SECTION 15815 REPAIR WING HEADQUARTERS, BLDG 706
METAL DUCTS CRWU 06-2071
06/09/09 15815-1 BUCKLEY AFB
SECTION 15815 - METAL DUCTS
PART 1 - GENERAL
1.01 SUMMARY:
A. Section Includes:
1. Single-wall rectangular ducts and fittings.
2. Sheet metal materials.
3. Sealants and gaskets.
4. Hangers and supports.
B. Related Work Specified Elsewhere:
1. For dampers, sound-control devices, duct-mounting access doors and panels, turning vanes, and flexible ducts: SECTION 15820 - DUCT ACCESSORIES.
2. For testing, adjusting, and balancing requirements for metal ducts: SECTION 15950 -
TESTING, ADJUSTING, AND BALANCING.
1.02 REFERENCES:
A. Applicable Standards (latest edition):
1. American Society of Civil Engineers/Structural Engineering Institute (ASCE/SEI):
a. 7 - Minimum Design Loads for Buildings and Other Structures.
2. American Welding Society (AWS):
a. D1.1/D1.1M - Structural Welding Code - Steel.
b. D9.1M/D9.1 - Sheet Metal Welding Code.
3. ASTM International (ASTM):
a. A36/A36M - Carbon Structural Steel.
b. A480/A480M - General Requirements for Flat-Rolled Stainless and Heat-Resisting
Steel Plate, Sheet, and Strip.
c. A492 - Stainless Steel Rope Wire.
d. A603 - Zinc-Coated Steel Structural Wire Rope.
e. A653/A653M - Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron. Alloy-Coated
(Galvannealed) by the Hot-Dip Process.
f. A1008/A1008M - Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength
Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable.
g. B209 - Aluminum and Aluminum-Alloy Sheet and Plate.
h. B209M - Aluminum and Aluminum-Alloy Sheet and Plate [Metric].
i. C518 - Steady-State Thermal Transmission Properties by Means of the Heat Flow
Meter Apparatus.
j. C534 - Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and
Tubular Form.
k. C916 - Adhesives for Duct Thermal Insulation.
l. C920 - Elastomeric Joint Sealants.
m. D3363 - Test Method for Film Hardness by Pencil Test.
n. E84 - Test Method for Surface Burning Characteristics of Building Materials.
o. E488 - Test Methods for Strength of Anchors in Concrete and Masonry Elements.
4. National Air Duct Cleaners Association (NADCA):
a. 1992 - Mechanical Cleaning of Non-Porous Air Conveyance System Components.
BUCKLEY AFB 15815-2 06/09/09
b. ACR - Assessment, Cleaning and Restoration of HVAC Systems.
5. National Fire Protection Association (NFPA):
a. 90A - Installation of Air Conditioning and Ventilating Systems (ANSI).
b. 90B - Installation of Warm Air Heating and Air Conditioning Systems (ANSI).
c. 96 - Ventilation Control and Fire Protection of Commercial Cooking Operations
(ANSI).
6. The North American Insulation Manufactures Association (NAIMA):
a. AH124 - Fibrous Glass Duct Liner Standard.
7. Sheet Metal and Air Conditioning Contractors' National Association (SMACNA):
a. Duct Cleanliness for New Construction Guidelines.
b. HVAC Air Duct Leakage Test Manual.
c. HVAC Duct Construction Standards - Metal and Flexible.
d. Seismic Restraint Manual: Guidelines for Mechanical Systems.
8. Underwriters Laboratories Inc. (UL):
a. 181 - Factory-Made Air Ducts and Air Connectors.
b. 723 - Test for Surface Burning Characteristics of Building Materials.
1.03 PERFORMANCE REQUIREMENTS:
A. Delegated Duct Design: Duct construction, including sheet metal thicknesses, seam and joint construction, reinforcements, and hangers and supports, shall comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" and performance requirements and design criteria indicated in "Duct Schedule" Article.
B. Structural Performance: Duct hangers and supports shall withstand the effects of gravity loads and stresses within limits and under conditions described in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible".
1. Seismic Hazard Level C: Seismic force to weight ratio, 0.15.
C. Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in
ASHRAE 62.1-2004.
1.04 SUBMITTALS:
A. General: Submit each item in this Article in accordance with SECTION 15050 - BASIC
MECHANICAL MATERIALS AND METHODS.
B. Product Data: For each type of the following products:
1. Liners and adhesives.
2. Sealants and gaskets.
3. Seismic-restraint devices.
4. Leakage Test Report for Prerequisite EA 2: Documentation of work performed for compliance with ASHRAE/IESNA 90.1-2004, Section 6.4.4.2.2 - "Duct Leakage Tests."
5. Duct-Cleaning Test Report for Prerequisite EQ 1: Documentation of work performed for compliance with ASHRAE 62.1-2004, Section 7.2.4 - "Ventilation System Start-Up."
C. Welding certificates.
D. Field quality-control reports.
1.05 QUALITY ASSURANCE:
A. Welding Qualifications: Qualify procedures and personnel according to the following:
1. AWS D1.1/D1.1M, "Structural Welding Code - Steel," for hangers and supports.
2. AWS D1.2/D1.2M, "Structural Welding Code - Aluminum," for aluminum supports.
3. AWS D9.1M/D9.1, "Sheet Metal Welding Code," for duct joint and seam welding.
06/09/09 15815-3 BUCKLEY AFB
B. ASHRAE Compliance: Applicable requirements in ASHRAE 62.1-2004, Section 5 - "Systems and Equipment" and Section 7 - "Construction and System Start-Up."
C. ASHRAE/IESNA Compliance: Applicable requirements in ASHRAE/IESNA 90.1-2004, Section 6.4.4 - "HVAC System Construction and Insulation."
PART 2 - PRODUCTS
2.01 SINGLE WALL RECTANGULAR DUCTS AND FITTINGS:
A. General Fabrication Requirements: Comply with SMACNA's "HVAC Duct Construction
Standards - Metal and Flexible" based on indicated static-pressure class unless otherwise indicated.
B. Transverse Joints: Select joint types and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 1-4, "Transverse (Girth) Joints," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."
C. Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 1-5, "Longitudinal Seams - Rectangular Ducts," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."
D. Elbows, Transitions, Offsets, Branch Connections, and Other Duct Construction: Select types and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Chapter 2, "Fittings and Other Construction," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."
2.02 SHEET METAL MATERIALS:
A. General Material Requirements: Comply with SMACNA's "HVAC Duct Construction
Standards - Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections.
B. Galvanized Sheet Steel: Comply with ASTM A653/A653M.
1. Galvanized Coating Designation: G90 (Z275).
C. Reinforcement Shapes and Plates: ASTM A36/A36M, steel plates, shapes, and bars; black and galvanized.
1. Where black- and galvanized-steel shapes and plates are used to reinforce aluminum ducts, isolate the different metals with butyl rubber, neoprene, or EPDM gasket materials.
D. Tie Rods: Galvanized steel, 1/4-inch (6-mm) minimum diameter for lengths 36 inches (900
mm) or less; 3/8-inch (10-mm) minimum diameter for lengths longer than 36 inches (900 mm).
2.03 SEALANT AND GASKETS:
A. General Sealant and Gasket Requirements: Surface-burning characteristics for sealants and gaskets shall be a maximum flame-spread index of 25 and a maximum smoke-developed index of 50 when tested according to UL 723; certified by an NRTL.
B. Two-Part Tape Sealing System:
BUCKLEY AFB 15815-4 06/09/09
1. Tape: Woven cotton fiber impregnated with mineral gypsum and modified acrylic/silicone activator to react exothermically with tape to form hard, durable, airtight seal.
2. Tape Width: 3 inches (76 mm).
3. Sealant: Modified styrene acrylic.
4. Water resistant.
5. Mold and mildew resistant.
6. Maximum Static-Pressure Class: 10-inch wg (2500 Pa), positive and negative.
7. Service: Indoor and outdoor.
8. Service Temperature: Minus 40 to plus 200ºF (Minus 40 to plus 93ºC).
9. Substrate: Compatible with galvanized sheet steel (both PVC coated and bare), stainless steel, or aluminum.
C. Water-Based Joint and Seam Sealant:
1. Application Method: Brush on.
2. Solids Content: Minimum 65%.
3. Shore A Hardness: Minimum 20.
4. Water resistant.
5. Mold and mildew resistant.
6. VOC: Maximum 75 g/L (less water).
7. Maximum Static-Pressure Class: 10-inch wg (2500 Pa), positive and negative.
8. Service: Indoor or outdoor.
9. Substrate: Compatible with galvanized sheet steel (both PVC coated and bare), stainless steel, or aluminum sheets.
D. Flanged Joint Sealant: Comply with ASTM C920.
1. General: Single-component, acid-curing, silicone, elastomeric.
2. Type: S.
3. Grade: NS.
4. Class: 25.
5. Use: O.
E. Flange Gaskets: Butyl rubber, neoprene, or EPDM polymer with polyisobutylene plasticizer.
2.04 HANGERS AND SUPPORTS:
A. Hanger Rods for Noncorrosive Environments: Cadmium-plated steel rods and nuts.
B. Strap and Rod Sizes: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 4-1 (Table 4-1M), "Rectangular Duct Hangers Minimum Size," and Table 4-2, "Minimum Hanger Sizes for Round Duct."
C. Steel Cables for Galvanized-Steel Ducts: Galvanized steel complying with ASTM A603.
D. Steel Cable End Connections: Cadmium-plated steel assemblies with brackets, swivel, and bolts designed for duct hanger service; with an automatic-locking and clamping device.
E. Duct Attachments: Sheet metal screws, blind rivets, or self-tapping metal screws; compatible with duct materials.
F. Trapeze and Riser Supports:
1. Supports for Galvanized-Steel Ducts: Galvanized-steel shapes and plates.
PART 3 - EXECUTION
3.01 DUCT INSTALLATION:
06/09/09 15815-5 BUCKLEY AFB
A. Drawing plans, schematics, and diagrams indicate general location and arrangement of duct system. Indicated duct locations, configurations, and arrangements were used to size ducts and calculate friction loss for air-handling equipment sizing and for other design considerations.
Install duct systems as indicated unless deviations to layout are approved on Shop Drawings and Coordination Drawings.
B. Install ducts according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" unless otherwise indicated.
C. Install ducts with fewest possible joints.
D. Install factory- or shop-fabricated fittings for changes in direction, size, and shape and for branch connections.
E. Unless otherwise indicated, install ducts vertically and horizontally, and parallel and perpendicular to building lines.
F. Install ducts close to walls, overhead construction, columns, and other structural and permanent enclosure elements of building.
G. Install ducts with a clearance of 1 inch (25 mm), plus allowance for insulation thickness.
H. Route ducts to avoid passing through transformer vaults and electrical equipment rooms and enclosures.
I. Where ducts pass through non-fire-rated interior partitions and exterior walls and are exposed to view, cover the opening between the partition and duct or duct insulation with sheet metal flanges of same metal thickness as the duct. Overlap openings on four sides by at least 1-1/2 inches (38 mm).
J. Where ducts pass through fire-rated interior partitions and exterior walls, install fire dampers.
Comply with requirements in SECTION 15820 - DUCT ACCESSORIES for fire and smoke dampers.
K. Protect duct interiors from moisture, construction debris and dust, and other foreign materials.[ Comply with SMACNA's "Duct Cleanliness for New Construction Guidelines."]
3.02 INSTALLATION OF EXPOSED DUCTWORK:
A. Protect ducts exposed in finished spaces from being dented, scratched, or damaged.
B. Trim duct sealants flush with metal. Create a smooth and uniform exposed bead. Do not use two-part tape sealing system.
C. Grind welds to provide smooth surface free of burrs, sharp edges, and weld splatter. When welding stainless steel with a No. 3 or 4 finish, grind the welds flush, polish the exposed welds, and treat the welds to remove discoloration caused by welding.
D. Maintain consistency, symmetry, and uniformity in the arrangement and fabrication of fittings, hangers and supports, duct accessories, and air outlets.
E. Repair or replace damaged sections and finished work that does not comply with these requirements.
3.03 DUCT SEALING:
A. Seal ducts for duct static-pressure, seal classes, and leakage classes specified in "Duct
Schedule" Article according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."
B. Seal ducts to the following seal classes according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible":
1. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."
2. Outdoor, Supply-Air Ducts: Seal Class A.
3. Outdoor, Exhaust Ducts: Seal Class C.
BUCKLEY AFB 15815-6 06/09/09
4. Unconditioned Space, Supply-Air Ducts in Pressure Classes 2-Inch wg (500 Pa) and Lower: Seal Class B.
5. Unconditioned Space, Supply-Air Ducts in Pressure Classes Higher Than 2-Inch wg (500 Pa): Seal Class A.
6. Unconditioned Space, Exhaust Ducts: Seal Class C.
7. Unconditioned Space, Return-Air Ducts: Seal Class B.
8. Conditioned Space, Supply-Air Ducts in Pressure Classes 2-Inch wg (500 Pa) and Lower:
Seal Class C.
9. Conditioned Space, Supply-Air Ducts in Pressure Classes Higher Than 2-Inch wg (500
Pa): Seal Class B.
10. Conditioned Space, Exhaust Ducts: Seal Class B.
11. Conditioned Space, Return-Air Ducts: Seal Class C.
3.04 HANGER AND SUPPORT INSTALLATION:
A. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible,"
Chapter 4, "Hangers and Supports."
B. Building Attachments: Concrete inserts, powder-actuated fasteners, or structural-steel fasteners appropriate for construction materials to which hangers are being attached.
1. Where practical, install concrete inserts before placing concrete.
2. Install powder-actuated concrete fasteners after concrete is placed and completely cured.
3. Use powder-actuated concrete fasteners for standard-weight aggregate concretes or for slabs more than 4 inches (100 mm) thick.
4. Do not use powder-actuated concrete fasteners for lightweight-aggregate concretes or for slabs less than 4 inches (100 mm) thick.
C. Hanger Spacing: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and
Flexible," Table 4-1 (Table 4-1M), "Rectangular Duct Hangers Minimum Size," and Table 4-2, "Minimum Hanger Sizes for Round Duct," for maximum hanger spacing; install hangers and supports within 24 inches (610 mm) of each elbow and within 48 inches (1200 mm) of each branch intersection.
D. Hangers Exposed to View: Threaded rod and angle or channel supports.
E. Support vertical ducts with steel angles or channel secured to the sides of the duct with welds, bolts, sheet metal screws, or blind rivets; support at each floor and at a maximum intervals of 16 feet (5 m).
F. Install upper attachments to structures. Select and size upper attachments with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used.
3.05 CONNECTIONS:
A. Make connections to equipment with flexible connectors complying with SECTION 15820 -
DUCT ACCESSORIES.
B. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for branch, outlet and inlet, and terminal unit connections.
3.06 PAINTING:
A. Paint interior of metal ducts that are visible through registers and grilles and that do not have duct liner. Apply one coat of flat, black, latex paint over a compatible galvanized-steel primer.
Paint materials and application requirements are specified in DIVISION 9 painting Sections.
06/09/09 15815-7 BUCKLEY AFB
3.07 FIELD QUALITY CONTROL:
A. Perform tests and inspections.
B. Leakage Tests:
1. Comply with SMACNA's "HVAC Air Duct Leakage Test Manual." Submit a test report for each test.
2. Test the following systems:
a. Supply Ducts with a Pressure Class of 2-Inch wg (500 Pa) or Higher: Test representative duct sections totaling no less than 50 percent of total installed duct area for each designated pressure class.
b. Exhaust Ducts with a Pressure Class of 2-Inch wg (500 Pa) or Higher: Test representative duct sections totaling no less than 50% of total installed duct area for each designated pressure class.
c. Outdoor Air Ducts with a Pressure Class of 2-Inch wg (500 Pa) or Higher: Test representative duct sections totaling no less than 50% of total installed duct area for each designated pressure class.
3. Disassemble, reassemble, and seal segments of systems to accommodate leakage testing and for compliance with test requirements.
4. Test for leaks before applying external insulation.
5. Conduct tests at static pressures equal to maximum design pressure of system or section being tested. If static-pressure classes are not indicated, test system at maximum system design pressure. Do not pressurize systems above maximum design operating pressure.
6. Give seven days' advance notice for testing.
C. Duct System Cleanliness Tests:
1. Visually inspect duct system to ensure that no visible contaminants are present.
2. Test sections of metal duct system, chosen randomly by Owner, for cleanliness according to "Vacuum Test" in NADCA ACR, "Assessment, Cleaning and Restoration of HVAC Systems."
a. Acceptable Cleanliness Level: Net weight of debris collected on the filter media shall not exceed 0.75 mg/100 sq. cm.
D. Duct system will be considered defective if it does not pass tests and inspections.
E. Prepare test and inspection reports.
3.08 DUCT CLEANING:
A. Clean new and existing duct system(s) before testing, adjusting, and balancing.
B. Use service openings for entry and inspection.
1. Create new openings and install access panels appropriate for duct static-pressure class if required for cleaning access. Provide insulated panels for insulated or lined duct. Patch insulation and liner as recommended by duct liner manufacturer. Comply with DIVISION 15 Section "Duct Accessories" for access panels and doors.
2. Disconnect and reconnect flexible ducts as needed for cleaning and inspection.
3. Remove and reinstall ceiling to gain access during the cleaning process.
C. Particulate Collection and Odor Control:
1. When venting vacuuming system inside the building, use HEPA filtration with 99.97% collection efficiency for 0.3-micron-size (or larger) particles.
2. When venting vacuuming system to outdoors, use filter to collect debris removed from
HVAC system, and locate exhaust downwind and away from air intakes and other points of entry into building.
D. Clean the following components by removing surface contaminants and deposits:
BUCKLEY AFB 15815-8 06/09/09
1. Air outlets and inlets (registers, grilles, and diffusers).
2. Supply, return, and exhaust fans including fan housings, plenums (except ceiling supply and return plenums), scrolls, blades or vanes, shafts, baffles, dampers, and drive assemblies.
3. Air-handling unit internal surfaces and components including mixing box, coil section, condensate drain pans, filters and filter sections, and condensate collectors and drains.
4. Coils and related components.
5. Return-air ducts, dampers, actuators, and turning vanes except in ceiling plenums and mechanical equipment rooms.
6. Supply-air ducts, dampers, actuators, and turning vanes.
7. Dedicated exhaust and ventilation components and makeup air systems.
3.09 START UP:
A. Air Balance: Comply with requirements in SECTION 15950 - TESTING, ADJUSTING, AND
BALANCING.
3.10 DUCT SCHEDULE:
A. Supply Ducts:
1. Ducts Connected to Terminal Units:
a. Pressure Class: Positive 1-inch wg (250 Pa).
b. Minimum SMACNA Seal Class: C.
c. SMACNA Leakage Class for Rectangular: 24.
2. Ducts Connected to Variable-Air-Volume Air-Handling Units:
a. Pressure Class: Positive 3-inch wg (750 Pa).
b. Minimum SMACNA Seal Class: B.
c. SMACNA Leakage Class for Rectangular: 12.
3. Ducts Connected to Equipment Not Listed Above:
a. Pressure Class: Positive 2-inch wg (500 Pa).
b. Minimum SMACNA Seal Class: B.
c. SMACNA Leakage Class for Rectangular: 12.
B. Return Ducts:
1. Ducts Connected to Air-Handling Units:
a. Pressure Class: Positive or negative 3-inch wg (750 Pa).
b. Minimum SMACNA Seal Class: B.
c. SMACNA Leakage Class for Rectangular: 12.
2. Ducts Connected to Equipment Not Listed Above:
a. Pressure Class: Positive or negative 3-inch wg (750 Pa).
b. Minimum SMACNA Seal Class: B.
c. SMACNA Leakage Class for Rectangular: 12.
C. Exhaust Ducts:
1. Ducts Connected to Fans Exhausting (ASHRAE 62.1, Class 1 and 2) Air:
a. Pressure Class: Negative 1-inch wg (250 Pa).
b. Minimum SMACNA Seal Class: C if negative pressure, and A if positive pressure.
c. SMACNA Leakage Class for Rectangular: 12.
2. Ducts Connected to Equipment Not Listed Above:
a. Pressure Class: Positive or negative 3-inch wg (750 Pa).
b. Minimum SMACNA Seal Class: B if negative pressure, and A if positive pressure.
c. SMACNA Leakage Class for Rectangular: 12.
06/09/09 15815-9 BUCKLEY AFB
3. Ducts Connected to Air-Handling Units:
a. Pressure Class: Positive or negative 2-inch wg (500 Pa).
b. Minimum SMACNA Seal Class: B.
c. SMACNA Leakage Class for Rectangular: 12.
4. Ducts Connected to Equipment Not Listed Above:
a. Pressure Class: Positive or negative 2-inch wg (500 Pa).
b. Minimum SMACNA Seal Class: B.
c. SMACNA Leakage Class for Rectangular: 12.
D. Intermediate Reinforcement:
1. Galvanized-Steel Ducts: Galvanized steel.
E. Elbow Configuration:
1. Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards -
Metal and Flexible," Figure 2-2, "Rectangular Elbows."
a. Velocity 1000 fpm (5 m/s) or Lower:
(1) Radius Type RE 1 with minimum 0.5 radius-to-diameter ratio.
(2) Mitered Type RE 4 without vanes.
b. Velocity 1000 to 1500 fpm (5 to 7.6 m/s):
(1) Radius Type RE 1 with minimum 1.0 radius-to-diameter ratio.
(2) Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct
Construction Standards - Metal and Flexible," Figure 2-3, "Vanes and Vane Runners," and Figure 2-4, "Vane Support in Elbows."
c. Velocity 1500 fpm (7.6 m/s) or Higher:
(1) Radius Type RE 1 with minimum 1.5 radius-to-diameter ratio.
(2) Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct
Construction Standards - Metal and Flexible," Figure 2-3, "Vanes and Vane Runners," and Figure 2-4, "Vane Support in Elbows."
2. Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 2-2, "Rectangular Elbows."
a. Radius Type RE 1 with minimum 1.5 radius-to-diameter ratio.
b. Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct
Construction Standards - Metal and Flexible," Figure 2-3, "Vanes and Vane Runners," and Figure 2-4, "Vane Support in Elbows."
F. Branch Configuration:
1. Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards -
Metal and Flexible," Figure 2-6, "Branch Connections."
a. Rectangular Main to Rectangular Branch: 45º entry.
b. Rectangular Main to Round Branch: Spin in.
END OF SECTION 15815