LEGEND:
EXISTING FACP
MANUFACTURER:
SILENT KNIGHT
F
X H
X
SD
EXISTING
DETECTION
DEVICES
EXISTING
NOTIFICATION
DEVICES
NEW NOTIFICATION
DEVICES IN AREA 3
NEW NOTIFICATION
DEVICES IN AREA 2
FAA
NEW ACU 4
5 5
3 3
NEW AMBER STROBES
NEW EXTERIOR SPEAKERS
NEW INTERIOR SPEAKERS
BATTERY
BACKUP
NEW LOCAL
OPERATOR
CONTROL
LOC
NEW 120VAC SIGNAL
NEW AUTONOMOUS
CONTROL UNIT MASS
NOTIFICATION SYSTEM
EXISTING REMOTE
ANNUNCIATOR
EXISTING MAIN FIRE ALARM
CONTROL PANEL
2#12 Cu FOR
SUPERVISORY
SIGNAL TO MONITOR
FACP FROM NEW MNS
2#12 Cu FOR
DEACTIVATION OF
NOTIFICATION
APPLIANCES IN
EXISTING FACP
EXISTING EQUIPMENT/CABLE
NEW EQUIPMENT/CABLE
EXISTING TELEPHONE BACKBOARDS LOCATED IN
- TRANSFORMER ROOM 1:124
- JANITOR ROOM 3:124A
- STORAGE ROOM 2:211
TELEPHONE/DATA
SYSTEM DIAGRAM
NTS
FIRE ALARM AND MNS
SYSTEM DIAGRAM
NTS
DUAL LEVEL SWITCHING WITH
OCCUPANCY SENSOR ONE-LINE
NTS
EXTERIOR LIGHTING CONTROL SCHEMATIC
NTS
DOOR CONTROL PANEL. ADJUST LIMIT
SWITCHES AND TORQUE SWITCHES AS
RECOMMENDED BY THE MANUFACTURER
DOOR MOTOR OPERATOR
MOTOR OPERATED DOOR
OVERHEAD DOOR THERMAL
LINK LIMIT SWITCH (ONLY
WHERE INDICATED)
PNEUMATIC SAFETY EDGE
P/E SWITCH
TO FACP
TO PANELBOARD INDICATED
2 #12, 1/2"C.
3 #12, 1/2"C.
OPEN-STOP-CLOSE PUSHBUTTON STATION
PROVIDE ON BOTH SIDES OF DOOR WHERE
INDICATED. PUSHBUTTON STATION IS
FURNISHED WITH DOOR AND INSTALLED BY
CONTRACTOR
30A, 3P, NEMA 1, DISCONNECT
4'-0"
(TYP)2'-0"
FLOOR
TYPICAL MOTORIZED DOOR INSTALLATION
NTS
NEW MANUAL FIRE
DETECTION DEVICES
IN AREA 3
1" C, INSTALLED BY ELECTRICAL
CONTRACTOR, STUBBED INTO
ACCESSIBLE CEILING SPACE
WITH BUSH ENDS AND PULL
CORD. TYPICAL FOR ALL
COMMUNICATION OUTLETS.
EXISTING COMMUNICATION CABINET
- NOTED ON PLANS
INDICATES DATA/TELEPHONE COMBO OUTLET.
PROVIDE (2) CAT 6 PLENUM RATED CABLES
FOR DATA PORTS ROUTED TO NEAREST
COMMUNICATION CABINET. PROVIDE (2) CAT 6
PLENUM RATED CABLES FOR TELEPHONE
PORTS ROUTED TO NEAREST TELEPHONE
BACKBOARD. CABLES INSTALLED AS PART OF
ALTERNATE BID ITEM #1.
3/4" C STUBBED INTO
ACCESSIBLE CEILING SPACE
WITH BUSH ENDS AND PULL
CORD. TYPICAL FOR ALL
COMMUNICATION OUTLETS.
INDICATES WALL TELEPHONE OUTLET.
PROVIDE (1) CAT 6 PLENUM RATED CABLES
FOR TELEPHONE PORT ROUTED TO NEAREST
TELEPHONE BACKBOARD. CABLES INSTALLED
AS PART OF ALTERNATE BID ITEM #1.
W
EXISTING
PUBLIC
ADDRESS
SYSTEM
AMPLIFIER
LEGEND:
EXISTING EQUIPMENT/CABLE
NEW EQUIPMENT/CABLE
2#12 Cu FOR
DEACTIVATION OF
EXISTING PA SYSTEM
6 6
EXISTING/NEW INTERIOR
SPEAKERS
OS
LOCAL
SWITCHES IN
ROOM FOR
LIGHTING
OS
20A/1P
277V NEW OCCUPANCY
SENSOR
LIGHTING IN
ROOM
H 20A/1P
0V
EXISTING TIME
CLOCK
H
TC
LC
C N
TC TC
LATCHING
EXISTING
MECHANICALLY
HELD LIGHTING
CONTACTOR
TO NEW
LIGHTS
C C
CIRCUIT BREAKERS
LOCATED IN EXISTING
LIGHTING PANELS
NEW CONCACTOR
WITH 120 VAC COIL
AND (6) 20 AMP
CONTACTS. NEMA 1
TYPE ENCLOSURE.
H
O
A
NEW HOA SWITCH
LOCATED NEXT TO
EXISTING CLOCK
NOTE:
PROVIDE QUANTITY OF
OUTLETS PER PLANS.
QUANTITIES OF DEVICES ARE
NOT NOTED ON ONE-LINE.
DMS
AS VS
M
G
EXISTING
MAIN DISTRIBUTION SWITCHBOARD "MDS"
1600A 277/480V, 3 PHASE, 4 WIRE
EXISTING
1600A 3P
EXISTING 100kVA
TRANSFORMER
EXISTING 100A EMERGENCY
POWER DISCONNECT TO EMERGENCY
TRANSFORMER
(3#350 kcmil, 1#4 GRD)
EXISTING 3"C
TYPICAL MOTORIZED DOOR INSTALLATION
NTS
NOTES:
1. EXISTING ELECTRICAL LOAD ON MAIN SWITCHBOARD
NOT SHOWN FOR CLARITY.
NOTES:
REPLACE EXISTING 275A 3P BREAKER WITH NEW 300A 3P
BREAKER. MATCH EXISTING MANUFACTURER, AIC
RATING AND TYPE WITH EXISTING.
ROUTE NEW CONDUCTORS IN EXISTING CONDUIT.2
300A 3P
VA
RTU-1
MCA = 251A
MOCP = 300A
NEW
400A, 3P
300A FRS-R
WP DISCONNECT
EXISTING
1600A 3P
PAGE NUMBER
SHEET NO.
OF
DATE
DRAWING TITLE:
COMMUNICATION
PROJECT TITLE:
PROJECT NUMBER:
DESIGNED BY
DRAWN BY
SAFETY
USING AGENCY
SECURITY POLICE
CHIEF OF ENGRG.
BASE CIVIL ENGINEER
BIO-ENVIR. ENGR.
CHIEF OF OPS. FIRE CHIEF
MSG COMMANDER
WING COMMANDER
MARK REVISION DATE
COLORADO
OFFICE OF THE BASE CIVIL ENGR.
AIR NATIONAL GUARD
Burns & McDonnell Proj No 51047
CRWU 06-2071
6-9-2009
REPAIR WING
BUILDING 706
HEADQUARTERS
E502
L. CREED
M. McNUTT
FIRE ALARM/MNS
SYSTEM
DIAGRAMS
NOTES:
1. ROUTE NEW COUNDUIT AND
CABLES FOR NEW TELEPHONE
OUTLETS TO NEAREST EXISTING
TELEPHONE BACKBOARD FOR
VOICE ROUTE CONDUITS AND
CABLES FOR NEW DATA OUTLETS
TO NEAREST COMMUNICATION
CLOSET FOR DATA OUTLETS.
J:\BUCKLEY AFB\51047-BUCKLEY WING HQ RREPAIR\CADD\ELEC\51047E502.DWG 07-20-2009 15:18 LCREED