_26 LNC BD - ELECTRICAL (pg 201-214).pdf
PDF 14 MB Posted
- Solicitation number
- 36C78626B0027
About this file
This document is a comprehensive set of electrical design and construction drawings for the Leavenworth National Cemetery Gravesite Expansion project located at 150 Muncie Road, Leavenworth, Kansas. The electrical scope includes site electrical plans, demolition plans for lower and first levels, lighting plans, power distribution plans, equipment power plans, lightning protection plans, one-line diagrams, electrical details, and schedules.
The project involves establishing new electrical infrastructure for an administrative building with a 150 kVA, 4160V to 208Y/120V transformer serving as the primary power source. Key deliverables include a Main Distribution Panel (MDP) with 600-ampere, 208Y/120V, three-phase, four-wire service rated for 14,095 amperes available short-circuit current and 10 kA SCCR; Panel A with 225-ampere capacity for general branch circuits; and Panel Equipment with 400-ampere capacity for mechanical equipment. The electrical systems must comply with the National Electrical Code (NEC), NFPA 780 for lightning protection systems, and local Kansas codes. Lighting fixtures include LED downlights, flat panels, linear fixtures, emergency exit signs, and emergency lighting units with dimming controls and occupancy sensors. All materials must be commercial grade, new, listed by nationally recognized testing laboratories, and Buy America Act (BABA) compliant. The contractor is responsible for coordinating with mechanical systems, maintaining NEC clearances, providing complete operations and maintenance manuals, and performing work under a licensed master electrician's supervision with all required permits and fees.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1P 1 Pole (2P, 3P, 4P, ETC.)
A, Amp Ampere AC Above Counter ACLG Above Ceiling ADO Automatic Door Opener AF Amp Frame AFF Above Finished Floor AFG Above Finished Grade AFI Arc Fault Circuit
Interrupter AHU Air Handling Unit AL Aluminum ALT Alternate AMP Ampere AMPL Amplifier ANNUN Annunciator APPROX Approximately AQ-STAT Aquastat ARCH Architect, Architectural AS Amp Switch AT Amp Trip ATS Automatic Transfer Switch AUTO Automatic AUX Auxiliary AV Audio Visual AWG American Wire Gauge BATT Battery BD Board BLDG Building BMS Building Management System C Conduit CAB Cabinet CAT Catalog CATV Cable Television CB Circuit Breaker CCTV Closed Circuit Television CKT Circuit CLG Ceiling COMB Combination CMPR Compressor CONN Connection CONST Construction CONT Continuation Or Continuous CONTR Contractor CONV Convector CP Circulating Pump CRT Cathode-Ray Tube CT Current Transformer CTR Center CU Copper DCP Domestic Water Circulating Pump DEPT Department DET Detail DIA Diameter DISC Disconnect DIST Distribution DN Down DPR Damper DS Safety Disconnect Switch DT Double Throw DWG Drawing EC Electrical Contractor ELEC Electric, Electrical ELEV Elevator ELU Emergency Lighting Unit EM Emergency EMS Energy Management System EMT Electrical Metallic Tubing EP Electric Pneumatic EQUIP Equipment EWC Electric Water Cooler EXIST Existing EXH Exhaust EXP Explosion Proof FA Fire Alarm FABP Fire Alarm Booster Power
Supply Panel FACP Fire Alarm Control Panel FCU Fan Coil Unit FIXT Fixture FLR Floor FLUOR Fluorescent FU Fuse FUDS Fused Safety Disconnect Switch GA Gauge GAL Gallon GALV Galvanized GC General Contractor GEN Generator GFI Ground Fault Circuit Interrupter GFP Ground Fault Protector GND Ground GRS Galvanized Rigid Steel (Conduit) GYP BD Gypsum Board HOA Hands-Off-Automatic Switch HORIZ Horizontal HP Horsepower HPF High Power Factor HT Height HTG Heating HTR Heater HV High Voltage HVAC Heating, Ventilating And Air
Conditioning IC Interrupting Capacity IG Isolated Ground IMC Intermediate Metal Conduit INCAND Incandescent IR Infrared I/W Interlock With J-BOX Junction Box KV Kilovolt KVA Kilovolt-Ampere KVAR Kilovolt-Ampere Reactive KW Kilowatt KWH Kilowatt Hour LOC Locate Or Location LT Light LTG Lighting LTNG Lightning LV Low Voltage MAX Maximum MAG.S Magnetic Starter M/C Momentary Contact MC Mechanical Contractor
Electrical Abbreviations
Electrical DeviceTags: Uppercase letter(s) indicates Panel ID and circuit number. Lowercase letter indicates designation of controlling switch (where applicable).
Switch ID indicated by a lowercase letter. Switch IDs are unique per space. A switch with an ID "a" controls all devices within the space in which it is located tagged with "a". A switch without a tagged ID controls all lighting fixtures within a space. ID tags may be used on control devices other than switches, such as occupancy sensors or contactors.
Equipment Tags: Equipment ID is indicated by an underlined tag adjacent to the equipment. See the equipment connection schedule for description, electrical requirements, and panel and circuit number. Symbols/graphic appearance of equipment varies.
Solid, arced lines connecting equipment, devices, or fixtures indicate unswitched power circuiting. Wires are only intended to indicate to what circuit devices are connected. Actual connections, circuit routing, installation, junction boxes, etc. shall be field-determined by the contractor.
Home run to branch circuit panelboard. The equipment name and circuit number(s) are indicated, separated by a hyphen. Homeruns are only intended to indicate panel and circuit number. Actual homerun location shall be field-determined by the contractor.
Power Symbols
Electrical Symbol Legend
Room
MCB Main Circuit Breaker MCC Motor Control Center MDC Main Distribution Center MDP Main Distribution Panel MFR Manufacturer MFS Main Fused Disconnect Switch MH Manhole MIC Microphone MIN Minimum MISC Miscellaneous MLO Main Lugs Only MMS Manual Motor Starter MOA Multioutlet Assembly MSP Motor Starter Panelboard MSBD Main Switchboard MSS Motor Starter Switch MT Mount MT.C Empty Conduit MTS Manual Transfer Switch MTR Motor, Motorized N.C. Normally Closed NEC National Electrical Code NEMA National Electrical
Manufacturer's Association NFSD Non-Fused Safety Disconnect
Switch NIC Not In Contract NL Night Light N.O. Normally Open NPF Normal Power Factor NTS Not To Scale OC On Center OH Overhead OL Overloads PA Public Address PB Pull Box Or Pushbutton PE Pneumatic Electric PED Pedestal PF Power Factor PH Phase PIV Post Indicating Valve PNL Panel PP Power Pole PR Pair PRI Primary PROJ Projection PRV Power Roof Ventilator PT Potential Transformer PVC Polyvinyl Chloride (Conduit) PWR Power QUAN Quantity RCPT Receptacle REQD Required RM Room RSC Rigid Steel Conduit RTU Roof Top Unit SC Surface Conduit SEC Secondary SHT Sheet SIM Similar SLD Single-Line Diagram S/N Solid Neutral SPEC Specification SPKR Speaker SP Spare SPP Single-Point Power SR Surface Raceway SS Stainless Steel SSW Selector Switch S/S Stop/Start Pushbuttons STA Station STD Standard SURF Surface Mounted SW Switch SWBD Switchboard SYM Symmetrical SYS System TEL Telephone TERM Terminal TL Twist Lock TR Tamper Resistant T-STAT Thermostat TTC Telephone Terminal Cabinet TV Television TVTC Television Terminal Cabinet TYP Typical UC Under Counter UE Underground Electrical UG Underground UH Unit Heater UT Underground Telephone UTIL Utility UV Ultraviolet V Volt VA Volt-Amperes VDT Video Display Terminal VERT Vertical VFD Variable Frequency Drive VOL Volume W Watt W/ With WG Wire Guard WH Water Heater W/O Without WP Weatherproof XFMR Transformer XFR Transfer
∠ Angle
@ At ▲ Delta ' Feet " Inches # Number Ø Phase C Center Line P Plate
Exit Light, Wall-Mounted.
Shading and arrows indicate faces and directional chevrons.
Wall-mounted fixtures, Typical (Various Symbols)
Emergency Lighting Unit, Wall-Mounted, Remote Battery
Emergency Lighting Unit, Wall-Mounted, Integral Battery
Emergency Lighting Unit, Ceiling-Mounted, Integral Battery
Emergency Lighting Unit, Ceiling-Mounted, Remote Battery
Lighting Fixtures, Typical, Rectangular (Various Symbols) Filled circles indicate recessed.
Open circles indicate surface-mounted.
Diagonal line indicates lensed.
Outer dots indicate suspended.
Lighting Fixtures, Typical, Round (Various Symbols) Center dot indicates pendant.
Diagonal line indicates lensed.
Chevron indicates wall wash.
Strip Fixture
Directional Light, Track Light, Flood Light
Exit Light, Ceiling-Mounted.
Shading and arrows indicate faces and directional chevrons.
Linear Light, Tape Light
Exit/ELU Combo
Diagonal hatch indicates light on a critical circuit.
Solid hatch indicates light on an emergency or life safety circuit.
Pole/Area Lights
Post-Top Area Light
Bollard Light
Single-Pole Switch
Two-Pole Switch
Three-Pole Switch
Switch Modifiers:
3: 3-Way 4: 4-Way K: Keyed D: Dimming T: Timer
OS: Occupancy Sensor VS: Vacancy Sensor AC: Above-Counter LV: Low-Voltage M: Motor-Rated
Lighting Contactor
Lighting Control Panel
Occupancy Sensor
Daylight Harvesting Sensor
Simplex Receptacle
Duplex Receptacle
Quadruplex Receptacle
Special Receptacle, Type as Indicated
W al l
C ei lin g
F lo or
Receptacle Modifiers:
##": Height AFF OC AC: Above Counter GFI: Ground-Fault Circuit Interrupter WP: Weatherproof In-Use Cover
Half shading indicates split (typically switched)
Outside shading indicates emergency circuit
Center shading indicates isolated ground
Multioutlet Assembly Filled squares indicate 120V outlet Open squares indicate with USB
Cord Reel, Device Varies
Drop Cord, Device Varies
Junction Box
Floor Box, see schedule for type
Emergency Power Off
Door Opener Push Plate
Power Meter
Safety Switch, Fused
Safety Switch, Unfused
Motor Starter
Combination Starter/Disconnect
Lighting Symbols
Contactor
Single-Pole Switch
Two-Pole Switch
Three-Pole Switch
Switch Modifiers:
K: Keyed T: Timer AC: Above-Counter M: Motor-Rated a
A A1a
Equipment is tagged with Panel Name and with Panel ID in parentheses. Panel ID is intended as a design documentation aid only. Do not include Panel ID in field-applied circuit directories or labels.
Hatched fill indicates distribution panel or switchboard.
Solid fill indicates branch panel or load center.
Dashed box indicates code-required clearance (width and depth).
Door indicates front of recessed panel.
Panelboards are assigned an abbreviated indicator (or Panel ID) for use with circuit numbers. Panel ID is listed within the panel schedule and in the panel abbreviation schedule.
Power Distribution Equipment
H P
1A (B
LP
1A
(C
M D
P (A
SB1(S)
Devices and fixtures are tagged with Panel ID and circuit number. For example, a device tagged with "A1" indicates the device is circuited to panel designated "A," circuit number 1. The panel schedule circuit number contains both the panel abbreviation and the circuit number.
XX-1
Transformer: Typically transformer names begin with or contain the letter "T". See Single-Line Diagram for description and requirements.
T1
Dashed, arced lines connecting equipment, devices, or fixtures indicate switched power.
Absence of a switch designation on a lighting fixture indicates fixture is controlled by the only switch in the space. An "x" in place of the switch designation indicates unswitched.
Bottom Value, Lowercase Letter: Switch ID
Lighting Tags
Top Value: Fixture Type ID (Underlined)
Bottom Value, Uppercase Letter(s): Panel ID
Bottom Value, Number(s): Circuit Number a a
C1a
Wiring
Power Device and Equipment Tags
Construction Phasing
Existing to Remain
Existing to Be Demolished
New
(Typical All Symbols and Equipment)
Existing to Be Demolished
Area Not in Contract
Miscellaneous
Keynote
Callout:
Top Value: Detail Number on Sheet Bottom Value: Sheet Number of Detail
Room Name and Number
Low voltage digital wall switch
Low voltage digital occupancy sensor wall switch
General Notes
A. Conductors operating at 50 volts or greater shall be in raceway. Raceway within the structure above the floor slab shall be metal. Raceway below the floor slab and underground raceway outside the structure shall be PVC.
B. Low voltage cables or conductors operating at less than 50 volts shall be in metal raceway where installed within walls or inaccessible spaces. Low voltage cables may be run in cable tray where noted. Low voltage cables may be run in cable support hooks above accessible ceilings where noted. Low voltage cable shall be plenum rated in plenum spaces.
C. Low voltage cables or conductors operating at less than 50 volts shall be in metal raceway.
Low voltage cables may be run in cable tray where noted. Low voltage cable shall be plenum rated in plenum spaces.
D. Coordinate locations of devices with architectural elevations and details. Architectural elevations and details take precedence over locations shown on electrical drawings.
E. Provide cable or conduit and wire as required to achieve circuiting shown. Size conductors per NEC ampacity and wire fill criteria. Provide dedicated neutral and ground conductors for circuiting, unless noted otherwise. Increase branch circuit and/or feeder conductors including equipment grounding conductors proportionally for no more than 3% voltage drop on branch circuits and 2% on feeders per energy code.
F. It is the responsibility of this contractor to coordinate installation of electrical systems and those requiring electrical connections to maintain NEC required clearances, included but not limited to areas above accessible ceilings.
G. Leave the site clean and ready for occupancy. Remove dirt, debris, empty cartons, tools, conduit and wire scraps, and miscellaneous spare equipment and materials used in this division of the work during construction. Components shall be free of dust, grit, and foreign materials and left as new before final acceptance of work.
H. The symbols and abbreviations shown on this sheet may or may not be used in this set of drawings.
I. Perform work to comply with the standard practices for good workmanship published by National Electrical Contractors Association (NECA). Comply with the latest enforced edition of the National Electrical Code (NEC), local codes, amendments, and ordinances.
J. Field coordinate final mechanical and equipment locations along with connection requirements and control wiring prior to rough-in. Adjust corresponding circuit breaker ratings and branch circuiting accordingly.
K. Electrical work shall be performed under the supervision of a licensed master electrician.
Procure permits and licenses and pay fees associated with this work.
L. Materials furnished for this project shall be new, commercial grade, free of defects, and listed by a nationally recognized testing laboratory unless noted otherwise.
M. Provide complete operation & maintenance manual including approved submittal drawings, warranty information for product supplied, and manufactures operation and maintenance instructions.
N. The contractor is responsible for making final wiring terminations to pre-installed receptacles in office furniture. Contractor is responsible for wiring and installing voice/data devices in office furniture. Coordinate placement of devices with furniture lay-out.
O. Security system to be provided under separate contract. It is the responsibility of this contractor to provide conduit provisions, back boxes, rough-ins, sleeves and power to head end equipment for exact requirements prior to start of work.
P. Conduit and wire shall not be installed below floor slab unless indicated on plan by dashed conduit.
Q. Contractor shall be responsible for wiring electrical items shown on drawings except for items listed in note ‘R’ below.
R. TV outlets, volume controls, nurse call dome lights, nurse call devices, telephone outlets, data outlets, and fire alarm devices shall consist of a back box with conduit stubbed above the accessible ceiling, see stub up detail. Verify size of back box required with device to be installed. Locate back boxes 6" from adjacent power receptacle intended for computer use.
S. Furnish and install conduit from back boxes for the following devices into the accessible ceiling space in the corridor, unless noted otherwise:
A. 1/2"C TV outlets B. 1/2"C Volume controls C. 1/2"C Door security devices (card readers, door strikes etc..)
D. 1/2"C Nurse call dome lights E. 3/4"C Nurse call devices F. 3/4"C Telephone outlets G. 3/4"C Information outlets H. 3/4"C Fire alarm devices
Electrical Remodel Notes
A. Branch circuiting indicated on plans and schedules is based upon existing plans and site observation, contractor to field verify.
B. Provide typed circuit board directories to reflect as-constructed conditions. Field verify during construction and revise accordingly.
C. Provide necessary demolition to facilitate new construction work associated with this project.
Coordinate outages with owner minimum 72 hours in advance. Owner retains right to first salvage. Provide disposal of removed material. Maintain circuit continuity as required.
D. It is the intent of these diagrammatic drawings to provide the project scope including, but not limited to phased demolition and new construction. Existing information indicated on these plans does not represent all existing conditions. This contractor shall become familiar with existing conditions, scope of phasing, and project intent prior to bid submission. No extra will be allowed due to the lack of knowledge of existing conditions to coordinate relocation of electrical systems as required.
E. Provide cutting, patching, and restoration of finishes necessary for work surfaces damaged by this work and spaces around conduits passing through floors and walls shall be neatly patched and finished to match new/existing. Structural members shall not be cut or penetrated in any manner. The spaces around the conduits shall be sealed to prevent entrance of moisture.
Provide fire stopping per UL approved methods.
F. Remove abandoned wiring completely. At contractors option, utilize existing abandoned raceway to extent available. Exposed abandoned raceway shall be removed.
G. Coordinate work in phases with general contractor and owner to facilitate demolition and new construction.
H. Remove electrical related equipment (e.g., junction boxes, receptacles, switches, devices, etc...) affected/abandoned as a result of demolition and new construction.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
Office of
Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
OPTIONAL BID #1
BID DOCUMENTS
C U s e rs \a w e b e r\
D o c u m e n ts \1
M E
P R a w e b e r9
S
.r v t
/1
/2
:3
:0
P
M
E-001
ELECTRICAL SYMBOLS, ABBREVIATIONS,
GENERAL NOTES
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
June 22, 2026 ATW DIL 18704
Electrical Sheet List
E-001 ELECTRICAL SYMBOLS,
ABBREVIATIONS, GENERAL NOTES
ES101 ELECTRICAL SITE PLAN
ED111 LOWER LEVEL - DEMOLITION PLANS
ED121 FIRST LEVEL -DEMOLITION PLANS
EL111 LOWER LEVEL - LIGHTING PLAN
EL121 FIRST LEVEL - LIGHTING PLAN
EP111 LOWER LEVEL - POWER PLAN
EP121 FIRST LEVEL - POWER PLAN
EQ111 LOWER LEVEL - EQUIPMENT POWER
PLAN
EQ121 FIRST LEVEL - EQUIPMENT POWER
PLAN
EY111 LIGHTNING PROTECTION PLAN
E-501 ONE-LINE DIAGRAMS
E-502 ELECTRICAL DETAILS
E-601 ELECTRICAL SCHEDULES AND
DETAILS
Revisions: Date:
ANDREW T . WEBER
L ICENSED
KANSAS
P R O F E S SI O N A L E N G I N E E R
31716 06.22.2026
VA
F
O R
M
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
U.S. Department of Veterans Affairs
Office of Design and Construction
Services
ELECTRICAL SITE PLAN
GENERAL NOTES
A. UNDERGROUND DUCTS AND CONDUITS SHALL BE ENCASED IN CONCRETE.
DIRECT BURIAL CONDUIT MAY BE USED FOR OUTDOOR LIGHTING AND POWER
BRANCH CIRCUITS 600V AND LESS.
B. UTILITIES SHOWN ARE INDICATED SCHEMATICALLY. CONTRACTORS SHALL
VERIFY ALL DEPTHS AND ALL LOCATIONS/DIMENSIONS PRIOR TO EXCAVATING. ALL
UTILITIES MAY NOT BE SHOWN.
C. REFER TO CIVIL DRAWINGS FOR ADDITIONAL INFORMATION ON EXISTING AND
NEW SITE CONDITIONS INCLUDING UTILITES.
D. ALL UNDERGROUND UTILITIES, PIPING, ETC. SHALL BE LOCATED EXACTLY
BEFORE DIGGING.
E. ANY BACKFILL SHALL BE TAMPED AND COMPACTED TO PREVENT FUTURE
SETTLING. ALL EXCESS DIRT SHALL BE CLEARED FROM THE AREA AND DISPOSED
OF.
F. MECHANICAL AND ELECTRICAL CONTRACTORS SHALL REPAIR ALL DISTRUBED
SURFACES SUCH AS SIDEWALKS, DRIVEWAYS, STREETS, GRASS, AND CONCRETE.
REPLACED SURFACES SHALL MATCH EXISTING.
G. COORDINATE ALL EXTERIOR SITE LIGHTING FIXTURES WITH DESIGN TEAM PRIOR
TO INSTALLATION.
H. CONTRACTOR IS RESPONSIBLE FOR DOING ALL WORK PER LOCAL RESPECTIVE
UTILITY REQUIREMENTS.
I. VERIFY EXACT LOCATIONS OF UTILITY CONNECTIONS, PRIOR TO START OF WORK.
ES101
E
CT CABINET AND DIGITAL
POWER MONITOR
E
E
T-ADMIN (T-42)
150kVA TRANSFORMER
4160V : 208Y/120V
UE
UE
UE
UE
REFER TO ONE-LINE DIAGRAM FOR
CONDUCTOR AND CONDUIT DETAILS
E
UE
UE
UE
UE
REFER TO ONE-LINE DIAGRAM FOR
CONDUCTOR AND CONDUIT DETAILS
EX M.H. 20
UE
UE
E
EX M.H. 19
UE
UE
EX M.H. 21
UE
ES1
M
WALL MOUNTED CT CABINET
DIGITAL POWER MONITOR
REFER TO ONE-LINE DIAGRAM FOR
CONDUCTOR AND CONDUIT DETAILS
T-ADMIN (T-42)
150kVA TRANSFORMER
4160V : 208Y/120V
UE
UE
SEE ELECTRICAL SITE PLAN -
OVERALL FOR CONTINUATION
UE
UE
UE
ELECTRICAL SITE KEYED NOTES
ES1
PROVIDE WATERPROOF TEE SPLICES IN EXISTING MANHOLE. NEW
CONDUCTORS SHALL BE SPLICED WITH EXISTING CONDUCTORS IN
MANHOLE 19. REFER TO ONE-LINE DIAGRAM FOR ADDITIONAL DETAILS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
Office of
Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
OPTIONAL BID #1
BID DOCUMENTS
C U s e rs \a w e b e r\
D o c u m e n ts \1
M E
P R a w e b e r9
S
.r v t
/1
/2
:3
:1
P
M
ES101
ELECTRICAL SITE PLAN
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
June 22, 2026 ATW DIL 18704
1" = 30'-0"
ELECTRICAL SITE PLAN
1/8" = 1'-0"
ELECTRICAL SITE PLAN - ADMIN BLDG
Revisions: Date:
ANDREW T . WEBER
L ICENSED
KANSAS
P R O F E S SI O N A L E N G I N E E R
31716 06.22.2026
VA
F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
U.S. Department of Veterans Affairs
Office of Design and Construction
F
C
ER PANEL A
ER
ER
ER PANEL A2
ER
ELECTRIC WATER
HEATER
FURNACE
FURNACE
ER ER
ER
ER ER ER ER ER
ER ER
ER
ER
ER
63 54.1 5.13.1
D.1
H
G
E
D
M
ER WATTHOUR
METER AND METER SOCKET
ER T-42
ELECTRICAL DEMOLITION
GENERAL NOTES
1. DEMOLITION DRAWINGS ARE BASED ON EXISTING AVAILABLE DRAWINGS AND FIELD
OBSERVATION. ELECTRICAL CONTRACTORS SHALL FIELD VERIFY THE SITE AND
INCLUDE ALL REQUIRED DEMOLITION IN THE BID.
2. ALL REQUIRED DEMOLITION MAY NOT BE INDICATED. IT IS THE INTENT OF THESE
DOCUMENTS THAT ALL MECHANICAL AND ELECTRICAL SYSTEMS (NOT TO BE
REUSED OR EXTENDED) BE REMOVED. COORDINATE WITH ARCHITECTURAL
DRAWINGS.
3. REMOVE ALL ELECTRICAL CONNECTIONS, WIRING, AND CONDUIT SERVING ALL
EQUIPMENT TO BE REMOVED.
4. MAINTAIN FIRE RATINGS OF WALLS AND FLOORS AFFECTED BY DEMOLITION.
5. REFER TO ARCHITECTURAL DRAWINGS FOR DETAILS ON FLOOR CUTTING AND
CEILING REMOVAL. CONTRACTOR SHALL COORDINATE WORK TO BE CONSISTENT
WITH SCOPE OF GENERAL CONTRACTOR'S DEMOLITION.
ELECTRICAL DEMOLITION PLAN KEYED
NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
ED1 DEMOLISH ALL POWER DEVICES, RACEWAY, AND CIRCUITING IN THIS AREA.
F
C
LD1
LD1
LD1
63 54.1 5.13.1
D.1
H
G
D
LIGHTING DEMOLITION PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
LD1 DEMOLISH ALL LIGHTING AND LIGHTING CONTROLS IN THIS AREA.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
Office of
Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
OPTIONAL BID #1
BID DOCUMENTS
C U s e rs \a w e b e r\
D o c u m e n ts \1
M E
P R a w e b e r9
S
.r v t
/1
/2
:3
:1
P
M
ED111
LOWER LEVEL - DEMOLITION PLANS
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
June 22, 2026 ATW DIL 18704
1/4" = 1'-0"1
LOWER LEVEL - POWER DEMOLITION PLAN
1/4" = 1'-0"2
LOWER LEVEL - LIGHTING DEMOLITION PLAN
Revisions: Date:
ANDREW T . WEBER
L ICENSED
KANSAS
P R O F E S SI O N A L E N G I N E E R
31716 06.22.2026
VA
F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
U.S. Department of Veterans Affairs
Office of Design and Construction
ER ER
ERER
ER ER
ER ER
ER ER ER
ER
ER
ER
ER
ER
ER
ER ER
ER
ER
ER
ER
ER
ER
ER ER
ER
ER
ER
ER ER
ER
ER ER ER
ER
ER
ER
ER
ER ER
ERER
63 54.1 5.13.1
D.1
H
G
E
D
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LIGHTING DEMOLITION PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
LD1 DEMOLISH ALL LIGHTING AND LIGHTING CONTROLS IN THIS AREA.
F
C
ER
ER
ER
ER
ER
ER
ER ER
ER
ER
ER
ERER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER ER ER
ER
ER
ER
ER
63 54.1 5.13.1
D.1
H
G
E
D
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1 ED1
ELECTRICAL DEMOLITION PLAN KEYED
NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
ED1 DEMOLISH ALL POWER DEVICES, RACEWAY, AND CIRCUITING IN THIS AREA.
ELECTRICAL DEMOLITION
GENERAL NOTES
1. DEMOLITION DRAWINGS ARE BASED ON EXISTING AVAILABLE DRAWINGS AND FIELD
OBSERVATION. ELECTRICAL CONTRACTORS SHALL FIELD VERIFY THE SITE AND
INCLUDE ALL REQUIRED DEMOLITION IN THE BID.
2. ALL REQUIRED DEMOLITION MAY NOT BE INDICATED. IT IS THE INTENT OF THESE
DOCUMENTS THAT ALL MECHANICAL AND ELECTRICAL SYSTEMS (NOT TO BE
REUSED OR EXTENDED) BE REMOVED. COORDINATE WITH ARCHITECTURAL
DRAWINGS.
3. REMOVE ALL ELECTRICAL CONNECTIONS, WIRING, AND CONDUIT SERVING ALL
EQUIPMENT TO BE REMOVED.
4. MAINTAIN FIRE RATINGS OF WALLS AND FLOORS AFFECTED BY DEMOLITION.
5. REFER TO ARCHITECTURAL DRAWINGS FOR DETAILS ON FLOOR CUTTING AND
CEILING REMOVAL. CONTRACTOR SHALL COORDINATE WORK TO BE CONSISTENT
WITH SCOPE OF GENERAL CONTRACTOR'S DEMOLITION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
Office of
Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
OPTIONAL BID #1
BID DOCUMENTS
C U s e rs \a w e b e r\
D o c u m e n ts \1
M E
P R a w e b e r9
S
.r v t
/1
/2
:3
:2
P
M
ED121
FIRST LEVEL -DEMOLITION PLANS
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
June 22, 2026 ATW DIL 18704
1/4" = 1'-0"
FIRST LEVEL - LIGHTING DEMOLITION PLAN
1/4" = 1'-0"
FIRST LEVEL - POWER DEMOLITION PLAN
Revisions: Date:
ANDREW T . WEBER
L ICENSED
KANSAS
P R O F E S SI O N A L E N G I N E E R
31716 06.22.2026
VA
F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
U.S. Department of Veterans Affairs
Office of Design and Construction
LIGHTING GENERAL NOTES
1. REFER TO SPECIFICATION SECTION 26 0923 FOR ADDITIONAL DETAILS ASSOCIATED
WITH LIGHTING CONTROLS.
2. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITHOUT PRIOR
APPROVAL OF THE DESIGN TEAM.
3. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITES SIDES OF THE
SAME WALL ARE WITHIN 6" OF EACH OTHER.
4. COORDINATE ALL DEVICES WITH ARCHITECTURAL PLANS AND CASEWORK.
5. ALL LIGHTING FIXTURES SHALL BE INSTALLED IN SUCH A WAY THAT DRIVERS ARE
ACCESSIBLE WITHOUT CUTTING OF CEILING. THE DESIGN TEAM SHALL BE NOTIFIED
IMMEDIATELY OF AREAS WHERE THIS IS NOT POSSIBLE.
6. ALL WALL-MOUNTED FIXTURES SHALL HAVE THEIR EXACT ROUGH-IN LOCATION
DETERMINED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
7. THE ELECTRICAL CONTRACTOR SHALL EXTEND AN "UNSWITCHED" HOT
CONDUCTOR FROM THE NEAREST NORMAL LIGHTING CIRCUIT TO EVERY
EMERGENCY FIXTURE AND EXIT SIGN REQUIRED FOR EMERGENCY EGRESS
OPERATION. THE "UNSWITCHED" HOT CONDUCTOR SHALL BE USED FOR SENSING
AND CHARGING PURPOSES.
8. UNLESS NOTED OTHERWISE BY DESIGNATED LIGHTING CONTROL ZONES,
SWITCHES SHOWN SHALL CONTROL ALL FIXTURES IN THE ROOM.
9. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE
SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE
ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED
AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
LIGHTING PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
L1 DEMOLISH ALL EXISTING LIGHTS IN THE AREA.
L2
LIGHT FIXTURE SHALL BE CONTROLLED WITH GENERAL CORRIDOR
LIGHTING UPSTAIRS.
F
C
BASEMENT
B02
ELECTRICAL
B04
BASEMENT
B01
TR
B03
FA
90"
FA
90"
FA
90"
FA
90"
FA
90"
EB
EB
EA
FA
90"
FA
90"
FA
90"
FA
90"
FA
90"
FA
90"
FA
90"
FA
90"
EA
MDP
PANEL A
PANEL
EQUIPMENT
DB C
A
A
A
A
WB(E)
96"
EA
A-29
A-11
A-33
61 2.1 3 54.1 5.13.12
D.1
L2
H
G
E
B
A
D
F c c
SEE FIRST LEVEL - LIGHTING PLAN
FOR CONTINUATION
NO LIGHTING SCOPE IN THIS AREA
NO LIGHTING SCOPE IN THIS AREA
NO LIGHTING SCOPE IN THIS AREA
NO LIGHTING SCOPE IN THIS AREA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
Office of
Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
OPTIONAL BID #1
BID DOCUMENTS
C U s e rs \a w e b e r\
D o c u m e n ts \1
M E
P R a w e b e r9
S
.r v t
/1
/2
:3
:2
P
M
EL111
LOWER LEVEL - LIGHTING PLAN
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
June 22, 2026 ATW DIL 18704
1/4" = 1'-0"
LOWER LEVEL - LIGHTING PLAN
F AUTO ON/OFF via PHOTOCELL AUTO ON/OFF via EXTERIOR PHOTOCELL. PROVIDE EXTERNAL PHOTOCELL ON BUILDING FACING NORTH TO CONTROL ALL EXTERIOR MOUNTED LIGHT FIXTURES. N/A
E MANUAL ON/ AUTO OFF w/
DIMMING MANUAL ON/ AUTO OFF w/ MULTI ZONE WALL CONTROL, CEILING SENSOR(S), AND ROOM CONTROLLERS AS APPROPRIATE. FIXTURES SHALL HAVE FULL DIMMING CONTROL WITH ZONES INDICATED ON PLAN. 15 MINUTE TIMEOUT
D MANUAL ON/ AUTO OFF w/
DIMMING MANUAL ON/ AUTO OFF w/ WALL CONTROL, CEILING SENSOR(S), AND ROOM CONTROLLERS AS APPROPRIATE. FIXTURES SHALL HAVE FULL DIMMING CONTROL. 15 MINUTE TIMEOUT
C AUTO ON/OFF w/ DIMMING AUTO ON/OFF w/ WALL MOUNTED AND/OR CEILING MOUNTED SENSOR(S) AS INDICATED ON PLANS. FIXTURES SHALL HAVE FULL DIMMING CONTROL. 15 MINUTE TIMEOUT
B AUTO ON/OFF AUTO ON/OFF w/ WALL MOUNTED AND/OR CEILING MOUNTED SENSOR(S) AS INDICATED ON PLANS. 15 MINUTE TIMEOUT
A MANUAL ON/OFF MANUAL LINE VOLTAGE TOGGLE SWITCH N/A
TAG ACTIVATION DECRIPTION SCHEDULE
LIGHTING CONTROL - SEQUENCE OF OPERATION
TRUE
NORTH
PLAN
NORTH
Revisions: Date:
ANDREW T . WEBER
L ICENSED
KANSAS
P R O F E S SI O N A L E N G I N E E R
31716 06.22.2026
VA
F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
U.S. Department of Veterans Affairs
Office of Design and Construction
LIGHTING GENERAL NOTES
1. REFER TO SPECIFICATION SECTION 26 0923 FOR ADDITIONAL DETAILS ASSOCIATED
WITH LIGHTING CONTROLS.
2. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITHOUT PRIOR
APPROVAL OF THE DESIGN TEAM.
3. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITES SIDES OF THE
SAME WALL ARE WITHIN 6" OF EACH OTHER.
4. COORDINATE ALL DEVICES WITH ARCHITECTURAL PLANS AND CASEWORK.
5. ALL LIGHTING FIXTURES SHALL BE INSTALLED IN SUCH A WAY THAT DRIVERS ARE
ACCESSIBLE WITHOUT CUTTING OF CEILING. THE DESIGN TEAM SHALL BE NOTIFIED
IMMEDIATELY OF AREAS WHERE THIS IS NOT POSSIBLE.
6. ALL WALL-MOUNTED FIXTURES SHALL HAVE THEIR EXACT ROUGH-IN LOCATION
DETERMINED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
7. THE ELECTRICAL CONTRACTOR SHALL EXTEND AN "UNSWITCHED" HOT
CONDUCTOR FROM THE NEAREST NORMAL LIGHTING CIRCUIT TO EVERY
EMERGENCY FIXTURE AND EXIT SIGN REQUIRED FOR EMERGENCY EGRESS
OPERATION. THE "UNSWITCHED" HOT CONDUCTOR SHALL BE USED FOR SENSING
AND CHARGING PURPOSES.
8. UNLESS NOTED OTHERWISE BY DESIGNATED LIGHTING CONTROL ZONES,
SWITCHES SHOWN SHALL CONTROL ALL FIXTURES IN THE ROOM.
9. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE
SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE
ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED
AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
LIGHTING PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
L1 DEMOLISH ALL EXISTING LIGHTS IN THE AREA.
L2
LIGHT FIXTURE SHALL BE CONTROLLED WITH GENERAL CORRIDOR
LIGHTING UPSTAIRS.
F
C
ASSISTANT DIRECTOR
118PROGRAM ANALYST
BUDGET ANALYST
HAC
OPERATIONAL CTR
DIRECTOR
ADMIN OFFICER
MENS
MULTIPURPOSE ROOM
STAFF WOMEN
113A
STAFF MEN
114A
WOMENS
LOBBY
HALLWAY
STORAGE
HALLWAY
105c
WORKSTATIONS
HALLWAY
105b
BREAK ROOM
MENS LOCKER ROOM
WOMENS LOCKER ROOM
RA
C
D
RA RA
D
WB(E)
104"
F
EA
RA
RA
EA
C
RA
RA
D
RB
RB
D
RA RA
C
DA DA
C
DA DA
C C
B
RA
DB DB
RA RA
WB(E)
104"
F
RA
EA
RA RA
RA RA
C
WB
104"
F
RA
RA
RA
RA RA
RA RA
EA
a,b
DB
DB
DB DB
DB
DB
b b b b b b a a a
E D
RA
RA
RA
DC
F
RA RA RA
C
B
C C
EB
EA
WA
84"
WA
84"
EB
EB
EB
EB
UA
30"
UA
36"
UA
36"
UA
30"
UA
33"
RA
RA
RA
RA
WA
84"
WA
84"
FA
DB
DB
DB DB
DB
EA
WC
99"
RA RA
DB
DB
DB
DB
DB
RA
A-37
A-37
A-39
A-27
A-27
A-49
1 2.1 3 54.1 5.13.12
D.1
A
EB EB
RA
F
FA
H
G
E
B
A
D
RA
d c d d c c c c c c c c c cb bb b b b b b b b b b b b b a a a a a
DA DA DA
c c c c
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
Office of
Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
OPTIONAL BID #1
BID DOCUMENTS
C U s e rs \a w e b e r\
D o c u m e n ts \1
M E
P R a w e b e r9
S
.r v t
/1
/2
:3
:3
P
M
EL121
FIRST LEVEL - LIGHTING PLAN
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
June 22, 2026 ATW DIL 18704
1/4" = 1'-0"
FIRST LEVEL - LIGHTING PLAN
F AUTO ON/OFF via PHOTOCELL AUTO ON/OFF via EXTERIOR PHOTOCELL. PROVIDE EXTERNAL PHOTOCELL ON BUILDING FACING NORTH TO CONTROL ALL EXTERIOR MOUNTED LIGHT FIXTURES. N/A
E MANUAL ON/ AUTO OFF w/
DIMMING MANUAL ON/ AUTO OFF w/ MULTI ZONE WALL CONTROL, CEILING SENSOR(S), AND ROOM CONTROLLERS AS APPROPRIATE. FIXTURES SHALL HAVE FULL DIMMING CONTROL WITH ZONES INDICATED ON PLAN. 15 MINUTE TIMEOUT
D MANUAL ON/ AUTO OFF w/
DIMMING MANUAL ON/ AUTO OFF w/ WALL CONTROL, CEILING SENSOR(S), AND ROOM CONTROLLERS AS APPROPRIATE. FIXTURES SHALL HAVE FULL DIMMING CONTROL. 15 MINUTE TIMEOUT
C AUTO ON/OFF w/ DIMMING AUTO ON/OFF w/ WALL MOUNTED AND/OR CEILING MOUNTED SENSOR(S) AS INDICATED ON PLANS. FIXTURES SHALL HAVE FULL DIMMING CONTROL. 15 MINUTE TIMEOUT
B AUTO ON/OFF AUTO ON/OFF w/ WALL MOUNTED AND/OR CEILING MOUNTED SENSOR(S) AS INDICATED ON PLANS. 15 MINUTE TIMEOUT
A MANUAL ON/OFF MANUAL LINE VOLTAGE TOGGLE SWITCH N/A
TAG ACTIVATION DECRIPTION SCHEDULE
LIGHTING CONTROL - SEQUENCE OF OPERATION
TRUE
NORTH
PLAN
NORTH
Revisions: Date:
ANDREW T . WEBER
L ICENSED
KANSAS
P R O F E S SI O N A L E N G I N E E R
31716 06.22.2026
VA
F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
U.S. Department of Veterans Affairs
Office of Design and Construction
72 SF
B04
ELECTRICAL
140 SF
B03
TR
215 SF
B02
BASEMENT
611 SF
B01
BASEMENT
57 SF
B05
STAIRS
F
C
PANEL
EQUIPMENT
PANEL A
MDP
E1
E2 E2
E3
E3
E3
A-1
A-9
TR RACK
120V-1P/30A A-5
TR RACK
120V-1P/30A A-7
1 2.1 3 54.1 5.13.12
D.1
A-13
A-15
A-3
A-17
A-19
A-21A-23
A-53
H
G
E
B
A
D
A-25
NO ELECTRICAL SCOPE IN THIS AREA
NO ELECTRICAL SCOPE IN THIS AREA
NO ELECTRICAL SCOPE IN THIS AREA
NO ELECTRICAL SCOPE IN THIS AREA
FACP
A-42
ER10
ELECTRICAL GENERAL NOTES
1. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE
OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND ELECTRICAL
BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED. GROUND AND
BOND PER NEC ARTICLE 250.
2. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON
STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH A
MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET
PRIOR TO ROUGH-IN.
3. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL EQUIPMENT.
DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.
4. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITH PRIOR
APPROVAL FROM THE DESIGN TEAM.
5. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.
6. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE SAME
WALL ARE WITHIN 24" OF EACH OTHER.
7. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE
SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE
ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED
AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
ELECTRICAL PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
E1
COORDINATE EXACT LOCATION WITH ACCESS CONTROL HEADEND PRIOR
TO ROUGH-IN.
E2
PROVIDE (2) L5-30 RECEPTACLES FOR TELECOM RACK ZONE PDU (2)
INPUTS. COORDINATE EXACT LOCATIONS WITH TELECOM RACK PRIOR TO
ROUGH-IN.
E3
ACCESS CONTROL LOCATION. REFER TO LOW VOLTAGE DETAILS AND
ARCHITECTURAL SPECIFICATIONS FOR OPERATION AND FURTHER
ROUGH-IN BIDDING INFORMATION. COORDINATE ALL DOORHOLDS, CARD
READERS, ADA PUSH BUTTONS, AND OTHER ACCESSORIES WITH DESIGN
TEAM PRIOR TO ROUGH-IN.
E4
COORDINATE FINAL ELECTRICAL REQUIREMENTS AND PLUG TYPE WITH
EQUIPMENT PROVIDED PRIOR TO ROUGH-IN.
E5
COORDINATE EXACT TV/MONITOR LOCATIONS WITH OWNER'S DESIRED
MOUNTING HEIGHT PRIOR TO ROUGH-IN. COORDINATE WITH OWNER
PROVIDED TV/MONITOR AND MOUNTING SYSTEM SO THAT DEVICES AND
CABLES ARE NEAT AND CONCEALED. REFER TO LOW VOLTAGE DRAWINGS
FOR DETAILS AND ADDITIONAL INFORMATION.
E6
COORDINATE FINAL FURNITURE FEED LOCATIONS AND WIRING WITH
FURNITURE PROVIDER PRIOR TO ROUGH-IN.
E7
COORDINATE FINAL DEVICE LOCATION WITH FURNITURE PRIOR TO
ROUGH-IN.
E8
COORDINATE DEVICE ELEVATION WITH ELECTRIC WATER COOLER
INSTRUCTIONS PRIOR TO ROUGH-IN.
E9
PROVIDE SINGLE POINT POWER CONNECTION FROM ASSOCIATED
MINI-SPLIT CONDENSING UNIT.
E10
PROVIDE 120V POWER TO FIRE ALARM CONTROL PANEL. COORDINATE
FINAL ELECTRICAL CONNECTION WITH FIRE ALARM CONTRACTOR. LABEL
BREAKER IN ACCORDANCE WITH NEC ARTICLE 760.41.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
Office of
Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
OPTIONAL BID #1
BID DOCUMENTS
C U s e rs \a w e b e r\
D o c u m e n ts \1
M E
P R a w e b e r9
S
.r v t
/1
/2
:3
:3
P
M
EP111
LOWER LEVEL - POWER PLAN
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
June 22, 2026 ATW DIL 18704
1/4" = 1'-0"
LOWER LEVEL - POWER PLAN
TRUE
NORTH
PLAN
NORTH
Revisions: Date:
ANDREW T . WEBER
L ICENSED
KANSAS
P R O F E S SI O N A L E N G I N E E R
31716 06.22.2026
VA
F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
U.S. Department of Veterans Affairs
Office of Design and Construction
ELECTRICAL GENERAL NOTES
1. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE
OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND ELECTRICAL
BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED. GROUND AND
BOND PER NEC ARTICLE 250.
2. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON
STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH A
MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET
PRIOR TO ROUGH-IN.
3. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL EQUIPMENT.
DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.
4. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITH PRIOR
APPROVAL FROM THE DESIGN TEAM.
5. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.
6. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE SAME
WALL ARE WITHIN 24" OF EACH OTHER.
7. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE
SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE
ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED
AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
ELECTRICAL PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
E1
COORDINATE EXACT LOCATION WITH ACCESS CONTROL HEADEND PRIOR
TO ROUGH-IN.
E2
PROVIDE (2) L5-30 RECEPTACLES FOR TELECOM RACK ZONE PDU (2)
INPUTS. COORDINATE EXACT LOCATIONS WITH TELECOM RACK PRIOR TO
ROUGH-IN.
E3
ACCESS CONTROL LOCATION. REFER TO LOW VOLTAGE DETAILS AND
ARCHITECTURAL SPECIFICATIONS FOR OPERATION AND FURTHER
ROUGH-IN BIDDING INFORMATION. COORDINATE ALL DOORHOLDS, CARD
READERS, ADA PUSH BUTTONS, AND OTHER ACCESSORIES WITH DESIGN
TEAM PRIOR TO ROUGH-IN.
E4
COORDINATE FINAL ELECTRICAL REQUIREMENTS AND PLUG TYPE WITH
EQUIPMENT PROVIDED PRIOR TO ROUGH-IN.
E5
COORDINATE EXACT TV/MONITOR LOCATIONS WITH OWNER'S DESIRED
MOUNTING HEIGHT PRIOR TO ROUGH-IN. COORDINATE WITH OWNER
PROVIDED TV/MONITOR AND MOUNTING SYSTEM SO THAT DEVICES AND
CABLES ARE NEAT AND CONCEALED. REFER TO LOW VOLTAGE DRAWINGS
FOR DETAILS AND ADDITIONAL INFORMATION.
E6
COORDINATE FINAL FURNITURE FEED LOCATIONS AND WIRING WITH
FURNITURE PROVIDER PRIOR TO ROUGH-IN.
E7
COORDINATE FINAL DEVICE LOCATION WITH FURNITURE PRIOR TO
ROUGH-IN.
E8
COORDINATE DEVICE ELEVATION WITH ELECTRIC WATER COOLER
INSTRUCTIONS PRIOR TO ROUGH-IN.
E9
PROVIDE SINGLE POINT POWER CONNECTION FROM ASSOCIATED
MINI-SPLIT CONDENSING UNIT.
E10
PROVIDE 120V POWER TO FIRE ALARM CONTROL PANEL. COORDINATE
FINAL ELECTRICAL CONNECTION WITH FIRE ALARM CONTRACTOR. LABEL
BREAKER IN ACCORDANCE WITH NEC ARTICLE 760.41.
F
C
PROGRAM ANALYST
BREAK ROOM
BUDGET ANALYST
HALLWAY
105c
ASSISTANT DIRECTOR
DIRECTOR
STAFF MEN
114A
STAFF WOMEN
113A
STORAGE
MULTIPURPOSE ROOM
108 ADMIN OFFICER
HALLWAY
OPERATIONAL CTR
LOBBY
HAC
MENS
WOMENS
DPM
PROVIDE NEMA 3R WALL MOUNTED
CT CABINET, CTs, AND DIGITAL
METER WITH WEATHERPROOF
ENCLOSURE WITH VIEWING WINDOW
AND HINGED ACCESS.
UE
SEE ELECTRICAL SITE PLANS FOR CONTINUATION
+24"
FB-2
FB-1
E3
E3
E4
E5
+6"
E3
E5
COFFEE
A-4,6 FRIDGE
A-8
MICROWAVE
A-31
A-12
A-14
A-35
MENS LOCKER ROOM
HALLWAY
105b
A-16
A-18
A-20
A-22
1 2.1 3 54.1 5.13.12
D.1
A-24
A-26
GRAVESITE LOCATOR
A-30
A-28
PRINTER
A-32
GFI WP
A-34
A-36
A-38
A-40
A-2
A-10
FURNITURE,FURNITURE
A-41,A-43E6
E6
EWC
A-51
H
G
E
B
A
D
A-34
A-55
FURNITURE,FURNITURE
A-45,A-47
E8
E4
E7
E7
E7
E7
AC GFI
AC GFI
GFI
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
Office of
Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
OPTIONAL BID #1
BID DOCUMENTS
C U s e rs \a w e b e r\
D o c u m e n ts \1
M E
P R a w e b e r9
S
.r v t
/1
/2
:4
:1
P
M
EP121
FIRST LEVEL - POWER PLAN
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
June 22, 2026 ATW DIL 18704
1/4" = 1'-0"
FIRST LEVEL - POWER PLAN
TRUE
NORTH
PLAN
NORTH
Revisions: Date:
ANDREW T . WEBER
L ICENSED
KANSAS
P R O F E S SI O N A L E N G I N E E R
31716 06.22.2026
ANDREW T . WEBER
L ICENSED
KANSAS
P R O F E S SI O N A L E N G I N E E R
31716 06.22.2026
VA
F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
U.S. Department of Veterans Affairs
Office of Design and Construction
72 SF
B04
ELECTRICAL
140 SF
B03
TR
215 SF
B02
BASEMENT
611 SF
B01
BASEMENT
57 SF
B05
STAIRS
F
C
MDP
PANEL
EQUIPMENT
PANEL A
AHU-1
208V-3P/40A
EQ-1,3,5
VAV-002
120V-1P/25A
EQ-4
VAV-001
120V-1P/25A
EQ-2
FROM CU-2
WH-2
EQ-26
1 2.1 3 54.1 5.13.12
D.1
H
G
E
B
A
D
CP-01
EQ-35
M
E9
NO ELECTRICAL SCOPE IN THIS AREA
NO ELECTRICAL SCOPE IN THIS AREA
NO ELECTRICAL SCOPE IN THIS AREA
NO ELECTRICAL SCOPE IN THIS AREA
ELECTRICAL GENERAL NOTES
1. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE
OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND ELECTRICAL
BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED. GROUND AND
BOND PER NEC ARTICLE 250.
2. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON
STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH A
MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET
PRIOR TO ROUGH-IN.
3. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL EQUIPMENT.
DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.
4. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITH PRIOR
APPROVAL FROM THE DESIGN TEAM.
5. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.
6. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE SAME
WALL ARE WITHIN 24" OF EACH OTHER.
7. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE
SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE
ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED
AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
ELECTRICAL PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
E1
COORDINATE EXACT LOCATION WITH ACCESS CONTROL HEADEND PRIOR
TO ROUGH-IN.
E2
PROVIDE (2) L5-30 RECEPTACLES FOR TELECOM RACK ZONE PDU (2)
INPUTS. COORDINATE EXACT LOCATIONS WITH TELECOM RACK PRIOR TO
ROUGH-IN.
E3
ACCESS CONTROL LOCATION. REFER TO LOW VOLTAGE DETAILS AND
ARCHITECTURAL SPECIFICATIONS FOR OPERATION AND FURTHER
ROUGH-IN BIDDING INFORMATION. COORDINATE ALL DOORHOLDS, CARD
READERS, ADA PUSH BUTTONS, AND OTHER ACCESSORIES WITH DESIGN
TEAM PRIOR TO ROUGH-IN.
E4
COORDINATE FINAL ELECTRICAL REQUIREMENTS AND PLUG TYPE WITH
EQUIPMENT PROVIDED PRIOR TO ROUGH-IN.
E5
COORDINATE EXACT TV/MONITOR LOCATIONS WITH OWNER'S DESIRED
MOUNTING HEIGHT PRIOR TO ROUGH-IN. COORDINATE WITH OWNER
PROVIDED TV/MONITOR AND MOUNTING SYSTEM SO THAT DEVICES AND
CABLES ARE NEAT AND CONCEALED. REFER TO LOW VOLTAGE DRAWINGS
FOR DETAILS AND ADDITIONAL INFORMATION.
E6
COORDINATE FINAL FURNITURE FEED LOCATIONS AND WIRING WITH
FURNITURE PROVIDER PRIOR TO ROUGH-IN.
E7
COORDINATE FINAL DEVICE LOCATION WITH FURNITURE PRIOR TO
ROUGH-IN.
E8
COORDINATE DEVICE ELEVATION WITH ELECTRIC WATER COOLER
INSTRUCTIONS PRIOR TO ROUGH-IN.
E9
PROVIDE SINGLE POINT POWER CONNECTION FROM ASSOCIATED
MINI-SPLIT CONDENSING UNIT.
E10
PROVIDE 120V POWER TO FIRE ALARM CONTROL PANEL. COORDINATE
FINAL ELECTRICAL CONNECTION WITH FIRE ALARM CONTRACTOR. LABEL
BREAKER IN ACCORDANCE WITH NEC ARTICLE 760.41.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
Office of
Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
OPTIONAL BID #1
BID DOCUMENTS
C U s e rs \a w e b e r\
D o c u m e n ts \1
M E
P R a w e b e r9
S
.r v t
/1
/2
:3
:4
P
M
EQ111
LOWER LEVEL - EQUIPMENT POWER PLAN
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
June 22, 2026 ATW DIL 18704
1/4" = 1'-0"
LOWER LEVEL - EQUIPMENT POWER PLAN
TRUE
NORTH
PLAN
NORTH
Revisions: Date:
ANDREW T . WEBER
L ICENSED
KANSAS
P R O F E S SI O N A L E N G I N E E R
31716 06.22.2026
VA
F
O
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:
IRRIGATION:
EC DESIGN
400 5th St West Des Moines, IA 50265
(515) 225-6265
COST ESTIMATING:GEOTECHNICAL:
TERRACON
15620 W 113th St Lenexa, KS 66219
(913) 202-7598
OCMI
2100 North Greenville Ave. #1150 Richardson, TX 75082
(469) 431-0571
TECHNOLOGY:
IMEG
900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258
(480) 222-3789
U.S. Department of Veterans Affairs
Office of Design and Construction
ELECTRICAL GENERAL NOTES
1. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE
OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND ELECTRICAL
BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED. GROUND AND
BOND PER NEC ARTICLE 250.
2. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON
STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH A
MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET
PRIOR TO ROUGH-IN.
3. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL EQUIPMENT.
DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.
4. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITH PRIOR
APPROVAL FROM THE DESIGN TEAM.
5. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.
6. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE SAME
WALL ARE WITHIN 24" OF EACH OTHER.
7. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE
SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE
ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED
AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
ELECTRICAL PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
E1
COORDINATE EXACT LOCATION WITH ACCESS CONTROL HEADEND PRIOR
TO ROUGH-IN.
E2
PROVIDE (2) L5-30 RECEPTACLES FOR TELECOM RACK ZONE PDU (2)
INPUTS. COORDINATE EXACT LOCATIONS WITH TELECOM RACK PRIOR TO
ROUGH-IN.
E3
ACCESS CONTROL LOCATION. REFER TO LOW VOLTAGE DETAILS AND
ARCHITECTURAL SPECIFICATIONS FOR OPERATION AND FURTHER
ROUGH-IN…