Asbestos Reinspection Report - August 2019.pdf
PDF 7 MB Posted
- Attached to
- Z2AA - Renovate Historic Building 4 Federal contract opportunity
- Solicitation number
- 36C24624R0030
About this file
This is an August 2019 asbestos reinspection report for the Fayetteville VA Medical Center conducted by Castle Hill Associates, LLC under Contract 36C24619N0872. The report documents a comprehensive asbestos survey of 23 buildings at the medical center campus, covering approximately 350,000 total square feet of facilities built between 1939-1996.
The inspection identified asbestos-containing materials (ACM) in several buildings, primarily consisting of vinyl floor tiles/mastic, window glazing/caulking, pipe insulation, and exterior caulking. The Main Hospital (Building 1) contained the most extensive ACM, with over 8,600 square feet of vinyl floor tile/mastic and asbestos in window materials throughout all floors. Eight buildings were found to contain ACM, while eleven buildings had no known asbestos materials. The report includes detailed sampling data, laboratory analysis results, material assessments, and recommendations for an operations and maintenance (O&M) program to manage the identified ACM. The inspection was conducted by Brett Brumbaugh, a North Carolina certified asbestos inspector, and analysis was performed by EMSL Analytical laboratory using EPA-approved methods.
View the file
Other files for this federal contract opportunity
Show all 50
Z2AA - Renovate Historic Building 4 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS REINSPECTION REPORT
LOCATION:
FAYETTEVILLE VA MEDICAL CENTER
2300 RAMSEY STREET
FAYETTEVILLE, NC 28301
PROJECT NO.: V06-18-102
CONTRACT: 36C24619N0872
INSPECTION DATES:
AUGUST 26-27, 2019
PRIME CONTRACTOR:
CASTLE HILL ASSOCIATES, LLC
218-A MECHANIC ST.
WATERVILLE, OH 43566
567-952-0212
FAYETTEVILLE VA MEDICAL CENTER - FAYETTEVILLE, NC
AUGUST 2019
TABLE OF CONTENTS
1.0 ASBESTOS INSPECTION REPORT
• Table 1 – List of Acronyms
• Table 2 - Removal Priority Protocols
2.0 APPENDICES
Appendix A – Asbestos Sampling Data
Appendix B – Asbestos Quantities, Assessments, & Remediation Cost Estimate
Appendix C – Photographs of Asbestos Materials
Appendix D – Asbestos Laboratory Reports
Appendix E - Inspector Certifications
Appendix F - Lab Certifications
Appendix G – Asbestos Locations and Sample Location Drawings
Appendix H – O&M Plan (Operations & Maintenance)
1.0 EXECUTIVE SUMMARY
On August 26-27, 2019, Castle Hill Associates, LLC was contracted by the US Department of Veterans Affairs (VA) to perform asbestos re-inspections of 23 buildings on the site of the Fayetteville VA Medical Center in Fayetteville, NC. The survey was performed as part of the VA Project Number V06-18-102 under Contract 36C24618Q0693. The Performance Work Statement (PWS) issued by the VA defined the scope of work for the asbestos survey. The buildings that were surveyed as part of this project included:
Building Number
Building Name/Description Total Square
Footage Year Built
1 Main Hospital 257,923 1939; Renovated 1988
3 Medical Center Ancillary Services 48,025 1939; Renovated 1976
4 Admin Education Nursing 10,100 1939
8 Health Admin Services 5,557 1939
9 Engineering Shops/Garages 6,073 1939
10 Laundry Plant/Drug Cache 7,912 1939; Renovated 1995
11 Boiler Plant 8,047 1939
15 Garage near Quarters 180 1939
16 Garage near Quarters 1,500 1939
18 Garage Storage 367 1939
20 Engineering Storage 300 1977
21 Computer Building 2,508 1986; Renovated 1994
22 Incinerator Building (no incinerator) 373 1988
24 Hazardous Waste Storage 200 1996
30 Quonset Hut Storage Building 1,300 1959
34 Generator Building 504 1973
35 Chiller Plant 2,417 1974
37 Electrical Distribution 250 1977
The inspection was conducted by Brett Brumbaugh. The project manager was Mr. Brumbaugh who has been conducting asbestos surveys, sampling, and consulting work since 1987. He is a State of North Carolina Asbestos Inspector. There was a previous asbestos reinspection and sampling conducted at the facility most recently in 2013 and those reports were reviewed and utilized by Castle Hill prior to this inspection. There were no limitations or exceptions to the PWS for the surveys conducted.
All accessible functional areas in the facilities were surveyed. All previous asbestos survey information and sampling conducted at the facilities were evaluated and incorporated into this survey. All confirmed asbestos-containing materials were verified. This report can be incorporated into the facility’s management plan for asbestos-containing materials.
2.0 STATE AND LOCAL REGULATIONS
The State of North Carolina asbestos inspection and licensing regulations are similar to the Federal regulations. State asbestos regulations include requirements for licensing and certification of personnel who will perform asbestos-related work activities. All personnel who engage in asbestos-related activities must comply with the state licensing/certification requirements as well as with all Federal requirements.
3.0 ANALYTICAL METHODS AND LIMITATIONS
3.1 Asbestos Sampling Protocol
EPA and OSHA define an ACBM as any material which contains greater than 1 percent asbestos. The ACBM inspection and bulk sampling were performed in accordance with the methods outlined in the EPA guidance document titled Guidance for Controlling Asbestos-Containing Materials in Buildings (Document No. 560/5- 85/024). In addition, bulk sampling of asbestos was performed in accordance with 40 CFR Part 763, AHERA requirements for number of samples and types of ACBM to be sampled. According to these requirements, materials are classified as either surfacing (e.g., decorative plaster, spray-applied fireproofing), thermal system insulation (e.g., pipe insulation, pipe fitting insulation, boiler insulation), or miscellaneous materials (e.g., floor tile, ceiling tile, plaster, wallboard, mastics).
The number of samples collected from each material varies based on the classification of the material and increases as the potential for a non-uniform mixture of asbestos in the material increases. Typically, regulations require a minimum number of samples to be collected from the different classifications of suspect
ACBM.
All bulk samples were analyzed utilizing current EPA methods for PLM (Polarized Light Microscopy) by EMSL Analytical in Plymouth, MI. EMSL is accredited by the NIST, NVLAP program (National Institute of Standards and Technology, National Voluntary Laboratory Accreditation Program) and also an American Industrial Hygiene Association (AIHA) accredited laboratory.
4.0 SUMMARY OF FINDINGS
4.1 Asbestos-Containing Building Materials
The following is a summary of the asbestos containing materials, locations, quantities of materials in each inspected building for this project:
Building 1 - Main Hospital
Asbestos Containing Materials Locations Quantity
12” or 9” vinyl floor tile and/or black mastic Basement, 1st, 2nd, 3rd, 4th, and 5th floors 8,620 sf Window glazing and window frame caulk Basement, 1st, 2nd, 3rd, 4th, and 5th floors All windows Pipe insulation behind walls and above ceilings
Basement, 1st, 2nd, 3rd, 4th, and 5th floors Unknown
Exterior door frame caulk Basement, 1st, and 5th floors 26 doors Exterior vent pipe caulk 5th floor 16 vents
Building 3 - Medical Center Ancillary Services
Pipe insulation on steam and domestic water lines
Mechanical Rooms 2 & 3; and assumed to be located behind plaster walls & ceilings
180 lf
12” vinyl floor tile and black mastic 1st, 2nd, 3rd, and 4th floors 820 sf
Building 4 - Admin Education Nursing lines
Inaccessible wall chases and ceiling plenums Unknown
12” vinyl floor tile and mastic Basement 140 sf
Building 8 - Health Admin Services lines
Inaccessible wall chases and ceiling plenums Unknown
12” vinyl floor tile and mastic 1st floor custodial storage closet 104 15 sf
Building 9 - Engineering Shops/Garages lines
Inaccessible wall chases and ceiling plenums Unknown
12” vinyl floor tile and mastic 103B, 104, 110, 111, and 113 1,020 sf Residual mastic under carpeting 108 and 109 1,100 sf
Building 10 - Laundry Plant/Drug Cache
• All known asbestos containing materials have been removed from this building.
Building 11 - Boiler Plant
Window glazing and caulking All windows (basement, 1st, and 2nd floors) 26 windows 12” vinyl floor tile and mastic Office, locker room, and hallway 494 sf
Building 15 - Garage near Quarters
• There are no known asbestos containing materials in this building.
Building 16 – Garage near Quarters
Building 18 – Garage Storage
Building 20 – Engineering Storage
Building 21 – Computer Building
Building 22 – Incinerator Building
Building 24 – Hazardous Waste Storage
Building 30 – Quonset Hut Storage Building lines
W. entrance and ceiling plenum 290 lf
Exterior caulking on metal roofing All seams of roofing 680 lf
Building 34 – Generator Building
Building 35 – Chiller Plant
Window glazing and caulking All windows 6 windows 12” vinyl floor tile and mastic Office 120 sf
Building 37 – Electrical Distribution
5.0 Explanation of Assessment of Asbestos Containing Materials
Re-inspection protocol is based on the Asbestos Hazard Emergency Response Act (AHERA), Environmental Protection Act’s (EPA’s) revised Asbestos Model Accreditation Plan (MAP) mandated by the Asbestos School Hazard Abatement Reauthorization Act (ASHARA), and the Department of Veterans Affairs (VA) Directive 7700. The tabular listing included in this report contains Building Number, Floor, Room Number, Material Category (i.e., TSI, SM or MM), Material Type, quantity, a numerical priority ranking, condition, potential for damage, potential for human exposure, drawing number, hazard ranking, recommended response action and associated cost estimate for implementation of those response actions.
The material assessment categories of the ACM identified in the building is formatted in the following order for the summary tables enclosed in this report:
• Material Category - Surfacing Material (SUR); Thermal System Insulation (TSI); Miscellaneous (MM)
• Material Type - Friable (F); Non-Fable (NF)
• Condition of Material - Good; Fair; Poor
• Potential for Damage - Low; Medium; High
• Physical Assessment - Low; Medium; High
• Recommended Response Action - 1 through 7
Material category is the type of material such as surfacing material (SUR), thermal system insulation (TSI), and miscellaneous (MM)
• Surfacing Material (SUR) - Surfacing ACM means surfacing material that is ACM. Surfacing material means material in a school building that is sprayed-on, troweled-on, or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, or other purposes.
• Thermal System Insulation (TSI) - Thermal system insulation ACM means thermal system insulation that is ACM. Thermal system insulation means material in a school building applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes.
• Miscellaneous (MM) - Miscellaneous ACM means miscellaneous material that is ACM Miscellaneous material means interior building material on structural components, structural members or fixtures, such as floor and ceiling tiles, and does not include surfacing material or thermal system insulation.
Material type refers to the hardness of a material to be crumbled, pulverized, or reduced to powder by hand pressure as friable (F), and includes previously non-friable (NF) material after such previously non-friable material becomes damaged to the extent that when dry it may be crumbled, pulverized, or reduced to powder by hand pressure.
• Condition of Material - Good; Fair; Poor
• Potential for Damage - Low; Medium; High
• Physical Assessment - Low; Medium; High
Seven Categories define in the AHERA regulation one of which must be assigned to each friable surfacing and miscellaneous ACBM and each asbestos-containing TSI during the inspection/re-inspection.
1. Damaged or significantly damaged TSI ACBM - Damaged or significantly damaged thermal system insulation ACM means thermal system insulation ACM on pipes, boilers, tanks, ducts, and other thermal system insulation equipment where the insulation has lost its structural integrity, or its covering, in whole or in part, is crushed, water-stained, gouged, punctured, missing, or not intact such that it is not able to contain fibers. Damage may be further illustrated by occasional punctures, gouges or other signs of physical injury to ACM; occasional water damage on the protective coverings/jackets; or exposed ACM ends or joints. Asbestos debris originating from the ACBM in question may also indicate damage.
2. Damaged friable surfacing ACBM - Damaged friable surfacing ACM means friable surfacing ACM which has deteriorated or sustained physical injury such that the internal structure (cohesion) of the material is inadequate or which has delaminated such that its bond to the substrate (adhesion) is inadequate, or which, for any other reason, lacks fiber cohesion or adhesion qualities. Such damage or deterioration may be illustrated by the separation of ACM into layers; separation of ACM from the substrate; flaking, blistering, or crumbling of the ACM surface; water damage; significant or repeated water stains, scrapes, gouges, mars or other signs of physical injury on the ACM. Asbestos debris originating from the ACBM in question may also indicate damage.
3. Significantly damaged friable surfacing ACBM - Significantly damaged friable surfacing ACM means damaged friable surfacing ACM in a functional space where the damage is extensive and severe.
4. Damaged or significantly damaged friable miscellaneous ACBM - Damaged friable miscellaneous ACM means friable miscellaneous ACM which has deteriorated or sustained physical injury such that the internal structure (cohesion) of the material is inadequate or, if applicable, which has delaminated such that its bond to the substrate (adhesion) is inadequate or which for any other reason lacks fiber cohesion or adhesion qualities.
Such damage or deterioration may be illustrated by the separation of ACM into layers; separation of ACM from the substrate; flaking, blistering, or crumbling of the ACM surface; water damage; significant or repeated water stains, scrapes, gouges, mars or other signs of physical injury on the ACM. Asbestos debris originating from the ACBM in question may also indicate damage.
5. ACBM with Potential for Damage - Potential damage means circumstances in which:
(1) Friable ACBM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.
(2) There are indications that there is a reasonable likelihood that the material or its covering will become damaged, deteriorated, or delaminated due to factors such as changes in building use, changes in operations and maintenance practices, changes in occupancy, or recurrent damage.
6. ACBM with potential for significant damaged - Potential significant damage means circumstances in which:
(1) Friable ACBM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.
(2) There are indications that there is a reasonable likelihood that the material or its covering will become significantly damaged, deteriorated, or delaminated due to factors such as changes in building use, changes in operations and maintenance practices, changes in occupancy, or recurrent damage.
7. Any remaining friable ACBM or Friable Suspected ACBM
6.0 EXPLANATION OF REMEDIATION COST ESTIMATES
All remediation cost (removal and repair) estimates are based upon RS Means data. Since RS Means does not account for work in VA Medical Centers, all cost estimates are adjusted to reflect the VA specific requirements for abatement. In addition, the cost estimates reflect the quantity and location of the asbestos materials. For example, abatement work in crawl spaces is expected to be much costlier than work in more accessible areas of building. Also, the costs for each material in each building are intended to be for “stand alone” projects and the combination of areas for removal will reduce the costs due to an economy of scale.
7.0 CONCLUSION/RECOMMENDATIONS
An operations and maintenance (O&M) program has been developed by the VAMC specifically for the positively identified ACBM in the facilities. Any renovation/demolition work which may impact these positive materials should be conducted in accordance with the O&M program and all applicable Federal, state, and local regulations by appropriately trained and VA-approved personnel and contractors. Since demolition was not performed as part of the inspection work at the facilities, certain areas such as pipe chases and areas above fixed permanent ceilings, fire-door interiors, and vault/safe wall and door linings were not inspected or tested. Prior to renovation and alteration work which could impact these areas, Castle Hill recommends that exploratory demolition be performed and a qualified inspector be utilized to examine the areas and collect samples as needed. Castle Hill recommends sampling of roofing materials and electrical components (not specifically examined as part of this survey) if renovation activities are planned which may disturb these materials.
Respectfully Submitted:
Brett L. Brumbaugh, REPA, CESCO State of North Carolina Asbestos Inspector License Number 12411
TABLE 1
LIST OF ACRONYMS
ACBM Asbestos Containing Building Material ACM Asbestos Containing Material AHERA Asbestos Hazard Emergency Response Act AIHA American Industrial Hygiene Association CAA Clean Air Act CFR Code of Federal Regulations EPA United States Environmental Protection Agency HazCom Hazard Communication HEPA High Efficiency Particulate Air Filter HVAC Heating, Ventilation, and Air Conditioning MISC Miscellaneous Asbestos Containing Material NESHAP National Emission Standards for Hazardous Air Pollutants NIOSH National Institute for Occupational Safety and Health NIST National Institute of Standards and Technology NOB Non-friable Organically Bound NVLAP National Voluntary Laboratory Accreditation Program OSHA Occupational Safety and Health Administration PAT AIHA Proficiency Analytical Testing Program PCM Phase Contrast Microscopy PEL Permissible Exposure Limit PLM Polarized Light Microscopy TEM Transmission Electron Microscopy TSCA Toxic Substances Control Act TSI Thermal Systems Insulation Castle Hill Castle Hill Associates, LLC VA United States Department of Veterans Affairs VAMC VA Medical Center XRD X-Ray Diffraction
TABLE 2
ASBESTOS REMOVAL PRIORITY PROTOCOLS
HAZARD
RANK
REMOVAL
PRIORITY
AHERA
CATEGORY
RESPONSE ACTION
RECOMMENDATION
7 1 Significantly Damaged
Evacuate or isolate the area.
Remove or repair if feasible.
O&M for all friable ACM.
6 2 Damaged with potential for significant damage
Evacuate or isolate the area.
Remove, encapsulate, or repair if feasible. O&M for all friable
ACM.
5 3 Damaged with potential for damage
Remove, encapsulate, or repair. O&M for all friable ACM.
4 4 Damaged Remove, encapsulate, or repair. O&M for all friable ACM.
3 5 Potential for significant damage
Take steps to reduce potential for damage. O&M for all friable
ACM.
2 6 Potential for damage O&M for all friable ACM.
1 7 No problem O&M for all friable ACM.
APPENDIX A
ASBESTOS BULK SAMPLING DATA
AUGUST 2019
ASBESTOS BULK SAMPLING INFORMATION
Facility:
Building:
Sampling Date:
Analysis Dates:
Laboratory:
Accreditation:
Sampler:
Accreditation:
Fayetteville VA Medical Center – Fayetteville, NC Building 1 - Main Hospital August 26, 2019 September 3, 2019 EMSL Analytical - Plymouth, MI NVLAP Asbestos Bulk Accredited Laboratory # 101048-4 Brett Brumbaugh State of North Carolina – Asbestos Inspector #12411
PLM Laboratory Analysis Result
SAMPLE
NUMBER
MATERIAL SAMPLE LOCATION
LABORATORY ANALYSIS
RESULT
1 Spray-on fireproofing on column Penthouse – S. side No Asbestos Detected
2 Spray-on fireproofing on column Penthouse – Middle No Asbestos Detected
3 Spray-on fireproofing on column Penthouse – N. side No Asbestos Detected
• EPA Definition of an asbestos containing material: Greater than 1% asbestos
AUGUST 2019
ASBESTOS BULK SAMPLING INFORMATION
Facility:
Building:
Sampling Date:
Analysis Dates:
Laboratory:
Accreditation:
Sampler:
Accreditation:
Fayetteville VA Medical Center – Fayetteville, NC Building 10 - Laundry Plant/Drug Cache August 26, 2019 September 3, 2019 EMSL Analytical - Plymouth, MI NVLAP Asbestos Bulk Accredited Laboratory # 101048-4 Brett Brumbaugh State of North Carolina – Asbestos Inspector #1241112411
PLM Laboratory Analysis Result
SAMPLE
NUMBER
MATERIAL SAMPLE LOCATION
LABORATORY ANALYSIS
RESULT
17a 12” grey vinyl floor tile Laundry office (S.E. corner) No Asbestos Detected
17b Yellow mastic “” No Asbestos Detected
18 Spray-on fireproofing on beams Laundry – S. wall No Asbestos Detected
19 Spray-on fireproofing on beams Laundry – S. wall No Asbestos Detected
20 Spray-on fireproofing on beams Laundry – S. wall No Asbestos Detected
AUGUST 2019
ASBESTOS BULK SAMPLING INFORMATION
Facility:
Building:
Sampling Date:
Analysis Dates:
Laboratory:
Accreditation:
Sampler:
Accreditation:
Fayetteville VA Medical Center – Fayetteville, NC Building 11 – Boiler Plant August 26, 2019 September 3, 2019 EMSL Analytical - Plymouth, MI NVLAP Asbestos Bulk Accredited Laboratory # 101048-4 Brett Brumbaugh State of North Carolina – Asbestos Inspector #12411
PLM Laboratory Analysis Result
SAMPLE
NUMBER
MATERIAL SAMPLE LOCATION
LABORATORY ANALYSIS
RESULT
10 Window glazing S.W. window 2% Chysotile Asbestos
11 Window glazing Middle window (S. side) 2% Chysotile Asbestos
12 Window glazing N.W. window 2% Chysotile Asbestos
13 Generator exhaust pipe insulation Generator room No Asbestos Detected
AUGUST 2019
ASBESTOS BULK SAMPLING INFORMATION
Facility:
Building:
Sampling Date:
Analysis Dates:
Laboratory:
Accreditation:
Sampler:
Accreditation:
Fayetteville VA Medical Center – Fayetteville, NC Building 15 – Garage near Quarters August 26, 2019 September 3, 2019 EMSL Analytical - Plymouth, MI NVLAP Asbestos Bulk Accredited Laboratory # 101048-4 Brett Brumbaugh State of North Carolina – Asbestos Inspector #1241112411
PLM Laboratory Analysis Result
SAMPLE
NUMBER
MATERIAL SAMPLE LOCATION
LABORATORY ANALYSIS
RESULT
21 Caulking around garage door N. door No asbestos detected
22 Caulking around garage door S. door No asbestos detected
AUGUST 2019
ASBESTOS BULK SAMPLING INFORMATION
Facility:
Building:
Sampling Date:
Analysis Dates:
Laboratory:
Accreditation:
Sampler:
Accreditation:
Fayetteville VA Medical Center – Fayetteville, NC Building 16 – Garage near Quarters August 26, 2019 September 3, 2019 EMSL Analytical - Plymouth, MI NVLAP Asbestos Bulk Accredited Laboratory # 101048-4 Brett Brumbaugh State of North Carolina – Asbestos Inspector #1241112411
PLM Laboratory Analysis Result
SAMPLE
NUMBER
MATERIAL SAMPLE LOCATION
LABORATORY ANALYSIS
RESULT
23 Caulking around garage door Middle door No asbestos detected
24 Caulking around garage door S. door No asbestos detected
AUGUST 2019
ASBESTOS BULK SAMPLING INFORMATION
Facility:
Building:
Sampling Date:
Analysis Dates:
Laboratory:
Accreditation:
Sampler:
Accreditation:
Fayetteville VA Medical Center – Fayetteville, NC Building 30 - Quonset Hut Storage Building August 26, 2019 September 3, 2019 EMSL Analytical - Plymouth, MI NVLAP Asbestos Bulk Accredited Laboratory # 101048-4 Brett Brumbaugh State of North Carolina – Asbestos Inspector #1241112411
PLM Laboratory Analysis Result
SAMPLE
NUMBER
MATERIAL SAMPLE LOCATION
LABORATORY ANALYSIS
RESULT
4 Window glazing S. window No Asbestos Detected
5 Window glazing Middle window No Asbestos Detected
6 Window glazing N. window No Asbestos Detected
7 Exterior caulk on metal roof seam S.E. side of building 2% Chysotile Asbestos
8 Exterior caulk on metal roof seam N.E. side of building 2% Chysotile Asbestos
9 Exterior caulk on metal roof seam Middle of building by entry 2% Chysotile Asbestos
AUGUST 2019
ASBESTOS BULK SAMPLING INFORMATION
Facility:
Building:
Sampling Date:
Analysis Dates:
Laboratory:
Accreditation:
Sampler:
Accreditation:
Fayetteville VA Medical Center – Fayetteville, NC Building 35 - Chiller Plant August 26, 2019 September 3, 2019 EMSL Analytical - Plymouth, MI NVLAP Asbestos Bulk Accredited Laboratory # 101048-4 Brett Brumbaugh State of North Carolina – Asbestos Inspector #1241112411
PLM Laboratory Analysis Result
SAMPLE
NUMBER
MATERIAL SAMPLE LOCATION
LABORATORY ANALYSIS
RESULT
14 Window glazing S.W. window <1% Chysotile Asbestos
15 Window glazing Middle window (W. side) 2% Chysotile Asbestos
16 Window glazing N.W. window <1% Chysotile Asbestos
APPENDIX B
Asbestos Quantities, Assessments, & Remediation Cost Estimates
Fayetteville VAMC - Fayetteville, NC
Asbestos Assessments and Cost Estimates
August 2019
Asbestos Material Locations Quantity
AHERA
Category
Friability
%Damage
AHERA
Assessment Recommendation
Removal
Priority
Repair Cost
Estimate
Removal Cost
Estimate
12” or 9” vinyl floor tile and/or black mastic Basement, 1st, 2nd, 3rd, 4th, and 5th floors 8,620 sf MISC Non-friable
0% 1 O&M; Remove at renovation or demolition 7 No damage $43,100
Window glazing and window frame caulk Basement, 1st, 2nd, 3rd, 4th, and 5th floors All windows MISC Non-friable
0% 1 O&M; Remove at renovation or demolition 7 No damage $120,000
Pipe insulation behind walls and above ceilings Basement, 1st, 2nd, 3rd, 4th, and 5th floors Unknown TSI Friable 0% 1 O&M; Remove at renovation or demolition 7 No damage Unknown
Exterior door frame caulk Basement, 1st, and 5th floors 26 doors MISC Non-friable
0% 1 O&M; Remove at renovation or demolition 7 No damage $52,000
Exterior vent pipe caulk 5th floor 16 vents MISC Non-friable
0% 1 O&M; Remove at renovation or demolition 7 No damage $16,000
TOTALS 0 $231,100
Note: The start date for all response actions is October of 2019
Building 3 - Medical Center Ancillary Services
Asbestos Assessments and Cost Estimates
August 2019
Asbestos Material Locations Quantity
AHERA
Category
Friability
%Damage
AHERA
Assessment Recommendation
Removal
Priority
Repair Cost
Estimate
Removal Cost
Estimate
Pipe insulation on steam and domestic water lines
Mechanical Rooms 2 & 3; and assumed to be located behind plaster walls & ceilings 180 lf TSI Friable 0% 1 O&M; Remove at renovation or demolition 7 No damage $13,500
12” vinyl floor tile and black mastic 1st, 2nd, 3rd, and 4th floors 820 sf MISC Non-friable
0% 1 O&M; Remove at renovation or demolition 7 No damage $6,560
TOTALS 0 $20,060
Building 4 - Admin Education Nursing
Asbestos Assessments and Cost Estimates
August 2019
Asbestos Material Locations Quantity
AHERA
Category
Friability
%Damage
AHERA
Assessment Recommendation
Removal
Priority
Repair Cost
Estimate
Removal Cost
Estimate
Pipe insulation on steam and domestic water lines Inaccessible wall chases and ceiling plenums Unknown TSI Friable 0% 1
O&M; Remove at renovation or demolition 7 No damage Unknown
12” vinyl floor tile and mastic Basement 140 sf MISC Non-friable 0% 1 O&M; Remove at renovation or demolition 7 No damage $2,800
TOTALS 0 $2,800
Building 8 - Health Admin Services
Asbestos Assessments and Cost Estimates
August 2019
Asbestos Material Locations Quantity
AHERA
Category
Friability
%Damage
AHERA
Assessment Recommendation
Removal
Priority
Repair Cost
Estimate
Removal Cost
Estimate
Pipe insulation on steam and domestic water lines Inaccessible wall chases and ceiling plenums Unknown TSI Friable 0% 1
O&M; Remove at renovation or demolition 7 No damage Unknown
12” vinyl floor tile and mastic 1st floor custodial storage closet 104 15 sf MISC Non-friable 0% 1 O&M; Remove at renovation or demolition 7 No damage $1,500
TOTALS 0 $1,500
Asbestos Assessments and Cost Estimates
August 2019
Asbestos Material Locations Quantity
AHERA
Category
Friability
%Damage
AHERA
Assessment Recommendation Removal Priority
Repair Cost
Estimate
Removal
Cost
Estimate
Pipe insulation on steam and domestic water lines
Inaccessible wall chases and ceiling plenums Unknown TSI Friable 0% 1
O&M; Remove at renovation or demolition 7 No damage Unknown
12” vinyl floor tile and mastic 103B, 104, 110, 111, and 113 1,020 sf MISC Non-friable 0% 1 O&M; Remove at renovation or demolition 7 No damage $5,100
Residual mastic under carpeting 108 and 109 1,100 sf MISC Non-friable 0% 1 O&M; Remove at renovation or demolition 7 No damage $5,300
TOTALS 0 $10,400
Building 11 - Boiler Plant
Asbestos Assessments and Cost Estimates
August 2019
Asbestos Material Locations Quantity
AHERA
Category
Friability
%Damage
AHERA
Assessment Recommendation Removal Priority
Repair Cost
Estimate
Removal
Cost
Estimate
Window glazing and caulking All windows (basement, 1st, and 2nd floors) 26 windows MISC Non-friable 0% 1
O&M; Remove at renovation or demolition 7 No damage $26,000
12” vinyl floor tile and mastic Office, locker room, and hallway 494 sf MISC Non-friable 0% 1
O&M; Remove at renovation or demolition 7 No damage $3,900
TOTALS 0 $29,900
Asbestos Assessments and Cost Estimates
August 2019
Asbestos Material Locations Quantity
AHERA
Category
Friability
%Damage
AHERA
Assessment Recommendation Removal Priority
Repair Cost
Estimate
Removal
Cost
Estimate
Pipe insulation on steam and domestic water lines W. entrance and ceiling plenum 290 lf TSI Friable 0% 1
O&M; Remove at renovation or demolition 7 No damage $16,000
Exterior caulking on metal roofing All seams of roofing 680 lf MISC Non-friable 0% 1 O&M; Remove at renovation or demolition 7 No damage $17,000
TOTALS 0 $33,000
Asbestos Assessments and Cost Estimates
August 2019
Asbestos Material Locations Quantity
AHERA
Category
Friability
%Damage
AHERA
Assessment Recommendation Removal Priority
Repair Cost
Estimate
Removal
Cost
Estimate
Window glazing and caulking All windows 6 windows MISC Non-friable 0% 1 O&M; Remove at renovation or demolition 7 No damage $6,000
12” vinyl floor tile and mastic Office 120 sf MISC Non-friable 0% 1 O&M; Remove at renovation or demolition 7 No damage $3,500
TOTALS 0 $9,500
APPENDIX C
PHOTOGRAPHS OF ASBESTOS MATERIALS
Photo 1-1 12” tan vinyl floor tile and black mastic
Photo 1-2
12” white vinyl floor tile and black mastic
Photo 1-3 9” red vinyl floor tile and black mastic
Photo 1-4 Window glazing and window frame caulk
Photo 1-5 Window glazing and window frame caulk
Photo 1-6
Exterior door frame caulk
Photo 1-7
Exterior door frame caulk
BUILDING 3 - MEDICAL CENTER ANCILLARY SERVICES
Photo 3-1 Pipe insulation on steam and domestic water lines
Photo 3-2
Pipe insulation on steam and domestic water lines
Photo 3-3
12” vinyl floor tile and black
Photo 3-4
12” vinyl floor tile and black
BUILDING 4 - ADMIN EDUCATION NURSING
Photo 4-1 12” vinyl floor tile and mastic
Photo 4-2
BUILDING 8 - HEALTH ADMIN SERVICES
Photo 8-1
Photo 9-1
Residual mastic under carpeting
Photo 9-2
Residual mastic under carpeting
Photo 9-3
BUILDING 11 – BOILER PLANT
Photo 11-1 Window glazing and caulking
Photo 11-2
Photo 11-3
Window glazing and caulking
Photo 11-4 12” vinyl floor tile and
Photo 30-1 Pipe insulation on steam lines
Photo 30-2
Pipe insulation on steam lines
Photo 30-3
Exterior caulking on metal roofing
Photo 30-4
Exterior caulking on metal roofing
Photo 35-1
Photo 35-2
APPENDIX D
ASBESTOS LABORATORY REPORTS
EMSL Analytical, Inc.
15111 Northville Rd Plymouth, MI 48170
Tel/Fax: (734) 668-6810 / (734) 668-8532 http://www.EMSL.com / annarborlab@emsl.com
081902549EMSL Order:
Customer ID: CHAS42
Customer PO: VISN6
Project ID:
Attention: Phone:Brett Brumbaugh (567) 952-0212
Fax:Castle Hill Associates, LLC
Received Date:218-A Mechanic St. 08/30/2019 12:00 PM
Analysis Date:Waterville, OH 43566 09/03/2019
Collected Date:
Project: VISN 6 - Fayetteville VAMC
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
081902549-0001
None DetectedNon-fibrous (Other)100%Glass<1%White
Non-Fibrous
Homogeneous
081902549-0002
None DetectedNon-fibrous (Other)98%Glass2%White
Non-Fibrous
Homogeneous
081902549-0003
None DetectedNon-fibrous (Other)96%Glass4%White
Non-Fibrous
Homogeneous
081902549-0004
None DetectedNon-fibrous (Other)98%Wollastonite
Fibrous (Other)
2%
<1%
Gray/Beige
Non-Fibrous
Homogeneous
081902549-0005
None DetectedMica
Non-fibrous (Other)
<1%
100%
Wollastonite<1%Gray/White/Beige
Non-Fibrous
Homogeneous
081902549-0006
None DetectedMica
Non-fibrous (Other)
2%
98%
Wollastonite<1%Gray/White
Non-Fibrous
Homogeneous
081902549-0007
None DetectedNon-fibrous (Other)100%Wollastonite<1%Gray/White
Non-Fibrous
Homogeneous
Caulk A
081902549-0007A
2% ChrysotileQuartz
Non-fibrous (Other)
2%
96%
Gray/White/Silver
Non-Fibrous
Heterogeneous
Caulk B
Result includes a small amount of inseparable attached material
081902549-0008
None DetectedNon-fibrous (Other)100%Wollastonite<1%Gray/White
Non-Fibrous
Homogeneous
Caulk A
081902549-0008A
2% ChrysotileQuartz
Non-fibrous (Other)
4%
94%
Gray/White/Silver
Non-Fibrous
Heterogeneous
Caulk B
Result includes a small amount of inseparable attached material
081902549-0009
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Caulk A
081902549-0009A
2% ChrysotileNon-fibrous (Other)96%Wollastonite2%Gray
Non-Fibrous
Homogeneous
Caulk B
Result includes a small amount of inseparable attached material
081902549-0010
2% ChrysotileNon-fibrous (Other)98%Gray/White
Non-Fibrous
Homogeneous
081902549-0011
2% ChrysotileNon-fibrous (Other)98%Gray/White/Beige
Non-Fibrous
Homogeneous
081902549-0012
2% ChrysotileQuartz
Non-fibrous (Other)
4%
94%
Gray
Non-Fibrous
Homogeneous
Initial report from: 09/04/2019 12:16:53
Page 1 of 2ASB_PLM_0008_0001 - 1.78 Printed: 9/4/2019 12:16 PM
EMSL Analytical, Inc.
15111 Northville Rd Plymouth, MI 48170
Tel/Fax: (734) 668-6810 / (734) 668-8532 http://www.EMSL.com / annarborlab@emsl.com
081902549EMSL Order:
Customer ID: CHAS42
Customer PO: VISN6
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
081902549-0013
None DetectedNon-fibrous (Other)88%Cellulose
Min. Wool
3%
9%
Gray/White
Fibrous
Homogeneous
081902549-0014
<1% ChrysotileNon-fibrous (Other)100%Gray
Fibrous
Homogeneous
081902549-0015
2% ChrysotileNon-fibrous (Other)98%Gray
Non-Fibrous
Homogeneous
081902549-0016
<1% ChrysotileNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
081902549-0017
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Floor Tile
081902549-0017A
None DetectedNon-fibrous (Other)100%Cellulose<1%Gray/Tan
Non-Fibrous
Homogeneous
Adhesive
081902549-0018
None DetectedNon-fibrous (Other)20%Synthetic
Min. Wool
<1%
80%
Gray
Fibrous
Homogeneous
081902549-0019
None DetectedNon-fibrous (Other)10%Cellulose
Min. Wool
<1%
90%
Gray
Fibrous
Homogeneous
081902549-0020
None DetectedNon-fibrous (Other)15%Min. Wool85%Gray
Fibrous
Homogeneous
Insulation
081902549-0020A
None DetectedQuartz
Non-fibrous (Other)
4%
96%
Gray
Non-Fibrous
Homogeneous
Concrete
081902549-0021
None DetectedNon-fibrous (Other)100%Wollastonite<1%White/Beige
Non-Fibrous
Homogeneous
081902549-0022
None DetectedNon-fibrous (Other)100%Wollastonite<1%Gray/White/Beige
Non-Fibrous
Homogeneous
081902549-0023
None DetectedNon-fibrous (Other)100%Wollastonite<1%White/Beige
Non-Fibrous
Homogeneous
081902549-0024
None DetectedNon-fibrous (Other)100%Wollastonite<1%White
Non-Fibrous
Homogeneous
Analyst(s)
Rebecca Newman (20)
Remy Sherman (9)
Ryan Shannon, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Plymouth, MI NVLAP Lab Code 101048-4
Initial report from: 09/04/2019 12:16:53
Page 2 of 2ASB_PLM_0008_0001 - 1.78 Printed: 9/4/2019 12:16 PM
OrderID: 081902549
APPENDIX E
INSPECTOR CERTIFICATIONS
APPENDIX F
LAB CERTIFICATIONS
United States Department of Commerce National Institute of Standards and Technology
Certificate of Accreditation to ISO/IEC 17025:2005
NVLAP LAB CODE: 101048-4
EMSL Analytical, Inc.
Plymouth, MI is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:
Asbestos Fiber Analysis
2018-07-01 through 2019-06-30 Effective Dates For the National Voluntary Laboratory Accreditation Program
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2005.
This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique dated January 2009).
United States Department of Commerce National Institute of Standards and Technology
Certificate of Accreditation to ISO/IEC 17025:2005
NVLAP LAB CODE: 101048-4
EMSL Analytical, Inc.
Plymouth, MI is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:
Asbestos Fiber Analysis
2018-07-01 through 2019-06-30 Effective Dates For the National Voluntary Laboratory Accreditation Program
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2005.
This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique dated January 2009).
APPENDIX G
ASBESTOS LOCATIONS & SAMPLE LOCATION DRAWINGS
CASTLE HILL ASSOCIATES, LLC.
DEPARTMENT OF VETERANS AFFAIRS
FAYETTEVILLE VA MEDICAL CENTER
FAYETTEVILLE, NORTH CAROLINA
2019 ASBESTOS REINSPECTION
VA CONTRACT NUMBER: 36C24619N0872
LEGEND
ABC
PROJECT V06-18-102 VISN ASBESTOS SURVEY
ASBESTOS CONTAINING MATERIALS NOT SHOWN ON DRAWINGS
AutoCAD SHX Text ENVIRONMENTAL CONSULTANT: 218-A MECHANIC STREET, WATERVILLE, OHIO 43566 Tel: (567) 952-0212
AutoCAD SHX Text one-quarter inch = one foot
AutoCAD SHX Text one-eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three-eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text one-half inch = one foot
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one and one-half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text three-quarters inch = one foot
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved : Division Chief
AutoCAD SHX Text Approved : Service Director
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Building Number
AutoCAD SHX Text Location
AutoCAD SHX Text Project Title
AutoCAD SHX Text Checked
AutoCAD SHX Text Department of
AutoCAD SHX Text Office of Facilities
AutoCAD SHX Text
AutoCAD SHX Text Drawn
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Project No.
AutoCAD SHX Text Date
AutoCAD SHX Text Veterans Affairs
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text Sheet 01 of 20
AutoCAD SHX Text Revisions
AutoCAD SHX Text Professional Seal:
AutoCAD SHX Text FACILITY ASBESTOS RE-SURVEY VETERANS ADMINISTRATION MEDICAL CENTER FAYETTEVILLE, NORTH CAROLINA
AutoCAD SHX Text V06-18-102
AutoCAD SHX Text
AUGUST 2019
AutoCAD SHX Text
AFS
AutoCAD SHX Text
BLB
AutoCAD SHX Text
FAYETTEVILLE, NORTH CAROLINA
AutoCAD SHX Text Dates
AutoCAD SHX Text
AutoCAD SHX Text
TITLE SHEET
AutoCAD SHX Text North:
AutoCAD SHX Text
CS
AutoCAD SHX Text
ASBESTOS-CONTAINING PIPE INSULATION
AutoCAD SHX Text
ASBESTOS-CONTAINING WINDOW GLAZING AND WINDOW FRAME CAULK
AutoCAD SHX Text
ASBESTOS-CONTAINING 12" OR 9" VINYL FLOOR TILE AND/OR BLACK MASTIC
AutoCAD SHX Text
ASBESTOS-CONTAINING PIPE INSULATION BEHIND WALLS AND ABOVE CEILINGS
AutoCAD SHX Text
ASBESTOS-CONTAINING EXTERIOR DOOR FRAME CAULK
AutoCAD SHX Text
ASBESTOS-CONTAINING EXTERIOR VENT PIPE CAULK
AutoCAD SHX Text
ASBESTOS-CONTAINING EXTERIOR WINDOW FRAME CAULK
N
S
W
E
BUILDING #1 - BASEMENT FLOOR PLAN
LEGEND
AutoCAD SHX Text
FC
AutoCAD SHX Text
FC
AutoCAD SHX Text
FC
AutoCAD SHX Text
FC
AutoCAD SHX Text
FC
AutoCAD SHX Text
GATE
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
AERATOR
AutoCAD SHX Text
STERILIZERS
AutoCAD SHX Text ENVIRONMENTAL CONSULTANT: 218-A MECHANIC STREET, WATERVILLE, OHIO 43566 Tel: (567) 952-0212
AutoCAD SHX Text one-quarter inch = one foot
AutoCAD SHX Text one-eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three-eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text one-half inch = one foot
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one and one-half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text three-quarters inch = one foot
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved : Division Chief
AutoCAD SHX Text Approved : Service Director
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Building Number
AutoCAD SHX Text Location
AutoCAD SHX Text Project Title
AutoCAD SHX Text Checked
AutoCAD SHX Text Department of
AutoCAD SHX Text Office of Facilities
AutoCAD SHX Text
AutoCAD SHX Text Drawn
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Project No.
AutoCAD SHX Text Date
AutoCAD SHX Text Veterans Affairs
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text Sheet 02 of 00
AutoCAD SHX Text Revisions
AutoCAD SHX Text Professional Seal:
AutoCAD SHX Text FACILITY ASBESTOS RE-SURVEY VETERANS ADMINISTRATION MEDICAL CENTER FAYETTEVILLE, NORTH CAROLINA
AutoCAD SHX Text V06-18-102
AutoCAD SHX Text
JULY 2019
AutoCAD SHX Text
AFS
AutoCAD SHX Text
BLB
AutoCAD SHX Text
FAYETTEVILLE, NORTH CAROLINA
AutoCAD SHX Text Dates
AutoCAD SHX Text
AutoCAD SHX Text ARCHITECTURAL PLAN BUILDING 1 Scale: 1/16" = 1'-0"" = 1'-0"
AutoCAD SHX Text North:
AutoCAD SHX Text 1A
ASBESTOS-CONTAINING 12" OR 9" VINYL FLOOR TILE AND/OR BLACK MASTIC
S
W
E
BUILDING #1 - FIRST FLOOR PLAN
LEGEND
AutoCAD SHX Text
FC
AutoCAD SHX Text
COUNTER
AutoCAD SHX Text
FC
AutoCAD SHX Text
FC
AutoCAD SHX Text ENVIRONMENTAL CONSULTANT: 218-A MECHANIC STREET, WATERVILLE, OHIO 43566 Tel: (567) 952-0212
AutoCAD SHX Text one-quarter inch = one foot
AutoCAD SHX Text one-eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three-eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text one-half inch = one foot
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one and one-half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text three-quarters inch = one foot
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved : Division Chief
AutoCAD SHX Text Approved : Service Director
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Building Number
AutoCAD SHX Text Location
AutoCAD SHX Text Project Title
AutoCAD SHX Text Checked
AutoCAD SHX Text Department of
AutoCAD SHX Text Office of Facilities
AutoCAD SHX Text
AutoCAD SHX Text Drawn
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Project No.
AutoCAD SHX Text Date
AutoCAD SHX Text Veterans Affairs
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text Sheet 03 of 00
AutoCAD SHX Text Revisions
AutoCAD SHX Text Professional Seal:
AutoCAD SHX Text FACILITY ASBESTOS RE-SURVEY VETERANS ADMINISTRATION MEDICAL CENTER FAYETTEVILLE, NORTH CAROLINA
AutoCAD SHX Text V06-18-102
AutoCAD SHX Text
JULY 2019
AutoCAD SHX Text
AFS
AutoCAD SHX Text
BLB
AutoCAD SHX Text
FAYETTEVILLE, NORTH CAROLINA
AutoCAD SHX Text Dates
AutoCAD SHX Text
AutoCAD SHX Text ARCHITECTURAL PLAN BUILDING 1 Scale: 1/16" = 1'-0"" = 1'-0"
AutoCAD SHX Text North:
AutoCAD SHX Text 2A
S
W
E
BUILDING #1 - SECOND FLOOR PLAN
LEGEND
AutoCAD SHX Text
VOLUNTARY
AutoCAD SHX Text
SERVICE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FC
AutoCAD SHX Text
TO BUILDING 3
AutoCAD SHX Text
FEC
AutoCAD SHX Text
TO D WING
AutoCAD SHX Text
PLAY AREA
AutoCAD SHX Text ENVIRONMENTAL CONSULTANT: 218-A MECHANIC STREET, WATERVILLE, OHIO 43566 Tel: (567) 952-0212
AutoCAD SHX Text one-quarter inch = one foot
AutoCAD SHX Text one-eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three-eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text one-half inch = one foot
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one and one-half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text three-quarters inch = one foot
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved : Division Chief
AutoCAD SHX Text Approved : Service Director
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Building Number
AutoCAD SHX Text Location
AutoCAD SHX Text Project Title
AutoCAD SHX Text Checked
AutoCAD SHX Text Department of
AutoCAD SHX Text Office of Facilities
AutoCAD SHX Text
AutoCAD SHX Text Drawn
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Project No.
AutoCAD SHX Text Date
AutoCAD SHX Text Veterans Affairs
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text Sheet 04 of 00
AutoCAD SHX Text Revisions
AutoCAD SHX Text Professional Seal:
AutoCAD SHX Text FACILITY ASBESTOS RE-SURVEY VETERANS ADMINISTRATION MEDICAL CENTER FAYETTEVILLE, NORTH CAROLINA
AutoCAD SHX Text V06-18-102
AutoCAD SHX Text
JULY 2019
AutoCAD SHX Text
AFS
AutoCAD SHX Text
BLB
AutoCAD SHX Text
FAYETTEVILLE, NORTH CAROLINA
AutoCAD SHX Text Dates
AutoCAD SHX Text
AutoCAD SHX Text ARCHITECTURAL PLAN BUILDING 1 Scale: 1/16" = 1'-0"" = 1'-0"
AutoCAD SHX Text North:
AutoCAD SHX Text 3A
S
W
E
BUILDING #1 - THIRD FLOOR PLAN
LEGEND
AutoCAD SHX Text
FC
AutoCAD SHX Text
FC
AutoCAD SHX Text
FC
AutoCAD SHX Text
TO BLDG 3
AutoCAD SHX Text
MEDICAL SURGICAL WARD
AutoCAD SHX Text
FC
AutoCAD SHX Text
COUNTER
AutoCAD SHX Text
DESK
AutoCAD SHX Text
HOPPER
AutoCAD SHX Text
FC
AutoCAD SHX Text ENVIRONMENTAL CONSULTANT: 218-A MECHANIC STREET, WATERVILLE, OHIO 43566 Tel: (567) 952-0212
AutoCAD SHX Text one-quarter inch = one foot
AutoCAD SHX Text one-eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three-eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text one-half inch = one foot
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one and one-half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text three-quarters inch = one foot
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved : Division Chief
AutoCAD SHX Text Approved : Service Director
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Building Number
AutoCAD SHX Text Location
AutoCAD SHX Text Project Title
AutoCAD SHX Text Checked
AutoCAD SHX Text Department of
AutoCAD SHX Text Office of Facilities
AutoCAD SHX Text
AutoCAD SHX Text Drawn
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Project No.
AutoCAD SHX Text Date
AutoCAD SHX Text Veterans Affairs
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text Sheet 05 of 00
AutoCAD SHX Text Revisions
AutoCAD SHX Text Professional Seal:
AutoCAD SHX Text FACILITY ASBESTOS RE-SURVEY VETERANS ADMINISTRATION MEDICAL CENTER FAYETTEVILLE, NORTH CAROLINA
AutoCAD SHX Text V06-18-102
AutoCAD SHX Text
JULY 2019
AutoCAD SHX Text
AFS
AutoCAD SHX Text
BLB
AutoCAD SHX Text
FAYETTEVILLE, NORTH CAROLINA
AutoCAD SHX Text Dates
AutoCAD SHX Text
AutoCAD SHX Text ARCHITECTURAL PLAN BUILDING 1 Scale: 1/16" = 1'-0"" = 1'-0"
AutoCAD SHX Text North:
AutoCAD SHX Text 4A
S
W
E
BUILDING #1 - FOURTH FLOOR PLAN
LEGEND
AutoCAD SHX Text
FC
AutoCAD SHX Text
FC
AutoCAD SHX Text
FC
AutoCAD SHX Text
FC
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
FC
AutoCAD SHX Text
CABINET BELOW
AutoCAD SHX Text
DAYROOM KITCHENETTE
AutoCAD SHX Text T.V
AutoCAD SHX Text
TV
AutoCAD SHX Text
REFRIGERATOR
AutoCAD SHX Text T.V.
AutoCAD SHX Text
FEC
AutoCAD SHX Text
FEC
AutoCAD SHX Text ENVIRONMENTAL CONSULTANT: 218-A MECHANIC STREET, WATERVILLE, OHIO 43566 Tel: (567) 952-0212
AutoCAD SHX Text one-quarter inch = one foot
AutoCAD SHX Text one-eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three-eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text one-half inch = one foot
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX…
This is the start of the file's text. The full file is on GovTribe.