234000 - HVAC AIR CLEANING DEVICES.pdf
PDF 36 KB Posted
- Attached to
- Z2AA - Renovate Historic Building 4 Federal contract opportunity
- Solicitation number
- 36C24624R0030
About this file
This is a technical specification document (Section 23 40 00) detailing requirements for HVAC air cleaning devices as part of the renovation of Historical Building 4. The document specifies requirements for air filters used in heating, ventilating and air conditioning systems, including both medium efficiency pre-filters (MERV 8) and high efficiency extended surface cartridge filters (MERV 13).
The specification requires factory assembled extended surface air filters with specific performance criteria, including UL 900 Class 2 compliance. Pre-filters must have a MERV 8 rating with 105 grams dust holding capacity and 2,000 CFM rated air flow capacity at 500 FPM. The high efficiency filters must have a MERV 13 rating with 465 grams dust holding capacity. Additional requirements include Magnehelic differential pressure filter gauges, DDC sensors across extended surface filters, and proper labeling of contaminated air ducts. The document includes detailed installation, startup, and commissioning requirements, with specific references to ASHRAE Standard 52.2 testing methods and performance standards.
View the file
Other files for this federal contract opportunity
Show all 50
Z2AA - Renovate Historic Building 4 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Renovation of Historical Building 4
Project #565 20 101
03-01-20
HVAC AIR CLEANING DEVICES
23 40 00 - 1
SECTION 23 40 00
HVAC AIR CLEANING DEVICES
PART 1 - GENERAL
1.1 DESCRIPTION
A. Air filters for heating, ventilating and air conditioning.
B. Definitions: Refer to ASHRAE Standard 52.2 for definitions of face velocity, net effective filtering area, media velocity, initial resistance (pressure drop), MERV (Minimum Efficiency Reporting Value), PSE (Particle Size Efficiency), particle size ranges for each MERV number, dust holding capacity and explanation of electrostatic media used filtration products versus mechanical filtration products. Refer to ASHRAE Standard 52.2 Appendix J for definition of MERV-A.
1.2 RELATED WORK
A. Section 01 00 00, GENERAL REQUIREMENTS
B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
C. Section 23 05 11, COMMON WORK RESULTS FOR HVAC: General mechanical requirements and items, which are common to more than one section of
Division 23.
D. Section 23 08 00 – COMMISSIONING OF HVAC SYSTEMS: Requirements for commissioning, systems readiness checklists, and training.
E. Section 23 37 00 AIR OUTLETS AND INLETS.
F. Section 23 73 00, INDOOR CENTRAL-STATION AIR-HANDLING UNITS: Filter housing and racks.
1.3 QUALITY ASSURANCE
A. Air Filter Performance Report for Extended Surface Filters:
1. Submit a test report for each Grade of filter being offered. The report shall not be more than three (3) years old and prepared by using test equipment, method and duct section as specified by ASHRAE
Standard 52.2 for type filter under test and acceptable to CxA and
COR, indicating that filters comply with the requirements of this specification. Filters utilizing partial or complete synthetic media will be tested in compliance with pre-conditioning steps as stated in Appendix J. All testing is to be conducted on filters with a nominal 24 inch by 24 inch face dimension. Test for 150 m/min (500 fpm) will be accepted for lower velocity rated filters provided the test report of an independent testing laboratory complies with all the requirements of this specification.
03-01-20
HVAC AIR CLEANING DEVICES
23 40 00 - 2
B. Filter Warranty for Extended Surface Filters: Guarantee the filters against leakage, blow-outs, and other deficiencies during their normal useful life, up to the time that the filter reaches the final pressure drop. Defective filters shall be replaced at no cost to the Government.
C. Comply with UL Standard 900 for flame test.
D. Nameplates: Each filter shall bear a label or name plate indicating manufacturer's name, filter size, rated efficiency, UL classification, and file number.
1.4 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Manufacturer's Literature and Data:
1. Extended surface filters.
2. Magnehelic gages.
C. Air Filter performance reports.
D. Suppliers warranty.
1.5 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by basic designation only.
B. American Society of Heating, Refrigerating and Air-conditioning
Engineers, Inc. (ASHRAE):
52.2-2017...........Method of Testing General Ventilation Air-Cleaning
Devices for Removal Efficiency by Particle
Size, including Appendix J
C. American Society of Mechanical Engineers (ASME):
NQA-1-2017..............Quality Assurance Requirements for Nuclear
Facilities Applications
D. Underwriters Laboratories, Inc. (UL):
900;Revision 15 July 2015 Test Performance of Air Filter Units
PART 2 - PRODUCTS
2.1 REPLACEMENT FILTER ELEMENTS TO BE FURNISHED
A. To allow temporary use of HVAC systems for testing and in accordance with Paragraph, TEMPORARY USE OF MECHANICAL AND ELECTRICAL SYSTEMS in
Section 01 00 00, GENERAL REQUIREMENTS, provide one complete set of additional filters to the COR.
03-01-20
HVAC AIR CLEANING DEVICES
23 40 00 - 3
B. The COR will direct whether these additional filters will either be installed as replacements for dirty units or turned over to VA for future use as replacements.
2.2 EXTENDED SURFACE AIR FILTERS
A. Use factory assembled air filters of the extended surface type with supported or non-supported cartridges for removal of particulate matter in air conditioning, heating and ventilating systems. Filter units shall be of the extended surface type fabricated for disposal when the contaminant load limit is reached as indicated by maximum (final) pressure drop.
B. Filter Classification: UL listed and approved conforming to UL Standard
900.
C. HVAC Filter Types
HVAC Filter Types
Table 2.2C
MERV Value
ASHRAE
52.2
MERV-A
Value
ASHRAE 62.2
Appendix J
Application Particle Size Thickness /Type
8 8-A Pre-Filter 3 to 10 Microns 50 mm (2-inch)
Throwaway
13 Pre-Filter 0.3 to 1 Microns 50 mm (2-inch)
Throwaway
2.3 MEDIUM EFFICIENCY PLEATED PANEL PRE-FILTERS (2”; MERV 8; UL 900 CLASS 2):
A. Construction: Air filters shall be medium efficiency ASHRAE pleated panels consisting of cotton and synthetic or 100% virgin synthetic media, self supporting media with required media stabilizers, and beverage board enclosing frame. Filter media shall be lofted to a uniform depth and formed into a uniform radial pleat. The media stabilizers shall be bonded to the downstream side of the media to maintain radial pleats and prevent media oscillation. An enclosing frame of no less than 28-point high wet-strength beverage board shall provide a rigid and durable enclosure. The frame shall be bonded to the media on all sides to prevent air bypass. Integral diagonal support members on the air entering and air exiting side shall be bonded to the apex of each pleat to maintain uniform pleat spacing in varying airflows.
B. Performance: The filter shall have a Minimum Efficiency Reporting Value of MERV 8 when evaluated under the guidelines of ASHRAE Standard 52.2.
It shall also have a MERV-A of 8 when tested per Appendix J of the same standard. The media shall maintain or increase in efficiency over the
03-01-20
HVAC AIR CLEANING DEVICES
23 40 00 - 4 life of the filter. Pertinent tolerances specified in Section 7.4 of the Air-Conditioning and Refrigeration Institute (ARI) Standard 850-
2014 shall apply to the performance ratings. All testing is to be conducted on filters with a nominal 24” x 24” face dimension.
Minimum Efficiency Reporting (MERV) 8
Dust Holding Capacity (Grams) 105
Nominal Size (Width x Height x Depth) 24x24x2
Rated Air Flow Capacity (Cubic Feet per
Minute)
2,000
Rated Air Flow Rate (Feet per Minute) 500
Final Resistance (Inches w.g.)
Maximum Recommended Change-Out Resistance
(Inches w.g.)
1.0
0.66
Rated Initial Resistance (Inches w.g.) 0.33
C. The filters shall be approved and listed by Underwriters' Laboratories, Inc. as Class 2 when tested according to U. L. Standard 900 and CAN 4-
5111.
2.4 HIGH EFFICIENCY EXTENDED SURFACE (INTERMEDIATE/AFTER (FINAL)) CARTRIDGE
FILTERS (2”; MERV 13; UL 900 CLASS 2):
A. Construction: Air filters shall consist of 8 pleated media packs assembled into 4 V-banks within a totally plastic frame. The filters shall be capable of operating at temperatures up to 80 degrees C (176 degrees F). The filters must either fit without modification or be adaptable to the existing holding frames. The molded end panels are to be made of high impact polystyrene plastic. The center support members shall be made of ABS plastic. No metal components are to be used.
B. Media: The media shall be made of micro glass fibers with a water repellent binder. The media shall be a dual density construction, with coarser fibers on the air entering side and finer fibers on the air leaving side. The media shall be pleated using separators made of continuous beads of low profile thermoplastic material. The media packs shall be bonded to the structural support members at all points of contact, this improves the rigidity as well as eliminates potential air bypass in the filter
C. Performance: Filters of the size, air flow capacity and nominal efficiency (MERV) shall meet the following rated performance specifications based on the ASHRAE 52.2-1999 test method. Where
03-01-20
HVAC AIR CLEANING DEVICES
23 40 00 - 5 applicable, performance tolerance specified in Section 7.4 of the Air-
Conditioning and Refrigeration Institute (ARI) Standard 850-2014 shall apply to the performance ratings. All testing is to be conducted on filters with a nominal 24"x24" header dimension.
Minimum Efficiency Reporting Value
(MERV)
Gross Media Area (Sq. Ft.)
Dust Holding Capacity (Grams)
Nominal Size (Width x Height x Depth) 24x24x12
Rated Air Flow Capacity (cubic feet per minute)
2,000
Rated Air Flow Rate (feet per minute) 500
Final Resistance (inches w.g.)
Maximum Recommended Change-Out
Resistance (Inches w.g.)
2.0
0.54
Rated Initial Resistance (inches w.g.) 0.27
2.5 INSTRUMENTATION
A. Magnehelic Differential Pressure Filter Gages: Nominal 100 mm (four inch) diameter, zero to 500 Pa (zero to two inch water gage), three inch for HEPA) range, Gauges shall be flush-mounted in aluminum panel board, complete with static tips, copper or aluminum tubing, and accessory items to provide zero adjustment.
B. DDC static (differential) air pressure measuring station. Refer to
Specification Section 23 09 23 DIRECT DIGITAL CONTROL SYSTEM FOR HVAC
C. Provide one DDC sensor across each extended surface filter. Provide
Petcocks for each gauge or sensor.
D. Provide one common filter gauge for two-stage filter banks with isolation valves to allow differential pressure measurement.
2.6 HVAC EQUIPMENT FACTORY FILTERS
A. Manufacturer standard filters within fabricated packaged equipment should be specified with the equipment and should adhere to industry standard.
B. Cleanable filters are not permitted.
C. Automatic Roll Type filters are not permitted.
PART 3 – EXECUTION
3.1 INSTALLATION
A. Install supports, filters and gages in accordance with manufacturer's instructions.
03-01-20
HVAC AIR CLEANING DEVICES
23 40 00 - 6
B. Label clearly with words "Contaminated Air" on exhaust ducts leading to the HEPA filter housing.
3.2 START-UP AND TEMPORARY USE
A. Clean and vacuum air handling units and plenums prior to starting air handling systems.
B. Replace Pre-filters and install clean filter units prior to final inspection as directed by the COR.
3.3 COMMISSIONING
A. Provide commissioning documentation in accordance with the requirements of Section 23 08 00 – COMMISSIONING OF HVAC SYSTEMS for all inspection, start up, and contractor testing required above and required by the
System Readiness Checklist provided by the Commissioning Agent.
B. Components provided under this section of the specification will be tested as part of a larger system. Refer to Section 23 08 00 –
COMMISSIONING OF HVAC SYSTEMS and related sections for contractor responsibilities for system commissioning.
- - E N D - - -