_31 LNC BD - TECHNOLOGY pt3 FIRE ALARM (pg 241-247).pdf
PDF 12 MB Posted
- Solicitation number
- 36C78626B0027
About this file
This document comprises the technology and fire alarm design drawings and schedules for the Leavenworth National Cemetery Gravesite Expansion project located at 150 Muncie Road, Leavenworth, Kansas. The bid documents are prepared for the U.S. Department of Veterans Affairs, with project number 897CM3025 and design number 18704, dated June 22, 2026.
The technology infrastructure requires installation of a comprehensive integrated security system including video surveillance, access control, and intrusion detection capabilities. The contractor must provide and install a new video management storage server compatible with the existing system, integrate new card readers and intrusion devices with the existing access control and intrusion detection system, and coordinate all connections and programming with VA OIT. The security system includes nine video surveillance cameras (four interior standard-view cameras mounted in ceilings; five exterior 360-degree cameras mounted at corners), access control door hardware with card readers for five controlled doors, and motion detectors for intrusion detection. All security network equipment must support a minimum of 8 hours of battery backup during power failures. The contractor must provide Category 6A plenum-rated horizontal cabling, install a 48-port network switch to support the dedicated security network, and establish connectivity through existing fiber optic cable between buildings. The fire alarm system integrates addressable smoke detectors, heat detectors, manual pull stations, audio/visual notification appliances, duct smoke detectors, and a carbon monoxide detector, with connections to HVAC shutdown relays and the existing Siemens Desigo fire alarm control panel. All bonding conductors must be plenum-rated copper connected via compression lugs, exothermic welding, or irreversible compression connectors, with sizing determined by conductor length per the bonding conductor sizing schedule. The contractor is responsible for all programming, configuration, testing, and coordination required to ensure devices are connected and operational in both buildings.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SC-MPP-1
EXISTING FIBER
PANEL
SC-NS-1
VS-VMS-1
EXISTING FIBER
PANEL
OWNER
PROVIDED
EQUIPMENT
SC-FDC-1
SC-NS-1
SC-GND-1
ELECTRICAL
PANEL
SERVING ROOM
BUILDING
STEEL
ACCESS
CONTROL
EQUIPMENT
METALLIC
CONDUITS AND
SLEEVES
EQUIPMENT
RACK(S)
CABLE TRAY
SC-GND-1
SC-NS-1
AC-SCP-1
REQUEST TO
EXIT
ELECTRONIC
LOCKING
HARDWARE
DOOR
POSITION
SWITCH
AC-R1-W
ID-ICP-1
SC-NS-1
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION(S), LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE SPECIFIC ROUTING INFORMATION.
REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. REFER TO FLOOR PLANS FOR QUANTITY OF CABLES AND JACKS TO BE INSTALLED AT EACH INFORMATION OUTLET.
SECURITY SYSTEM PROGRAMMING NOTES:
1. CONTRACTOR TO PROVIDE AND INSTALL NEW VIDEO MANAGEMENT STORAGE SERVER TO SUPPORT NEW CAMERAS BY THIS PROJECT. VIDEO MANAGEMENT SERVER SHALL MATCH EXISTING SERVER INSTALLED UNDER SEPARATE PROJECT.
2. CONTRACTOR SHALL COORDINATE WITH VA OIT TO INTEGRATE NEW CARD READERS AND INTRUSION DEVICES TO THE EXISTING ACCESS CONTROL AND INTRUSION DETECTION SYSTEM. CONTRACTOR SHALL PROVIDE ALL NECESSARY
CONNECTIONS, PROGRAMMING, ETC. FOR CAMERA INTEGRATION AND TESTING.
3. CONTRACTOR SHALL COORDINATE WITH VA OIT TO INTEGRATE NEW CAMERAS TO THE EXISTING VIDEO MANAGEMENT SYSTEM. CONTRACTOR SHALL PROVIDE ALL NECESSARY CONNECTIONS, PROGRAMMING, ETC. FOR CAMERA
INTEGRATION AND TESTING.
4. CONTRACTOR SHALL INCLUDE IN THEIR BID ALL PROGRAMMING NECESSARY TO INSTALL AND CONFIGURE SECURITY NETWORK. TEST ALL DEVICES IN BOTH BUILDINGS TO ENSURE DEVICES ARE CONNECTED AND OPERATIONAL.
KEYNOTES:
1. CATEGORY 6A PLENUM RATED HORIZONTAL CABLE. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. REFER TO THE INFORMATION OUTLET SCHEDULE ON T600 AND THE FLOOR PLANS FOR THE QUANTITY OF CABLES AND
JACKS TO BE INSTALLED AT EACH LOCATION.
3. CONTRACTOR PROVIDED GOVERNMENT INSTALLED PATCH CABLE. REFER TO SPECIFICATIONS.
4. CONTRACTOR PROVIDED AND INSTALLED PATCH CABLE. REFER TO SPECIFICATIONS.
5. OPTICAL FIBER INSTALLED UNDER SEPARATE PROJECT.
6. CONTRACTOR TO COORDINATE WITH VA OIT AND CONNECT NEW SECURITY NETWORK SWITCHES TO EXISTING FIBER
OPTIC CABLE INSTALLED BETWEEN BUILDINGS.
7. CONTRACTOR PROVIDED AND INSTALLED PATCH CORD TO SUPPORT VIDEO SURVEILLANCE CAMERAS.
8. RACK OR CABINET AS DEFINED ON THE TELECOM ROOM LAYOUT. REFER TO THE TELECOM ROOM REFERENCES MATRIX
ON THE COVER PAGE FOR LOCATION.
9. REFER TO FLOOR PLANS FOR TELECOMMUNICATIONS ROOM LOCATIONS.
10. INSTALL NEW NETWORK SWITCH TO SUPPORT A NEW DEDICATED SECURITY NETWORK. CONNECT EXISTING VIDEO
SURVEILLANCE AND ACCESS CONTROL SERVERS TO SECURITY NETWORK.
11. COORDINATE WITH TRAILER MANUFACTURER ON FINAL LOCATION OF FIBER PANEL PRIOR TO CABLE INSTALLATION.
12. RELOCATE EXISTING WALL CABINET TO NEW RACK. CONTRACTOR SHALL COORDINATE WITH VA OIT WHEN PANEL AND
OPTICAL CABLE WILL BE RELOCATED.
13. 6-STRAND OS2 SINGLE MODE OPTICAL FIBER. TERMINATE NEW FIBERS IN EXISTING FIBER PANEL IN THE ADMINISTRATION
BUILDING.
C#
C#
MAINTENANCE BUILDING
ADMINISTRATION BUILDING 9
EXISTING VIDEO
MONITOR AND
KEYBOARD
EXISTING VIDEO
SURVEILLANCE
SERVER
EXISTING ACCESS
CONTROL
SERVER
TEMPORARY TRAILER
TELECOMMUNICATIONS
BONDING JUMPER (TBJ)
TELECOMMUNICATIONS ROOM 1
TELECOMMUNICATIONS
BONDING JUMPER (TBJ)
NOTES:
1. THIS FLOW DIAGRAM IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS. THIS FLOW DIAGRAM IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CONDUCTOR TYPE. ALL CONNECTIONS AND SYSTEM DEVICES SHOWN ARE TYPICAL AND NOT REPRESENTATIVE OF ACTUAL PROJECT QUANTITIES. REFER TO FLOOR PLANS AND ENLARGED FLOOR PLANS FOR ACTUAL QUANTITIES AND LOCATIONS OF DEVICES AND SPECIFIC ROUTING INFORMATION. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
2. ALL CONDUCTORS IN THE TECHNOLOGY BONDING SYSTEM MUST BE [PLENUM RATED] COPPER (GREEN OR MARKED WITH A DISTINCTIVE GREEN COLOR). REFER TO BONDING CONDUCTOR SIZING SCHEDULE FOR SIZING CRITERIA FOR CONDUCTORS. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
3. ALL BONDING CONDUCTORS MUST BE CONNECTED BY COMPRESSION LUGS, EXOTHERMIC WELDING, OR IRREVERSIBLE COMPRESSION CONNECTORS. SOLDER IS NOT AN ACCEPTABLE MEANS OF CONNECTION. SHEET METAL SCREWS MUST NOT BE USED TO CONNECT COMMUNICATIONS BONDING CONDUCTORS TO EQUIPMENT. WHERE NECESSARY, REMOVE PAINT AND/OR USE PAINT-
PIERCING WASHERS TO PROVIDE PROPER ELECTRICAL BOND AT ALL CONNECTIONS.
4. REFER TO 4/T400 FOR BONDING BUS BAR DETAIL AND ADDITIONAL INFORMATION AND REQUIREMENTS FOR SC-GND-1.
KEYNOTES:
1. REFER TO TELECOM ROOM REFERENCES SCHEDULE ON THE COVERSHEET T000 FOR TELECOMMUNICATIONS ROOM NUMBER AND
LOCATION INFORMATION.
2. INCLUDES HORIZONTAL AND VERTICAL CONDUIT SLEEVES FOR TECHNOLOGY CABLING.
3. BONDING CONDUCTOR FOR TELECOMMUNICATIONS (BCT), TO ELECTRICAL ENTRANCE INTERSYSTEM BONDING TERMINATION. REFER
TO 3/T402 FOR TELECOMMUNICATIONS BONDING RISER DIAGRAM FOR CONTINUATION AND ADDITIONAL INFORMATION AND
REQUIREMENTS.
4. REFER TO THE ELECTRICAL DRAWINGS FOR LOCATION.
5. PROVIDE SC-GND-2 RACK MOUNT TELECOMMUNICATIONS BONDING BUSBAR AT EACH EQUIPMENT RACK AND CABINET.
CONDUCTOR
LENGTH IN FEET
BONDING CONDUCTOR SIZING SCHEDULE
MINIMUM ACCEPTABLE
SIZE - AWG
LESS THAN 13' 6
14' - 20' 4
21' - 26' 3
27' - 33' 2
34' - 41' 1
42' - 52' 1/0
53' - 66' 2/0
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS.
THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CONDUCTOR TYPE.
ALL CONNECTIONS AND SYSTEM DEVICES SHOWN ARE TYPICAL AND NOT REPRESENTATIVE OF
ACTUAL PROJECT QUANTITIES. REFER TO FLOOR PLANS AND ENLARGED FLOOR PLANS FOR ACTUAL QUANTITIES AND LOCATIONS OF DEVICES AND MORE SPECIFIC ROUTING INFORMATION. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. ALL CONDUCTORS IN THE TECHNOLOGY BONDING SYSTEM SHALL BE MINIMUM SIZE OF 3/0 AWG
PLENUM RATED COPPER (GREEN OR MARKED WITH A DISTINCTIVE GREEN COLOR) UNLESS
CONDUCTOR LENGTH IS LESS THAN 66 FEET. REFER TO BONDING CONDUCTOR SIZING SCHEDULE FOR SIZING CRITERIA FOR CONDUCTORS LESS THAN 66 FEET IN LENGTH. REFER TO SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS.
3. ALL BONDING CONDUCTORS AND BONDING JUMPERS SHALL BE CONNECTED BY COMPRESSION
LUGS, EXOTHERMIC WELDING, OR IRREVERSIBLE COMPRESSION CONNECTORS. SOLDER IS NOT AN
ACCEPTABLE MEANS OF CONNECTION. SHEET METAL SCREWS SHALL NOT BE USED TO CONNECT
COMMUNICATIONS BONDING CONDUCTORS TO EQUIPMENT. WHERE NECESSARY, REMOVE PAINT
AND/OR USE PAINT-PIERCING WASHERS TO PROVIDE PROPER ELECTRICAL BOND AT ALL
CONNECTIONS.
4. REFER TO 2/T500 FOR TYPICAL TELECOM ROOM BONDING FLOW DIAGRAM.
5. REFER TO TELECOM ROOM REFERENCES SCHEDULE ON DRAWING ON THE COVERSHEET T000 FOR
TELECOMMUNICATIONS ROOM NUMBER AND LOCATION INFORMATION.
KEYNOTES:
1. BONDING CONDUCTOR FOR TELECOMMUNICATIONS (BCT). BCT SHALL BE THE SAME SIZE AS THE TBB
OR LARGER. REFER TO BONDING CONDUCTOR SIZING SCHEDULE FOR SIZING REQUIREMENTS.
ELECTRICAL ENTRANCE
INTERSYSTEM BONDING
TERMINATION
GROUNDING ELECTRODE
CONDUCTOR BY OTHERS
ELECTRICAL GROUNDING
ELECTRODE SYSTEM
FIRST
FLOOR
TR-1
GREATER THAN 301' 750 kcmil
ADMINISTRATION BUILDING
NOTES:
1. THIS RISER IS A DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIAL SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION(S), LOCATIONS, AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO THE FLOOR PLANS FOR MORE SPECIFIC ROUTING
INFORMATION. REFER TO THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. THIS INTEGRATED SYSTEM INCLUDES DEVICES FOR AN INTRUSION DETECTION SYSTEM AND AN ACCESS CONTROL SYSTEM. REFER TO THE SPECIFICATIONS FOR ADDITIONAL
INFORMATION .
3. ALL CABLING LISTED HERE ARE MINIMUM REQUIREMENTS. FINAL GUAGE AND QUANTITY IS BASED ON THE DISTANCE FROM THE NEAREST CONTROL PANEL AND THE NUMBER OF DOORS AT EACH LOCATION. CREDENTIAL READERS WILL OPEN A SINGLE DOOR WITH THE SECOND DOOR BEING MONITORED BY THE SYSTEM.
4. ALL ACCESS CONTROL EQUIPMENT AND DOOR HARDWARE WILL REQUIRE TO BE ON A MINIMUM OF 8 HOURS OF BATTERY TIME IN THE EVENT OF A POWER FAILURE. THIS INCLUDES ALL OF THE INPUT/OUTPUT CARDS, DOOR CONTROLLERS, ENDPOINTS (SUCH AS CARD READERS, MOTION DETECTORS, AND DOOR POSITIONS SWITCHES), DOOR POWER SUPPLIES AND ALL OTHER DEVICES REQUIRED TO SUPPORT THE SYSTEM FUNCTIONALITY. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
5. ALL DOORS REQUIRE ROUGH-IN AT ALL LOCATIONS. REFER TO 5/T400 FOR ROUGH-IN REQUIREMENTS.
6. THIS SYSTEM INCLUDES A SINGLE SYSTEM THAT IS CAPABLE OF PROVIDING CARD ACCESS AND INTRUSION DETECTION. COORDINATE WITH THE CONTRACTOR FOR PROGRAMMING
REQUIREMENTS TO DISABLE THE ALARM SYSTEM. THE ALARM SYSTEM WILL BE DISABLED VIA A DEDICATED KEYPAD AND THE KEYPAD ON NAY CREDENTIAL READER.
7. CREDENTIALS ARE BY GOVERNMENT. CONTRACTOR SHALL INCLUDE IN THEIR BID PROGRAMMING COST TO ASSIST GOVERNMENT TO INSURE ALL CURRENT STAFF HAVE BUILDING
ACCESS.
8. THE EXISTING ACCESS CONTROL SYSTEM HEADEND IS MANUFACTURED BY SOFTWAREHOUSE. NEW SYSTEM COMPONENTS SHALL BE OF THE SAME MANUFACTURER.
KEYNOTES:
1. DOOR POSITION SWITCH WILL CONNECT TO BOTH THE ACCESS CONTROL AND INTRUSION DETECTION SYSTEM. REFER TO FLOOR PLANS AND SITE PLANS FOR ADDITIONAL
INFORMATION.
2. TYPICAL OF ALL DOORS AS SHOWN ON THE DRAWINGS. REFER TO THE CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULE ON T600 AND SPECIFICATIONS FOR QUANTITY OF
DEVICES AT EACH LOCATION.
3. A MINIMUM OF 18 AWG 4-CONDUCTOR, UNSHIELDED CABLE. 2 CONDUCTORS WILL CONNECT TO THE ACCESS CONTROL SYSTEM AND THE REMAINING 2 CONDUCTORS WILL CONNECT TO THE INTRUSION DETECTION SYSTEM. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
4. A MINIMUM OF 18 AWG 4-CONDUCTOR, SHIELDED CABLE. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION
5. A MINIMUM OF 18 AWG 6-CONDUCTOR, UNSHIELDED CABLE. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
6. CATEGORY 6 PATCH CABLE FROM THE ACCESS CONTROL SYSTEM TO THE SECURITY NETWORK. PATCH PANEL INSTALLED IN THE NEAREST TELECOM ROOM. REFER TO TELECOM ROOM
LAYOUTS ON 1/T300 AND 3/T300 FOR ADDITIONAL INFORMATION.
7. EXISTING CABLE INSTALLED UNDER SEPARATE PROJECT.
8. REFER TO FLOOR PLANS FOR CARD READER LOCATIONS.
9. CONTRACTOR SHALL PROVIDE ALL INPUT/OUTPUT CARDS, MODULES, ETC NECESSARY FOR A COMPLETE INSTALLATION AND INTEGRATE TO THE EXISTING HEADEND SYSTEM.
10. PROVIDED AND INSTALLED BY THE DOOR HARDWARE CONTRACTOR.
ADMINISTRATION BUILDING
EQUIPMENT RACK
DOOR HARDWARE 2
A
G
M
WALL MOUNTED
EQUIPMENT
K1
MAINTENANCE BUILDING TR
EXISTING
ACCESS
CONTROL
SERVER
GB1
MD1
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:3
P
M
T500
TECHNOLOGY DIAGRAMS
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 PMM TK
BID DOCUMENTS
18704
NO SCALE1
FIBER AND COPPER CONNECTIVITY DIAGRAM
NO SCALE2
TYPICAL TELECOM ROOM BONDING FLOW DIAGRAM
NO SCALE3
TECHNOLOGY BONDING RISER DIAGRAM
NO SCALE4
ACCESS CONTROL & INTRUSION DETECTION CONNECTIVITY DIAGRAM
Revisions: Date:
VA
F
O R
M
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
Office of Design and Construction
Services
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789 T-500
2-Port Faceplate
IDENTIFICATION
IDENTIFICATION
PAIR 3
PAIR 1PAIR 2 PAIR 4
WO WGO BL WBL G WBR BR
1 32 4 5 6 7 8
ANSI/TIA/EIA T568B
PIN/PAIR ASSIGNMENT
REFER TO SPECIFICATIONS FOR
IDENTIFICATION REQUIREMENTS (TYP.)
NUMBER INDICATES
FACEPLATE POSITION
(TYP.)
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:3
P
M
T600
TECHNOLOGY SCHEDULES
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 PMM TK
BID DOCUMENTS
18704
THE EQUIPMENT LIST ABBREVIATIONS AND THE TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING
SYSTEM.
CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE
DRAWINGS AND SPECIFICATIONS.
MANUFACTURER PROVIDED SHALL BE CONSISTENT WITH APPROVED MANUFACTURERS LISTED. "STANDARD COLOR" INDICATES FACTORY FINISH AT NO ADDITOINAL
CHARGE. ALL EQUIPMENT MUST MEET BY AMERICAN REQUIREMENTS.
TECHNOLOGY EQUIPMENT SCHEDULE
EQUIPMENT LIST
ABBREVIATION EQUIPMENT LIST DESCRIPTION
MANUFACTURER AND
MODEL
AC-AA-1 WALL MOUNTED AUDIBLE SIREN TO NOTIFY OF A BREACH. INSTALL DEVICE IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMT CONDUIT TO THE NEAREST SUPPORTING SECURITY PANEL
WBOX
OE-1GANGSIRN
AC-K1-W INTRUSION ALARM KEYPAD. ILLUMINATED 4-LINE DISPLAY LCD SHOWS ZONE INFORMATION. ECP BUS COMPATIBLE.
INSTALL KEYPAD IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING WITH (1) 1" CONDUIT TO ABOVE
ACCESSIBLE CEILING.
HONEYWELL
VISTA 6160
AC-R1-W DUAL AUTHENTICATION CARD READER WITH KEYPAD. PROVIDED AS INTEGRAL PART OF SECURITY MANAGEMENT SYSTEM. REFER TO CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULE FOR ADDITIONAL INFORMATION. CARD READERS SHOWN ON PLANS TO INDENTIFY INTENDED MOUNTING LOCATION. REFER TO THE SPECIFICATIONS FOR
COMPLETE INFORMATION.
HID
SIGN 40K SERIES
AC-SCP-1 SECURITY MANAGEMENT SYSTEM CONTROLLER, FOR USE WITH INTEGRATED SECURITY MANAGEMENT SYSTEM.
REFER TO SPECIFICATION SECTION 28 13 00 FOR COMPLETE INFORMATION.
SOFTWARE HOUSE
ISTAR ULTRA G2
NO SUBSTITUTIONS
ID-GB1-C GLASS BREAK CEILING SURFACE MOUNTED. PROVIDE 22/4 TO THE SECURITY PANEL. FIELD VERIFY LOCATION.
PROVIDE ONE 711S ADDRESSABLE MODULE FOR EACH LOCATION.
HONEYWELL INTELLISENSE
FG-1625RT
ID-ICP-1 INTRUSION DETECTION CONTROLLER. PROVIDES UP TO 40 POINTS INCLUDING MOTION DETECTORS, KEYPADS, GLASS BREAKS, ETC. PROVIDE WITH INPUT CARDS AS REQUIRED TO SUPPORT THE CONNECTED DEVICES. PROVIDE AN INTERFACE MODULE FOR UP TO (2) TELEPHONE LINES, A LOCKABLE CABINET, AND BATTERY BACKUP FOR A MINIMUM
OF 6 HOURS.
HONEYWELL
VISTA 128BPT SERIES
ID-MD1-C INTRUSION DETECTION MOTION SENSOR, CEILING MOUNTED, DIMENSION: 3.5" x 5.25" (H x Dia.) REQUIRE INPUT POWER 6-15 VDC; 8mA STANDARD BY, 60mA IN ALARM WITH LEDS ENABLED. DEVICE COMPLIES WITH PART 15 OF THE FCC
RULES.
BOSCH
ISC-CDL1-WA15G
PW-CPW-1 4"X4" FIREPROOF CABLE PATHWAY FOR WALLS UP TO 10" THICK. STI
44 SERIES
OR PRE-APPROVED EQUAL
SC-CT-1 CABLE TRAY, WIRE MESH TYPE, 18" LOADING DEPTH, 4" WIDTH, COMPLETE WITH ALL FITTINGS AND MOUNTING HARDWARE. PROVIDE TRAPEZE SUPPORT WITH PLASTIC RETAINER. CUTTING OF THE MESH CABLE TRAY SHALL BE DONE WITH OFFSET BOLT CUTTERS ONLY. 10' MAXIMUM SUPPORT SPAN. EITHER SPLICE WASHERS OR TERMINAL GROUND SUPPORT AND JUMPER WIRE SHALL BE USED TO ATTAIN GROUNDING CONTINUITY THROUGHOUT.
Z-BRACKETS SHALL BE USED FOR WALL MOUNTED APPLICATIONS. REFER TO MANUFACTURERS INSTALLATION
INSTRUCTIONS AND SPECIFICATION SECTION 27 05 28 FOR ADDITIONAL INFORMATION.
WBT
WBT18X4
CABOLFIL
B-LINE
CHATSWORTH
SC-ER-1 4-POST TELECOMMUNICATIONS CHANNEL RACK. 30" DEEP, 7' HIGH, WHITE FINISH, 45RU USABLE HEIGHT, 23.75" WIDE,STATIC LOAD CAPACITY OF 2,000 POUNDS, SQUARE HOLES. REFER TO 3/T401 TYPICAL RACK DIMENSIONS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
ORTRONICS
MM2073038-W
OR PRE-APPROVED EQUAL
SC-FDC-1 1-RU ANGLED FIBER DISTRIBUTION ENCLOSURE. 144 MAXIMUM FIBERS WITH SLIDING TRAY. PROVIDE COMPLETE WITH FIBER ADAPTER PANELS WITH LC CONNECTORS FOR ALL TERMINATED FIBERS. PROVIDE BLANK PANELS FOR ALL
UNUSED OPENINGS. PROVIDE CABLE CLAMP KITS AS REQUIRED, 5RCMP-KIT.
LEVITON
HDX1A-144
FIBER ADAPTER PANELS
SPLCH-12L (SM)
CABLE MANAGER:
E2XHD-CMB
BLANKS
SF100-PLT
OR PRE-APPROVED EQUAL
SC-GND-1 WALL-MOUNT GROUND BAR. 4" H X 12" L X 1/4" D COPPER, ELECTRICALLY ISOLATED BY INSULATORS INTEGRAL TO MOUNTING BRACKETS. PROVIDE UNIT CONFIGURED WITH SIXTEEN (16) SETS OF 5/16" HOLES SPACED 5/8" ON CENTER TO ACCOMMODATE "A" SPACED TWO-HOLE COMPRESSION LUGS AND THREE (3) SETS OF 7/16" HOLES SPACED 1" ON CENTER TO ACCOMMODATE "C" SPACED TWO-HOLE COMPRESSION LUGS. ANSI/EIA/TIA-607 AND BICSI COMPLIANT. UL
LISTED.
CPI
40153-012
PANDUIT
HARGER
SC-GND-2 RACK MOUNT GROUND BAR WITH FLAT WASHER AND GROUND BAR LUG. ANSI/EIA/TIA-607 AND BICSI COMPLIANT. UL
LISTED.
CHATSWORTH PRODUCTS
10610-019
SC-HWM-1 1RU HORIZONTAL CABLE MANAGER FOR 19' RACK MOUNTING, SINGLE SIDED, BLACK. FRONT COVER WITH HINGE
CLIPS. 8.31" DEEP.
ORTRONICS
SHMC1RU
SC-HWM-2 2RU HORIZONTAL CABLE MANAGER FOR 19' RACK MOUNTING, SINGLE SIDED, BLACK. FRONT COVER WITH HINGE
CLIPS. 8.86" DEEP.
ORTRONICS
SHMC2RU
SC-IO-C OUTLET, SURFACE MOUNT BOX, 2 PORT AS INDICATED ON DRAWINGS. "#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO T600 FOR INFORMATION OUTLET SCHEDULE FOR PIN CONFIGURATION. INSTALL A 1" EMT CONDUIT 6" BEYOND BOX OR TO ABOVE ACCESSIBLE CEILING AND TERMINATE WITH A NYLON BUSHING. REFER TO DETAIL 3/T400 FOR ADDITIONAL INFORMATION AND INSTALLATION
REQUIREMENTS.
SURFACE BOX -PLENUM
LEVITON
41089 SERIES
JACKS
LEVITON
6AUJK-R*6
SC-IO-F FLOOR BOX - BY ELECTRICAL REFER TO ELECTRICAL
DRAWINGS
SC-IO-W INFORMATION WALL MOUNT, 2, 4 PORT COVERPLATE AS INDICATED ON DRAWINGS. REFER TO TYPICAL INFORMATION OUTLET CONFIGURATIONS DETAIL FOR ADDITIONAL INFORMATION. "#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO INFORMATION OUTLET SCHEDULE FOR PIN CONFIGURATION. " W " PROVIDE (1) RJ-45 JACK FOR VOICE AT +48" AFF FOR WALL HUNG PHONE. PROVIDE WITH STAINLESS STEEL FACEPLATE, MATING LUGS. INSTALL NEW INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE/DOUBLE GANG PLASTER RING. INSTALL A 1 1/4" EMT CONDUIT TO ABOVE ACCESSIBLE CEILING. PROVIDE
REMOVABLE BLANK INSERTS FOR UNUSED PORTS.
LEVITON
42080 SERIES
JACKS
LEVITON
6AUJK-R*6
SC-MPP-1 ANGLED MODULAR PATCH PANEL, RACK MOUNT, 48 MODULAR RJ-45 TERMINATIONS, MOUNTS DIRECTLY TO EIA/TIA STANDARD 19" RELAY RACK, PORT IDENTIFICATION NUMBERS, COLOR-CODING, AND LABEL HOLDER KITS, U.L. LISTED.
REQUIRES (1) 1.75" MOUNTING SPACE. POPULATE PATCH PANEL FRAME WITH CAT 6A JACKS AS NEEDED FOR A COMPLETE INSTALLATION. REFER TO 2/T401 UTP PATCH PANEL FOR ADDITIONAL INFORMATION.
PROVIDE WITH ANGLED PANEL COVER.
PATCH PANEL
LEVITON
E2X1A-S48
JACKS
LEVITON
6AUJK-RB6
BLANKS
41084-0BE
ANGLED COVER
E2XHD-COV
CABLE MANAGER
E2XHD-CMB
SC-NS-1 48-PORT LAYER 2/3/4 10/100/1000 GIGABIT SWITCH - POE. 48 RJ-45 CONNECTORS FOR 10BASE - T/100BASE-TX/1000 BASE-T WITH 4 GIGABIT COMBO PORTS SHARED BETWEEN MINI-GBIC PORTS: CONSOLE PORT: AUTO MEDIUM
DEPENDENT INTERFACE (MDI) AND MDI CROSSOVER (MDI-X). AUTO.
CISCO
5500 SERIES
SC-RI-W ROUGH-IN WALL OUTLET 4" SQUARE BACKBOX WITH A SINGLE/DOUBLE GANG PLASTER RING. INSTALL 1 1/4" EMT CONDUIT TO ABOVE ACCESSIBLE CEILING. PROVIDE BLANK FACEPLATE WTIH GROMMET FOR CABLE TO PASS
THROUGH.
SC-TTB TELECOMMUNICATIONS TERMINAL BOARD, 4’X8’X3/4” A-C GRADE FIRE-RATED PLYWOOD. EXPOSED SIDE SHALL BE SMOOTH. MOUNT VERTICALLY WITH TOP OF PLYWOOD AT 8’-6” AFF. IN THE EVENT THE MANUFACTURER’S RATING STAMP IS NOT VISIBLE ON THE SMOOTH SIDE, THE CONTRACTOR SHALL PROVIDE A LAMINATED LETTER FROM THE MANUFACTURER OR SUPPLIER CERTIFYING THAT THE PLYWOOD IS FIRE-RATED AND ATTACH THE LETTER WITH A PICTURE OF THE RATING STAMP, TO THE PLYWOOD. FIRE RATED PLYWOOD SHALL NOT BE PAINTED OR TREATED WITH
ANY TYPE OF SEALANT THAT WOULD LESSEN THE INTEGRITY OF THE FIRE RATING.
SC-UPS RACK MOUNT 3KVA SMART UPS. 2 RACK UNITS. NEMA L5-30P INPUT. (3) NEMA 5-15R, (3) NEMA 5-20R, AND (1) NEMA
L5-30R OUTPUTS. RACK MOUNTABLE.
APC
SMX3000RMLV2U
SC-VWM-1 VERTICAL CABLE MANAGEMENT CAGE WITH DOOR, 6.45” X 10.26” X 76.94” WHITE CAPACITY 350 CATEGORY 6 PR 245 CATEGORY 6A PATCH CORDS. REFER TO 6" WIDE VERTICAL CABLE MANAGER FOR ADDITIONAL INFORMATION.
ORTRONICS
MM20VMD706-W
VS-CM-1 EXTERIOR/INTERIOR 5MP (SINGLE SENSOR) CAMERA. FIXED DOME CAMERA FOR OUTDOOR, HDTV 1080P VIDEO QUALITY, VANDAL-RESISTANT WITH WDR. PROVIDE A PROPER MOUNT BASED ON THE INSTALLED APPLICATIONS ON THE WALL OR CEILING. FOR WALL APPLICATIONS, PROVIDE A 4" SQUARE BACKBOX WITH CONDUIT TO ABOVE THE NEAREST ACCESSIBLE CEILING. ALL CABLING SHALL BE EITHER ABOVE THE ACCESSIBLE CEILING OR INSTALLED IN CONDUIT. NO CABLING SHALL BE EXPOSED. FOR OPEN CEILINGS, INSTALL IN CONDUIT. REFER TO THE DRAWINGS FOR
ADDITIONAL INFORMATION.
AXIS COMMUNICATIONS
P3367-VE
VS-CM-4 360 DEGREE EXTERIOR CORNER MOUNTED CAMERA. 360° OVERVIEW IN CHALLENGING LIGHT CONDITIONS. THREE SENSORS, ONE CAMERA AND ONE IP ADDRESS. 3 X QUAD HD AT 30 FPS OR 15 MP AT 20 FPS. PROVIDE A PROPER MOUNT BASED ON THE INSTALLED APPLICATIONS ON THE WALL OR CEILING. FOR WALL APPLICATIONS, PROVIDE A 4" SQUARE BACKBOX WITH CONDUIT TO ABOVE THE NEAREST ACCESSIBLE CEILING. ALL CABLING SHALL BE EITHER ABOVE THE ACCESSIBLE CEILING OR INSTALLED IN CONDUIT. NO CABLING SHALL BE EXPOSED. FOR OPEN CEILINGS, INSTALL IN CONDUIT. REFER TO THE DRAWINGS FOR ADDITIONAL INFORMATION.
AXIS COMMUNICATIONS
P3737-PLE
VS-VMS-1 VIDEO MANAGEMENT STORAGE SERVER. REFER TO SPECIFICATIONS GENETEC - MATCH EXISTING
ZONE PDU RACK MOUNT PDU, L5-30 INPUT. NEMA 5-20 OUTPUT, 1RU. ZONE*IT
Z-PDS SERIES
INDIVIDUAL CAMERA REQUIREMENTS SCHEDULE
CAMERA #
CAMERA
TYPE
CAMERA
ENVIRONMENT
TELECOM
ROOM # LOCATION FIELD OF VIEW DESCRIPTION
MOUNTING
TYPE
DETAIL
REFERENCE F
R A
M E
R A
T E
P E
R C
E N
T M
O T
IO
N
ADDITIONAL
INFORMATION NOTES
01-01 CM-1 INTERIOR TR-1 TR-1 STANDARD VIEW CEILING 2/T402 15 50
01-02 CM-1 INTERIOR TR-1 CORRIDOR STANDARD VIEW CEILING 2/T402 15 50
01-03 CM-1 INTERIOR TR-1 LOBBY STANDARD VIEW CEILING 2/T402 15 50
01-04 CM-1 INTERIOR TR-1 VESTIBULE STANDARD VIEW CEILING 2/T402 15 50
01-05 CM-4 EXTERIOR TR-1 EXTERIOR 360 DEGREE VIEW CORNER 1/T402 15 50
01-06 CM-4 EXTERIOR TR-1 EXTERIOR 360 DEGREE VIEW CORNER 1/T402 15 50
01-07 CM-4 EXTERIOR TR-1 EXTERIOR 360 DEGREE VIEW CORNER 1/T402 15 50
01-08 CM-4 EXTERIOR TR-1 EXTERIOR 360 DEGREE VIEW CORNER 1/T402 15 50
01-09 CM-4 EXTERIOR TR-1 EXTERIOR 360 DEGREE VIEW CORNER 1/T402 15 50
1. ELECTRONIC DOOR HARDWARE SUCH AS ELECTRIC STRIKES, ELECTRIC LATCH RETRACTION, ETC. SHALL BE PROVIDED AND INSTALLED BY OTHERS.
2. REFER TO THE TECHNOLOGY EQUIPMENT SCHEDULE FOR CREDENTIAL READER TYPE INFORMATION.
ACCESS CONTROL DOOR TYPE SCHEDULE
DOOR # S
E
C U
R
IT
Y D
O O
R T
Y P
E
R O
U G
H I N
O N
L Y
CREDENTIAL
READER
REQUEST TO
EXIT DOOR HARDWARE / MONITORING INTEGRATION
OTHER
(REFER TO NOTES)
D E
T A
IL
R
E F
E R
E N
C E
NOTESC
R
E D
E N
T
IA
L R
E A
D E
R T
Y P
E
M U
L T
IP
L
E C
R E
D E
N T
IA
L
R E
A D
E R
S O
P E
R A
T E
S S
IN
G
L E
D O
O R
O P
E R
A T
E S
M U
L T
IP
L
E D
O O
R S
IN
T
E R
N A
L E
L E
C T
R
IF
IE
D
H A
R D
W A
R E
C O
N N
E C
T
IO
N
B Y
O T
H E
R S
M O
T
IO
N D
E T
E C
T O
R
L O
C A
L P
U S
H B
U T
T O
N D
O O
R H
A R
D W
A R
E O
V E
R R
ID
E
E L
E C
T R
O N
IC
L
O C
K
IN
G H
A R
D W
A R
E
B Y
O T
H E
R S
M A
G L
O C
K
L O
C A
L A
L A
R M
H O
R N
L A
T C
H S
T A
T U
S D
E T
E C
T
IO
N
B Y
O T
H E
R S
M O
N
IT
O R
L A
T C
H B
O L
T
B Y
O T
H E
R S
M O
N
IT
O R
D O
O R
P O
S
IT
IO
N
S W
IT
C
H S
P D
T
M O
N
IT
O R
D O
O R
P O
S
IT
IO
N
S W
IT
C
H D
P D
T
M O
N
IT
O R
D O
O R
P O
S
IT
IO
N
S W
IT
C
H
O V
E R
H E
A D
D O
O R
M O
N
IT
O R
D O
O R
P O
S
IT
IO
N
S W
IT
C
H
R O
O F
H A
T C
H
A U
T O
M A
T
IC
D O
O R
O P
E R
A T
O R
E L
E V
A T
O R
L O
C K
E D
B Y
E M
E R
G E
N C
Y D
U R
E S
S S
E Q
U E
N C
E
IN
F
A N
T P
R O
T E
C T
IO
N
R E
M O
T E
U N
L O
C K
V
IA
I N
T E
R C
O M
M A
S T
E R
R E
M O
T E
U N
L O
C K
V
IA
P U
S H
B U
T T
O N
IN
T
R U
S
IO
N D
E T
E C
T
IO
N
R E
M O
T E
U N
L O
C K
V
IA
F
IR
E C
O M
M A
N D
C E
N T
E R
V
ID
E O
S U
R V
E
IL
L A
N C
E
W A
N D
E R
P R
E V
E N
T
IO
N S
Y S
T E
M
D E
L A
Y E
D E
G R
E S
S
B Y
O T
H E
R S
L O
C A
L
V
A C
P O
W E
R S
U P
P L
Y
S C
H E
D U
L E
B A
S E
D L
O C
K
IN
G
V
IS
U A
L S
T R
O B
E /A
U D
IB
L
E A
L A
R M
101A RME R1 ● ● ● ●
105B RME R1 ● ● ●
105C RME R1 ● ● ● ●
B01A RME R1 ● ● ●
B03A RME R2 ● ● ●
SUPPORT FOR POSSIBLE RELOCATION AFTER WIRELESS SURVEY.
1. LOCATION OF FUTURE OR OWNER PROVIDED WIRELESS ACCESS POINT. PROVIDE A 20' SLACK COIL AT THE NEAREST CABLE
SCHEDULE NOTES:
2. REFER TO SPECIFICATIONS SECTION 27 05 53 FOR ADDITIONAL INFORMATION ON LABELING REQUIREMENTS. VOICE CAT 6 RJ-45
1. PROVIDE REMOVABLE BLANK INSERT(S) FOR ALL UNUSED PORTS. DATA CAT 6 RJ-45
NOTES: LEGEND
SINGLE GANG WALLPLATES
TELECOMMUNICATIONS OUTLET SCHEDULE
CONFIGURATION F
A
C E
P L
A T
E P
O R
T S
FACEPLATE PORT IDENTIFICATION
NOTESP
O
S
IT
IO
N
J
A C
K T
Y P
E
P O
S
IT
IO
N
J
A C
K T
Y P
E
P O
S
IT
IO
N
J
A C
K T
Y P
E
P O
S
IT
IO
N
J
A C
K T
Y P
E
P O
S
IT
IO
N
J
A C
K T
Y P
E
P O
S
IT
IO
N
J
A C
K T
Y P
E
C2 2 DATA DATA .
C2-M 2 DATA DATA
C2-WAP 2 DATA DATA 1.
W 1 VOICE
Revisions: Date:
VA
F
O
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
Office of Design and Construction
Services
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789 T-600
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 KEYNOTE: INDICATES NOTE USED TO
DESCRIBE ADDITIONAL INFORMATION
ABOUT WORK REQUIRED, SPECIFIC
TO THE SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
FIRE ALARM NOTIFICATION AND SIGNAL WIRING
WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,
INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)
FIRE ALARM CONDUIT INSTALLATION SCHEDULE
THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT
SPECIFIED IN THIS SCHEDULE.
INSTALLATION TYPE RMC EMT
X
X
INTERIOR LOCATIONS WITH FINISHED CEILING AND WALLS: CONCEALED
IN WALLS AND ABOVE FINISHED CEILINGS
INTERIOR LOCATIONS WITHOUT FINISHED CEILINGS: CONCEALED IN
WALL, EXPOSED ABOVE CEILINGS
X
X
ASR
EXISTING INTERIOR LOCATIONS WITH FINISHED CEILINGS AND WALLS:
CONCEALED IN WALLS AND ABOVE FINISHED CEILING UNLESS
OTHERWISE NOTED
X
PVC
CONCRETE
ENCASED
UNDERGROUND / SLABS ON GRADE
(IN OR UNDER SLABS ON GRADE)
WITHIN 5' FROM PERIMETER OF THE BUILDING
WITHIN 5' FROM THE PERIMETER OF THE BUILDING WHEN PASSING
THROUGH THE PERIMETER OF THE BUILDING FOUNDATION:
UNDERGROUND SITE CONDUITS:
WITHIN 5' FROM THE PERIMETER OF A BUILDING FOUNDATION
5' OR GREATER FROM THE PERIMETER OF A BUILDING FOUNDATION
X
X
X
X
X
NAC
HVAC UNIT SHUTDOWN (TYPICAL)
(TYP)
SIGNAL LINE CIRCUIT
(SLC)
NOTIFICATION
APPLIANCE CIRCUIT
(NAC)
EXISTING FIRE
ALARM PANEL
2 3
KEYNOTES:
1. REPRESENTATIVE OF PROGRAMMABLE I/O POINTS IN THE PANEL OR A GENERAL
SYSTEM TROUBLE/ALARM CONTACT CONNECTED TO THE SYSTEM NOTED. REFER
TO SPECIFICATIONS FOR MORE INFORMATION.
2. REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH INITIATION LOOP AND
WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.
3. REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH NOTIFICATION
APPLIANCE CIRCUIT AND WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES
AND THEIR LOCATIONS.
4. PROVIDE NOTIFICATION APPLIANCE EXTENDER PANELS AS REQUIRED.
DETERMINATION OF NEED TO BE MADE BY FIRE ALARM VENDOR. REFER TO
SPECIFICATIONS FOR REQUIREMENTS AND ACCEPTABLE MOUNTING LOCATIONS.
5. REPRESENTS THE EXTENSION OF PROGRAMMABLE RELAYS TO THE ACCESS
CONTROL SYSTEM. REFER TO SPECIFICATION SECTION 28 13 00 FOR QUANTITY OF
POINTS REQUIRED.
6. PROVIDE STANDALONE CELLULAR MODEM. OWNER WILL PROVIDE CELLULAR
SERVICE CONTRACT AS REQUIRED.
NOTES:
1. THE RISER DIAGRAM IS INTENDED TO CONVEY THE TYPES OF FIRE ALARM
CONNECTIONS AND SPECIFICALLY DOES NOT INDICATE QUANTITIES, NUMBER OF
CIRCUITS REQUIRED OR DISTANCES.
2. THE COMPLETE FIRE ALARM SYSTEM SHALL MEET ALL APPLICABLE CODES AND
MANUFACTURER'S RECOMMENDATIONS.
3. CONTRACTOR SHALL COORDINATE ALL WIRE SIZES, TYPES AND REQUIREMENTS
WITH THE VENDOR PRIOR TO BID. REFER TO SPECIFICATIONS TO DETERMINE
CIRCUIT STYLES AND IF CONDUIT IS REQUIRED OR PLENUM RATED CABLE IS
ACCEPTABLE.
4. ALL +120VAC WIRING REQUIRED FOR OPERATION OF THE SYSTEM AS DESCRIBED
IN THE CONSTRUCTION DOCUMENTS SHALL BE PROVIDED BY THE ELECTRICAL
CONTRACTOR.
5. ALL NECESSARY RELAYS MAY NOT BE SHOWN ON THIS PLAN, BUT WHERE
REQUIRED FOR PROPER OPERATION OF THE SYSTEM THEY SHALL BE PROVIDED
BY THE CONTRACTOR.
F
F
S #F
SRT
CM
H
CELLULAR
DIGITAL
COMMUNICATOR
ACCESS
CONTROL PANEL
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE 2010 (LATEST
PUBLISHED) ADA STANDARDS FOR ACCESSIBLE DESIGN. REFER TO THE ADA STANDARDS
FOR ALL CONFIGURATION DETAILS ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)
EXCEPT WHERE OTHERWISE NOTED.
3. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED
FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE
NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.
4. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS, SHALL
BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.
CARBON MONOXIDE DETECTORS SHALL BE LOCATED 10 PLUS FT FROM FIRE PLACES,
COOKING, AND SIMILAR FUEL-BURNING APPLIANCES.
5. FIRE ALARM EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF, OPERATION OF,
AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF FIRE
ALARM EQUIPMENT, ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE
APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
7. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE
IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES.
FIRE ALARM INSTALLATION NOTES:
GENERAL FIRE ALARM EQUIPMENT SCHEDULE
THE SYMBOLS AND THE EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING
SYSTEM.
CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGS AND SPECIFICATIONS. MANUFACTURER PROVIDED SHALL BE CONSISTENT WITH APPROVED MANUFACTURERS LISTED. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE. ALL EQUIPMENT MUST MEET BUY
AMERICAN REQUIREMENTS. REFER TO SPECIFICATIONS FOR MORE INFORMATION.
ITEM
NO
SYMBOL DESCRIPTION
FIRE ALARM CEILING VISUAL NOTIFICATION APPLIANCE, HIGH-INTENSITY STROBE, WHITE HOUSING
WITH RED LETTERING OR PICTOGRAM, SEMI-FLUSH CEILING MOUNT; 24 VDC.
CANDELA RATINGS: 15cd, 75cd. CANDELA
RATING SHALL BE VISIBLE FROM THE OUTSIDE OF THE DEVICE.
SIEMENS FIRE SAFETY
SMOKE DETECTOR, ADDRESSABLE, ANALOG PHOTOELECTRIC SENSOR, 24 VDC, 2-PIECE DESIGN, LOW-PROFILE MOUNTING BASE WITH MULTI-FUNCTION LED INDICATOR, COMPLETE WITH MOUNTING
HARDWARE AND BACKBOX.
SIEMENS FIRE SAFETY
HEAT DETECTOR, ADDRESSABLE, ANALOG SENSOR, COMBINATION RATE OF RISE AND 135 DEGREE FAHRENHEIT FIXED TEMPERATURE, 2-WIRE OPERATION, 24 VDC, 2-PIECE DESIGN, LOW-PROFILE
MOUNTING BASE WITH MULTI-FUNCTION LED INDICATOR, COMPLETE WITH MOUNTING HARDWARE
AND BACKBOX. PROVIDE A REMOTE LED INDICATOR DEVICE IF DETECTOR IS NOT VISIBLE FROM A
FLOOR-STANDING POSITION.
H
FIRE ALARM CEILING AUDIO/VISUAL NOTIFICATION APPLIANCE, ELECTRONIC HORN WITH
SELECTABLE CONTINUOUS OR TEMPORAL TONE, SELECTABLE SOUND OUTPUT, AND HIGH
INTENSITY STROBE, WHITE HOUSING WITH RED LETTERING OR PICTOGRAM, SEMI-FLUSH CEILING
MOUNT, 24 VDC.
CANDELA RATINGS: 15cd, 75cd. CANDELA
RATING SHALL BE VISIBLE FROM THE OUTSIDE OF THE DEVICE.
SIEMENS FIRE SAFETY
F
S
FIRE ALARM MANUAL PULL STATION, ADDRESSABLE, DOUBLE ACTION WITH PLASTIC BREAKROD, RESET KEY LOCK, SEMI-FLUSH MOUNT, RED HIGH-ABUSE PLASTIC OR CAST METAL
CONSTRUCTION WITH WHITE LETTERING. USE SURFACE MOUNT ONLY ON PRECAST CONCRETE
OR STRUCTURE.
SIEMENS FIRE SAFETY
F
S
DUCT TYPE SMOKE DETECTOR, PHOTOELECTRIC TYPE, 4-WIRE OPERATION, 24 VDC, LED ALARM
INDICATOR, SAMPLING TUBES SIZED TO MATCH DUCT APPLICATION, HOUSING WITH COMPLETE
MOUNTING ACCESSORIES. PROVIDE A REMOTE ALARM LED INDICATOR WITH TEST SWITCH IF
DETECTOR IS NOT VISIBLE FROM A FLOOR-STANDING POSITION. IF DETECTOR IS LOCATED ABOVE A SUSPENDED CEILING, MOUNT REMOTE INDICATOR IN CEILING DIRECTLY BELOW DETECTOR WITH A
WHITE SINGLE-GANG FACEPLATE LABELED: DUCT SMOKE DETECTOR.
SIEMENS FIRE SAFETY
SIEMENS FIRE SAFETY
FIRE ALARM ADDRESSABLE RELAY CONSISTING OF AN ADDRESSABLE CONTROL MODULE AND
SLAVE RELAY WITH CONTACTS SUITABLE FOR CONTROLLING THE DESIGNATED AUXILIARY LOAD, PROVIDE AN ADDITIONAL CHILD RELAY(S) AS REQUIRED, 24 VDC, 4-WIRE OPERATION, MOUNT IN
ENCLOUSER IN AN ACCESSIBLE SERVICE LOCATION.
SIEMENS FIRE SAFETY
CM
GAS DETECTOR, ADDRESSABLE, ANALOG CARBON MONOXIDE TYPE SENSOR, CARBON MONOXIDE
ELECTROLYTIC SENSING MODULE SHALL PROVIDE TOXIC GAS SENSING TO UL2034 AND UL2075
STANDARDS, 24 VDC, LOW-PROFILE MOUNTING BASE WITH MULTI-FUNCTION LED INDICATOR,
COMPLETE WITH MOUNTING HARDWARE AND BACKBOX. CO SENSOR CARTRIDGE ELEMENT SHALL
BE FIELD REPLACEABLE.
SIEMENS FIRE SAFETY
APPROVED MANUFACTURERS
BUILDING CODE: IBC 2024 EDITION
FIRE CODE: IFC 2024 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2023 EDITION
LIFE SAFETY CODE: NFPA 101 2024 EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS
INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:
CONTACT PERSONS:
PROJECT MANAGER
FIRE ALARM
TECHNOLOGY
MATT SNYDER
MATT SNYDER
PETE MCGHEE
DESCRIPTION: PERSON:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS. CONTRACTOR SHALL REVIEW EXISTING
CONDITIONS AND REPORT CONFLICTS.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. CONTRACTOR
SHALL REVIEW EXISTING CONDITIONS AND REPORT CONFLICTS.
3. CONTRACTOR SHALL REVIEW EXISTING CONDITIONS PRIOR TO FABRICATION OF CABLE
TRAY, BUSWAY, CONDUIT RACKS, AND OTHER SYSTEMS. RISES AND DROPS MAY BE
NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. ELECTRICAL CONTRACTOR SHALL REVIEW EXISTING CONDITIONS TO VERIFY ACCESSIBILITY
TO THE AREAS OF THEIR WORK INCLUDING WALLS, FLOOR, CEILINGS, CEILING TILES/GRID,
AND ROOF. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE CUTTING, REMOVAL,
PATCHING, AND REINSTALLATION OF AFFECTED AREAS ASSOCIATED WITH THEIR WORK BY
COORDINATING WITH THE GENERAL CONTRACTOR OR QUALIFIED CONTRACTOR.
5. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
FIRE ALARM RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO FIRE ALARM.
SYSTEM INPUTS
SEQUENCE OF
OPERATION
P A
N E
L /A
N N
U N
C
IA
T O
R A
L A
R M
I N
D
IC
A T
IO
N
P A
N E
L /A
N N
U N
C
IA
T O
R S
U P
E R
V
IS
O R
Y I N
D
IC
A T
IO
N
P A
N E
L /A
N N
U N
C
IA
T O
R T
R O
U B
L E
I N
D
IC
A T
IO
N
A U
D
IB
L E
A L A
R
S
E
Q U
E N
C E
V
IS
U A
L A
L A
R
E
Q U
E N
C E
FIRE ALARM PANEL, TRANSPONDER, NAC PANEL
LOW BATTERY
FIRE ALARM PANEL, TRANSPONDER, NAC PANEL
BATTERY OR CHARGER FAILURE
FIRE ALARM PANEL, TRANSPONDER, NAC PANEL
ABNORMAL SWITCH OR CONTROL POSITION.
FIRE ALARM PANEL, TRANSPONDER, NAC PANEL
GROUND FAULT, OPEN CIRCUIT, SHORT CIRCUIT
FIRE ALARM PANEL, TRANSPONDER, NAC PANEL
AC POWER LOSS OR IRREGULARITY
INITIATING DEVICE
FAILURE OR COMMUNICATION ERROR
FIRE ALARM PANEL
MANUAL FIRE DRILL
SMOKE DETECTOR
NOTIFICATION APPLIANCE CIRCUIT OR SLC LOOP
GROUND FAULT, OPEN CIRCUIT, SHORT CIRCUIT
HEAT DETECTOR
SMOKE DETECTOR
FOR HVAC CONTROL
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
NOTES:
1. ALL SYSTEM EVENTS SHALL BE LOGGED. SEE SPECIFICATIONS FOR MORE
INFORMATION AND DESCRIPTIONS OF SEQUENCES OF OPERATION.
SS
S
HH
H
SS
S S
HH
A H
U
M E
C H
A N
IC
A
L F
A N
H U
T D
O W
N S
E Q
U E
N C
E
X
GAS DETECTOR
XMM
# # X X
A C
C E
S S
C O
N T
R O
L
O V
E R
R
ID
E S
E Q
U E
N C
E
X
X
X
FIRE ALARM SHEET INDEX
FA000 FIRE ALARM COVERSHEET
FA001 LOWER LEVEL DEMOLITION PLAN - FIRE ALARM
FA002 FIRST LEVEL DEMOLITION PLAN - FIRE ALARM
FA100 LOWER LEVEL PLAN - FIRE ALARM
FA101 FIRST LEVEL PLAN - FIRE ALARM
GRAND TOTAL: 5
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:4
A
M
FA000
FIRE ALARM COVERSHEET
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 JDD SAC
BID DOCUMENTS
18704
NO SCALE1
FIRE ALARM RISER
NO SCALE2
FIRE ALARM OPERATION MATRIX
Revisions: Date: EXPIRES 4/30/2028VA F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
STAMP
U.S. Department of Veterans Affairs
Office of Design and Construction
Services
EXPIRES 4/30/2028
F
S
H
C
G
F
E
D
3 4 5
4.1 5.1
3.1
D.1
EXISTING PANEL A
EXISTING FIRE ALARM CONTROL
PANEL (SIEMENS DESIGO)
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:4
A
M
FA001
LOWER LEVEL DEMOLITION PLAN -
FIRE ALARM
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 JDD SAC
BID DOCUMENTS
18704
N O R
HT
1/4" = 1'-0"1
LOWER LEVEL DEMOLITION PLAN - FIRE ALARM
SHEET NOTES:
1. REFER TO FA000 FOR FIRE ALARM RENOVATION
NOTES, FIRE ALARM INSTALLATION NOTES AND
VIEW KEY.
2. CONTRACTOR TO PATCH AND PAINT THE
DAMAGED WALL/CEILING AREAS AND
ABANDONED OPENINGS AS REQUIRED TO
MATCH THE ORIGINAL CONSTRUCTION AFTER
DEMOLITION.
3. EXISTING CONDUIT TO BE ABANDONED SHALL
BE REMOVED IF EXPOSED.
Revisions: Date: EXPIRES 4/30/2028VA F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
STAMP
U.S. Department of Veterans Affairs
Office of Design and Construction
Services
S S
F
F
S
S
S
S
F
S S
F
S
S
F
S
H
C
G
F
E
D
3 4 5
4.1 5.1
3.1
D.1
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:5
A
M
FA002
FIRST LEVEL DEMOLITION PLAN -
FIRE ALARM
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 JDD SAC
BID DOCUMENTS
18704
N O R
HT
1/4" = 1'-0"1
FIRST LEVEL DEMOLITION PLAN - FIRE ALARM
SHEET NOTES:
1. REFER TO FA000 FOR FIRE ALARM RENOVATION
NOTES, FIRE ALARM INSTALLATION NOTES AND
VIEW KEY.
2. CONTRACTOR TO PATCH AND PAINT THE
DAMAGED WALL/CEILING AREAS AND
ABANDONED OPENINGS AS REQUIRED TO
MATCH THE ORIGINAL CONSTRUCTION AFTER
DEMOLITION.
3. EXISTING CONDUIT TO BE ABANDONED SHALL
BE REMOVED IF EXPOSED.
Revisions: Date: EXPIRES 4/30/2028VA F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
STAMP
U.S. Department of Veterans Affairs
Office of Design and Construction
Services
F
F
S
S
H
HF
F
F
F
S
F
S
S S
C M
C M
H
C
G
F
E
D
B
A
2.1
4 5
4.1 5.1
3.1
D.1
ELECTRICAL
B04
TR
B03
BASEMENT
B02
BASEMENT
B01
STAIRS
B05
E1
EXISTING PANEL A
EXISTING FIRE ALARM CONTROL
PANEL (SIEMENS DESIGO)
AHU-01 RETURN
AHU-01 SUPPLY
E4
E3
AHU-01
E2
CO
ACCESS CONTROL
SYSTEM
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:5
A
M
FA100
LOWER LEVEL PLAN - FIRE ALARM
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 JDD SAC
BID DOCUMENTS
18704
N O R
HT
1/4" = 1'-0"1
LOWER LEVEL PLAN - FIRE ALARM
KEYNOTES
E1 MOUNT SMOKE DETECTOR WITHIN 5'-0" OF
EXISTING FIRE ALARM CONTROL PANEL.
E2 PROVIDE FIRE ALARM CONTROL MODULE WITHIN
HVAC UNIT CONTROL CABINET. COORDINATE
EXACT MOUNTING LOCATION WITH M.C. RELAY
SHALL PROVIDE SIGNAL TO SHUTDOWN HVAC
UNIT. MOUNT WITHIN 3'-0" OF CONTROLLER.
E3 MOUNT DUCT TYPE SMOKE DETECTOR ABOVE
ACCESSIBLE CEILING IN RETURN DUCT AHEAD
OF LAST DUCT TAP.
E4 MOUNT DUCT TYPE SMOKE DETECTOR ABOVE
ACCESSIBLE CEILING IN SUPPLY DUCT AHEAD OF
FIRST DUCT TAP.
SHEET NOTES:
1. REFER TO FA000 FOR GENERAL FIRE ALARM
EQUIPMENT SCHEDULE, FIRE ALARM
INSTALLATION NOTES AND VIEW KEY.
2. REFER TO 1/FA000 FOR FIRE ALARM
RISER AND 2/FA000 FOR FIRE ALARM
OPERATION MATRIX.
3. PROVIDE ARCHITECTURAL SURFACE RACEWAY
TO INSTALL THE NEW DEVICE ON EXISTING
WALL AND CEILING IN PUBLIC FINISHED SPACES
WHERE WALLS ARE FINISHED. IF APPLICABLE,
THE CONTRACTOR IS ALLOWED TO INSTALL
NEW DEVICE IN EXISTING RECESSED BACKBOX
AND UTILIZE EXISTING CONCEALED CONDUIT TO
RUN NEW WIRING.
Revisions: Date: EXPIRES 4/30/2028VA F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
STAMP
U.S. Department of Veterans Affairs
Office of Design and Construction
Services
S
F
F
15 15
S S
F
S
F
S
F
F
F
F
F
S
S
S S
F
S
F
S
S
S S
S
S S
S
H
F
F
H
C
G
F
E
D
B
A
2.1
4 5
4.1 5.1
3.1
D.1
ASSISTANT DIRECTOR
PROGRAM ANALYST
BUDGET ANALYST
OPERATIONAL CTR
DIRECTOR
STAFF MEN
114A STAFF WOMEN
113A
ADMIN OFFICER
MULTIPURPOSE ROOM
HAC
MENS
WOMENS
LOBBY
HALLWAY
STORAGE
HALLWAY
105c
WORKSTATIONS
HALLWAY
105b
BREAK ROOM
MENS LOCKER ROOM
WOMENS LOCKER ROOM
CO
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
BID DOCUMENTS
400 5th St
West Des Moines, IA 50265
(515) 225-6265
9000 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTCHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
OPTIONAL BID #1
A u to d e s k D o c s /2
.0
N C
A C a m p L e a v e n w o rt h G ra v e s it e
E x p a n s io n /E
T
.0
N
C A
C a m p L e a v e n w o rt h
G ra v e s it e E x p a n s io n C
.r v t
/1
/2
:5
:5
A
M
FA101
FIRST LEVEL PLAN - FIRE ALARM
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 JDD SAC
BID DOCUMENTS
18704
N O R
HT
1/4" = 1'-0"1
FIRST LEVEL PLAN - FIRE ALARM
SHEET NOTES:
1. REFER TO FA000 FOR GENERAL FIRE ALARM
EQUIPMENT SCHEDULE, FIRE ALARM
INSTALLATION NOTES AND VIEW KEY.
2. REFER TO 1/FA000 FOR FIRE ALARM
RISER AND 2/FA000 FOR FIRE ALARM
OPERATION MATRIX.
3. PROVIDE ARCHITECTURAL SURFACE RACEWAY
TO INSTALL THE NEW DEVICE ON EXISTING
WALL AND CEILING IN PUBLIC FINISHED SPACES
WHERE WALLS ARE FINISHED. IF APPLICABLE,
THE CONTRACTOR IS ALLOWED TO INSTALL
NEW DEVICE IN EXISTING RECESSED BACKBOX
AND UTILIZE EXISTING CONCEALED CONDUIT TO
RUN NEW WIRING.
Revisions: Date: EXPIRES 4/30/2028VA F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST…