This document is a mechanical site plan drawing for fuel tank piping modifications at Watervliet Arsenal in Watervliet, New York, issued by the U.S. Army Corps of Engineers New York District. The drawing, dated September 18, 2025 (Amendment 1 issued October 17, 2025), depicts a 9-foot high diesel fuel tank containment structure in Building 136 (Boiler House) with associated piping systems, including a 4-inch tank nozzle with 6-inch protrusion per API 650 standards, 6-inch and 3-inch fill lines, and various shut-off valves (FOS and FOR lines) connecting to a piping shed and raised walkway access points. The containment area features a membrane floor throughout.

The contractor must provide connections to the tank and ensure all qualified personnel comply with UFC 3-460-01 (2023), UFC 3-460-03 (2021), API 650, and API 653 standards, with the critical understanding that the tank will remain fuel-filled during all work. Key contractual requirements include that the contractor is responsible for all fuel removal, storage, and replenishment if penetrations are required; work must not impact Watervliet Arsenal's heating season (October 15-May 1); and an API 653 certified tank inspector must validate tank material, shell thickness, and proposed port locations before work commences. The existing fuel will not be removed or stored by the installation, and the tank may contain varying fuel levels throughout the construction contract duration.

View the file

Other files

File Type Posted
Amendment 0016.pdf PDF
Amendment 0015.pdf PDF
Amendment 0015_23 09 00 and 23 09 23.02.pdf PDF
Amendment 0015_JA for Johnson Controls Inc Metasys.pdf PDF
Amendment 0015_Submittal REGISTER.pdf PDF
Amendment 0014.pdf PDF
Amendment 0013.pdf PDF
Amendment 0012.pdf PDF
Amendment 0011_33 57 55.pdf PDF
Amendment 0011.pdf PDF
Amendment 0011_RFI Photos.pdf PDF
Amendment 0010_Pictures_Switches Nameplates.pdf PDF
Amendment 0010.pdf PDF
Amendment 0009.pdf PDF
Amendment 0009_Photos.pdf PDF
Amendment 0008.pdf PDF
Amendment 0007.pdf PDF
Amendment 0007_Pictures.pdf PDF
Amendment 0007_Site Visit Photos Compressed.pdf PDF
Amendment 0006.pdf PDF
Amendment 0005.pdf PDF
Amendment 0004.pdf PDF
Amendment 0004_C-001.pdf PDF
Amendment 0004_01 14 00.pdf PDF
Amendment 0003_Site Visit Sign In Sheet_06MAY2026.pdf PDF
Amendment 0003.pdf PDF
Amendment 0003_ Site Visit Photos.pdf PDF
Amendment 0002.pdf PDF
Amendment 0002_G-101.pdf PDF
Amendment 0002_01 14 00.pdf PDF
Amendment 0002_01 50 00.pdf PDF
Amendment 0001_JA - ESS North - North - Square D.pdf PDF
Amendment 0001.pdf PDF
Amendment 0001_ JA - ESS North - Fire Alarm.pdf PDF
Amendment 0001_ Spec 33 57 55.pdf PDF
Amendment 0001_ JA - ESS North - CAC-IDS.pdf PDF
Evaluation Factors.pdf PDF
Drawings.pdf PDF
Solicitation - W912DS26RA015.pdf PDF
Specifications.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FUEL TANK

FUEL TANK

DIESEL FUELTANK

FPU

(E) 9-FT HIGH

CONTAINMENT

(E)

ABOVEGROUND

TANK

BUILDING 136

(BOILER HOUSE)(E) TANK

PIPING SHED

(E) STAIRS TO

RAISED WALKWAY

(E) STAIRS TO

RAISED WALKWAY

(E) STAIRS TO

TOP OF TANK

(E) 3" TANK

FILL LINE

(E) 6" FOT

(E) 3" FOR

(E) 6" FOS

FO

R

FO

S

C O

M M

BELOW GRADE

PAINTED STEEL FRAMING TO SIDE

OF WALL FOR RISER SUPPORT

PAINTED STEEL FRAMING TO

TOP OF WALL FOR PIPE

SUPPORT, W/ PIPE ROLLERS

NON-PENETRATING ROOF SUPPORT

STAND W/ PIPE ROLLERS W/ SLIP

SHEET OF 80 MIL WHITE HDPE

MATCHING (E) CONTAINMENT

MEMBRANE SIZED AT LEAST 2 TIMES

THE BASE LENGTH AND WIDTH, TYP

PROVIDE 2" TANK NOZZLE

WITH 6" PROTRUSION PER

API 650, LOCATE UNDER

STAIRS APPROX 20' OFF

THE BASE OF THE TANK

PROVIDE 4" TANK

NOZZLE WITH 6"

PROTRUSION PER API

650, LOCATE UNDER

STAIRS APPROX 20' OFF

THE BASE OF THE TANK

(3) 42"Ø KETTLE

FUEL FILTERS

SUPPLY 8" SCH 40 CS LOW

VELOCITY HEADER BELOW,

AND RETURN 8" SCH 40 LOW

VELOCITY HEADER BELOW

FOS&R, 2"

SCH 80 CS

6" PLUG VALVE

6" FOS,

SCH 40 CS

2" FOS,

SCH 80 CS

FOP-1

FOS-2

(E) DRAIN SUMP (E) MEMBRANE

FLOOR THROUGHOUT

CONTAINMENT AREA

(E) MEMBRANE

FLOOR THROUGHOUT

CONTAINMENT AREA

FOP-3

0 10' 20'

Scale: 1" = 10'-0"

S O

LI

C

IT

A

TI

O

N N

O

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N M

A R

K S

IZ

E

S U

B M

IT

TE

D B

Y

D A

TE

C O

N

TR

A C

T N

O

C H

E C

K E

D B

Y

D R

A W

N B

Y

IS

S

U E

D A

TE

US Army Corps of Engineers

U .S

.A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S N

E W

Y O

R K

D

IS

TR

IC

T

F E

D E

R A

L P

LA

ZA

N E

W Y

O R

K , N

Y

-0

S C

A

LE

S

H E

E T

D R

A W

IN

G

C O

D E

O F

1 2 3 4 5 6 7 8 9 10

G

F

E

D

C

B

A

A

Y or k S t P or tla nd , M

E

7.

3.

SHEET ID

W A

TE

R

V

LI

E T

A R

S E

N A

L W

A

TE

R V

LI

E

T, N

E W

Y O

R K

N O

R

TH

S W

IT

C

H S

TA

TI

O N

X

/1

8/

A N

S I D

IS

S

U E

D F

O R

C O

N S

TR

U

C

TI

O N

/1 8/

MS101

S

IT

E P

LA

N

D H

B

R D

A

R

LM

1:

X

NOTES:

1. SEE M-001 FOR LEGEND ABBREVIATIONS AND GENERAL

NOTES.

2. SEE CIVIL SHEETS FOR FOS & FOR PIPING ROUTING.

3. ASSUME TANK WILL CONTAIN VARYING LEVELS OF FUEL

THROUGHOUT THE DURATION OF THE CONSTRUCTION

CONTRACT.

4. PROVIDE CONNECTIONS TO TANK, AND QUALIFIED

PERSONNEL PERFORMING WORK, IN ACCORDANCE WITH

UFC 3-460-01 (2023), UFC 3-460-03 (2021), API 650, AND API

653, WITH THE UNDERSTANDING THAT TANK IS ASSUMED

TO CONTAIN FUEL DURING THE PROCESS.

5. EXISTING FUEL IN TANK WILL NOT BE REMOVED OR

STORED BY THE INSTALLATION THROUGHOUT DURATION

OF THE CONSTRUCTION CONTRACT.

6. CONTRACTOR IS RESPONSIBLE FOR ALL FUEL REMOVAL,

STORAGE, AND REPLENISHMENT IF CONTRACTOR

REQUIRES IT TO PERFORM PENETRATIONS.

7. PERFORMANCE OF WORK MUST NOT IMPACT

WATERVLIET ARSENAL’S HEATING SEASON (OCTOBER

15-MAY 1).

8. EXISTING TANK MUST BE INSPECTED BY AN API 653

CERTIFIED TANK INSPECTOR TO VALIDATE THE TANK

MATERIAL, SHELL THICKNESS, AND LOCATION OF THE

PROPOSED PORTS BEFORE THE WORK IS PERFORMED.

PLAN

NORTH

SCALE 1" = 10'-0"

MECHANICAL SITE PLANA1