18111 - DVAMC PETCTPart-5.pdf

PDF 9 MB Posted

Attached to
Y1DA--552-CSI-162: Site Prep for PET CT Federal contract opportunity
Solicitation number
36C25021B0001
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This is a presolicitation notice for site preparation services for a PET-CT replacement project at a VA medical center. The Department of Veterans Affairs seeks to completely prepare the site, including demolishing existing structures and furnishing labor, materials, and work. The project value is between $1-5 million. The solicitation will be issued as a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. Interested parties must register at SAM.gov to receive the solicitation documents, which will be posted on November 9th with proposals due approximately 30 days later. The work must be completed within 245 calendar days of notice to proceed. Performance and payment bonds will be required.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--552-CSI-162: Site Prep for PET CT, newest first.
File Type Posted
36C25021B0001 A00007.pdf PDF
36C25021B0001 A00006.pdf PDF
JA - GOJO toilet accessories 2-18-2021_Redacted (1).pdf PDF
Bid Opening Instructions.pdf PDF
36C25021B0001 A00004.docx DOCX document
JA - Tork toilet accessories 2-18-2021_Redacted.pdf PDF
Pre-Bid RFI Responses Add No 2.pdf PDF
image001 (3).png PNG image
275223 - Nurse Call and Code Blue Systems - Add 2 (1).pdf PDF
G100 - Cover Sheet - Add 2 (1).pdf PDF
2019-1206_C301 (DETLS) (1).pdf PDF
2019-1206_C300 (DETLS) (1).pdf PDF
36C25021B0001 A00005 (1).pdf PDF
CBLH Addendum 1 Narrative.pdf PDF
102800ToiletAccessoriesADDNo1.pdf PDF
18111DVAMCPETCTGeotechReport.pdf PDF
18111DVAMCPETCTGeotechAddendumNo1.pdf PDF
36C25021B0001A00003.docx DOCX document
090600ScheduleofFinishesAddNo1.pdf PDF
EL2.3+Add+1.pdf PDF
EL3.4+Add+1+.pdf PDF
AS400EXTERIORELEVATIONSADDNo1.pdf PDF
230711HVACandBoilerPlantInsulationAddNo1.pdf PDF
EL4.3+Add+1.pdf PDF
EL2.0+Add+1.pdf PDF
BidOpeningInstructions.docx DOCX document
Pre-BidRFIResponsesAddNo2-19-2021.pdf PDF
Nu.+12+-+Site+Plan+Add+No+1.pdf PDF
AS522DETAILSADDNo1.pdf PDF
EL0.2+Add+1.pdf PDF
552-CSI-162 Site Visit Sign In.pdf PDF
36C25021B0001 A00002.docx DOCX document
Bid Opening Instructions.docx DOCX document
Site Visit Sign-In Sheet .xlsx XLSX spreadsheet
36C25021B0001 A00001.docx DOCX document
Valcom - ja_Redacted.pdf PDF
Masonry Veneer-JA_Redacted.pdf PDF
Fire Alarm-ja_Redacted.pdf PDF
Corbin Russwin Locksets-ja_Redacted.pdf PDF
18111 - DVAMC PETCTPart-4.pdf PDF
18111 - DVAMC PETCTPart-1.pdf PDF
Chicago Faucets-ja_Redacted.pdf PDF
18111 - DVAMC PETCTPart-2.pdf PDF
18111 - DVAMC PETCT PM VOL 1 of 2.pdf PDF
36C25021B0001_1.docx DOCX document
Wage Determination.pdf PDF
18111 - DVAMC PETCTPart-3.pdf PDF
Patient Lifts-ja_Redacted.pdf PDF
Beldon - Homestead - masonry brick-ja_Redacted.pdf PDF
18111 - DVAMC PETCT PM VOL 2 of 2.pdf PDF
Show all 50

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N.1

1.7

2.4

2.9

2.5

1" MV

1/2" MA

1/2" O

1/2" O

1/2" O

PLAN NOTES

A. SEE SHEET PL0.1 FOR GENERAL NOTES, SYMBOL LEGEND AND SCHEDULES

B. SEE SHEET PL3.1 FOR DETAILS.

C. EXISTING PIPING AND EQUIPMENT SHOWN WITH LIGHT LINES.

D. NEW PIPING AND EQUIPMENT SHOWN WITH DARK LINES.

E. COORDINATE WITH OWNER 2 WEEKS PRIOR TO TYING INTO EXISTING MEDICAL GAS PIPING.

CODED NOTES

1. 1/2" O, 1" MV AND 1/2" MA PIPING UP.

2. 1" MV PIPING. TIE INTO EXSTING MV PIPING MAIN AT POINT INDICATED. INSTALL SHUT-OFF

VALVE AT TIE IN LOCATION.

3. EXISTING MEDICAL VACUUM SYSTEM.

4. 1/2" MA PIPING. TIE INTO EXSTING MA PIPING MAIN AT POINT INDICATED. INSTALL SHUT-OFF

VALVE AT TIE IN LOCATION.

5. EXSTING MEDICAL AIR SYSTEM

6. 1/2" O PIPING. TIE INTO EXSTING O PIPING MAIN AT POINT INDICATED. INSTALL SHUT-OFF

VALVE AT TIE IN LOCATION.

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

R EG I ST E RE

D

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C :\U se rs

\J Bi lin sk i\D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ jb ilin sk i@ sb m ce

.c om

.rv t

9/

/2

7:

:4

AM

PL2.3

NEW WORK - BASEMENT FLOOR

PLAN - MED GAS (PHASE 2)

SITE PREP FOR PET/CT

REPLACEMENT

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020 Checker Author

BID AND CONSTRUCTION

(REVISED)18111

09/16/2020

1/8" = 1'-0"

NEW WORK - BASEMENT FLOOR PLAN - MED GAS (PHASE 2)

Revisions: Date:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

BID AND CONSTRUCTION (REVISED) 07-13-2020

SOLE SOURCE REVISION 09-16-2020

SRQPON.1

1.7

2.4

2.9

2.5

A103

A104

A105

A106

A109

A107

A108 A110

A102

A101

E103

A111

A112

A113

E102

E101

P-418

CODED NOTES

1. RELOCATED WATER CLOSET.

2. RELOCATED LAV/SINK.

3. TIE NEW 4" SAN PIPING INTO EXISTING SAN PIPING IN CHASE AND EXTEND TO RELOCATED

WATER CLOSET AND LAV IN CHASE.

4. 2" VENT PIPING. TIE INTO EXISTING 2" VENT PIPING AT POINT INDICATED.

PLAN NOTES

A. SEE SHEET PL0.1 FOR GENERAL NOTES, SYMBOL LEGEND AND SCHEDULES

B. SEE SHEET PL3.1 FOR DETAILS.

C. EXISTING PIPING AND EQUIPMENT SHOWN WITH LIGHT LINES.

D. NEW PIPING AND EQUIPMENT SHOWN WITH DARK LINES.

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

R EG I ST E RE

D

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C :\U se rs

\J Bi lin sk i\D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ jb ilin sk i@ sb m ce

.c om

.rv t

9/

/2

7:

:4

AM

PL2.4

NEW WORK - FIRST FLOOR PLAN -

SANITARY/VENT (PHASE 2)

SITE PREP FOR PET/CT

REPLACEMENT

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020 CJS Author

BID AND CONSTRUCTION

(REVISED)18111

09/16/2020

1/4" = 1'-0"

NEW WORK - FIRST FLOOR PLAN - SANITARY/VENT (PHASE 2)

ROOM LEGEND

Number Name

14 EXISTING ELECTRICAL ROOM

15 EXISTING STORAGE

16 EXISTING CONFERENCE ROOM

17 EXISTING OFFICE

18 EXISTING STORAGE

20 EXISTING STAIR

21 EXISTING STORAGE

22 EXISTING VESTIBULE

24 EXISTING CORRIDOR

25 EXISTING CORRIDOR

A101 CONTROL ROOM

A102 EXAM ROOM

A103 EQUIPMENT ROOM

A104 PATIENT PREP

A105 TOILET ROOM

A106 TOILET ROOM

A107 PATIENT PREP

A108 PATIENT PREP

A109 CORRIDOR

A110 CORRIDOR

A111 CORRIDOR

A112 CORRIDOR

A113 TOILET ROOM

E101 EXISTING PATIENT PREP

E102 EXISTING PATIENT PREP

E103 EXISTING EXAM ROOM

Revisions: Date:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

SRQPON.1

1.7

2.4

2.9

2.5

A103

A104

A105

A106

A109

A107

A108 A110

A102

A101

E103

A111

A112

A113

E102

E101

1/2" O

1" MV

1/2" MA

1/2" O

1" MV

1/2" MA

CODED NOTES

1. 1-1/2" DCW PIPING AND 1/2" DHW PIPING. TIE INTO EXISTING DCW AND DHW PIPING AT POINTS

INDICATED.

2. EXTEND 1-1/4" DCW PIPING DOWN IN WALL TO WATER CLOSET.

3. 1/2" DCW AND 1/2" DHW PIPING DOWN TO LAV/SINK.

4. SHOCK STOP, SEE SCHEDULE.

5. RELOCATED WATER CLOSET.

6. RELOCATED LAV/SINK.

7. CAP 3/4" MV AND 1/2" MA PIPING AT POINTS INDICATED.

8. 1/2" O, 1" MV AND 1/2" MA PIPING. TIE INTO EXISTING 1/2" O, 1" MV AND 1/2" MA PIPING AT

POINTS INDICATED.

9. INSTALL 1/2" O, 1" MV AND 1/2" MA PIPING DOWN IN WALL TO ZONE VALVE BOX, ME-1. INSTALL

BOX ON CORRIDOR SIDE OF WALL AND LABEL "PET SCANNING", INCLUDE ROOM NUMBERS IN

LABELING AND COORDINATE ROOM NUMBERS WITH VA.

10. AREA ALARM PANEL, ME-2 IN WALL, LABEL "PET SCANNING", INCLUDE ROOM NUMBERS IN

LABELING AND COORDINATE ROOM NUMBERS WITH VA.

11. 1/2" O, 1" MV AND 1/2" MA PIPING DOWN TO FLOOR BELOW.

12. TIE NEW 1/2" O PIPING INTO EXISTING 1/2" O PIPING AT POINT INDICATED.

PLAN NOTES

A. SEE SHEET PL0.1 FOR GENERAL NOTES, SYMBOL LEGEND AND SCHEDULES

B. SEE SHEET PL3.1 FOR DETAILS.

C. EXISTING PIPING AND EQUIPMENT SHOWN WITH LIGHT LINES.

D. NEW PIPING AND EQUIPMENT SHOWN WITH DARK LINES.

E. RELABEL EXSTING ZONE VALVE BOX AND ALARM PANEL TO REMOVE EXISTING ROOMS.

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

R EG I ST E RE

D

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C :\U se rs

\J Bi lin sk i\D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ jb ilin sk i@ sb m ce

.c om

.rv t

9/

/2

7:

:5

AM

PL2.5

NEW WORK - FIRST FLOOR PLAN -

WATER AND MED GAS (PHASE 2)

SITE PREP FOR PET/CT

REPLACEMENT

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020 CJS Author

BID AND CONSTRUCTION

(REVISED)18111

09/16/2020

1/4" = 1'-0"

NEW WORK - FIRST FLOOR PLAN - WATER AND MED GAS (PHASE 2)

ROOM LEGEND

Number Name

14 EXISTING ELECTRICAL ROOM

15 EXISTING STORAGE

16 EXISTING CONFERENCE ROOM

17 EXISTING OFFICE

18 EXISTING STORAGE

20 EXISTING STAIR

21 EXISTING STORAGE

22 EXISTING VESTIBULE

24 EXISTING CORRIDOR

25 EXISTING CORRIDOR

A101 CONTROL ROOM

A102 EXAM ROOM

A103 EQUIPMENT ROOM

A104 PATIENT PREP

A105 TOILET ROOM

A106 TOILET ROOM

A107 PATIENT PREP

A108 PATIENT PREP

A109 CORRIDOR

A110 CORRIDOR

A111 CORRIDOR

A112 CORRIDOR

A113 TOILET ROOM

E101 EXISTING PATIENT PREP

E102 EXISTING PATIENT PREP

E103 EXISTING EXAM ROOM

Revisions: Date:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

WALL SECTION

FLOOR SECTION

FURNISH AND INSTALL

FIRESTOP MATERIALS IN

ACCORDANCE WITH

APPROPRIATE U.L. SYSTEMS

TO MAINTAIN FIRE RESISTANCE

RATING

PIPE SLEEVE

DAMMING MATERIAL

(PER U.L. TESTED

SYSTEM DESIGN)

FLOOR SLAB; SEE

ARCHITECTURAL DRAWINGS

FOR FLOOR CONSTRUCTION

AND FIRE RATING

PIPE INSULATION

(WHERE SPECIFIED)

PENETRATING COMPONENT

FURNISH AND INSTALL FIRESTOP

MATERIALS IN ACCORDANCE WITH

APPROPRIATE U.L. SYSTEMS TO

MAINTAIN FIRE RESISTANCE RATING

PIPE SLEEVE (SLEEVE TO

EXTEND 2" ABOVE FLOOR

IN MECHANICAL EQUIPMENT

ROOMS.)

SEAL JOINT BETWEEN SLEEVE

AND FLOOR SLAB WITH MIN. 1/2"

BEAD FIRESTOP CAULK

SEE ARCHITECTURAL

DRAWINGS FOR WALL

CONSTRUCTION AND FIRE

RATING

PENETRATING COMPONENT

PIPE INSULATION

(WHERE SPECIFIED)

NOTES:

1. WHERE PIPES, DUCTS AND OTHER COMPONENTS PASS THROUGH FIRE OR SMOKE RATED WALLS OR FLOORS, PROVIDE NON-ASBESTOS SEAL ASSEMBLIES CLASSIFIED BY U.L. TO PROVIDE FIRE BARRIERS EQUAL TO OR GREATER THAN THE TIME RATING OF THE CONSTRUCTION BEING PENETRATED, WITH APPROPRIATE MATERIALS AND SYSTEMS THAT COMPLY WITH APPLICABLE CODES AND THAT HAVE BEEN

TESTED IN ACCORDANCE WITH U.L. 1479 OR ASTM E814.

2. GROUT, MORTAR OR GYPSUM BASED PRODUCTS SHALL NOT BE INSTALLED IN LIEU OF FIRESTOPPING

MATERIALS AND U.L. SYSTEMS.

3. FOR SLEEVED PENETRATIONS, FIRESTOP ANNULAR SPACE, IF ANY, BETWEEN SLEEVE AND ADJACENT

CONSTRUCTION TO MEET U.L. SYSTEM REQUIREMENTS. SEE NOTE 2 ABOVE.

4. THIS CONTRACTOR SHALL FIRESTOP ALL MISCELLANEOUS OPENINGS IN FIRE-RATED CONSTRUCTION

RESULTING FROM HIS WORK.

5. CONTRACTOR SHALL PROVIDE SUBMITTAL DRAWINGS TO ARCHITECT, INCLUDING U.L. RATED SYSTEM

NUMBER AND DETAIL FOR EACH TYPE OF PENETRATION AND CONFIGURATION.

6. THE FIRESTOPPING SYSTEMS ARE TO BE INSTALLED BY EXPERIENCED, MANUFACTURER TRAINED, AND

UL CERTIFIED OR FM CERTIFIED PERSONNEL.

7. ALL FIRESTOPPING MATERIAL IS TO BE PROVIDED FROM A SINGLE MANUFACTURER FOR ALL

APPLICATIONS.

8. CONTRACTOR SHALL CONSULT MANUFACTURER'S TECHNICAL EXPERTS FOR ASSISTANCE IN SELECTING

APPROPRIATE FIRESTOPPING SYSTEM FOR EACH APPLICATION.

THROUGH FIRE-RATED CONSTRUCTIONS

N.T.S.

FIRESTOPPING DETAIL FOR PENETRATIONS

CLEVIS HANGER PIPE SUPPORT

N.T.S.

NOTE:

REFER TO HANGER SPECIFICATIONS

FOR ADDITIONAL REQUIREMENTS.

PIPE ℄

TYPICAL FOR

UN-INSULATED PIPE

TYPICAL FOR

INSULATED PIPE

STRUCTURAL FRAMING

NOTE: SUPPLY ADDITIONAL

SUPPORT STEEL AS

REQUIRED

BEAM CLAMP

HEX NUTS (4 REQUIRED)

THREADED ROD (SEE

SPECIFICATIONS FOR DIAMETER)

ADJUSTABLE CLEVIS HANGER

PIPE WITH INSULATION AND

JACKET (AS APPLICABLE).

SEE SPECIFICATIONS FOR

REQUIREMENTS.

180 DEG. INSULATION PROTECTION

SHIELD, 14 GA., GALVANIZED BY 18"

LONG FOR PIPING 8" AND OVER.

SEE SPECIFICATIONS FOR 6" AND

UNDER.

SUPPORT BLOCK (SEE

SPECIFICATIONS)

BUILDING DRAIN CLEANOUT DETAIL

N.T.S.

"Y" BRANCH

FINISHED GRADE

ADJUSTABLE HOUSING

6" C.I. ENCASED IN IN CONCRETE

6" THICK ON EACH SIDE OF PIPE

6" C.I.

P.C. TO COORDINATE WITH ROOM FINISH SCHEDULE

AND PLUMBING FIXTURE SCHEDULE, PROVIDE

CARPET MARKERS WHERE APPLICABLE.

COORDINATE LOCATIONS WITH CARPET INSTALLER.

P.C. TO FURNISH COVER LIDS TO MATCH TYPE OF

FLOOR FINISH.

M A

X

VENT PIPE CURB DETAIL

N.T.S.

STORM COLLAR CLAMP

TO PIPE

SILICONE CAULK

ROOF LINE

ROOF INSULATION

ROOFING, MEMBRANE, RUN

UP UNDER COVER (BY G.C.)

PIPE - SEE PLANS FOR QUANTITY

SIZES, ARRANGEMENT, AND

CONTINUATION

ANCHOR TO EXISTING ROOF

DECK AS REQUIRED

"PATE" TYPE PCA-5

CURB ASSEMBLY

GALVANIZED STEEL COVER

SECURE TO CURB

STAINLESS STEEL CLAMP

VENT TERMINATION HEIGHT IN

ACCORDANCE WITH LOCAL

JURISDICTION.

8 "

10 3/4"

FAUCET

LAMINAR FLOW

CONTROL DEVICE

LOOSE KEY

ANGLE STOP

OFFSET WASTE

TRAP PARALLEL TO

WALL

ESCUTCHEON

FINISHED FLOOR

TYPICAL WHEELCHAIR LAVATORY DETAIL

N.T.S.

COLUMN OR WALL

DOWNSPOUT

INSULATE ABOVE CEILING AND

TIGHT TO UNDERSIDE OF ROOF

DRAIN, NO EXPOSED PIPING OR

DRAIN.

ROOF DECK

ROOF DRAIN, SEE DETAIL

CEILING

CLEANOUT TEE WITH

BRONZE PLUG

FLOOR

LONG SWEEP ELBOW

WHERE POSSIBLE

COLUMN FOOTING

TYPICAL ROOF DRAIN AND DOWNSPOUT DETAIL

N.T.S.

CHASE WALL

STORM DRAIN

DOWNSPOUT NOZZLE

WITH SCREEN.

MOUNT 6" ABOVE

FINISHED GRADE.

COORDINATE INSTALLATION

OF NOZZLE WITH WALL

WORK. GROUT ALL OPEN

AREAS AROUND EXTERIOR

FLANGE. SECURE TO WALL

WITH STAINLESS STEEL

FASTENERS.

PLUMBING CHASE

EXTERIOR WALL

GRADE

CONCRETE SPLASH BLOCK.CAULK REMAINING AREA

WEATHERTIGHT

INSTALL THROUGH

SMOOTH BORE HOLE BY

CORE DRILLING

EXTERIOR BLOCK

DOWNSPOUT NOZZLE DETAIL

N.T.S.

METAL DECK

GRAVEL

INSULATION

ROOF MEMBRANE FLASHING AND COUNTER

FLASHING BY ROOFING

CONTRACTOR . P.C. TO

COORDINATE AND SECURE

ROOF MEMBRANE TO ROOF

DRAIN.

UNDERDECK CLAMP

SEE DRAWINGS FOR SIZES

TYPICAL ROOF DRAIN DETAIL

N.T.S.

INSULATE ALL VERTICAL

AND HORIZONTAL

SECTIONS OF DOWNSPOUT

TYPICAL OVERFLOW ROOF DRAIN DETAIL

N.T.S.

OVERFLOW DAM

FLASHING AND COUNTER

FLASHING BY ROOFING

CONTRACTOR. P.C. TO

COORDINATE AND SECURE

ROOFING MEMBRANE TO

ROOF DRAIN.

P.C. TO INSTALL ALL

NECESSARY SUPPORT

BRACING PLATE AROUND

OPENING AS REQUIRED TO

INSTALL ROOF DRAIN.

UNDERDECK CLAMP

SEE DRAWINGS FOR SIZES

INSULATE ALL VERTICAL AND

HORIZONTAL SECTIONS OF

DOWNSPOUT, SEE DOWNSPOUT

DETAIL

CONCRETE DECK

ROOF MEMBRANE

INSULATION

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

R EG I ST E RE

D

E-62197

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C :\U se rs

\J Bi lin sk i\D oc um en ts \1

_M

EP

_C

EN

TR

AL

F

IL

E_ jb ilin sk i@ sb m ce

.c om

.rv t

9/

/2

7:

:5

AM

PL3.1

DETAILS - PLUMBING SITE PREP FOR PET/CT

REPLACEMENT

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020 CJS Author

BID AND CONSTRUCTION

(REVISED)18111

09/16/2020 Revisions: Date:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

OC1

S

S

S

OC

A

N SP

N T

NCPS

GFI

J

"T-X"

PAN. " "

PAN. " "

DIST. PAN.

A

A

FX

E

F

N

X

S

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

SYMBOL DESCRIPTIONSYMBOL DESCRIPTION

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

ABBREVIATION LEGEND

AFF ABOVE FINISHED FLOOR

"C" SUBSCRIPT "C" INDICATES DEVICE TO BE MOUNTED 8" ABOVE COUNTERTOP TO CENTERLINE.

CLG CEILING

DP DISTRIBUTION PANEL

CR CRITICAL BRANCH CIRCUIT

EC ELECTRICAL CONTRACTOR

EM EMERGENCY

GFI GROUND FAULT INTERRUPTER

LS LIFE SAFETY BRANCH CIRCUIT

MC MECHANICAL CONTRACTOR (HVAC)

NL NIGHT LIGHT

"R" SUBSCRIPT "R" INDICATES RED DEVICE CONNECTED TO EMERGENCY POWER.

"X" SUBSCRIPT "X" BY SYMBOL INDICATES EXISTING ITEM TO REMAIN.

DLM LIGHTING LEGEND

WATTSTOPPER #LMDC-100 DUAL-TECHNOLOGY CEILING MOUNT OCCUPANCY SENSOR.

FIRE ALARM LEGEND

MANUAL FIRE ALARM SENDING STATION. REFER TO SPECIFICATIONS FOR DETAILS. MOUNT AT 46" AFF

TO CENTERLINE UNLESS OTHERWISE NOTED.

FIRE ALARM SYSTEM AUTOMATIC DETECTOR. REFER TO SPECIFICATIONS FOR DETAILS. SUBSCRIPT INDICATES TYPE.

SMD - SMOKE DETECTOR, DUCT TYPE COMPLETE WITH SAMPLING TUBES AND REMOTE KEY TEST SWITCH INDICATOR LIGHT. INSTALL IN AIR HANDLING UNIT OR DUCT AS RECOMMENDED BY RESPECTIVE MANUFACTURER AND

COORDINATE INSTALLATION WITH MECHANICAL CONTRACTOR.

SMP - SMOKE DETECTOR, PHOTOELECTRIC TYPE, CEILING MOUNTED.

FIRE ALARM SYSTEM ALARM SIGNAL WITH STROBE LIGHT. XENON FLASH TUBE TYPE MINIMUM 15 CANDELA IN TOILET ROOMS AND 75 CANDELA IN ALL OTHER AREAS WITH A FLASH RATE OF 1 HZ. STROBES SHALL BE SYNCHRONIZED WHERE REQUIRED BY THE NATIONAL FIRE ALARM CODE (NFPA 72). REFER TO SPECIFICATIONS FOR DETAILS. MOUNT AT 82" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. SUBSCRIPT "V" INDICATES VISUAL ONLY ALARM SIGNAL.

LIGHTS/SWITCHES LEGEND

EXTRA HEAVY DUTY 20 AMP, SINGLE POLE SWITCH. HUBBELL #HBL1221LA. MOUNT AT 46" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, SWITCH TO BE RED IN COLOR HUBBELL

#HBL1221R.

EXTRA HEAVY DUTY 20 AMP, THREE-WAY SWITCH. HUBBELL #HBL1223LA. MOUNT AT 46" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, SWITCH TO BE COLORED RED AND TO BE SERVED

BY ESSENTIAL POWER.

SINGLE-LEVEL SWITCH TYPE OCCUPANCY SENSOR. REFER TO DETAIL FOR MORE INFORMATION. MOUNT

AT 46" AFF TO CENTERLINE UNLESS OTHERWISE NOTED.

LIGHTING CONTROL REFERENCE TAG

LED LIGHTING FIXTURES. REFER TO LIGHTING FIXTURE SCHEDULE FOR DETAILS.

CEILING OR WALL MOUNTED SINGLE FACE EXIT SIGN. SHADED AREA INDICATES LOCATION OF FACE(S).

ARROWS INDICATE CHEVRONS.

CEILING OR WALL MOUNTED DOUBLE FACE EXIT SIGN. SHADED AREA INDICATES LOCATION OF FACE(S).

ARROWS INDICATE CHEVRONS.

NURSE CALL LEGEND

NURSE CALL SYSTEM SINGLE PATIENT STATION. REFER TO DETAILS.

NURSE CALL SYSTEM TOILET STATION. MOUNT AT 48" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. REFER

TO DETAILS.

NURSE CALL POWER SUPPLY. REFER TO DETAILS.

NURSE CALL CORRIDOR DOME FOR SINGLE BED INSTALLATION. PROVIDE 4-11/16" SQUARE BOX WITH 2-GANG PLASTER RING MOUNTED IN THE ACCESSIBLE CEILING TILE ABOVE THE ROOM DOOR. REFER TO DRAWINGS

AND/OR SPECIFICATIONS FOR DETAILS. "Z" DESIGNATION INDICATES ZONE INDICATION.

POWER LEGEND

20 AMP, 125 VOLT, DUPLEX GROUNDING TYPE RECEPTACLE. HUBBELL #HBLB300I (HOSPITAL GRADE). PROVIDE TAMPER RESISTANT RECEPTACLES HUBBELL #BL8300-SGLA IN ALL PUBLIC ACCESSIBLE AREAS (I.E. PATIENT ROOMS, CORRIDORS, NURSES STATIONS, WAITING ROOMS, ETC.). SEE SPECIFICATIONS TO DETERMINE WHERE EACH TYPE IS REQUIRED. MOUNT AT 18" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT

"R" OCCURS, RECEPTACLE TO BE COLORED RED AND TO BE SERVED BY ESSENTIAL POWER.

20 AMP, 125 VOLT, DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE. HUBBELL #GFR8300HILA (HOSPITAL GRADE). PROVIDE TAMPER RESISTANT RECEPTACLES HUBBELL #HBL8300-SGLA IN IN ALL PUBLIC ACCESSIBLE AREAS (I.E. PATIENT ROOMS, CORRIDORS, NURSES STATIONS, WAITING ROOMS, ETC.). SEE SPECIFICATIONS TO DETERMINE WHERE EACH TYPE IS REQUIRED. MOUNT AT 18" AFG TO CENTERLINE UNLESS OTHERWISE NOTED.

WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED RED AND TO BE SERVED BY ESSENTIAL POWER.

TWO 20 AMP, 125 VOLT, DUPLEX GROUNDING TYPE RECEPTACLES. HUBBELL #HBL5362I (HOSPITAL GRADE).

PROVIDE TAMPER RESISTANT RECEPTACLES HUBBELL #HBL8300-SGLA IN ALL PUBLIC ACCESSIBLE AREAS (I.E.

PATIENT ROOMS, CORRIDORS, NURSES STATIONS, WAITING ROOMS, ETC.). SEE SPECIFICATIONS TO DETERMINE WHERE EACH TYPE IS REQUIRED. MOUNT IN COMMON BOX WITH COMMON PLATE AT 18" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED RED AND TO BE

SERVED BY ESSENTIAL POWER.

STANDARD STEEL JUNCTION BOX WITH COVER. LOCATE AND CONNECT AS DIRECTED. SUBSCRIPT INDICATES

EQUIPMENT SERVED.

TC - TEMPERATURE CONTROL

VAV - VAV TERMINAL UNIT

SEC - SECURITY

BL - BLANK

POINT OF CONNECTION TO ELECTRIFIED EQUIPMENT. VERIFY EXACT LOCATION WITH RESPECTIVE EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN. UNLESS NOTED OTHERWISE, REFER TO MECHANICAL EQUIPMENT SCHEDULE FOR

MORE INFORMATION.

FUSIBLE DISCONNECT SWITCH, HEAVY DUTY TYPE, (UNLESS NOTED OTHERWISE ON DRAWINGS) COMPLETE WITH FUSETRONS SIZED TO PROTECT MOTOR, EQUIPMENT OR CONDUCTORS (WHICHEVER IS APPLICABLE). SIZE, POLES, AND TYPE AS INDICATED. HORSEPOWER RATED, QUICK-MAKE, QUICK-BREAK.

PUSH BUTTON. REFER TO DRAWINGS AND/OR SPECIFICATIONS FOR DETAILS.

TRANSFORMER.

208/120V,3∅,4W PANELBOARD. REFER TO PANELBOARD SCHEDULE AND/OR SPECIFICATIONS FOR DETAILS.

480/277V,3∅,4W PANELBOARD. REFER TO PANELBOARD SCHEDULE AND/OR SPECIFICATIONS FOR DETAILS.

DISTRIBUTION PANEL.

GENERAL LEGEND

EXPOSED BRANCH CIRCUIT HOMERUN. FOR NORMAL BRANCH CIRCUIT WIRING, CONTRACTOR MAY COMBINE UP TO THREE HOMERUNS IN ONE RACEWAY ON A WYE SYSTEM AND TWO HOMERUNS IN ONE RACEWAY ON A DELTA SYSTEM. QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTORS UNLESS NOTED OTHERWISE. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN

CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

CONCEALED BRANCH CIRCUIT HOMERUN. FOR NORMAL BRANCH CIRCUIT WIRING, CONTRACTOR MAY COMBINE UP TO THREE HOMERUNS IN ONE RACEWAY ON A WYE SYSTEM AND TWO HOMERUNS IN ONE RACEWAY ON A DELTA SYSTEM. QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTORS UNLESS NOTED OTHERWISE. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN

CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

FLEXIBLE METAL CONDUIT OR LIQUIDTIGHT FLEXIBLE METAL CONDUIT (REFER TO SPECIFICATIONS) AND WIRING.

QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTOR UNLESS OTHERWISE NOTED. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE

SHARED BETWEEN CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

RACEWAY AND CONDUCTORS CONCEALED ABOVE CEILING OR IN WALL AT ELECTRICAL CONTRACTOR'S OPTION.

QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTOR UNLESS OTHERWISE NOTED. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE

SHARED BETWEEN CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

RACEWAY AND CONDUCTORS RUN EXPOSED ON CEILINGS OR WALLS. QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTOR UNLESS OTHERWISE NOTED. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN CIRCUITS. REFER TO

SPECIFICATIONS FOR RACEWAY TYPE.

EMERGENCY POWER SYSTEM CONDUIT AND WIRING. QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. # 12 AWG MINIMUM SIZE CONDUCTOR UNLESS OTHERWISE NOTED. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR.

NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY

TYPE.

FIRE ALARM SYSTEM CONDUIT AND WIRING. REFER TO FIRE ALARM CABLE LEGEND FOR WIRE AND CABLE

DETAILS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

NURSES CALL SYSTEM CONDUIT AND WIRING. REFER TO NURSE CALL SYSTEM CABLE LEGEND FOR WIRE AND

CABLE DETAILS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

EXISTING RACEWAY OR BRANCH CIRCUIT.

BRANCH CIRCUIT UNDER FLOOR SLAB, UNDERGROUND OR ABOVE ACCESSIBLE CEILING OF FLOOR BELOW.

QUANTITY OF MARKS INDICATES NUMBER OF CONDUCTORS. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN CIRCUITS. ALL RACEWAYS TO

CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTORS.

ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS TO BE REMOVED (UNLESS OTHERWISE NOTED).

ELECTRICAL GENERAL NOTES

1. THE GENERAL NOTES LISTED HERE APPLY TO ALL ELECTRICAL

DRAWINGS IN ADDITION TO ANY ADDITIONAL DRAWING NOTES ON THE

INDIVIDUAL DRAWINGS.

2. ALL EXISTING ELECTRICAL DEVICES WITHIN HATCHED AREAS TO

REMAIN IN OPERATION UNLESS SHOWN OTHERWISE. REFEED ANY

ITEM WHOSE WIRING IS INTERRUPTED DUE TO WORK IN ADJACENT

AREAS.

3. DARK, DASHED ITEMS INDICATE ELECTRICAL EQUIPMENT, DEVICES,

AND/OR LIGHTING TO BE REMOVED UNDER THE DEMOLITION PHASE OF

PROJECT.

4. SEE SPECIFICATIONS FOR GENERAL CUTTING AND PATCHING

REQUIREMENTS REQUIRED DURING DEMOLITION AND NEW

CONSTRUCTION PHASES. REFER TO DRAWINGS FOR MORE SPECIFIC

REQUIREMENTS.

5. SEE SPECIFICATIONS FOR SALVAGE RIGHTS TO ANY EQUIPMENT

OR MATERIALS BEING REMOVED.

6. REMOVE ALL HANGERS AND SUPPORTS SERVING CONDUIT AND

WIRE TO BE DEMOLISHED. PROVIDE AND/OR ADJUST EXISTING

HANGERS TO SUPPORT ANY REMAINING CONDUIT AND WIRE, OR

EQUIPMENT ADJACENT, TO REMAIN.

7. REMOVE ALL EXISTING WIRE FROM CONDUITS TO BE ABANDONED.

REFER TO SPECIFICATIONS FOR REQUIREMENTS REGARDING

ABANDONED CONDUITS.

8. DARKENED WALLS INDICATE NEW WALL CONSTRUCTION.

9. EC SHALL REMOVE AND REINSTALL ALL CEILING MATERIAL AS

REQUIRED FOR ELECTRICAL WORK SHOWN. REPLACE ALL MATERIAL

DAMAGED BY THIS CONTRACTOR.

10. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR

SPECIFIC INSTRUCTIONAL NOTES.

11. FIELD VERIFY EXISTING CONDITIONS.

12. COORDINATE ELECTRICAL WORK WITH ALL CONTRACTORS ON

SITE (GENERAL TRADES, PLUMBING, FIRE PROTECTION, HVAC, ETC)

PRIOR TO COMMENCEMENT OF DEMOLITION/CONSTRUCTION WORK.

13. THE ELECTRICAL DESIGN DRAWINGS ARE DIAGRAMMATIC AND ARE

NOT INTENDED TO SHOW EXACT LOCATION OF EQUIPMENT, LIGHTING,

AND DEVICES UNLESS DIMENSIONS ARE GIVEN FOR CLEARANCES,

ETC. LIGHTING, DEVICES AND ELECTRICAL EQUIPMENT ARE TO BE

INSTALLED ALONG THE GENERAL PLANS SHOWN ON THE DRAWINGS,

BUT KEEPING IN MIND ACTUAL BUILDING CONDITIONS WHICH MUST BE

CONFIRMED WITH-IN THE ACTUAL WORK AREA. CONTRACTORS, IN

THEIR BIDS, ARE REQUIRED TO INCLUDE ALL LABOR AND MATERIALS

AND OTHER RELATED WORK NECESSARY TO PROVIDE MINOR

OFFSETS IN ELECTRICAL INSTALLATION TO AVOID CONFLICT WITH

OTHER WORK ON THIS PROJECT, OR AS REQUIRED IN ORDER TO

OBTAIN MAXIMUM HEAD ROOM OR EQUIPMENT ACCESS IN SPACES.

14. EC TO VERIFY ALL UNDERCABINET LIGHTING LCOATIONS WITH

THOSE SHOWN ON THE ARCHITECTURAL ELEVATION AND REPORT ANY

CONFLICTS PRIOR TO BID. ANY UNDERCABINET LIGHTING INDICATED

ON THE ARCHITECTURAL ELEVATIONS THAT DOES NOT APPEAR ON

THE ELECTRICAL DOCUMENTS SHALL BE PROVIDED BY THE EC.

15. MAINTAIN REQUIRED RIGGING ACCESS CLEARANCES. COORDINATE

CLEARANCE REQUIREMENTS WITH OTHER TRADES.

16. E.C. IS TO COORDINATE ALL MASONRY PENETRATION LOCATIONS

AND SIZES WITH G.C.

17. AN ATTEMPT HAS BEEN MADE TO SHOW ALL ELECTRICAL ITEMS

TO REMAIN OR BE REMOVED. EC SHALL FIELD VERIFY EXISTING

CONDITIONS AND REMOVE AND/OR RELOCATE ANY ITEM WHICH

INTERFERES WITH NEW CONSTRUCTION.

18. POWER AND TELECOM RISER PULL BOXES MAY NOT BE SHOWN.

PROVIDE PULL BOXES AT LOCATIONS REQUIRED. IN NO CASE SHALL A

FEEDER CONDUIT HAVE BENDS OF MORE THEN 270° WITHOUT THE

INSTALLATION OF A PULL BOX.

19. PROVIDE FIRESEALING OF ALL OPENINGS THROUGH FIRE RATED

WALLS AND ASSEMBLIES. SEE DETAIL SHEETS AND SPECIFICATIONS

FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

20. EC TO COORDINATE ELECTRICAL AND TELECOMMUNICATIONS

DEVICE LOCATIONS WITH ARCHITECTURAL ELEVATIONS PRIOR TO

ROUGH-IN. IF ELEVATIONS ARE NOT PROVIDED ON DOCUMENTS, EC

SHALL COORDINATE LOCATIONS AND MOUNTING HEIGHTS WITH

ARCHITECT. DEVICE REQUIRED TO BE RELOCATED DUE TO LACK OF

COORDINATION WILL BE DONE AT THE CONTRACTOR'S EXPENSE.

S

OCD

DUAL-TECHNOLOGY OCCUPANCY SENSOR SWITCH. REFER TO DETAIL FOR MORE INFORMATION. MOUNT

AT 46" AFF TO CENTERLINE UNLESS OTHERWISE NOTED.

WP/GFI

20 AMP, 125 VOLT, TAMPER RESISTANT DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE. HUBBELL #GFTR201 (HOSPITAL GRADE) WITH WEATHERPROOF "IN-USE" COVERPLATE MOUNT VERTICALLY AT 24" AFG TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED RED

AND TO BE SERVED BY ESSENTIAL POWER.

FIRE ALARM SYSTEM REMOTE ANNUCIATOR PANEL. REFER TO SPECIFICATIONS FOR DETAILS.

FAAP

S M

MANUAL MOTOR STARTER WITH NEON PILOT LIGHT. ALLEN-BRADLEY #600TQX216. MOUNT AT 46" AFF

TO CENTERLINE UNLESS OTHERWISE NOTED.

I M FIRE ALARM SYSTEM ZONE ADDRESSABLE MODULE (INDIVIDUAL TYPE). REFER TO SPECIFICATIONS FOR DETAILS.

TS

J

SPRINKLER SYSTEM TAMPER SWITCH. FURNISHED AND INSTALLED BY FIRE PROTECTION CONTRACTOR, CONNECTED TO FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR. VERIFY LOCATION WITH EQUIPMENT

SUPPLIER PRIOR TO ROUGH-IN.

PP - POWER PACK

LTG - LIGHTING

LTG/EM - EMERGENCY LIGHTING

20 AMP, 125 VOLT, DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE. HUBBELL #GFTWRST83I (HOSPITAL GRADE) OR HUBBELL #GFTWRST20I (SPECIFICATION GRADE) SEE SPECIFICATIONS TO DETERMINE WHERE EACH TYPE IS REQUIRED. PROVIDE WEATHERPROOF "IN-USE" COVERPLATE. SURFACE MOUNT AT 18" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED RED

AND TO BE SERVED BY ESSENTIAL POWER.

WP/GFI

D1 - DOOR DETAIL

D2 - DOOR DETAIL

DIMMER SWITCH. SEE DETAIL FOR MORE INFORMATION. MOUNT AT 46" AFF TO CENTERLINE UNLESS

OTHERWISE NOTED.

DIMMER SWITCH. SEE DETAIL FOR MORE INFORMATION. MOUNT AT 46" AFF TO CENTERLINE UNLESS OTHERWISE

NOTED.

X

WAP

SYMBOL DESCRIPTION

SYSTEMS LEGEND

TELECOM OUTLET TO BE REMOVED DURING DEMOLITION PHASE. REMOVE FACE PLATE, JACK MODULES, AND

ASSOCIATED CABLES BACK TO TERMINATION PANEL IN TELECOM ROOM.

EXISTING TELECOM OUTLET TO REMAIN THROUGH PHASE. PROTECT JACK MODULES FROM CONSTRUCTION DUST

AND DEBRIS.

FLUSH TELECOM OUTLET. USE 5" SQUARE X 2-7/8" DEEP BACK BOX WITH REDUCER RING. REFER TO TELECOM OUTLET ROUGH-IN DETAIL. REDUCER RING SIZE, BOX MOUNTING HEIGHT, AND CONDUIT SIZE PER SUBSCRIPT AS

NOTED BELOW:

SUBSCRIPT #1 GANG/MOUNTING HEIGHT CONDUIT

W 1-GANG/48" AFF 1"C

2D THRU 4D 2-GANG/18" AFF 1-1/4"C

TV 1-GANG/ADJACENT TO TV POWER 1-1/4"C

SUBSCRIPT #2 (WHERE APPLICABLE):

##" OUTLET HEIGHT AFF TO CENTERLINE IN INCHES. THIS SUPERSEDES HEIGHT CITED FOR SUBSCRIPT #1

C INDICATES OUTLET TO BE LOCATED AT 8" ABOVE COUNTERTOP HEIGHT.

WIRELESS ACCESS POINT TELECOM OUTLET. THIS OUTLET TO "FLOAT" ABOVE CEILING. PROVIDE CONDUIT ONLY AS

NOTED ON FLOOR PLAN.

SUBSCRIPT #1

SUBSCRIPT #2

REFER TO TELECOM DETAILS FOR CABLING REQUIREMENTS PER SUBSCRIPTS

S CEILING SPEAKER (VALCOM V-1020C) WITH BACKCAN/BRIDGE (VALCOM V-9916M). CONNECT TO TELECOM ROOM WITH HOME-RUN CAT3 CABLE (DO NOT DAISY-CHAIN SPEAKERS) TERMINATED ON WALL-MOUNTED 66-BLOCK.

COORDINATE CONNECTION TO SYSTEM WITH OWNER'S I.T. DEPT.

SIGNATURE DATE

HATHAWAY

STATE OF O

H IO

P R

O F

ESS IO N

AL E N G

I N

E E

R

R E G I S T E RE D

E-61777

MARLON

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C :\U se rs

\M Ky ag ab a\ D oc um en ts

\1

_M

EP

_C

EN

TR

AL

F

IL

E_ m ky ag ab a@ sb m ce

.c om

.rv t

9/

/2

2:

:4

PM

EL0.1

ELECTRICAL GENERAL NOTES AND

SYMBOL LEGEND

SITE PREP FOR PET/CT

REPLACEMENT

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020 MCH

BID AND CONSTRUCTION

(REVISED)18111

09/16/2020 Revisions: Date:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

LIGHTING CONTROL GENERAL NOTES

1. REFER TO FLOOR PLANS FOR QUANTITIES, WIRING AND SWITCHING ARRANGEMENTS.

2. REFER TO OCCUPANCY SENSOR MANUFACTURER'S WIRING DIAGRAMS FOR INSTALLATION DRAWINGS.

3. FOR ALL OCCUPANCY SENSORS, TIME DELAY DIP SWITCH SETTINGS SHALL BE FOR 15 MINUTES, UNLESS DIRECTED OTHERWISE. WALL MOUNTED DEVICES SHALL HAVE DIP SWITCH SETTINGS FOR

MANUAL ON.

4. OCCUPANCY SENSORS SHALL BE PROVIDED AS SPECIFIED BY SENSOR SWITCH. EQUALS SHALL BE MANUFACTURED BY WATTSTOPPER, TOUCHÉ CONTROLS, OR LEVITON. ALL EQUIVALENT SYSTEMS SHALL PROVIDE ALL DEVICES, WIRING, AND COMPONENTS FOR A COMPLETE INSTALLATION COMPARABLE TO

WATTSTOPPER.

5. EC IS RESPONSIBLE FOR PROPER COMMISSIONING OF ALL OCCUPANCY SENSORS. COMMISSIONING SHALL BE PERFORMED ONCE ALL SPACES ARE OCCUPIED AND HVAC SYSTEM IS PROPERLY BALANCED FOR AIR FLOW AND TEMPERATURE. COMMISSIONING SHALL INCLUDE A ROOM-BY-ROOM 100% TEST OF EACH SENSOR IN A SHORT TIME-OUT TEST MADE TO ENSURE SENSOR DETECTS HUMAN MOVEMENTS, NO AIR INTERFERENCE IS PRESENT, AND SENSOR CANNOT DETECT MOVEMENT OUTSIDE OF CONTROLLED

SPACE. INCLUDE ALL ADJUSTMENTS TO SETTINGS AND MINOR RELOCATION OF DEVICES.

LIGHTING CONTROL DIAGRAM #2

N.T.S.

SYMBOL " "

B

120V

WHITE

GROUND

NEUTRAL

NEUTRAL

GREEN

RED

BLACK

WHITE

(SEE INSTALLATION

INSTRUCTIONS)

120V GROUND

OC

Primary Load

SENSORSWITCH: PASSIVE

INFRARED WALL SWITCH

SENSOR #WSX-PDT.

BLK

WHT

120V

NEUTRAL

RED/EM 277V

YLW/EM 120V

BLU/EM MVOLT

WHT-RED/EM NEUTRAL

VLT DIM COMMON

GRY DIM POSITIVE

BLU LINE OUTGRN

CAT 5e

LIGHTING CONTROL DIAGRAM #5

N.T.S.

J

SYMBOL " "

E

SENSORSWITCH:

#nPODM-DX-WH

SINGLE CHANNEL

DIMMER SWITCH.

SYMBOL

SENSORSWITCH:

#nPP16-D POWER

PACK WITH MVOLT

INPUT.

SS

PP

A

LIGHTING CONTROL TAG DETAIL

LIGHTING CONTROL

TAG FOR ROOM OR

SPACE.

PANEL

CIRCUIT #

N.T.S.

LIGHTING CONTROL DIAGRAM #4

D

BLK

WHT

120V

NEUTRAL

CAT 5e

RED/EM 277V

YLW/EM 120V

BLU/EM MVOLT

WHT-RED/EM NEUTRAL

VLT DIM COMMON

GRY DIM POSITIVE

BLU LINE OUTGRN

CAT 5e

CAT 5e CAT 5e nCM-PDT-10

OCCUPANCY SENSOR

SENSOR SWITCH

J nCM-PDT-10

OCCUPANCY SENSOR

SENSOR SWITCH

FOR ADDITIONAL

POWER PACKS (IF

REQUIRED) IN WORK

SPACE, SEE PLANS

SYMBOL

SENSORSWITCH:

#nPP16-D POWER

PACK WITH MVOLT

INPUT.

SS

SENSORSWITCH:

#nPODM-DX-WH

SINGLE CHANNEL

DIMMER SWITCH.

OC1OC1

PP

N.T.S.

OR

Refer to floor plans for exact quantity and types of switches required.

A

LIGHTING CONTROL DIAGRAM #1

Lighting Load

Neutral White

Unswitched Hot Black

Lighting Load

Unswitched Hot Black

N.T.S.

BLK

WHT

120V

NEUTRAL

CAT 5e

RED/EM 277V

YLW/EM 120V

BLU/EM MVOLT

WHT-RED/EM NEUTRAL

RED/EM

YLW/EM

BLU/EM

WHT-RED/EM

VLT DIM COMMON

GRY DIM POSITIVE

BLU LINE OUT

VLT DIM COMMON

GRY DIM POSITIVE

BLUGRN

GRN

CAT 5e

CAT 5e a,b

LIGHTING CONTROL DIAGRAM #3

N.T.S.

C

J

J

SENSORSWITCH:

#nPODM-2P-DX-WH

TWO

CHANNEL DIMMER

SWITCH.

SYMBOL

SENSORSWITCH:

#nPP16-D POWER

PACK WITH

MVOLT

INPUT.

FOR ADDITIONAL

POWER PACKS (IF

REQUIRED) IN WORK

SPACE, SEE PLANS

a,b

SENSORSWITCH:

#nPODM-2P-DX-WH

TWO

CHANNEL DIMMER

SWITCH.

CAT 5e

SS

PP

SS

PP

SIGNATURE DATE

HATHAWAY

STATE OF O

H IO

P R

O F

ESS IO N

AL E N G

I N

E E

R

R E G I S T E RE D

E-61777

MARLON

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C :\U se rs

\M Ky ag ab a\ D oc um en ts

\1

_M

EP

_C

EN

TR

AL

F

IL

E_ m ky ag ab a@ sb m ce

.c om

.rv t

9/

/2

:4 2:

A

M

EL0.2

LIGHTING FIXTURE SCHEDULE AND

DETAILS

SITE PREP FOR PET/CT

REPLACEMENT

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020 MCH

BID AND CONSTRUCTION

(REVISED)18111

09/16/2020

1. ALL FLUORESCENT FIXTURES SHALL BE PROVIDED WITH MVOLT ELECTRONIC BALLASTS WITH 10% TOTAL HARMONIC DISTORTION OR LESS UNLESS NOTED OTHERWISE. REFER TO SPECIFICATIONS FOR ACCEPTABLE BALLAST MANUFACTURERS

2. "NL" SUBSCRIPT INDICATES THAT THE FIXTURE IS CONNECTED TO AN UNSWITCHED CIRCUIT FOR "NIGHT LIGHT"

ILLUMINATION.

3. "EM" SUBSCRIPT INDICATES THAT THE FIXTURE IS CONNECTED TO AN EMERGENCY POWER SOURCE FOR EMERGENCY

ILLUMINATION.

4. EC TO USE BRAND NAME OR EQUAL.

5. VERIFY CEILING TYPE WITH ARCHITECTURAL REFLECTED CEILING PLAN. PROVIDE MOUNTING TYPE AS REQUIRED TO ACCOMMODATE THE CEILING. (i.e. FLANGE OR GRID MOUNT).

6. CONFIRM ALL MOUNTING HEIGHTS WITH ARCHITECT.

NOTES:

LIGHTING FIXTURE SCHEDULE

SYMBOL CATALOG NUMBER DESCRIPTION MOUNTING LAMP(S)

POWER

REQUIREMENT

0 VA

D1 LDN4-35/05-L04-AR-LSS-MVOLT-EZ1 LITHONIA: 11 3/16" x 9 7/16" x 5 11/16" DEEP LED FIXTURE WITH 4" APERATURE, 3500K, 523.6 LUMEN OUTPUT, 5.74W, MVOLT, WHITE FINISH AND ONE (1) 0-10V DIMMING LED DRIVER.

RECESSED INTEGRAL 6 VA

P1 ZL1D-L48-7000LM-FST-120-35K-80CRI

-WH

LITHONIA: 2.234"x4'x2.9882" DEEP LED FIXTURE WITH STEEL CONSTRUCTION, SNAP ON/SNAP OFF LENS, 7480 LUMEN OUTPUT, 120V, 3500K COLOR TEMPERATURE, 33W, WHITE FINISH AND (1) LED DRIVER.

PENDANT INTEGRAL 59 VA

R1 2BLT2-33L-ADP-EZ1-LP835 LITHONIA: 2'x2'x2-3/4" DEEP LED FIXTURE WITH ALUMINUM FRAM HOUSING, ACRYLIC LENS, 3300 LUMENT OUTPUT, 3500K, 82

CRI, 26W, WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 26 VA

R2 2BLT2-20L-ADP-EZ1-LP835 LITHONIA: 2'x2'x2-3/4" DEEP LED FIXTURE WITH ALUMINUM FRAM HOUSING, ACRYLIC LENS, 2000 LUMENT OUTPUT, 3500K, 82

CRI, 17W, WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 17 VA

R3 2BLT2-40L-ADP-EZ1-LP835 LITHONIA: 2'x2'x2-3/4" DEEP LED FIXTURE WITH ALUMINUM FRAM HOUSING, ACRYLIC LENS, 4041 LUMENT OUTPUT, 3500K, 82

CRI, 31.73W, WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 32 VA

W1 WAL14-LED4-LO-4-P-TMW-SC-UNV-W

M-DM10

PURDENTIAL LTG: 4'X7"X4" DEEP WALL MOUNT LED FIXTURE, 770LM/FT, 28W, MVOLT, WHITE FINISH AND 1- (ONE) 0-10V DIMMING

DRIVER.

WALL MOUNT INTEGRAL 20 VA

W2 LE-P-W-1-R-120/277-SW16 LITHONIA: "X-RAY IN USE" SIGN, WHITE HOUSING, RED LETTER COLOR, DUAL VOLTAGE. CEILING/WALL

SURFACE

INTEGRAL 3 VA

W3 070442-35K-PHC PERFORMANCE IN LIGHTING: 8.9"x8.6" LED EXTERIOR WALL MOUNT FIXTURE, ALUMINUM HOUSING, 3500K COLOR TEMPERATURE, TYPE 3 DISTRIBUTION, 18.5W, ALUMINUM METALLIC FINISH, INTEGRAL PHOTOCELL AND ONE (1) 0-10V LED

DIMMING DRIVER. FIXTURE TO BE MOUNTED 10' AFF UNLESS SPECIFIED OTHERWISE BY ARCHITECT.

WALL MOUNT INTEGRAL 19 VA

X1 LRP-()-RW-120/277-ELN LITHONIA: "EDGE-LIT" 13-1/4"X14-3/4" LED EXIT SIGN WITH GREEN LETTERS ON CLEAR PLEXIGLASS PANEL, BRUSHED ALUMINUM HOUSING, UNIVERSAL CEILING OR WALL MOUNTING KIT, NICKEL-CADMIUM BATTERY. PROVIDE CHEVRONS AS INDICATED ON

FLOOR PLANS. SINGLE OR DOUBLE FACE AS INDICATED ON DRAWINGS.

UNIVERSAL INTEGRAL 3 VA

Revisions: Date:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

EXISTING MRI

BUILDING (335)

NEW MRI

ADDITION

EXISTING HOSPITAL

(BUILDING 330

EXISTING

COURTYARD

EXISTING

LOADING DOCK

EXISTING

RETAINING WALL

CONTRACT LIMIT LINE

FIBER OPTIC DUCT SCHEMATIC

CONSTRUCTION NOTES

CODED NOTES

MANHOLE #16 DETAIL

SECTION "A-A" - PLAN VIEW

SECTION "B-B" - ELEVATION

A A

MANHOLE NOTES

B

B

ELECTRICAL SITE PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020Revisions: Date:

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162BID AND CONSTRUCTION

(REVISED)

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

SITE PREP FOR PET/CT

REPLACEMENT

09-16-2020

BID AND CONSTRUCTION (REVISED) 07-13-2020

SOLE SOURCE REVISION 09-16-2020

ELECTRICAL SITE PLAN

MCH MSK

ES.1

A

B

B

E

E

J

J

J

J

J

J

J

J

E

C

A

J

B

SRQPON.1

1.7

2.4

2.9

2.5

R1

R1

R1

R1

R2

R2

R2

R2

R2

R2

R1R1R1R1R1

R2 R2

R2R2

R2 R2

P1P1P1

R

R1 R1 R1

X X X

XXX

X XX

X X X X

XXXX

XXXXXX

X

XX

X

X

X

X X X

X X X

X

X

XX

X

XXX

X

X

X X

X

X

X X

P1

O C

O C

1 (TYP.)

NL/EM

NL/EMNL/EM

EM EM EM EM EM

W1

W1

LTG

LTG

LTG

LTG/EM

LTG

LTG

LTG

X

X

X

X

X

HE-1B-PET

LN-1B-PET

XFMR-N-1B-PET

HN-1B-PET

LN-2B-PET

HN-1B-PET

HN-1B-PET

HN-1B-PET

HN-1B-PET

HN-1B-PET

HN-1B-PET

E

E

HE-1B-PET

LTG/EM

HE-1B-PET

A103

A105

A109

A106

A107

A108

A102

A101

A110

E103

E104

E105

E106

E107

E102E101

326327

XFMR-N-2B-PET

TC PANEL

D1 D1

D1D1

D1 D1 a b a b a b a b a b a b a, b

W2

E

X1

E

X1

E

HE-2B-PET

W3

E

P1

P1

P1

P1

LTG

HN-1B-PET

a,b LN-1B-PET

NL/EM

X X

PLAN NOTES

A. REFER TO DRAWING ES1.0 FOR ELECTRICAL GENERAL NOTES.

B. COORDINATE EXACT LOCATION OF ALL ELECTRICAL DEVICES WITH ARCHITECT PRIOR TO

FINAL INSTALLATION.

C. REFER TO LIGHTING CONTROL DETAIL SPECIFIED BY TAG DESIGNATION.

D. REFER TO DRAWING EL1.4B FOR PANELBOARD LOCATION.

PHASE 1 CODED NOTES

1. LIGHTING CONTROL TAG. REFER TO DETAIL FOR MORE INFORMATION.

2. PHASE 1 ELECTRICAL SCOPE OF WORK.

3. EXISTING ELECTRICAL ROOM.

4. SPLICE AND EXTEND TO EXISTING LIFE SAFETY LIGHTING CORRIDOR BRANCH CIRCUIT. FIELD

VERIFY.

5. SPLICE AND EXTEND TO EXISTING NORMAL LIGHTING CORRIDOR BRANCH CIRCUIT. FIELD

VERIFY.

6. EXISTING EMERGENCY LIGHTING FIXTURE PER RECORD DRAWINGS. CONTRACTOR SHALL

FIELD VERIFY.

7. TO RECEPTACLE BRANCH CIRCUIT THIS SPACE. REFER TO PHASE 1 POWER PLANS FOR

EXACT LOCATION OF RECEPTACLE(S).

8. TEMPORARY LIGHTING THIS SPACE TO BE REMOVED UNDER PHASE 2.

SIGNATURE DATE

HATHAWAY

STATE OF O

H IO

P R

O F

ESS IO N

AL E N G

I N

E E

R

R E G I S T E RE D

E-61777

MARLON

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C :\U se rs

\M Ky ag ab a\ D oc um en ts

\1

_M

EP

_C

EN

TR

AL

F

IL

E_ m ky ag ab a@ sb m ce

.c om

.rv t

9/

/2

:4 2:

A

M

EL1.1

LIGHTING - PARTIAL FIRST FLOOR

PLAN - ELECTRICAL (PHASE 1)

SITE PREP FOR PET/CT

REPLACEMENT

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020 MCH

BID AND CONSTRUCTION

(REVISED)18111

09/16/2020

1/4" = 1'-0"

LIGHTING - PARTIAL FIRST FLOOR PLAN - ELECTRICAL (PHASE 1)

ROOM LEGEND

Number Name

325 EXISTING ELECTRICAL ROOM

326 EXISTING STORAGE

327 EXISTING CONFERENCE ROOM

328 EXISTING CORRIDOR

332 EXISTING STORAGE

333 EXISTING OFFICE

334 EXISTING STORAGE

335 EXISTING STAIRS

336 EXISTING VESTIBULE

337 EXISTING CORRIDOR

A101 CONTROL ROOM

A102 EXAM ROOM

A103 EQUIPMENT ROOM

A105 TOILET ROOM

A106 TOILET ROOM

A107 PATIENT PREP

A108 PATIENT PREP

A109 CORRIDOR

A110 CORRIDOR

E101 EXISTING PATIENT PREP

E102 EXISTING PATIENT PREP

E103 EXISTING EXAM ROOM

E104 EXISTING CONTROL ROOM

E105 EXISTING TOILET ROOM

E106 EXISTING EQUIPMENT ROOM

E107 EXISTING CORRIDOR

Revisions: Date:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

L6

E11

E11

CIRCUITING NOTES

PLAN NOTES

CODED NOTES

PARTIAL POWER ONE LINE DIAGRAMS

PARTIAL FIRST FLOOR PLAN - ELECTRICAL

PARTIAL FIRST BASEMENT LEVEL PLAN - ELECTRICAL

STANDARD FEEDER SCHEDULE

PET/CT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020Revisions: Date:

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162BID AND CONSTRUCTION

(REVISED)

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

SITE PREP FOR PET/CT

REPLACEMENT

09-16-2020

BID AND CONSTRUCTION (REVISED) 07-13-2020

SOLE SOURCE REVISION 09-16-2020

POWER - PARTIAL BASEMENT FLR

PLAN - ELECTRICAL (PHASE 1)

MCH MSK

EL1.2A

90C

100C

SRQPON.1

1.7

2.4

2.9

2.5

LN-2B-PET

X X

X

X X X

X

X X

X

X

X X

X

X

X

X

X

X

X

X

XX

X

X X X

HE-1B-PET

HN-1B-PET

LN-1B-PET

X

X

X

X

XFMR-N-1B-PET

X

X

HC1A

X

HN1A

X

LC2A

XFMR-N-2B-PET

A103

A105

A109

A106

A107

A108

A102

A101

A110

E103

E104

E105E106

E107

E102

E101

326327

5 5

MDP

HE-2B-PET

(TYP.)

LN-2B-PET

LN-2B-PET

LN-1B-PET

LN-1B-PET

GFI/C

GFI/48"

GFI/48"

GFI/C

GFI/C

GFI/C GFI/C

CP-1

TP-1

ES-1

ES-1

WH-3

WH-2

RPM-1

RCH-5

RCH-1

WH-1

RPM-1

RCH-4

RCH-6

RCH-2

DS-CP-1

LN-1B-PET

LN-1B-PET

LN-1B-PET

LN-2B-PET

LC2A

LN-1B-PET

20LN-1B-PET

LN-2B-PET

LN-1B-PET

LN-1B-PET

LN-1B-PET

LN-1B-PET

LN-1B-PET

LN-1B-PET

LN-2B-PET

LN-2B-PET

CLG

LN-2B-PET

RPM-1

RCH-3LN-1B-PET

LN-1B-PET

LC2A

LN-2B-PET

ECU-1

X

X

X

GFI

GFI

LN-1B-PET

LN-1B-PET

GFI

LN-2B-PET

LN-2B-PET

C

C

LN-1B-PET

LN-1B-PET

C

LN-1B-PET

NCPS

LC2A

R

R

X

PHASE 1 CODED NOTES

1. EXISTING ELECTRICAL ROOM.

2. NEW PET ADDITION.

3. TEMPERATURE CONTROL PANEL.

4. TO DISTRIBUTION PANELBOARD "NDB" ON FLOOR BELOW.

5. EXISTING CEILING MOUNTED ELECTRICAL DEVICES TO BE TEMPORARILY REMOVED AND

REINSTALLED AS REQUIRED IN THIS SPACE FOR NEW PET/CT CONDUIT AND FEEDER(S).

6. UPS FURNISHED BY GE. EC TO INSTALL.

7. FEEDER DESIGNATION, SEE STANDARD FEEDER SCHEDULE. (TYP.).

8. 12" X 12" X 4"D SC PULL BOX ABOVE ACCESSIBLE CEILING. (TYP.)

9. TO DISTRIBUTION PANELBOARD "EDP2" ON FLOOR BELOW.

10. MAIN DISCONNECT PANEL FURNISHED BY GE. EC TO INSTALL.

11. REFER TO GE DRAWING(S) THIS SPACE FOR ADDITIONAL INFORMATION.

12. CHILLER FURNISHED BY GE. EC TO INSTALL.

13. PARC4 FURNISHED BY GE. EC TO INSTALL.

14. POWER DISTRIBUTION UNIT FURNISHED BY GE. EC TO INSTALL.

PLAN NOTES

A. REFER TO DRAWING EL0.1 FOR ELECTRICAL GENERAL NOTES.

B. COORDINATE EXACT LOCATION OF ALL ELECTRICAL DEVICES WITH ARCHITECT PRIOR TO

FINAL INSTALLATION.

SIGNATURE DATE

HATHAWAY

STATE OF O

H IO

P R

O F

ESS IO N

AL E N G

I N

E E

R

R E G I S T E RE D

E-61777

MARLON

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C :\U se rs

\M Ky ag ab a\ D oc um en ts

\1

_M

EP

_C

EN

TR

AL

F

IL

E_ m ky ag ab a@ sb m ce

.c om

.rv t

9/

/2

:4 2:

A

M

EL1.2B

POWER - PARTIAL FIRST FLOOR

PLAN - ELECTRICAL (PHASE 1)

SITE PREP FOR PET/CT

REPLACEMENT

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020 Checker Author

BID AND CONSTRUCTION

(REVISED)18111

09/16/2020

3/16" = 1'-0"

POWER - PARTIAL FIRST FLOOR PLAN - ELECTRICAL (PHASE 1)

ROOM LEGEND

Number Name

325 EXISTING ELECTRICAL ROOM

326 EXISTING STORAGE

327 EXISTING CONFERENCE ROOM

328 EXISTING CORRIDOR

332 EXISTING STORAGE

333 EXISTING OFFICE

334 EXISTING STORAGE

335 EXISTING STAIRS

336 EXISTING VESTIBULE

337 EXISTING CORRIDOR

A101 CONTROL ROOM

A102 EXAM ROOM

A103 EQUIPMENT ROOM

A105 TOILET ROOM

A106 TOILET ROOM

A107 PATIENT PREP

A108 PATIENT PREP

A109 CORRIDOR

A110 CORRIDOR

E101 EXISTING PATIENT PREP

E102 EXISTING PATIENT PREP

E103 EXISTING EXAM ROOM

E104 EXISTING CONTROL ROOM

E105 EXISTING TOILET ROOM

E106 EXISTING EQUIPMENT ROOM

E107 EXISTING CORRIDOR

Revisions: Date:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

N

PHASE 1 CODED NOTES

1. LIGHTNING PROTECTION AIR TERMINAL. REFER TO DETAIL AND SPECIFICATION FOR

MOUNTING INFORMATION. MOUNT AIRE TERMINAL AT 20' ON CENTER MAXIMUM SPACING. (TYP.)

2. EC TO PROVIDE BOND TO BUILDING STEEL FOR DOWN CONDUCTOR AT 60' INTERVALS

MAXIMUM. BOND TO MAIN CONDUCTOR AND GROUND ROD. PROTECT CONDUCTOR WITH SCH 80

PVC BELOW GRADE TO CONNECTION POINTS. (TYP.).

3. EC TO PROVIDE BONDED CONNECTIONS. (TYP.)

4. EC TO PROVIDE COPPER MAIN CONDUCTOR. SIZE PER NFPA 780. (TYP.)

5. PROVIDE GROUND ROD AND WELDED CONNECTION TO BUILDING STEEL. REFER TO DETAILS

FOR MORE INFORMATION. (TYP.).

6. BOND TO EXISTING LIGHTING PROTECTION SYSTEM, FIELD VERIFY.

7. BOND TO EQUIPMENT ENCLOSURE. (TYP.)

PLAN NOTES

A. REFER TO DRAWING ES1.0 FOR ELECTRICAL GENERAL NOTES.

B. COORDINATE EXACT LOCATION OF ALL ELECTRICAL DEVICES WITH ARCHITECT PRIOR TO

FINAL INSTALLATION.

B. REFER TO SPECIFICATION SECTION FOR ADDITIONAL LIGHTNING PROTECTION

REQUIREMENTS.

C. LIGHTNING PROTECTION ITEMS ON THIS SHEET ARE FOR BIDDING PURPOSES ONLY. VERIFY

ALL LIGHTNING PROTECTION REQUIREMENTS WITH LIGHTNING PROTECTION CONTRACTOR.

D. LOCATION OF ALL DEVICES SHOWN ARE APPROXIMATES ONLY. ARCHITECT/ENGINEER MAY

RELOCATE ANY/ALL DEVICES UP TO 10' FROM WHERE SHOWN ON PLANS WITH NO ADDITIONAL

COST.

E. LIGHTNING PROTECTION MATERIAL TO BE COPPER AND COMPLY WITH NFPA 780 CLASS I

REQUIREMENTS UNLESS OTHERWISE NOTED.

F. THROUGH THE ROOF PENETRATIONS TO BE ROUTED TO NEAREST BUILDING STEEL. SEE

DETAIL SHEETS FOR ADDITIONAL INFORMATION.

G. LIGHTNING PROTECTION TO BE BONDED TO GROUNDING ELECTRODE SYSTEM. SIZE

CONDUCTOR PER NFPA 780 REQUIREMENTS.

H. LIGHTNING PROTECTION SYSTEM TO BE INSTALLED WITH THE FOLLOWING GUIDELINES:

1) METAL BODIES OF INDUCTANCE LOCATED ABOUT THE ROOF, SUCH AS METAL FLASHING,

GRAVEL STOPS, ROOF DRAINS, SOIL PIPE VENTS, ETC., SITUATED WITHIN 6' OF LIGHTNING

CONDUCTOR, SHALL BE INTERCONNECTED TO THE LIGHTNING CONDUCTOR SYSTEM.

2) NO BEND OF A CONDUCTOR SHALL FORM A FINAL INCLUDED ANGLE OF LESS THAN 90

DEGREES NOR SHALL HAVE A RADIUS OF BEN LESS THAN 8".

3) ALL LIGHTNING PROTECTION CONDUCTORS SHALL BE FASTENED NOT MORE THAN 3'

MAXIMUM SPACING.

4) CONNECTIONS TO GROUND ROD CONDUCTOR SHALL BE MADE AT A POINT NOT LESS THAN

1' BELOW GRADE AND 2' AWAY FROM FOUNDATION WALL.

5) ACTUAL JOB-SITE CONDITIONS MAY NECESSITATE SLIGHT ALTERATIONS IN AIR TERMINAL

AND GROUND ROD LOCATIONS.

6) LIGHTNING PROTECTION MATERIALS SHALL NOT BE INSTALLED ON ALUMINUM ROOF OR

OTHER ALUMINUM SURFACES.

7) THE LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT AND

INCONSPICUOUS MANNER SO THAT ALL COMPONENTS WILL BLEND IN WITH THE APPEARANCE OF

THE BUILDING.

8) ALL CONDUIT FASTENERS AND MISCELLANEOUS ACCESSORIES SHALL BE FURNISHED AND

INSTALLED BY THE ELECTRICAL CONTRACTOR.

9) ALL ADHESIVE TYPE FITTINGS SHALL BE SET IN PLACE WITH AN APPLICATION OF

COMPATIBLE ROOF CEMENT.

10) FIELD AND JOB CONDITIONS MAY REQUIRE VARIANCES TO ANY AND ALL DIMENSIONS,

DETAILS, AND CABLE ROUTINGS.

SRQPON.1

1.7

2.4

2.9

2.5

1 4 3

ECU-1/CU-1

RTU-1-SF

WP/GFI

LN-2B-PET

CU-1

RTU-1-RF

SIGNATURE DATE

HATHAWAY

STATE OF O

H IO

P R

O F

ESS IO N

AL E N G

I N

E E

R

R E G I S T E RE D

E-61777

MARLON

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C :\U se rs

\M Ky ag ab a\ D oc um en ts

\1

_M

EP

_C

EN

TR

AL

F

IL

E_ m ky ag ab a@ sb m ce

.c om

.rv t

9/

/2

:4 2:

A

M

EL1.3

POWER - ROOF PLAN -

ELECTRICAL (PHASE 1)

SITE PREP FOR PET/CT

REPLACEMENT

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020 MCH

BID AND CONSTRUCTION

(REVISED)18111

09/16/2020

1/4" = 1'-0"

POWER - ROOF PLAN - ELECTRICAL (PHASE 1)

Revisions: Date:

35% SUBMISSION 12-12-2019

65% SUBMISSION 02-24-2020

65% RE-SUBMISSION 03-31-2020

95% SUBMISSION 05-08-2020

BID AND CONSTRUCTION 06-12-2020

N N

N N

N

N

N

N

S S

S

SRQPON.1

1.7

2.4

2.9

2.5

X

X X

X

X X

X

X X

X

X

X

X

X X

X

X

X

X

XX

X

X

T

T

V

V

SMP SMP

W

W

FAAP

X

X

X

X

X

HE-1B-PET

LN-1B-PET

HN-1B-PET

XFMR-N-1B-PET

LN-2B-PET

CB

V

SMP

SMPSMP

W

W

W

XFMR-N-2B-PET

A103

A105

A109 A106

A107

A108

A102

A101

A110

E103

E104

E105E106

E107

E102

E101

326327

WAP

2D

SMD

SMD

TC PANEL

HE-2B-PET

SP

SP

SP

NCPS

PHASE 1 CODED NOTES

1. PHASE 1 ELECTRICAL SCOPE OF WORK.

2. EXISTING ELECTRICAL ROOM.

3. NURSE CALL POWER SUPPLY/ STEP DOWN TRANSFORMER ABOVE CEILING SPACE. REFER TO

DETAIL FOR MORE INFORMATION.

PLAN NOTES

A. REFER TO DRAWING EL0.1 FOR ELECTRICAL GENERAL NOTES.

B. COORDINATE EXACT LOCATION OF ALL ELECTRICAL DEVICES WITH ARCHITECT PRIOR TO

FINAL INSTALLATION.

C. ALL NEW FIRE ALARM DEVICES TO CONNECT TO EXISTING EST3 FIRE ALARM SYSTEM.

SIGNATURE DATE

HATHAWAY

STATE OF O

H IO

P R

O F

ESS IO N

AL E N G

I N

E E

R

R E G I S T E RE D

E-61777

MARLON

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

PHILIP P. KIRK

CHIEF ENGINEER

552-CSI-162

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C :\U se rs

\M Ky ag ab a\ D oc um en ts

\1

_M

EP

_C

EN

TR

AL

F

IL

E_ m ky ag ab a@ sb m ce

.c om

.rv t

9/

/2

2:

:1

PM

EL1.4

SYSTEMS - PARTIAL FIRST FLOOR

PLAN - ELECTRICAL (PHASE 1)

SITE PREP FOR PET/CT

REPLACEMENT

4100 WEST THIRD STREET,

DAYTON, OHIO 45428

09/16/2020 MCH

BID AND CONSTRUCTION

(REVISED)18111

09/16/2020

1/4" = 1'-0"

SYSTEMS - PARTIAL FIRST FLOOR PLAN - ELECTRICAL (PHASE 1)

ROOM LEGEND

Number Name

325 EXISTING ELECTRICAL ROOM

326 EXISTING STORAGE

327 EXISTING CONFERENCE ROOM

328 EXISTING CORRIDOR

332 EXISTING STORAGE

333 EXISTING OFFICE

334 EXISTING STORAGE

335 EXISTING STAIRS

336 EXISTING VESTIBULE

337 EXISTING CORRIDOR

A101 CONTROL ROOM

A102 EXAM ROOM

A103 EQUIPMENT ROOM

A105 TOILET ROOM

A106 TOILET ROOM

A107 PATIENT PREP

A108 PATIENT PREP

A109 CORRIDOR

A110 CORRIDOR

E101 EXISTING PATIENT PREP

E102 EXISTING PATIENT…