This is a Limited and Directed Pre-Renovation Asbestos Survey Report prepared by Reliance Environmental, LLC for Kent Memorial Library, a Connecticut state and local property located at 30-32 North Main Street, Kent, CT. The survey was conducted on October 27, 2025, by a State of Connecticut licensed asbestos inspector to identify asbestos-containing materials (ACMs) prior to facility renovation. A total of 45 bulk samples were collected from the two-building property (Building #30, the Firehouse, and Building #32, the Library) and analyzed using Polarized Light Microscopy (PLM) according to EPA 600/R-93/116 protocol. The survey identified four locations containing asbestos at concentrations greater than or equal to 1.0 percent: vermiculite insulation in the attic of Building #30 (approximately 2,000 square feet), mastic in flooring layers on the second floor front room of Building #30 (approximately 1,500 square feet), window glazing on the exterior of Building #30 (35 windows), and 9" x 9" floor tiles on the first-floor stairs of Building #32 (approximately 100 square feet). The report notes that removal of all identified ACMs must be performed by a Connecticut State licensed asbestos abatement contractor and that abatement contractors should verify quantities and removal difficulty prior to submitting cost proposals.
The survey was performed for Ms. Sarah Marshall, Director of Kent Memorial Library, with the report prepared by Vidya N. Trivedi of Reliance Environmental, LLC, who holds current Connecticut Department of Public Health Asbestos Consultant-Project Designer certification (Certificate No. 000017, valid through March 31, 2026). The laboratory analysis was completed by Asbestos Identification Laboratory in Woburn, Massachusetts, which holds multiple state certifications and NVLAP accreditation. The report specifically notes that additional suspect materials may exist behind fixed walls, under flooring, or above ceilings, and if any such materials are discovered during renovation, all activities must cease pending sampling by a licensed inspector. The EPA recommends that vermiculite insulation not be disturbed and that any removal be performed by trained, accredited abatement contractors independent from the assessment firm to avoid conflicts of interest.
Text of this file
Reliance Environmental, LLC Asbestos, Lead, Mold, Phase 1-3, Hazmat, Soil, Indoor Air & Ground Water Quality Specialists
Limited & Directed Pre-renovation Asbestos Survey Report For Kent Memorial Library Located at
30-32 North Main Street Kent, CT 06757
Prepared for:
Ms. Sarah Marshall, Director Kent Memorial Library 30 North Main Street Danbury, CT 06810
(860) 927-3761 | smarshall@biblio.org
November 04, 2025
Reliance Project # 25-LIBRARY-01
140 Captain Thomas Blvd • Suite 201 • West Haven • CT 06516
(203) 553-9070 • Fax (203) 553-9069 • vidyatrivedi2002@yahoo.com
Reliance Environmental, LLC - S Kent Memorial Library.
Reliance #25-LIBRARY-01 1 30-32 North Main Street, Kent, CT
TABLE OF CONTENTS
Section Page
I. PROJECT NARRATIVE
OVERVIEW
SUMMARY OF RESULTS
II. SAMPLE LOG AND RESULTS TABLE
BULK SAMPLES COLLECTED ON 10-27-25
III. CHAIN OF CUSTODY & LAB ANALYSIS SHEETS FOR ASBESTOS
IV. STATE OF CT ASBESTOS INSPECTOR LICENSE
Reliance #25-LIBRARY-01 2 30-32 North Main Street, Kent, CT
I. PROJECT NARRATIVE
Overview
On October 27 of 2025, a State of Connecticut licensed asbestos inspector from Reliance Environmental, LLC performed a limited and directed pre-renovation asbestos survey for Kent Memorial Library of a property located at 30-32 North Main Street, Kent, CT. The purpose of this inspection was to determine the presence of asbestos in suspect building materials so that all issues related to asbestos containing materials could be addressed prior to renovation of the referenced facility.
Samples were collected according to 40 CFR Part 763.86 and 29 CFR Part 1926.1101 and analyzed using Polarized Light Microscopy (PLM) using EPA 600/R-93/116 protocol.
A total of Forty-Five (45) bulk samples were collected from the above noted facility.
Please refer to table in Section II for various types of building materials sampled during this asbestos survey.
Summary of Results
The Asbestos Identification Lab analyzed the bulk samples. Section III presents the complete list of analytical result for samples collected.
“MATERIALS FOUND TO CONTAIN GREATER THAN OR EQUAL TO 1.0 PERCENT ASBESTOS
(CALLED ASBESTOS CONTAINING MATRERIALS OR “ACMs”) DURING THE ASBESTOS
SURVEY”
Note: SF-Square Feet PACM-Presumed Asbestos Containing Materials Location Asbestos Containing Materials (ACM) Approximate
Quantity Attic – Firehouse (Building
#30) Vermiculite (PACM) ~ 2,000 SF
Second Floor – Front Room, Firehouse (Building #30)
Mastic (Third Layer) (Remove all layers of flooring up to substrate) ~1,500 SF
Exterior (Building #30) Glazing 35 Each (Windows)
First Floor – Stairs, Library (Building #32) 9” x 9” Floor Tiles ~ 100 SF
Specific Notes:
1. This inspection has been performed based on standard industry practices. The possibility however exists that suspect asbestos-containing materials may be located behind fixed walls, under fixed Flooring or above fixed ceilings. If additional materials are seen or become accessible, all activities shall cease and the materials shall be sampled by a licensed inspector to determine the presence of asbestos.
Reliance #25-LIBRARY-01 3 30-32 North Main Street, Kent, CT
2. Please note that certain OSHA, 29 CFR 1926.1101 regulations apply if materials containing less than 1% asbestos are disturbed.
3. The abatement contractor shall verify the quantities of asbestos containing materials indicated in the table above and degree of difficulty that will be encountered during removal prior to submitting quotes.
4. Removal of all asbestos containing materials listed in the table above shall be removed by a CT State licensed asbestos abatement contractor.
Reliance #25-LIBRARY-01 4 30-32 North Main Street, Kent, CT
II. SAMPLE LOG AND RESULTS TABLE
BULK SAMPLES COLLECTED ON 10-27-25
NAD = No Asbestos Detected NA = Not Analyzed SP/NA = Stop Positive/Not Analyzed Sample
ID
Number
Location Material Sampled Percent Asbestos
1 First Floor – Passage, Library (Building #32) Cove Base NAD
2 First Floor – Passage, Library (Building #32) Cove Base NAD
3 First Floor – Passage, Library (Building #32) Glue NAD
4 First Floor – Passage, Library (Building #32) Glue NAD
5 First Floor – Passage, Library (Building #32) Carpet Glue NAD
6 First Floor – Passage, Library (Building #32) Carpet Glue NAD
7 First Floor – Stairs Landing, Library (Building #32) Flooring Materials NAD
8 First Floor – Stairs Landing, Library (Building #32) Flooring Materials NAD
9 First Floor – Stairs Landing, Library (Building #32) Glue NAD
10 First Floor – Stairs Landing, Library (Building #32) Glue NAD
11 First Floor – Stairs, Library (Building #32) 9” x 9” Floor Tiles 2
12 First Floor – Stairs, Library (Building #32) 9” x 9” Floor Tiles SP/NA
13 First Floor – Stairs, Library (Building #32) Glue NAD
14 First Floor – Stairs, Library (Building #32) Glue NAD
15 Second Floor – Kitchen, Firehouse (Building #30) Wall Board NAD
16 Second Floor – Room by Kitchen, Firehouse (Building #30) Wall Board NAD
17 Second Floor – Front Room, Firehouse (Building #30) Joint Compound NAD
18 Second Floor – Front Room, Firehouse (Building #30) Joint Compound NAD
19 Second Floor – Front Room, Firehouse (Building #30) Textured Ceiling NAD
20 Second Floor – Front Room, Firehouse (Building #30) Textured Ceiling NAD
21 Second Floor – Front Room, Firehouse (Building #30) Textured Ceiling NAD
22 Second Floor – Front Room, Firehouse (Building #30) Carpet Glue (First Layer) SP/NA
23 Second Floor – Front Room, Firehouse (Building #30) Floor Materials (Second Layer) SP/NA
Reliance #25-LIBRARY-01 5 30-32 North Main Street, Kent, CT
NAD = No Asbestos Detected NA = Not Analyzed SP/NA = Stop Positive/Not Analyzed Sample
ID
Number
Location Material Sampled Percent Asbestos
24 Second Floor – Front Room, Firehouse (Building #30) Mastic (Third Layer) 5
25 Second Floor – Room by Kitchen, Firehouse (Building #30)
Carpet Glue (First Layer) SP/NA
26 Second Floor – Room by Kitchen, Firehouse (Building #30)
Floor Materials (Second Layer) SP/NA
27 Second Floor – Room by Kitchen, Firehouse (Building #30)
Mastic (Third Layer) SP/NA
28 Second Floor – Kitchen, Firehouse (Building #30) Formica Glue NAD
29 Second Floor – Kitchen, Firehouse (Building #30) Sink Under Coating NAD
30 Second Floor – Kitchen, Firehouse (Building #30) Cove Base NAD
31 Second Floor – Kitchen, Firehouse (Building #30) Glue NAD
32 Second Floor – Kitchen, Firehouse (Building #30) 1’x1’ Floor Tiles NAD
33 Second Floor – Kitchen, Firehouse (Building #30) 1’x1’ Floor Tiles NAD
34 Second Floor – Kitchen, Firehouse (Building #30) Mastic NAD
35 Second Floor – Kitchen, Firehouse (Building #30) Mastic NAD
36 First Floor – Bathroom, Firehouse (Building #30) Cove Base NAD
37 First Floor – Bathroom, Firehouse (Building #30) Glue NAD
38 First Floor – Bathroom, Firehouse (Building #30) 1’x1’ Floor Tiles NAD
39 First Floor – Bathroom, Firehouse (Building #30) 1’x1’ Floor Tiles NAD
40 First Floor – Bathroom, Firehouse (Building #30) Glue NAD
41 First Floor – Bathroom, Firehouse (Building #30) Glue NAD
42 First Floor – Rear Room, Firehouse (Building #30) Brick Mortar NAD
43 First Floor – Firehouse (Building #30) Breeching Grout NAD
44 Exterior (Building #30) Window Glazing 2
45 Exterior (Building #30) Window Glazing SP/NA
Reliance #25-LIBRARY-01 6 30-32 North Main Street, Kent, CT
III. CHAIN OF CUSTODY & LAB ANALYSIS SHEETS FOR ASBESTOS
Asbestos Identification Laboratory.
165 New Boston St., Ste 227
Woburn, MA 01801 781-932-9600
Web: www.asbestosidentificationlab.com Email:
mikemanning@asbestosidentificationlab.com
Batch: 144513
Dear Vidya N. Trivedi, Thank you Vidya N. Trivedi for your business.
Michael Manning Owner/Director
Asbestos Identification Laboratory has completed the analysis of the samples from your office for the above referenced project.
The Analysis Method is BULK PLM ANALYSIS, EPA/600/R-93/116The information and analysis contained in this report have been generated using the EPA /600/R-93/116 Method for the Determination of Asbestos in Bulk Building Materials. Materials or products that contain more than 1% of any kind or combination of asbestos are considered an asbestos containing building material as determined by the EPA. This Polarized Light Microscope (PLM) technique may be performed either by visual estimation or point counting. Point counting provides a determination of the area percentage of asbestos in a sample. If the asbestos is estimated to be less than 10% by visual estimation of friable material, the determination may be repeated using the point counting technique. The results of the point counting supersede visual PLM results. Results in this report only relate to the items tested. This report may not be used by the customer to claim product endorsement by NVLAP or any other U.S.
Government Agency.
The EPA recommends you should assume vermiculite contains asbestos and not to disturb it. Airborne asbestos fibers present a health risk through inhalation, so the first step is to not disturb the material, which could release fibers into the air. If you disturb the insulation, you may inhale some asbestos fibers. The degree of health risk depends on how much and how often this occurred. If you choose to remove the vermiculite insulation, this work should be done by a trained and accredited asbestos abatement contractor that is separate and independent from the company that performed the assessment of the vermiculite insulation to avoid any conflict of interest. Link: "https://www.epa.gov/asbestos/my-attic-has-vermiculite-insulation-it-am-i-risk-should-i-take-it-outld I take it out? | US EPA"
Vidya N. Trivedi Reliance Environmental, LLC 11 Old Farm Road Woodbridge, CT 06525
Project Information
30-32 North Main St., Kent, CT
Method: BULK PLM ANALYSIS, EPA/600/R-93/116
• NVLAP Lab Code: 200919-0
• Massachusetts Certification License: AA000208
• State of Connecticut, Department of Public Health Approved Environmental Laboratory Registration Number: PH-0142
• State of Maine, Department of Environmental Protection Asbestos Analytical Laboratory License Number: LB-0078(Bulk) LA-0087(Air)
• State of Rhode Island and Providence Plantations. Department of Health Certification: AAL-121
• State of Vermont, Department of Health Environmental Health License AL934461
Laboratory results represent the analysis of samples as submitted by the customer. Information regarding sample location, description, area, volume, etc., was provided by the customer. Information provided by the customer can affect the validity of results. Asbestos Identification Laboratory is not responsible for sample collection activities or analytical method limitations.
Unless notified in writing to return samples, Asbestos Identification Laboratory discards customer samples after 30 days.
Samples containing subsamples or layers will be analyzed separately when applicable. Reports are kept at Asbestos Identification Laboratory for three years. All customer information will be maintained in confidentiality. This report shall not be reproduced, except in full, without the written consent of Asbestos Identification Laboratory.
Vidya N. Trivedi
11 Old Farm Road Woodbridge, CT 06525
Project Information
30-32 North Main St., Kent, CT
Method: BULK PLM ANALYSIS, EPA/600/R-93/116
Asbestos %Material Color Non-Asbestos %LocationFieldID
LabID green Non-Fibrous 100
1630721
1 1st Fl Passage, Library (Bldg #32)
Cove Base None Detected green Non-Fibrous 100
1630722
2 1st Fl Passage, Library (Bldg #32)
Cove Base None Detected gray Non-Fibrous 100
1630723
3 1st Fl Passage, Library (Bldg #32)
Glue None Detected tan Non-Fibrous 100
1630724
4 1st Fl Passage, Library (Bldg #32)
Glue None Detected tan Non-Fibrous 100
1630725
5 1st Fl Passage, Library (Bldg #32)
Carpet Glue None Detected tan Non-Fibrous 100
1630726
6 1st Fl Passage, Library (Bldg #32)
Carpet Glue None Detected blue Non-Fibrous 100
1630727
7 1st Fl Stairs Landing Library (Bldg #32)
Flooring Material None Detected blue Non-Fibrous 100
1630728
8 1st Fl Stairs Landing Library (Bldg #32)
Flooring Material None Detected tan Non-Fibrous 100
1630729
9 1st Fl Stairs Landing Library (Bldg #32)
Glue None Detected tan Non-Fibrous 100
1630730
10 1st Fl Stairs Landing Library (Bldg #32)
Glue None Detected
Detected Chrysotile 2 red Non-Fibrous 98
1630731
11 1st Fl Stairs, Library (Bldg #32)
9"x9" Floor Tiles
1630732
12 1st Fl Stairs, Library (Bldg #32)
9"x9" Floor Tiles Not Analyzed tan Non-Fibrous 100
1630733
13 1st Fl Stairs, Library (Bldg #32)
Glue None Detected tan Non-Fibrous 100
1630734
14 1st Fl Stairs, Library (Bldg #32)
Glue None Detected gray Cellulose 10 Non-Fibrous 90
1630735
15 2nd Fl Kitchen, Firehouse (Bldg #30)
Wallboard None Detected gray Cellulose 10 Non-Fibrous 90
1630736
16 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
Wallboard None Detected
Sampled: Received: October 31, 2025October 29, 2025 Analyzed:October 27, 2025
Analyzed by: 144513Batch:
Saturday 01 November
11 Old Farm Road Woodbridge, CT 06525
Project Information
30-32 North Main St., Kent, CT
Method: BULK PLM ANALYSIS, EPA/600/R-93/116
Asbestos %Material Color Non-Asbestos %LocationFieldID
LabID white Non-Fibrous 100
1630737
17 2nd Fl Front Room, Firehouse (Bldg #30)
Joint Compound None Detected white Non-Fibrous 100
1630738
18 2nd Fl Front Room, Firehouse (Bldg #30)
Joint Compound None Detected white Non-Fibrous 100
1630739
19 2nd Fl Front Rm, Firehouse (Bldg #30)
Textured Ceiling None Detected white Non-Fibrous 100
1630740
20 2nd Fl Front Rm, Firehouse (Bldg #30)
Textured Ceiling None Detected white Non-Fibrous 100
1630741
21 2nd Fl Front Rm, Firehouse (Bldg #30)
Textured Ceiling None Detected
1630742
22 2nd Fl Front Rm, Firehouse (Bldg #30)
Carpet Glue 1st Layer Not Analyzed
1630743
23 2nd Fl Front Rm, Firehouse (Bldg #30)
Flr Material 2nd Layer Not Analyzed
Detected Chrysotile 5 black Non-Fibrous 95
1630744
24 2nd Fl Front Rm, Firehouse (Bldg #30)
Mastic 3rd Layer
1630745
25 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
Carpet Glue 1st Layer Not Analyzed
1630746
26 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
Fl Material 2nd Layer Not Analyzed
1630747
27 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
Mastic 3rd Layer Not Analyzed tan Non-Fibrous 100
1630748
28 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
Formica Glue None Detected tan Cellulose 20 Non-Fibrous 80
1630749
29 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
Sink Under Coating None Detected brown Non-Fibrous 100
1630750
30 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
Cove Base None Detected tan Non-Fibrous 100
1630751
31 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
Glue None Detected tan Non-Fibrous 100
1630752
32 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
1'x1' Fl Tiles None Detected
Sampled: Received: October 31, 2025October 29, 2025 Analyzed:October 27, 2025
Analyzed by: 144513Batch:
11 Old Farm Road Woodbridge, CT 06525
Project Information
30-32 North Main St., Kent, CT
Method: BULK PLM ANALYSIS, EPA/600/R-93/116
Asbestos %Material Color Non-Asbestos %LocationFieldID
LabID tan Non-Fibrous 100
1630753
33 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
1'x1' Fl Tiles None Detected black Non-Fibrous 100
1630754
34 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
Mastic None Detected black Non-Fibrous 100
1630755
35 2nd Fl Room by Kitchen, Firehouse (Bldg #30)
Mastic None Detected brown Non-Fibrous 100
1630756
36 1st Fl Bathroom, Firehouse (Bldg #30)
Cove Base None Detected tan Non-Fibrous 100
1630757
37 1st Fl Bathroom, Firehouse (Bldg #30)
Glue None Detected tan Non-Fibrous 100
1630758
38 1st Fl Bathroom, Firehouse (Bldg #30)
1'x1' Fl Tiles None Detected tan Non-Fibrous 100
1630759
39 1st Fl Bathroom, Firehouse (Bldg #30)
1'x1' Fl Tiles None Detected tan Non-Fibrous 100
1630760
40 1st Fl Bathroom, Firehouse (Bldg #30)
Glue None Detected tan Non-Fibrous 100
1630761
41 1st Fl Bathroom, Firehouse (Bldg #30)
Glue None Detected gray Non-Fibrous 100
1630762
42 1st Fl Rear Room, Firehouse (Bldg #30)
Brick Mortar None Detected gray Non-Fibrous 100
1630763
43 1st Fl Rear Room, Firehouse (Bldg #30)
Breeching Grout None Detected
Detected Chrysotile 2 gray Non-Fibrous 98
1630764
44 Exterior (Bldg #30)Window Glazing
1630765
45 Exterior (Bldg #30)Window Glazing Not Analyzed
Sampled: Received: October 31, 2025October 29, 2025 Analyzed:October 27, 2025
Analyzed by: 144513Batch:
Reliance #25-LIBRARY-01 7 30-32 North Main Street, Kent, CT
IV. STATE OF CT ASBESTOS INSPECTOR LICENSE
1000435 SP 0664 -C01-P00437-I
VIDYA N. TRIVEDI
RELIANCE ENVIRONMNET AL LLC
11 OLD FARM RD
WOODBRIDGE CT 06525-2400
Dear VIDYA N. TRIVEDI , Attached you will find your validated certificate for the coming year. Should you have any questions about your certificate renewal, please do not hesitate to write or call:
Department of Public Health P .0. Box 340308
M.S.#12MQA
(860) 509-7603 oplc.dph@ct.gov www.ct.gov/dph/license Hartford, CT 06134-0308
MANISHA JUTHANI, MD, COMMISSIONER
DEPARTMENT OF PUBLIC HEALTH
STATE OF CONNECTICUT
DEPARTMENT OF PUBLIC HEALTH
PURSUANT TO THE PROVISIONS OF THE GENERAL STATUTES OF CONNECTICUT
THE INDIVIDUAL NAMED BELOW IS CERTIFIED
BY TIIIS DEPARTMENT AS A
ASBESTOS CONSULT ANT-PROJECT DESIGNER
CERTIFICATE NO.
VIDYA N. TRIVEDI
000017
CURRENT 11-IROUGH
03/31/26
VALIDATION NO.
03-172601
EMPLOYER'S COPY
ST ATE OF CONNECTICUT
DEPARTMENT OF PUBLIC HEALTH
NAME
VIDYA N. TRIVEDI
VALIDATION NO. CERTIFICATE NO. CURRENT THROUGH
03-172601 000017 03/31/26
PROFESSION
ASBESTOS CONSULTANT-PROJECT DESIGNER
~±¥ N• r/iw M~HA ,CO~SIONER
:I• -- - _______ ..._ __ ..__..___..........._.. _..__ __ ..._ __ ...._..__ ____ ..__. __ ..._..,_..,_r_.._. _____________ _
INSTRUCTIONS:
I . Deta ch and ll i).! n eac h or th e ca rds on 1his form
2. Di~play the large ca rd in u promincnl place in ~our Mfin • or ll lun· of ht1 !1 ill r!lll.
3. The \\ Ull ct ca n.I is for ~o u to rn rry on yo ur perso n. If you do not n ill h 10 c 111-r~ 1hc \\ a lk1 c:trcl. place it in a sec ure pl :tce.
-4 . The emp loye r 's copy is fo r perso ns "ho must demonstrat e cunent liccnsure/n;rtifi ca ti on in ordc,· to r eta in employ·ment o r prhileges. The employer ·s ciu-d i,; to bl' prcscnll'd lo lhl' emp loyer and kepi by them as a part or your perso nnel fil e. O nly one copy of th is ca rd ca 11 he 'i llJlplicd to ~OIi.
WALL.Hf CARD
STATE OF CONNECTICUT
DEPARTMENT OF PUBLIC HEALTH
NAME
VIDYA N. TRIVEDI
VALIDATION NO. CERTIFICATE NO. CURRENT THROUGH
03-172601 000017 03/31/26
PROFESSION
ASBESTOS CONSUL TANT-PROJECT DESIGNER
l6& ~1
• 1~~HA .co=oNER
| I. PROJECT NARRATIVE |
| Overview |
| Summary of Results |
| II. SAMPLE LOG AND RESULTS TABLE |
| BULK SAMPLES COLLECTED ON 10-27-25 |
| III. CHAIN OF CUSTODY & LAB ANALYSIS SHEETS FOR ASBESTOS |
| IV. STATE OF CT ASBESTOS INSPECTOR LICENSE |
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .