SECTION 15820 REPAIR WING HEADQUARTERS, BLDG 706
DUCT ACCESSORIES CRWU 06-2071
06/09/09 15820-1 BUCKLEY AFB
SECTION 15820 - DUCT ACCESSORIES
PART 1 - GENERAL
1.01 SUMMARY:
A. Section Includes:
1. Manual volume dampers.
2. Control dampers.
3. Flange connectors.
4. Turning vanes.
5. Duct-mounted access doors.
6. Flexible connectors.
7. Flexible ducts.
8. Duct accessory hardware.
1.02 REFERENCES:
A. Applicable Standards (latest edition):
1. Air Movement and Control Association International, Inc. (AMCA):
a. 500-D - Laboratory Methods of Testing Dampers for Rating.
2. ASTM International (ASTM):
a. A480/A480M - General Requirements for Flat-Rolled Stainless and Heat-Resisting
Steel Plate, Sheet, and Strip.
b. A653/A653M - Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated
(Galvannealed) by the Hot-Dip Process.
c. B209 - Aluminum and Aluminum-Alloy Sheet and Plate.
d. B209M - Aluminum and Aluminum-Alloy Sheet and Plate (Metric).
e. B221 - Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and
Tubes.
f. B221M - Aluminum and aluminum-Alloy Extruded Bars, Rods, Wires, Profiles, and
Tubes (Metric).
g. E84 - Test Method for Surface Burning Characteristics of Building Materials.
h. E477 - Test Method for Measuring Acoustical and Airflow Performance of Duct
Liner Materials and Prefabricated Silencers.
3. National Fire Protection Association (NFPA):
a. 90A - Installation of Air Conditioning and Ventilating Systems (ANSI).
b. 90B - Installation of Warm Air Heating and Air Conditioning Systems (ANSI).
4. The North American Insulation Manufacturers Association (NAIMA):
a. AH116 - Fibrous Glass Duct Construction Standards.
5. Sheet Metal and Air Conditioning Contractors' National Association (SMACNA):
a. HVAC Duct Construction Standards - Metal and Flexible.
6. Underwriters Laboratories Inc. (UL):
a. 181 - Factory-Made Air Ducts and Air Connectors.
b. Fire Resistance Directory.
1.03 SUBMITTALS:
A. General: Submit the following in accordance with SECTION 15050 - BASIC MECHANICAL
MATERIALS AND METHODS.
B. Product Data: For each type of product indicated.
BUCKLEY AFB 15820-2 06/09/09
C. Operation and Maintenance Data: For air duct accessories to include in operation and maintenance manuals.
1.04 QUALITY ASSURANCE:
A. Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," and with
NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems."
B. Comply with AMCA 500-D testing for damper rating.
PART 2 - PRODUCTS
2.01 MATERIALS
A. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections.
B. Galvanized Sheet Steel: Comply with ASTM A653/A653M.
1. Galvanized Coating Designation: G90 (Z275).
2. Exposed-Surface Finish: Mill phosphatized.
C. Reinforcement Shapes and Plates: Galvanized-steel reinforcement where installed on galvanized sheet metal ducts.
D. Tie Rods: Galvanized steel, 1/4-inch (6-mm) minimum diameter for lengths 36 inches (900
mm) or less; 3/8-inch (10-mm) minimum diameter for lengths longer than 36 inches (900 mm).
2.02 MANUAL VOLUME DAMPERS:
A. Standard, Steel, Manual Volume Dampers:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Air Balance Inc.; a division of Mestek, Inc.
b. American Warming and Ventilating; a division of Mestek, Inc.
c. McGill AirFlow LLC.
d. Ruskin Company.
e. Trox USA Inc.
f. Vent Products Company, Inc.
2. Standard leakage rating, with linkage outside airstream.
3. Suitable for horizontal or vertical applications.
4. Frames:
a. Hat-shaped, galvanized-steel channels, 0.064-inch (1.62-mm) minimum thickness.
b. Mitered and welded corners.
c. Flanges for attaching to walls and flangeless frames for installing in ducts.
5. Blades:
a. Multiple or single blade.
b. Parallel- or opposed-blade design.
c. Stiffen damper blades for stability.
d. Galvanized-steel, 0.064 inch (1.62 mm) thick.
6. Blade Axles: Galvanized steel or Nonferrous metal.
7. Bearings:
a. Oil-impregnated bronze or molded synthetic.
06/09/09 15820-3 BUCKLEY AFB
b. Dampers in ducts with pressure classes of 3-inch wg (750 Pa) or less shall have axles full length of damper blades and bearings at both ends of operating shaft.
8. Tie Bars and Brackets: Galvanized steel.
B. Jackshaft:
1. Size: 1-inch (25-mm) diameter.
2. Material: Galvanized-steel pipe rotating within pipe-bearing assembly mounted on supports at each mullion and at each end of multiple-damper assemblies.
3. Length and Number of Mountings: As required to connect linkage of each damper in multiple-damper assembly.
C. Damper Hardware:
1. Zinc-plated, die-cast core with dial and handle made of 3/32-inch- (2.4-mm-) thick zinc-plated steel, and a 3/4-inch (19-mm) hexagon locking nut.
2. Include center hole to suit damper operating-rod size.
3. Include elevated platform for insulated duct mounting.
2.03 CONTROL DAMPERS:
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. American Warming and Ventilating; a division of Mestek, Inc.
2. Arrow United Industries; a division of Mestek, Inc.
3. Greenheck Fan Corporation.
4. Ruskin Company.
B. Low-leakage rating and bearing AMCA's Certified Ratings Seal for both air performance and air leakage.
C. Frames:
1. Hat, U, or Angle shaped.
2. Galvanized-steel channels, 0.064 inch (1.62 mm) thick.
3. Mitered and welded corners.
D. Blades:
1. Multiple blade with maximum blade width of 8 inches (200 mm).
2. Opposed-blade design.
3. Galvanized steel.
4. 0.064 inch (1.62 mm) thick.
5. Blade Edging: Closed-cell neoprene edging.
E. Blade Axles: 1/2-inch- (13-mm-) diameter; galvanized steel or nonferrous metal; blade-linkage hardware of zinc-plated steel and brass; ends sealed against blade bearings.
1. Operating Temperature Range: From minus 40 to plus 200oF (minus 40 to plus 93oC).
F. Bearings:
1. Oil-impregnated bronze or Molded synthetic.
2. Dampers in ducts with pressure classes of 3-inch wg (750 Pa) or less shall have axles full length of damper blades and bearings at both ends of operating shaft.
3. Thrust bearings at each end of every blade.
2.04 FLANGE CONNECTORS:
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Ductmate Industries, Inc.
2. Nexus PDQ; Division of Shilco Holdings Inc.
BUCKLEY AFB 15820-4 06/09/09
3. Ward Industries, Inc.; a division of Hart & Cooley, Inc.
B. Description: Add-on or roll-formed, factory-fabricated, slide-on transverse flange connectors, gaskets, and components.
C. Material: Galvanized steel.
D. Gage and Shape: Match connecting ductwork.
2.05 TURNING VANES:
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Ductmate Industries, Inc.
2. Duro Dyne Inc.
3. METALAIRE, Inc.
4. SEMCO Incorporated.
5. Ward Industries, Inc.; a division of Hart & Cooley, Inc.
B. Manufactured Turning Vanes for Metal Ducts: Curved blades of galvanized sheet steel;
support with bars perpendicular to blades set; set into vane runners suitable for duct mounting.
1. Acoustic Turning Vanes: Fabricate airfoil-shaped aluminum extrusions with perforated faces and fibrous-glass fill.
C. General Requirements: Comply with SMACNA's "HVAC Duct Construction Standards -
Metal and Flexible"; Figures 2-3, "Vanes and Vane Runners," and 2-4, "Vane Support in Elbows."
D. Vane Construction: Single wall.
2.06 DUCT-MOUNTED ACCESS DOORS:
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. American Warming and Ventilating; a division of Mestek, Inc.
2. Ductmate Industries, Inc.
3. Greenheck Fan Corporation.
4. McGill AirFlow LLC.
5. Pottorff; a division of PCI Industries, Inc.
6. Ventfabrics, Inc.
B. Duct-Mounted Access Doors: Fabricate access panels according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible"; Figures 2-10, "Duct Access Doors and Panels," and 2-11, "Access Panels - Round Duct."
1. Door:
a. Double wall, rectangular.
b. Galvanized sheet metal with insulation fill and thickness as indicated for duct pressure class.
c. Vision panel.
d. Hinges and Latches: 1-by-1-inch (25-by-25-mm) butt or piano hinge and cam latches.
e. Fabricate doors airtight and suitable for duct pressure class.
2. Frame: Galvanized sheet steel, with bend-over tabs and foam gaskets.
3. Number of Hinges and Locks:
a. Access Doors Less Than 12 Inches (300 mm) Square: No hinges and two sash locks.
b. Access Doors up to 18 Inches (460 mm) Square: Two hinges and two sash locks.
06/09/09 15820-5 BUCKLEY AFB
2.07 FLEXIBLE CONNECTORS:
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Ductmate Industries, Inc.
2. Duro Dyne Inc.
3. Ventfabrics, Inc.
4. Ward Industries, Inc.; a division of Hart & Cooley, Inc.
B. Materials: Flame-retardant or noncombustible fabrics.
C. Coatings and Adhesives: Comply with UL 181, Class 1.
D. Metal-Edged Connectors: Factory fabricated with a fabric strip 3-1/2 inches (89 mm) wide attached to 2 strips of 2-3/4-inch- (70-mm-) wide, 0.028-inch- (0.7-mm-) thick, galvanized sheet steel or 0.032-inch- (0.8-mm-) thick aluminum sheets. Provide metal compatible with connected ducts.
E. Indoor System, Flexible Connector Fabric: Glass fabric double coated with neoprene.
1. Minimum Weight: 26 oz./sq. yd. (880 g/sq. m).
2. Tensile Strength: 480 lbf/inch (84 N/mm) in the warp and 360 lbf/inch (63 N/mm) in the filling.
3. Service Temperature: Minus 40 to plus 200oF (Minus 40 to plus 93oC).
F. Outdoor System, Flexible Connector Fabric: Glass fabric double coated with weatherproof, synthetic rubber resistant to UV rays and ozone.
1. Minimum Weight: 24 oz./sq. yd. (810 g/sq. m).
2. Tensile Strength: 530 lbf/inch (93 N/mm) in the warp and 440 lbf/inch (77 N/mm) in the filling.
3. Service Temperature: Minus 50 to plus 250oF (Minus 45 to plus 121oC).
2.08 FLEXIBLE DUCTS:
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Flexmaster U.S.A., Inc.
2. McGill AirFlow LLC.
3. Ward Industries, Inc.; a division of Hart & Cooley, Inc.
B. Insulated, Flexible Duct: UL 181, Class 1, 2-ply vinyl film supported by helically wound, spring-steel wire; fibrous-glass insulation; aluminized vapor-barrier film.
1. Pressure Rating: 10-inch wg (2500 Pa) positive and 1.0-inch wg (250 Pa) negative.
2. Maximum Air Velocity: 4000 fpm (20 m/s).
3. Temperature Range: Minus 10 to plus 160oF (Minus 23 to plus 71oC).
4. Insulation R-value: Comply with ASHRAE/IESNA 90.1-2004.
C. Flexible Duct Connectors:
1. Clamps: Stainless-steel band with cadmium-plated hex screw to tighten band with a worm-gear action in sizes 3 through 18 inches (75 through 460 mm), to suit duct size.
2.09 DUCT ACCESSORY HARDWARE:
A. Instrument Test Holes: Cast iron or cast aluminum to suit duct material, including screw cap and gasket. Size to allow insertion of pitot tube and other testing instruments and of length to suit duct-insulation thickness.
B. Adhesives: High strength, quick setting, neoprene based, waterproof, and resistant to gasoline and grease.
BUCKLEY AFB 15820-6 06/09/09
PART 3 - EXECUTION
3.01 INSTALLATION:
A. Install duct accessories according to applicable details in SMACNA's "HVAC Duct
Construction Standards - Metal and Flexible" for metal ducts.
B. Install duct accessories of materials suited to duct materials; use galvanized-steel accessories in galvanized-steel, and aluminum accessories in aluminum ducts.
C. Install control dampers at inlet of exhaust fans or exhaust ducts as close as possible to exhaust fan unless otherwise indicated.
D. Install volume dampers at points on supply, return, and exhaust systems where branches extend from larger ducts. Where dampers are installed in ducts having duct liner, install dampers with hat channels of same depth as liner, and terminate liner with nosing at hat channel.
1. Install steel volume dampers in steel ducts.
E. Set dampers to fully open position before testing, adjusting, and balancing.
F. Install test holes at fan inlets and outlets and elsewhere as indicated.
G. Install duct access doors on sides of ducts to allow for inspecting, adjusting, and maintaining accessories and equipment at the following locations:
1. On both sides of duct coils.
2. At drain pans and seals.
3. Downstream from manual volume dampers, control dampers, backdraft dampers, and equipment.
4. At each change in direction and at maximum 50-foot (15-m) spacing.
5. Upstream from turning vanes.
6. Upstream or downstream from duct silencers.
7. Control devices requiring inspection.
8. Elsewhere as indicated.
H. Install access doors with swing against duct static pressure.
I. Access Door Sizes:
1. One-Hand or Inspection Access: 8 by 5 inches (200 by 125 mm).
2. Two-Hand Access: 12 by 6 inches (300 by 150 mm).
3. Head and Hand Access: 18 by 10 inches (460 by 250 mm).
J. Label access doors according to SECTION 15075 - MECHANICAL IDENTIFICATION to indicate the purpose of access door.
K. Install flexible connectors to connect ducts to equipment.
L. For fans developing static pressures of 5-inch wg (1250 Pa) and more, cover flexible connectors with loaded vinyl sheet held in place with metal straps.
M. Connect terminal units to supply ducts using sheet metal ducts. Do not use flexible ducts.
N. Connect diffusers or light troffer boots to ducts directly or with maximum 60-inch (1500-mm) lengths of flexible duct clamped or strapped in place.
O. Connect flexible ducts to metal ducts with draw bands.
P. Install duct test holes where required for testing and balancing purposes.
Q. Install turning vanes at each change of direction 45 degrees or greater in supply ductwork.
3.02 FIELD QUALITY CONTROL:
A. Tests and Inspections:
1. Operate dampers to verify full range of movement.
2. Inspect locations of access doors and verify that purpose of access door can be performed.
06/09/09 15820-7 BUCKLEY AFB
3. Inspect turning vanes for proper and secure installation.
END OF SECTION 15820