SECTION 15055 REPAIR WING HEADQUARTERS, BLDG 706
MOTORS CRWU 06-2071
06/09/09 15055-1 BUCKLEY AFB
SECTION 15055 - MOTORS
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section includes basic requirements for factory-installed motors.
1.02 REFERENCES:
A. Applicable Standards:
1. 29 CFR - Labor, Chapter XVII - Occupational Safety and Health Administration, Department of Labor, Part 1910 - "Occupational Safety and Health Standards," Subpart B
- "Regulations Relating to Labor," Section 1910.7 - "Definition and Requirements for a Nationally Recognized Testing Laboratory."
2. InterNational Electrical Testing Association (NETA):
a. ATS - Acceptance Testing Specifications for Electrical Power Distribution
Equipment and Systems.
3. National Electrical Manufacturers Association (NEMA):
a. MG 1 - Motors and Generators.
4. National Fire Protection Association (NFPA):
a. 70 - National Electrical Code.
1.03 DEFINITIONS:
A. Factory-Installed Motor: A motor installed by motorized-equipment manufacturer as a component of equipment.
1.04 QUALITY ASSURANCE:
A. Testing Agency Qualifications: An independent agency, with the experience and capability to conduct the testing indicated, that is a member company of the InterNational Electrical Testing Association or is a nationally recognized testing laboratory (NRTL) as defined by OSHA in 29 CFR 1910.7, and that is acceptable to authorities having jurisdiction.
1. Testing Agency's Field Supervisor: Person currently certified by the InterNational
Electrical Testing Association or the National Institute for Certification in Engineering Technologies to supervise on-site testing specified in PART 3.
B. Source Limitations: Obtain field-installed motors through one source from a single manufacturer.
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
D. Comply with NFPA 70.
1.05 COORDINATION:
A. Coordinate features of motors, installed units, and accessory devices and features that comply with the following:
1. Compatible with the following:
a. Magnetic controllers.
b. Multispeed controllers.
c. Reduced-voltage controllers.
BUCKLEY AFB 15055-2 06/09/09
2. Designed and labeled for use with variable frequency controllers, and suitable for use throughout speed range without overheating.
3. Matched to torque and horsepower requirements of the load.
4. Matched to ratings and characteristics of supply circuit and required control sequence.
PART 2 - PRODUCTS
2.01 MOTOR REQUIREMENTS:
A. Motor requirements apply to factory-installed motors except as follows:
1. Different ratings, performance, or characteristics for motor are specified in another Section.
2. Motorized-equipment manufacturer requires ratings, performance, or characteristics, other than those specified in this Section, to meet performance specified.
2.02 MOTOR CHARACTERISTICS:
A. Motors 3/4 HP and Larger: Three phase.
B. Motors Smaller Than 3/4 HP: Single phase.
C. Frequency Rating: 60 Hz.
D. Voltage Rating: NEMA standard voltage selected to operate on nominal circuit voltage to which motor is connected.
E. Service Factor: 1.15 for open dripproof motors; 1.0 for totally enclosed motors.
F. Duty: Continuous duty at ambient temperature of 105oF (40oC) and at altitude of 3300 feet
(1005 m) above sea level.
G. Capacity and Torque Characteristics: Sufficient to start, accelerate, and operate connected loads at designated speeds, at installed altitude and environment, with indicated operating sequence, and without exceeding nameplate ratings or considering service factor.
H. Enclosure: Open dripproof.
2.03 POLYPHASE MOTORS:
A. Description: NEMA MG 1, Design B, medium induction motor.
B. Efficiency: Premium, as defined in NEMA MG 1.
C. Stator: Copper windings, unless otherwise indicated.
1. Multispeed motors shall have separate winding for each speed.
D. Rotor: Squirrel cage, unless otherwise indicated.
E. Bearings: Double-shielded, prelubricated ball bearings suitable for radial and thrust loading.
F. Temperature Rise: Match insulation rating, unless otherwise indicated.
G. Insulation: Class F, unless otherwise indicated.
H. Code Letter Designation:
1. Motors 15 HP and Larger: NEMA starting Code F or Code G.
2. Motors Smaller Than 15 HP: Manufacturer's standard starting characteristic.
I. Enclosure: Cast iron for motors 7.5 hp and larger; rolled steel for motors smaller than 7.5 hp.
1. Finish: Gray enamel.
2.04 POLYPHASE MOTORS WITH ADDITIONAL REQUIREMENTS:
A. Motors Used with Reduced-Inrush Controllers: Match wiring connection requirements for controller with required motor leads. Provide terminals in motor terminal box, suited to control method.
06/09/09 15055-3 BUCKLEY AFB
B. Motors Used with Variable Frequency Controllers: Ratings, characteristics, and features coordinated with and approved by controller manufacturer.
1. Designed with critical vibration frequencies outside operating range of controller output.
2. Temperature Rise: Matched to rating for Class B insulation.
3. Insulation: Class H.
4. Thermal Protection: Comply with NEMA MG 1 requirements for thermally protected motors.
C. Rugged-Duty Motors: Totally enclosed, with 1.25 minimum service factor, greased bearings, integral condensate drains, and capped relief vents. Windings insulated with non-hygroscopic material.
1. Finish: Chemical-resistant paint over corrosion-resistant primer.
D. Source Quality Control for Field-Installed Motors: Perform the following tests on each motor according to NEMA MG 1:
1. Measure winding resistance.
2. Read no-load current and speed at rated voltage and frequency.
3. Measure locked rotor current at rated frequency.
4. Perform high-potential test.
2.05 SINGLE-PHASE MOTORS:
A. Type: One of the following, to suit starting torque and requirements of specific motor application:
1. Permanent-split capacitor.
2. Split-phase start, capacitor run.
3. Capacitor start, capacitor run.
B. Shaded-Pole Motors: For motors 1/20 hp and smaller only.
C. Thermal Protection: Internal protection to automatically open power supply circuit to motor when winding temperature exceeds a safe value calibrated to temperature rating of motor insulation. Thermal-protection device shall automatically reset when motor temperature returns to normal range.
D. Bearings: Ball type for belt-connected motors and other motors with high radial forces on motor shaft; sealed, prelubricated-sleeve type for other single-phase motors.
E. Source Quality Control for Field-Installed Motors: Perform the following tests on each motor according to NEMA MG 1:
1. Measure winding resistance.
2. Read no-load current and speed at rated voltage and frequency.
3. Measure locked rotor current at rated frequency.
4. Perform high-potential test.
PART 3 - EXECUTION - Not Applicable.
END OF SECTION 15055