This solicitation requests proposals for the construction and design of an Operations Support Facility at Fort Bragg, North Carolina. The scope of work includes construction of a 36,000 square foot facility with spaces such as offices, conference rooms, training rooms, medical exam areas, latrines, mechanical and electrical rooms, and secure server rooms. The facility is to be built to sensitive compartmented information standards. Supporting site work includes utilities, parking, drives, drainage, landscaping and signage. Comprehensive interior design services are required. The contract will be firm-fixed price with a period of performance of 540 calendar days. The Department of the Army Corps of Engineers Engineering District Wilmington is the issuing agency.
View the file
Other files for this federal contract opportunity
Show all 50
PN 92594 SOF Operations Support Facility has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TOP
PLAN
BASE
TOP
PLAN
BASE
(1) LAYER 5/8" GYPSUM
BOARD EACH SIDE;
TYPE 'X' AT P21B
4" 20 GAUGE METAL
STUDS @ 16" O.C.
UNDERSIDE OF
STRUCTURE
PROVIDE SLOTTED
DEFLECTION
TRACK ASSEMBLY
RUNNER TRACK
CEILING AS SCHED -
SEE FINISH
SCHEDULE
(1) LAYER 5/8"
GYPSUM BOARD ONE
SIDE
2 1/2" METAL STUDS @
16" O.C.
CEILING AS SCHED -
SEE FINISH
SCHEDULE
3 1/2" BATT INSUL
P01 1 1/2" METAL STUDS
CLIPPED TO COLUMN P21 4" METAL STUDS @ 16" O.C., SMOKE TIGHT
W/ ACOUSTICAL BATT INSULATION
P21A 4" METAL STUDS @ 16" O.C., SMOKE TIGHT
W/ NO ACOUSTICAL BATT INSULATION
FLOOR AND BASE AS
SCHED - SEE FINISH
SCHEDULE
FLOOR AND BASE AS
SCHED - SEE FINISH
SCHEDULE
(1) LAYER 5/8"
GYPSUM BOARD ONE
SIDE
2 1/2", 3 5/8, 4" OR 6"
20 GAUGE METAL
STUDS @ 16" O.C.
RUNNER TRACK
CEILING AS SCHED -
SEE FINISH SCHEDULE
P12 2 1/2" METAL STUDS @ 16" O.C.
P12A 3 5/8" METAL STUDS @ 16" O.C.
P12B 4" METAL STUDS @ 16" O.C.
FLOOR AND BASE AS
SCHED - SEE FINISH
SCHEDULE
CEILING AS SCHED - SEE
FINISH SCHEDULE
P02 2 1/2" METAL STUDS @ 16" O.C.
(1) LAYER 5/8" GYPSUM
BOARD EACH SIDE
3 5/8" 20 GAUGE METAL
STUDS @ 16" O.C.
UNDERSIDE OF
STRUCTURE
PROVIDE SLOTTED
DEFLECTION
TRACK ASSEMBLY
RUNNER TRACK
3 1/2" BATT INSUL
P22 3 5/8" METAL STUDS @ 16" O.C. W/ ACOUSTICAL BATT
INSULATION
P22A 3 5/8" METAL STUDS @ 16" O.C. W/ NO ACOUSTICAL
BATT INSULATION
FLOOR AND BASE AS
SCHED - SEE FINISH
SCHEDULE
CEILING AS SCHED - SEE
FINISH SCHEDULE
UNDERSIDE OF
STRUCTURE
PROVIDE SLOTTED
DEFLECTION
TRACK ASSEMBLY
CONT. SEALANT, TOP & BOT. FIRESAFE
SEAL/TIGHT TO DECK AT P21B
SHAFT
SIDE
(OR
INACCESS-
IBLE SIDE)
P52 STC 50; 2 1/2" C-H STUDS
P52A STC 50; 4" C-H STUDS; 1 HR
FIRE/SMOKE BARRIER SHAFTWALL
WHERE REQUIRED - SEE LIFE SAFETY
"J" RUNNER TRACK
FLOOR AND BASE AS SCHED -
SEE FINISH SCHEDULE
FIRESTOP SEALANT, TOP &
BOT.; ACOUSTIC SNT ONLY
BOTH SIDES AT P52
3 1/2" BATT INSUL
UL DESIGN NO. U415 - SYSTEM B, 2 HOUR SYSTEM
STC 50 - SOUND TEST RAL-OT04-019 W/ MINERAL WOOL
2 1/2" OR 4" 20 GAUGE
METAL CH STUDS @ 24"
O.C.
(2) LAYERS 5/8" TYPE "X"
OR (1) LAYER 1/2"
FIRECODE TYPE "C"
GYPSUM BOARD
(1) LAYER 1" X 24" TYPE "X"
GYPSUM LINER PANEL
UNDERSIDE OF
STRUCTURE
ACOUSTIC SNT, BOTH SIDES;
FIRESAFE / SEAL TIGHT
TO DECK, SEE NOTES
PROVIDE SLOTTED DEFLECTION
TRACK ASSEMBLY
CEILING AS SCHED - SEE
FINISH SCHEDULE
P61 8" CMU W/ 7/8" FURRING AND 5/8" GWB
ONE SIDE ONLY; SMOKE BARRIER
FLOOR AND BASE AS
SCHED - SEE FINISH
SCHEDULE
7/8" METAL HAT CHANNEL
FURRING @16" O.C. ONE
SIDE ONLY
(1) LAYER 5/8" GWB, ONE
SIDE ONLY
UNDERSIDE OF
STRUCTURE
CEILING AS SCHED - SEE
FINISH SCHEDULE
6" 6"
6" 6"
8" NOMINAL CMU
6"
P71 1 HR FIRE/SMOKE BARRIER UL
DESIGN NO. U905
FLOOR AND BASE AS
SCHED - SEE FINISH
SCHEDULE
8" NOMINAL FIRE-RATED
CMU, UL CLASSIFICATION
D-2, PNT TYP
UNDERSIDE OF
STRUCTURE
CEILING AS SCHED - SEE
FINISH SCHEDULE
UL DESIGN NO. U905 - 2-HR
SYSTEM, FIRE RATED D-2 CMU
FIRESAFE / SEAL TIGHT
TO DECK, SEE NOTES
(2) LAYERS 5/8" TYPE
"X" GYPSUM BOARD
EACH SIDE
4" OR 6" 20 GAUGE
METAL STUDS @
16" O.C.
3 1/2" BATT INSUL
UNDERSIDE OF
STRUCTURE
ACOUSTIC SNT, BOTH SIDES;
FIRESAFE SEAL/TIGHT TO
DECK AT P41C AND P41D
PROVIDE SLOTTED
DEFLECTION
TRACK ASSEMBLY
4" METAL STUDS; STC 50
CEILING AS SCHED - SEE
FINISH SCHEDULE
RUNNER TRACK
FLOOR AND BASE AS SCHED -
SEE FINISH SCHEDULE
ACOUSTIC SNT,
BOTH SIDES;
FIRESTOP
SEALANT AT P41C
P41
6" METAL STUDS; STC 50P41A
P81 8" CAST-IN-PLACE CONCRETE
FLOOR AND BASE AS
SCHED - SEE FINISH
SCHEDULE
8" CAST-IN-PLACE CONC -
SEE STRL
UNDERSIDE OF
STRUCTURE
CONC CEILING - SEE STRL
(1) LAYER 5/8"
GYPSUM BOARD
LAMINATED TO CONC
CEILING AS SCHED - SEE
FINISH SCHEDULE
(1) LAYER 5/8"
GYPSUM BOARD
ONE SIDE
1 1/2" METAL
STUDS @ 16" O.C.
P12C 6" METAL STUDS @ 16" O.C.
CONC SLABCONC SLAB CONC SLAB
RAF, WHERE SCHED RAF, WHERE SCHED RAF, WHERE SCHED
FLOOR AND BASE AS
SCHED - SEE FINISH
SCHEDULE
RAF, WHERE SCHED RAF, WHERE SCHED
CONC SLAB CONC SLAB
RAF, WHERE SCHED
SHAFT
SIDE
(OR
INACCESS-
IBLE SIDE)
SHAFT
SIDE
(OR
INACCESS-
IBLE SIDE)
RAF, WHERE SCHED
RAF (AT NON-
SHAFT
CONDITIONS)
CONC SLAB
(AT NON-
SHAFT
CONDITIONS)
CONC SLAB CONC SLAB CONC SLAB CONC SLAB CONC SLAB
4" METAL STUDS; STC 45P41B
CONT SNT AT SMOKE
PARTITIONS
P61A STC 50; 1 HR FIRE/SMOKE BARRIER,
8" CMU W/ 7/8" FURRING AND 5/8"
GWB ONE SIDE ONLY
4" MET. STUDS; STC 50; 1 HR
FIRE/SMOKE BARRIER
P41C
UL DESIGN NO. U407 - 1 HOUR SYSTEM
STC 52 - SOUND TEST RAL-TL-11-080
4" MET. STUDS; STC 45; 1 HR
FIRE/SMOKE BARRIER
P41D
P21B 4" METAL STUDS @ 16" O.C., 1 HR FIRE RATED
W/ 3 1/2" MIN BATT INSULATION
UL DESIGN NO. U419 - 1 HOUR SYSTEM
P52B STC 50; 4" C-H STUDS
A. AT FIRE RATED PARTITIONS AND FIRE RATED SHAFT WALLS, PROVIDE TYPE X GWB UNO AND
CONTINUOUS FIRE STOPPING BOTH SIDES, TOP, BOTTOM AND ALL PENETRATIONS. PROVIDE
CONTINUITY OF FIRE RATED PARTITIONS IN ORDER OF HIGHEST TO LOWEST LEVEL OF FIRE RATED PROTECTION, I.E. (HIGH)...2HR, 1HR, SMOKE, 0HR...(LOW), PARTICULARLY AT INTERSECTING AND
EXTERIOR WALLS.
B. PROVIDE MOISTURE RESISTANT GWB AT PARTITIONS AND SHAFT WALLS WITH WATER CLOSETS, URINALS, LAVATORIES, HOSE BIBBS, UTILITY SINKS, MOP BASINS, ELECTRIC WATER COOLERS, AND
WHERE NO TILE IS SCHEDULED.
C. PROVIDE MOISTURE RESISTANT GWB AT PARTITIONS AND EXTERIOR SIDE OF SHAFT WALLS
SCHEDULED TO RECEIVE EPOXY PAINT.
D. PROVIDE ABUSE RESISTANT GWB TO 8'-0" AFF AT CORRIDOR 1500.
E. PROVIDE CEMENTITIOUS BACKER UNITS IN LIEU OF GWB (REGULAR TYPE, MOISTURE RESISTANT TYPE
AND ABUSE RESISTANT TYPE) IN LOCATIONS SCHEDULED TO RECEIVE WALL TILE. CEMENTITIOUS
BACKER UNITS THICKNESS TO BE THE SAME THICKNESS AS SCHEDULED GWB.
F. SHAFT WALL STUD SPACING IS 24" OC. ALL OTHER STUD SPACING IS 16" OC.
G. PROVIDE FRT WOOD BLOCKING BEHIND GWB AS REQUIRED AT WALL MOUNTED MILLWORK, HANDRAILS, PLUMBING FIXTURES, CABINETRY, WALL MOUNTED CABLE TRAY AND OTHER WALL MOUNTED
ACCESSORIES AND EQUIPMENT. PROVIDE 3/4" FRT PLYWOOD BLOCKING WHERE WALL MOUNTED
DISPLAYS ARE INDICATED, SEE A/V DRAWINGS.
H. PROVIDE PARTITION CONTROL JOINTS AS INDICATED ON PLANS. CONSTRUCT CONTROL JOINTS IN ACCORDANCE WITH GYPSUM ASSOCIATION GA 216-2010 ARTICLE. AT CONTROL JOINTS IN RATED PARTITIONS OR AT CONTROL JOINTS IN STC 45 WALLS AND GREATER, REFER TO DETAIL 1 ON SH A-601.
I. 1-HR FIRE RATED PARTITIONS TO COMPLY WITH UL DETAIL U419 AND HEAD OF WALL DETAIL HW-D-0031.
J. 1-HR FIRE RATED SHAFT WALLS TO COMPLY WITH UL DETAIL U415, SYSTEM A AND HEAD OF WALL
DETAIL HW-D-0031.
K. DO NOT ATTACH PARTITIONS TO MET. ROOF DECK. PROVIDE SUPPLEMENTAL FRAMING AS REQUIRED.
L. THE CONTRACTOR SHALL PERFORM FIELD TESTING TO CERTIFY THAT THE ACOUSTICAL WALL
CONSTRUCTION INDICATED HAS BEEN MET. THE CONTRACTOR MAY CHOOSE TO USE EITHER NOISE ISOLATION CRITERIA (NIC) OR FIELD SOUND TRANSMISSION CLASS (FSTC) TESTING TO DETERMINE FIELD RATINGS OF CONSTRUCTED SOUND RATED PARTITIONS. CONTRACTOR TESTING MUST COMPLY WITH ICD/ICS 705 REQUIREMENTS. SUBMIT TESTING EQUIPMENT AND PROCESSES TO BE USED TO CONTRACTING OFFICER FOR APPROVAL. WALLS TESTED MUST HAVE A SOUND RATING OF NIC OR FSTC 45 AT STC 50 PARTITIONS, AND NIC OR FSTC 40 AT STC 45 PARTITIONS. THE CONTRACTOR WILL BE RESPONSIBLE FOR PERFORMING REMEDIAL WORK TO MEET THE REQUIRED FIELD SOUND RATINGS.
M. GOVERNMENT WILL PERFORM INDEPENDENT SOUND TESTING IN ADDITION TO CONTRACTOR'S SOUND
TESTING. CONTRACTOR WILL BE RESPONSIBLE FOR PERFORMING REMEDIAL WORK TO MEET THE
REQUIRED FIELD SOUND RATINGS RESULTING FROM GOVERNMENT TESTING.
N. 1-HR HORIZONTAL SHAFT WALL ASSEMBLIES ARE TO COMPLY WITH PROGRESSIVE ENGINEERING, INC.
ASSEMBLY EVALUATION REPORT AER-09038.
O. REFER TO DETAIL 2 ON SHEET A-531 FOR PARTITION DETAIL AT SLAB STEP. PLATFORM FRAMING
PERIMETER CONDITION IS SIMILAR TO THIS DETAIL.
P. LOCATE DEVICES IN ACOUSTICAL PARTITIONS IN A MANNER THAT MAINTAINS THE ACOUSTICAL
PROPERTIES OF THE PARTITION. REFER TO DETAIL 2 ON A-601.
Q. LABEL FIRE RATED AND SMOKE RATED PARTITIONS WITH STENCILING OR SIGNS. LOCATE
IDENTIFICATION BELOW RAISED ACCESS FLOOR AND ABOVE ACCESSIBLE CEILINGS. SPACE
IDENTIFICATION AT NO MORE THAN 10 FEET ON CENTER MEASURED HORIZONTALLY ALONG THE
PARTITION. INCORPORATE LETTERING NOT LESS THAN 1 INCH IN HEIGHT. LABEL WITH RESISTANCE
RATING (E.G. "1 HOUR FIRE RATED PARTITION, PROTECT ALL OPENINGS").
R. REFER TO SHEET S-503 FOR CMU TO STEEL BEAM/SLAB PARTITION BRACING DETAILS.
PARTITION TYPE NOTES:
BATT INSUL
PER PTN TYPE
MET. FRAMING
PER PTN TYPE
GWB PER
PTN TYPE
GWB PER
PTN TYPE
1/2" MAX
2 LAYERS 5/8" GWB
GWB CJ
5/8" GAP CONT SNT
BATT INSUL PER PTN TYPE
MET. FRAMING PER PTN TYPE
GWB PER PTN TYPE
ACOUSTIC PUTTY PAD AT
DEVICE BACKBOXES (@ ALL
SIDES), TYP
ACOUSTIC SEALANT
BETWEEN EDGE OF WALL AND
BACKBOX (@ ALL SIDES), TYP
GENERAL NOTE: DETAIL APPLIES TO
BACKBOXES IN ALL PARTITIONS
SCHEDULED TO HAVE STC RATINGS.
DEVICE BACKBOX, TYP
1'-6" MIN
12" 9" 6" 3" 0 1' 1-1/2"=1'-0"
12" 9" 6" 3" 0 3"=1'-0"
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
C
AT
EG
O
R Y
C O
D E:
1 2 3 4 5
A
GRAPHIC SCALES
FO
R
T
BR
AG
G
, N O
R
TH
C
AR
O
LI
N A
SO
F
O
PE
R
AT
IO
N
S
FA
C
IL
IT
Y
FY
0, P
N
W
IL
M
IN
G
TO
N D
IS
TR
IC
T
W
IL
M
IN
G
TO
N , N
O R
TH
C
AR
O
LI
N
A
AE
C
O M
S
ER
VI
C
ES
, I
N C
S J
EF
FE
R
SO
N S
T
ST
E
R
O
AN
O
KE
V A
/2
4/
7 8 9 10
B
C
D
E
F
G
TM
J
UNCLASSIFIED//FOR OFFICIAL USE ONLY
UNCLASSIFIED//FOR OFFICIAL USE ONLY
-W
2P M
R
A-601
PA
R
TI
TI
O N
T
YP
ES
C
LB
C
LB
R M
G
FY
PN
4A
-6
.d w g
READY TO ADVERTISE
3" = 1'-0"A-601
1 CJ AT ACOUSTIC PTN
1 1/2" = 1'-0"A-601
TYP PLAN DETAIL - DEVICE BACKBOX @
ACOUSTIC PTN
MA
RK
DE
SC
RI
PT
IO
N
DA
TE
RE
VI
SE
D
IN
A C C
OR
DA
N C E
W
IT
H
AM
EN
DM
EN
T
M
AR
2 0
| Sheets |
| A-101 - FIRST FLOOR PLAN |
| A-102 - SECOND FLOOR PLAN |
| A-402 - STAIR PLANS AND SECTIONS |
| A-412 - EXAM ROOM ENLARGED PLAN AND ELEVATIONS |
| A-531 - INTERIOR DETAILS |
| A-601 - PARTITION TYPES |
| A-602 - DOOR SCHEDULE |