_26 LNC BD - ELECTRICAL (pg 201-214).pdf

PDF 14 MB Posted

Attached to
Leavenworth National Cemetery, Gravesite Expansion
Solicitation number
36C78626B0027
Issued by

About this file

This document is a comprehensive set of electrical design and construction drawings for the Leavenworth National Cemetery Gravesite Expansion project located at 150 Muncie Road, Leavenworth, Kansas. The electrical scope includes site electrical plans, demolition plans for lower and first levels, lighting plans, power distribution plans, equipment power plans, lightning protection plans, one-line diagrams, electrical details, and schedules.

The project involves establishing new electrical infrastructure for an administrative building with a 150 kVA, 4160V to 208Y/120V transformer serving as the primary power source. Key deliverables include a Main Distribution Panel (MDP) with 600-ampere, 208Y/120V, three-phase, four-wire service rated for 14,095 amperes available short-circuit current and 10 kA SCCR; Panel A with 225-ampere capacity for general branch circuits; and Panel Equipment with 400-ampere capacity for mechanical equipment. The electrical systems must comply with the National Electrical Code (NEC), NFPA 780 for lightning protection systems, and local Kansas codes. Lighting fixtures include LED downlights, flat panels, linear fixtures, emergency exit signs, and emergency lighting units with dimming controls and occupancy sensors. All materials must be commercial grade, new, listed by nationally recognized testing laboratories, and Buy America Act (BABA) compliant. The contractor is responsible for coordinating with mechanical systems, maintaining NEC clearances, providing complete operations and maintenance manuals, and performing work under a licensed master electrician's supervision with all required permits and fees.

View the file

Other files

File Type Posted
S06_36C78626B0027 Amend. 0002.pdf PDF
S02_Attachment - 18704_LNC_Addendum1_CivilSheets_CG100-CR117_20260916.pdf PDF
S02_Attachment - 18704_LNC_Addendum1_CivilSheets_CD100-CB501_20260916.pdf PDF
S04_Attachment - Site Visit Attendance Roster.pdf PDF
S02_Attachment - 18704_LNC_Addendum1_SurveySheets_V100-V113_20260916.pdf PDF
S02_Attachment - 00 01 10 Table of Contents.pdf PDF
S02_Attachment - Substitution Request - Leavenworth GSE.pdf PDF
S02_Attachment - 00 00 00 Specification Cover.pdf PDF
S02_Attachment - 01 35 26 Safety Requirements.pdf PDF
_31 LNC BD - TECHNOLOGY pt3 FIRE ALARM (pg 241-247).pdf PDF
_11 LNC BD - GRADING DRAINAGE (pg 78-82).pdf PDF
_28 LNC BD - PLUMBING (pg 224-230).pdf PDF
_24 LNC BD - INTERIORS (pg 182-188).pdf PDF
_23 LNC BD - ARCH pt2 (pg 171-181).pdf PDF
_19 LNC BD - SIGNAGE FURNISHINGS pt2 (pg 126-138).pdf PDF
_16 LNC BD - ROADS pt2 (pg 106-113).pdf PDF
_05 LNC BD - DEMOLITION pt1 (pg 22-34).pdf PDF
_07 LNC BD - SITE (pg 41-49).pdf PDF
_02 LNC BD - EX CON pt1 (pg 3-16).pdf PDF
LNC Gravesite Expansion VOL1SPECS wGEOTECH - BD 06-22-2026.pdf PDF
S02_Attachment - Price Schedule Sheet.pdf PDF
_20 LNC BD - PLANTING IRR pt1 (pg 139-149).pdf PDF
_14 LNC BD - EROSION CONTROL pt3 UTIL pt1 (pg 91-98).pdf PDF
_22 LNC BD - ARCH pt1 (pg 159-170).pdf PDF
_09 LNC BD - COLUMBARIUM 3 pt1 (pg 60-69).pdf PDF
_10 LNC BD - COLUMBARIUM 3 pt2 (pg 70-77).pdf PDF
LNC Gravesite Expansion VOL2SPECS wGEOTECH - BD 06-22-2026.pdf PDF
_08 LNC BD - BURIALS (pg 50-59).pdf PDF
_30 LNC BD - TECHNOLOGY pt2 (pg 236-240).pdf PDF
_03 LNC BD - EX CON pt2 (pg 17).pdf PDF
S02_Attachment - Statement of Work.pdf PDF
S02_Attachment - Davis-Bacon Act Poster.pdf PDF
_29 LNC BD - TECHNOLOGY pt1 (pg 231-235).pdf PDF
_25 LNC BD - STRUCTURAL (pg 189-200).pdf PDF
_21 LNC BD - IRR pt2 (pg 150-158).pdf PDF
_18 LNC BD - SIGNAGE FURNISHINGS pt1 (pg 118-125).pdf PDF
_12 LNC BD - EROSION CONTROL pt1 (pg 83-86).pdf PDF
_13 LNC BD - EROSION CONTROL pt2 (pg 87-90).pdf PDF
_17 LNC BD - ROADS pt3 (pg 114-117).pdf PDF
_04 LNC BD - GEOTECH (pg 18-21).pdf PDF
S02_Attachment - Wage Determination Heavy.pdf PDF
S02_Attachment - Wage Determination Building.pdf PDF
S02_Attachment - Limitations on Subcontracting Cert.docx DOCX document
S02_Attachment - DOL Payroll Form.pdf PDF
_15 LNC BD - UTIL pt2 ROADS pt1 (pg 99-105).pdf PDF
_06 LNC BD - DEMO pt2 OPERATIONS (pg 35-40).pdf PDF
_27 LNC BD - MECHANICAL (pg 215-223).pdf PDF
_01 LNC BD - GENERAL (pg 1-2).pdf PDF
S02_Attachment - Standard Form 1413.pdf PDF
S02_36C78626B0027 Solicitation.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1P 1 Pole (2P, 3P, 4P, ETC.)

A, Amp Ampere AC Above Counter ACLG Above Ceiling ADO Automatic Door Opener AF Amp Frame AFF Above Finished Floor AFG Above Finished Grade AFI Arc Fault Circuit

Interrupter AHU Air Handling Unit AL Aluminum ALT Alternate AMP Ampere AMPL Amplifier ANNUN Annunciator APPROX Approximately AQ-STAT Aquastat ARCH Architect, Architectural AS Amp Switch AT Amp Trip ATS Automatic Transfer Switch AUTO Automatic AUX Auxiliary AV Audio Visual AWG American Wire Gauge BATT Battery BD Board BLDG Building BMS Building Management System C Conduit CAB Cabinet CAT Catalog CATV Cable Television CB Circuit Breaker CCTV Closed Circuit Television CKT Circuit CLG Ceiling COMB Combination CMPR Compressor CONN Connection CONST Construction CONT Continuation Or Continuous CONTR Contractor CONV Convector CP Circulating Pump CRT Cathode-Ray Tube CT Current Transformer CTR Center CU Copper DCP Domestic Water Circulating Pump DEPT Department DET Detail DIA Diameter DISC Disconnect DIST Distribution DN Down DPR Damper DS Safety Disconnect Switch DT Double Throw DWG Drawing EC Electrical Contractor ELEC Electric, Electrical ELEV Elevator ELU Emergency Lighting Unit EM Emergency EMS Energy Management System EMT Electrical Metallic Tubing EP Electric Pneumatic EQUIP Equipment EWC Electric Water Cooler EXIST Existing EXH Exhaust EXP Explosion Proof FA Fire Alarm FABP Fire Alarm Booster Power

Supply Panel FACP Fire Alarm Control Panel FCU Fan Coil Unit FIXT Fixture FLR Floor FLUOR Fluorescent FU Fuse FUDS Fused Safety Disconnect Switch GA Gauge GAL Gallon GALV Galvanized GC General Contractor GEN Generator GFI Ground Fault Circuit Interrupter GFP Ground Fault Protector GND Ground GRS Galvanized Rigid Steel (Conduit) GYP BD Gypsum Board HOA Hands-Off-Automatic Switch HORIZ Horizontal HP Horsepower HPF High Power Factor HT Height HTG Heating HTR Heater HV High Voltage HVAC Heating, Ventilating And Air

Conditioning IC Interrupting Capacity IG Isolated Ground IMC Intermediate Metal Conduit INCAND Incandescent IR Infrared I/W Interlock With J-BOX Junction Box KV Kilovolt KVA Kilovolt-Ampere KVAR Kilovolt-Ampere Reactive KW Kilowatt KWH Kilowatt Hour LOC Locate Or Location LT Light LTG Lighting LTNG Lightning LV Low Voltage MAX Maximum MAG.S Magnetic Starter M/C Momentary Contact MC Mechanical Contractor

Electrical Abbreviations

Electrical DeviceTags: Uppercase letter(s) indicates Panel ID and circuit number. Lowercase letter indicates designation of controlling switch (where applicable).

Switch ID indicated by a lowercase letter. Switch IDs are unique per space. A switch with an ID "a" controls all devices within the space in which it is located tagged with "a". A switch without a tagged ID controls all lighting fixtures within a space. ID tags may be used on control devices other than switches, such as occupancy sensors or contactors.

Equipment Tags: Equipment ID is indicated by an underlined tag adjacent to the equipment. See the equipment connection schedule for description, electrical requirements, and panel and circuit number. Symbols/graphic appearance of equipment varies.

Solid, arced lines connecting equipment, devices, or fixtures indicate unswitched power circuiting. Wires are only intended to indicate to what circuit devices are connected. Actual connections, circuit routing, installation, junction boxes, etc. shall be field-determined by the contractor.

Home run to branch circuit panelboard. The equipment name and circuit number(s) are indicated, separated by a hyphen. Homeruns are only intended to indicate panel and circuit number. Actual homerun location shall be field-determined by the contractor.

Power Symbols

Electrical Symbol Legend

Room

MCB Main Circuit Breaker MCC Motor Control Center MDC Main Distribution Center MDP Main Distribution Panel MFR Manufacturer MFS Main Fused Disconnect Switch MH Manhole MIC Microphone MIN Minimum MISC Miscellaneous MLO Main Lugs Only MMS Manual Motor Starter MOA Multioutlet Assembly MSP Motor Starter Panelboard MSBD Main Switchboard MSS Motor Starter Switch MT Mount MT.C Empty Conduit MTS Manual Transfer Switch MTR Motor, Motorized N.C. Normally Closed NEC National Electrical Code NEMA National Electrical

Manufacturer's Association NFSD Non-Fused Safety Disconnect

Switch NIC Not In Contract NL Night Light N.O. Normally Open NPF Normal Power Factor NTS Not To Scale OC On Center OH Overhead OL Overloads PA Public Address PB Pull Box Or Pushbutton PE Pneumatic Electric PED Pedestal PF Power Factor PH Phase PIV Post Indicating Valve PNL Panel PP Power Pole PR Pair PRI Primary PROJ Projection PRV Power Roof Ventilator PT Potential Transformer PVC Polyvinyl Chloride (Conduit) PWR Power QUAN Quantity RCPT Receptacle REQD Required RM Room RSC Rigid Steel Conduit RTU Roof Top Unit SC Surface Conduit SEC Secondary SHT Sheet SIM Similar SLD Single-Line Diagram S/N Solid Neutral SPEC Specification SPKR Speaker SP Spare SPP Single-Point Power SR Surface Raceway SS Stainless Steel SSW Selector Switch S/S Stop/Start Pushbuttons STA Station STD Standard SURF Surface Mounted SW Switch SWBD Switchboard SYM Symmetrical SYS System TEL Telephone TERM Terminal TL Twist Lock TR Tamper Resistant T-STAT Thermostat TTC Telephone Terminal Cabinet TV Television TVTC Television Terminal Cabinet TYP Typical UC Under Counter UE Underground Electrical UG Underground UH Unit Heater UT Underground Telephone UTIL Utility UV Ultraviolet V Volt VA Volt-Amperes VDT Video Display Terminal VERT Vertical VFD Variable Frequency Drive VOL Volume W Watt W/ With WG Wire Guard WH Water Heater W/O Without WP Weatherproof XFMR Transformer XFR Transfer

∠ Angle

@ At ▲ Delta ' Feet " Inches # Number Ø Phase C Center Line P Plate

Exit Light, Wall-Mounted.

Shading and arrows indicate faces and directional chevrons.

Wall-mounted fixtures, Typical (Various Symbols)

Emergency Lighting Unit, Wall-Mounted, Remote Battery

Emergency Lighting Unit, Wall-Mounted, Integral Battery

Emergency Lighting Unit, Ceiling-Mounted, Integral Battery

Emergency Lighting Unit, Ceiling-Mounted, Remote Battery

Lighting Fixtures, Typical, Rectangular (Various Symbols) Filled circles indicate recessed.

Open circles indicate surface-mounted.

Diagonal line indicates lensed.

Outer dots indicate suspended.

Lighting Fixtures, Typical, Round (Various Symbols) Center dot indicates pendant.

Diagonal line indicates lensed.

Chevron indicates wall wash.

Strip Fixture

Directional Light, Track Light, Flood Light

Exit Light, Ceiling-Mounted.

Shading and arrows indicate faces and directional chevrons.

Linear Light, Tape Light

Exit/ELU Combo

Diagonal hatch indicates light on a critical circuit.

Solid hatch indicates light on an emergency or life safety circuit.

Pole/Area Lights

Post-Top Area Light

Bollard Light

Single-Pole Switch

Two-Pole Switch

Three-Pole Switch

Switch Modifiers:

3: 3-Way 4: 4-Way K: Keyed D: Dimming T: Timer

OS: Occupancy Sensor VS: Vacancy Sensor AC: Above-Counter LV: Low-Voltage M: Motor-Rated

Lighting Contactor

Lighting Control Panel

Occupancy Sensor

Daylight Harvesting Sensor

Simplex Receptacle

Duplex Receptacle

Quadruplex Receptacle

Special Receptacle, Type as Indicated

W al l

C ei lin g

F lo or

Receptacle Modifiers:

##": Height AFF OC AC: Above Counter GFI: Ground-Fault Circuit Interrupter WP: Weatherproof In-Use Cover

Half shading indicates split (typically switched)

Outside shading indicates emergency circuit

Center shading indicates isolated ground

Multioutlet Assembly Filled squares indicate 120V outlet Open squares indicate with USB

Cord Reel, Device Varies

Drop Cord, Device Varies

Junction Box

Floor Box, see schedule for type

Emergency Power Off

Door Opener Push Plate

Power Meter

Safety Switch, Fused

Safety Switch, Unfused

Motor Starter

Combination Starter/Disconnect

Lighting Symbols

Contactor

Single-Pole Switch

Two-Pole Switch

Three-Pole Switch

Switch Modifiers:

K: Keyed T: Timer AC: Above-Counter M: Motor-Rated a

A A1a

Equipment is tagged with Panel Name and with Panel ID in parentheses. Panel ID is intended as a design documentation aid only. Do not include Panel ID in field-applied circuit directories or labels.

Hatched fill indicates distribution panel or switchboard.

Solid fill indicates branch panel or load center.

Dashed box indicates code-required clearance (width and depth).

Door indicates front of recessed panel.

Panelboards are assigned an abbreviated indicator (or Panel ID) for use with circuit numbers. Panel ID is listed within the panel schedule and in the panel abbreviation schedule.

Power Distribution Equipment

H P

1A (B

LP

1A

(C

M D

P (A

SB1(S)

Devices and fixtures are tagged with Panel ID and circuit number. For example, a device tagged with "A1" indicates the device is circuited to panel designated "A," circuit number 1. The panel schedule circuit number contains both the panel abbreviation and the circuit number.

XX-1

Transformer: Typically transformer names begin with or contain the letter "T". See Single-Line Diagram for description and requirements.

T1

Dashed, arced lines connecting equipment, devices, or fixtures indicate switched power.

Absence of a switch designation on a lighting fixture indicates fixture is controlled by the only switch in the space. An "x" in place of the switch designation indicates unswitched.

Bottom Value, Lowercase Letter: Switch ID

Lighting Tags

Top Value: Fixture Type ID (Underlined)

Bottom Value, Uppercase Letter(s): Panel ID

Bottom Value, Number(s): Circuit Number a a

C1a

Wiring

Power Device and Equipment Tags

Construction Phasing

Existing to Remain

Existing to Be Demolished

New

(Typical All Symbols and Equipment)

Existing to Be Demolished

Area Not in Contract

Miscellaneous

Keynote

Callout:

Top Value: Detail Number on Sheet Bottom Value: Sheet Number of Detail

Room Name and Number

Low voltage digital wall switch

Low voltage digital occupancy sensor wall switch

General Notes

A. Conductors operating at 50 volts or greater shall be in raceway. Raceway within the structure above the floor slab shall be metal. Raceway below the floor slab and underground raceway outside the structure shall be PVC.

B. Low voltage cables or conductors operating at less than 50 volts shall be in metal raceway where installed within walls or inaccessible spaces. Low voltage cables may be run in cable tray where noted. Low voltage cables may be run in cable support hooks above accessible ceilings where noted. Low voltage cable shall be plenum rated in plenum spaces.

C. Low voltage cables or conductors operating at less than 50 volts shall be in metal raceway.

Low voltage cables may be run in cable tray where noted. Low voltage cable shall be plenum rated in plenum spaces.

D. Coordinate locations of devices with architectural elevations and details. Architectural elevations and details take precedence over locations shown on electrical drawings.

E. Provide cable or conduit and wire as required to achieve circuiting shown. Size conductors per NEC ampacity and wire fill criteria. Provide dedicated neutral and ground conductors for circuiting, unless noted otherwise. Increase branch circuit and/or feeder conductors including equipment grounding conductors proportionally for no more than 3% voltage drop on branch circuits and 2% on feeders per energy code.

F. It is the responsibility of this contractor to coordinate installation of electrical systems and those requiring electrical connections to maintain NEC required clearances, included but not limited to areas above accessible ceilings.

G. Leave the site clean and ready for occupancy. Remove dirt, debris, empty cartons, tools, conduit and wire scraps, and miscellaneous spare equipment and materials used in this division of the work during construction. Components shall be free of dust, grit, and foreign materials and left as new before final acceptance of work.

H. The symbols and abbreviations shown on this sheet may or may not be used in this set of drawings.

I. Perform work to comply with the standard practices for good workmanship published by National Electrical Contractors Association (NECA). Comply with the latest enforced edition of the National Electrical Code (NEC), local codes, amendments, and ordinances.

J. Field coordinate final mechanical and equipment locations along with connection requirements and control wiring prior to rough-in. Adjust corresponding circuit breaker ratings and branch circuiting accordingly.

K. Electrical work shall be performed under the supervision of a licensed master electrician.

Procure permits and licenses and pay fees associated with this work.

L. Materials furnished for this project shall be new, commercial grade, free of defects, and listed by a nationally recognized testing laboratory unless noted otherwise.

M. Provide complete operation & maintenance manual including approved submittal drawings, warranty information for product supplied, and manufactures operation and maintenance instructions.

N. The contractor is responsible for making final wiring terminations to pre-installed receptacles in office furniture. Contractor is responsible for wiring and installing voice/data devices in office furniture. Coordinate placement of devices with furniture lay-out.

O. Security system to be provided under separate contract. It is the responsibility of this contractor to provide conduit provisions, back boxes, rough-ins, sleeves and power to head end equipment for exact requirements prior to start of work.

P. Conduit and wire shall not be installed below floor slab unless indicated on plan by dashed conduit.

Q. Contractor shall be responsible for wiring electrical items shown on drawings except for items listed in note ‘R’ below.

R. TV outlets, volume controls, nurse call dome lights, nurse call devices, telephone outlets, data outlets, and fire alarm devices shall consist of a back box with conduit stubbed above the accessible ceiling, see stub up detail. Verify size of back box required with device to be installed. Locate back boxes 6" from adjacent power receptacle intended for computer use.

S. Furnish and install conduit from back boxes for the following devices into the accessible ceiling space in the corridor, unless noted otherwise:

A. 1/2"C TV outlets B. 1/2"C Volume controls C. 1/2"C Door security devices (card readers, door strikes etc..)

D. 1/2"C Nurse call dome lights E. 3/4"C Nurse call devices F. 3/4"C Telephone outlets G. 3/4"C Information outlets H. 3/4"C Fire alarm devices

Electrical Remodel Notes

A. Branch circuiting indicated on plans and schedules is based upon existing plans and site observation, contractor to field verify.

B. Provide typed circuit board directories to reflect as-constructed conditions. Field verify during construction and revise accordingly.

C. Provide necessary demolition to facilitate new construction work associated with this project.

Coordinate outages with owner minimum 72 hours in advance. Owner retains right to first salvage. Provide disposal of removed material. Maintain circuit continuity as required.

D. It is the intent of these diagrammatic drawings to provide the project scope including, but not limited to phased demolition and new construction. Existing information indicated on these plans does not represent all existing conditions. This contractor shall become familiar with existing conditions, scope of phasing, and project intent prior to bid submission. No extra will be allowed due to the lack of knowledge of existing conditions to coordinate relocation of electrical systems as required.

E. Provide cutting, patching, and restoration of finishes necessary for work surfaces damaged by this work and spaces around conduits passing through floors and walls shall be neatly patched and finished to match new/existing. Structural members shall not be cut or penetrated in any manner. The spaces around the conduits shall be sealed to prevent entrance of moisture.

Provide fire stopping per UL approved methods.

F. Remove abandoned wiring completely. At contractors option, utilize existing abandoned raceway to extent available. Exposed abandoned raceway shall be removed.

G. Coordinate work in phases with general contractor and owner to facilitate demolition and new construction.

H. Remove electrical related equipment (e.g., junction boxes, receptacles, switches, devices, etc...) affected/abandoned as a result of demolition and new construction.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

Office of

Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OPTIONAL BID #1

BID DOCUMENTS

C U s e rs \a w e b e r\

D o c u m e n ts \1

M E

P R a w e b e r9

S

.r v t

/1

/2

:3

:0

P

M

E-001

ELECTRICAL SYMBOLS, ABBREVIATIONS,

GENERAL NOTES

LEAVENWORTH NATIONAL CEMETERY

GRAVESITE EXPANSION

150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048

897CM3025

June 22, 2026 ATW DIL 18704

Electrical Sheet List

E-001 ELECTRICAL SYMBOLS,

ABBREVIATIONS, GENERAL NOTES

ES101 ELECTRICAL SITE PLAN

ED111 LOWER LEVEL - DEMOLITION PLANS

ED121 FIRST LEVEL -DEMOLITION PLANS

EL111 LOWER LEVEL - LIGHTING PLAN

EL121 FIRST LEVEL - LIGHTING PLAN

EP111 LOWER LEVEL - POWER PLAN

EP121 FIRST LEVEL - POWER PLAN

EQ111 LOWER LEVEL - EQUIPMENT POWER

PLAN

EQ121 FIRST LEVEL - EQUIPMENT POWER

PLAN

EY111 LIGHTNING PROTECTION PLAN

E-501 ONE-LINE DIAGRAMS

E-502 ELECTRICAL DETAILS

E-601 ELECTRICAL SCHEDULES AND

DETAILS

Revisions: Date:

ANDREW T . WEBER

L ICENSED

KANSAS

P R O F E S SI O N A L E N G I N E E R

31716 06.22.2026

VA

F

O R

M

ARCHITECT/ENGINEER OF RECORDCONSULTANT

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:

IRRIGATION:

EC DESIGN

400 5th St West Des Moines, IA 50265

(515) 225-6265

COST ESTIMATING:GEOTECHNICAL:

TERRACON

15620 W 113th St Lenexa, KS 66219

(913) 202-7598

OCMI

2100 North Greenville Ave. #1150 Richardson, TX 75082

(469) 431-0571

TECHNOLOGY:

IMEG

900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258

(480) 222-3789

U.S. Department of Veterans Affairs

Office of Design and Construction

Services

ELECTRICAL SITE PLAN

GENERAL NOTES

A. UNDERGROUND DUCTS AND CONDUITS SHALL BE ENCASED IN CONCRETE.

DIRECT BURIAL CONDUIT MAY BE USED FOR OUTDOOR LIGHTING AND POWER

BRANCH CIRCUITS 600V AND LESS.

B. UTILITIES SHOWN ARE INDICATED SCHEMATICALLY. CONTRACTORS SHALL

VERIFY ALL DEPTHS AND ALL LOCATIONS/DIMENSIONS PRIOR TO EXCAVATING. ALL

UTILITIES MAY NOT BE SHOWN.

C. REFER TO CIVIL DRAWINGS FOR ADDITIONAL INFORMATION ON EXISTING AND

NEW SITE CONDITIONS INCLUDING UTILITES.

D. ALL UNDERGROUND UTILITIES, PIPING, ETC. SHALL BE LOCATED EXACTLY

BEFORE DIGGING.

E. ANY BACKFILL SHALL BE TAMPED AND COMPACTED TO PREVENT FUTURE

SETTLING. ALL EXCESS DIRT SHALL BE CLEARED FROM THE AREA AND DISPOSED

OF.

F. MECHANICAL AND ELECTRICAL CONTRACTORS SHALL REPAIR ALL DISTRUBED

SURFACES SUCH AS SIDEWALKS, DRIVEWAYS, STREETS, GRASS, AND CONCRETE.

REPLACED SURFACES SHALL MATCH EXISTING.

G. COORDINATE ALL EXTERIOR SITE LIGHTING FIXTURES WITH DESIGN TEAM PRIOR

TO INSTALLATION.

H. CONTRACTOR IS RESPONSIBLE FOR DOING ALL WORK PER LOCAL RESPECTIVE

UTILITY REQUIREMENTS.

I. VERIFY EXACT LOCATIONS OF UTILITY CONNECTIONS, PRIOR TO START OF WORK.

ES101

E

CT CABINET AND DIGITAL

POWER MONITOR

E

E

T-ADMIN (T-42)

150kVA TRANSFORMER

4160V : 208Y/120V

UE

UE

UE

UE

REFER TO ONE-LINE DIAGRAM FOR

CONDUCTOR AND CONDUIT DETAILS

E

UE

UE

UE

UE

REFER TO ONE-LINE DIAGRAM FOR

CONDUCTOR AND CONDUIT DETAILS

EX M.H. 20

UE

UE

E

EX M.H. 19

UE

UE

EX M.H. 21

UE

ES1

M

WALL MOUNTED CT CABINET

DIGITAL POWER MONITOR

REFER TO ONE-LINE DIAGRAM FOR

CONDUCTOR AND CONDUIT DETAILS

T-ADMIN (T-42)

150kVA TRANSFORMER

4160V : 208Y/120V

UE

UE

SEE ELECTRICAL SITE PLAN -

OVERALL FOR CONTINUATION

UE

UE

UE

ELECTRICAL SITE KEYED NOTES

ES1

PROVIDE WATERPROOF TEE SPLICES IN EXISTING MANHOLE. NEW

CONDUCTORS SHALL BE SPLICED WITH EXISTING CONDUCTORS IN

MANHOLE 19. REFER TO ONE-LINE DIAGRAM FOR ADDITIONAL DETAILS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

Office of

Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OPTIONAL BID #1

BID DOCUMENTS

C U s e rs \a w e b e r\

D o c u m e n ts \1

M E

P R a w e b e r9

S

.r v t

/1

/2

:3

:1

P

M

ES101

ELECTRICAL SITE PLAN

LEAVENWORTH NATIONAL CEMETERY

GRAVESITE EXPANSION

150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048

897CM3025

June 22, 2026 ATW DIL 18704

1" = 30'-0"

ELECTRICAL SITE PLAN

1/8" = 1'-0"

ELECTRICAL SITE PLAN - ADMIN BLDG

Revisions: Date:

ANDREW T . WEBER

L ICENSED

KANSAS

P R O F E S SI O N A L E N G I N E E R

31716 06.22.2026

VA

F

O

ARCHITECT/ENGINEER OF RECORDCONSULTANT

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:

IRRIGATION:

EC DESIGN

400 5th St West Des Moines, IA 50265

(515) 225-6265

COST ESTIMATING:GEOTECHNICAL:

TERRACON

15620 W 113th St Lenexa, KS 66219

(913) 202-7598

OCMI

2100 North Greenville Ave. #1150 Richardson, TX 75082

(469) 431-0571

TECHNOLOGY:

IMEG

900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258

(480) 222-3789

U.S. Department of Veterans Affairs

Office of Design and Construction

F

C

ER PANEL A

ER

ER

ER PANEL A2

ER

ELECTRIC WATER

HEATER

FURNACE

FURNACE

ER ER

ER

ER ER ER ER ER

ER ER

ER

ER

ER

63 54.1 5.13.1

D.1

H

G

E

D

M

ER WATTHOUR

METER AND METER SOCKET

ER T-42

ELECTRICAL DEMOLITION

GENERAL NOTES

1. DEMOLITION DRAWINGS ARE BASED ON EXISTING AVAILABLE DRAWINGS AND FIELD

OBSERVATION. ELECTRICAL CONTRACTORS SHALL FIELD VERIFY THE SITE AND

INCLUDE ALL REQUIRED DEMOLITION IN THE BID.

2. ALL REQUIRED DEMOLITION MAY NOT BE INDICATED. IT IS THE INTENT OF THESE

DOCUMENTS THAT ALL MECHANICAL AND ELECTRICAL SYSTEMS (NOT TO BE

REUSED OR EXTENDED) BE REMOVED. COORDINATE WITH ARCHITECTURAL

DRAWINGS.

3. REMOVE ALL ELECTRICAL CONNECTIONS, WIRING, AND CONDUIT SERVING ALL

EQUIPMENT TO BE REMOVED.

4. MAINTAIN FIRE RATINGS OF WALLS AND FLOORS AFFECTED BY DEMOLITION.

5. REFER TO ARCHITECTURAL DRAWINGS FOR DETAILS ON FLOOR CUTTING AND

CEILING REMOVAL. CONTRACTOR SHALL COORDINATE WORK TO BE CONSISTENT

WITH SCOPE OF GENERAL CONTRACTOR'S DEMOLITION.

ELECTRICAL DEMOLITION PLAN KEYED

NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

ED1 DEMOLISH ALL POWER DEVICES, RACEWAY, AND CIRCUITING IN THIS AREA.

F

C

LD1

LD1

LD1

63 54.1 5.13.1

D.1

H

G

D

LIGHTING DEMOLITION PLAN KEYED NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

LD1 DEMOLISH ALL LIGHTING AND LIGHTING CONTROLS IN THIS AREA.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

Office of

Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OPTIONAL BID #1

BID DOCUMENTS

C U s e rs \a w e b e r\

D o c u m e n ts \1

M E

P R a w e b e r9

S

.r v t

/1

/2

:3

:1

P

M

ED111

LOWER LEVEL - DEMOLITION PLANS

LEAVENWORTH NATIONAL CEMETERY

GRAVESITE EXPANSION

150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048

897CM3025

June 22, 2026 ATW DIL 18704

1/4" = 1'-0"1

LOWER LEVEL - POWER DEMOLITION PLAN

1/4" = 1'-0"2

LOWER LEVEL - LIGHTING DEMOLITION PLAN

Revisions: Date:

ANDREW T . WEBER

L ICENSED

KANSAS

P R O F E S SI O N A L E N G I N E E R

31716 06.22.2026

VA

F

O

ARCHITECT/ENGINEER OF RECORDCONSULTANT

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:

IRRIGATION:

EC DESIGN

400 5th St West Des Moines, IA 50265

(515) 225-6265

COST ESTIMATING:GEOTECHNICAL:

TERRACON

15620 W 113th St Lenexa, KS 66219

(913) 202-7598

OCMI

2100 North Greenville Ave. #1150 Richardson, TX 75082

(469) 431-0571

TECHNOLOGY:

IMEG

900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258

(480) 222-3789

U.S. Department of Veterans Affairs

Office of Design and Construction

ER ER

ERER

ER ER

ER ER

ER ER ER

ER

ER

ER

ER

ER

ER

ER ER

ER

ER

ER

ER

ER

ER

ER ER

ER

ER

ER

ER ER

ER

ER ER ER

ER

ER

ER

ER

ER ER

ERER

63 54.1 5.13.1

D.1

H

G

E

D

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LIGHTING DEMOLITION PLAN KEYED NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

LD1 DEMOLISH ALL LIGHTING AND LIGHTING CONTROLS IN THIS AREA.

F

C

ER

ER

ER

ER

ER

ER

ER ER

ER

ER

ER

ERER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER ER ER

ER

ER

ER

ER

63 54.1 5.13.1

D.1

H

G

E

D

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1 ED1

ELECTRICAL DEMOLITION PLAN KEYED

NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

ED1 DEMOLISH ALL POWER DEVICES, RACEWAY, AND CIRCUITING IN THIS AREA.

ELECTRICAL DEMOLITION

GENERAL NOTES

1. DEMOLITION DRAWINGS ARE BASED ON EXISTING AVAILABLE DRAWINGS AND FIELD

OBSERVATION. ELECTRICAL CONTRACTORS SHALL FIELD VERIFY THE SITE AND

INCLUDE ALL REQUIRED DEMOLITION IN THE BID.

2. ALL REQUIRED DEMOLITION MAY NOT BE INDICATED. IT IS THE INTENT OF THESE

DOCUMENTS THAT ALL MECHANICAL AND ELECTRICAL SYSTEMS (NOT TO BE

REUSED OR EXTENDED) BE REMOVED. COORDINATE WITH ARCHITECTURAL

DRAWINGS.

3. REMOVE ALL ELECTRICAL CONNECTIONS, WIRING, AND CONDUIT SERVING ALL

EQUIPMENT TO BE REMOVED.

4. MAINTAIN FIRE RATINGS OF WALLS AND FLOORS AFFECTED BY DEMOLITION.

5. REFER TO ARCHITECTURAL DRAWINGS FOR DETAILS ON FLOOR CUTTING AND

CEILING REMOVAL. CONTRACTOR SHALL COORDINATE WORK TO BE CONSISTENT

WITH SCOPE OF GENERAL CONTRACTOR'S DEMOLITION.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

Office of

Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OPTIONAL BID #1

BID DOCUMENTS

C U s e rs \a w e b e r\

D o c u m e n ts \1

M E

P R a w e b e r9

S

.r v t

/1

/2

:3

:2

P

M

ED121

FIRST LEVEL -DEMOLITION PLANS

LEAVENWORTH NATIONAL CEMETERY

GRAVESITE EXPANSION

150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048

897CM3025

June 22, 2026 ATW DIL 18704

1/4" = 1'-0"

FIRST LEVEL - LIGHTING DEMOLITION PLAN

1/4" = 1'-0"

FIRST LEVEL - POWER DEMOLITION PLAN

Revisions: Date:

ANDREW T . WEBER

L ICENSED

KANSAS

P R O F E S SI O N A L E N G I N E E R

31716 06.22.2026

VA

F

O

ARCHITECT/ENGINEER OF RECORDCONSULTANT

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:

IRRIGATION:

EC DESIGN

400 5th St West Des Moines, IA 50265

(515) 225-6265

COST ESTIMATING:GEOTECHNICAL:

TERRACON

15620 W 113th St Lenexa, KS 66219

(913) 202-7598

OCMI

2100 North Greenville Ave. #1150 Richardson, TX 75082

(469) 431-0571

TECHNOLOGY:

IMEG

900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258

(480) 222-3789

U.S. Department of Veterans Affairs

Office of Design and Construction

LIGHTING GENERAL NOTES

1. REFER TO SPECIFICATION SECTION 26 0923 FOR ADDITIONAL DETAILS ASSOCIATED

WITH LIGHTING CONTROLS.

2. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITHOUT PRIOR

APPROVAL OF THE DESIGN TEAM.

3. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITES SIDES OF THE

SAME WALL ARE WITHIN 6" OF EACH OTHER.

4. COORDINATE ALL DEVICES WITH ARCHITECTURAL PLANS AND CASEWORK.

5. ALL LIGHTING FIXTURES SHALL BE INSTALLED IN SUCH A WAY THAT DRIVERS ARE

ACCESSIBLE WITHOUT CUTTING OF CEILING. THE DESIGN TEAM SHALL BE NOTIFIED

IMMEDIATELY OF AREAS WHERE THIS IS NOT POSSIBLE.

6. ALL WALL-MOUNTED FIXTURES SHALL HAVE THEIR EXACT ROUGH-IN LOCATION

DETERMINED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

7. THE ELECTRICAL CONTRACTOR SHALL EXTEND AN "UNSWITCHED" HOT

CONDUCTOR FROM THE NEAREST NORMAL LIGHTING CIRCUIT TO EVERY

EMERGENCY FIXTURE AND EXIT SIGN REQUIRED FOR EMERGENCY EGRESS

OPERATION. THE "UNSWITCHED" HOT CONDUCTOR SHALL BE USED FOR SENSING

AND CHARGING PURPOSES.

8. UNLESS NOTED OTHERWISE BY DESIGNATED LIGHTING CONTROL ZONES,

SWITCHES SHOWN SHALL CONTROL ALL FIXTURES IN THE ROOM.

9. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE

SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE

ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED

AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

LIGHTING PLAN KEYED NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

L1 DEMOLISH ALL EXISTING LIGHTS IN THE AREA.

L2

LIGHT FIXTURE SHALL BE CONTROLLED WITH GENERAL CORRIDOR

LIGHTING UPSTAIRS.

F

C

BASEMENT

B02

ELECTRICAL

B04

BASEMENT

B01

TR

B03

FA

90"

FA

90"

FA

90"

FA

90"

FA

90"

EB

EB

EA

FA

90"

FA

90"

FA

90"

FA

90"

FA

90"

FA

90"

FA

90"

FA

90"

EA

MDP

PANEL A

PANEL

EQUIPMENT

DB C

A

A

A

A

WB(E)

96"

EA

A-29

A-11

A-33

61 2.1 3 54.1 5.13.12

D.1

L2

H

G

E

B

A

D

F c c

SEE FIRST LEVEL - LIGHTING PLAN

FOR CONTINUATION

NO LIGHTING SCOPE IN THIS AREA

NO LIGHTING SCOPE IN THIS AREA

NO LIGHTING SCOPE IN THIS AREA

NO LIGHTING SCOPE IN THIS AREA

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

Office of

Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OPTIONAL BID #1

BID DOCUMENTS

C U s e rs \a w e b e r\

D o c u m e n ts \1

M E

P R a w e b e r9

S

.r v t

/1

/2

:3

:2

P

M

EL111

LOWER LEVEL - LIGHTING PLAN

LEAVENWORTH NATIONAL CEMETERY

GRAVESITE EXPANSION

150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048

897CM3025

June 22, 2026 ATW DIL 18704

1/4" = 1'-0"

LOWER LEVEL - LIGHTING PLAN

F AUTO ON/OFF via PHOTOCELL AUTO ON/OFF via EXTERIOR PHOTOCELL. PROVIDE EXTERNAL PHOTOCELL ON BUILDING FACING NORTH TO CONTROL ALL EXTERIOR MOUNTED LIGHT FIXTURES. N/A

E MANUAL ON/ AUTO OFF w/

DIMMING MANUAL ON/ AUTO OFF w/ MULTI ZONE WALL CONTROL, CEILING SENSOR(S), AND ROOM CONTROLLERS AS APPROPRIATE. FIXTURES SHALL HAVE FULL DIMMING CONTROL WITH ZONES INDICATED ON PLAN. 15 MINUTE TIMEOUT

D MANUAL ON/ AUTO OFF w/

DIMMING MANUAL ON/ AUTO OFF w/ WALL CONTROL, CEILING SENSOR(S), AND ROOM CONTROLLERS AS APPROPRIATE. FIXTURES SHALL HAVE FULL DIMMING CONTROL. 15 MINUTE TIMEOUT

C AUTO ON/OFF w/ DIMMING AUTO ON/OFF w/ WALL MOUNTED AND/OR CEILING MOUNTED SENSOR(S) AS INDICATED ON PLANS. FIXTURES SHALL HAVE FULL DIMMING CONTROL. 15 MINUTE TIMEOUT

B AUTO ON/OFF AUTO ON/OFF w/ WALL MOUNTED AND/OR CEILING MOUNTED SENSOR(S) AS INDICATED ON PLANS. 15 MINUTE TIMEOUT

A MANUAL ON/OFF MANUAL LINE VOLTAGE TOGGLE SWITCH N/A

TAG ACTIVATION DECRIPTION SCHEDULE

LIGHTING CONTROL - SEQUENCE OF OPERATION

TRUE

NORTH

PLAN

NORTH

Revisions: Date:

ANDREW T . WEBER

L ICENSED

KANSAS

P R O F E S SI O N A L E N G I N E E R

31716 06.22.2026

VA

F

O

ARCHITECT/ENGINEER OF RECORDCONSULTANT

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:

IRRIGATION:

EC DESIGN

400 5th St West Des Moines, IA 50265

(515) 225-6265

COST ESTIMATING:GEOTECHNICAL:

TERRACON

15620 W 113th St Lenexa, KS 66219

(913) 202-7598

OCMI

2100 North Greenville Ave. #1150 Richardson, TX 75082

(469) 431-0571

TECHNOLOGY:

IMEG

900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258

(480) 222-3789

U.S. Department of Veterans Affairs

Office of Design and Construction

LIGHTING GENERAL NOTES

1. REFER TO SPECIFICATION SECTION 26 0923 FOR ADDITIONAL DETAILS ASSOCIATED

WITH LIGHTING CONTROLS.

2. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITHOUT PRIOR

APPROVAL OF THE DESIGN TEAM.

3. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITES SIDES OF THE

SAME WALL ARE WITHIN 6" OF EACH OTHER.

4. COORDINATE ALL DEVICES WITH ARCHITECTURAL PLANS AND CASEWORK.

5. ALL LIGHTING FIXTURES SHALL BE INSTALLED IN SUCH A WAY THAT DRIVERS ARE

ACCESSIBLE WITHOUT CUTTING OF CEILING. THE DESIGN TEAM SHALL BE NOTIFIED

IMMEDIATELY OF AREAS WHERE THIS IS NOT POSSIBLE.

6. ALL WALL-MOUNTED FIXTURES SHALL HAVE THEIR EXACT ROUGH-IN LOCATION

DETERMINED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

7. THE ELECTRICAL CONTRACTOR SHALL EXTEND AN "UNSWITCHED" HOT

CONDUCTOR FROM THE NEAREST NORMAL LIGHTING CIRCUIT TO EVERY

EMERGENCY FIXTURE AND EXIT SIGN REQUIRED FOR EMERGENCY EGRESS

OPERATION. THE "UNSWITCHED" HOT CONDUCTOR SHALL BE USED FOR SENSING

AND CHARGING PURPOSES.

8. UNLESS NOTED OTHERWISE BY DESIGNATED LIGHTING CONTROL ZONES,

SWITCHES SHOWN SHALL CONTROL ALL FIXTURES IN THE ROOM.

9. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE

SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE

ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED

AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

LIGHTING PLAN KEYED NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

L1 DEMOLISH ALL EXISTING LIGHTS IN THE AREA.

L2

LIGHT FIXTURE SHALL BE CONTROLLED WITH GENERAL CORRIDOR

LIGHTING UPSTAIRS.

F

C

ASSISTANT DIRECTOR

118PROGRAM ANALYST

BUDGET ANALYST

HAC

OPERATIONAL CTR

DIRECTOR

ADMIN OFFICER

MENS

MULTIPURPOSE ROOM

STAFF WOMEN

113A

STAFF MEN

114A

WOMENS

LOBBY

HALLWAY

STORAGE

HALLWAY

105c

WORKSTATIONS

HALLWAY

105b

BREAK ROOM

MENS LOCKER ROOM

WOMENS LOCKER ROOM

RA

C

D

RA RA

D

WB(E)

104"

F

EA

RA

RA

EA

C

RA

RA

D

RB

RB

D

RA RA

C

DA DA

C

DA DA

C C

B

RA

DB DB

RA RA

WB(E)

104"

F

RA

EA

RA RA

RA RA

C

WB

104"

F

RA

RA

RA

RA RA

RA RA

EA

a,b

DB

DB

DB DB

DB

DB

b b b b b b a a a

E D

RA

RA

RA

DC

F

RA RA RA

C

B

C C

EB

EA

WA

84"

WA

84"

EB

EB

EB

EB

UA

30"

UA

36"

UA

36"

UA

30"

UA

33"

RA

RA

RA

RA

WA

84"

WA

84"

FA

DB

DB

DB DB

DB

EA

WC

99"

RA RA

DB

DB

DB

DB

DB

RA

A-37

A-37

A-39

A-27

A-27

A-49

1 2.1 3 54.1 5.13.12

D.1

A

EB EB

RA

F

FA

H

G

E

B

A

D

RA

d c d d c c c c c c c c c cb bb b b b b b b b b b b b b a a a a a

DA DA DA

c c c c

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

Office of

Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OPTIONAL BID #1

BID DOCUMENTS

C U s e rs \a w e b e r\

D o c u m e n ts \1

M E

P R a w e b e r9

S

.r v t

/1

/2

:3

:3

P

M

EL121

FIRST LEVEL - LIGHTING PLAN

LEAVENWORTH NATIONAL CEMETERY

GRAVESITE EXPANSION

150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048

897CM3025

June 22, 2026 ATW DIL 18704

1/4" = 1'-0"

FIRST LEVEL - LIGHTING PLAN

F AUTO ON/OFF via PHOTOCELL AUTO ON/OFF via EXTERIOR PHOTOCELL. PROVIDE EXTERNAL PHOTOCELL ON BUILDING FACING NORTH TO CONTROL ALL EXTERIOR MOUNTED LIGHT FIXTURES. N/A

E MANUAL ON/ AUTO OFF w/

DIMMING MANUAL ON/ AUTO OFF w/ MULTI ZONE WALL CONTROL, CEILING SENSOR(S), AND ROOM CONTROLLERS AS APPROPRIATE. FIXTURES SHALL HAVE FULL DIMMING CONTROL WITH ZONES INDICATED ON PLAN. 15 MINUTE TIMEOUT

D MANUAL ON/ AUTO OFF w/

DIMMING MANUAL ON/ AUTO OFF w/ WALL CONTROL, CEILING SENSOR(S), AND ROOM CONTROLLERS AS APPROPRIATE. FIXTURES SHALL HAVE FULL DIMMING CONTROL. 15 MINUTE TIMEOUT

C AUTO ON/OFF w/ DIMMING AUTO ON/OFF w/ WALL MOUNTED AND/OR CEILING MOUNTED SENSOR(S) AS INDICATED ON PLANS. FIXTURES SHALL HAVE FULL DIMMING CONTROL. 15 MINUTE TIMEOUT

B AUTO ON/OFF AUTO ON/OFF w/ WALL MOUNTED AND/OR CEILING MOUNTED SENSOR(S) AS INDICATED ON PLANS. 15 MINUTE TIMEOUT

A MANUAL ON/OFF MANUAL LINE VOLTAGE TOGGLE SWITCH N/A

TAG ACTIVATION DECRIPTION SCHEDULE

LIGHTING CONTROL - SEQUENCE OF OPERATION

TRUE

NORTH

PLAN

NORTH

Revisions: Date:

ANDREW T . WEBER

L ICENSED

KANSAS

P R O F E S SI O N A L E N G I N E E R

31716 06.22.2026

VA

F

O

ARCHITECT/ENGINEER OF RECORDCONSULTANT

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:

IRRIGATION:

EC DESIGN

400 5th St West Des Moines, IA 50265

(515) 225-6265

COST ESTIMATING:GEOTECHNICAL:

TERRACON

15620 W 113th St Lenexa, KS 66219

(913) 202-7598

OCMI

2100 North Greenville Ave. #1150 Richardson, TX 75082

(469) 431-0571

TECHNOLOGY:

IMEG

900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258

(480) 222-3789

U.S. Department of Veterans Affairs

Office of Design and Construction

72 SF

B04

ELECTRICAL

140 SF

B03

TR

215 SF

B02

BASEMENT

611 SF

B01

BASEMENT

57 SF

B05

STAIRS

F

C

PANEL

EQUIPMENT

PANEL A

MDP

E1

E2 E2

E3

E3

E3

A-1

A-9

TR RACK

120V-1P/30A A-5

TR RACK

120V-1P/30A A-7

1 2.1 3 54.1 5.13.12

D.1

A-13

A-15

A-3

A-17

A-19

A-21A-23

A-53

H

G

E

B

A

D

A-25

NO ELECTRICAL SCOPE IN THIS AREA

NO ELECTRICAL SCOPE IN THIS AREA

NO ELECTRICAL SCOPE IN THIS AREA

NO ELECTRICAL SCOPE IN THIS AREA

FACP

A-42

ER10

ELECTRICAL GENERAL NOTES

1. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE

OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND ELECTRICAL

BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED. GROUND AND

BOND PER NEC ARTICLE 250.

2. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON

STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH A

MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET

PRIOR TO ROUGH-IN.

3. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL EQUIPMENT.

DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.

4. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITH PRIOR

APPROVAL FROM THE DESIGN TEAM.

5. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.

6. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE SAME

WALL ARE WITHIN 24" OF EACH OTHER.

7. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE

SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE

ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED

AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

ELECTRICAL PLAN KEYED NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

E1

COORDINATE EXACT LOCATION WITH ACCESS CONTROL HEADEND PRIOR

TO ROUGH-IN.

E2

PROVIDE (2) L5-30 RECEPTACLES FOR TELECOM RACK ZONE PDU (2)

INPUTS. COORDINATE EXACT LOCATIONS WITH TELECOM RACK PRIOR TO

ROUGH-IN.

E3

ACCESS CONTROL LOCATION. REFER TO LOW VOLTAGE DETAILS AND

ARCHITECTURAL SPECIFICATIONS FOR OPERATION AND FURTHER

ROUGH-IN BIDDING INFORMATION. COORDINATE ALL DOORHOLDS, CARD

READERS, ADA PUSH BUTTONS, AND OTHER ACCESSORIES WITH DESIGN

TEAM PRIOR TO ROUGH-IN.

E4

COORDINATE FINAL ELECTRICAL REQUIREMENTS AND PLUG TYPE WITH

EQUIPMENT PROVIDED PRIOR TO ROUGH-IN.

E5

COORDINATE EXACT TV/MONITOR LOCATIONS WITH OWNER'S DESIRED

MOUNTING HEIGHT PRIOR TO ROUGH-IN. COORDINATE WITH OWNER

PROVIDED TV/MONITOR AND MOUNTING SYSTEM SO THAT DEVICES AND

CABLES ARE NEAT AND CONCEALED. REFER TO LOW VOLTAGE DRAWINGS

FOR DETAILS AND ADDITIONAL INFORMATION.

E6

COORDINATE FINAL FURNITURE FEED LOCATIONS AND WIRING WITH

FURNITURE PROVIDER PRIOR TO ROUGH-IN.

E7

COORDINATE FINAL DEVICE LOCATION WITH FURNITURE PRIOR TO

ROUGH-IN.

E8

COORDINATE DEVICE ELEVATION WITH ELECTRIC WATER COOLER

INSTRUCTIONS PRIOR TO ROUGH-IN.

E9

PROVIDE SINGLE POINT POWER CONNECTION FROM ASSOCIATED

MINI-SPLIT CONDENSING UNIT.

E10

PROVIDE 120V POWER TO FIRE ALARM CONTROL PANEL. COORDINATE

FINAL ELECTRICAL CONNECTION WITH FIRE ALARM CONTRACTOR. LABEL

BREAKER IN ACCORDANCE WITH NEC ARTICLE 760.41.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

Office of

Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OPTIONAL BID #1

BID DOCUMENTS

C U s e rs \a w e b e r\

D o c u m e n ts \1

M E

P R a w e b e r9

S

.r v t

/1

/2

:3

:3

P

M

EP111

LOWER LEVEL - POWER PLAN

LEAVENWORTH NATIONAL CEMETERY

GRAVESITE EXPANSION

150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048

897CM3025

June 22, 2026 ATW DIL 18704

1/4" = 1'-0"

LOWER LEVEL - POWER PLAN

TRUE

NORTH

PLAN

NORTH

Revisions: Date:

ANDREW T . WEBER

L ICENSED

KANSAS

P R O F E S SI O N A L E N G I N E E R

31716 06.22.2026

VA

F

O

ARCHITECT/ENGINEER OF RECORDCONSULTANT

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:

IRRIGATION:

EC DESIGN

400 5th St West Des Moines, IA 50265

(515) 225-6265

COST ESTIMATING:GEOTECHNICAL:

TERRACON

15620 W 113th St Lenexa, KS 66219

(913) 202-7598

OCMI

2100 North Greenville Ave. #1150 Richardson, TX 75082

(469) 431-0571

TECHNOLOGY:

IMEG

900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258

(480) 222-3789

U.S. Department of Veterans Affairs

Office of Design and Construction

ELECTRICAL GENERAL NOTES

1. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE

OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND ELECTRICAL

BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED. GROUND AND

BOND PER NEC ARTICLE 250.

2. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON

STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH A

MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET

PRIOR TO ROUGH-IN.

3. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL EQUIPMENT.

DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.

4. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITH PRIOR

APPROVAL FROM THE DESIGN TEAM.

5. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.

6. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE SAME

WALL ARE WITHIN 24" OF EACH OTHER.

7. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE

SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE

ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED

AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

ELECTRICAL PLAN KEYED NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

E1

COORDINATE EXACT LOCATION WITH ACCESS CONTROL HEADEND PRIOR

TO ROUGH-IN.

E2

PROVIDE (2) L5-30 RECEPTACLES FOR TELECOM RACK ZONE PDU (2)

INPUTS. COORDINATE EXACT LOCATIONS WITH TELECOM RACK PRIOR TO

ROUGH-IN.

E3

ACCESS CONTROL LOCATION. REFER TO LOW VOLTAGE DETAILS AND

ARCHITECTURAL SPECIFICATIONS FOR OPERATION AND FURTHER

ROUGH-IN BIDDING INFORMATION. COORDINATE ALL DOORHOLDS, CARD

READERS, ADA PUSH BUTTONS, AND OTHER ACCESSORIES WITH DESIGN

TEAM PRIOR TO ROUGH-IN.

E4

COORDINATE FINAL ELECTRICAL REQUIREMENTS AND PLUG TYPE WITH

EQUIPMENT PROVIDED PRIOR TO ROUGH-IN.

E5

COORDINATE EXACT TV/MONITOR LOCATIONS WITH OWNER'S DESIRED

MOUNTING HEIGHT PRIOR TO ROUGH-IN. COORDINATE WITH OWNER

PROVIDED TV/MONITOR AND MOUNTING SYSTEM SO THAT DEVICES AND

CABLES ARE NEAT AND CONCEALED. REFER TO LOW VOLTAGE DRAWINGS

FOR DETAILS AND ADDITIONAL INFORMATION.

E6

COORDINATE FINAL FURNITURE FEED LOCATIONS AND WIRING WITH

FURNITURE PROVIDER PRIOR TO ROUGH-IN.

E7

COORDINATE FINAL DEVICE LOCATION WITH FURNITURE PRIOR TO

ROUGH-IN.

E8

COORDINATE DEVICE ELEVATION WITH ELECTRIC WATER COOLER

INSTRUCTIONS PRIOR TO ROUGH-IN.

E9

PROVIDE SINGLE POINT POWER CONNECTION FROM ASSOCIATED

MINI-SPLIT CONDENSING UNIT.

E10

PROVIDE 120V POWER TO FIRE ALARM CONTROL PANEL. COORDINATE

FINAL ELECTRICAL CONNECTION WITH FIRE ALARM CONTRACTOR. LABEL

BREAKER IN ACCORDANCE WITH NEC ARTICLE 760.41.

F

C

PROGRAM ANALYST

BREAK ROOM

BUDGET ANALYST

HALLWAY

105c

ASSISTANT DIRECTOR

DIRECTOR

STAFF MEN

114A

STAFF WOMEN

113A

STORAGE

MULTIPURPOSE ROOM

108 ADMIN OFFICER

HALLWAY

OPERATIONAL CTR

LOBBY

HAC

MENS

WOMENS

DPM

PROVIDE NEMA 3R WALL MOUNTED

CT CABINET, CTs, AND DIGITAL

METER WITH WEATHERPROOF

ENCLOSURE WITH VIEWING WINDOW

AND HINGED ACCESS.

UE

SEE ELECTRICAL SITE PLANS FOR CONTINUATION

+24"

FB-2

FB-1

E3

E3

E4

E5

+6"

E3

E5

COFFEE

A-4,6 FRIDGE

A-8

MICROWAVE

A-31

A-12

A-14

A-35

MENS LOCKER ROOM

HALLWAY

105b

A-16

A-18

A-20

A-22

1 2.1 3 54.1 5.13.12

D.1

A-24

A-26

GRAVESITE LOCATOR

A-30

A-28

PRINTER

A-32

GFI WP

A-34

A-36

A-38

A-40

A-2

A-10

FURNITURE,FURNITURE

A-41,A-43E6

E6

EWC

A-51

H

G

E

B

A

D

A-34

A-55

FURNITURE,FURNITURE

A-45,A-47

E8

E4

E7

E7

E7

E7

AC GFI

AC GFI

GFI

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

Office of

Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OPTIONAL BID #1

BID DOCUMENTS

C U s e rs \a w e b e r\

D o c u m e n ts \1

M E

P R a w e b e r9

S

.r v t

/1

/2

:4

:1

P

M

EP121

FIRST LEVEL - POWER PLAN

LEAVENWORTH NATIONAL CEMETERY

GRAVESITE EXPANSION

150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048

897CM3025

June 22, 2026 ATW DIL 18704

1/4" = 1'-0"

FIRST LEVEL - POWER PLAN

TRUE

NORTH

PLAN

NORTH

Revisions: Date:

ANDREW T . WEBER

L ICENSED

KANSAS

P R O F E S SI O N A L E N G I N E E R

31716 06.22.2026

ANDREW T . WEBER

L ICENSED

KANSAS

P R O F E S SI O N A L E N G I N E E R

31716 06.22.2026

VA

F

O

ARCHITECT/ENGINEER OF RECORDCONSULTANT

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:

IRRIGATION:

EC DESIGN

400 5th St West Des Moines, IA 50265

(515) 225-6265

COST ESTIMATING:GEOTECHNICAL:

TERRACON

15620 W 113th St Lenexa, KS 66219

(913) 202-7598

OCMI

2100 North Greenville Ave. #1150 Richardson, TX 75082

(469) 431-0571

TECHNOLOGY:

IMEG

900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258

(480) 222-3789

U.S. Department of Veterans Affairs

Office of Design and Construction

72 SF

B04

ELECTRICAL

140 SF

B03

TR

215 SF

B02

BASEMENT

611 SF

B01

BASEMENT

57 SF

B05

STAIRS

F

C

MDP

PANEL

EQUIPMENT

PANEL A

AHU-1

208V-3P/40A

EQ-1,3,5

VAV-002

120V-1P/25A

EQ-4

VAV-001

120V-1P/25A

EQ-2

FROM CU-2

WH-2

EQ-26

1 2.1 3 54.1 5.13.12

D.1

H

G

E

B

A

D

CP-01

EQ-35

M

E9

NO ELECTRICAL SCOPE IN THIS AREA

NO ELECTRICAL SCOPE IN THIS AREA

NO ELECTRICAL SCOPE IN THIS AREA

NO ELECTRICAL SCOPE IN THIS AREA

ELECTRICAL GENERAL NOTES

1. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE

OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND ELECTRICAL

BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED. GROUND AND

BOND PER NEC ARTICLE 250.

2. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON

STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH A

MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET

PRIOR TO ROUGH-IN.

3. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL EQUIPMENT.

DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.

4. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITH PRIOR

APPROVAL FROM THE DESIGN TEAM.

5. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.

6. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE SAME

WALL ARE WITHIN 24" OF EACH OTHER.

7. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE

SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE

ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED

AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

ELECTRICAL PLAN KEYED NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

E1

COORDINATE EXACT LOCATION WITH ACCESS CONTROL HEADEND PRIOR

TO ROUGH-IN.

E2

PROVIDE (2) L5-30 RECEPTACLES FOR TELECOM RACK ZONE PDU (2)

INPUTS. COORDINATE EXACT LOCATIONS WITH TELECOM RACK PRIOR TO

ROUGH-IN.

E3

ACCESS CONTROL LOCATION. REFER TO LOW VOLTAGE DETAILS AND

ARCHITECTURAL SPECIFICATIONS FOR OPERATION AND FURTHER

ROUGH-IN BIDDING INFORMATION. COORDINATE ALL DOORHOLDS, CARD

READERS, ADA PUSH BUTTONS, AND OTHER ACCESSORIES WITH DESIGN

TEAM PRIOR TO ROUGH-IN.

E4

COORDINATE FINAL ELECTRICAL REQUIREMENTS AND PLUG TYPE WITH

EQUIPMENT PROVIDED PRIOR TO ROUGH-IN.

E5

COORDINATE EXACT TV/MONITOR LOCATIONS WITH OWNER'S DESIRED

MOUNTING HEIGHT PRIOR TO ROUGH-IN. COORDINATE WITH OWNER

PROVIDED TV/MONITOR AND MOUNTING SYSTEM SO THAT DEVICES AND

CABLES ARE NEAT AND CONCEALED. REFER TO LOW VOLTAGE DRAWINGS

FOR DETAILS AND ADDITIONAL INFORMATION.

E6

COORDINATE FINAL FURNITURE FEED LOCATIONS AND WIRING WITH

FURNITURE PROVIDER PRIOR TO ROUGH-IN.

E7

COORDINATE FINAL DEVICE LOCATION WITH FURNITURE PRIOR TO

ROUGH-IN.

E8

COORDINATE DEVICE ELEVATION WITH ELECTRIC WATER COOLER

INSTRUCTIONS PRIOR TO ROUGH-IN.

E9

PROVIDE SINGLE POINT POWER CONNECTION FROM ASSOCIATED

MINI-SPLIT CONDENSING UNIT.

E10

PROVIDE 120V POWER TO FIRE ALARM CONTROL PANEL. COORDINATE

FINAL ELECTRICAL CONNECTION WITH FIRE ALARM CONTRACTOR. LABEL

BREAKER IN ACCORDANCE WITH NEC ARTICLE 760.41.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

Office of

Design and Construction

Services

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OPTIONAL BID #1

BID DOCUMENTS

C U s e rs \a w e b e r\

D o c u m e n ts \1

M E

P R a w e b e r9

S

.r v t

/1

/2

:3

:4

P

M

EQ111

LOWER LEVEL - EQUIPMENT POWER PLAN

LEAVENWORTH NATIONAL CEMETERY

GRAVESITE EXPANSION

150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048

897CM3025

June 22, 2026 ATW DIL 18704

1/4" = 1'-0"

LOWER LEVEL - EQUIPMENT POWER PLAN

TRUE

NORTH

PLAN

NORTH

Revisions: Date:

ANDREW T . WEBER

L ICENSED

KANSAS

P R O F E S SI O N A L E N G I N E E R

31716 06.22.2026

VA

F

O

ARCHITECT/ENGINEER OF RECORDCONSULTANT

Revisions:

1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18704Date:

IRRIGATION:

EC DESIGN

400 5th St West Des Moines, IA 50265

(515) 225-6265

COST ESTIMATING:GEOTECHNICAL:

TERRACON

15620 W 113th St Lenexa, KS 66219

(913) 202-7598

OCMI

2100 North Greenville Ave. #1150 Richardson, TX 75082

(469) 431-0571

TECHNOLOGY:

IMEG

900 E. Prima Ctr Pkwy #320 Scottsdale, AZ 85258

(480) 222-3789

U.S. Department of Veterans Affairs

Office of Design and Construction

ELECTRICAL GENERAL NOTES

1. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE

OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND ELECTRICAL

BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED. GROUND AND

BOND PER NEC ARTICLE 250.

2. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON

STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH A

MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET

PRIOR TO ROUGH-IN.

3. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL EQUIPMENT.

DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.

4. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITH PRIOR

APPROVAL FROM THE DESIGN TEAM.

5. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.

6. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE SAME

WALL ARE WITHIN 24" OF EACH OTHER.

7. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE

SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE

ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE REVIEWED

AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

ELECTRICAL PLAN KEYED NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

E1

COORDINATE EXACT LOCATION WITH ACCESS CONTROL HEADEND PRIOR

TO ROUGH-IN.

E2

PROVIDE (2) L5-30 RECEPTACLES FOR TELECOM RACK ZONE PDU (2)

INPUTS. COORDINATE EXACT LOCATIONS WITH TELECOM RACK PRIOR TO

ROUGH-IN.

E3

ACCESS CONTROL LOCATION. REFER TO LOW VOLTAGE DETAILS AND

ARCHITECTURAL SPECIFICATIONS FOR OPERATION AND FURTHER

ROUGH-IN…