_25 LNC BD - STRUCTURAL (pg 189-200).pdf
PDF 6 MB Posted
- Solicitation number
- 36C78626B0027
About this file
These are structural design drawings and specifications for the Leavenworth National Cemetery Gravesite Expansion project located at 150 Muncie Road, Leavenworth, Kansas 66048. The documents are prepared for the U.S. Department of Veterans Affairs and include general construction notes, foundation details, framing plans, and structural details for both an administrative building expansion and site elements including a columbarium and service seals wall.
The work shall comply with PG-18-10 Structural Design Manual (dated 7/1/2023), International Building Code 2024, ASCE/SEI 7-22, and VA Handbook H-18-8. Foundation design is based on a geotechnical report by Terracon dated February 18, 2026 (Report #02255188), with footings designed for 1500 psf minimum net allowable soil bearing pressure. Concrete compressive strengths range from 4000-5000 psi depending on application. The project includes cast-in-place concrete construction with reinforcing steel (Grade 60), structural steel members (ASTM A992, A500, A36 specifications), and wood framing complying with APA and International Building Code standards. Design loads include roof snow load of 26 psf with 1.169 thermal factor for R-30 insulation, floor live loads of 80-125 psf, ultimate wind speed of 103-110 mph (Exposure C), and seismic design category B. Contractor responsibilities include verification of all dimensions, provision of temporary bracing and shoring, protection of the structure during construction, coordination with mechanical and electrical trades, and submission of shop drawings and delegated design submittals (prefabricated wood trusses, precast columbarium units, window glazing systems, stairs, and handrails) stamped by appropriately licensed engineers for approval prior to construction.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL CONSTRUCTION NOTES:
1. ALL WORK SHALL COMPLY WITH THE PG-18-10 STRUCTURAL DESIGN
MANUAL DATED 7/1/2023 AS APPROVED BY THE DEPARTMENT OF VETERANS
AFFAIRS. THE FOLLOWING CODES APPLY:
-INTERNATIONAL BUILDING CODE 2024
-ASCE/SEI 7-22
-VA HANDBOOK H-18-8 SEISMIC DESIGN REQUIREMENTS
2. REFERENCE STANDARDS: UNLESS OTHERWISE NOTED (U.O.N.), ALL
STANDARDS SHALL BE CURRENT EDITION, WITH LATEST ADDENDA, IF
APPLICABLE.
3. THE CONTRACTOR SHALL VERIFY ALL CONTRACT DOCUMENTS, SITE
ELEVATIONS, DIMENSIONS AND CONDITIONS PRIOR TO STARTING WORK
AND SHALL NOTIFY THE ARCHITECT/ ENGINEER OF ANY DISCREPANCIES OR
INCONSISTENCIES.
4. SPECIFIC NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL
NOTES.
5. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS
REPRESENT THE FINISHED STRUCTURE. UNLESS OTHERWISE INDICATED,
THEY DO NOT INDICATE THE MEANS OR METHOD OF CONSTRUCTION.
TEMPORARY BRACING AND SHORING AGAINST WIND AND ERECTION
CONDITIONS DURING CONSTRUCTION OF THE BUILDING, SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR IS SOLELY
RESPONSIBLE FOR THE PROTECTION OF THE STRUCTURE DURING ALL
PHASES OF DEMOLITION, CONSTRUCTION, AND INSTALLATION.
6. NO AREA OF THE STRUCTURE SHALL BE LOADED WITH CONSTRUCTION
MATERIALS OR EQUIPMENT THAT EXCEEDS FINAL DESIGN CRITERIA.
7. VERIFY LOCATION OF BOX OUTS AND OPENINGS WITH MECHANICAL
CONTRACTORS. OPENING SIZES AND LOCATIONS SHOWN FOR PIPES,
DUCTS ETC. ARE FOR GENERAL INFORMATION ONLY AND SHALL BE
VERIFIED WITH THE MECHANICAL CONTRACTOR BEFORE COMMENCING
THE WORK.
8. IF MECHANICAL AND ELECTRICAL EQUIPMENT SIZES, WEIGHTS, OR
LOCATIONS DO NOT COINCIDE WITH EQUIPMENT SHOWN ON PLANS,
COORDINATE ADJUSTMENTS WITH THE STRUCTURAL ENGINEER.
9. HOLES, PIPES, SLEEVES, ETC. NOT SHOWN ON THE DRAWINGS MUST BE
APPROVED BY THE STRUCTURAL ENGINEER BEFORE PLACEMENT
THROUGH STRUCTURAL MEMBERS.
10. CONTRACTOR SHALL PROVIDE A CAST-IN SLEEVE FOR ALL HORIZONTAL
ELEMENTS THAT EXTEND THROUGH FOOTING. IE: DRAIN TILE, ELECTRICAL
CONDUIT, MECHANICAL PIPING, ETC. ALL SLEEVES SHALL BE
COORDINATED WITH ARCHITECT/ENGINEER.
11. SHOP DRAWINGS PREPARED BY SUPPLIERS, SUBCONTRACTORS, ETC.,
SHALL BE DIMENSIONED, REVIEWED, COORDINATED, AND SIGNED/
STAMPED BY THE GENERAL CONTRACTOR PRIOR TO SUBMITTING TO THE
STRUCTURAL ENGINEER.
12. FABRICATOR SHALL CLEARLY NOTE CHANGES MADE IN THE SHOP
DRAWINGS WHICH DO NOT COMPLY WITH THE CONTRACT DOCUMENTS.
REVIEWED APPROVAL SHOP DRAWINGS SHOWING ENGINEERS COMMENTS
ACCOMPANIED WITH RECORD SET SHOP SHOP DRAWINGS, SHALL BE
AVAILABLE FOR REFERENCE AT THE CONSTRUCTION SITE.
13. CONCRETE ANCHORS SHALL BE SIMPSON 'TITEN HD" SCREW ANCHORS OR
EQUIVALENT (U.O.N.). INSTALL ANCHORS USING THE MANUFACTURER'S
RECOMMENDATIONS.
FOUNDATION NOTES:
1. FOOTING ELEVATIONS ARE TO TOP OF FOOTING (T.O. FTG.), UNLESS
OTHERWISE NOTED.
2. FOOTINGS ARE DESIGNED FOR A MINIMUM NET ALLOWABLE SOIL BEARING
PRESSURE OF1500 psf FOR CONTINUOUS AND 1500 psf FOR PAD FOOTINGS.
FOUNDATION DESIGN COMPLIES W/ GEOTECHNICAL REPORT DATED: MARCH 23,
2026 BY TERRACON. REPORT #: 02255188.01 (ADDENDUM)
3. FOOTINGS SHALL BEAR ON NATURAL UNDISTURBED SOIL OR ENGINEERED FILL.
SOILS SHALL BE OBSERVED AND APPROVED BY A GEOTECHNICAL ENGINEER
PRIOR TO PLACEMENT OF FOOTING CONCRETE. IF NATURAL UNDISTURBED
SOILS ARE NOT ENCOUNTERED AND/OR INADEQUATE SOILS ARE NOTED AT
FOOTING BEARING LEVEL, ARCHITECT/ENGINEER SHALL BE NOTIFIED PRIOR TO
PROCEEDING WITH FURTHER WORK AT THOSE FOOTING LOCATIONS.
4. PROTECT FOOTINGS FROM THE ACTION OF WATER OR FREEZING.
5. FOOTINGS ARE CENTERED UNDER WALLS ABOVE - UNLESS OTHERWISE
NOTED.
6. PRIOR TO PLACEMENT OF FOOTING CONCRETE, CLEAN FOOTING EXCAVATIONS
OF SNOW, WATER AND DEBRIS.
7. FOOTINGS MAY NOT BE EARTH FORMED.
EXCAVATION & BACKFILL NOTES:
1. EXCAVATION AND BACKFILL SHALL BE EXECUTED IN ACCORDANCE WITH THE
PROJECT SPECIFICATIONS.
2. BACKFILL, & COMPACTION SHALL BE INSPECTED AND CERTIFIED BY A LICENSED
GEOTECHNICAL ENGINEER. REPORTS ARE TO BE SUBMITTED TO THE
ARCHITECT/ ENGINEER.
3. FOOTING EXCAVATIONS SHALL BE EXCAVATED TO PROPER LINE AND LEVEL TO
ENSURE MINIMUM CONCRETE COVER OF FOOTING REINFORCEMENT FOR
FOOTING DEPTH.
4. BACKFILL SHALL BE COMPACTED BY MECHANICAL MEANS. FLOODING OR
WATER INUNDATION SHALL NOT BE PERMITTED.
5. BACKFILL SHALL BE PLACED IN ALTERNATING LIFTS ON EACH SIDE OF THE
FOUNDATION WALLS TO MAINTAIN STABILITY OF THE FOUNDATION WALLS.
6. BACKFILL SHALL NOT BE PLACED AGAINST BASEMENT FOUNDATION WALLS
UNLESS WALLS ARE ADEQUATELY BRACED TOP AND BOTTOM. FINAL WALL
BRACING IS BASEMENT SLAB OR ENGINEERED BACKFILL AND 1ST FLOOR
STRUCTURE. IF THESE ELEMENTS ARE NOT IN PLACE AT TIME OF BACKFILL,
CONTRACTOR SHALL PROVIDE AN ENGINEERED, TEMPORARY BRACING
SYSTEM. THE TEMPORARY BRACING SYSTEM PROPOSED SHALL BE SUBMITTED
TO THE ARCHITECT/ ENGINEER FOR REVIEW PRIOR TO BACKFILLING.
CONCRETE NOTES:
1. CONCRETE CONSTRUCTION SHALL CONFORM TO AMERICAN CONCRETE
INSTITUTE (ACI) CODES AND SPECIFICATIONS, LATEST EDITION. ACI 301
"SPECIFICATIONS FOR STRUCTURAL CONCRETE" ACI 315 "DETAILS &
DETAILING OF CONCRETE REINFORCEMENT" ACI 318 "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE".
2. CONCRETE MIX DESIGN SHALL BE BY AN INDEPENDENT TESTING
LABORATORY.
3. CAST-IN-PLACE CONCRETE SHALL BE SUBJECT TO TESTING BY AN
INDEPENDENT TESTING LABORATORY. SEE PROJECT SPECIFICATIONS
FOR REQUIREMENTS.
4. NON WELDED REINFORCING STEEL SHALL BE GRADE 60 DEFORMED,
BILLET-STEEL, ASTM A615, U.O.N. ALL WELDED WIRE FABRIC (WWF)
SHALL BE PLAIN, ASTM A185.
5. WELDED REINFORCING STEEL SHALL BE GRADE 60, LOW CARBON, ASTM
A706.
6. PROVIDE EXTRA REINFORCEMENT AROUND ALL OPENINGS GREATER
THAN 12" SQUARE OR 12" IN DIAMETER, INCLUDING DOOR OPENINGS, IN
CONCRETE WALLS & SLABS. PROVIDE 2 - #5 BARS @ 3" O.C., ON EACH
SIDE OF THE OPENING EXTENDING 24" BEYOND THE CORNER OF THE
OPENING & 2 - #5 BARS AT 3" O.C. BY 3'-0" LONG DIAGONAL BARS AT EACH
CORNER. PLACE DIAGONAL BARS CENTERED ON CORNER @ 2" CLEAR
OF CORNER. ADDITIONAL REINFORCEMENT SHALL BE PROVIDED AT EACH
LAYER OF REINFORCING.
7. REINFORCING STEEL SHALL BE BENT, SPLICED, AND PLACED IN
ACCORDANCE WITH THE ACI 301 (LATEST EDITION).
8. PROVIDE ADEQUATE SUPPORT BARS AND ACCESSORIES TO HOLD
REINFORCING BARS FIRMLY IN PLACE TO SPECIFIED COVERAGES.
9. CONTROL JOINTS SHALL BE PLACED IN A SQUARE PATTERN WITH A
MAXIMUM SPACING OF 10' - 0" O.C. FOR 4" THICK SLAB, 12' - 0" O.C. FOR 5"
THICK SLAB, 15' - 0" O.C. FOR 6" THICK SLAB. WHERE A SQUARE PATTERN
IS NOT POSSIBLE, THE MAXIMUM LONG SIDE TO SHORT SIDE OF THE
JOINT PATTERN SHALL NOT EXCEED A RATIO OF 1.5:1. CONSTRUCTION
JOINTS SHALL BE LOCATED BY THE CONTRACTOR AS REQUIRED FOR
CONSTRUCTION WITH A MAXIMUM OF 3,000 SQUARE FEET.
10. CAST DOWELS, WITH STD 90 DEGREE HOOK, IN FOOTINGS FOR
CONCRETE PIERS AND WALLS ABOVE. DOWELS SHALL BE THE SAME SIZE
AND NUMBER AS THE VERTICAL REINFORCING. (U.O.N.)
11. CONCRETE MIX DESIGNS REQUIREMENTS: - AGGREGATES SHALL
CONFORM TO ASTM C33. - CONCRETE EXPOSED TO FREEZE THAW SHALL
HAVE 4.5%-7.5% AIR. - WATER/CEMENT RATIO 0.55 MAX. FOR FOOTINGS
AND WALLS, 0.5 MAX. FOR SLABS - NO FLY ASH IN EXPOSED SLABS, 0.25
MAX. FLY ASH/CEMENT RATIO IN ALL OTHER APPLICATIONS - WATER
PROOFING ADMIXTURE ADD FOR EXTERIOR EXPOSED CONCRETE.
12 INJECTION ADHESIVE ANCHORS SHALL BE SIMPSON "SET-3G" USING
STANDARD 36 KSI THREADED RODS (U.O.N.). SEE SPECIFICATIONS FOR
USAGE. INSTALL ANCHORS IN STRUCTURAL CONFORMANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
CAST-IN-PLACE CONCRETE COMPRESSIVE STRENGTHS
FOOTINGS 4000 psi.
EXTERIOR FOUNDATION WALLS 5000 psi.
INTERIOR FOUNDATION WALLS 4000 psi.
PIERS 4000 psi.
INTERIOR SLABS ON GRADE 4000 psi.
EXTERIOR SLABS ON GRADE (AIR ENTRAINED) 4000 psi.
RAISED SLABS 4000 psi.
EXTERIOR SLABS ON DECK (AIR ENTRAINED) 4000 psi.
REINFORCING CLEAR CONCRETE COVER
CONCRETE ON SOIL 3"
SLABS ON GRADE MIDHEIGHT
FORMED WALLS & STRUCTURAL SLABS EXPOSED TO EARTH OR
WEATHER: #6 THRU #18
2"
FORMED WALLS & STRUCTURAL SLABS EXPOSED TO EARTH OR
WEATHER: #5 OR SMALLER
1 1/2"
FORMED WALLS & STRUCTURAL SLABS NOT EXPOSED TO EARTH OR
WEATHER: #11 AND SMALLER
3/4"
BEAMS AND COLUMNS (COVER TO STIRRUPS OR TIES) 1 1/2"
CONC. REINFORCING BAR LAP SPLICE
SCHEDULE
BAR SIZE
f'c = 3000 psi.
f'c = 4000 psi.
f'c = 5000 psi.
CLASS
"B"
CLASS
"B"
CLASS
"B"
#3 22" 20" 18"
#4 30" 26" 22"
#5 36" 32" 28"
#6 44" 38" 34"
#7 64" 54" 50"
#8 72" 62" 56"
#9 82" 70" 64"
#10 92" 80" 70"
#11 102" 88" 78"
BAR LAP SCHEDULE NOTES:
A. REINFORCING BAR LAP SPLICE SCHEDULE APPLIES TO UNCOATED, GRADE 60
REINFORCING BAR NORMAL WEIGHT CONCRETE.
B. PROVIDE CLASS "B" LAP UNLESS OTHERWISE NOTED.
C. FOR EPOXY COATED BAR, MULTIPLY THE NOTED LENGTHS BY 1.5.
D. FOR LIGHT WEIGHT CONCRETE, MULTIPLY THE NOTED LENGTHS BY 1.3.
E. MAXIMUM SPACING OF BARS BEING LAPPED IS ONE FIFTH THE LAP SPLICE
LENGTH, NOT TO EXCEED 6".
F. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12" OF FRESH CONCRETE
PLACED BELOW HORIZONTAL REINFORCEMENT.FOR TOP BARS, MULTIPLY THE
NOTED LENGTHS BY 1.3.
STRUCTURAL STEEL NOTES:
1. WELDED CONNECTIONS SHALL BE MADE IN ACCORDANCE WITH THE LATEST
RECOMMENDATIONS OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION
(AISC) AND THE AMERICAN WELDING SOCIETY (AWS).
2. COLUMN BASE AND CAP PLATES TO BE WELDED AROUND ALL SIDES.
3. WELDS NOT SPECIFIED SHALL BE A FILLET WELD, CONTINUOUS AND/OR ALL
AROUND WITH MINIMUM THROAT DIMENSION AS REQUIRED FOR MATERIAL
THICKNESS PER AWS.
4. STRUCTURAL FABRICATORS SHALL SHOW ALL FIELD WELDING REQUIREMENTS
ON SHOP DRAWINGS SUBMITTED TO THE ENGINEER.
5. BEFORE ENCASING STEEL COLUMNS IN CONCRETE OR MASONRY, COAT
COLUMN BASES AND TOPS OF ANCHOR BOLTS WITH ASPHALTIC ROOF
CEMENT.
6. BEAMS AND COLUMNS SHALL BE ERECTED TRUE AND PLUMB WITHIN AISC
TOLERANCE. PROVIDE TEMPORARY BRACING AS REQUIRED.
7. BEARING PLATES FOR STEEL SHALL BE DRY PACKED WITH A NON-SHRINK,
NON-METALLIC GROUT AS SPECIFIED.
8. PROVIDE DOUBLE ANGLE CONNECTIONS AS DESCRIBED IN PART 10 OF THE
AISC MANUAL OF STEEL CONSTRUCTION (15TH ED-ASD). CONNECTIONS SHALL
BE SELECTED TO SUPPORT BEAM END REACTIONS INDICATED ON THE
CONTRACT DRAWINGS. IF BEAM END REACTIONS ARE NOT INDICATED,
CONNECTIONS MUST BE SELECTED ACCORDING TO THE STANDARD DETAILS
OF THE CONTRACT DRAWINGS. IF BEAM IS NOT ABLE TO SATISFY THE
CONDITIONS OF THE STANDARD DETAILS CONTACT ENGINEER OF RECORD
FOR SPECIFIC DETAILING.
9. FRAMED STEEL BEAM CONNECTIONS SHALL BE "BEARING TYPE", (U.O.N.).
10. DO NOT PAINT STEEL TO BE FIELD WELDED.
AISC MATERIAL SPECIFICATION (13TH EDITION)
"W", "S" AND "M" SHAPES ASTM A992 Fy = 50 ksi.
GRADE "B" STANDARD PIPES ASTM A53 Fy = 35 ksi.
GRADE "C" HSS PIPES ASTM A500 Fy = 46 ksi.
GRADE "C" HSS TUBES ASTM A500 Fy = 50 ksi.
PLATES, BARS, CHANNELS, RODS, ANGLES AND
MISC. SHAPES
ASTM A36 Fy = 36 ksi.
GRADE 36 ANCHOR BOLTS ASTM F1554-99 Fy = 36 ksi.
CONNECTION BOLTS ASTM A325 Fv = 120 ksi.
CONNECTION BOLTS ASTM A490 Fv = 150 ksi.
CONNECTION NUTS ASTM A563
WASHERS ASTM F436
ELECTRODES E70XX
WOOD FRAMING NOTES:
1. WOOD AND TIMBER CONSTRUCTION SHALL CONFORM TO PROJECT SPECIFICATIONS
AND AMERICAN INSTITUTE OF TIMBER CONSTRUCTION (AITC) STANDARDS.
2. WOOD CONSTRUCTION SHALL CONFORM TO CHAPTER 23, OF THE INTERNATIONAL
BUILDING CODE (UNLESS OTHERWISE NOTED). ALL NAILING SHALL CONFORM TO
TABLE 2304.10.1 "FASTENING SCHEDULE" OF THE INTERNATIONAL BUILDING CODE
UNLESS OTHER REQUIREMENTS NOTED ON THE PLAN ARE MORE STRICT. JOINTS IN
LOAD BEARING TOP PLATES SHALL BE OFFSET AT LEAST 48". HOLES IN SAWN LUMBER
SHALL BE AS SPECIFIED IN THE INTERNATIONAL BUILDING CODE.
3. FRAMING LUMBER SHALL CONFORM WITH THE PROVISIONS OF THE AMERICAN
SOFTWOOD LUMBER STANDARD PS-20-70 AND EACH PIECE SHALL BEAR THE GRADE
STAMP OF A GRADING AGENCY APPROVED BY THE AMERICAN LUMBER STANDARDS
COMMITTEE. ALL FRAMING LUMBER 2" AND LESS IN THICKNESS SHALL BE SEASONED
TO A MOISTURE CONTENT OF 19% OR LESS PRIOR TO SURFACING WITH THE
INDICATION "S-DRY" ON THE GRADE STAMP.
4. FOUNDATION PLATES ON CONCRETE OR MASONRY WALLS FOR ALL STRUCTURAL
WALLS SHALL BE AWPA FDN ACQ/AC2 TREATED PLATES OF NO. 2 GRADE MINIMUM.
THERE SHALL BE A MINIMUM OF 3 - BOLTS PER PIECE WITH ONE BOLT LOCATED
WITHIN 8" OF EACH END OF EACH PIECE. THERE SHALL BE NO SILL SPLICE UNDER ANY
POST OR MULLION.
5. STUD WALLS TO BE CONSTRUCTED WITH CONTINUOUS TREATED SILL PLATE AND WITH
DOUBLE TOP PLATE. SEE STANDARD DETAILS FOR TOP SPLICE CONNECTION
6. BUILT UP MEMBERS, COLUMNS, BEAMS AND DOUBLE JOISTS SHALL BE CONNECTED
WITH TWO ROWS 0.148 x 3" LONG NAILS AT 12" O.C. STAGGERED, UNLESS OTHERWISE
NOTED.
7. WHERE POSTS ARE CALLED OUT, HEADERS SHALL BEAR FULLY ON POSTS.
8. ALL 2x HEADERS & BEAMS SHALL HAVE 3 SUPPORT STUDS (1 - KING BOARD & 2 - JACK
STUDS) UNLESS REQUIREMENTS NOTED ON PLAN ARE MORE STRICT.
9. ALL JOISTS, ROOF BEAMS AND GIRDERS SHALL HAVE FULL HORIZONTAL BEARING OF
THE MEMBER OVER SUPPORT UNLESS OTHERWISE SHOWN. DO NOT OVERCUT.
10. NO NOTCHING OF STUDS, JOISTS, RAFTERS, BEAMS OR TRUSSES IS PERMITTED
WITHOUT THE ENGINEERS APPROVAL. HOLES BORED IN THE STUD OR JOIST SHALL BE
IN THE MIDDLE ONE-THIRD OF THE DEPTH AND THE DIAMETER OF ANY SUCH HOLE
SHALL NOT EXCEED ONE-FOURTH THE DEPTH WITHOUT REINFORCEMENT. HOLES
EXCEEDING ONE-FOURTH THE DEPTH SHALL HAVE A SIMPSON "HSS" STUD SHOE
APPLIED TO THE STUD.
11. FLOOR AND ROOF TRUSSES ARE TO BE ENGINEERED BY FABRICATOR AND ERECTED
ACCORDING TO MANUFACTURER'S SPECIFICATIONS. PLAN LOCATIONS FOR TRUSSES
ARE FOR REFERENCE ONLY. FINAL LOCATIONS SHALL BE DETERMINED BY SUPPLIER
USING MAXIMUM SPACING & DETAILS INDICATED ON PLANS. WOOD TRUSS
CONSTRUCTION AND FABRICATION SHALL FOLLOW GUIDELINES SET FORTH BY THE
WOOD TRUSS COUNCIL OF AMERICA. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL
TRUSS INFORMATION.
12. ALL FABRICATED WOOD TRUSSES SHALL BE FURNISHED IN ACCORDANCE WITH
DESIGNS PREPARED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE THE
PROJECT IS LOCATED, USING THE DESIGN LOADS AND SPAN CONDITIONS INDICATED
ON THE CONTRACT DOCUMENTS. NO DEVIATION OF TRUSS SHAPE, MEMBER SIZE
BEARING POINT LOCATION OR SUPERIMPOSED LOADS, FROM THE CONTRACT
DOCUMENTS SHALL BE PERMITTED WITHOUT THE APPROVAL OF THE ARCHITECT AND /
OR THE ENGINEER. SHOP DRAWINGS, INCLUDING AN OVERALL ERECTION PLAN
INDICATING EACH TYPE OF TRUSS, TRUSS BEARING POINT LOCATIONS, REQUIRED
LATERAL BRACING, EACH TRUSS MEMBERS SIZE AND STRESS AND CONNECTION
DETAILS, SHALL BE SUBMITTED FOR PRIOR APPROVAL TO THE GENERAL
CONTRACTOR.
13. THE WOOD TRUSS SUPPLIER SHALL PROVIDE A BCSI WITH THE TRUSS ERECTION
DWGS FOR REFERENCE BY THE TRUSS INSTALLER.
14. THE GUIDELINES SET FORTH BY THE TRUSS PLATE INSTITUTE PUBLICATION ANSI/TPI
1-2014: "COMMENTARY & RECOMMENDATIONS FOR HANDLING, INSTALLING, & BRACING
MTL. PLATE CONNECTED WOOD TRUSSES" SHALL BE FOLLOWED BY THE TRUSS
INSTALLER.
15. PERMANENT BRACING OF WOOD TRUSSES SHALL BE INSTALLED BY THE TRUSS
INSTALLER, WHERE INDICATED BY THE TRUSS ERECTION DWGS. MINIMUM BRACING
REQUIREMENTS FOR TOP CHORD, BOTTOM CHORD, & WEB MEMBER PLANES SHALL BE
IN ACCORDANCE W/ ANSI/TPI 1-2014. UNLESS REQUIR
16. ERECTION BRACING OF WOOD TRUSSES IS THE RESPONSIBILITY OF THE TRUSS
INSTALLER. THE TRUSS INSTALLER SHALL PROVIDE TEMPORARY DIAGONAL, LATERAL,
& CROSS BRACING (PER ANSI/TPI 1-2014) UNTIL ROOF SHEATHING, CEILING &
PERMANENT BRACING CAN BE APPLIED & SHEAR WALLS COMPLETED.
17. ROOF TRUSSES SHALL BE FASTENED TO THE SUPPORT WALLS WITH SIMPSON "H2.5A"
TIES OR EQUAL (U.O.N.) AND SHALL BE NAILED PER MANUFACTURES
RECOMMENDATION.
18. CONTRACTOR TO PROVIDE DIAGONAL BRACING AT STUD WALLS TO PREVENT
RACKING DURING CONSTRUCTION.
19. PROVIDE EITHER SIMPSON "DTC" CLIP OR SIMPSON "SDPW" DEFLECTOR SCREW AT
EACH FLOOR AND ROOF TRUSS OR BLOCKING @ 2'-0" O.C FOR NON-BEARING WALL
CONNECTION.
20. ALL FASTENERS THAT ARE 1/4" DIAMETER OR GREATER REQUIRE PREDRILLED HOLES.
21. HANGERS FOR DIMENSIONAL LUMBER REFRENCED IN FRAMING DETAILS SHALL MATCH
THE MAXIMUM SIZE OF CONNECTING FRAMING MEMBER.
VENEER LINTEL SCHEDULE
0'-1" TO 3'-11" L 3 1/2" x 3 1/2" x 1/4"
4'-0" TO 5'-11" L 4" x 3 1/2" x 1/4"
6'-0" TO 7'-11" L 5" x 3 1/2" x 1/4"
8'-0" AND GREATER CONTACT STRUCTURAL ENGINEER
VENEER LINTEL SCHEDULE NOTES:
A. ALL LINTELS TO HAVE 1" BEARING PER FOOT OF SPAN AT EACH END, 8" MINIMUM.
B. VENEER LINTEL SCHEDULE INDICATES MEMBERS TO BE USED FOR A 4" WALL
VENEER, UNLESS OTHERWISE NOTED.
DIMENSIONAL LUMBER DESIGN PROPERTIES
SPF. #2 OR
BETTER
BENDING Fb = 875 psi.
SHEAR Fv = 135 psi.
COMPRESSION PARALLEL TO GRAIN Fc = 1150 psi.
COMPRESSION PERPENDICULAR TO GRAIN Fc = 425 psi.
MODULUS OF ELASTICITY E = 1400 ksi.
DF-L. #2 OR
BETTER
BENDING Fb = 900 psi.
SHEAR Fv = 180 psi.
COMPRESSION PARALLEL TO GRAIN Fc = 1350 psi.
COMPRESSION PERPENDICULAR TO GRAIN Fc = 625 psi.
MODULUS OF ELASTICITY E = 1600 ksi.
VERTICAL STRUCTURAL PANEL SHEATHING NOTES:
VERTICAL GENERAL:
1. FASTENERS SHALL NOT BE LOCATED LESS THAN 3/8" IN FROM THE EDGE OF THE
PANEL.
2. FASTENERS SHALL BE DRIVEN FLUSH WITH SURFACE OF SHEATHING.
3. FASTENERS SHALL BE OF SUFFICIENT LENGTH TO ENSURE PENETRATION INTO
FRAMING MEMBERS BY AT LEAST 1 1/2" INTO WOOD FRAMING.
4. NO SHEATHING PANEL LESS THAN 1'-0" WIDE SHALL BE USED.
5. SHEATHING PANEL EDGES SHALL BUTT ALONG THE CENTERLINE OF A COMMON
FRAMING MEMBER.
6. IN THE PRE-FABRICATED WALL PANEL APPLICATION, ALL ADJACENT WALL PANEL
EDGES THAT DO NOT SHARE A COMMON FRAMING MEMBER OF ADJOINED WALL
PANELS FASTENED TOGETHER WITH ONE ROW OF STAGGERED 10D NAILS @ 6"
ON CENTER FROM BOTH SIDES.
7. ALL PANEL EDGES SHALL BE FULLY BLOCKED. WHERE HORIZONTAL STRAP
BLOCKING IS USED, IT SHALL BE A MINIMUM 1 1/2" WIDE & OF THE SAME
MATERIAL & THICKNESS AS THE TRACK & STUDS.
8. WOOD STRUCTURAL PANELS SHALL CONFORM TO THE REQUIREMENTS FOR
THEIR TYPE IN DOC PS1 OR PS2.
HORIZONTAL STRUCTURAL PANEL SHEATHING NOTES:
HORIZONTAL GENERAL:
1. FASTENERS SHALL NOT BE LOCATED LESS THAN 3/8" IN FROM THE EDGE OF
THE SHEATHING PANEL.
2. FASTENERS SHALL BE DRIVEN FLUSH WITH SURFACE OF SHEATHING.
3. FASTENERS SHALL BE OF SUFFICIENT LENGTH TO ENSURE PENETRATION
INTO FRAMING MEMBERS BY AT LEAST 1 1/2" INTO WOOD FRAMING.
4. NO UNBLOCKED PANELS LESS THAN 1'-0" WIDE SHALL BE USED.
5. SHEATHING PANEL EDGES SHALL BUTT ALONG THE CENTERLINE OF A
COMMON FRAMING MEMBER.
6 WOOD STRUCTURAL PANELS SHALL CONFORM TO THE REQUIREMENTS FOR
THEIR TYPE IN DOC PS1 OR PS2.
HORIZONTAL WOOD SHEATHING:
1. PANEL ROOF SHEATHING SHALL BE 1/2" APA EXPOSURE 1, RATED
SHEATHING WITH A 32/16 SPAN RATING (U.O.N.).
2. PANEL FLOOR SHEATHING SHALL BE 3/4" APA EXPOSURE 1, RATED PLYWOOD
WITH A 48/24 SPAN RATING (U.O.N.).
3. WOOD FRAMING SHEATHING FASTENERS SHALL BE A MINIMUM 0.131" DIA. x 2
1/2" LONG COMMON NAILS. SEE HORIZONTAL GENERAL NOTE #3 FOR
LENGTH.
4. FLOOR/ ROOF PANEL SHEATHING SHALL BE CONTINUOUS OVER 2 OR MORE
SUPPORTS (MINIMUM).
5. FLOOR/ ROOF PANEL SHEATHING SHALL BE ORIENTED WITH THE STRENGTH
AXIS PERPENDICULAR TO THE SUPPORTS.
6. TONGUE & GROOVE EDGES, PANEL EDGE CLIPS (1 - MIDWAY BETWEEN EACH
SUPPORT), OR BLOCKING SHALL BE USED @ ALL UNSUPPORTED EDGES.
7. SPACE FASTENERS @ 12" O.C. ALONG INTERMEDIATE FRAMING MEMBERS
(FIELD OFSHEATHING PANEL); SPACE FASTENERS @ 6" O.C. ALONG ALL
SHEATHING PANEL EDGE FRAMING MEMBERS (SUPPORTED EDGES) (U.O.N.).
8. EACH SHEATHING PANEL SHALL BE IDENTIFIED WITH THE GRADE
TRADEMARK OF THE AMERICAN PLYWOOD ASSOCIATION AND SHALL MEET
THE REQUIREMENTS OF PRODUCT STANDARD (psi). APPLICATION AND
NAILING OF PLYWOOD SHALL BE IN ACCORDANCE WITH THE
RECOMMENDATIONS OF THE AMERICAN PLYWOOD ASSOCIATION & TABLE
2304.10.1 "FASTENING SCHEDULE" OF THE INTERNATIONAL BUILDING CODE
UNLESS OTHER REQUIREMENTS NOTED ON THE PLAN ARE MORE STRICT.
VERTICAL WOOD SHEATHING:
1. BLOCK ALL SHEATHING PANEL EDGES.
2. PANEL SHEATHING SHALL BE_7/16" APA EXPOSURE 1, RATED SHEATHING
WITH A 32/16 SPAN RATING (U.O.N.).
3. FRAMING SPACING TO BE MAXIMUM 1'-4" O.C. UNLESS SPECIFIC NOTES AND /
OR DETAILS ARE MORE STRICT.
4. WOOD FRAMING SHEATHING FASTENERS SHALL BE A MINIMUM 0.131" DIA. x 2
1/2" LONG COMMON NAILS OR GALVANIZED BOX NAILS (GALVANIZED NAILS
SHALL BE HOT-DIPPED OR TUMBLED). SEE VERTICAL GENERAL NOTE #3 FOR
LENGTH.
5. OFFSET SHEATHING PANEL JOINTS ON EACH SIDE OF WALL MINIMUM ONE
STUD BAY.
6. SHEATHING PANELS MAY BE INSTALLED EITHER PARALLEL OR
PERPENDICULAR TO FRAMING.
7. SPACE FASTENERS @ 12" O.C. ALONG INTERMEDIATE FRAMING MEMBERS
(FIELD OF PANEL); SPACE FASTENERS @ 6" O.C. ALONG ALL EDGE FRAMING
MEMBERS (SUPPORTED EDGES) (U.O.N.).
8. EACH SHEATHING PANEL SHALL BE IDENTIFIED WITH THE GRADE
TRADEMARK OF THE AMERICAN PLYWOOD ASSOCIATION AND SHALL MEET
THE REQUIREMENTS OF PRODUCT STANDARD (psi). APPLICATION AND
NAILING OF PLYWOOD SHALL BE IN ACCORDANCE WITH THE
RECOMMENDATIONS OF THE AMERICAN PLYWOOD ASSOCIATION & TABLE
2304.10.1 "FASTENING SCHEDULE" OF THE INTERNATIONAL BUILDING CODE
UNLESS OTHER REQUIREMENTS NOTED ON THE PLAN ARE MORE STRICT.
16. DESIGN LOADS:
ROOF LIVE LOADS:
ROOF SNOW Pf = 26 psf.
IMPORTANCE FACTOR Is = 1.0
EXPOSURE FACTOR Ce = 1.0
THERMAL FACTOR Ct = 1.169 (R=30)
GROUND SNOW LOAD Pg =31 psf.
CONSTRUCTION LOADING 25 psf.
LIVE LOAD 20 psf.
DEAD LOADS
TYPICAL ROOF BCDL = 7 psf.
TCDL = 13 psf.
TYPICAL FLOOR DL = 20 psf.
FLOOR LIVE LOADS:
ADMINISTRATIVE SERVICES,
OFFICE AREAS
80 psf.
LIGHT STORAGE 125 psf.
PARTITIONS 20 psf.
LATERAL LOADS (WIND -
MSFRS)
IMPORTANCE FACTOR 1.0 Iw
ULTIMATE WIND SPEED (3 SECOND
GUST)
110 MPH.
NOMINAL WIND SPEED 85.2 MPH.
RISK CATEGORY II
WIND EXPOSURE "C"
INTERNAL PRESSURE COEFF +/- 0.18
COMPONENTS CLADDING BASE
PRESSURE
Qh = 27 psf.
LATERAL LOADS (SEISMIC
- MSFRS)
RISK CATEGORY II
SEISMIC IMPORTANCE FACTOR Ie = 1
MAPPED SPECTRAL RESPONSE Ss = 0.13
MAPPED SPECTRAL RESPONSE S1 = 0.073
DESIGN SPECTRAL RESPONSE Sds = 0.120
DESIGN SPECTRAL RESPONSE Sd1 = 0.100
SITE CLASS D
SEISMIC DESIGN CATEGORY B
SEISMIC FORCE RESISTING
SYSTEM
WOOD SHEARWALLS
DESIGN BASE SHEAR V = 0.017W
SEISMIC RESPONCE COEFFICIENT Cs = 0.017
RESPONSE MODIFICATION FACTOR R = 7
ANALYSIS PROCEDURE ELFA
ABBREVIATIONS & SYMBOLS:
+/- PLUS OR MINUS
@ AT
A.B. ANCHOR BOLT
A.P.A. AMERICAN PLYWOOD
ASSOCIATION
A.S.T.M. AMERICAN SOCIETY OF TESTING
MATERIALS
ARCH. ARCHITECTURAL
B.B. BOND BEAM
B.O. BOTTOM OF
BLK. BLOCK
BM. BEAM
BOT. BOTTOM
BRG. BEARING
C CHANNEL
C.M.U. CONCRETE MASONRY UNIT
CCJ CONSTRUCTION CONTROL JOINT
CJ CONTROL JOINT
CL. CENTER LINE
CLR. CLEAR
COL. COLUMN
CONC. CONCRETE
CONN. CONNECTION
CONT. CONTINUOUS
D.L. DEAD LOAD
D.T. DOUBLE TEE / DRAIN TILE
DBL. DOUBLE
DIA. DIAMETER
DIM. DIMENSION
DWL. DOWEL
E.F. EACH FACE
E.J. EXPANSION JOINT
E.W. EACH WAY
EA. EACH
EL. ELEVATION
ELEV. ELEVATOR
EQ. EQUAL
EX. EXISTING
EXC. EXCAVATION
EXP. EXPANSION
F.D. FLOOR DRAIN
FDN. FOUNDATION
FT. FEET
FTG. FOOTING
G.C. GENERAL CONTRACTOR
G.T. GIRDER TRUSS
GA. GAUGE
GALV. GALVANIZE
HC. HOLLOWCORE
HORIZ. HORIZONTAL
HSS HOLLOW STRUCTURAL SECTION
I.F. INSIDE FACE
INT. INTERIOR
JST. JOIST
KLF. KIPS PER LINEAR FOOT
KSI. KIPS PER SQUARE INCH
L ANGLE
LB LEDGER BEAM
LL LIVE LOAD / DOUBLE ANGLE
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG. LONGITUDINAL
LWC LIGHT WEIGHT CONCRETE
M.C. MECHANICAL CONTRACTOR
MAS. MASONRY
MAX. MAXIMUM
MECH. MECHANICAL
MFG. MANUFACTURER
MIN. MINIMUM
MISC. MISCELLANEOUS
MTL. METAL
N. NORTH
N.T.S. NOT TO SCALE
NS. NON-SHRINK
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
O.F. OUTSIDE FACE
O.H. OVERHEAD
OPNG. OPENING
ORIG. ORIGINAL
P.A.F. POWDER ACTUATED FASTENER
P.C. PRECAST CONCRETE
PART. PARTITION
PL. PLATE
PLF POUNDS PER LINEAR FOOT
PNL. PANEL
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PW PLYWOOD
R. OR
RAD.
RADIUS
R.D. ROOF DRAIN
REINF. REINFORCING
REQD. REQUIRED
S.A. STUD ANCHOR
S.B. SOIL BORING
S.D. SEE DETAIL
S.D.L. SUPERIMPOSED DEAD LOAD
S.E.R. STRUCTURAL ENGINEER OF
RECORD
S.L. SNOW LOAD
S.L.L. SUPERIMPOSED LIVE LOAD
S.S. STAINLESS STEEL
SCHED. SCHEDULE
SHT. SHEET
SIM. SIMILAR
SPA. SPACING / SPACES
SPECS. SPECIFICATIONS
SQ. SQUARE
STD. STANDARD
STL. STEEL
T & B TOP & BOTTOM
T & G TONGUE & GROOVE
T.M.L. TOP OF MASONRY LEDGE
T.O. TOP OF
T.O.B. TOP OF BEAM
T.O.J. TOP OF JOIST
T.O.S. TOP OF STEEL
T.O.W. TOP OF WALL
T.S.E. TOP OF STEEL ELEVATION
T.S.W. TOP OF STEM WALL
TEMP. TEMPORARY
THK. THICK / THICKENED
TRANS. TRANSVERSE
TYP. TYPICAL
U.O.N. UNLESS OTHERWISE NOTED
V. / VER. VERIFY
VERT. VERTICAL
W.L. WIND LOAD
W/ WITH
W/O WITH OUT
WD. WOOD
WTS. WEIGHTS
WWF WELDED WIRE FABRIC
DEFERRED SUBMITTAL SCHEDULE NOTES:
1. PREFABRICATED COMPONENTS OR SYSTEMS SPECIFIED ON THE STRUCTURAL
DRAWINGS TO BE DESIGNED BY OTHERS SHALL BE SUBMITTED BY THE
CONTRACTOR TO THE ARCHITECT OR ENGINEER OF RECORD FOR REVIEW AS A
DEFERRED SUBMITTAL. DEFERRED SUBMITTALS SHALL INCLUDE DRAWINGS
AND CALCULATIONS THAT HAVE BEEN STAMPED AND SIGNED BY AN ENGINEER
APPROPRIATELY LICENSED IN THE STATE OF CONSTRUCTION.
2. THE PURPOSE OF THE ENGINEER OF RECORD’S REVIEW SHALL BE
DETERMINING THAT THE DRAWINGS AND CALCULATIONS HAVE BEEN PROPERLY
SEALED, THAT THE LOAD CRITERIA IS IN GENERAL CONFORMANCE WITH THE
CONTRACT DOCUMENTS AND THE REFERENCED BUILDING CODE, AND THAT THE
CONNECTIONS TO THE PRIMARY STRUCTURE ARE APPROPRIATE FOR THE
STRUCTURE’S DESIGNED CAPABILITIES.
3. THE STRUCTURAL ENGINEER WILL RELY ON THE SPECIALTY ENGINEER’S SEAL
AS CERTIFICATION THAT THE ITEMS DESIGNED BY THE SPECIALTY ENGINEER
COMPLY WITH THE CRITERIA SET FORTH IN THE CONTRACT DOCUMENTS AND
APPLICABLE CODES AND STANDARDS. THE STRUCTURAL ENGINEER SHALL NOT
BE RESPONSIBLE FOR THE ADEQUACY OF DESIGNS PROVIDED BY OTHERS.
DEFERRED SUBMITTAL SCHEDULE:
PREFABRICATED WOOD TRUSSES
WINDOW GLAZING SYSTEMS
STAIRS, HANDRAILS, GUARDRAILS AND THEIR COMPONENTS
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
BID DOCUMENTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
OPTIONAL BID #1
400 5th St
West Des Moines, IA 50265
(515) 225-6265
900 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTECHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
JUNE 22, 2026
C U s e rs \J
B u e rm a n n \D o c u m e n ts \1
S
R
V T jb u e rm a n n S
R X
R
.r v t
/2
/2
:2
:3
A
M
1001-S-001
NOTE SHEET
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 EW DW/JB
BID DOCUMENTS
18704
Revisions: Date: Page 189 of 247
1 2 3 4 5 6
A
B
C
D
E
F
G
H
D.1
2.1 3.1 4.1 5.1
9'
4" 9'
4"
9'
4" 8'
1/ 4"
3/
4" 9'
4"
/4
5'
0" 20' - 4 1/4" 6 1/2" 20' - 2 1/4" 6 1/2" 22' - 11 1/2" 6" 20' - 10" 6" 20' - 8"
107' - 1"
3/
4"
FC2.5
8"
4"
1001-S-301
4"
8"
FC2.5
FC2.5
1001-S-301
8" 4"
8 3/4" 1' - 3 1/4"
4"
8"
FC2.5
1001-S-301
FC2
1001-S-301
FC2.5
1001-S-301
4" 8"
1001-S-301
________________________________________________________________________________ 4"
8"
1001-S-301
1001-S-301
8" 4"
1001-S-301
4"
10"
4" CONC. SLAB, REINF. W/ #4 @ 1'-6" EACH WAY,
ON 12 MIL. (MIN.) VAPOR BARRIER ON 6" SAND FILL
T.O. SLAB EL. = 100'-0" U.O.N.
4" 10"
(E) 4x4
FTG.
10" 4"
10"
10"
10"
FC2.5
4" 8"
4"
8"
FC2.5
(E) 4x4
FTG.
4" 10"
10" 4"
4"
10"
10" 4"
4"
10"
8"
4"
10"
4" 10"
FC2.5
FC2.5
FC2.5
FC11TB
FC2.5
T.O. (E) FTG.
EL. = 90' - 11"
T.O. (E) FTG.
EL. = 90' - 11"
T.O. (E) FTG.
EL. = 90' - 11"
T.O. (E) FTG.
EL. = 90' - 11"
T.O. (E) FTG.
EL. = 90' - 11"
S
S
(E)
(E)
T.O. (E) FTG.
EL. = 90' - 11"
T.O. (E) FTG.
EL. = 88' - 11"
T.O. (E) FTG.
EL. = 90' - 11"
(E) 4x4
FTG.
4" CONC. SLAB, REINF. W/ #4 @ 1'-6" EACH WAY,
ON 12 MIL. (MIN.) VAPOR BARRIER ON 6" SAND FILL
T.O. SLAB EL. = 100'-0" U.O.N.
10"
10"
4"
10"
T.O. (E) FTG.
EL. = 96' - 1 1/2"
T.O. (E) FTG.
EL. = 96' - 1 1/2"
S(E)
T.O. (E) FTG.
EL. = 94' - 1 1/2"
T.O. (E) FTG.
EL. = 94' - 1 1/2"
4" CONC. SLAB, REINF. W/ #4 @ 1'-6" EACH WAY,
ON 12 MIL. (MIN.) VAPOR BARRIER ON 6" SAND FILL
T.O. SLAB EL. = 100'-0" U.O.N.
10"
4"
(E) 4x4
FTG.
T.O. EXISTING SLAB EL. = 91'-6 5/8"
T.O. (E) FTG.
EL. = 88' - 11"
10"
T.O. EXISTING SLAB EL. = 100'-0"
S(E)
5'
4"
5' - 0"
8"
FC1.7
4" 8"
T.O. LEDGE
EL. = 98' - 10"
T.O. LEDGE
EL. = 98' - 10"
T.O. LEDGE
EL. = 98' - 10"
T.O. LEDGE
EL. = 99' - 4"
L
L
SSS
T.O. LEDGE
EL. = 98' - 10"
T.O. LEDGE
EL. = 99' - 4"
T.O. LEDGE
EL. = 99' - 4"
T.O. FTG.
EL. = 95' - 6"
T.O. FTG.
EL. = 94' - 11"
T.O. FTG.
EL. = 92' - 11"
T.O. FTG.
EL. = 90' - 11"
T.O. FTG.
EL. = 90' - 11"
T.O. LEDGE
EL. = 96' - 11"
T.O. FTG.
EL. = 90' - 11"
T.O. (E) FTG.
EL. = 90' - 11"
T.O. (E) FTG.
EL. = 94' - 1 1/2"
8" 4"
8"
4"
S S S
T.O. LEDGE
EL. = 99' - 4"
T.O. LEDGE
EL. = 99' - 4"
T.O. FTG.
EL. = 90' - 11"
T.O. FTG.
EL. = 92' - 11"
T.O. FTG.
EL. = 94' - 11"
5'
0"
FC1.75' - 0"
8"
5'
0"
5' - 0"
FC1.7
S
S
S
T.O. LEDGE
EL. = 99' - 4"
T.O. FTG.
EL. = 95' - 6"
T.O. FTG.
EL. = 94' - 11"
T.O. FTG.
EL. = 92' - 11"
T.O. FTG.
EL. = 90' - 11"
BP1
T.O. (E) FTG.EL. = 96' - 11"
T.O. LEDGE
T.O. FTG.
EL. = 95' - 6"
T.O. LEDGE
EL. = 98' - 10"
1001-S-301
FS6.5TB
BP2
P1
2"
9 1/2"
HD2
L1
8" 5' - 0" 10"
STAIR
10"
1001-S-301
L1
BP1
FS3
P2
FS3
P3
BP5
BP4
HD1
HD1
HD3
HD2
HD2
HD3
HD3
HD2
HD3
HD3
HD3
HD3
HD3
HD3
HD3 HD3
6'
8" 3'
6"
FC2.5
S
T.O. FTG.
EL. = 89' - 3"
1001-S-302
S8
1001-S-301
8" 8"
8"
1001-S-302
1001-S-301
1001-S-302
8"
8"
1001-S-301
L1
8"
1001-S-301
6'
7"2' - 6"
1'
7"
2' - 6"
T.O. FTG.
EL. = 97' - 0"
S
S
S
T.O. FTG.
EL. = 94' - 11"
T.O. FTG.
EL. = 92' - 11"
T.O. FTG.
EL. = 90' - 11"
8A
8A
3"
3"
3"
3"
3"
3"
3"
3"9 1/
2"
4 1/2"
2"
3"
BP1
BP1
BP3
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
BID DOCUMENTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
OPTIONAL BID #1
400 5th St
West Des Moines, IA 50265
(515) 225-6265
900 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTECHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
JUNE 22, 2026
C U s e rs \J
B u e rm a n n \D o c u m e n ts \1
S
R
V T jb u e rm a n n S
R X
R
.r v t
/2
/2
:2
:3
A
M
1001-S-101
FOOTING & FOUNDATION PLAN
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 EW DW/JB
BID DOCUMENTS
18704
KEYNOTES:
1 FOOTING CONNECTION DETAIL - S.D. 10/1001-S-301
2 DRILL & EPOXY EXISTING FOOTING INTO NEW FOOTING W/ 2 - #5
DWLS. EMBED = 6"
3 DRILL & EPOXY EXISTING FOUNDATION WALL INTO NEW FOUNDATION
WALL W/ #5 DWLS. @ 1'-4" O.C. EMBED = 6"
4 RAISED EQUIPMENT PAD - COORDINATE FINAL SIZE AND LOCATION
WITH MEP DRAWINGS - S.D. 19/1001-S-301
5 WALL PENETRATION. COORDINATE FINAL LOCATION WITH MEP.
6 INFILL EXISTING BRICK LEDGE WITH CONCRETE - S.D. 18/1001-S-301
7 NEW FOOTING TO EXISTING FOOTING CONNECTION DETAIL - S.D.
7/1001-S-302
1. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
2. SEE SHEET 1001-S-001 FOR GENERAL STRUCTURAL NOTES.
3. P# = PIER MARK - SEE PIER SCHEDULE ON THIS SHEET.
4. BP# = BASE PLATE MARK - SEE BASE PLATE SCHEDULE ON THIS SHEET.
5. FC/S/T# = FOOTING MARK - SEE FOOTING SCHEDULE ON THIS SHEET.
6. HD# = HOLDOWN MARK - SEE HOLDOWN SCHEDULE ON THIS SHEET.
7. = STEPPED FOOTING LOCATION - S.D. 1/1001-S-301.
8. ADMIN BUILDING FIRST LEVEL FINISH FLOOR ELEVATION (FFE) = 100'-0"
UNO ON PLAN REFERENCED FROM DATUM ELEVATION 854.2'. VERIFY
WITH CIVIL.
9. = STEPPED BRICK LEDGE LOCATION - S.D. 8/1001-S-301
10. COORDINATE EXTENT OF SLAB REMOVAL WITH MEP PLANS. REMOVE &
REPLACE CONCRETE SLAB ON GRADE AND EXCAVATE FOR PLUMBING AS
REQUIRED. IF DEEP TRENCHES ARE REQUIRED, CONTRACTOR SHALL
ASSUME MINIMUM OF 4 FOOT WIDE SLAB REMOVAL AND TRENCH WIDTHS.
CONTRACTOR SHALL USE TRENCH BOXES OR HAND SHORING TO
PREVENT SOIL STABILITY CONCERNS & OVER EXCAVATION. IF BOTTOM
OF TRENCH IS LOWER THAN BOTTOM OF ANY EXISTING FOOTINGS IT
NEEDS TO BE A MINIMUM OF 2:1 SLOPE AWAY FROM BOTTOM EDGE OF
EXISTING FOOTING. SEE DETAIL 15/1001-S-301 FOR CONCRETE SLAB
REPLACEMENT.
11. L# = LINTEL MARK - SEE LINTEL SCHEDULE ON THIS SHEET.
SHEET NOTES:
S
1/4" = 1'-0"
FOOTING & FOUNDATION PLAN
T.O. INT. FOOTING EL. = 99'-4"
T.O. EXT. FOOTING EL. = SEE PLAN 0 4' 8'2'
Schedule Notes - Pier
MARK PIER SIZE COMMENTS
P1 3'-0" x 3'-0" S.D. 3/S-302
P2 2'-0" x 1'-5 1/2" S.D. 4/S-302
P3 2'-0" x 1'-6" S.D. 4/S-302
Schedule - Base Plate
MARK PLATE SIZE ANCHOR BOLTS COMMENTS
BP1 PL. 3/4" x 7 1/2" x 7 1/2" 3 - 3/4" DIA. S.D. 1/S302 & 2/S302
BP2 PL. 1" x 1'-2" x 1'-2" 4 - 3/4" DIA. S.D. 1/S302
BP3 PL. 3/4" x 1'-2" x 1-0" 4 - 3/4" DIA. S.D. 1/S302
BP4 PL. 3/4" x 10" x 7 1/2" 4 - 3/4" DIA. S.D. 1/S302 & 2/S302
BP5 PL. 3/4" x 10" x 7 1/2" 4 - 3/4" DIA. S.D. 1/S302
Schedule - Footings
MARK WIDTH DEPTH
REINFORCING
COMMENTS
TRANSVERSE LONGITUDINAL
FC1.7 1'-8" CONT. 1'-0" --- 2 - #5
FC2 2'-0" CONT. 1'-0" #5 @ 6'-0" O.C. 2 - #5
FC2.5 2'-6" CONT. 1'-0" #5 @ 6'-0" O.C. 2 - #5
FC11TB 11'-0" CONT. 1'-4" #6 @ 1'-0" O.C. 11 - #5 T&B
FS3 3'-0" x 3'-0" 1'-0" 5 - #5 5 - #5
FS6.5TB 6'-6" x 6'-6" 1'-0" 8 - #5 8 - #5 T&B
Schedule - Holdowns
MARK HOLDOWN TYPE
ANCHOR
POST SIZE
ANCHOR
BOLT SIZE
"E" MINIMUM
EMBED DEPTH
COMMENTS
HD1 SIMPSON "HDUE13-SDS3.5" 3 - 2x6 1" DIA. 2'-4" S.D. 16/S-301
HD2 SIMPSON "HDUE9-SDS3.5" 3 - 2x6 7/8" DIA. 2'-0" S.D. 16/S-301
HD3 SIMPSON "HDUE5-SDS3" 3 - 2x6 5/8" DIA. 8" S.D. 16/S-301
HD4 SIMPSON "HDUE5-SDS3" 3 - 2x6 5/8" DIA. - S.D. 10/S-402
FOOTING SCHEDULE NOTES:
1. FC/S/T#TB DESIGNATES REINFORCING STEEL TO BE AT TOP & BOTTOM OF FOOTING.
HOLDOWN SCHEDULE NOTES:
1. ALL ANCHOR POSTS TO BE SPF. #2 GRADE U.O.N.
2. ALL "HD" HOLDOWN ANCHOR BOLTS MAY BE INJECTION ADHESIVE ANCHORS U.O.N.
3. ANCHOR BOLT NUTS TO BE SNUG TIGHT PLUS 1/2 TURN.
4. PROVIDE 3" x 3" x .229" WASHER BETWEEN SILL PLATE & NUT @ ALL HOLDOWN ANCHORS.
L
Schedule - Lintel
MARK LINTEL / VENEER LINTEL COMMENTS
L1 2 - L 5x5x3/8" w/ 1/4" PL. S.D. 17/S301
Revisions: Date:
LINTEL SCHEDULE NOTES:
1. ALL LINTELS TO HAVE 8" BEARING MINIMUM @ EACH END.
1 2 3 4 5 6
A
B
C
D
E
F
G
H
D.1
2.1 3.1 4.1 5.1
9'
4" 9'
4"
9'
4" 8'
1/ 4"
3/
4" 9'
4"
/4
5'
0"
20' - 4 1/4" 6 1/2" 20' - 2 1/4" 6 1/2" 22' - 11 1/2" 6" 20' - 10" 6" 20' - 8"
107' - 1"
3/ 4" (E
)C
OL.
(E)W8x21
(E)W8x21
(E )C
OL.
(E )W
X
4" CONC. SLAB, REINF. W/ #4 @ 1'-6" EACH WAY,
ON 12 MIL. (MIN.) VAPOR BARRIER ON 6" SAND FILL
T.O. SLAB EL. = 100'-0" U.O.N.
JOISTS @ 1'-4" O.C.
(E) 2x12 FLOOR
4" CONC. SLAB, REINF. W/ #4 @ 1'-6" EACH WAY,
ON 12 MIL. (MIN.) VAPOR BARRIER ON 6" SAND FILL
T.O. SLAB EL. = 100'-0" U.O.N.
4" CONC. SLAB, REINF. W/ #4 @ 1'-6" EACH WAY,
ON 12 MIL. (MIN.) VAPOR BARRIER ON 6" SAND FILL
T.O. SLAB EL. = 100'-0" U.O.N.
1001-S-401
HD4
1001-S-301
1001-S-302
1001-S-302
1001-S-302
1001-S-302
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
BID DOCUMENTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
OPTIONAL BID #1
400 5th St
West Des Moines, IA 50265
(515) 225-6265
900 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTECHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
JUNE 22, 2026
C U s e rs \J
B u e rm a n n \D o c u m e n ts \1
S
R
V T jb u e rm a n n S
R X
R
.r v t
/2
/2
:2
:3
A
M
1001-S-102
FIRST FLOOR FRAMING PLAN
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 EW DW/JB
BID DOCUMENTS
18704
1. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
2. SEE SHEET 1001-S-001 FOR GENERAL STRUCTURAL NOTES.
3. HD# = HOLDOWN MARK - SEE HOLDOWN SCHEDULE ON THIS 1001-S-101.
4. ADMIN BUILDING FIRST LEVEL FINISH FLOOR ELEVATION (FFE) = 100'-0"
UNO ON PLAN REFERENCED FROM DATUM ELEVATION 854.2'. VERIFY
WITH CIVIL.
5. ALL EXISTING 2x12 BLOCKING AT FIRST FLOOR FRAMING END WALLS SHALL BE ATTACHED TO EXISTING 2x PLATE W/ 2-SIMPSON "A34" CLIPS - S.D. 11/1001-S301 & 8/1001-S-302
6. ALL EXISTING 2x12 FLOOR JOISTS AT FIRST FLOOR FRAMING BEARING WALLS SHALL BE ATTACHED TO EXISTING 2x PLATE W/ 2-SIMPSON "A34"
CLIPS - S.D. 9/1001-S-302 & 10/S1001-S-302
SHEET NOTES:
1/4" = 1'-0"
FIRST FLOOR FRAMING PLAN
0 4' 8'2'
KEYNOTES:
1 EXISTING FLOOR PENETRATION TO BE INFILLED WITH 2x12 FLOOR
JOISTS @ 1'-4" O.C. - S.D.11/1001-S-402
Revisions: Date: Page 191 of 247
T.O. (E) STEEL
EL. = 109' - 4 1/2"
1 2 3 4 5 6
A
B
C
D
E
F
G
H
D.1
2.1 3.1 4.1 5.1
5'
0"
/4
9'
4"
3/
4" 8'
1/ 4"
9'
4" 9'
4"
9'
4"
20' - 4 1/4" 6 1/2" 20' - 2 1/4" 6 1/2" 22' - 11 1/2" 6" 20' - 10" 6" 20' - 8"
RIDGE
RIDGE
RIDGE
RIDGE
3/ 4"
107' - 1"
ROOF TRUSSES @ 2'-0" O.C.
1001-S-401
1001-S-401
1001-S-401
1001-S-401
H
H
H
H1 H1 H1
H
H1 H1 H1
H4 H4
1001-S-401
1001-S-401
1001-S-401
1001-S-401
C2
C1C1
HSS8X8X5/8
1001-S-401
C2 W8x21
(E )C
OL.
(E )C
OL.
(E)W8x18
(E) RIDGE
(V E
R
IF
Y
4'
5"
5'
3/
4"
1001-S-401
H1
H
ROOF TRUSSES @ 2'-0" O.C.
(E) ROOF TRUSSES @ 2'-0" O.C.
C2
C2 W8x40
C2C2
1001-S-401
1001-S-401
W8x40
1001-S-401
1001-S-401
9 1/2"
10"
4'
8"
ROOF TRUSSES @ 2'-0" O.C.
(E) RIDGE
(E) ROOF TRUSSES @ 2'-0" O.C.
RIDGE
ROOF TRUSSES @ 2'-0" O.C.
(E) ROOF TRUSSES @ 2'-0" O.C.
(E) RIDGE
4'
8"
(E) (4)-2x8 (E) (4)-2x8 (E) (4)-2x8 (E) (4)-2x8 (E) (4)-2x8
H
1001-S-401
H
H
1001-S-401
3" 3"
3"
3"
1001-S-401
3"
1001-S-401
(VERIFY)
SW1
SW1
SW2
SW1
SW1
SW1
SW1
SW2
SW1
SW1
H1
3"
SW3
SW1
1001-S-401
2"
H
1001-S-402
H
1001-S-402
1001-S-402
1001-S-402
1001-S-402
1001-S-402
1001-S-402
1001-S-402
1001-S-402
1001-S-402
H
1001-S-401
1001-S-402
H
1001-S-402
SW1
SW1
SW1
SW1
SW1
4 1/2"
C3 C3
C3
1001-S-402
2"
3"
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
BID DOCUMENTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
OPTIONAL BID #1
400 5th St
West Des Moines, IA 50265
(515) 225-6265
900 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTECHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
JUNE 22, 2026
C U s e rs \J
B u e rm a n n \D o c u m e n ts \1
S
R
V T jb u e rm a n n S
R X
R
.r v t
/2
/2
:2
:3
A
M
1001-S-201
ROOF FRAMING PLAN
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 EW DW/JB
BID DOCUMENTS
18704
1. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
2. SEE SHEET 1001-S-001 FOR GENERAL STRUCTURAL NOTES.
3. B# / H# - BEAM / HEADER MARK - SEE BEAM / HEADER SCHEDULE ON THIS
SHEET.
4. SW# - SHEAR WALL TYPE MARK (BELOW) - SEE SHEARWALL SCHEDULE
ON THIS SHEET.
5. C# - COLUMN MARK - SEE COLUMN SCHEDULE ON THIS SHEET.
6. ALL FIRST FLOOR STRUCTURAL BEARING "EXTERIOR" STUD WALLS SHALL
BE SPF #2 OR BETTER @ 1'-4" O.C. (U.O.N.) WITH SPF #2 DOUBLE TOP
PLATE & SOLE PLATE.
7. ROOF SHEATHING TO BE 1/2" APA RATED SHEATHING WITH A 32/16 SPAN
RATING.
8. = MOMENT CONNECTION - S.D. 4/1001-S-401
9. WHERE NEW WALL FRAMING TIES INTO EXISTING WALL FRAMING, STUDS
SHALL BE FASTENED TOGETHER WITH ONE ROW OF STAGGERED 10D
NAILS @ 6" ON CENTER FROM BOTH SIDES. PROVIDE SIMPSON "CS16"
STRAP x 2'-4" LONG @ DOUBLE TOP PLATE TO TIE EXISTING WALL TO NEW
WALL.
SHEET NOTES:
1/4" = 1'-0"
ROOF FRAMING PLAN
T.O. STEEL EL. = 109'-1 1/2" (FIELD VERIFY)
0 4' 8'2'
Schedule - Beams & Headers
MARK BEAM / HEADER SIZE
JACK
STUD #
KING
STUD #
COMMENTS
H1 2-2x8 2 1 S.D. 2/S-401
H2 2 - 2x8 2 1 S.D. 12/S-401
H3 3 - 2x8 2 1 S.D. 12/S-401 & 12/S-402
H4 2-2x8 2 1 S.D. 2/S-401 & 13/S-402
Schedule - Shearwall
MARK SHEATHING # OF SIDES PERIMETER NAILING ANCHOR BOLT FASTENING
SW1 7/16" RATED 1 0.131" x 2 1/2" @ 6" O.C. 5/8" DIA. @ 4'-0" O.C.
SW2 7/16" RATED 1 0.131" x 2 1/2" @ 3" O.C. 5/8" DIA. @ 2'-0" O.C.
SW3 7/16" RATED 2 0.131" x 2 1/2" @ 4" O.C. 5/8" DIA. @ 1'-0" O.C.
Schedule - Columns
MARK COLUMN TYPE COMMENTS
C1 HSS8x8x5/8 S.D. 4/S-401
C2 HSS4x4x1/4" S.D. 3/S-401
C3 4x6 WOOD POST S.D. 13/S-402
SHEARWALL SCHEDULE NOTES:
1. FASTENERS SHALL BE A MINIMUM 0.131" DIA. x 2 1/2" COMMON OR GALVANIZED (HOTDIPPED) BOX
NAILS.
2. BACK ALL PANEL EDGES WITH 2x BLOCKING MINIMUM.
3. GYPSUM & RATED SHEATHING PANEL EDGES TO BE FASTENED AS NOTED. INTERMEDIATE
SUPPORTS SHALL BE FASTENED @ 1'-0" O.C.
4. WHERE PANELS ARE APPLIED ON 2 - SIDES OF WALL PANEL JOISTS SHALL BE OFFSET TO FALL
ON DIFFERENT FRAMING MEMBERS. ALTERNATIVLEY WHERE PANEL JOINTS CAN NOT BE
STAGGERED THE WIDTH OF THE FACE OF FRAMING MEMBERS SHALL BE 3" NOMINAL OR
GREATER AT ADJOINING PANEL EDGES WITH PANEL EDGE NAILING STAGGERED.
5. 7/16" RATED SHEATHING SHALL BE EXPOSURE NO.1, WITH A 24/16 SPAN RATING. 19/32" RATED
SHEATHING SHALL BE EXPOSURE NO. 1, WITH A 40/20 SPAN RATING.
6. SHEATHING TO EXTEND FROM THE FLOOR TO THE FLOOR OR ROOF SHEATHING ABOVE.
7. ANCHOR BOLTS FOR SHEARWALLS SHALL BE SIMPSON "TITEN HD" SCREW ANCHORS WITH A
MINIMUM OF 3 1/4" EMBED U.O.N.
8. 2x6 WALLS SHALL HAVE SIMPSON "BPS 5/8-6" BEARING PLATE WASHER AT EACH ANCHOR BOLT.
2x4 WALLS SHALL HAVE SIMPSON "BPS 5/8-3" BEARING PLATE WASHER AT EACH ANCHOR BOLT.
Revisions: Date: Page 192 of 247
T.O. LEDGE
EL. = VARIES;
T.O. (E) BRICK LEDGE
EL. = VARIES (VERIFY)
T.O. WALL
EL. = SEE ARCH/CIVIL
T.O. OPENING
EL. = SEE ARCH
SEE SCHED.
LAP SPLICE2a U.O.N.
a
SEE PLAN
3" CLR. - TYP.
DEPTH 1'-0" MIN.
EQUAL TO FTG.
2a U.O.N.
NOTES:
1. SEE PLAN FOR FOOTING SIZE AND REINFORCING.
2. SLOPED OR STEPPED FOOTINGS SHALL BE CAST AS A UNIT.
3. STEPPED FOOTING LINES SHOWN ON PLAN ARE @ BOTTOM OF FOOTING.
NOTE:
IF WALL SURFACE IS SOIL LOADED EXTEND HORIZONTAL BARS TO OPPOSITE FACE & PROVIDE STANDARD HOOK.
SIZE & REINF.
SEE PLAN FOR
3 - #4 VERT. W/ DWL.
TO MATCH @ FOOTING.
CORNER BARS TO
MATCH SIZE &
SPACING OF HORIZ.
WALL REINF.
SIZE & REINF.
SEE PLAN FOR
CORNER BARS
TO MATCH SIZE
& SPACING OF
HORIZ. WALL
REINF.
S E
E S
C H
E D
LA
P
S P
LI
C
E
1 1/2" CLR. - U.O.N.
SIZE & REINF.
SEE PLAN FOR
VERT. W/ DWL. TO
MATCH @ FOOTING.
CORNER BARS TO
MATCH SIZE &
SPACING OF HORIZ.
WALL REINF.
S E
E S
C H
E D
LA
P
S P
LI
C
E
1 1/2" CLR. - U.O.N.
S E
E S
C H
E D
LA
P
S P
LI
C
E
1 1/2" CLR. - TYP.
NOTE:
CONST. JOINT SHOWN MAY BE OMITTED @ CONTRACTOR'S OPTION.
SIZE & REINF.
SEE PLAN FOR
2" x 4" x 6" LONG.
VERT. KEYWAY
EVENLY SPACED
BETWEEN HORIZ.
REINF. SPACING
DWL. W/ STANDARD
HOOK TO MATCH
SIZE & SPACING OF
HORIZ. REINFORCING2" CLR. - TYP.
S E
E S
C H
E D
LA
P
S P
LI
C
E
2" x 6" x 6" LONG.
VERT. KEYWAY
EVENLY SPACED
BETWEEN HORIZ.
REINF. SPACING
DWL. W/ STANDARD
HOOK TO MATCH
SIZE & SPACING OF
HORIZ. REINFORCING
SIZE & REINF.
SEE PLAN FOR
2" CLR. - TYP.
S E
E S
C H
E D
LA
P
S P
LI
C
E
NOTE:
JOINT MAXIMUM SPACING 40'-0". SPACING MAY BE INCREASED TO 80'-0"
IF WALL IS BACKFILLED INTERIOR SIDE FOR FULL HEIGHT OR 120'-0" IF
WALL IS BACKFILLED ON BOTH SIDES FOR FULL HEIGHT.
1"
1/2"
S
IZ
E
R E
IN
F
S E
E P
LA
N
F O
R
1 1/2"
6" 6"
SEE SCHED.
LAP SPLICE3" CLR.
VERT. CAULK JOINT
@ EACH FACE
2" x 4" x 6" LONG. VERT. KEYWAY
EVENLY SPACED BETWEEN
HORIZ. REINF. SPACING.
KEYWAY CONT. WHERE
WATERSTOP IS REQUIRED
VERT. CAULK
VERT. ROD STOCK
WATERSTOP
WHERE
REQUIRED
NOTE:
SAW CUT SHALL BE EXECUTED AS SOON AS CONCRETE HAS HARDENED
SUFFICIENTLY TO PREVENT AGGREGATE DISLODGING BY SAW & PRIOR
TO SHRINKAGE STRESS CRACKING.
SLAB ON GRADE
SEE PLAN
1/4 SLAB DEPTH
3/16" SAW CUT OR TOOL
JOINT IN EXPOSED SLAB
OPENING
2 - #5 DWL. @ EACH
LAYER OF REINFORCING,
TYP. @ PERIMETER
2 - #5 DWL. x 3'-0"
@ EACH LAYER
OF REINFORCING,
TYP. @ CORNERS
1 1/2" CLR.
TYP.
1'
T Y
P
3" O.C.
TYP.
NOTES:
1. WHERE SLAB ON GRADE EXTENDS BEYOND STOOP SLAB HOLD STOOP SLAB
BACK 2" AND PROVIDE 3/4" DIA. x 1'-6" SMOOTH ROD @ 1'-0" O.C. PROVIDE
SLEEVE FOR ROD OR WRAP & TAPE WITH BUILDING FELT.
2. PROVIDE L4x4x1/4" W/ 1/2" DIA. SCREW ANCHORS @ 1'-0" O.C. (2 - ANCHORS MIN.), EMBED 3 1/2" MIN. WHERE DECK IS UNSUPPORTED FOR MORE THAN 1'-0".
3" CLR.
TYP.
DWL. TO MATCH @
EACH VERT. TYP.
4 @ 1'-0" O.C.
EACH WAY
8"
#4 DWL. 9" x 15" @
2'-0" O.C. TYP.
S.D. NOTE 1
CONC. SLAB OVER 1 1/2", TYPE "C", 20 GA.
(GALV.) DECK W/ 3" BRG. @ EACH END,
OVER 3" VOID. REINF. W/ 4 @ 1'-0" O.C.
EACH WAY. SLOPE SLAB 1/4"/FOOT. MIN -
SEE CIVIL
SEE PLAN
EQEQ
SEE PLAN FOR
FOOTING SIZE,
REINF. & ELEV. TYP.
SEE PLAN FOR
WALL SIZE &
REINFORCING
BOND BREAK
SLAB ON GRADE
SEE PLAN
WALL BEYOND
SEE PLAN
5 1/2"
S.D. NOTE 2 BOND BREAK
2x TREATED PLATE W/ 5-8" DIA. SIMPSON
"TITEN-HD" SCREW ANCHORS @ 4'-0" O.C.,
EMBED 3 1/4" MINIMUM, U.O.N. IN SHEAR
WALL SCHEDULE
SLAB ON GRADE SEE
PLAN
#5 @ 1'-4" O.C.
EACH WAY,
EACH FACE
SEE PLAN FOR
FOOTING SIZE,
REINF. & ELEV.
DWL. TO MATCH @
EACH VERT.
SEE ARCH.
2x STUD WALL
SEE PLAN
4"
1' - 0"
3" CLR. - TYP.
TYP.
1 1/2" CLR.
SEE PLAN
GRID
5 1/2"
#4 DOWEL @
1'-4" O.C. @ 8A
SLAB ON GRADE SEE
PLAN
1'-0" 1'-0"
2x TREATED PLATE W/ 5/8" DIA.
SIMPSON "TITEN-HD" SCREW
ANCHORS @ 4'-0" O.C., EMBED 3
1/4" MINIMUM, U.O.N. IN SHEAR
WALL SCHEDULE
2x STUD WALL SEE
PLAN
BENT DWL. SEE
PLAN 3" CLR. - TYP.
8"
SEE PLAN FOR FOOTING SIZE,
REINF. & ELEV.
GRID
2x STUD WALL
SEE PLAN
SEE PLAN FOR
WALL SIZE &
REINFORCING
SEE PLAN FOR
FOOTING SIZE,
REINF. & ELEV.
SLAB ON GRADE SEE
PLAN
INTERIOR FTG. - S.D. 9/S-301
#5 HORIZONTAL @ 1'-4" O.C.
2 - #5 VERT., DRILL & EPOXY
INTO FOOTING, 6" MINIMUM
EMBED
8" MIN. x FTG. WIDTH
1'
8"
NOTE:
CONTRACTORS OPTION: CONCRETE PIER MAY BE REPLACED
WITH C.M.U. W/ #5 DWL. @ EACH CORE, 6" MIN. EMBED INTO
FOOTING.
#5 DWL. @ EACH VERT.
SLAB ON GRADE
SEE PLAN
(E) 5/8" FLOOR
SHEATHING
(E) 2x STUDWALL
(E) 2x12 BLOCKING
GRID
4" 6" 4"
(E) 2x12 FLOOR JOIST
EXISTING FOUNDATION WALL
BOND BREAK
5 1/2"
S.D. 18/S301 FOR BRICK
LEDGE INFILL DETAIL & NOTE 1
2-SIMPSON "A34" CLIPS @ EA.
2x12 BLOCKING - INSTALL W/ # 9 x 1 1/2" SD SCREWS
2x4 VERT. W/ 8 - 0.148" DIA. x 3" NAILS @ EA. (E) 2x12 BLOCKING
(E) 2x PLATE
(E) WALL SHEATHING
NOTE:
1. TOP #4 DWL. EMBED INTO (E) FDN WALL
SHALL BE 4"
#4 BENT DOWEL
6" 6"
SLAB ON GRADE
SEE PLAN "A"
3/16" SAW CUT OR TOOL JOINT
IN EXPOSED SLAB. FILL WITH
POURABLE SEALANT
4"
3/4" DIA. X 1'- 1" SMOOTH DOWEL
@ 1'-0" O.C. GREASE ONE END.
NOTE:
DIM. "A" = 1" FOR 4" SLABS, 1 1/4" FOR 5" SLABS, & 1 1/2" FOR 6" SLABS
STEEL COLUMN & BASE
PLATE
SEE PLAN
CONSTRUCTION JOINT
S.D. 12/S-301 FORM
DURING CONST. OF
SLAB ON GRADE.
WOOD FORM TYP.
SLAB ON GRADE
SEE PLAN
2" CLR. MIN.
@ STEEL COLUMN
GRID
GRID
BOND BREAK - TYP.
#5 @ 1'-4" O.C.
EACH WAY
TYPICAL
SEE PLAN FOR
FOOTING SIZE,
REINF. & ELEV.
TYPICAL
DWL. TO MATCH
@ EACH VERT.
TYPICAL
#4 @ 1'-4" O.C.
EACH WAY
#4 DWL. @ 1'-4" O.C.
GRANULAR FILL
CONSTRUCTION JOINT S.D. 12/S-301
SLAB ON GRADE
SEE CIVIL
3" CLR. - U.O.N.
8"
8"
V E
R
IF
Y
#4 DWL. @ 1'-4" O.C.
8" VERIFY
#3 @ EACH NOSING
6"
3" CLR.
1" CLR. - TYP.
#5 VERTICALS @
1'-4" O.C. EACH FACE
#6 HORIZONTALS @
1'-0" O.C. EACH FACE
10"
L4x4x1/4" W/ 1/2" DIA.
SCREW ANCHORS @ 1'-0"
O.C. - EMBED = 3 1/2" MIN.
2 1/2" CONC. OVER 1 1/2", (4"
TOTAL THICKNESS) TYPE "C", 20
GA. (GALV.) DECK W/ 3" BRG. @
EACH END, OVER 3" VOID,
REINF. W/ WWR 4x4 W2.9xW2.9.
SLOPE SLAB 1/4"/FOOT MIN. TO
DRAIN - SEE CIVIL
8"
HANDRAIL AND POST
ATTACHMENT BY OTHERS -
POSTS @ 4'-0" O.C. MAX
SLAB ON GRADE -
SEE CIVIL
DWL. TO MATCH @
EACH VERT.
INFILL AND REPLACE CONCRETE SLAB ON GRADE
AND REINF. W/ #4 @ 1'-0" O.C. EACH WAY
NOTES: 1. SEE PLUMBING DRAWINGS FOR EXACT PLUMBING LOCATIONS
2. SEE STANDARD SPECIFICATION FOR BACK FILL AND
COMPACTION REQUIREMENTS
HOLDOWN SEE
PLAN AND
SCHEDULE
HOLDOWN ANCHOR
SEE PLAN AND
SCHEDULE
BOND BREAK
TYPICAL
SLAB ON GRADE
SEE PLAN
@ MID. FDN. WALL
1/
2"
D E
P T
H "E
- E
M B
E D
ANCHOR POST SEE PLAN
AND SCHEDULE
2x NON-
TREATED PLATE
SLAB ON GRADE SEE
PLAN
"E" - EMBED DEPTH
8"
SEE PLAN FOR FOOTING SIZE,
REINF. & ELEV.
HOLDOWN SEE
PLAN AND
SCHEDULE
HOLDOWN ANCHOR
SEE PLAN AND
SCHEDULE
ANCHOR POST SEE PLAN
AND SCHEDULE
2x NON-
TREATED PLATE
@ INT. FDN. WALL
(E) 2x STUD WALL
STEEL LINTEL
SEE PLAN
(E) 2x FLOOR JOIST
PL. 1/4" x 1'-0"
(E) FOUNDATION WALL
VERIFY
VERIFY
1' - 0"
(E) FLOOR SHEATHING
3/16 3-12
TYP.
(E) 2x STUD WALL
INFILL EXISTING
BRICK LEDGE W.
CONC.
(E) 2x FLOOR JOIST
(E) FOUNDATION WALL
VERIFY4" 1' - 0"
(E) FLOOR SHEATHING
E M
B E
D
EMBED
#4 VERTS @ 1'-4" O.C. DRILL
& EPOXY INTO (E) FDN WALL
EMBED=6"
#4 BENT DOWEL @ 1'-4" O.C.
DRILL & EPOXY INTO (E) FDN
WALL - EMBED = 6"
5 7/8"
3"
CONT. #4 HORIZ.
@ 1'-4" (2 MIN)
BOND BREAK
TYPICAL
(E) SLAB ON
GRADE BEYOND
SEE NOTES
1 1/2" CLR.
TYP.
NOTE:
1. VERIFY OVERALL LENGTH AND WIDTH WITH ARCHITECTURAL &
MECHANICAL DRAWINGS.
2. DIMENSION "A" AT MECHANICAL RAISED SLABS SHALL BE 4" U.O.N.
#5 @ 1'-0" O.C. EACH
WAY, BOTTOM
#5 @ 1'-0" O.C. EACH
WAY, TOP & SIDES
(E) SLAB ON
GRADE - VERIFY
"A"
VERIFY
8"
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
BID DOCUMENTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Design and Construction
Services
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT ARCHITECT/ENGINEER OF RECORD
2100 North Greenville Ave. #1150
Richardson, TX 75082
(469) 431-0571
OPTIONAL BID #1
400 5th St
West Des Moines, IA 50265
(515) 225-6265
900 E. Prima Ctr Pkwy #320
Scottsdale, AZ 85258
(480) 222-3789
15620 W 113th St
Lenexa, KS 66219
(913) 202-7598
TERRACON EC DESIGN IMEG OCMI
GEOTECHNICAL: IRRIGATION: TECHNOLOGY: COST ESTIMATING:
JUNE 22, 2026
C U s e rs \J
B u e rm a n n \D o c u m e n ts \1
S
R
V T jb u e rm a n n S
R X
R
.r v t
/2
/2
:2
:3
A
M
1001-S-301
FOOTING & FOUNDATION DETAILS
LEAVENWORTH NATIONAL CEMETERY
GRAVESITE EXPANSION
150 MUNCIE ROAD; LEAVENWORTH, KANSAS 66048
897CM3025
JUNE 22, 2026 EW DW/JB
BID DOCUMENTS
18704
1/2" = 1'-0"1001-S-301
1 STEPPED FOOTING DETAIL
1/2" = 1'-0"1001-S-301
2 WALL CORNER REINF. DETAIL
1/2" = 1'-0"1001-S-301
3 WALL INTERSECTION DETAIL
1/2" = 1'-0"1001-S-301
4 WALL CONSTRUCTION JOINT DETAIL
1/2" = 1'-0"1001-S-301
5 FLOOR CONTROL JOINT DETAIL
1/2" = 1'-0"1001-S-301
6 ADDT. REINF. @ OPENING
1/2" = 1'-0"1001-S-301
7 STOOP DETAIL
1/2" = 1'-0"1001-S-3011001-S-301
8 FOUNDATION WALL DETAIL8A
1/2" = 1'-0"1001-S-301
9 INTERIOR FOOTING DETAIL
1/2" = 1'-0"1001-S-301
10 INT. FTG. CONN. DETAIL
1/2" = 1'-0"1001-S-301
11 SLAB CONN. DETAIL
1/2" = 1'-0"1001-S-301
12 FLOOR CONSTRUCTION JOINT DETAIL
1/2" = 1'-0"1001-S-301
13 COLUMN ISOLATION JOINT DETAIL
1/2" = 1'-0"1001-S-301
14 STAIR DETAIL
1" = 1'-0"1001-S-301
15 CONC. SLAB ON GRADE REPAIR DETAIL
1/2" = 1'-0"1001-S-301
16 TYPICAL HOLDOWN DETAIL
1" = 1'-0"1001-S-301
17 LINTEL @ EXISTING FOUNDATION WALL DETAIL
1" = 1'-0"1001-S-301
18 BRICK LEDGE INFILL DETAIL
Revisions: Date:
1/2" = 1'-0"1001-S-301
19 RAISED SLAB DETAIL
T.O. (E) FDN WALL
EL. = 98' - 10 5/8" (VERIFY)
T.O. (E) LEDGE
EL. = FIELD VERIFY
T.O. PIER
EL. = 99'-4"
T.O. SLAB
EL. = 100'-0"
T.O. PIER
EL. = 99'-4"
T.O. WALL
EL. = 100'-0"
T.O. LEDGE
EL. = SEE PLAN
T.O. WALL
EL. = SEE ARCH/CIVIL
T.O. GRADE
EL. = 90' - 11 5/8"
T.O. SLAB
EL. = 91'-6 5/8"
T.O. FTG
EL. = 89' - 3"
T.O. FTG
EL. = 87' - 11"
T.O. GRADE
EL. = 90' - 11 5/8"
T.O. SLAB
EL. = 91'-6 5/8"
T.O. FTG
EL. = 89' - 3"
B.O. FTG
EL. = 87' - 11"
T.O. (E) BRICK LEDGE
EL. = VARIES (VERIFY)
T.O. (E) BRICK LEDGE
EL. = VARIES (VERIFY)
T.O. (E) BRICK LEDGE
EL. = VARIES (VERIFY)
PL. 3/4" x 7 1/2" x 7 1/2" W/
3 - 3/4" DIA. ANCHOR BOLTS
NOTE:
DRILL & EPOXY ANCHOR BOLT INTO EXISTING FOUNDATION
WALL W/ SIMPSON 'SET-3G' EPOXY OR EQUIVALENT
2 1/2" 3 1/2"
1 1/2"
CL.
CL.
2 1/2"
3 1/2"
1 1/2"
3/4" DIA. @ BP1 & BP4
ANCHOR BOLTS
T.O. (E) WALL
MARK BP1
8" 5"
PL. 1" x 1' - 2" x 1' - 2" W/
4 - 3/4" DIA. ANCHOR BOLTS
1 1/2" 5 1/2" 5 1/2" 1 1/2"
GRID
GRID
1 1/2"
5 1/2"
5 1/2"
1 1/2"
MARK BP2
3/4" DIA. @ BP2 & BP3, & BP5
T.O. PIER
1'
0" 6"
HEAVY HEX NUT - TYP.
PL. 3/4" x 1' - 2" x 1' - 0" W/
4 - 3/4" DIA. ANCHOR BOLTS
MARK BP3
PL. 3/4" x 7 1/2" x 10" W/
4 - 3/4" DIA. ANCHOR BOLTS
1 1/2"
3 1/2"
2 1/2"
CL.
CL.
1 1/2"
3 1/2"
3 1/2"
1 1/2"
MARK BP4
PL. 3/4" x 7 1/2" x 10" W/
4 - 3/4" DIA. ANCHOR BOLTS
MARK BP5
1 1/2"
3 1/2" 3 1/2" 1 1/2"
CL.
CL.
2 1/2"
3 1/2"
1 1/2"
G
E
2"
5"
5 1/2"
1 1/2"
1 1/2"5 1/2"5 1/2"1 1/2"
1/
2"
CL.
CL.
D
5.1
3"
EXISTING WALL SHEATHING
(VERIFY)
BASE PLATE & ANCHOR BOLT
S.D. 1/S-302
4" 10"
VERIFY
EXISTING 1'-2" FDN WALL
3"
1 1/2" N.S. GROUT
EXISTING FLOOR SHEATHING
(VERIFY)
(E) 2x FLOOR JOIST
(VERIFY)
GRID
CL.
STEEL COLUMN
SEE PLAN
CL.
4"
4" 10"
F
3"
4 CL.
3"
BP1 @ GRID F/4
BASEPLATE &
ANCHOR BOLT
S.D. 1/S-302
STEEL COLUMN
SEE PLAN
(E) FDN. WALL
VERIFY
CL.
4"
4"10"
D
3"
4.1CL.
3"
BASEPLATE &
ANCHOR BOLT
S.D. 1/S-302
STEEL COLUMN
SEE…