FAN
MS
D
X
FILTER
ERU-1 AND RTU-3 (E)
HOA
M
EXHAUST
AIR
START / STOP
SUPPLY AIR
TO VAV
BOXES
FAN
MS
HOA
M
START / STOP
M
ENERGY
RECOVERY
UNIT (ERU-1)
MODIFICATIONS TO SEQUENCE OF OPERATIONS:
A.
B.
C.
1.
2.
THE ENERGY RECOVERY UNIT (ERU-1) SHALL BE SUPPLIED WITH A FACTORY
MOUNTED CONTROL PANEL THAT CONTAINS A DAMPER CONTROL TIMER.
ERU-1 SHALL ENERGIZE WHENEVER RTU-3 IS IN OCCUPIED MODE. WHEN
DAMPER CONTROL TIMER CALLS FOR THE DAMPER POSITION CHANGE, THE
ELECTRIC SOLENOID VALVE SHALL CHANGE THE DAMPER POSITION. THE
ERU-1 SHALL OPERATE THROUGH FACTORY CONTROL SEQUENCE.
WHEN RTU-3 IS IN MINIMUM VENTILATION OR OFF, MOTORIZED DAMPER M-1
SHALL BE OPEN AND M-2 SHALL BE CLOSED. WHEN RTU-3 IS OPERATING IN
ECONOMIZER MODE, M-1 SHALL BE CLOSED AND M-2 SHALL BE OPEN.
ALARMS:
WHEN THE DISCHARGE AIR TEMPERATURE SENSES TEMPERATURE
BELOW 40 DEG F OR ABOVE 85 DEG F, THE RTU-3, EF-8 AND ERU-1
SHALL SHUT DOWN AND MOTORIZED DAMPERS SHALL CLOSE.
WHEN THE EMERGENCY SHUT OFF IS ACTIVATED ALL EXHAUST FANS
ON AREAS 1, 2, AND 3, RTU-1 THROUGH 4 AND ERU-1 SHALL SHUT DOWN
AND ALL MOTORIZED DAMPERS SHALL CLOSE.
M
EF-8
CONTROL
PANEL
INPUTS
DESCRIPTION ITEM
DCC OUTPUTS
DESCRIPTION ITEM
MIXED AIR TEMPERATURE
3BUILDING TIME CLOCK
4EMERGENCY SHUT-OFF
2OUTSIDE AIR TEMPERATURE
5EF STATUS
6RTU FAN STATUS
CONTROL
PANEL
OAT2
BTC
ESO4
7MOTORIZED DAMPER STATUS
10FAN START/STOP
11DAMPER OPEN/CLOSE
12EF START/STOP
H
C
CONTROL
PANEL
INPUTS
DESCRIPTION ITEM
DCC OUTPUTS
DESCRIPTION ITEM
SPACE TEMPERATURE
3ENTERING AIR TEMPERATURE
2MOTORIZED DAMPER
4DAMPER POSITION
5HEATING WATER VALVE
VAV (TYPICAL)
M 2 4
CONTROL
PANEL
SUPPLY AIR
FROM RTU
SUPPLY AIR
TO SPACE
TS1
VAV BOX SEQUENCE OF OPERATIONS:
VAV BOX SHALL CONSIST OF A DAMPER, HEATING COILS AND UNIT
MOUNTED CONTROL PANEL.
COOLING MODE:
a) WHEN THE ENTERING AIR TEMPERATURE IS BELOW 65 DEG F, THE VAV BOX SHALL MODULATE TO MAINTAIN SPACE
TEMPERATURE SETPOINT OF 78 DEG F.
b) THE HEATING COIL CONTROL VALVE SHALL BE CLOSED.
HEATING MODE:
a) WHEN THE ENTERING AIR TEMPERATURE IS ABOVE 65 DEG F, VAV
BOX SHALL BE SET TO THE MINIMUM OPEN POSTION.
b) THE HEATING COIL CONTROL VALVE SHALL MODULATE TO
MAINTAIN A SPACE TEMPERATURE OF 70 DEG F.
1.
2.
A.
CONTRACTOR SHALL ENSURE ALL VAV BOXES (NEW AND EXISTING) IN
AREAS 1, 2, AND 3 ARE CONNECTED TO THE DIRECT DIGITAL CONTROL
(DDC) SYSTEM AND ARE CAPABLE OF BEING RESET REMOTELY FROM THE
DDC SYSTEM.
B.
SD
RETURN
AIR
SD
OSA/ EA
OSA/ EA
DP
FILTER DIFFERENTIAL PRESSURE 8
DUCT PRESSURE SENSOR 9
CONTROL
PANEL
EAT3
CT
CT
OUTSIDE
AIR
RELIEF
AIR
G
EXISTING
EXISTING
MAT
M
7 11
M-1 M-2
RTU-3 EXISTING SEQUENCE OF OPERATIONS:
A.
B.
C.
UNIT STARTS BY TIME-CLOCK OR MANUAL OFF-ON-AUTO SWITCH. PACKAGE
CONTROLS BY UNIT MANUFACTURER CONTROL THE VAV, ECONOMIZER AND
D-X COIL SECTIONS. UNITS STOP BY TIME-CLOCK OR MANUAL OFF-ON-AUTO
SWITCH.
WHEN UNIT IS IN MANUAL "OFF" POSITION, BUILDING OCCUPIED TEMPERATURE
IS BY- PASSED, BUT UNIT SHALL CONTINUE TO OPERATE FROM NIGHT
SET-BACK AND MIXED AIR THERMOSTATS (SEE NEXT PARAGRAPH). NIGHT
SET-BACK THERMOSTATS (NSB) START THE UNIT WHEN THE INDOOR
TEMPERATURE REACHES 60 DEGREES F. (ADJ). AVERAGING ELEMENT
THERMOSTATS START THE UNIT WHEN MIXED AIR CHAMBERS REACH 45
DEGREES F. (ADJ). ECONOMIZER SECTIONS ARE LOCKED OUT WHEN UNITS
ARE STARTED BY THESE THERMOSTATS AND UNITS RUN UNTIL THERMOSTATS
ARE SATISFIED. EACH NIGHT SET-BACK THERMOSTAT HAS A DIFFERENTIAL OF
5 DEGREES AND THE MIXED AIR THERMOSTAT HAS A DIFFERENTIAL OF 10
DEGREES.
THE FOLLOWING SAFETY DEVICES SHALL BE HARD-WIRED BACK TO THE
SUPPLY MOTOR AND ECONOMIZER DAMPER CONTROL: SUPPLY AND RETURN
AIR SMOKE DETECTORS AND FREEZE-STAT. UPON ACTIVATION OF ANY
SAFETY DEVICE, SUPPLY FAN STOP AND ECONOMIZER DAMPERS RETURN TO
NORMAL POSITIONS. SAFETY DEVICES SHALL REQUIRE MANUAL RESET.
PAGE NUMBER
SHEET NO.
OF
DATE
DRAWING TITLE:
COMMUNICATION
PROJECT TITLE:
PROJECT NUMBER:
DESIGNED BY
DRAWN BY
SAFETY
USING AGENCY
SECURITY POLICE
CHIEF OF ENGRG.
BASE CIVIL ENGINEER
BIO-ENVIR. ENGR.
CHIEF OF OPS. FIRE CHIEF
MSG COMMANDER
WING COMMANDER
MARK REVISION DATE
COLORADO
OFFICE OF THE BASE CIVIL ENGR.
AIR NATIONAL GUARD
Burns & McDonnell Proj No 51047
CRWU 06-2071
6-9-2009
REPAIR WING
BUILDING 706
HEADQUARTERS
M201
P. HUNTZINGER
B. BIRGE
CONTROL
SCHEMATIC
CORRECTIONS