_29 LNC BD - TECHNOLOGY pt1 (pg 231-235).pdf
PDF 13 MB Posted
- Solicitation number
- 36C78626B0027
About this file
This is a technology coversheet and planning document set for a federal construction project at Leavenworth National Cemetery in Kansas. The document package includes technology design plans, schedules, specifications, and installation guidance for a gravesite expansion project managed by the U.S. Department of Veterans Affairs. The project involves telecommunications infrastructure, security systems, and audiovisual technology installation across a lower level and first level of a new facility. Key technology systems include access control door readers and keypads, intrusion detection equipment (motion detectors and glass break sensors), video surveillance cameras, wireless access points, information outlets, conduit and cable pathways, and a telecommunications room with equipment racks. The technology contractor is responsible for rough-in work including conduit sleeves, backboxes, and cable routing, while the telecommunications contractor handles equipment procurement, cabling terminations, and final installations. All installations must comply with ADA Standards for Accessible Design, with specific mounting heights and accessibility requirements detailed throughout the specifications. The document establishes a matrix of responsibility clearly delineating tasks between the electrical contractor and telecommunications contractor, including provisions for the relocation of existing optical fiber from a maintenance building and coordination with VA Office of Information Technology for equipment removal and replacement. The contract documents are dated June 22, 2026, and reference optional bid number one for the project numbered 897CM3025.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TECHNOLOGY ABBREVIATION KEY
MAIN CROSS-CONNECTMC-#
TELECOMMUNICATIONS ROOMTR-#
ABOVE FINISHED FLOORAFF
BELOW FINISHED CEILINGBFC
CONDUITC
SIMILARSIM
TYPICALTYP
MOUNTING HEIGHT ABOVE FINISHED FLOOR+#
JUNCTION BOXJ-BOX
ABBR: DESCRIPTION:
UNLESS OTHERWISE NOTEDUON
FIELD OF VIEWFOV
DOUBLE POLE DOUBLE THROWDPDT
PAN TILT ZOOMPTZ
POWER OVER ETHERNETPOE
ABOVE FINISHED GRADEAFG
DELAYED EGRESSDE
GOVERNMENT FURNISHED GOVERNMENT INSTALLEDGFGI
TECHNOLOGY GENERAL NOTES:
1. ##-###-# INDICATES TECHNOLOGY EQUIPMENT SCHEDULE ITEM LABELED AS "EQUIPMENT
LIST ABBREVIATION"
2. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR FULL
DESCRIPTIONS AND MANUFACTURERS OF ALL DEVICES.
TECHNOLOGY MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
S MOUNT IN SURFACE RACEWAY
A SLASH IS USED BETWEEN TWO SUBSCRIPTS, E.G., A/H.
3. REFER TO THE TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE COMPLETE DESCRIPTION
AND ITEMS.
4. REFER TO DIAGRAMS ON SHEET(S): T500.
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS
ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, IN FLOOR SLAB, ETC.
UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT IN
MECHANICAL ROOMS AND STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON
BUILDING STRUCTURE.
3. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE OFFSET A MINIMUM
OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE
OFFSET A MINIMUM OF 24" HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE
ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
4. VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT LOCATIONS WITH
ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING
THE ACTUAL TELECOMMUNICATIONS INSTALLATION, ADJUST OUTLETS OR CONNECTION
LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT.
5. TELECOMMUNICATIONS EQUIPMENT SHALL BE MOUNTED TO ALLOW ACCESS TO
ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF TELECOMMUNICATION
DEVICES ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR SHALL BE APPROVED IN
ADVANCE BY THE OTHER CONTRACTOR.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
7. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
8. THE TECHNOLOGY CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
THE CEILINGS, CEILING TILES, AND CEILING GRID ASSOCIATED WITH THE AREAS OF WORK
BY ALL CONTRACTORS.
9. ALL LADDER RACK SIZES ARE AS DEFINED ON THE DRAWINGS. REFER TO SPECIFICATION
SECTIONS FOR APPROVED MANUFACTURERS AND INSTALLATION REQUIREMENTS.
10. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES
DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE
RATING, AND FINISH.
11. FLUSH MOUNT ALL TELECOMMUNICATION OUTLETS AT +18" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. OUTLETS MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
12. MOUNT BACKBOXES FLUSH WITH WALL. ALL BACKBOX HEIGHTS ARE TO CENTERLINE
DIMENSION, UNLESS OTHERWISE NOTED.
13. PROVIDE RACEWAY AND BOXES LISTED FOR THE INSTALLED ENVIRONMENT. SEAL
RACEWAY AND BOX FROM WATER AND MOISTURE AT TRANSITION BETWEEN DIFFERENT
ENVIRONMENTAL CONDITIONS SUCH AS INTERIOR/EXTERIOR, TEMPERATURE CHANGES,
ETC.
TECHNOLOGY INSTALLATION NOTES:
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 KEYNOTE: INDICATES NOTE USED TO
DESCRIBE ADDITIONAL INFORMATION
ABOUT WORK REQUIRED, SPECIFIC
TO THE SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
M
A X
20" MAX.
M
A X
20"-25" MAX.
M
A X
M
IN
. 4
M
A X
M
A X
10" MAX. 10"-24" MAX.
ADA STANDARDS - FRONT ACCESS
ADA STANDARDS FOR ACCESSIBLE DESIGN
INSTALL ABOVE COUNTER
DEVICE AT 44" ABOVE
FINISHED FLOOR.
INSTALL ABOVE COUNTER
DEVICE AT 40" ABOVE
FINISHED FLOOR.
INSTALL DEVICE AT 18"
ABOVE FINISHED FLOOR.
ADA STANDARDS - SIDE ACCESS
INSTALL DEVICE AT 44"
ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 42"
ABOVE FINISHED FLOOR.
TECHNOLOGY SYMBOL LIST
SYMBOL TAG
EQUIPMENT LIST
ABBREVIATION
DESCRIPTION
DBDB DETENTION DOORBELL BUTTON (WALL) EXISTING
RME NA
ACCESS CONTROL DOOR (READER / MOTION REX /
ELECTRONIC LOCKING HARDWARE)
R1 AC-R1-W SECURITY CREDENTIAL READER (WALL) TYPE 1
K SECURITY KEY SWITCH (WALL) EXISTING
A AL1 AC-AA-1 INTRUSION DETECTION AUDIBLE ALARM (WALL)
G GB1 ID-GB1-C INTRUSION DETECTION GLASS BREAK (CEILING)
K1 AC-K1-W INTRUSION DETECTION KEYPAD (WALL) TYPE 1
M MD1 ID-MD1-C INTRUSION DETECTION MOTION DETECTOR (CEILING)
M
INTRUSION DETECTION MOTION DETECTOR (WALL)
EXISTING
C# C2-WAP SC-IO-C INFORMATION OUTLET (CEILING)
C# C2 SC-IO-F INFORMATION OUTLET CONNECTION IN FLOOR BOX
C# C2 SC-IO-W INFORMATION OUTLET (WALL)
C2-M SC-IO-W INFORMATION OUTLET (WALL)
INFORMATION OUTLET (WALL) EXISTING
RI RI SC-RI-W INFORMATION OUTLET ROUGH-IN (WALL)
W W SC-IO-W INFORMATION OUTLET WALL PHONE (WALL)
WAP
WIRELESS ACCESS POINT WITH ENCLOSURE (CEILING)
EXISTING
CM-1 VS-CM-1
VIDEO SURVEILLANCE CAMERA SINGLE LENS FOV
(CEILING/HORIZONTAL SURFACE)
VIDEO SURVEILLANCE CAMERA 360° FOV
(CEILING/HORIZONTAL SURFACE) EXISTING
CM-4 VS-CM-4
VIDEO SURVEILLANCE CAMERA 360° FOV
(WALL/VERTICAL SURFACE)
TECHNOLOGY SYMBOL LIST GENERAL NOTES:
1. "C#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO DATA
CONNECTION SCHEDULE ON T600 FOR ADDITIONAL INFORMATION.
2. REFER TO ACCESS CONTROL DOOR TYPE SCHEDULE ON T600 FOR ADDITIONAL
INFORMATION.
3. "CM-#" ON FLOOR PLANS INDICATES CAMERA TYPE AND IS ASSOCIATED WITH THE
CORRESPONDING "VS-CM-#" EQUIPMENT SCHEDULE ABBREVIATION.
LADDER RACKWIDTH X HEIGHT
DIAMETERø C CONDUIT
CONDUIT DOWN
CONDUIT UP OR UP/DOWN
CONDUIT SLEEVE
CONTINUATION
PATHWAY SYMBOL LIST:
SYMBOL DESCRIPTION
TECHNOLOGY SHEET INDEX
T000 TECHNOLOGY COVERSHEET
T001 SITE - TECHNOLOGY
T002 LOWER LEVEL DEMOLITION PLAN - TECHNOLOGY
T003 FIRST LEVEL DEMOLITION PLAN - TECHNOLOGY
T100 LOWER LEVEL PLAN - TECHNOLOGY
T101 FIRST LEVEL PLAN - TECHNOLOGY
T300 TECHNOLOGY ENLARGED PLANS
T400 TECHNOLOGY DETAILS
T401 TECHNOLOGY DETAILS
T402 TECHNOLOGY DETAILS
T500 TECHNOLOGY DIAGRAMS
T600 TECHNOLOGY SCHEDULES
GRAND TOTAL: 12
SUGGESTED MATRIX OF RESPONSIBILITY
ITEM: SHOWN ON:
FURNISHED
BY:
INSTALLED
BY: NOTES:
TECHNOLOGY ROUGH-IN, REFER TO
TECHNOLOGY EQUIPMENT SCHEDULE
AND SPECIFICATIONS FOR DEFINITION
T-SERIES E.C. E.C. 3. 4.
INFORMATION OUTLET FACEPLATES,
JACKS, AND TERMINATIONS
T-SERIES T.C. T.C.
CONDUIT SLEEVES (WHEN SHOWN ON
DRAWINGS)
T-SERIES E.C. E.C.
CONDUIT SLEEVES (NOT SHOWN BUT
REQUIRED FOR PROPER INSTALLATION
OF SYSTEM)
N/A T.C. T.C. 2. 4.
TELECOMMUNICATION SYSTEMS
ROUGH-IN
T-SERIES E.C. E.C. 1.
TELECOMMUNICATION EQUIPMENT,
CABLING, AND TERMINATIONS
T-SERIES T.C. T.C.
LADDER RACK T-SERIES T.C. T.C. 5.
GROUNDING LUGS ON TECHNOLOGY
EQUIPMENT
T-SERIES T.C. E.C. 6.
BONDING SYSTEM FOR TECHNOLOGY
SYSTEM, REFER TO SPECIFICATION
SECTION 27 05 26 FOR DEFINITION
T-SERIES E.C. E.C. 7. 8.
CONNECTION OF TECHNOLOGY
BONDING SYSTEM TO THE ELECTRICAL
GROUND SYSTEM
T-SERIES E.C. E.C.
LINE VOLTAGE POWER (+120V OR
GREATER)
E-SERIES E.C. E.C.
LINE VOLTAGE POWER (NOT SHOWN
BUT REQUIRED FOR PROPER
INSTALLATION OF SYSTEM)
N/A T.C. E.C. 2. 4.
LINE VOLTAGE POWER FOR DOOR
HARDWARE POWER SUPPLIES
ARCH SPEC E.C. E.C.
LOW VOLTAGE CABLING FOR
TECHNOLOGY SYSTEMS
T-SERIES T.C. T.C.
CABLE HANGERS AND SUPPORTS OR
OTHER CABLE ROUTING METHODS
(OTHER THAN CONDUIT AND CABLE
TRAY)
T-SERIES T.C. T.C. 5.
SUGGESTED MATRIX OF RESPONSIBILITY NOTES
1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATION
OUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FOR
ADDITIONAL INFORMATION.
2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALL
REQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLE
MANUFACTURERS.
3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMS
INSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THE
CONTRACT DOCUMENTS.
4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OF
THE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEM
CONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDED
IN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.
5. UNLESS TRADE RULES DICTATE OTHERWISE.
6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FOR
INSTALLATION IN THE FIELD.
7. INCLUDES ALL CONDUCTORS, GROUND BARS, AND TERMINATIONS FOR THE COMPLETE
BONDING SYSTEM REQUIRED BY THE SPECIFICATIONS.
8. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF PANELS AND SWITCHBOARDS SHOWN
IN THE TECHNOLOGY BONDING RISER DIAGRAM AND TYPICAL TELECOM ROOM BONDING FLOW
DIAGRAM.
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:4
P
M
T000
TECHNOLOGY COVERSHEET
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 PMM TK
BID DOCUMENTS
18704
Revisions: Date:
VA
F
O R
M
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
Office of Design and Construction
Services
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789 T-000
CEMETERY RD
L P
L P
L P
L P
Temporary Trailer
MH/7
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:5
P
M
T001
SITE - TECHNOLOGY
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 PMM TK
BID DOCUMENTS
18704
N O R
HT
1" = 20'-0"1
SITE - TECHNOLOGY
GENERAL SHEET NOTES:
1. THE LOCATION OF EXISTING COMMUNICATIONS MANHOLES SHOWN
ON THIS SHEET ARE APPROXIMATE. CONTRACTOR SHALL FIELD
VERIFY THE LOCATION OF ALL EXISTING CONDUITS AND MANHOLES
AND OTHER UTILITIES PRIOR TO THE INSTALLATION OF NEW WORK
SHOWN ON THIS SHEET.
2. CONTRACTOR SHALL INCLUDE IN THEIR BID ANY REMOVAL AND
REPLACEMENT OF EXISTING SIDEWALK, PAVEMENT, GRASS,
SHRUBS, TREES, ETC. THAT WILL BE IMPACTED BY THE
INSTALLATION OF THE NEW WORK SHOWN IN THIS DRAWING. IF
TREES ARE REQUIRED TO BE REMOVED THE CONTRACTOR SHALL
CONTACT THE VA AND DISCUSS OPTIONS PRIOR TO CUTTING DOWN
ANY TREE OR SHRUB OVER 5' IN HEIGHT.
3. NO ADDITIONAL COST SHALL BE APPROVED FOR PLACING
CONDUITS DEEPER THAN REQUIRED MINIMUM DEPTH TO AVOID
EXISTING UTILITIES.
4. COORDINATE ALL UTILITY WORK WITH FINAL CIVIL DRAWINGS.
5. NUMBER OF BENDS IN A SINGLE CONDUIT RUN SHALL NOT EXCEED
180 DEGREES AND NO MORE THAN TWO 90 DEGREE BENDS.
6. SLOPE CONDUIT RUNS FOR DRAINAGE TOWARD THE MANHOLES
AND AWAY FROM BUILDING WITH A SLOPE OF APPROXIMATELY 3-
INCHES PER 100 FEET.
7. PLUG AND SEAL EMPTY SPARE CONDUITS ENTERING BUILDINGS.
8. DRAWINGS ARE FOR REFERENCE ONLY. REFER TO CIVIL DRAWINGS
FOR ADDITIONAL INFORMATION.
9. ALL UNDERGROUND CONDUITS SHALL BE ENCASED IN CONCRETE.
10. CONTRACTOR SHALL SUBMIT PROPOSED CONDUIT PLAN TO A/E
FOR REVIEW AND APPROVAL PRIOR TO INSTALLATION.
11. VIDEO SURVEILLANCE CAMERAS SHOWN ON THIS SHEET ARE FOR
REFERENCE ONLY. REFER TO 1/T101 FOR ADDITIONAL
INFORMATION.
KEYNOTES:
1. INSTALL 2" CONDUIT FROM TEMP TRAILER TO
TELECOMMUNICATIONS MANHOLE (MH/7). MANHOLE TO BE
INSTALLED IN MAINTENANCE BUILDING PROJECT. COORDINATE
WITH TRAILER MANUFACTURER ON FINAL LOCATION OF CONDUIT.
Revisions: Date:
VA
F
O
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
Office of Design and Construction
Services
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789 T-001
H
C
G
F
E
D
3 4 5
4.1 5.1
3.1
D.1
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:5
P
M
T002
LOWER LEVEL DEMOLITION PLAN -
TECHNOLOGY
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 PMM TK
BID DOCUMENTS
18704
N O R
HT
1/4" = 1'-0"1
LOWER LEVEL DEMOLITION PLAN - TECHNOLOGY
KEYNOTES:
1. EXISTING TELECOMMUNICATIONS CABINET.
REMOVE CABINET AND ALL CABLING BACK TO
ITS SOURCE. COORDINATE WITH VA OIT FOR
REMOVAL OF IT EQUIPMENT.
2. EXISTING SERVICE PROVIDER DEMARCATION
POINT.
3. EXISTING FIBER PANEL TO REMAIN.
4. EXISTING CONDUIT FOR SERVICE PROVIDER
CABLING.
5. EXISTING SERVICE PROVIDER CABLING TO
REMAIN.
6. EXISTING OPTICAL FIBER TO EXISTING
MAINTENANCE BUILDING. REMOVE FIBER ONCE
NEW MAINTENANCE BUILDING HAS BEEN
CONSTRUCTED AND FULLY OPERATIONAL.
Revisions: Date:
VA
F
O
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
Office of Design and Construction
Services
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789 T-002
D B
D B
WAP
WAP
M K
M
H
C
G
F
E
D
3 4 5
4.1 5.1
3.1
D.1
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:5
P
M
T003
FIRST LEVEL DEMOLITION PLAN -
TECHNOLOGY
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 PMM TK
BID DOCUMENTS
18704
N O R
HT
1/4" = 1'-0"1
FIRST LEVEL DEMOLITION PLAN - TECHNOLOGY
SHEET NOTES:
1. REMOVE ALL CABLING BACK TO ITS SOURCE.
KEYNOTES:
1. EXISTING DISPLAY. REMOVE DISPLAY AND
MOUNT AND RETURN TO GOVERNMENT.
REMOVE ALL CABLING BACK TO SOURCE.
2. PLUG-IN DOOR BELL RECEIVER. REMOVE AND
REPLACE DEVICE. REFER TO T101 FOR
ADDITIONAL INFORMATION.
3. VIDEO SURVEILLANCE SERVER. REMOVE AND
RETURN TO GOVERNMENT. REMOVE ALL
CABLING BACK TO SOURCE
4. REMOVE DOOR POSITION SWITCH AND CABLING
BACK TO SOURCE.
5. WIRELESS DOOR BELL AND CHIME. REMOVE
AND REPLACE. REFER TO T101 FOR ADDITIONAL
INFORMATION.
6. RADIO ANTENNA. ANTENNA AND EQUIPMENT TO
REMAIN.
Revisions: Date:
VA
F
O
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
Office of Design and Construction
Services
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789 T-003
M
C2-WAP
R1
H
C
G
F
E
D
B
A
2.1
4 5
4.1 5.1
3.1
D.1
ELECTRICAL
B04
TR
B03
BASEMENT
B02
BASEMENT
B01
B02A
B04A
B02B
B01A
B03A
STAIRS
B05
T300
T300
CM-1
01-01
CM-1
01-02
RME
MD1
RME TR-1
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:5
P
M
T100
LOWER LEVEL PLAN -
TECHNOLOGY
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 PMM TK
BID DOCUMENTS
18704
N O R
HT
1/4" = 1'-0"1
LOWER LEVEL PLAN - TECHNOLOGY
SHEET NOTES:
1. ALL CABLING SHALL ROUTE TO
TELECOMMUNICATIONS ROOM B03.
KEYNOTES:
1. EXISTING SERVICE PROVIDER EQUIPMENT.
2. NEW SECURITY GATE. REFER TO ARCHITECT
DRAWINGS FOR ADDITIONAL INFORMATION.
3. CONTRACTOR TO RELOCATE EXISTING
OPTICAL FIBER FROM NEW MAINTENANCE
BUILDING, INSTALLED UNDER SEPARATE
PROJECT. RELOCATE FIBER AND FIBER
OPTICAL PANEL TO NEW RACK IN NEW
TELECOMMUNICATIONS ROOM. CONTRACTOR
SHALL COORDINATE WITH VA OIT WHEN FIBER
RELOCATION CAN OCCUR.
Revisions: Date:
VA
F
O
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
Office of Design and Construction
Services
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789 T-100