/EIA/TIA):
1) 568-B - Commercial Building Telecommunications Wiring
Standards:
a) B-1 – General Requirements.
b) B-2 – Balanced twisted-pair cable systems.
c) B-3 - Fiber optic cable systems.
2) 569 - Commercial Building Standard for Telecommunications
Pathways and Spaces.
3) 606 – Administration Standard for the Telecommunications
Infrastructure of Communications Buildings.
4) 607 – Commercial Building Grounding and Bonding Requirements for Telecommunications.
5) REC 127-49 – Power Supplies.
6) RS 270 – Tools, Crimping, Solderless Wiring Devices, Recommended Procedures for User Certification.
c. American Society of Mechanical Engineers (ASME):
1) Standard 17.4 – Guide for Emergency Personnel.
2) Standard 17.5 – Elevator & Escalator Equipment (prohibition of installing non-elevator equipment in Elevator Equipment Room /
Mechanical Penthouse).
d. American Society of Testing Material (ASTM):
1) D2301-04 - Standard Specification for Vinyl Chloride Plastic
Pressure Sensitive Electrical Insulating Tape.
e. Building Industries Communications Services Installation (BICSI):
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 8
1) All standards for smart building wiring, connections and devices for commercial and medical facilities.
2) Structured Building Cable Topologies.
3) In consort with ANSI/EIA/TIA.
f. Institute of Electrical and Electronics Engineers (IEEE):
1) SO/TR 21730:2007 - Use of mobile wireless communication and computing technology in healthcare facilities -
Recommendations for electromagnetic compatibility (management of unintentional electromagnetic interference) with medical devices.
2) 0739-5175/08/©2008 IEEE – Medical Grade – Mission Critical –
Wireless Networks.
3) C62.41 – Surge Voltages in Low-Voltage AC Power Circuits.
g. NFPA:
1) 70 - National Electrical Code (current date of issue) –
Articles 517, 645 & 800.
2) 75 - Standard for Protection of Electronic Computer Data-
Processing Equipment.
3) 77 – Recommended Practice on Static Electricity.
4) 99 - Healthcare Facilities.
5) 101 - Life Safety Code.
3. State Hospital Code(s).
4. Local Town, City and/or County Codes.
5. Accreditation Organization(s):
a. Joint Commission on Accreditation of Hospitals Organization
(JCAHO) – Section VI, Part 3a – Operating Features.
1.5 QUALIFICATIONS
A. The OEM shall have had experience with three (3) or more installations of Nurse Call systems of comparable size and interfacing complexity with regards to type and design as specified herein. Each of these installations shall have performed satisfactorily for at least one (1) year after final acceptance by the user. Include the names, locations and point of contact for these installations as a part of the submittal.
B. The Contractor shall submit certified documentation that they have been an authorized distributor and service organization for the OEM for a
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 9 minimum of three (3) years. The Contractor shall be authorized by the
OEM to pass thru the OEM’s warranty of the installed equipment to VA.
In addition, the OEM and Contractor shall accept complete responsibility for the design, installation, certification, operation, and physical support for the System. This documentation, along with the System Contractor and OEM certifications must be provided in writing as part of the Contractor’s Technical submittal.
C. The Contractor’s Communications Technicians assigned to the System shall be fully trained, qualified, and certified by the OEM on the engineering, installation, operation, and testing of the System. The
Contractor shall provide formal written evidence of current OEM certification(s) for the installer(s) as a part of the submittal or to the RE before being allowed to commence work on the System.
D. The Contractor shall display all applicable national, state and local licenses.
E. The Contractor shall submit copy (s) of Certificate of successful completion of OEM’s installation/training school for installing technicians of the System’s Nurse Call and/or Code Blue equipment being proposed.
1.6 CODES AND PERMITS
A. Provide all necessary permits and schedule all inspections as identified in the contract’s milestone chart, so that the system is proof of performance tested, certified and approved by VA and ready for operation on a date directed by the Owner.
B. The contractor is responsible to adhere to all codes described herein and associated contractual, state and local codes.
1.7 SCHEDULING
A. After the award of contract, the Contractor shall prepare a detailed schedule (aka milestone chart) using “Microsoft Project” software or equivalent. The Contractor Project Schedule (CPS) shall indicate detailed activities for the projected life of the project. The CPS shall consist of detailed activities and their restraining relationships. It will also detail manpower usage throughout the project.
B. It is the responsibility of the Contractor to coordinate all work with the other trades for scheduling, rough-in, and finishing all work
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 10 specified. The owner will not be liable for any additional costs due to missed dates or poor coordination of the supplying contractor with other trades.
1.8 REVIEW OF CONTRACT DRAWINGS AND EQUIPMENT DATA SUBMITTALS (AKA
TECHNICAL SUBMITTAL[S])
(Note: The Contractor is encouraged, but not required, to submit separate technical submittal(s) outlining alternate technical approach(s) to the system requirements stated here-in as long as each alternate technical document(s) is complete, separate, and submitted in precisely the same manner as outlined herein. VA will review and rate each received alternate submittal, which follows this requirement, in exactly the same procedure as outlined herein. Partial, add-on, or addenda type alternates will not be accepted or reviewed.)
A. Submit at one time within 10 days of contract awarding, drawings and product data on all proposed equipment and system. Check for compliance with contract documents and certify compliance with
Contractor's "APPROVED" stamp and signature.
B. Support all submittals with descriptive materials, i.e., catalog sheets, product data sheets, diagrams, and charts published by the manufacturer. These materials shall show conformance to specification and drawing requirements.
C. Where multiple products are listed on a single cut-sheet, circle or highlight the one that you propose to use. Provide a complete and through equipment list of equipment expected to be installed in the system, with spares, as a part of the submittal. Special
Communications (TVE-005OP3B) will not review any submittal that does not have this list.
D. Provide four (4) copies to the PM for technical review. The PM will provide a copy to the offices identified in Paragraph 1.3.C & D, at a minimum for compliance review as described herein where each responsible individual(s) shall respond to the PM within 10 days of receipt of their acceptance or rejection of the submittal(s).
E. Provide interconnection methods, conduit (where not already installed), junction boxes (J-Boxes), cable, interface fixtures and equipment lists for the: ENR(s) ( aka DMARC), TER, TCR, MCR, MCOR, PCR, ECR, Stacked
Telecommunications Rooms (STR), Nurses Stations (NS), Head End Room
(HER), Head End Cabinet (HEC), Head End Interface Cabinet (HEIC) and
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 11 approved TCO locations TIP interface distribution layout drawing, as they are to be installed and interconnected to teach other (REFER TO
APPENDIX B – SUGGESTED TELECOMMUNI-CAITONS ONE LINE TOPOLOGY pull-out drawing).
F. Equipment technical literature detailing the electrical and technical characteristics of each item of equipment to be furnished.
G. Engineering drawings of the System, showing calculated of expected signal levels at the headend input and output, each input and output distribution point, and signal level at each telecommunications outlet.
H. Surveys Required as a Part of The Technical Submittal:
1. The Contractor shall provide the following System surveys that depict various system features and capacities required in addition to the on-site survey requirements described herein (see
Specification Paragraph 2.4.3). Each survey shall be in writing and contain the following information (the formats are suggestions and may be used for the initial Technical Submittal Survey requirements), as a minimum:
a. Nurse Call Cable System Design Plan:
1) An OEM and contractor designed functioning Nurse Call System cable plan shall be provided as a part of the technical proposal. A specific functioning Nurse Call: cable, interfaces, J-boxes and back boxes shall coincide with the total growth items as described herein. It is the
Contractor’s responsibility to provide the Systems’ entire
Nurse Call cable and accessory requirements and engineer a functioning Nurse Call distribution system and equipment requirement plan of the following paragraph(s), at a minimum:
2) The required Nurse Call and/or Code Blue Equipment Locations:
EQUIPPED ITEM CAPACITY GROWTH
Master Stations
Dome Lights
Room
Corridor
Other
Patient Stations
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 12
EQUIPPED ITEM CAPACITY GROWTH
Single
Dual
Isolation
Other
Emergency Stations
Bath
Toilet
Isolation
Other
Staff Stations
Duty Stations
Code Blue
Patient Locations
Surgical Recovery Locations
Medical Recovery Locations
ICU Locations
SICU
MICU
CCU
Other
Emergency Room Locations
Other
Supervisory Locations
Nurse Stations
On-Call Rooms
Other
Remote Locations
Telephone Operator’s Room
Police Control Room
Other
Radio Paging Access (when pre-approved by TVE-005OP3B)
Audio Paging Access (when pre-approved by TVE-005OP3B)
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 13
EQUIPPED ITEM CAPACITY GROWTH
Wireless Access (when pre-approved by
TVE-005OP3B)
Maintenance/Programming Console
Location(s)
Central Control Cabinet/Equipment
Location
Power Supply(s)
UPS(s)
3) The required Nurse Call and/or Code Blue Cable
Plant/Connections:
The Contractor shall clearly and fully indicate this category for each item identified herein as a part of the technical submittal. For this purpose, the following definitions and sample connections are provided to detail the system’s capability:
EQUIPPED ITEM CAPACITY GROWTH
Central Control Cabinet/Equipment
Location
Power Supply(s)
UPS(s)
Essential Electrical Power Panel(s)
Other
Cable Plant
Supply to Locations Identified in Paragraph 1.8.H.1.a.2)
Remote Locations
Telephone Operator Room
Police Control Room
Other
Maintenance/Program Console
Location(s)
Other
LAN (Local Facility) Access/Equipment/Location (when pre-approved by TVE-005OP3B)
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 14
EQUIPPED ITEM CAPACITY GROWTH
Wireless Access/Equipment/Location (when pre-approved by TVE-005OP3B)
PA Access/Equipment/Location (when pre-approved by TVE-005OP3B)
Other
1.9 PROJECT RECORD DOCUMENTS (AS BUILTS)
A. Throughout progress of the Work, maintain an accurate record of changes in Contract Documents. Upon completion of Work, transfer recorded changes to a set of Project Record Documents.
B. The floorplans shall be marked in pen to include the following:
1. Each device specific locations with UL labels affixed.
2. Conduit locations.
3. Each interface and equipment specific location.
4. Head-end equipment and specific location.
5. Wiring diagram.
6. Labeling and administration documentation.
7. Warranty certificate.
8. System test results.
1.10 WARRANTIES / GUARANTY
A. The Contractor shall warrant the installation to be free from defect in material and workmanship for a period of two (2) years from the date of acceptance of the project by the owner. The Contractor shall agree to remedy covered defects within four (4) hours of notification of major failures or within twenty-four (24) hours of notification for individual station related problems.
B. The Contractor shall agree to grantee the system according to the guidelines outlined in Article 4 herein.
1.11 USE OF THE SITE
A. Use of the site shall be at the GC’s direction.
B. Coordinate with the GC for lay-down areas for product storage and administration areas.
C. Coordinate work with the GC and their sub-contractors.
D. Access to buildings wherein the work is performed shall be directed by the GC.
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 15
1.12 DELIVERY, STORAGE, AND HANDLING
A. Deliver, store, and handle products using means and methods that will prevent damage, deterioration, and loss, including theft.
B. Store products in original containers.
C. Coordinate with the GC for product storage. There may be little or no storage space available on site. Plan to potentially store materials off site.
D. Do not install damaged products. Remove damaged products from the site and replaced with new product at no cost to the Owner.
1.13 PROJECT CLOSE-OUT
A. Prior to final inspection and acceptance of the work, remove all debris, rubbish, waste material, tools, construction equipment, machinery and surplus materials from the project site and thoroughly clean your work area.
B. Before the project closeout date, the Contractor shall submit:
1. OEM Equipment Warranty Certificates.
2. Evidence of compliance with requirements of governing authorities such as the Low Voltage Certificate of Inspection.
3. Project record documents.
4. Instruction manuals and software that is a part of the system.
5. System Guaranty Certificate.
C. Contractor shall submit written notice that:
1. Contract Documents have been reviewed.
2. Project has been inspected for compliance with contract.
3. Work has been completed in accordance with the contract.
PART 2 – PRODUCTS / FUNCTIONAL REQUIREMENTS
2.0 GENERAL REQUIREMENTS FOR EQUIPMENT AND MATERIALS
A. Furnish and install a complete and fully functional and operable Nurse
Call System for each location shown on the contract drawings and TCOs.
B. Coordinate features and select interface components to form an integrated Nurse Call system. Match components and interconnections between the systems for optimum performance of specified functions.
C. Expansion Capability: The Nurse Call equipment interfaces and cables shall be able to increase number of enunciation points in the future by a minimum of 50 percent (%) above those indicated without adding any internal or external components or main trunk cable conductors.
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 16
D. Equipment: Active electronic type shall use solid-state components, fully rated for continuous duty unless otherwise indicated. Select equipment for normal operation on input power usually supplied between
110 to 130 VAC, 60 Hz supplied from the Facility’s Emergency Electrical
Power System.
E. Meet all FCC requirements regarding equipment listing, low radiation and/or interference of RF signal(s). The system shall be designed to prevent direct pickup of signals from within and outside the building structure.
F. Weather/Water Proof Equipment: Listed and labeled by an OSHA certified
NRTL (i.e. UL) for duty outdoors or in damp locations.
2.1 SYSTEM DESCRIPTION
A. Furnish and install a complete and fully functional and operable Nurse
Call and/or Code Blue System.
B. The System Contractor shall connect the System ensuring that all NFPA and UL Critical Care and Life Safety Circuit and System separation guidelines are satisfied. The System Contractor is not allowed to make any connections to the Telephone System.
C. System hardware shall consist of a standalone (separate) nurse call
Code Blue patient communications network comprised of nurse consoles, control stations, staff and duty stations, room and corridor dome lights, pull cord and/or emergency push button stations, wiring. And, other options such as, pocket page interfaces, computer interfaces, printer interfaces, wireless / telephone network interfaces, and nurse locating system interface (when specifically approved first by TVE
005OP3B) and as shown on drawings. All necessary equipment required to meet the intent of these specifications, whether or not enumerated within these specifications, shall be supplied and installed to provide a complete and operating nurse call Code Blue patient communications network. It is not acceptable to utilize the telephone cable system for the control and distribution of nurse call (code Blue) signals and equipment.
D. System firmware shall be the product of a reputable firmware OEM of record with a proven history of product reliability and sole control over all source code. Manufacturer shall provide, free of charge, product firmware/software upgrades for a period of two (2) years from
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 17 date of acceptance by VA for any product feature enhancements. System configuration programming changes shall not require any exchange of parts and shall be capable of being executed remotely via a modem connection (when specifically approved first by TVE 005OP3B).
E. The Nurse Call Head End Equipment shall be located on first floor
Telecommunications Room.
F. The System shall utilize microprocessor components for all signaling and programming circuits and functions. Self contained or on board system program memory shall be non-volatile and protected from erasure from power outages for a minimum of 12 hours.
G. Provide a backup battery or a UPS for the System (including each distribution cabinet/point, CRT and Monitor) to allow normal operation and function (as if there was no AC power failure) in the event of an
AC power failure or during input power fluctuations for a minimum of 30 minutes.
H. Each Code Blue System shall be designed to provide continuous electrical supervision of the complete and entire system (i.e. dome light bulbs [each light will be considered supervised if they use any one or a combination of (UL) approved electrical supervision alternates, as identified in UL-1069, 1992 revision], wires, contact switch connections, circuit boards, data, audio, and communication busses, main and UPS power, etc.). All alarm initiating and signaling circuits shall be supervised for open circuits, short circuits, and system grounds. Main and UPS power circuits shall be supervised for a change in state (i.e. primary to backup, low battery, UPS on line, etc.). When an open, short or ground occurs in any system circuit, an audible and visual fault alarm signal shall be initiated at the nurse control station and all remote locations.
I. All passive distribution equipment shall meet or exceed -80 dB radiation shielding (aka RFI) shielding specifications and be provided with connectors specified by the OEM.
J. All equipment face plates utilized in the system shall be stainless steel, anodized aluminum or UL approved cycolac plastic for the areas where provided.
K. Noise filters and surge protectors shall be provided for each equipment interface cabinet, headend cabinet, control console and local and
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 18 remote amplifier locations to insure protection from input primary AC power surges and to insure noise glitches are not induced into low voltage data circuits.
L. Plug-in connectors shall be provided to connect all equipment, except coaxial cables. Coaxial cable distribution points shall use coaxial cable connections recommended by the cable OEM and approved by the system OEM. Base band cable systems shall utilize barrier terminal screw type connectors, at a minimum. As an alternate, crimp type connectors installed with a ratchet type installation tool are acceptable provided the cable dress, pairs, shielding, grounding, connections and labeling are the same as the barrier terminal strip connectors. Tape of any type, wire nuts or solder type connections are unacceptable and will not be approved.
M. Audio Level Processing: The control equipment shall consist of audio mixer(s), volume limiter(s) and/or compressor(s), and power amplifier(s) to process, adjust, equalize, isolate, filter, and amplify each audio channel for each sub-zone in the system and distribute them into the System’s RF interfacing distribution trunks and amplification circuits. It is acceptable to use identified Telephone System cable pairs designated for Two-Way Radio interface and control use or identified as spare telephone cable pairs by the Facility’s Telephone
System Contractor. The use of telephone cable to distribute RF signals, carrying system or sub-system AC or DC voltage is not acceptable and will not be approved. Additionally, each control location shall be provided with the equipment required to insure the system can produce its designed audio channel capacity at each speaker identified on the contract drawings. The Contractor shall provide: a spare set of telephone paging modules as recommended by the OEM (as a minimum provide one spare module for each installed module); one spare audio power amplifier, one spare audio mixer, one spare audio volume limiter and/or compressor, and one spare audio automatic gain adjusting device, and minimum RF equipment recommended by the OEM.
N. Contractor is responsible for pricing all accessories and miscellaneous equipment required to form a complete and operating system. Unless otherwise noted in this Part, equipment quantities shall be as indicated on the drawings.
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 19
O. System Performance:
1. At a minimum, each distribution, interconnection, interface, terminating point and TCO shall be capable of supporting the
Facility’s Nurse Call and/or Code Blue System voice and data service as follows:
a. Shall be compliant with and not degrade the operating parameters of the Public Switched Telephone Network (PSTN) and the Federal
Telecommunications System (FTS) at each PSTN and FTS interface
(if attachment is permitted by TVE 005OP3B), interconnection and
TCO terminating locations detailed on the contract drawings.
b. The System shall provide the following minimum operational functions:
1) Code Blue calls shall be cancelable at the calling station only. The nurse call master station (s) that a managing Code
Blue functions shall not have the ability to cancel Code Blue calls.
2) Each Code Blue system shall be able to receive audio calls from all bedside stations simultaneously.
3) Calls placed from any Code Blue station shall generate Code
Blue emergency type audible and visual signals at each associated nurse control and duty station, respective dome lights and all local and remote annunciator panels. Calls placed from a bedside station shall generate emergency type visual signals at the bedside station and associated dome light(s) in addition to the previous stated stations and panels.
4) Activating the silencing device at any location, while a Code
Blue call or system fault is occurring shall mute the audible signals at the alarm location.
a) The audible alarm shall regenerate at the end of the selected time-out period until the call or fault is corrected.
b) The visual signals shall continue until the call is canceled and/or a fault is corrected. When the fault is corrected, all signals generated by the fault shall
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 20 automatically cease, returning the System to a standby status.
c) Audible signals shall be regenerated in any local or remote annunciator panel that is in the silence mode, in the event an additional Code Blue call is placed in any Code Blue system.
d) The additional Code Blue call shall also generate visual signals at all annunciators to identify the location of the call.
2. Each System Nurse Call location shall generate a minimum of distinct calls:
a. Routine: single flashing dome lights & master station color and audio tone,
b. Staff Assist: rapid flashing dome lights & master station color and audio tone,
c. Emergency: Red flashing done lights & master station color and audio tone,
d. Code Blue (if equipped): Blue flashing dome lights and master station color and audio tone,
e. Each generated call shall be cancelable at ONLY the originating location,
f. Staff Locator: Green Flashing dome lights & master station color and audio tone, and
2.3 MANUFACTURERS
A. The products specified shall be new, FCC and UL Listed, labeled and produced by OEM manufacturer of record. An OEM of record shall be defined as a company whose main occupation is the manufacture for sale of the items of equipment supplied and which:
1. Maintains a stock of replacement parts for the item submitted,
2. Maintains engineering drawings, specifications, and operating manuals for the items submitted, and
3. Has published and distributed descriptive literature and equipment specifications on the items of equipment submitted at least 30 days prior to the Invitation for Bid.
B. Specifications contained herein as set forth in this document detail the salient operating and performance characteristics of equipment in
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 21 order for VA to distinguish acceptable items of equipment from unacceptable items of equipment. When an item of equipment is offered or furnished for which there is a specification contained herein, the item of equipment offered or furnished shall meet or exceed the specification for that item of equipment.
C. Equipment Standards and Testing:
1. The System has been defined herein as connected to systems identified as Critical Service performing various Emergency and Life
Support Functions. Therefore, at a minimum, the system shall conform to all aforementioned National and/or Local Life Safety Codes (which ever are the more stringent), NFPA, NEC, this specification, JCAHCO
Life Safety Accreditation requirements, and the OEM recommendations, instructions, and guidelines.
2. All supplies and materials shall be listed, labeled or certified by
UL or a NRTL where such standards have been established for the supplies, materials or equipment.
3. The provided equipment required by the System design and approved technical submittal must conform with each UL standard in effect for the equipment, as of the date of the technical submittal (or the date when the RE approved system equipment necessary to be replaced) was technically reviewed and approved by VA. Where a UL standard is in existence for equipment to be used in completion of this contract, the equipment must bear the approved UL seal.
4. Each item of electronic equipment to be provided under this contract must bear the approved UL seal or the seal of the testing laboratory that warrants the equipment has been tested in accordance with, and conforms to the specified standards. The placement of the UL Seal shall be a permanent part of the electronic equipment that is not capable of being transportable from one equipment item to another.
2.4 PORDUCTS
A. General.
1. Contractor is responsible for pricing all accessories and miscellaneous equipment required to form a complete and operating system. The equipment quantities provided herein shall be as indicated on the drawings with the exception of the indicated spare equipment.
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 22
2. Contractor Furnished Equipment List (CFEs):
a. The Contractor is required to provide a list of the CFE equipment to be furnished. The quantity, make and model number of each item is required. Select the required equipment items quantities that will satisfy the needs of the system as described herein and with the OEM’s concurrence applied to the list(s), in writing.
Item Quantity Unit
1. As Required Interface Panel(s) 1.a As Required Electrical Supervision
Trouble Enunciator 1.a.1 As Required Equipment Back Box(s) 1.b As Required Telephone 1.c As Required Public Address 1.d As Required Radio Paging / Equipment 1.e As Required Wireless / Equipment 1.f. As Required Radio Pager / Equipment 1.g As Required Wireless / Equipment 1.f As Required Personal Communicator /
Equipment
2. As Required Lightning Arrestor
3. As Required Head End Equipment/Locations 3.a As Required Cabinet(s) 3.a.1 As Required AC Power Conditioner & Filter 3.a.2 As Required AC Power Strip 3.a.3 As Required UPS 3.a.4 As Required Interconnecting Wire/Cables 3.a.5 As Required Wire / Cable Connector(s) 3.a.6 As Required Wire / Cable Terminator(s) 3.b As Required Wire Management System 3.b As Required Head End Function(s) 3.b.1 As Required H7 Interface 3.b.2 As Required Nurse Locator 3.b.3 As Required Staff Locator
4. As Required Master Station(s) 4.a As Required Nurse Locator 4.b As Required Staff Locator
5. As Required Distribution System(s) 5.a As Required Staff Station 5.a.1 As Required Equipment Back Box(s) 5.b As Required Duty Station 5.b.1 As Required Equipment Back Box(s) 5.c As Required Code Blue Station 5.c.1 As Required Equipment Back Box(s) 5.c.2 2 (MIN) Remote Station(s) 5.d As Required Patient Station(s) 5.d.1 As Required Equipment Back Box(s) 5.d.2 As Required Bed Interface(s) 5.d.3 As Required Pillow Speaker 5.d.4 As Required Push Button Cordset 5.d.5 As Required Dummy Plugs
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 23
5.d.6 As Required Bed Integrated Control 5.d.7 As Required Lighting Interface Module 5.d.8 As Required TV Control Interface 5.d.9 As Required TV Control Jack 5.d.10 As Required TV Interconnection Cables 5.d.11 As Required HDTV Coaxial
5.d.12 As Required HDTV/Nurses Call Interface/ Control
5.d.13 As Required Auxiliary Mounting Interface 5.e As Required Emergency Station(s) 5.e.1 As Required Equipment Back Box(s) 5.e.2 As Required Toilet Emergency Station
(waterproof) 5.e.3 As Required Shower Emergency Station
(waterproof) 5.e.4 As Required Lavatory Emergency Station
(waterproof) 5.f. As Required Room Dome Light 5.f.1 As Required Equipment Back Box(s) 5.g As Required Other Dome Light(s) 5.g.1 As Required Equipment Back Box(s) 5.g.2 As Required Corridor Dome Light 5.g.3 As Required Intersectional Dome Light 5.h As Required System Cable(s) 5.h.1 As Required Coaxial 5.h.2 As Required System Pin 5.h.3 As Required Audio 5.h.4 As Required Control 5.h.5 As Required Video 5.i As Required System Connector(s) 5.i.1 As Required Coaxial 5.i.2 As Required System Pin 5.i.2 As Required Audio 5.i.3 As Required Control 5.i.4 As Required Video 5.j As Required Wire Management Required as described herein
6. As Required Mental Health Unit 6.a As Required Head End Function(s) 6.a.1 As Required H7 Interface 6.a.2 As Required Nurse Locator 6.a.3 As Required Staff Locator 6.b. As Required Master Station(s) 6.b.1 As Required Nurse Locator 6.b.2 As Required Staff Locator 6.c As Required Distribution System(s) 6.c.1 As Required Staff Station 6.c.1.a As Required Equipment Back Box(s) 6.c.2 As Required Duty Station 6.c.2.a As Required Equipment Back Box(s) 6.c.3 As Required Patient Station(s) 6.c.3.a As Required Equipment Back Box(s)\ 6.c.4 As Required Security Room(s)
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 24
6.c.4.a As Required Security Station(s) 6.c.4.b As Required Equipment Back Box(s)\ 6.c.4.c As Required Overhead Speaker/Microphone 6.c.4.d As Required Equipment Back Box(s)\ 6.c.4.e As Required TV Surveillance System 6.c.4.f As Required Equipment Back Box(s)\ 6.c.4.g As Required TV Interconnection Cables 6.c.4.h As Required Audio Interconnection Cables 6.c.5 As Required Emergency Station(s) 6.c.5.a As Required Equipment Back Box(s) 6.c.5.b As Required Toilet Emergency Station
(waterproof) 6.c.5.c As Required Shower Emergency Station
(waterproof) 6.c.5.d As Required Lavatory Emergency Station
(waterproof) 6.c.6 As Required Room Dome Light 6.c.7 As Required Other Dome Light(s) 6.c.7.a As Required Equipment Back Box(s) 6.c.7.b As Required Corridor Dome Light 6.c.7.c As Required Intersectional Dome Light 6.c.8 As Required System Cable(s) 6.c.8.a As Required Coaxial 6.c.8.b As Required System Pin 6.c.8.c As Required Audio 6.c.8.d As Required Control 6.c.8.e As Required Video 6.c.9 As Required System Connector(s) 6.c.9.a As Required Coaxial 6.c.9.b As Required System Pin 6.c.9.c As Required Audio 6.c.9.d As Required Control 6.c.9.e As Required Video 6.c.9.f As Required Wire Management Required as described herein
7 As Required Blind Rehabilitation Unit 7.a As Required Head End Function(s) 7.a.1 As Required H7 Interface 7.a.2 As Required Nurse Locator 7.a.3 As Required Staff Locator 7.b. As Required Master Station(s) 7.b.1 As Required Nurse Locator 7.b.2 As Required Staff Locator 7.c As Required Distribution System(s) 7.c.1 As Required Staff Station 7.c.1.a As Required Equipment Back Box(s) 7.c.2 As Required Duty Station 7.c.2.a As Required Equipment Back Box(s) 7.c.3 As Required Patient Station(s) 7.c.3.a As Required Equipment Back Box(s)\ 7.c.4 As Required Emergency Station(s) 7.c.4.a As Required Equipment Back Box(s) 7.c.4.b As Required Toilet Emergency Station
(waterproof)
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 25
7.c.4.c As Required Shower Emergency Station (waterproof)
7.c.4.d As Required Lavatory Emergency Station (waterproof)
7.c.5 As Required Room Dome Light 7.c.5.a As Required Equipment Back Box(s) 7.c.6 As Required Other Dome Light(s) 7.c.6.a As Required Equipment Back Box(s) 7.c.6.b As Required Corridor Dome Light 7.c.6.c As Required Intersectional Dome Light 7.c.7 As Required System Cable(s) 7.c.7.a As Required Coaxial 7.c.6.b As Required System Pin 7.c.7.c As Required Audio 7.c.7.d As Required Control 7.c.7.e As Required Video 7.c.8 As Required System Connector(s) 7.c.8.a As Required Coaxial 7.c.8.b As Required System Pin 7.c.8.c As Required Audio 7.c.8.d As Required Control 7.c.8.e As Required Video 7.c.9 As Required Wire Management Required as described herein
8. As Required Center for the Aging (aka Nursing Home Care Unit)
8.a As Required Head End Function(s) 8.a.1 As Required H7 Interface 8.a.2 As Required Nurse Locator 8.a.3 As Required Staff Locator 8.b. As Required Master Station(s) 8.b.1 As Required Nurse Locator 8.b.2 As Required Staff Locator 8.c As Required Distribution System(s) 8.c.1 As Required Staff Station 8.c.1.a As Required Equipment Back Box(s) 8.c.2 As Required Duty Station 8.c.2.a As Required Equipment Back Box(s) 8.c.3 As Required Patient Station(s) 8.c.3.a As Required Equipment Back Box(s)\ 8.c.4 As Required Security Room(s) 8.c.4.a As Required Security Station(s) 8.c.4.b As Required Equipment Back Box(s)\ 8.c.4.c As Required Overhead Speaker/Microphone 8.c.4.d As Required Equipment Back Box(s)\ 8.c.4.e As Required TV Surveillance System 8.c.4.f As Required Equipment Back Box(s)\ 8.c.4.g As Required TV Interconnection Cables 8.c.4.h As Required Audio Interconnection Cables 8.c.5 As Required Emergency Station(s) 8.c.5.a As Required Equipment Back Box(s) 8.c.5.b As Required Toilet Emergency Station
(waterproof) 8.c.5.c As Required Shower Emergency Station
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 26
(waterproof) 8.c.5.d As Required Lavatory Emergency Station
(waterproof) 8.c.6 As Required Room Dome Light 8.c.7 As Required Other Dome Light(s) 8.c.7.a As Required Equipment Back Box(s) 8.c.7.b As Required Corridor Dome Light 8.c.7.c As Required Intersectional Dome Light 8.c.8 As Required System Cable(s) 8.c.8.a As Required Coaxial 8.c.8.b As Required System Pin 8.c.8.c As Required Audio 8.c.8.d As Required Control 8.c.8.e As Required Video 8.c.9 As Required System Connector(s) 8.c.9.a As Required Coaxial 8.c.9.b As Required System Pin 8.c.9.c As Required Audio 8.c.9.d As Required Control 8.c.9.e As Required Video 8.c.9.f As Required Wire Management Required as described herein
10. On Hand Spares Provide a separate system spares list as indicated in each equipment description.
B. Telecommunications Room(s) (TR):
1. Locate the Nurse Call and/or Code Blue floor distribution equipment
0 by system design and OEM direction. Provide secured and lockable cabinet/rack(s) 0.
2. Head-End Equipment:
a. Provide all required power supplies, communications hubs, network switches, intelligent controllers and other devices necessary to form a complete system. Head-end components may be rack mounted or wall mounted in an enclosed metal enclosure.
b. Provide the head end equipment in the closest Telecommunications
Room where the System is installed.
c. Provide the System UPS inside the cabinet or in a separate cabinet adjacent to the head end cabinet that shall maintain a minimum of 30 minute battery back-up to all system components.
d. Equipment Cabinet: Comply with TIA/EIA-310-D. Lockable, ventilated metal cabinet houses terminal strips, power supplies, amplifiers, system volume control, and other switching and control devices required for conversation channels and control
CBLH PRJOECT NO. 18111
SITE PREP FOR PET/CT REPLACEMENT – DAYTON VA MEDICAL CENTER – BID AND
CONSTRUCTION(REVISED)
27 52 23 - 27 functions. See Paragraph 2.5.E for the Cabinet’s minimum internal items that are in addition to the installed System equipment.
C. Call Initiation, Annunciation and Response:
1. Light and Tones:
a Calls may be initiated through:
1) Staff station.
2) Code Blue station.
3) Toilet Emergency Station pull cord / push button.
4) Shower Emergency Station pull cord.
b Once a call is initiated, it must be annunciated at the following locations:
1) The Corridor, Intersectional and Room dome…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .