Asbestos - Lead Paint Survey 12-31-2020.pdf
PDF 5 MB Posted
- Attached to
- Z2AA - Renovate Historic Building 4 Federal contract opportunity
- Solicitation number
- 36C24624R0030
About this file
This is an asbestos and lead paint survey report conducted by Terracon Consultants Inc. for Building 4 at the Fayetteville Veterans Affairs Medical Center campus in North Carolina, dated December 31, 2020.
The survey identified multiple asbestos-containing materials throughout the approximately 14,000-square-foot building, including air cell pipe insulation (40% chrysotile), various floor tiles and mastics (2-5% chrysotile), carpet glue and black mastic (2% chrysotile), black membrane/mastic (2% chrysotile), and white exterior caulk (5% chrysotile). Fire doors were assumed to contain asbestos. Lead paint sampling detected concentrations above laboratory reporting limits in 38 of 46 paint samples, with levels ranging from 0.024% to 65% by weight on various surfaces including metal doors, wood trim, window frames, columns, and decorative elements. The report provides detailed sampling locations, laboratory results, and photo documentation to support renovation activities planned for the building. The survey was conducted in accordance with EPA and OSHA regulations, with samples analyzed by EMSL Analytical Inc., an accredited laboratory.
View the file
Other files for this federal contract opportunity
Show all 50
Z2AA - Renovate Historic Building 4 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Terracon Consultants, Inc. 2401 Brentwood Road Suite 107 Raleigh, North Carolina 27604
P (919) 873-2211 F (919) 873-9555 terracon.com
December 31, 2020
FFE, Inc.
110 Boggs Lane, Suite 170
Cincinnati, Ohio 45246
Attn: Clint Weekley
P: (513) 522-0956
E: clint.weekley@ffe-serv.com
Re: Asbestos and Lead Paint Survey Report
Fayetteville VAMC Building 4 2300 Ramsey Street Fayetteville, North Carolina 28301 Terracon Project No. 70207552
Dear Mr. Weekley:
The purpose of this report is to present the results of the asbestos and lead paint survey performed on December 7 and 8, 2020 at Building 4 located at the Fayetteville Veterans Affairs Medical
Center campus at 2300 Ramsey Street in Fayetteville, North Carolina. This survey was conducted in general accordance with the Subcontract Agreement between FFE, Inc. (client) and Terracon, dated November 23, 2020. We understand that these services were requested due to the planned renovation of the building.
Asbestos was detected in samples collected from the building. Lead was detected above laboratory reporting limits in samples collected. Please refer to the attached report for details.
Terracon appreciates the opportunity to provide these services to FFE, Inc. If you have any questions regarding this report, please contact the undersigned at (919) 873-2211.
Sincerely, Terracon Consultants Inc.
Alicia Coley, CIH Jeffrey A. Gurrie, CIH
Project Industrial Hygienist Authorized Project Reviewer
ASBESTOS AND LEAD PAINT
SURVEY REPORT
Fayetteville VAMC – Building 4
2300 Ramsey Street
Fayetteville, North Carolina 28301
Prepared For:
FFE, Inc.
Cincinnati, Ohio
Prepared By:
Terracon Consultants, Inc.
Raleigh, North Carolina
TABLE OF CONTENTS
Page No.
1.0 INTRODUCTION
1.1 Project Objective
2.0 BUILDING DESCRIPTION
3.0 FIELD ACTIVITIES
3.1 Asbestos
3.2 Lead Paint
4.0 REGULATORY OVERVIEW
4.1 Asbestos
4.2 Lead Paint
5.0 FINDINGS AND RECOMMENDATIONS
5.1 Asbestos
5.2 Lead Paint
6.0 GENERAL COMMENTS
Appendix A Asbestos Survey Sample Summary
Appendix B Materials Containing Asbestos Summary
Appendix C Asbestos Laboratory Analytical Report
Appendix D Lead Paint Survey Sample Summary
Appendix E Lead Paint Laboratory Analytical Report
Appendix F Photographs
Appendix G Accreditations
Responsive ■ Resourceful ■ Reliable 1
ASBESTOS AND LEAD PAINT SURVEY REPORT
FAYETTEVILLE VAMC – BUILDING 4
2300 RAMSEY STREET
FAYETTEVILLE, NORTH CAROLINA 28301
1.0 INTRODUCTION
Terracon Consultants, Inc. (Terracon) conducted an asbestos survey and lead paint sampling of
Building 4 located at the Fayetteville Veterans Affairs Medical Center campus at 2300 Ramsey
Street in Fayetteville, North Carolina. The survey was conducted on December 7 and 8, 2020 by
State of North Carolina Accredited Asbestos Building Inspectors in general accordance with
Subcontract Agreement between FFE, Inc. (client) and Terracon, dated November 23, 2020.
Building components within the building were visually assessed and homogeneous areas of suspect asbestos-containing materials (ACM) and suspect lead paint coatings were identified and documented. The survey was limited to safely accessible areas of the building. Suspect ACM samples were collected in general accordance with the sampling protocols outlined in
Environmental Protection Agency (EPA) regulation 40 CFR 763 (Asbestos Hazard Emergency
Response Act, AHERA). Suspect ACM samples were delivered to an accredited laboratory for analysis by Polarized Light Microscopy (PLM).
In addition to the asbestos survey, Terracon conducted a lead-containing paint survey. Paint chip samples were collected from representative surfaces and delivered to an accredited laboratory to perform total lead analysis by Flame Atomic Absorption Spectrophotometry (Flame AAS).
1.1 Project Objective
We understand this asbestos survey was requested due to planned renovation of the structure. We understand the purpose of these services is to identify and quantify ACM and lead-containing paint present prior to renovation or demolition activities. EPA regulation 40 CFR 61, Subpart M, National
Emission Standards for Hazardous Air Pollutants (NESHAP), prohibits the release of asbestos fibers to the atmosphere during renovation or demolition activities. The asbestos NESHAP requires that potentially regulated ACM be identified, classified and quantified prior to planned disturbances, renovation or demolition activities.
The Occupational Health and Safety Administration (OSHA) has promulgated a worker protection standard for the disturbance of lead-containing paints during demolition projects. The limited lead paint sampling was performed to meet informational needs to comply with the OSHA Lead in
Construction Standard (29 CRF 1926.62). Currently, proposed renovations or demolition activities which may impact lead paint is subject to OSHA regulation 29 CFR 1926.62 – Lead Exposure in
Construction.
Asbestos and Lead Paint Survey Report
Fayetteville VAMC – Building 4 ■ Fayetteville, North Carolina
December 31, 2020 ■ Terracon Project No. 70207552
Responsive ■ Resourceful ■ Reliable 2
2.0 BUILDING DESCRIPTION
According to client-provided documents, Building 4 is an approximately 14,000-square foot building, reportedly constructed in 1939. The building is a wood and concrete structure atop a concrete slab. The exterior of the building is finished with brick. The main roof is a gable roof with slate tiles. The porch roofs are flat roofs with rolled asphalt roofing. The front portico roof is a flat roof that appears to be finished with metal. Ceilings are finished with acoustical ceiling tile, and/or plaster, or are unfinished. Walls are painted concrete masonry unit (CMU), plaster, or drywall. The floors are finished with vinyl floor tile, carpet, and/or vinyl sheet flooring or are unfinished concrete.
3.0 FIELD ACTIVITIES
3.1 Asbestos
The survey was conducted by state of North Carolina Accredited Asbestos Building Inspectors
Alicia Coley (NC Accredited Asbestos Inspector Number 12548) and Cory Edwards (NC
Accredited Asbestos Inspector Number 12677). The survey was conducted in general accordance with the sample collection protocols established in EPA regulation 40 CFR 763
(AHERA). Copies of applicable accreditations are included in Appendix H. A summary of survey activities is provided below.
3.1.1 Visual Assessment
Our survey activities began with visual observation of the structure to identify homogeneous areas of suspect ACM. A homogeneous area consists of building materials that appear similar throughout in terms of color, texture and date of application. The assessment was conducted throughout visually accessible areas of the building. Building materials identified as concrete, glass, wood, masonry, metal or rubber were not considered suspect ACM.
3.1.2 Physical Assessment
A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material, which can be crumbled, pulverized or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
3.1.3 Sample Collection
Based on results of our visual observations, bulk samples of suspect ACM were collected in general accordance with AHERA sampling protocols. Random samples of suspect materials were collected in each homogeneous area. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
Responsive ■ Resourceful ■ Reliable 3
Terracon collected 108 bulk samples from 35 homogeneous areas of suspect ACM. A summary of suspect ACM samples collected during the survey is included as Appendix A. Photographs are included as Appendix F.
3.1.4 Sample Analysis
Bulk samples were submitted under chain of custody to EMSL Analytical, Inc. (EMSL) of Morrisville, North Carolina for analysis by PLM with dispersion staining techniques per EPA’s Method for the
Determination of Asbestos in Bulk Building Materials (600/R-93-116). The percentage of asbestos, where applicable, was determined by microscopic visual estimation. EMSL is accredited under the
National Voluntary Laboratory Accreditation Program NVLAP (Accreditation Number 200671-0).
The asbestos laboratory analytical report is provided in Appendix C.
3.2 Lead Paint Sampling
The lead paint sampling was conducted by Alicia Coley and Cory Edwards of Terracon. A paint chip sample was collected from homogenous painted surfaces identified to determine its lead content, measured by percent by weight. Suspect lead paint samples were collected in general accordance with the EPA’s work practice standards for conducting lead paint activities (40 CFR
745.227). Currently, proposed renovation and demolition activities that could potentially disturb lead paint are subject to the OSHA regulations (29 CFR 1926.62 – Lead).
The lead paint sampling began with the Terracon representatives walking the structure, observing painted surfaces, and selecting sample locations. After the sampling strategy was determined, Terracon collected 46 paint chip samples from homogeneous surfaces.
Paint chip samples were submitted under a chain of custody to EMSL of Kernersville, North
Carolina. Paint chip samples were analyzed by Flame Atomic Absorption Spectrophotometry method SW846-3050B/7000B. EMSL is an American Industrial Hygiene Association (AIHA)
Environmental Lead Laboratory Accreditation (ELLAP) accredited laboratory (ELLAP, Lab Code
102564), to perform Flame Atomic Absorption Spectrophotometry analysis. A summary of the paint chip samples collected during the survey is presented in Appendix D. The lead paint laboratory analytical report is provided in Appendix E.
4.0 REGULATORY OVERVIEW
4.1 Asbestos
The following sections provide a general overview to the applicable asbestos regulations. Please refer to the complete current regulation in order to verify compliance before any actions are initiated on an ACM.
Responsive ■ Resourceful ■ Reliable 4
4.1.1 NESHAP
The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. It also requires the identification and classification of existing building materials prior to demolition or renovation activities. Under NESHAP, asbestos-containing building materials are classified as either friable, Category I non-friable or Category II non-friable
ACM. Friable materials are those that, when dry, may be crumbled, pulverized or reduced to powder by hand pressure. Category I non-friable ACM includes packings, gaskets, resilient floor coverings and asphalt roofing products containing more than 1% asbestos. Category II non-friable ACM are any materials other than Category I materials that contain more than 1% asbestos.
Friable ACM, Category I and Category II non-friable ACM which is in poor condition and has become friable or which will be subjected to drilling, sanding, grinding, cutting or abrading and which could be crushed or pulverized during anticipated renovation or demolition activities are considered regulated ACM (RACM).
4.1.2 North Carolina State Regulations
In the state of North Carolina, asbestos activities are regulated by the North Carolina Department of Health and Human Services, Health Hazards Control Unit (HHCU) under 10A NCAC 41C Section
.0600 – Asbestos Hazard Management Program (AHMP). The AHMP requires that any asbestos-related activity conducted in a public building be performed by personnel accredited by the HHCU.
Asbestos abatement must be conducted under the direct supervision of a North Carolina accredited supervisor, except that permitted removals of roofing products may be conducted under the direct supervision of a North Carolina accredited roofing supervisor. An asbestos abatement design must be prepared by a North Carolina accredited abatement designer for each individually permitted removal of more than 3000 square feet (281 square meters), 1500 linear feet (462 meters) or 656 cubic feet (18 cubic meters), of regulated asbestos containing materials conducted in public areas.
Third-party air monitoring must be conducted during the abatement activities in accordance with
AHMP requirements.
AHMP requires that no person remove more than 35 cubic feet (1 cubic meter), 160 square feet (15 square meters), or 260 linear feet (80 linear meters) of regulated asbestos containing material, without a permit issued by the HHCU. Applications must be postmarked or received by the HHCU at least 10 working days prior to the scheduled removal start date.
4.1.3 OSHA
OSHA’s general industry asbestos standard (29 CFR 1910.1001) requires employers to exercise due diligence in complying with the requirements to inform their employees and affected contractors working in the facility about the presence and location of both ACM and materials assumed to contain asbestos.
Responsive ■ Resourceful ■ Reliable 5
The OSHA Asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos during construction and maintenance activities. The standard classifies construction and maintenance activities which could disturb ACM, and specifies work practices and precautions which employers must follow when engaging in each class of regulated work. States which administer their own federally-approved state OSHA programs may require additional precautions.
A full copy of the OSHA asbestos standard for general and construction industry may be found at
OSHA’s website (www.osha.gov) and should be referenced for specific information.
4.2 Lead Paint
The lead paint sampling activities were conducted in general accordance with the EPA’s work practice standards for conducting lead paint activities (40 CFR 745, and State and local regulations) to meet informational needs to comply with the OSHA Lead in Construction Standard. Lead is regulated by the Environmental Protection Agency (EPA) and the Occupational Safety and Health
Administration (OSHA).
The Resource Conservation and Recovery Act (RCRA) gave the USEPA authority to regulate the waste status of demolition or renovation debris, including lead-containing materials. Specific notification and testing requirements must be addressed prior to transporting, treating, storing, or disposing of hazardous wastes. Lead containing wastes are considered hazardous waste under
RCRA if Toxicity Characteristic Leaching Procedure (TCLP) results exceed 5 milligrams per liter
(mg/L). EPA exempts from most RCRA requirements those generators whose combined hazardous waste generation is less than 100 kilograms (kg) per month.
Detectable lead quantities may constitute a lead dust hazard during renovation/demolition activities.
Personnel performing renovation/demolition activities that may disturb painted components with concentrations of lead above the designated analytical detection limit should comply with all current
OSHA regulations in order to minimize employee exposure. OSHA defines lead-based paint as a paint, which contains lead, regardless of the concentration. Currently, any proposed renovation/demolition is subject to the OSHA regulations (29 CFR 1926.62 – Lead). The OSHA regulation defines specific training requirements, engineering controls and working practices for construction personnel subject to this standard. Occupational exposure to lead occurring in the course of construction work, including maintenance activities, painting, alteration and repairs is subject to the OSHA Lead Exposure in Construction standard.
Construction work covered by 29 CFR 1926.62 includes any repair or renovation activities or other activities that disturb in-place lead-containing materials, but does not include routine cleaning and repainting where there is insignificant damage, wear, or corrosion of existing lead-containing coatings or substrates. Employers must assure that no employee will be exposed to lead at concentrations greater than 50 micrograms per cubic meter (g/m3) averaged over an eight-hour period without adequate protection. The OSHA Standard also establishes an action level of 30 g/m3 which if exceeded triggers the requirement for medical monitoring.
http://www.osha.gov/
Responsive ■ Resourceful ■ Reliable 6
The above overview is not intended to be inclusive of all potentially pertinent regulatory information.
The relevant EPA and OSHA standards should be consulted prior to undertaking activities involving the demolition, renovation, or maintenance of surfaces coated with lead-based paints.
5.0 FINDINGS AND RECOMMENDATIONS
5.1 Asbestos
Asbestos was identified at concentrations greater than 1% in the following materials:
▪ Air Cell Pipe Insulation
▪ 12” x 12” Beige with Tan Specks Floor Tile and Mastic – mastic assumed to be remaining in areas from previous abatement
▪ 12” x 12” Blue with Red Specks Floor Tile and Mastic - mastic assumed to be remaining in areas from previous abatement
▪ 12” x 12” Tri-blue Floor Tile and Mastic – mastic only
▪ Black Floor Mastic
▪ Carpet Glue and Black Mastic
▪ Black Membrane/Mastic (under ceramic floor tile) – mastic only
▪ Tan Floor Tile and Mastic – mastic only
▪ 12” x 12” Tan with Brown Specks Floor Tile and Mastic – tile and mastic
▪ 12” x 12” Beige with Brown Specks Floor Tile and Mastic – mastic only; floor tile contains
<1% asbestos
▪ White Exterior Caulk at Brick and Wood
In addition, the following material is assumed to contain asbestos in concentrations greater than 1% at the VAMC representative’s request.
▪ Fire Doors
Asbestos was identified at concentrations less than 1% in the following material:
▪ 12” x 12” Beige with Brown Specks Floor Tile and Mastic – floor tile contains <1% asbestos;
mastic contains greater than 1% asbestos
▪ Window Glazing
Regarding materials with less than 1% asbestos, OSHA does regulate these materials and requires specified work practice requirements and prohibitions regardless of exposure levels to employees, including (but not limited to):
▪ Use of wet methods, prompt cleanup and disposal in leak-proof containers;
Responsive ■ Resourceful ■ Reliable 7
▪ Use of compressed air or high-speed abrasive disc saws not equipped with point-of cut ventilators or HEPA-filtered enclosures are prohibited;
▪ The employee is required to document employee exposures via a “competent person” relative to published permissible exposure limits to ascertain expected exposures to asbestos during the work operation.
If additional suspect material is found during renovation or demolition activities, they should be assumed to contain asbestos until laboratory analysis can confirm or deny their asbestos content.
If the final scope of work changes to include areas or materials other than those sampled during this sampling event, additional investigations will be necessary.
Terracon recommends that the identified, assumed, and less than 1% asbestos ACM be removed and disposed of by a State of North Carolina licensed asbestos abatement contractor prior to renovation. Please refer to Appendix B for specific materials and locations of the identified, assumed, and less than 1% asbestos ACM. A summary of suspect materials sampled is provided in Appendix A. Laboratory analytical reports are provided in Appendix C. Photographs are provided in Appendix F.
5.2 Lead Paint
Lead was detected above laboratory reporting limits in 38 of the 46 paint samples collected as listed below:
▪ Green Paint on Metal Door
▪ White Paint on Poured Concrete Wall
▪ White Paint on Concrete at Window
▪ Beige Paint on Metal Stair Post
▪ Beige Paint on Metal Stair Stringer
▪ White Paint on Metal Stair Tread (Exterior Fire Escape)
▪ Red Paint on Metal Stair Roof/Overhang (Exterior Fire Escape)
▪ White Paint on Exterior Wood Fascia
▪ White Paint on Exterior Wood Trim at Soffit
▪ White Paint on Exterior Wood Soffit
▪ Black Paint on Metal Decorative Insert (Parapet Wall)
▪ Red Paint on Metal Stair Handrail (Exterior Fire Escape)
▪ Beige Paint on Wood Window Frame
▪ Gray Paint on Metal I-Beam
▪ Off-white Paint on Plaster – multiple samples
▪ Tan Paint on Wood Shelf (Closet)
▪ Tan Paint on Wood Door (Closet)
▪ Tan Paint on Wood Door
▪ Tan Paint on Metal Door Frame
▪ Beige Paint on Wood Window Sill
Responsive ■ Resourceful ■ Reliable 8
▪ Tan Paint on Metal Radiator Cover
▪ Beige Paint on Metal Radiator Cover
▪ Off-white Paint on Wood Shelf (Closet)
▪ Off-white Paint on Wood Door (Closet)
▪ Off-white Paint on Wood Window Sill
▪ Off-white Paint on Metal Door Frame
▪ Off-white Paint on Wood Door – multiple samples
▪ Off-white Paint on Window Sill
▪ Off-white Paint on Wood Door Trim
▪ Black Paint on Metal Decorative Window Pane Insert
▪ Off-white Paint on Exterior Wood Door Frame
▪ Off-white Paint on Exterior Wood Column
▪ Off-white Paint on Exterior Wood Door
▪ Off-white Paint on Exterior Metal Door
▪ Off-white Paint on Exterior Wood Door Trim
A summary of the paint chip samples collected during the survey is presented in Appendix D.
The lead paint laboratory analytical report is provided in Appendix E.
Contractors should be made aware of the presence of the identified lead coatings, so that they may maintain compliance with worker protection regulations, employ lead-safe work practices, and/or conduct a negative exposure assessment per OSHA (29 CFR 1926.62 – Lead Exposure in
Construction).
6.0 GENERAL COMMENTS
This asbestos and lead paint survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions and recommendations expressed in this report are based on conditions observed during our survey of the building.
This report has been prepared on behalf of and exclusively for use by FFE, Inc. for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information, which may have been used in the preparation of this report. No warranty, expressed or implied is made.
APPENDIX A
ASBESTOS SURVEY SAMPLE SUMMARY
HA Sample No. Description Sample Location Lab Results
1 4-1 Air Cell Pipe Insulation Crawlspace 40% Chrysotile
1 4-2 Air Cell Pipe Insulation Crawlspace Positive Stop (Not Analyzed)
1 4-3 Air Cell Pipe Insulation Crawlspace Positive Stop (Not Analyzed)
2 4-4 Felt Paper Crawlspace None Detected
2 4-5 Felt Paper Crawlspace None Detected
2 4-6 Felt Paper Crawlspace None Detected
3 4-7 Black Waterproofing Crawlspace None Detected
3 4-8 Black Waterproofing Crawlspace None Detected
3 4-9 Black Waterproofing Crawlspace None Detected
4 4-10 Window Glazing Crawlspace <1% Chrysotile
4 4-11 Window Glazing Crawlspace <1% Chrysotile
4 4-12 Window Glazing Crawlspace <1% Chrysotile
5 4-13 White Sealant Crawlspace None Detected
5 4-14 White Sealant Crawlspace None Detected
5 4-15 White Sealant Crawlspace None Detected
6 4-16 Canvas Wrap over Mud Mechanical Room - Tank Wrap: None Detected
Mud: None Detected
6 4-17 Canvas Wrap over Mud Mechanical Room - Tank Wrap: None Detected
Mud: None Detected
6 4-18 Canvas Wrap over Mud Mechanical Room - Tank Wrap: None Detected
Mud: None Detected
7 4-19 White Mastic Mechanical Room - Fiberglass
Duct Insulation None Detected
7 4-20 White Mastic Mechanical Room - Fiberglass
Duct Insulation None Detected
7 4-21 White Mastic Mechanical Room - Fiberglass
Duct Insulation None Detected
8 4-22 2'x2' White Ceiling Tile with Dots and Small
Lines Basement Hallway at Rm. 002 None Detected
8 4-23 2'x2' White Ceiling Tile with Dots and Small
Lines Room 009 None Detected
8 4-24 2'x2' White Ceiling Tile with Dots and Small
Lines Room 117 None Detected
9 4-25 Drywall, Joint Compound Basement Hallway at Rm. 002 Composite: None Detected
9 4-26 Drywall, Joint Compound Rm. 010 - Men's Restroom Composite: None Detected
9 4-27 Drywall, Joint Compound Room 009 Composite: None Detected
10 4-28 Brown Fire Caulk Basement Hallway at Rm. 002 None Detected
10 4-29 Brown Fire Caulk Basement Hallway at Rm. 002 None Detected
10 4-30 Brown Fire Caulk Basement Hallway at Rm. 002 None Detected
11 4-31 12"x12" Beige with Tan Specks Floor Tile and Mastic Basement Hallway at Rm. 002
Floor Tile: None Detected
Mastic: None Detected
11 4-32 12"x12" Beige with Tan Specks Floor Tile and Mastic Basement Hallway at Rm. 009
Floor Tile: None Detected
Mastic: None Detected
11 4-33 12"x12" Beige with Tan Specks Floor Tile and Mastic Basement Hallway at Rm. 011
Floor Tile: None Detected
Mastic: None Detected
Fayetteville, North Carolina
Terracon Project No. 70207552
Appendix A
ASBESTOS SURVEY SAMPLE SUMMARY
2300 Ramsey Street
Fayetteville VAMC - Building 4
A-1
Fayetteville, North Carolina
Terracon Project No. 70207552
Appendix A
ASBESTOS SURVEY SAMPLE SUMMARY
2300 Ramsey Street
Fayetteville VAMC - Building 4
12 4-34 12" x 12" Blue with White and Red
Specks Floor Tile and Mastic Room 002
Floor Tile: None Detected
Mastic: None Detected
12 4-35 12" x 12" Blue with White and Red
Specks Floor Tile and Mastic Room 006
Floor Tile: None Detected
Mastic: 5% Chrysotile
12 4-36 12" x 12" Blue with White and Red
Specks Floor Tile and Mastic Room 005
Floor Tile: None Detected
Mastic: Positive Stop (Not Analyzed)
13 4-37 6" Navy Blue Cove Base and Mastic Basement Hallway at Rm. 002 Cove Base: None Detected
Mastic: None Detected
13 4-38 6" Navy Blue Cove Base and Mastic Basement Hallway at Rm. 011 Cove Base: None Detected
Mastic: None Detected
13 4-39 6" Navy Blue Cove Base and Mastic Room 006 Cove Base: None Detected
Mastic: None Detected
14 4-40 Plaster Basement Hallway at Rm. 004 Skim Coat: None Detected
Base Coat: None Detected
14 4-41 Plaster Room 011 - Women's
Restroom
Skim Coat: None Detected
Base Coat: None Detected
14 4-42 Plaster Room 117 Skim Coat: None Detected
Base Coat: None Detected
14 4-43 Plaster Room 117 Skim Coat: None Detected
Base Coat: None Detected
14 4-44 Plaster Room 111 Skim Coat: None Detected
Base Coat: None Detected
14 4-45 Plaster 2nd Floor Hallway at Rm. 211 Skim Coat: None Detected
Base Coat: None Detected
14 4-46 Plaster 2nd Floor Hallway at Rm. 212 Skim Coat: None Detected
Base Coat: None Detected
15 4-47 Black Floor Mastic Room 012 5% Chrysotile
15 4-48 Black Floor Mastic 1st Floor Hallway at Rm. 113 Positive Stop (Not Analyzed)
15 4-49 Black Floor Mastic 1st Floor Hallway at Rm. 113 Positive Stop (Not Analyzed)
16 4-50 CMU Surface Block Filler Room 012 None Detected
16 4-51 CMU Surface Block Filler Room 012 None Detected
16 4-52 CMU Surface Block Filler Room 012 None Detected
17 4-53 White Ceramic Wall Tile Mastic and Grout Room 011 - Women's
Restroom
Mastic: None Detected
Grout: None Detected
17 4-54 White Ceramic Wall Tile Mastic and Grout Room 011 - Women's
Restroom
Mastic: None Detected
Grout: None Detected
17 4-55 White Ceramic Wall Tile Mastic and Grout Room 011 - Women's
Restroom
Mastic: None Detected
Grout: None Detected
18 4-56 2'x2' White Ceiling Tile with Dots and Lines Room 010 - Men's Restroom
Closet None Detected
18 4-57 2'x2' White Ceiling Tile with Dots and Lines Room 118 None Detected
18 4-58 2'x2' White Ceiling Tile with Dots and Lines Room 120 None Detected
19 4-59 2' x 4' White Ceiling Tile with Dots and Lines Room 011 - Women's
Restroom None Detected
19 4-60 2' x 4' White Ceiling Tile with Dots and Lines Room 109 None Detected
19 4-61 2' x 4' White Ceiling Tile with Dots and Lines Room 109 None Detected
20 4-62 2" Tan Porcelain Floor Tile Mortar and Grout Room 010 - Men's Restroom Mortar: None Detected
Grout: None Detected
20 4-63 2" Tan Porcelain Floor Tile Mortar and Grout Room 010 - Men's Restroom Mortar: None Detected
Grout: None Detected
A-2
Terracon Project No. 70207552
Appendix A
ASBESTOS SURVEY SAMPLE SUMMARY
2300 Ramsey Street
Fayetteville VAMC - Building 4
20 4-64 2" Tan Porcelain Floor Tile Mortar and Grout Room 010 - Men's Restroom Mortar: None Detected
Grout: None Detected
21 4-65 Blue with White and Blue Specks Vinyl
Sheet Flooring Room 004
Sheet Flooring 1: None Detected
Sheet Flooring 2: None Detected
Mastic: None Detected
21 4-66 Blue with White and Blue Specks Vinyl
Sheet Flooring Room 004
Sheet Flooring 1: None Detected
Sheet Flooring 2: None Detected
Mastic: None Detected
21 4-67 Blue with White and Blue Specks Vinyl
Sheet Flooring Room 004
Sheet Flooring 1: None Detected
Sheet Flooring 2: None Detected
Mastic: None Detected
22 4-68 4" Cream Cove Base and Mastic Room 004 Cove Base: None Detected
Mastic: None Detected
22 4-69 4" Cream Cove Base and Mastic Room 004 Cove Base: None Detected
Mastic: None Detected
22 4-70 4" Cream Cove Base and Mastic Room 004 Cove Base: None Detected
Mastic: None Detected
23 4-71 Red Fire Caulk Room 010 - Men's Restroom
Closet None Detected
23 4-72 Red Fire Caulk Room 010 - Men's Restroom
Closet None Detected
23 4-73 Red Fire Caulk Room 010 - Men's Restroom
Closet None Detected
24 4-74 Off-white Duct Mastic on Foil-backed
Fiberglass Insulation Room 010 - Men's Restroom Mastic: None Detected
24 4-75 Off-white Duct Mastic on Foil-backed
Fiberglass Insulation Room 004 Mastic: None Detected
24 4-76 Off-white Duct Mastic on Foil-backed
Fiberglass Insulation Room 004 Mastic: None Detected
25 4-77 Green Faux Terrazzo Vinyl Sheet Flooring Room 004 None Detected
25 4-78 Green Faux Terrazzo Vinyl Sheet Flooring Room 004 None Detected
25 4-79 Green Faux Terrazzo Vinyl Sheet Flooring Room 004 None Detected
26 4-80 2'x4' White Ceiling Tile with Dots and Y's Room 004 None Detected
26 4-81 2'x4' White Ceiling Tile with Dots and Y's Room 004 None Detected
26 4-82 2'x4' White Ceiling Tile with Dots and Y's Room 004 None Detected
27 4-83 Gray Stair Tread and Mastic Basement Stair Tread: None Detected
Mastic: None Detected
27 4-84 Gray Stair Tread and Mastic Basement Stair Tread: None Detected
Mastic: None Detected
27 4-85 Gray Stair Tread and Mastic Basement Stair Tread: None Detected
Mastic: None Detected
28 4-86 4" Black Cove Base and Mastic Room 009 Cove Base: None Detected
Mastic: None Detected
28 4-87 4" Black Cove Base and Mastic Room 009 Cove Base: None Detected
Mastic: None Detected
28 4-88 4" Black Cove Base and Mastic Room 009 Cove Base: None Detected
Mastic: None Detected
29 4-89 Carpet Glue and Black Mastic Room 009 Glue: None Detected
Mastic: 2% Chrysotile
29 4-90 Carpet Glue and Black Mastic Room 009 Glue: None Detected
Mastic: Positive Stop (Not Analyzed)
29 4-91 Carpet Glue and Black Mastic Room 009 Glue: <1% Chrysotile
Mastic: Positive Stop (Not Analyzed)
A-3
Terracon Project No. 70207552
Appendix A
ASBESTOS SURVEY SAMPLE SUMMARY
2300 Ramsey Street
Fayetteville VAMC - Building 4
30 4-92 12"x12" Tri-blue Floor Tile and Mastic Rm. 008 - Mechanical Floor Tile: None Detected
Mastic: 5% Chrysotile
30 4-93 12"x12" Tri-blue Floor Tile and Mastic Rm. 008 - Mechanical Floor Tile: None Detected
Mastic: Positive Stop (Not Analyzed)
30 4-94 12"x12" Tri-blue Floor Tile and Mastic Rm. 008 - Mechanical Floor Tile: None Detected
Mastic: Positive Stop (Not Analyzed)
31 4-95 Blue Fire Caulk Room 007B None Detected
31 4-96 Blue Fire Caulk Room 007B None Detected
31 4-97 Blue Fire Caulk Room 007B None Detected
32 4-98 Black Tar Room 007B - Ceiling
Penetrations None Detected
32 4-99 Black Tar Room 007B - Ceiling
Penetrations None Detected
32 4-100 Black Tar Room 007B - Ceiling
Penetrations None Detected
33 4-101 6" Brown Cove Base and Mastic Room 117 Cove Base: None Detected
Mastic: None Detected
33 4-102 6" Brown Cove Base and Mastic Room 117 Cove Base: None Detected
Mastic: None Detected
33 4-103 6" Brown Cove Base and Mastic Room 121 Cove Base: None Detected
Mastic: None Detected
34 4-104 Drywall, Joint Compound Room 117 Composite: None Detected
34 4-105 Drywall, Joint Compound Room 101 Composite: None Detected
34 4-106 Drywall, Joint Compound Room 102 Composite: None Detected
35 4-107 6" Gray Cove Base and Mastic Room 203B Cove Base: None Detected
Mastic: None Detected
35 4-108 6" Gray Cove Base and Mastic 2nd Floor Hallway at Rm. 212 Cove Base: None Detected
Mastic: None Detected
35 4-109 6" Gray Cove Base and Mastic 2nd Floor Hallway at Rm. 218 Cove Base: None Detected
Mastic: None Detected
36 4-110 12"x12" Off-white with Tan Specks Floor
Tile and Mastic Room 120
Floor Tile: None Detected
Mastic: None Detected
Leveler: None Detected
36 4-111 12"x12" Off-white with Tan Specks Floor
Tile and Mastic Room 102
Floor Tile: None Detected
Mastic: None Detected
Leveler: None Detected
36 4-112 12"x12" Off-white with Tan Specks Floor
Tile and Mastic 1st Floor Lobby
Floor Tile: None Detected
Mastic: None Detected
Leveler: None Detected
37 4-113 6" Black Cove Base and Mastic Room 120 Cove Base: None Detected
Mastic: None Detected
37 4-114 6" Black Cove Base and Mastic Room 120 Cove Base: None Detected
Mastic: None Detected
37 4-115 6" Black Cove Base and Mastic Room 120 Cove Base: None Detected
Mastic: None Detected
38 4-116 2'x4' White Ceiling Tile with Dots and Wide
Lines Room 116 - Restroom None Detected
38 4-117 2'x4' White Ceiling Tile with Dots and Wide
Lines Room 116 - Restroom None Detected
38 4-118 2'x4' White Ceiling Tile with Dots and Wide
Lines Room 116 - Restroom None Detected
39 4-119 12"x12" Tan with Brown Specks Floor
Tile and Mastic Room 116 - Restroom Closet
Floor Tile: 2% Chrysotile
Mastic: 2% Chrysotile
39 4-120 12"x12" Tan with Brown Specks Floor
Tile and Mastic Room 116 - Restroom Closet Positive Stop (Not Analyzed)
A-4
Terracon Project No. 70207552
Appendix A
ASBESTOS SURVEY SAMPLE SUMMARY
2300 Ramsey Street
Fayetteville VAMC - Building 4
39 4-121 12"x12" Tan with Brown Specks Floor
Tile and Mastic Room 116 - Restroom Closet Positive Stop (Not Analyzed)
40 4-122 Black Membrane/Mastic Room 116 - Restroom (Under
Tile Floor)
Membrane: None Detected
Mastic: 2% Chrysotile
40 4-123 Black Membrane/Mastic Room 116 - Restroom (Under
Tile Floor)
Membrane: None Detected
Mastic: Positive Stop (Not Analyzed)
40 4-124 Black Membrane/Mastic Room 116 - Restroom (Under
Tile Floor)
Membrane: None Detected
Mastic: Positive Stop (Not Analyzed)
41 4-125 Ceramic Floor Tile Mortar and Grout Room 116 - Restroom Mortar: None Detected
Grout: None Detected
41 4-126 Ceramic Floor Tile Mortar and Grout Room 116 - Restroom Mortar: None Detected
Grout: None Detected
41 4-127 Ceramic Floor Tile Mortar and Grout Room 116 - Restroom Mortar: None Detected
Grout: None Detected
42 4-128 Green Ceramic Wall Tile Mastic and
Grout Room 116 - Restroom
Mastic: 3% Chrysotile (Contaminated with Mastic from HA 40)
Grout: None Detected
42 4-129 Green Ceramic Wall Tile Mastic and
Grout Room 116 - Restroom
Mastic: Positive Stop (Not Analyzed)
Grout: None Detected
42 4-130 Green Ceramic Wall Tile Mastic and
Grout Room 116 - Restroom
Mastic: Positive Stop (Not Analyzed)
Grout: None Detected
43 4-131 Tan Carpet Glue Room 203 None Detected
43 4-132 Tan Carpet Glue Room 107 None Detected
43 4-133 Tan Carpet Glue Room 207 None Detected
44 4-134 Tan Carpet Glue and White Leveling
Compound 1st Floor Hallway at Rm. 113
Glue: None Detected
Leveling Compound: None Detected
44 4-135 Tan Carpet Glue and White Leveling
Compound 1st Floor Hallway at Rm. 113
Glue: None Detected
Leveling Compound: None Detected
44 4-136 Tan Carpet Glue and White Leveling
Compound 1st Floor Hallway at Rm. 113
Glue: None Detected
Leveling Compound: None Detected
45 4-137 Pink Ceramic Floor Tile Mortar and Grout Room 112 - Restroom Mortar: None Detected
Grout: None Detected
45 4-138 Pink Ceramic Floor Tile Mortar and Grout Room 112 - Restroom Mortar: None Detected
Grout: None Detected
45 4-139 Pink Ceramic Floor Tile Mortar and Grout Room 112 - Restroom Mortar: None Detected
Grout: None Detected
46 4-140 Pink Fire Caulk Room 111 - Housekeeping None Detected
46 4-141 Pink Fire Caulk Room 111 - Housekeeping None Detected
46 4-142 Pink Fire Caulk Room 111 - Housekeeping None Detected
47 4-143 White HVAC Duct Tape Room 109A None Detected
47 4-144 White HVAC Duct Tape Room 109A None Detected
47 4-145 White HVAC Duct Tape Room 109A None Detected
48 4-146 Tan Floor Tile and Mastic 1st Floor Lobby at Stairs
(Bottom Layer)
Floor Tile: None Detected
Mastic: <1% Chrysotile
48 4-147 Tan Floor Tile and Mastic 1st Floor Lobby at Stairs
(Bottom Layer)
Floor Tile: None Detected
Mastic: <1% Chrysotile
48 4-148 Tan Floor Tile and Mastic 1st Floor Lobby at Stairs
(Bottom Layer)
Floor Tile: None Detected
Mastic 1: 5% Chrysotile
Mastic 2: None Detected
49 4-149 Faux Wood Flooring Room 105 Closet None Detected
49 4-150 Faux Wood Flooring Room 105 Closet None Detected
A-5
Terracon Project No. 70207552
Appendix A
ASBESTOS SURVEY SAMPLE SUMMARY
2300 Ramsey Street
Fayetteville VAMC - Building 4
49 4-151 Faux Wood Flooring Room 105 Closet None Detected
50 4-152 18"x18" Tan/Gray Faux Stone Pattern Vinyl
Floor Tile 2nd Floor - Kitchen
Floor Tile: None Detected
Mastic: None Detected
50 4-153 18"x18" Tan/Gray Faux Stone Pattern Vinyl
Floor Tile 2nd Floor - Kitchen
Floor Tile: None Detected
Mastic: None Detected
50 4-154 18"x18" Tan/Gray Faux Stone Pattern Vinyl
Floor Tile 2nd Floor - Kitchen
Floor Tile: None Detected
Mastic: None Detected
51 4-155 12"x12" Tri-brown Floor Tile and Mastic 2nd Floor - Kitchen Floor Tile: None Detected
Mastic: None Detected
51 4-156 12"x12" Tri-brown Floor Tile and Mastic 2nd Floor - Kitchen Floor Tile: None Detected
Mastic: None Detected
51 4-157 12"x12" Tri-brown Floor Tile and Mastic 2nd Floor - Kitchen Floor Tile: None Detected
Mastic: None Detected
52 4-158 12"x12" Beige with Brown Specks Floor
Tile and Mastic
2nd Floor - Kitchen (Bottom
Layer)
Floor Tile: <1% Chrysotile
Mastic 1: 3% Chrysotile
Mastic 2: None Detected
52 4-159 12"x12" Beige with Brown Specks Floor
Tile and Mastic
2nd Floor - Kitchen (Bottom
Layer)
Floor Tile: <1% Chrysotile
Mastic 1: Positive Stop (Not Analyzed)
Mastic 2: None Detected
52 4-160 12"x12" Beige with Brown Specks Floor
Tile and Mastic 2nd Floor - Stairwell
Floor Tile: <1% Chrysotile
Mastic 1: Positive Stop (Not Analyzed)
Mastic 2: Layer Not Present
53 4-161 Gray Leveling Compound Room 207 Leveling Compound: None Detected
Mastic: None Detected
53 4-162 Gray Leveling Compound Room 207 Leveling Compound: None Detected
Mastic: None Detected
53 4-163 Gray Leveling Compound 2nd Floor Hallway at Rm. 205 Leveling Compound: None Detected
Mastic: None Detected
54 4-164 Blue and White Ceramic Wall Tile Mastic and Grout
Room 210 - Women's
Restroom
Mastic: None Detected
Grout: None Detected
54 4-165 Blue and White Ceramic Wall Tile Mastic and Grout
Room 210 - Women's
Restroom
Mastic: None Detected
Grout: None Detected
54 4-166 Blue and White Ceramic Wall Tile Mastic and Grout
Room 210 - Women's
Restroom
Mastic: None Detected
Grout: None Detected
55 4-167 Blue and Gray Ceramic Floor Tile Mortar and Grout
Room 210 - Women's
Restroom
Mortar: None Detected
Grout: None Detected
55 4-168 Blue and Gray Ceramic Floor Tile Mortar and Grout
Room 210 - Women's
Restroom
Mortar: None Detected
Grout: None Detected
55 4-169 Blue and Gray Ceramic Floor Tile Mortar and Grout
Room 210 - Women's
Restroom
Mortar: None Detected
Grout: None Detected
56 4-170 Gray Roof Caulk Flat Roof on North End of
Building - 2nd Floor Access None Detected
56 4-171 Gray Roof Caulk Flat Roof on North End of
Building - 2nd Floor Access None Detected
56 4-172 Gray Roof Caulk Flat Roof on North End of
Building - 2nd Floor Access None Detected
57 4-173 Beige Roof Caulk Flat Roof on North End of
Building - 2nd Floor Access None Detected
57 4-174 Beige Roof Caulk Flat Roof on North End of
Building - 2nd Floor Access None Detected
57 4-175 Beige Roof Caulk Flat Roof on North End of
Building - 2nd Floor Access None Detected
58 4-176 Gray Rolled Asphalt Roofing Flat Roof on North End of
Building - 2nd Floor Access
Shingle 1: None Detected
Shingle 2: None Detected
58 4-177 Gray Rolled Asphalt Roofing Flat Roof on North End of
Building - 2nd Floor Access
Shingle 1: None Detected
Shingle 2: None Detected
A-6
Terracon Project No. 70207552
Appendix A
ASBESTOS SURVEY SAMPLE SUMMARY
2300 Ramsey Street
Fayetteville VAMC - Building 4
58 4-178 Gray Rolled Asphalt Roofing Flat Roof on North End of
Building - 2nd Floor Access
Shingle 1: None Detected
Shingle 2: None Detected
59 4-179 Black Flashing Flat Roof on North End of
Building - 2nd Floor Access
Roofing 1: None Detected
Roofing 2: None Detected
Roofing 3: None Detected
Roofing 4: None Detected
59 4-180 Black Flashing Flat Roof on North End of
Building - 2nd Floor Access
Roofing 1: None Detected
Roofing 2: None Detected
Roofing 3: Layer Not Present
Roofing 4: None Detected
59 4-181 Black Flashing Flat Roof on North End of
Building - 2nd Floor Access
Roofing 1: None Detected
Roofing 2: None Detected
Roofing 3: Layer Not Present
Roofing 4: None Detected
60 4-182 White Interior Window Caulk Attic None Detected
60 4-183 White Interior Window Caulk Attic None Detected
60 4-184 White Interior Window Caulk Attic None Detected
61 4-185 Roofing Felt Paper Attic None Detected
61 4-186 Roofing Felt Paper Attic None Detected
61 4-187 Roofing Felt Paper Attic None Detected
62 4-188 Gray Duct Mastic Attic None Detected
62 4-189 Gray Duct Mastic Attic None Detected
62 4-190 Gray Duct Mastic Attic None Detected
63 4-191 Brown Cellulose Board over Black
Felt/Mastic Room 116 - Restroom
Fiberboard: None Detected
Felt/Mastic: None Detected
63 4-192 Brown Cellulose Board over Black
Felt/Mastic Room 116 - Restroom
Fiberboard: None Detected
Felt/Mastic: None Detected
63 4-193 Brown Cellulose Board over Black
Felt/Mastic Room 116 - Restroom
Fiberboard: None Detected
Felt/Mastic: None Detected
64 4-194 White Exterior Caulk - at Brick and Wood Exterior - South Door None Detected
64 4-195 White Exterior Caulk - at Brick and Wood Exterior - North Window None Detected
64 4-196 White Exterior Caulk - at Brick and Wood Exterior - Front Door 5% Chrysotile
65 4-197 White Exterior Caulk - at Metal Window
Trim Exterior - South Window None Detected
65 4-198 White Exterior Caulk - at Metal Window
Trim Exterior -North Window None Detected
65 4-199 White Exterior Caulk - at Metal Window
Trim Exterior - Southwest Window None Detected
66 4-200 White Expansion Joint Caulk Exterior - ADA Ramp at South
End of Building None Detected
66 4-201 White Expansion Joint Caulk Exterior - ADA Ramp at South
End of Building None Detected
66 4-202 White Expansion Joint Caulk Exterior - ADA Ramp at South
End of Building None Detected
67 4-203 Tan Exterior Caulk Exterior - East Door None Detected
67 4-204 Tan Exterior Caulk Exterior - East Window None Detected
67 4-205 Tan Exterior Caulk Exterior - West Window None Detected
*Highlighted samples indicate materials with <1% asbestos.
*Highlighted and bolded samples indicate materials with >1% asbestos.
A-7
APPENDIX B
MATERIALS CONTAINING ASBESTOS SUMMARY
HA Sample No. Description Material Location
NESHAP
Classification
Percent/Type
Asbestos Condition
Estimated
Quantity*
1 4-1 Air Cell Pipe Insulation
Interior Pipe Chases;
Steam Pipe Chases
Outside Building
Footprint
Friable 40% Chrysotile Unknown Unknown
11 4-31
12"x12" Beige with Tan
Specks Floor Tile and
Mastic*
12 4-35
12" x 12" Blue with White and Red Specks Floor
Tile and Mastic (Pattern with HA 11)
30 4-92 12"x12" Tri-blue Floor Tile and Mastic
Rm. 008 -
Mechanical Room
Category I
Non-Friable
Floor Tile: None Detected
Mastic: 5% Chrysotile Good
15 4-47 Black Floor Mastic Category I
Non-Friable 5% Chrysotile Good
4-89
4-90
Carpet Glue and Black
Mastic
Category I
Non-Friable
Glue: <1% Chrysotile
(inseparable from mastic)
Mastic: 2% Chrysotile
Good
40 4-122 Black Membrane/Mastic Category I
Non-Friable
Membrane: None Detected
Mastic: 2% Chrysotile Good
42 4-128 Green Ceramic Wall Tile
Mastic and Grout
Category I
Non-Friable
Mastic: 3% Chrysotile
(Contaminated with Mastic from HA 40)
Grout: None Detected
Good
4-146
4-147
4-148
Tan Floor Tile and Mastic 1st Floor Lobby at
Stairs (Bottom Layer)
Category I
Non-Friable
Floor Tile: None Detected
Mastic 1: <1 - 5% Chrysotile Good
50 Square
Feet
39 4-119
12"x12" Tan with Brown
Specks Floor Tile and
Mastic
Room 116 -
Restroom Closet
Category I
Non-Friable
Floor Tile: 2% Chrysotile
Mastic: 2% Chrysotile Good
10 Square
Feet
52 4-158
12"x12" Beige with Brown
Specks Floor Tile and
Mastic
Throughout 2nd Floor Category I
Non-Friable
Floor Tile: <1% Chrysotile
Mastic 1: 3% Chrysotile
Mastic 2: None Detected
Good 4,500 Square
Feet
64 4-196 White Exterior Caulk - at
Brick and Wood
Front Door - Main
Entrance
Category II
Non-Friable 5% Chrysotile Good
10 Square
Feet
HA Sample No. Description Material Location
NESHAP
Classification
Percent/Type
Asbestos Condition
Estimated
Quantity*
Fire Doors Throughout Building Friable Assumed Good Approximately
15 Doors
600 Square
Feet
Terracon Project No. 70207552
Appendix B
MATERIALS CONTAINING ASBESTOS SUMMARY
2300 Ramsey Street
Fayetteville, North Carolina
MATERIALS CONTAINING GREATER THAN 1% ASBESTOS
Fayetteville VAMC - Building 4
ASSUMED ASBESTOS-CONTAINING MATERIALS
N/A
Throughout
Basement
Category I
Non-Friable
Floor Tile: None Detected
Mastic: 5% Chrysotile
(*asbestos-containing mastic associated with HA
12 is assumed to be homogeneous to HA 11;
asbestos-containing mastic may remain in various areas following a previous abatement)
Good
Under Ceramic Floor
Tile and 1st Foot Up from Floor on Wall
Room 009, 012; 1st
Floor North
2,500 Square
Feet
4,500 Square
Feet
B-1
HA Sample No. Description Material Location
NESHAP
Classification
Percent/Type
Asbestos Condition
Estimated
Quantity*
Terracon Project No. 70207552
Appendix B
MATERIALS CONTAINING ASBESTOS SUMMARY
2300 Ramsey Street
Fayetteville, North Carolina
MATERIALS CONTAINING GREATER THAN 1% ASBESTOS
Fayetteville VAMC - Building 4
HA Sample No. Description Material Location
NESHAP
Classification
Percent/Type
Asbestos Condition
Estimated
Quantity*
4 4-10 Window Glazing Crawlspace (remnant
- not installed) N/A <1% Chrysotile Damaged 1 Window
Note: All quantities should be verified by the asbestos abatement contractor.
MATERIALS 1% OR LESS ASBESTOS
B-2
APPENDIX C
ASBESTOS LABORATORY ANALYTICAL REPORT
EMSL Analytical, Inc.
2500 Gateway Centre Blvd., Suite 600 Morrisville, NC 27560
Tel/Fax: (919) 465-3900 / (919) 465-3950 http://www.EMSL.com / raleighlab@emsl.com
292012881EMSL Order:
Customer ID: TITA51
Customer PO: 70207552
Project ID:
Attention: Phone:Cory Edwards (919) 873-2211
Fax:Terracon Consultants, Inc. (919) 873-9555
Received Date:2401 Brentwood Road 12/10/2020 12:51 PM
Analysis Date:Suite 107 12/15/2020 - 12/29/2020
Collected Date:Raleigh, NC 27604
Project: 70207552, VAMC Bldg 4
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
4-1
292012881-0001
40% ChrysotileNon-fibrous (Other)20%Cellulose40%Brown/Gray
Fibrous
Homogeneous
Crawlspace - Air Cell
Pipe Insulation
4-2
292012881-0002
Positive Stop (Not Analyzed)Crawlspace - Air Cell
Pipe Insulation
4-3
292012881-0003
Positive Stop (Not Analyzed)Crawlspace - Air Cell
Pipe Insulation
4-4
292012881-0004
None DetectedNon-fibrous (Other)35%Cellulose65%Brown
Fibrous
Homogeneous
Crawlspace - Felt
Paper
4-5
292012881-0005
None DetectedNon-fibrous (Other)35%Cellulose65%Brown
Fibrous
Homogeneous
Crawlspace - Felt
Paper
4-6
292012881-0006
None DetectedNon-fibrous (Other)35%Cellulose
Synthetic
45%
20%
Black
Fibrous
Homogeneous
Crawlspace - Felt
Paper
4-7
292012881-0007
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Cellulose<1%Black
Non-Fibrous
Homogeneous
Crawlspace - Black
Waterproofing
4-8
292012881-0008
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Cellulose<1%Black
Non-Fibrous
Homogeneous
Crawlspace - Black
Waterproofing
4-9
292012881-0009
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
20%
40%
40%
Gray
Non-Fibrous
Homogeneous
Crawlspace - Black
Waterproofing
4-10
292012881-0010
<1% ChrysotileCa Carbonate
Non-fibrous (Other)
25%
75%
Gray
Non-Fibrous
Homogeneous
Crawlspace - Window
Glazing
4-11
292012881-0011
<1% ChrysotileCa Carbonate
Non-fibrous (Other)
25%
75%
Gray
Non-Fibrous
Homogeneous
Crawlspace - Window
Glazing
4-12
292012881-0012
<1% ChrysotileCa Carbonate
Non-fibrous (Other)
25%
75%
Gray
Non-Fibrous
Homogeneous
Crawlspace - Window
Glazing
4-13
292012881-0013
None DetectedCa Carbonate
Non-fibrous (Other)
15%
81%
Wollastonite
Fibrous (Other)
2%
2%
White
Fibrous
Homogeneous
Crawlspace - White
Sealant
4-14
292012881-0014
None DetectedCa Carbonate
Non-fibrous (Other)
15%
81%
Wollastonite
Fibrous (Other)
2%
2%
White
Fibrous
Homogeneous
Crawlspace - White
Sealant
4-15
292012881-0015
None DetectedCa Carbonate
Non-fibrous (Other)
10%
90%
White/Black
Non-Fibrous
Homogeneous
Crawlspace - White
Sealant
4-16-Wrap
292012881-0016
None DetectedCa Carbonate
Non-fibrous (Other)
10%
15%
Cellulose75%White
Fibrous
Homogeneous
Mechanical Room -
Tank - Canvas Wrap over Mud
Initial report from: 12/17/2020 10:35:35
Page 1 of 21ASB_PLM_0008_0001 - 1.78 Printed: 12/29/2020 10:20 AM
Tel/Fax: (919) 465-3900 / (919) 465-3950 http://www.EMSL.com / raleighlab@emsl.com
292012881EMSL Order:
Customer ID: TITA51
Customer PO: 70207552
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
4-16-Mud
292012881-0016A
None DetectedCa Carbonate
Non-fibrous (Other)
30%
40%
Min. Wool30%Gray
Fibrous
Homogeneous
Mechanical Room -
Tank - Canvas Wrap over Mud
4-17-Wrap
292012881-0017
None DetectedCa Carbonate
Non-fibrous (Other)
10%
15%
Cellulose75%White
Fibrous
Homogeneous
Mechanical Room -
Tank - Canvas Wrap over Mud
4-17-Mud
292012881-0017A
None DetectedCa Carbonate
Non-fibrous (Other)
30%
40%
Min. Wool30%Gray
Fibrous
Homogeneous
Mechanical Room -
Tank - Canvas Wrap over Mud
4-18-Wrap
292012881-0018
None DetectedCa Carbonate
Non-fibrous (Other)
10%
15%
Cellulose75%Gray
Fibrous
Homogeneous
Mechanical Room -
Tank - Canvas Wrap over Mud
4-18-Mud
292012881-0018A
None DetectedCa Carbonate
Non-fibrous (Other)
40%
25%
Min. Wool35%Gray
Non-Fibrous
Homogeneous
Mechanical Room -
Tank - Canvas Wrap over Mud
4-19
292012881-0019
None DetectedCa Carbonate
Non-fibrous (Other)
25%
73%
Cellulose
Wollastonite
<1%
2%
White
Fibrous
Homogeneous
Mechanical Room -
Fiberglass Duct
Insulation - White
Mastic
4-20
292012881-0020
None DetectedCa Carbonate
Non-fibrous (Other)
25%
73%
Cellulose
Wollastonite
<1%
2%
White
Fibrous
Homogeneous
Mechanical Room -
Fiberglass Duct
Insulation - White
Mastic
4-21
292012881-0021
None DetectedCa Carbonate
Non-fibrous (Other)
10%
86%
Cellulose
Wollastonite
2%
2%
White
Fibrous
Homogeneous
Mechanical Room -
Fiberglass Duct
Insulation - White
Mastic
4-22
292012881-0022
None DetectedPerlite
Non-fibrous (Other)
15%
15%
Cellulose
Min. Wool
30%
40%
Gray/White
Fibrous
Homogeneous
Basement Hallway at
Rm. 002 - 2'x2' White
Ceiling Tile w/Dots &
Small Lines
4-23
292012881-0023
None DetectedPerlite
Non-fibrous (Other)
15%
15%
Cellulose
Min. Wool
30%
40%
Gray/White
Fibrous
Homogeneous
Room 009 - 2'x2'
White Ceiling Tile…
This is the start of the file's text. The full file is on GovTribe.