CWF Spec 08 36 16.20 Vertical Lift Fabric Hanger Door.pdf
PDF 64 KB Posted
- Attached to
- F-35 CONSTRUCT COMBINED WEAPONS FACILITY
- Solicitation number
- W50S6Y-25-B-A004
About this file
This document is a technical specification for vertical lift fabric doors for a Combined Weapons Facility (CWF) project. The specification provides detailed requirements for manufacturing, installing, and operating high-performance fabric hangar doors designed for aircraft maintenance environments. Key technical specifications include:
The doors must be fabricated with corrosion-resistant materials like extruded aluminum and heavy-duty vinyl-coated polyester fabric, capable of withstanding wind loads up to 78 mph. The specification mandates complex electrical and mechanical requirements, including electric operators, safety mechanisms, control panels, limit switches, and wind locks. The doors must have a minimum maintenance-free operation of 3 years or 1,500 cycles, with a 3-year warranty on mechanical/electrical components and a 10-year warranty on fabric material. Installation requires precise alignment, testing, and coordination with electrical contractors, with specific requirements for door speed, operational performance, and safety features.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LSGA239001 JAXCWF-0
IFC B-3 Submission 100%
SECTION TABLE OF CONTENTS
DIVISION 08 - OPENINGS
SECTION 08 34 16.20
VERTICAL LIFT FABRIC DOORS
08/21, CHG 2: 08/24
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 DESIGN REQUIREMENTS
1.3.1 Door Design and Components
1.3.1.1 Steel Door Components
1.3.1.2 Aluminum Door Components
1.3.1.3 Door Operational Performance
1.3.2 Loads
1.3.2.1 Wind Loads
1.3.2.2 Other Loads
1.3.3 Door Speed
1.3.4 Door Weight
1.4 QUALITY ASSURANCE
1.4.1 Manufacturer's Qualifications
1.4.2 Installer's Qualifications
1.4.3 Warranty
1.4.4 Delivery, Storage and Handling
1.5 WELDING PROCEDURES AND QUALIFICATIONS
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Steel Plate and Bars
2.1.2 Steel Sheet
2.1.3 Steel Shapes
2.1.4 Aluminum Extrusions
2.1.5 Aluminum Sheets and Strips
2.1.6 Aluminum Welding Rods and Bare Electrodes
2.1.7 Door Fabric
2.1.8 Wire Rope
2.2 DOORS
2.2.1 Fabric Door Leaves
2.2.2 Intermediate Door Beams
2.2.3 Door Guides
2.3 ELECTRIC OPERATORS
2.3.1 Drive Units
2.3.2 Belt/Wire Rope System
2.3.3 Door Drop Prevention
2.3.3.1 Swing-Up Door Mullion Safety Arrester
2.3.4 Slack Belt/Wire Rope Breaker
2.3.5 Motors
2.3.6 Controls
2.3.6.1 Control Panel Enclosures
2.3.7 Limit Switches
SECTION 08 34 16.20 Page 1 Friday March 14, 2025 Version 0a
2.3.8 Door Control Alarms
2.3.9 Safety Device
2.3.10 Control Transformers
2.3.11 Electrical Components
2.4 HEADER BOX
2.5 BOTTOM BEAM
2.6 WIND LOCK
2.7 OPERATION
2.7.1 Door Operation
2.7.2 Electrical Operation
2.8 FINISHES
2.8.1 Aluminum
2.9 SIGNAGE
PART 3 EXECUTION
3.1 PROTECTIVE COATINGS
3.1.1 Cleaning
3.1.2 Shop Painting
3.1.3 Metal Protection
3.2 ERECTION
3.2.1 Assembly
3.2.2 Cleaning
3.2.3 Control Panel Installation
3.3 ELECTRICAL WORK
3.4 ACCEPTANCE TESTING PROCEDURE AND REPORT
3.4.1 General
3.5 PERSONNEL TRAINING
3.6 EXTRA MATERIALS
3.7 INSPECTION AND ADJUSTMENT
-- End of Section Table of Contents --
SECTION 08 34 16.20 Page 2
SECTION 08 34 16.20
VERTICAL LIFT FABRIC DOORS
08/21, CHG 2: 08/24
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ALUMINUM ASSOCIATION (AA)
AA ADM (2020) Aluminum Design Manual
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 611 (2014) Voluntary Specification for Anodized Architectural Aluminum
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 325 (2017) Steel Construction Manual
AISC 360 (2016) Specification for Structural Steel Buildings
AMERICAN WELDING SOCIETY (AWS)
AWS A5.10/A5.10M (2023) Welding Consumables - Wire Electrodes, Wires and Rods for Welding of Aluminum and Aluminum-Alloys - Classification
AWS D1.1/D1.1M (2020; Errata 1 2021) Structural Welding Code - Steel
AWS D1.2/D1.2M (2014; Errata 1 2014; Errata 2 2020) Structural Welding Code - Aluminum
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2019) Standard Specification for Carbon Structural Steel
ASTM A653/A653M (2023) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A992/A992M (2022) Standard Specification for Structural Steel Shapes
ASTM A1023/A1023M (2021) Standard Specification for Stranded Carbon Steel Wire Ropes for General
SECTION 08 34 16.20 Page 3
Purposes
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B221 (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM D751 (2019) Standard Test Methods for Coated Fabrics
ASTM D2136 (2002; R 2012) Coated Fabrics - Low-Temperature Bend Test
ASTM E84 (2023) Standard Test Method for Surface Burning Characteristics of Building Materials
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM AMP 500 (2006) Metal Finishes Manual
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA AB 1 (2002) Molded-Case Circuit Breakers, Molded Case Switches, and Circuit-Breaker Enclosures
NEMA ICS 1 (2022) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2020) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 5 (2017) Industrial Control and Systems:
Control Circuit and Pilot Devices
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA KS 1 (2013) Enclosed and Miscellaneous Distribution Equipment Switches (600 V Maximum)
NEMA MG 1 (2021) Motors and Generators
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 4 2023; ERTA 5 2023; ERTA 6
2023) National Electrical Code
NFPA 79 (2015) Electrical Standard for Industrial Machinery
NFPA 220 (2024) Standard on Types of Building Construction
SECTION 08 34 16.20 Page 4
NFPA 409 (2022) Standard on Aircraft Hangars
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-STD-889 (2021; Rev D) Galvanic Compatibility of Electrically Conductive Materials
UFC 1-200-01 (2022; with Change 4, 2024) DoD Building Code
UFC 3-301-01 (2023) Structural Engineering
UL SOLUTIONS (UL)
UL 98 (2016; Reprint Jan 2022) UL Standard for Safety Enclosed and Dead-Front Switches
UL 248-1 (2011) Low Voltage Fuses - Part 1: General Requirements
UL 248-12 (2011; Reprint Aug 2020) Low Voltage Fuses
- Part 12: Class R Fuses
UL 489 (2016; Rev 2019) UL Standard for Safety Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures
UL 508 (2018; Reprint Jul 2021) UL Standard for Safety Industrial Control Equipment
UL 698A (2018; Rev 2019) UL Standard for Safety Industrial Control Panels Relating to Hazardous (Classified) Locations
UL 1449 (2021; Reprint Dec 2022) UL Standard for Safety Surge Protective Devices
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Manufacturer's Qualifications ; G
Installer's Qualifications ; G
SD-02 Shop Drawings specific to this project, sealed by the Door Manufacturer's Registered Professional Engineer.
Door Design ; G
SD-03 Product Data
Diagrams, performance curves and characteristic curves of equipment and systems.
SECTION 08 34 16.20 Page 5
Electric Operator ; G
Motors ; G
Doors ; G
Controls ; G
Door Fabric ; G
SD-05 Design Data
Calculations ; G
SD-06 Test Reports
Door Fabric : ASTM D2136; G
Door Fabric : ASTM E84; G
Door Fabric Connection ; G
SD-07 Certificates
Manufacturer's Qualifications ; G
Installers Qualifications ; G
Welding Procedures and Qualifications ; G
SD-10 Operation and Maintenance Data
Door Operation , Data Package 2; G
SD-11 Closeout Submittals
Manufacturer's Warranty ; G
1.3 DESIGN REQUIREMENTS
1.3.1 Door Design and Components
The vertical lift fabric doors and components indicated in the construction documents are representative of a commercially-available door. Design and fabricate the door to fit within the space allocated and in accordance with the criteria specified herein and without binding, interfering, or damaging the adjacent structure or itself. Provide a door with a minimum maintenance free operation for 3 years or 1,500 cycles, whichever occurs first, as counted by the door close limit switch.
Construct the door with limited combustible construction materials in accordance with NFPA 220 and NFPA 409 .
SECTION 08 34 16.20 Page 6
Shop drawings of motors, all electrical control devices, and all electrical control panels, including schematic diagrams, dimensional drawings of control panels, details of control panel installations, internal wiring diagrams of control panels, and wiring diagrams indicating all external connections between control panels and from control panels to remote control devices. Furnish list of materials for all control devices, both inside and remote from control panels including manufacturer's model number, electrical ratings, location, and quantity of each item furnished.
Show all vertical lift fabric doors and components, including types, sizes, locations, fabric, supporting, bracing and framing steel and aluminum members, metal gages, fasteners, speed, hardware provisions, signage, installation details, and other details of construction. Include supporting brackets for motors, location of motors, and safety devices.
Include personnel door, mullion pit and cover or retractable pin and strike if utilized. Provide details for the closure between bulkhead and doors. Include details for supporting and bracing the door assembly from the structure. Demonstrate through detailing that the indicated superstructure's non-dead load, service level deflections are accommodated in both the downward and upward directions. Indicate finishes to be used.
1.3.1.1 Steel Door Components
The door manufacturer's registered professional engineer is responsible for designing all supporting, bracing and framing steel members associated with the door system for the specified loads in accordance with the requirements of AISC 325 and AISC 360 . Comply with the AWS D1.1/D1.1M Standards for all steel welding. Refer to Section 05 12 00 STRUCTURAL STEEL for other requirements, including bolted connections.
1.3.1.2 Aluminum Door Components
The door manufacturer's registered professional engineer is responsible for designing all supporting, bracing and framing aluminum members associated with the door system for the specified loads in accordance with the requirements of the Aluminum Association ( AA ADM). Comply with the AWS D1.2/D1.2M Standards for all aluminum welding.
1.3.1.3 Door Operational Performance
Provide a door which does not bind, catch or become adversely out of level during door operation. Door operation includes (1) fully opening then closing, (2) partially opening then closing, and (3) partially opening, then fully opening, and then closing. Partially opened doors may occur at any intermediate point and smooth operation of the door is required with smooth operation without binding.
1.3.2 Loads
Use the governing design loads for the design of the door system in accordance with UFC 1-200-01 , UFC 3-301-01 and all other applicable criteria.
1.3.2.1 Wind Loads
In the closed position, design the entire door system to withstand the component and cladding wind pressures as indicated by the Engineer of Record for a Partially Enclosed building, based upon the indicated design
SECTION 08 34 16.20 Page 7 wind velocity, geometry and other factors. Design all elements of the door's components and cladding to withstand both the highest positive and negative pressures based upon the actual tributary area from the wind, as indicated.
In addition, design the entire door system to be both fully open and fully operational for wind velocities up to 78 mph . Calculate the applicable component and cladding wind pressures, including importance factor, and utilize the controlling wind pressures or a positive and negative wind pressure of 15 psf on the surface of the door, whichever is greater.
Design door mullions and jambs for the unbalanced positive or negative pressure on the surface of a closed adjacent door with the other adjacent door being open.
Submit complete calculations for all components sealed by the door manufacturer's registered professional engineer for review. Include calculations with analysis of the intermediate and bottom beams using the above applied wind conditions and door positions. Do not design intermediate or bottom beams to rely upon stabilization or bracing from the fabric when the door is not in the closed position. In both the open and closed position, design all intermediate beams for the maximum potential rotation permitted by manufacturer detailing such that applied wind loads are not assumed to act in only the strong axis.
1.3.2.2 Other Loads
Provide door mullions and jambs of adequate strength to transmit the forces from design wind loads, in addition to the other loads resulting from door operations or the door's action as a tributary element, with no detrimental effect on the operation of the door. Submit the vertical and horizontal loads imposed upon the building structure by the vertical lift fabric door system.
1.3.3 Door Speed
Provide for each door leaf to open fully with a minimum speed of 6 inches per second under all design conditions. Provide door mullion(s), when required by the contract documents, to rotate with a minimum wire rope retraction speed of 6 inches per second.
1.3.4 Door Weight
Submit door load diagrams of the door in the closed and governing open position(s). Provide details showing clearance and attachment requirements for coordination with the structural steel, miscellaneous steel, slab/foundation, and demonstration that superstructure's unfactored deflections are accommodated by the design of the mullions, pits and door leaves.
1.4 QUALITY ASSURANCE
1.4.1 Manufacturer's Qualifications
Use a vertical lift fabric door product from a manufacturer who is regularly engaged in the design, fabrication, erection, and service of vertical lift fabric doors of type and size required for this project.
The manufacturer must have at least 5 years of similar vertical lift fabric door design experience. Similar doors must have comparable function and design including size, configuration, type of use, SECTION 08 34 16.20 Page 8 retractable or moving elements, safety features, controls, and other key engineering elements as the door being specified. It is acceptable to show that a series of similar doors collectively meet all comparable elements to the door being specified, although not necessarily individually. Submit written manufacturer evidence on similar past door designs and installations listing the name, location, contact information of owners, installation dates, overall sizes, features, and other relevant information for experience and qualifications evaluation. Only manufacturers who can submit this evidence of actual installations where the products have proven practical, durable, and require a minimum of maintenance, will be qualified under this specification.
1.4.2 Installer's Qualifications
A manufacturer's representative, skilled and experienced in the erection of vertical lift fabric doors of the type specified herein, is required to supervise installation of the door system(s) in accordance with approved shop drawings. For each Installer, submit written evidence of similar past door installations listing the name, locations, contacts information of owners, installation dates, overall sizes, features, and other relevant information for experience and qualifications evaluation.
1.4.3 Warranty
Provide a three-year warranty for all mechanical and electrical components against defects in material and workmanship beginning on the date of Project Acceptance. Manufacturer is responsible for items requiring adjustment, repair or replacement for the three-year maintenance-free warranty period, or 1500 door cycles, whichever occurs first. Provide a ten year warranty for defects in the fabric material.
1.4.4 Delivery, Storage and Handling
Provide shipment of all materials required for door installation in protective packaging. Protect door and accessories from damage during delivery, storage, and handling. Mark all packaging clearly with manufacturer's brand name, door model and job site location. Store in dry location with adequate ventilation, and free from dust and water. Storage must permit easy access for inspection and handling. Remove damaged items that cannot be restored to like new condition or provide new items.
1.5 WELDING PROCEDURES AND QUALIFICATIONS
Prior to welding, submit certification for each welder stating the type of welding and positions qualified for, the code and procedure qualified under, date qualified, and the firm and individual certifying the qualification tests. If the qualification date of the welder or welding operator is more than 6 months old, the welding operator's qualification certificate must be accompanied by a current certificate by the welder attesting to the fact that he has been engaged in welding since the date of certification, with no break in welding service greater than 6 months.
Comply with applicable provisions of AWS D1.1/D1.1M for Steel.
Comply with applicable provisions of AWS D1.2/D1.2M for Aluminum.
SECTION 08 34 16.20 Page 9
PART 2 PRODUCTS
2.1 MATERIALS
Select materials based on durability, low maintenance, weather resistance and strength (permanent deformation from loading is not permitted).
Comply with ASTM E84 for limited combustible construction for all door system materials.
2.1.1 Steel Plate and Bars
ASTM A36/A36M
2.1.2 Steel Sheet
ASTM A653/A653M
2.1.3 Steel Shapes
ASTM A992/A992M
2.1.4 Aluminum Extrusions
ASTM B221, Alloy 6063-T6, Alloy 6005-T5 or 6000 Series Aluminum
2.1.5 Aluminum Sheets and Strips
ASTM B209, alloy and temper best suited for the purpose.
2.1.6 Aluminum Welding Rods and Bare Electrodes
AWS A5.10/A5.10M .
2.1.7 Door Fabric
Provide fabric material that is a heavy-duty, rip stop, vinyl coated polyester fabric weighing not less than 19 oz/square yard , capable of carrying 250 lb/in per panel. Provide fabric that is impervious and resistant to solvents, fuel, lubricants, and other similar fluids commonly found in aircraft maintenance hangars. Provide fabric that is ultraviolet (UV) stabilized, self-extinguishing (0-75 flame spread), and suitable to withstand temperatures between plus 158 to minus 31 degrees F in compliance with ASTM D2136. Fabric color will be selected by the Government from the manufacturer's standard colors. Construct door system such that fabric is tight between the intermediate beams when the door is closed and the wind locks engaged. Test the fabric to meet the criteria of ASTM E84 (flame spread - Class A interior wall and ceiling finish), ASTM D2136 (cold cracking, brittleness and temperature), and ASTM D751 (tensile and tear strength). Provide a minimum 4:1 factor of safety on the fabric design while accounting for degradation due to UV and temperature effects.
Submit door fabric panel samples for weight, strength, and color approval.
2.1.8 Wire Rope
ASTM A1023/A1023M .
SECTION 08 34 16.20 Page 10
2.2 DOORS
Door system consists of individual hoist-up fabric door leaves with intermediate aluminum beams or trusses. Maximum wind load deflection of steel structural door members is not to exceed the member length divided by 120. Maximum wind load deflection of extruded aluminum door members is not to exceed the member length divided by 30. Design and install the door system to accommodate the anticipated downward deflection due to self weight of the door system after all the building dead load has been applied. Then provide a door system which accommodates the stated unfactored downward and upward deflections of the superstructure to which it is being attached.
2.2.1 Fabric Door Leaves
When one-piece fabric construction is utilized, loop fabric over the uppermost beam and attach the fabric to both flanges of the intermediate beams, top beam, and bottom beam with self-tapping screws through corrosion resistant anodized or coated aluminum batten strip. Provide independent, third party laboratory testing to demonstrate door fabric connection has a minimum 2:1 factor of safety above the required connection forces while accounting for fabric degradation due to UV and temperature effects.
2.2.2 Intermediate Door Beams
Provide corrosion resistant, extruded aluminum intermediate beams of a suitable depth dependent on the door width and the wind load requirements with a spacing not to exceed 6 feet . Provide, at each end of the beams, a guide block of self-lubricating material or rollers that run along the guides. Built-up members meeting these requirements are acceptable.
Design the intermediate door beams and guide block or rollers to carry the full design wind load without failure and without being pulled from the door guides. Guide block or roller design cannot put the intermediate beam into tension under design wind load which would cause pulling forces on door jambs. Provide guide block material of nylon, polyoxymethylene (POM), or Ultra High Molecular Weight (UHMW) polyethylene. Provide rollers that are galvanized steel with maintenance free, lifetime sealed ball-bearings in case-hardened steel races. Midspan splices are prohibited in intermediate beams.
2.2.3 Door Guides
The vertical door guides are an integral part of the door, made of extruded aluminum with a suitable depth and width dependent on the size of the intermediate beams and wind load requirements. Provide guide rails with a T-shaped center guide designed to prevent guide blocks from escaping the guides and designed to prevent placing the intermediate beam in tension under design winds loads (catenary effect). Design the guides to provide weather sealing on the inside and outside faces. Provide adequate space inside the guides, or within the door, for all required components such as the nylon belt, polyester belt, or wire rope of the drive unit, windlocks and safety arresters. Provide removable door guides with anchorage to the mullion and jambs, as applicable, of the size and type required to carry the full design wind load without failure and without permanent deformation. Removable door guides will be mechanically fastened to permit the guide rail to be readily removed with standard tools. Provide guide blocks or roller, inside the guides, sufficient to
SECTION 08 34 16.20 Page 11 prevent scraping or damage to the guide rail during normal door operation.
2.3 ELECTRIC OPERATORS
2.3.1 Drive Units
Provide each door leaf with a motor drive system with horsepower sized as appropriate for the weight of the door leaf plus door friction to account for operational wind speeds and corresponding pressures. Equip the gear motor with a drum on which the nylon belt, polyester belt, or wire ropes are wound, including required safety wraps and connections. For dead ends on wire ropes, provide a minimum of two unclamped dead wraps on the wire rope drum with the dead end anchored on the drum barrel by clamps or by inserting end fitting into reinforced pockets. For hoists using synthetic belts, provide a minimum of five dead wraps and belt anchorage to the drum.
If a single motor drive is used, wind the belts and wire ropes on the same drum. When using wire ropes, provide a grooved drum. Attach the belts and wire ropes to the bottom beam via the safety arresters. Provide a hand crank device or other manual means on the motor for manual operation of the door in the event of a power failure. Provide a gear motor that is removable without disturbing limit switch adjustment. Coordinate the drive units with the location of aircraft such that the drive units are accessible while aircraft are in the hangar.
Submit drive unit system horsepower, belt type, and locations. Safety arrestor type, test reports, and brake system details.
2.3.2 Belt/Wire Rope System
Properly select and utilize belts and/or wire ropes to transmit motive force to each door leaf. Install belts/wire ropes free of any kinks and design the system and sheave diameter to prevent the occurrence of any kinks, and abnormal stress in the operating belts/wire ropes. Where belts/wire ropes pass through openings of the building structure, construct the openings to prevent abrasion, wear, or damage to the belts/wire ropes. Design belts, wire ropes, and their connections to have a minimum 6:1 factor of safety, including impact loads.
Do not use belt systems where individual lifted door weight exceeds 6,200 Lbs . Include edge wear indicators on belts and properly terminate at all connections. Provide fully stitched flat eye belt terminations which are permanent and do not require routine adjustment or maintenance.
Properly swage wire rope ends and include thimble loops to prevent wire rope abrasion at end connections. Provide wire rope end connections which are permanent and do not require routine adjustment or maintenance.
Minimize the quantity of motors, sheaves and drums used to guide the belts or wire ropes to reduce maintenance requirements. Provide sheave units in accessible locations that allow inspection and preventive maintenance. Do not locate motors, sheaves, and drums in enclosed locations, which are not readily accessible for visual inspection and maintenance.
2.3.3 Door Drop Prevention
[ 2.3.3.1 Swing-Up Door Mullion Safety Arrester
Provide swing-up door mullions with a lifting motor that includes a backup
SECTION 08 34 16.20 Page 12 arresting system or secondary brake system to prevent the mullion from falling in case of motor, wire rope, or primary brake failure.
] 2.3.4 Slack Belt/Wire Rope Breaker
Use a safety device on all belts and wire ropes that will send a slack belt/wire rope condition to the appropriate drive unit(s) and prevent unsafe operation or any other unsafe condition.
2.3.5 Motors
NEMA MG 1, high-starting torque, reversible type with sufficient horsepower and torque output to move the door in either direction from any position. Provide a motor to produce a door travel speed of not less than 6 inches per second without exceeding the rated capacity. Provide motors that operate on the indicated voltage. Provide motor enclosures that are drip-proof type or NEMA totally enclosed. Supply a hand crank which fits the motor for manual operation of the door in the event of a power failure. Install motors in approved locations. Provide motors that have a minimum service factor of 1.2 at continuous duty under maximum full load. Provide motors in accordance with Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM and requirements listed above.
When two or more motors are used, provide mechanical linkage, electronic position monitoring and/or logic to eliminate the possibility that the door may bind, catch or become adversely out of level during door operation.
Submit motor characteristics including horsepower, service factor, safety factor, and standards compliance.
2.3.6 Controls
Provide control equipment in accordance with NEMA ICS 2 . Provide control enclosures in accordance with NEMA ICS 6 , Type 12 or Type 4X. Provide door electrical controls in accordance with NEMA AB 1, NEMA ICS 2 , NEMA ICS 5 , and NEMA KS 1. Provide door electrical controls in accordance with NEMA ICS 1 , NEMA ICS 6 , NFPA 70 , NFPA 79 , UL 98 , UL 248-1 , UL 248-12 , UL 489 , UL 508 , UL 1449 , and UL 698A . Provide UL listed door control components. Provide each Door Module with the following operators:
a. Main Control Panel (Station) [NEMA Type 4][NEMA Type 4X] enclosure.
b. Remote (Auxiliary) Control Panel (Station) at the opposite end of hangar door [NEMA Type 4][NEMA Type 4X] enclosure to match Main Control Panel.
[ c. Provide emergency Stop Buttons located outside at the end of each hangar bay in a NEMA Type 4X enclosure.
] d. Provide "Open" operator on the exterior of each bay of doors, keyed for use by Fire Department personnel to allow entry in the event of an emergency, in a NEMA Type 4X enclosure.
Provide conduit and control wiring between Main, Auxiliary, emergency stop controls, proximity switches, limit switches, and each door motor drive unit. Provide power and controls wiring and conduit in accordance with Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM.
SECTION 08 34 16.20 Page 13
Submit controls characteristics including all electrical components and devices used in the control system, enclosures, safety devices, transformer size and voltage, and emergency power connection.
2.3.6.1 Control Panel Enclosures
Provide NEMA ICS 6 , Type 12 or Type 4X control panel enclosures. Provide an integral main power disconnect switch that is mechanically interlocked with the control panel door at each control panel. Provide factory wired field wiring terminal strip in each control panel and instantaneous three-phase thermal overload relays. Provide each control panel enclosure including an internal motor starter or VFD with adequate integral ventilation (air conditioning if required) for operation in a 120 degree F ambient environment. Provide [NEMA][ or ][IEC] rated control relays.
Provide main control panel with programmable logic controller.
Provide devices to control the logic and sequence of door and mullion operation to ensure safe, smooth and dependable operation at each control panel. Provide interlocks to preclude personnel injury, including an interlock between the power supply system and use of the hand crank for manual operation of the door. Provide constant-pressure type, fully guarded, illuminated push buttons on the control panel for both up and down operations. Provide mushroom type emergency stop button on each control panel. Utilize individual user password protected touch screen interface to select desired door or mullion motion. Door motion will be initiated via fully guarded push buttons.
Provide back-up power hook up at the control panel to connect to a portable generator provided by the Base via a pin and sleeve female receptacle (coordinate with Base) and manual transfer switch provided on the main control panel.
2.3.7 Limit Switches
Provide limit switches or proximity switches to automatically stop doors [and mullions] at the fully open and fully closed positions. Provide limit switches or proximity switch positions that are readily adjustable.
Provide limit switches or proximity switches for the wind lock with visual indication on the control panel for each door leaf. Provide visual indication to notify the door operator that the wind locks are engaged for all door leaves.
Demonstrate the operability of all limit switches prior to Government occupancy.
2.3.8 Door Control Alarms
Provide an audible alarm device on each door main control panel (minimum 100 dbA) that sounds 5 seconds before the door moves and continues to sound when the door is moving. Coordinate this audible signal such that it is clearly different from all of the other audible signals utilized in the hangar bay.
Provide a visual alarm device above each door main control panel (LED beacon with 1600 lumens) that operates 5 seconds before the door moves and continues to operate when the door is moving. Coordinate the color of this visual signal such that it is clearly a different color than all of the other visual signals utilized in the hangar bay.
SECTION 08 34 16.20 Page 14
2.3.9 Safety Device
Provide an intrinsically safe (suitable for a Class I Division 2 hazardous location) electric safety edge on the bottom of the edge of each door, continuous over the full length of the door. Provide a safety edge located inside of a rubber cushioned bottom weather sealing edge (or boot) with sufficient vertical height (factoring in the time and distance that it takes to stop a closing door) to prevent collision damage along the bottom edge of the door. Activate the safety edge when the door is closing and do not allow the safety edge to prevent the door from completely closing and properly sealing along its entire length.
2.3.10 Control Transformers
Provide fused transformers inside of each Main Control Panel as necessary to reduce the voltage on the control circuits to 120 volts or less.
2.3.11 Electrical Components
NFPA 70 . Provide automatic control and safety devices, including failsafe battery powered wireless limit switches or hard-wired limit switches electrified components[ including personnel door interlocks]. Wire rope reel type take-up devices are not allowed. Provide control wiring in accordance with NFPA 70 . Provide conduit, wiring, and mounting of controls in accordance with Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM.
2.4 HEADER BOX
Construct the header boxes of carbon steel and finished in accordance with the paragraph FINISHES.
2.5 BOTTOM BEAM
Construct the bottom beam of carbon steel and finished in accordance with the paragraph FINISHES. Provide a bottom beam of a suitable width and depth to carry the load of the intermediate beams when the door is not closed, and to ensure full closing and a tight floor seal under full design wind speeds spanning between windlocks located at each jamb.
Provide a heavy-duty bottom rubber seal to form a tight seal with the floor under all design conditions. Provide a bottom edge safety device that is integral with the bottom seal.
Design bottom beams to span between safety arrestors at the jambs and support the weight of the door, including intermediate beams, while remaining stable and within the door guides. If the door leaf safety arrestor alternative is utilized per paragraph DOOR LEAF SAFETY ARRESTERS, design the bottom beam to support the weight of the door, including intermediate beams with either end belt/wire rope, or any two intermediate belts/wire ropes, removed while remaining stable and within the door guides. Midspan splices are prohibited in the bottom beam.
2.6 WIND LOCK
At each door leaf provide wind locks at each jamb, which automatically activate and lock the bottom beam into place when the door reaches its closed position to maintain a tight floor seal and intermediate beam stability with tight fabric under design wind conditions. Provide a limit switch, or a proximity switch, with indicator to notify the door operator
SECTION 08 34 16.20 Page 15 that all wind locks are engaged properly. Provide switches located below 18 inches above finish floor that are compliant with NFPA 70 , Class I, Division 2 hazardous environment.
[] 2.7 OPERATION
2.7.1 Door Operation
Provide a vertical lift fabric door which guides up and down in weather sealed vertical guides attached to the structure[ and mullions]. Provide a door system which operates by lifting the bottom beam upwards in each door leaf, thereby stacking the intermediate beams one on top of the other, with the fabric material folding in pleats. Door operational safety is of paramount importance.
When the door system is fully open, all door system components will be outside of the required clearance area for the door opening.
When the door system is fully closed the door system will seal the opening and form a portion of the building's air barrier. The intermediate beams hang between the two fabric faces thus pulling the fabric material tight and sealing along the guides at each jamb. The tension created in the fabric panels is permitted to stabilize the intermediate beams, if proven capable by the manufacturer, and the bottom beam seal will fit tightly along the entire length of the door threshold.
Submit in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA. Including wiring diagrams and the complete manufacturer's instructions for operation and maintenance of the doors, door mullions where indicated, and accessories, including emergency operation, in the event of general building power failure to the doors.
2.7.2 Electrical Operation
Provide the main control panel with control logic such that when the integral female pin and sleeve emergency power receptacle is inserted and the integral manual transfer switch associated with the pin and sleeve receptacle is engaged the control panel will automatically limit only one door lift motor or one mullion lift motor to operate at a time.
The door will be stopped by a primary limit switch when the door is opened completely. In case of over travel, the door will be stopped by a secondary limit switch to prevent damage. Slack belt/wire rope breakers will stop the drive unit when the door is closed. In case of belt/wire rope break/rupture or if an obstruction should prevent the door from being closed the slack belt/wire rope breakers will also stop the drive unit.
Weight or springs activate the slack breakers.
Control door operation by three buttons marked "OPEN", "CLOSE", and "STOP". The "OPEN" and "STOP" buttons require only momentary pressure to operate. The "CLOSE" button requires constant pressure to maintain the closing motion of the door. The door will immediately stop, and remain in that position, when the door is in motion and the "STOP" button is pressed or the "CLOSE" button is released. From that stop position, the door operation is then continued in either direction by the "OPEN" or "CLOSE" buttons. Removing the pressure from the "CLOSE" button results in stopping the motor drive and setting the brake.
SECTION 08 34 16.20 Page 16
2.8 FINISHES
2.8.1 Aluminum
Clear Anodized: Conforming to AA-M12-C22-A41 in accordance with NAAMM AMP 500 and complying with AAMA 611. The minimum finish thickness is
0.7 mil or greater.
2.9 SIGNAGE
Provide a placard sign immediately adjacent to all control panels indicating the below Notice. Include the service level wind speed which corresponds to the ultimate wind speed used in design of the open/operational door in paragraph WIND LOADS in the Notice post..
Notice:
Vertical lift fabric doors will be closed and not operated when wind speeds above[ 60 mph ][_____] are expected.
Vertical lift fabric doors will be transferred to back-up power for operation when commercial power is not available.
PART 3 EXECUTION
3.1 PROTECTIVE COATINGS
3.1.1 Cleaning
After fabrication, clean all metal surfaces thoroughly of all mill scale, rust, oil, grease and other foreign substances. Apply rust-preventive primer to all steel parts immediately after cleaning.
3.1.2 Shop Painting
After cleaning, coat with primer all steel surfaces other than machine-finished parts. Keep paint off finished bearing surfaces. Before assembly, prime surfaces that will be inaccessible after assembly. Handle painted materials with care to avoid scraping and breaking the protective film. Ferrous metal surfaces that will be exposed after fabrication will be shop coated and touch-up painted in the field in accordance with the paragraph FINISHES.
3.1.3 Metal Protection
Provide in accordance with Chapter 4 of UFC 1-200-01 when door system is in a corrosion prone location or where door system components use dissimilar metals. If dissimilar metals are used, also provide in accordance with MIL-STD-889 . Provide added corrosion protection to the design such as, but not limited to, the following. Where aluminum will contact dissimilar metals, protect against galvanic action by painting contact surfaces with primer or by applying sealant or tape recommended by manufacturer for this purpose. Where aluminum will contact masonry or concrete, protect against corrosion by painting contact surfaces with bituminous coating.
3.2 ERECTION
Provide all work associated with these door systems under the direct
SECTION 08 34 16.20 Page 17 supervision and control of the fabricator for safety, control of product liability, and Engineer of Record responsibilities. Coordinate the erection of the doors with the work of other trades. Coordinate the design, fabrication and erection of the door systems and adjust for actual camber, fabrication, and erection tolerances of the supporting structure including simulated door weight load testing and survey to ensure proper fit-up of the final door system. Coordinate mullion pit locations (including their drains), alignment and orientation. Ensure that all steel support, bracing and framing members are furnished and accurately installed. Coordinate electrical work, including locations of all panels, equipment, motors and other components for required clearances, access and routing of power.
3.2.1 Assembly
Assemble and install the doors and accessories in accordance with the manufacturer's recommendations and installation manual. Secure guides to the walls plum, level, and in-line. Anchor guides at spacing indicated on the manufacturer's installation drawings. Provide additional supports as necessary for attachment of guides, brackets, doors, and operation mechanisms. After erection is complete and before touch-up field painting is applied, thoroughly clean all abraded surfaces, field welds, and field bolts; coat in accordance with paragraph FINISHES.
3.2.2 Cleaning
Clean both the interior and exterior of doors after the completion of erection.
3.2.3 Control Panel Installation
Locate all door control panels indoors, adjacent to the door opening, and with an unobstructed line of sight for the entire door opening. Provide all conduit entries into the bottom of the control panel. Mount control panels and provide three phase power to each control panel.
3.3 ELECTRICAL WORK
NFPA 70 . Provide all conduit, wiring, and mounting of controls in accordance with Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM.
Door manufacturer to coordinate with the qualified, licensed electrical contractor who will provide and install all 480 3-phase supply power to all components (such as Main, auxiliary, controllers, panels, motors, and other electrical devices) which require this low voltage supply power.
The qualified, licensed electrical contractor will provide and install all conduit for the control level power under the review and approval of the door manufacturer. Either the qualified, licensed electrical contractor or a factory authorized technician may provide and install all wiring for control level power under the review and approval of the door manufacturer in accordance with the approved construction submittals.
3.4 ACCEPTANCE TESTING PROCEDURE AND REPORT
3.4.1 General
Upon completion of installation, including work by other trades, lubricate, adjust, and test doors to verify operation in accordance with manufacturer's product data. Final adjustments will be made by the
SECTION 08 34 16.20 Page 18
Manufacturer's authorized representative. Adjust and re-test the doors until the entire installation is fully operational and acceptable.
Acceptance testing must consist of operating each door open and closed (one cycle) ten times successfully and consecutively within a nine-hour time interval in accordance with manufacturer's recommended time interval between open/close cycles. Provide Contracting Officer's Representative a copy of the final acceptance testing report with completed tests.
3.5 PERSONNEL TRAINING
Provide an 8-hour on-site training session for the door operating personnel and maintenance department. In the training, outline door safety, operation, troubleshooting and repair guidelines.
3.6 EXTRA MATERIALS
Supply a door fabric patch kit with approximately 45 square feet of fabric for each hangar door and all other materials required for door panel repair. Provide all unique tools required to maintain the door system.
Provide a patch kit with color matched fabric and associated repair materials and tools.
3.7 INSPECTION AND ADJUSTMENT
Within the 12 month warranty period, following the initial period of use and changes in seasonal temperature, the manufacturer's authorized representative will return to inspect and adjust doors to confirm the door system is fully operational and acceptable. Provide the Contracting Officer's Representative an inspection report outlining observations, door condition, operation, and all items requiring adjustment or requiring repair/replacement under the door system warranty. Include a report with recommended annual inspection and maintenance items. As needed, schedule a follow-up visit to complete items requiring adjustment, repair or replacement. Manufacturer is responsible for items requiring adjustment, repair or replacement for the 3 year maintenance-free warranty period or 1500 cycles, whichever occurs first, beginning after the first 12 month contractor's warranty period.
-- End of Section --