S09 09 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_05212026 1.pdf
PDF 18 MB Posted
- Solicitation number
- 36C78626R0058
About this file
This document is a comprehensive set of construction bid drawings for a federal cemetery facility correction project at Camp Nelson National Cemetery in Kentucky, prepared by Prime Consultant/ASTUTE ENGINEERING, PLLC. The project scope encompasses plumbing, electrical, and related infrastructure improvements across multiple cemetery buildings and site locations, with a bid set effective January 7, 2026.
The plumbing scope includes domestic water piping installation with new water heater (EWH-1) and hot water recirculation system, sanitary and vent piping modifications, floor drains and cleanouts, mixing valves for lavatories and eyewash stations set to 110°F, and water hammer arresters. Gas piping work involves connection to existing radiant tube heaters and propane systems. The electrical work encompasses new electrical panels (designated as Panel M, Panel A, Panel D, Panel F), lighting fixture installations with occupancy sensors and photocell controls, grounding and lightning protection systems with multiple ground rods and test wells, new utility service connections, and underground conduit runs. Specific site improvements include a new above-ground fuel storage tank with monitoring systems, pond fountain electrical controls, temporary restroom and office trailer electrical feeds, and flagpole lighting fixture upgrades. All work requires compliance with 2018 Kentucky Building Code, 2021 International Energy Conservation Code (IECC), 2021 International Mechanical Code (IMC), NFPA standards, and VA Fire Protection Design Manual. The contractor must provide complete submittal documentation, as-built drawings, warranty coverage for one year post-acceptance, and operator training. Fire-stopping, insulation, coordination with multiple trades, and protection of existing conditions during construction are mandatory requirements throughout all work areas.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
Correct FCA Deficiencies
CAMP NELSON NATIONAL CEMETERY
833CM3030
SA AB, MM
JANUARY 7, 2026
Bid Set
BID SET 1-7-2026
PLUMBING NOTES,
ABBREVIATIONS, AND LEGEND
P-001
SYMBOL DESCRIPTION
SANITARY PIPE (SAN)
GREASE WASTE PIPE (GW)
STORM WATER PIPE (ST)
COLD WATER PIPE (CW)
HOT WATER PIPE (HW)
HOT WATER RECIRCULATION PIPE (HWR)
VENT PIPE (V)
GAS PIPE (G)
GATE VALVE
BALL VALVE
BACK FLOW PREVENTER
BACK WATER VALVE
BALANCING VALVE
PRESSURE REDUCING VALVE (PRV)
OS&Y VALVE
OS&Y VALVE (IN VERTICAL)
BUTTERFLY VALVE
THERMOSTATIC MIXING VALVE
GAS COCK
PRESSURE RELIEF VALVE
REDUCER
PIPE DOWN
PIPE UP
PIPE CAP
FLANGE
UNION
WATER HAMMER ARRESTER
FLOOR DRAIN
FLOOR CLEAN OUT (FCO)
WALL CLEAN OUT (WCO)
EXPANSION TANK
PUMP
WATER METER
GAS PRESSURE REGULATOR
FLOOR SINK
RECIRCULATION PUMP
CONNECT TO EXISTING (CX)
POINT OF DISCONNECT (POD)
ABBREVIATION DESCRIPTION
Ø OR DIA DIAMETER
AFF ABOVE FINISHED FLOOR
AP ACCESS PANEL
BT BATHTUB
BLDG BUILDING
CLG CEILING
CO CLEAN OUT
CW COLD WATER
DEG DEGREES
DF DRINKING FOUNTAIN
DFU DAINAGE FIXTURE UNITS
DIA DIAMETER
DN DOWN
DW DISHWASHER
DWH DOMESTIC WATER HEATER
ETR EXISTING TO REMAIN
EWH ELECTRIC WATER HEATER
EWS EYE WASH STATION
EX EXISTING
F FAHRENHEIT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FS FLOOR SINK
G GAS
GAL GALLONS
GPM GALLONS PER MINUTE
GWH GAS WATER HEATER
HB HOSE BIB
HP HORSE POWER
HS HAND SINK
HW HOT WATER
HWR HOT WATER RECIRCULATION
I.E. INVERT ELEVATION
JAN JANITOR
LAV LAVATORY
LP LIQUID PROPANE
MAX MAXIMUM
MBH 1000 BTU/HR
MFR MANUFACTURER
MIN MINIMUM
MS MOP SINK
NIC NOT IN CONTRACT
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
PW POWER WASHER
RH RELATIVE HUMIDITY
RX REMOVE EXISTING
SAN SANITARY
SHW SHOWER
SP STATIC PRESSURE
TEMP TEMPERATURE
TYP TYPICAL
UR URINAL
V VENT
VA VETERANS AFFAIRS
VTR VENT THROUGH ROOF
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAUGE
PLUMBING ABBREVIATIONS
PLUMBING LEGEND
APPLICABLE CODES & STANDARDSPLUMBING NOTES
DIVISION 22 PLUMBING
22-0000 GENERAL REQUIREMENTS
SCOPE AND DRAWINGS
1. CONTRACTOR SHALL REFER TO ALL DRAWINGS AND SPECIFICATIONS IN THIS PACKAGE SUCH AS ARCHITECTURAL, STRUCTURAL, ELECTRICAL, AND PLUMBING. FULLY COORDINATE WITH ALL OTHER TRADES, OWNER, AND ARCHITECT REQUIREMENTS. ALL OF THE ABOVE-MENTIONED DRAWINGS AND
SPECIFICATIONS ARE CONSIDERED A PART OF THE CONTRACT DOCUMENTS.
2. CONTRACTOR IS TO INSPECT THE SITE BEFORE SUBMITTING BID AND MAKE ALLOWANCES FOR ALL VISIBLE, SPECIFIED OR REASONABLY ANTICIPATED FIELD CONDITIONS. SIGNIFICANT DISCREPANCIES FROM THE DRAWINGS, EXISTING SITE CONDITIONS, SPECIFICATIONS OR OTHER TRADES CONFLICT, ARE TO BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE OWNER, ARCHITECT AND ENGINEER IN
WRITING PRIOR TO SUBMITTAL OF BID.
3. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATE THE GENERAL LOCATION AND INTENT OF THE SYSTEMS. AS SUCH DRAWINGS DO NOT INDICATE EVERY FITTING, ELBOW, OFFSET, VALVE, AND OTHER COMPONENTS NECESSARY TO INSURE PROPER INSTALLATION OF A WORKING SYSTEM.
CONTRACTOR SHALL PROVIDE ALL NECESSARY FITTINGS, ACCESSORIES, AND AUXILIARY ITEMS TO
INSTALL THE SYSTEM AS DIAGRAMMED.
4. DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER, WHEN IN CONFLICT, THE STRICTEST PROVISION SHALL GOVERN. IF ONE IS MISSING MATERIAL OR LABOR SCOPE, CONTRACTOR SHALL PROVIDE AS IF IT IS MENTIONED IN BOTH.
5. CONTRACTOR SHALL PROVIDE AND INSTALL ALL WORK EQUIPMENT AND MATERIALS AS INDICATED ON THE PROJECT DRAWINGS AND SPECIFICATIONS TO PROVIDE A COMPLETELY OPERATIONAL SYSTEM.
6. PROVIDE ALL SUPERVISION, LABOR, MATERIALS, EQUIPMENT MISCELLANEOUS ITEMS, SERVICES AND ACCESSORIES REQUIRED BY STANDARD INDUSTRY PRACTICE FOR SUCH INSTALLATIONS, AND FOR
THE SAFE AND CORRECT OPERATION OF THE ENTIRE INSTALLATION.
7. PRODUCTS SHALL BE INSTALLED IN ACCORDANCE WITH MANUALS, GUIDELINES, OR INSTRUCTIONS
FURNISHED BY THE PRODUCT MANUFACTURER.
8. COMPETENT MECHANICS AND SUBCONTRACTORS USING PROPER TOOLS AND EQUIPMENT SHALL
PERFORM ALL WORK TO PRODUCE FIRST-QUALITY INSTALLATIONS. ALL WORK SHALL BE NEATLY INSTALLED, ACCESSIBLE FOR MAINTENANCE, AND COMPLETE WITH ALL ACCESSORIES REQUIRED.
9. COORDINATE ALL WORK WITH OTHER TRADES TO ENSURE ALL SYSTEMS FIT IN GIVEN SPACE SUCH AS ABOVE CEILINGS. ALL CEILING HEIGHTS INDICATED ON ARCHITECTURAL AND/OR INTERIOR DESIGN DRAWINGS AS WELL AS MINIMUM CLEARANCES REQUIRED BY LOCAL CODES SHALL BE MAINTAINED
THROUGHOUT THE BUILDING.
APPLICABLE CODES
1. ALL WORK AND EQUIPMENT SHALL BE INSTALLED AND COMPLY WITH THE LOCAL CODES. THE
CONTRACTOR SHALL COMPLY WITH THE LAWS, ORDINANCES, RULES, AND REGULATIONS OF ALL
GOVERNMENTAL AND PUBLIC UTILITY AUTHORITIES HAVING JURISDICTION OF ANY OF THE SYSTEMS
SPECIFIED.
2. ALL WORK SHALL CONFORM TO LOCAL AND STATE CODES AND TO APPLICABLE STATE LAWS AND, INCLUDING, BUT NOT LIMITED TO NATIONAL ELECTRIC CODE, IMC, IPC, IECC AND NFPA CODES. WHERE
CODE REQUIRES A VARIATION FROM SPECIFIC INFORMATION IN CONTRACT DOCUMENTS,
CONTRACTOR SHALL INCLUDE WORK REQUIRED TO COMPLY WITH CODE. CERTAIN CODE-REQUIRED ITEMS ARE MENTIONED IN THESE CRITERIA FOR EMPHASIS OR EXAMPLE ONLY. IDENTIFICATION AND
COMPLIANCE WITH ALL APPLICABLE CODES AND REGULATIONS ARE THE CONTRACTOR'S
RESPONSIBILITY.
3. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL APPLICABLE PERMITS AND CERTIFICATES OF
INSPECTION.
4. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE REQUIREMENTS OF THE OWNER'S INSURANCE CARRIER, INDUSTRY PRACTICE STANDARDS AND THE AMERICANS WITH DISABILITIES ACT (ADA).
ADDITIONALLY, FOOD SERVICE FACILITIES MUST ADHERE TO THE PERTINENT DEPARTMENT OF HEALTH REGULATIONS, SANITARY CODES, AND ALL OTHER APPLICABLE CODES, LAWS, REGULATIONS AND
DIRECTIVES.
GENERAL
1. CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, SEQUENCES AND
WORKMAN SAFETY.
2. COORDINATE SEQUENCING OF INSTALLATION, PHASING OF EQUIPMENT DEMOLITION, SCHEDULE OF WORK, UTILITY SHUTDOWNS, PARKING, MATERIAL STAGING AND OTHER POTENTIALLY DISRUPTIVE
ACTIVITIES WITH BUILDING MANAGEMENT.
3. THE DESIGN AND APPEARANCE OF ALL EXPOSED PIPING WHICH ARE VISIBLE FROM THE PUBLIC AREAS
ARE CRITICAL TO THE OVERALL VISUAL EFFECT AND ARE SUBJECT TO DETAILED REVIEW AND
APPROVAL BY THE OWNER.
4. ALL WATER AND VENT PIPING, CONDUIT SHALL BE INSTALLED AS HIGH AS REASONABLY POSSIBLE. ALL SANITARY PIPING SHALL BE INSTALLED BELOW THE SLAB AND AS TIGHT TO THE UNDERSIDE OF THE
SLAB AS POSSIBLE.
5. PIPING SHALL BE INSTALLED CONCEALED ABOVE CEILINGS OR IN WALL CHASES UNLESS OTHERWISE NOTED. PIPING SHALL BE INSTALLED AS DIRECT AS POSSIBLE WITHOUT UNNECESSARY BENDS OR
OFFSETS.
6. PIPING SHALL NOT BE INSTALLED OR ROUTED ABOVE OR BELOW ELECTRICAL PANELS AND
EQUIPMENT, THROUGH ELEVATOR EQUIPMENT ROOMS, ELEVATOR SHAFTS, OR STAIRWAYS UNLESS
THESE ITEMS SERVE THESE AREAS ONLY.
7. CONNECTIONS BETWEEN DISSIMILAR PIPING METALS SHALL BE MADE WITH SUITABLE DIELECTRIC
UNIONS.
8. PIPE OPENINGS SHALL BE STORED WITH CAPS OR COVERINGS DURING INSTALLATION.
9. CONFIRM UTILITY COMPANY REQUIREMENTS AND CONNECTION POINTS IN THE FIELD PRIOR TO
STARTING WORK.
10. IN CASE OF PARTIAL OCCUPANCY OF BUILDING, PERFORM THOSE ITEMS SPECIFICALLY MENTIONED AND OTHER ACTIVITIES THAT PRODUCE OBJECTIONABLE NOISE IN A MANNER PRESCRIBED BY OWNER
AND IN A MANNER THAT DOES NOT INTERFERE WITH THE USE OF THE EXISTING FACILITY.
11. CONTRACTOR SHALL REFER TO ARCHITECTURAL PLANS FOR APPROVED FLOOR PLAN DIMENSIONS
AND EXACT COMPONENT LOCATIONS. DO NOT SCALE ENGINEERING DRAWINGS.
CUTTING, DRILLING, AND PATCHING
1. ALL CUTTING AND REPAIRING NECESSARY TO THE EXECUTION OF THIS WORK SHALL BE DONE AND REPAIRED BY CONTRACTOR. ALL OPENINGS IN FIRE RATED ENCLOSURES SHALL BE FIRE STOPPED.
ALL OPENINGS SHALL BE FINISHED WITH NEAT TRIM OR FLANGES. PATCH AND FINISH AREAS
DAMAGED AS A RESULT OF OPENINGS TO MATCH ADJACENT AREAS.
2. ALL OPENINGS MUST BE NEATLY SAW CUT, CORE-BORED, SLEEVED, GROUTED, SEALED AND MADE
WATER AND FIREPROOF.
3. CONTRACTOR SHALL OBTAIN WRITTEN STRUCTURAL ENGINEER APPROVAL BEFORE DRILLING OR
CUTTING STRUCTURAL COMPONENTS.
4. SEAL ALL OPENINGS AND PENETRATIONS THROUGH FIRE RATED WALLS AND PARTITIONS WITH FIRE RESISTANT SEALANT THAT WILL PREVENT THE PASSAGE OF FIRE AND SMOKE. SEALANT SHALL HAVE
RATING EQUAL OR GREATER TO PENETRATED WALL.
5. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT EQUIPMENT LOCATIONS BEFORE CUTTING.
6. ALL ROOF PENETRATIONS SHALL BE COMPLETED BY ROOFER OF RECORD SO AS NOT TO VOID THE WARRANTY. PROVIDE CURBS AT LEAST 12” HIGH FROM THE TOP OF THE FINISHED ROOF, FOR ALL
ROOF OPENINGS AND EQUIPMENT MOUNTING. SUPPORT CURBS ON STRUCTURAL MEMBERS AND
FLASH INTO ROOFING FOR WATER TIGHT SEAL.
EXISTING CONDITIONS:
1. WHEN EXISTING WORK IS REMOVED, PIPES AND CONDUITS SHALL BE REMOVED, INCLUDING HANGERS, TO A POINT BELOW FINISHED FLOORS OR BEHIND FINISHED WALLS AND CAPPED. SUCH POINT SHALL BE FAR ENOUGH BEHIND FINISHED SURFACES TO ALLOW FOR INSTALLATION OF NORMAL THICKNESS OF REQUIRED FINISH MATERIAL. EQUIPMENT SHALL BE REMOVED AND NOT ABANDONED IN PLACE UNLESS OTHERWISE NOTED. AS REQUESTED BY OWNER, EXISTING EQUIPMENT SHALL REMAIN THEIR
PROPERTY AND BE DELIVERED TO THEM ON THE PREMISES WHERE DIRECTED. ALL OTHER
MATERIALS AND EQUIPMENT THAT ARE REMOVED SHALL BECOME PROPERTY OF THE CONTRACTOR
AND SHALL BE PROMPTLY REMOVED AND DISPOSED OF IN AN APPROVED MANNER.
2. WHEN WORK SPECIFIED CONNECTS TO EXISTING EQUIPMENT, PERFORM ALL NECESSARY
ALTERATIONS, CUTTINGS, FITTINGS, ETC., OF EXISTING WORK AS MAY BE NECESSARY TO MAKE
SATISFACTORY CONNECTIONS BETWEEN NEW AND EXISTING WORK, AND TO LEAVE COMPLETED
WORK IN A FINISHED AND WORKMANLIKE CONDITION.
3. REMOVAL AND RELOCATION OF SOME EXISTING COMPONENTS MAY BE NECESSARY FOR THE
COMPLETION OF THIS SCOPE. NOT ALL EXISTING CONDITIONS CAN BE COMPLETELY DETAILED ON THE
DRAWINGS AND AS SUCH THE CONTRACTOR SHALL SURVEY THE SITE PRIOR TO BIDDING.
4. WHEN THE WORK REQUIRES RELOCATION OF EXISTING EQUIPMENT, PERFORM ALL WORK AND MAKE NECESSARY CHANGES TO EXISTING WORK AS MAY BE REQUIRED TO LEAVE COMPLETED WORK IN A FINISHED AND WORKMANLIKE CONDITION. WHERE EXISTING INSULATION IS DISTURBED, REPLACE INSULATION WHERE REMOVED OR DAMAGED EQUAL TO EXISTING, IN TYPE THICKNESS AND R VALUE.
5. ENGINEER HAS NOT FUNCTIONALLY TESTED EXISTING EQUIPMENT. WHERE EXISTING EQUIPMENT IS TO BE REUSED, CONTRACTOR SHALL ALLOW FOR REASONABLE CHECKING, ADJUSTMENT AND MINOR
REPAIR TO RESTORE FULL FUNCTION. WORK WHICH IS REQUIRED AND WHICH IS BEYOND THAT
DESCRIBED ABOVE OR ON THE PLANS SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER,
ARCHITECT AND ENGINEER.
SITE PROTECTION AND CLEAN UP
1. THE CONTRACTOR SHALL PROVIDE FOR HIS OWN CLEAN UP, REMOVAL AND DISPOSAL OF DAILY TRASH. THE CONTRACTOR SHALL KEEP CLEAN AND MAINTAIN EACH AREA FOR USE AFTER WORK IN
THAT AREA IS COMPLETE.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF HIS OWN WORK, MATERIALS, AND OTHER BELONGINGS FROM DAMAGE.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL OWNER-PROPERTY IN THE WORK AREA. ALL MATERIALS THAT CAN BE DAMAGED BY TEMPERATURE OR HUMIDITY EXCURSIONS SHALL
BE REMOVED FROM THE WORK AREA AND STORED IN AN AIR-CONDITIONED ENVIRONMENT.
4. PROTECTION OF ROOF: THE ROOF SURROUNDING THE WORK AREA WHERE NEW EQUIPMENT IS TO BE DEMOLISHED OR INSTALLED SHALL BE PROTECTED WITH 1” INSULATION BOARD COVERED BY ½” PLYWOOD. SEAMS OF THE BOARD AND PLYWOOD SHALL BE STAGGERED SO NO ROOF MEMBRANE IS EXPOSED. FOLLOWING THE COMPLETION OF THE WORK, ALL DEBRIS IS TO BE CAREFULLY REMOVED
FROM THE ROOF PRIOR TO REMOVAL OF THE ROOF PROTECTION.
5. PROVIDE TEMPORARY HEATERS TO MAINTAIN WORKING TEMPERATURES. DO NOT USE INSTALLED
HVAC SYSTEMS FOR CONDITIONING DURING CONSTRUCTION.
6. WORK AREA SHALL BE COMPLETELY ENCLOSED AND SEALED FROM OCCUPIED AREAS. NEGATIVE
PRESSURE SHALL BE MAINTAINED AT ALL TIMES DURING CONSTRUCTION ACTIVITIES SUCH AS
DRYWALL SANDING, CUTTING AND GRINDING THAT RELEASE PARTICLES; OR ACTIVITIES SUCH AS
GLUING, PAINTING OR WELDING THAT RELEASE GASEOUS CONTAMINANTS. CLOSE SUPPLY AIR
OUTLETS AND RETURN AIR INLETS, CONNECT EXHAUST FAN TO EXHAUST SYSTEM OR TO BUILDING EXTERIOR AND OPERATE CONTINUOUSLY UNTIL COMPLETION OF ALL CONSTRUCTION ACTIVITIES.
7. PERFORM ALL ACTIVITIES THAT RELEASE PARTICLES, SUCH AS CUTTING AND SANDING, OR GASEOUS CONTAMINANTS, SUCH AS USE OF ADHESIVES AND PAINT, AT LEAST 72 HOURS PRIOR TO OCCUPANCY.
FULLY FLUSH SPACE WITH FRESH AIR AS MUCH AS CONDITIONS PERMIT IN THE 72 HOURS PRIOR TO
OCCUPANCY, BY OPENING DOORS, RUNNING HVAC UNITS AND EXHAUST FANS.
SUBMITTALS
1. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, CATALOG CUTS OR CERTIFIED PRINTS COVERING
ITEMS OF MECHANICAL AND ELECTRICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO, THE
FOLLOWING:
PIPING VALVES INSULATION
PUMPS BACKFLOW PREVENTERS WATER HEATERS
TANKS PLUMBING FIXTURES ALL OTHER PLUMBING EQUIPMENT
2. CONTRACTOR SHALL CLEARLY INDICATE CHARACTERISTICS ON EACH REQUIRED SUBMITTAL AND CERTIFY THAT THE EQUIPMENT & MATERIALS REPRESENTED BY THE SUBMITTALS ARE IN COMPLIANCE
WITH CONTRACT DOCUMENTS.
3. SUBMITTALS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE CONTRACT DOCUMENTS.
SUBMITTAL REVIEW SHALL NOT RELIEVE THE CONTRACTOR OF COMPLIANCE WITH CONTRACT
DOCUMENTS.
4. VERIFY ALL ELECTRICAL REQUIREMENTS FOR EQUIPMENT BEFORE ISSUING SUBMITTALS AND
EQUIPMENT PURCHASE.
5. EQUIPMENT SHALL BE AS SCHEDULED AND MEET ALL REQUIREMENTS AND PERFORMANCE LISTED IN SCHEDULES. MANUFACTURERS LISTED ARE BASIS OF DESIGN. SUBSTITUTIONS ARE SUBJECT TO OWNER AND ENGINEER'S APPROVAL. IT IS THE CONTRACTOR'S RESPONSIBILITY TO RE-EVALUATE ANY
SUBSTITUTED EQUIPMENT, REDESIGN IN ORDER TO COORDINATE THE SUBSTITUTION WITH THE
SYSTEM AND CERTIFY THAT THE SUBSTITUTION IS EQUIVALENT TO BASIS OF DESIGN.
RECORD DRAWINGS
1. MAINTAIN RECORD SET OF PLANS AS WORK PROGRESSES, SHOWING ADDITIONS AND SUBSTITUTIONS FROM DESIGN AND CONCEALED WORK. AT COMPLETION, A RECORD SET OF PLANS SHALL BE TURNED OVER TO THE OWNER AND INCORPORATED INTO THE OPERATION AND MAINTENANCE MANUALS. AS BUILT SET SHALL BE COMPETED IN CAD OR CLEAN NEAT PDF FORMAT WITH MARK-UPS IN RED.
CLOSEOUT & WARRANTY
1. UPON COMPLETION OF WORK, THE CONTRACTOR SHALL REMOVE ALL DEBRIS & UNUSED MATERIALS
AND THOROUGHLY CLEAN THE CONTRACT AREA.
2. PROVIDE OWNER WITH THREE BOUND COPIES OF ALL EQUIPMENT MANUFACTURER'S INSTALLATION, OPERATION AND MAINTENANCE MANUALS, TEST AND BALANCE REPORTS, RECORD DRAWINGS
EQUIPMENT SUBMITTALS, PARTS DIAGRAMS, AND OTHER MATERIALS RECEIVED OR PRODUCED
DURING CONSTRUCTION.
3. PROVIDE AT LEAST ONE DAY OF TRAINING TO OWNER'S PERSONNEL IN OPERATION OF EQUIPMENT
AND PREVENTATIVE MAINTENANCE REQUIRED FOR EACH SYSTEM.
4. ALL WORK SHALL BE GUARANTEED AGAINST DEFECTS OF MATERIAL AND/OR WORKMANSHIP FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE WORK BY THE OWNER FOR THE BENEFICIAL USE THEREOF. THE CONTRACTOR WILL REMEDY ANY DEFECTS AND ANY DAMAGE RESULTING FROM THE
WORK THAT OCCURS WITHIN THE PERIOD NAMED ABOVE.
5. REPAIR OR REPLACE WITHOUT MATERIAL AND LABOR CHARGE TO THE OWNER ALL ITEMS FOUND DEFECTIVE DURING THE WARRANTY PERIODS. IN THE CASE OF REPLACEMENT OR REPAIR DUE TO FAILURE WITHIN THE WARRANTY PERIOD, THE WARRANTY ON THAT PORTION OF THE WORK SHALL BE EXTENDED FOR A MINIMUM PERIOD OF ONE (1) YEAR FROM THE DATE OF SUCH REPLACEMENT OR
REPAIR.
GW
ST
G G
M
R
IT IS THE CONTRACTOR'S RESPONSIBILITY TO REVIEW THESE
CONSTRUCTION DOCUMENTS WITH THE LOCAL INSPECTORS FOR THEIR
APPROVAL. CONTACT ENGINEER WITH ANY ISSUES RAISED BY THE
INSPECTOR. THIS REVIEW SHALL TAKE PLACE BEFORE STARTING ANY
WORK.
CODE & PLANS REVIEW
2018 KENTUCKY BUILDING CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
2021 INTERNATIONAL MECHANICAL CODE (IMC)
2005 ENERGY POLICY ACT (EPAct)
2019 ASHRAE 90.1
ASHRAE 62.1
2024 VA FIRE PROTECTION DESIGN MANUAL
FEDERAL ENERGY MANAGEMENT PROGRAM (FEMP)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA 72, 88A, 90A, 96, 101)
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
AutoCAD SHX Text
CONSULTANTS
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
Correct FCA Deficiencies
CAMP NELSON NATIONAL CEMETERY
833CM3030
SA AB, MM
JANUARY 7, 2026
Bid Set
BID SET 1-7-2026
PLUMBING DETAILS
P-002
2"CWSEE PLANS FOR
CONTINUATION
SEE SITE PLAN FOR
CONTINUATION.
2" C
W
1/ 2"
C W5' -0
" M
AX
P
EXISTING BACKFLOW
PREVENTER (RPZ)
SERVING DRINKING
FOUNTAIN
EXISTING BACKFLOW
PREVENTER (RPZ)
STRAINER
NEW UTILITY
ROOM WALL
STAND PIPE
IN ROOM
EXISTING PRESSURE
REDUCING VALVE
(SET TO 70 PSI)
PRESSURE
GAUGE
P
EXTEND DOMESTIC WATER PIPES
BELOW SLAB TO LOCATION SHOWN
ON NEW WORK WATER PLAN
EXISTING DOMESTIC
WATER PIPES BELOW
SLAB
SCALE: NTS3 DOMESTIC WATER SERVICE ENTRANCE
TOP OF STRAINER TO BE SLIGHTLY LOWER
THAN FINISHED FLOOR - FINISHED FLOOR
TO BE SLOPED DOWN TOWARD DRAINS.
COORDINATE WITH FLOORING INSTALLER
CUT OFF EXCESSIVE RING
IF REQUIRED
FINISHED FLOOR ON REQUIRED
SETTING BED (SEE ARCHITECTURAL
FOR FLOOR SLOPES)
INSIDE CAULK
DRAIN SUPPORT
STRAP
PIPE
DRAIN BODY
ADJUSTABLE DRAIN
HEAD
TRAP PRIMER CONNECTION
(WHEN REQUIRED)
SCALE: NTS2 FLOOR DRAIN DETAIL
NOTES:
1. PROVIDE ROUND SECURED NICKEL BRONZE ADJUSTABLE TOP WITH "CO" CAST IN COVER. PROVIDE
CLEANOUT TOP WITH VARIATIONS SUITABLE FOR FLOOR COVERING (CARPET MARKER, RECESSED FOR TILE, SCORIATED FOR UNFINISHED FLOORS). PROVIDE PLASTIC PLUG IN CAST IRON BODY. CLEAN THE
TOP OF EXPOSED FCO AFTER INSTALLATION.
2. LOCATE AT BUILDING EXIT, AT ENDS OF RUNS, AT TURNS OF PIPE GREATER THAN 45 DEGREES, AT 50'
INTERVALS ON STRAIGHT RUNS, AND WHERE SHOWN ON PLANS. PROVIDE BACKFILL PER
ARCHITECTURAL SPECIFICATION. LOCATE CLEANOUTS WHERE THERE IS 18'' CLEAR AROUND. CONSULT
LOCAL CODES FOR OTHER FCO REQUIREMENTS.
MEMBRANE CLAMP
FLOOR SLAB ON
GRADE
HUB AND SPIGOT CAST
IRON PIPE BELOW FLOOR
SANITARY OR STORM
SEWER LINE
TWO-WAY CLEANOUT, FOR LOCATION
SEE SANITARY PLUMBING PLAN
COMBINATION WYE AND EIGHTH
BEND IN RUN. ENTER TOP OF PIPE.
LONG SWEEP ELBOW AT END
OR TURN OF RUN
SAME SIZE AS SANITARY PIPE
UP TO 4'' MAXIMUM
DIRECTION
OF FLOW
TOP OF STRAINER TO BE FLUSH
WITH FINISHED FLOOR -
COORDINATE WITH ARCHITECTURAL
PLANS
CUT OFF EXCESSIVE
RING IF REQUIRED
DRAIN BODY
ADJUSTABLE DRAIN
HEAD
TRAP PRIMER CONNECTION
(WHEN REQUIRED)
AS REQUIRED FOR
DEPTH OF SANITARY
PIPE
SCALE: NTS4 FLOOR CLEAN OUT DETAIL
PIPE
PIPE WITHOUT INSULATION PIPE WITH INSULATION
INSULATION
METAL JACKET
PIPE SLEEVE OR
CORE DRILLED
OPENING
SEALANT - JOINT 14"
MINIMUM WIDE BY 3 8"
DEEP
PIPE SLEEVE OR
CORE DRILLED
OPENING
POLY BACKUP
MATERIAL
SCALE: NTS6 PIPE THRU FLOOR DETAIL
4" 4" 4" 4"
SCALE: NTS5 SLAB REPAIR DETAIL
NEW SLAB
6X6X10 10 W.W.M.
EXIST.
ADJACENT SLAB
MIN. 4,000 P.S.I. CONC. SLAB
INFILL DEPTH TO MATCH
EXIST.
NEW WASTE LINE 6 MIL VIZQUEEN BARRIER W/
4'' COMPACTED GRANULAR
BASE BELOW
#4 REBAR X8'' @ 18'' O.C. MIN.
4'' EMBEDMENT HILTI HY150
ADHESIVE ANCHOR SYSTEM
NOTES:
1. ANY DISTURBED SOIL WILL BE RE-TREATED FOR
TERMITE PROTECTION
EXIST. EXIST.
SCALE: NTS9 PIPE SUPPORT DETAIL
NOTES:
1. ALL PIPE, CONDUIT, ETC. OF ALL TRADES SHALL BE COMBINED ON
SAME SUPPORT CHANNEL WHERE PRACTICAL.
2. SUPPORT CHANNEL LENGTH SHALL NOT BE DETERMINED UNTIL ALL
PIPING, CONDUIT, ETC. TO BE SUPPORTED IS COORDINATED.
3. SUPPORT CHANNEL SPACING SHALL BE NO MORE THAN 10'-0"
UNISTRUT P-1100 SERIES PIPE CLAMP,
USE FOR PIPING (TYP.)
NUMBER OF HANGER RODS SHALL BE
REQUIRED FOR PROPER SUPPORT
(MIN OF 2) ONLY ONE IS SHOWN FOR
CLARITY
UNISTRUT SUPPORT NUT (TYP.)
20 GA. GALV. 12" LONG METAL SHIELDS
SHALL BE USED AROUND INSULATION
AT ALL SUPPORT LOCATIONS (TYP.)
INSULATION (TYP.)
PIPE (TYP.)
CONDUIT (TYP.)
UNISTRUT UNI-CLIP CLAMP USE FOR
ELEC. CONDUIT
UNISTRUT 1 5 8" x 1 5 8" CHANNEL
SUPPORT (TYP.)
SCALE: NTS8 INSULATED PIPE HANGER DETAIL
CLEVIS HANGER (TYP.)
PIPE INSULATION COVER AND
FINISH TO MATCH ADJACENT
INSULATION
PRECAST INSULATION WITHIN
VAPOR BARRIER AS PER
MFRG. SPEC. COLD PIPE-TYPE
2 FIBERGLASS 7 14# DENSITY.
HOT PIPE-CALCIUM SILICATE
PIPE INSULATION BETWEEN
HANGER SECTION
16 GA. SHEET METAL
SADDLE 12" LONG
THREADED STEEL ROD WITH NUT
AND WASHER, BOTH SIDES (TYP.)
SECURE PIPE HANGER TO
STRUCTURE (TYP.)
HANGER ROD (TYP.)
SUPPORT ADJUSTMENT
NUT (TYP.)
PIPE
2'' CW SUPPLY
1 12'' O.D. P-TRAP
2'' HW 140° F
SUPPLY
2'' THERMOSTATIC
TEMPERING VALVE SEE NOTE
BELOW
NOTE:
1. PROVIDE THERMOSTATIC MIXING VALVE WITH CHECK STOPS
BELOW LAVS, SINKS & EYE WASH STATIONS. VALVE SHALL BE:
ZURN MODEL NO. TMV-1 W/ 12'' INLET/OUTLET, OR SYMMONS
MODEL NO. 7-225-CK-MS W/ 12'' INLET/OUTLET, 2.0 GPM SUPPLY,
MAX. SET SUPPLY TEMP. AT 110°F FOR LAVS & SINKS AND 90°F
FOR EYE WASH STATIONS.
SCALE: NTS1 MIXING VALVE DETAIL
WATER
HEATER
SCALE: NTS7 EWH-1 WATER HEATER DETAIL
VACUUM RELIEF VALVE LOCATED 6"
ABOVE TOP OF WATER HEATER
T&P RELIEF VALVE
MINIMUM 1-12"
AIR GAP
30"x30"x6" DRAIN PAN 18
GA. GALV. STEEL W/
HEMMED EDGES
2" DISCHARGE DRAIN FOR
T&P RELIEF VALVE
UNION (TYP)
EXPANSION TANK
4" CW
4" HW
BALL VALVE (TYP)
1" DRAIN LINE
2" DRAIN LINE.
DISCHARGE INTO
FLOOR DRAIN.
CHECK VALVE
4" HWR
RECIRC PUMP
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
CG-1
CG-1
CG-1
1 2 3 4 5
FE
FE
FE
EXISTING
GENERATOR
RX GWH
50-GAL
EXISTING 500 GAL
PROPANE TANK
EX 3" SAN UP TO
RX 3" STANDPIPE
RX
FD
EX
FD
EX
FCOEX 4" SAN
EX
I.E.=98.4'
EX I.E.=98.5'
EX 2" VENT UP
EX
" S
AN
RX 11
2" VENT UP
EX 2" SANEX
FCO
RX 11
2" VENT UP
RX
FD EX
" S
AN
EX 4" SAN
EX 4" SAN RX 2" SAN
EX 11
2" VENT UP
RX 11
2" VENT UP
RX
FD
EX
FCO
RX 11
4" VENT UP
EX 4" SAN
EX I.E.=94'
EX 4" SAN. REFER TO
CIVIL PLANS FOR
CONTINUATION.
EX 4" SAN. REFER TO
CIVIL PLANS FOR
CONTINUATION.
EX I.E.=94'
EX
" S
AN
EX OIL
SEPERATOR
EX 2" VENT
EX 2" VENT UP
EX 3" VENT
EX 4" VTR EX 4" VENT
EX 3" VENT
EX 11
2" VENT
EX 2" VENT
EX 4" VTR
EX 3" VENTEX 2" VENT
RX 2" VENT
PUBLIC
MALE
A-103
UTILITIES
A-102
IT ROOM
B-100
VESTIBULE
BW-117M
MULTI PURPOSE
A-100
A-101
PUBLIC
FEMALE
A-104
CORRIDOR
A-105
STAFF FEMALE
A-107
WASH BAY
STAFF MALE
A-106
RX
WC
RX
SHW RX
SHW
RX 2" VENT
RX
LAV
RX
LAV
RX
WC
RX
LAV
RX
LAV
RX
UR
RX WC RX
WC
RX MS
EX
FD
CG-1
CG-1
CG-1
CG-1
1 2 3 4 5
FE
FE
FE
RX GWH
50-GAL
EXISTING
GENERATOR
EXISTING 500 GAL
PROPANE TANK
EX SNK
EX
SHWR
RX
MS
RX
LAV
RX
LAV
RX
WC
RX
WCRX
UR
EX
HB
RX
LAV
RX
LAV
EX
SHWREX
HB
EX
REF
RX
UR
RX
WC
EX
EWS
EX
WALL
HYDRANT
EX
PW
2" INCOMING CW. REFER
TO CIVIL PLANS FOR
CONTINUATION.
2" CW
2" CW TO EXISTING
DRINKING FOUNTAIN.
REFER TO CIVIL PLANS
FOR EXACT LOCATION.
PUBLIC
MALE
A-103
UTILITIES
A-102
IT ROOM
B-100
VESTIBULE
BW-117M
MULTI PURPOSE
A-100
A-101
PUBLIC
FEMALE
A-104
CORRIDOR
A-105
STAFF FEMALE
A-107
WASH BAY
STAFF MALE
A-106
G G
G G
GGGG
GG
GG
EX 3 4" GAS TO
EX WATER HEATER
RX 3 4" GAS
EX 1" GAS
EX 3 4" GAS
EX 3 4" GAS
EX 3 4" GAS
EXISTING RADIANT
TUBE HEATER
EX BACKFLOW
PREVENTER
EX GAS
BELOW
GRADE
RX
WC
EX 1" CW
EX 3 4" CW
EX 3 4" HW
EX 1" HW
EX 11
2" HW
EX 2" CW
EX 11
2" HW
EX 2" CW
EX 11
2" CW
EX 11
4" HW
EX 1" CW
EX 1" CW
EX
" H W
EX 3 4" CW
EX 3 4" HW
EX 1" HW
EX 2" CW
EX 3 4" HWR
EX GAS
BELOW
GRADE
EX PUMP
1. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO START OF
ANY WORK AND ADVISE ENGINEER OF ANY DISCREPANCIES.
LEGEND
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
Correct FCA Deficiencies
CAMP NELSON NATIONAL CEMETERY
833CM3030
SA AB, MM
JANUARY 7, 2026
Bid Set
BID SET 1-7-2026
NOTES
NOT TO SCALE
KEY PLAN
1 SANITARY AND VENT PIPING PLAN - EXISTING AND REMOVAL
SCALE: 1/4" = 1'-0"
PUBLIC RESTROOM AND WASH
HOUSE BUILDING PLUMBING
PLAN - EXISTING AND REMOVAL
PD-101
2 DOMESTIC WATER AND GAS PIPING PLAN - EXISTING AND REMOVAL
SCALE: 1/4" = 1'-0"
DISCONNECT EXISTING AAON DOAS UNIT FROM EXISTING GAS PIPING. REMOVE
EXISTING GAS PIPING BACK TO LOCATION SHOWN. CAP AND SEAL PIPE AIRTIGHT.
REMOVE AND DISCARD EXISTING GAS WATER HEATER AND ASSOCIATED
EXPANSION TANK.
RELOCATE EXISTING BACKFLOW PREVENTER TO LOCATION SHOWN ON NEW
WORK DRAWINGS, ON SHEET PN-101.
REMOVE EXISTING HOT/COLD WATER BRANCH PIPE BACK TO MAIN, CAP AND
SEAL WATERTIGHT.
RELOCATE STUB-UP FOR DOMESTIC WATER SUPPLY AND COLD WATER FEED
FOR REMOTE WATER FOUNTAIN TO LOCATION SHOWN ON NEW WORK
DRAWINGS, ON SHEET PN-101.
REMOVE EXISTING GAS BRANCH PIPE TO EXISTING RADIANT TUBE HEATER. CAP
AND SEAL EXISTING GAS MAIN AIRTIGHT.
CAP EXISTING SANITARY PIPE WITH CLEANOUT PLUG, FLUSH WITH FINISHED
FLOOR.
INSULATE ALL NEW AND EXISTING
WATER PIPING ACCORDING TO
SPECIFICATION SECTION 22 07 11
-PLUMBING INSULATION
INSULATE ALL NEW AND EXISTING
WATER PIPING ACCORDING TO
SPECIFICATION SECTION 22 07 11
-PLUMBING INSULATION
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
SERVICE BAY
B1
OFFICE
B3
LOUNGE
B2
VESTIBULE
B4
LOCKER RM
B5
WOMEN
B6
MEN
B7
RX EWH
EX
HB
RX
SNK
RX
UR
RX
WC
EX
WC
EX
WC
EX
LAV
EX
LAV
RX
SNK
RX
EWS
EX 3 4" CW
RX 12" CW
& HW
EX 3 4" HW
EX 3 4" HW
EX 12" CW
EX 12" CW
& HW
RX
SHW
1 1
SERVICE BAY
B1
OFFICE
B3
LOUNGE
B2
VESTIBULE
B4
LOCKER RM
B5
WOMEN
B6
MEN
B7
RX EWH
RX
SHW
RX
SNK
RX
UR
RX
WC
EX
WC
EX
WC
EX
LAV
EX
LAV
RX
SNK
RX
EWS
EX 2" VENT UP
RX 2" VENT UP
EX 4" VTR
EX
CO
EX
CO
EX 4" SAN TO
EX SEPTIC TANK
EX 4" SANEX 2" SAN
EX 3" SAN
EX 2" SAN
EX 2" VENT UP
EX 4" SAN
EX 2" VENT
RX 2" VENT
EX 2" VENT
EX
FD
EX
FD
REMOVE EXISTING HOT/COLD WATER BRANCH PIPE BACK TO MAIN, CAP AND
SEAL WATERTIGHT.
REMOVE EXISTING WATER HEATER. DISCONNECT AND REMOVE ASSOCIATED
EXISTING CW & HW PIPING BACK TO MAIN, CAP AND SEAL WATERTIGHT.
MODIFY EXISTING SANITARY PIPE IN WALL TO CONNECT TO PLUMBING FIXTURES
SEE NEW WORK PLANS FOR MORE INFORMATION.
REMOVE EXISTING HOT/COLD WATER STUB OUTS BACK TO WALL, TEMPORARILY
CAP, WATERTIGHT.
REMOVE EXISTING SANITARY PIPE BACK TO WALL CAVITY. CAP AND SEAL
SANITARY IN WALL CAVITY, WATERTIGHT.
REMOVE EXISTING TOILET FLANGE AND ASSOCIATED SANITARY BACK TO SLAB.
CAP AND SEAL SANITARY WITH CLEANOUT PLUG FLUSH WITH FINISHED FLOOR,
WATERTIGHT.
1. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO START OF
ANY WORK AND ADVISE ENGINEER OF ANY DISCREPANCIES.
LEGEND
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
Correct FCA Deficiencies
CAMP NELSON NATIONAL CEMETERY
833CM3030
SA AB, MM
JANUARY 7, 2026
Bid Set
BID SET 1-7-2026
NOTES
NOT TO SCALE
KEY PLAN
2 DOMESTIC WATER PIPING PLAN - EXISTING AND REMOVAL
SCALE: 1/4" = 1'-0"
HISTORIC MAINTENANCE
BUILDING PLUMBING PLAN -
EXISTING AND REMOVAL
PD-102
1 SANITARY AND VENT PIPING PLAN - EXISTING AND REMOVAL
SCALE: 1/4" = 1'-0"
INSULATE ALL NEW AND EXISTING
WATER PIPING ACCORDING TO
SPECIFICATION SECTION 22 07 11
-PLUMBING INSULATION
INSULATE ALL NEW AND EXISTING
WATER PIPING ACCORDING TO
SPECIFICATION SECTION 22 07 11
-PLUMBING INSULATION
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
1 2 3 4 5
CG-1
CG-1
CG-1 CG-1
FE
FE
FE
CG-1
EXISTING
GENERATOR
GWH-1
50-GAL
EXISTING 500 GAL
PROPANE TANK
3" SAN UP TO
3" STANDPIPE
EX 4" SAN
EX I.E.=98.4'
EX I.E.=98.5'
EX
FCO
EX 4" SAN
4" VENT UP
EX I.E.=94'
EX 4" SAN. REFER TO
CIVIL PLANS FOR
CONTINUATION.
EX 4" SAN. REFER TO
CIVIL PLANS FOR
CONTINUATION.
EX I.E.=94'
EX
" S
AN
EX OIL
SEPERATOR
EX 2" VENT UP
EX 3" VENT
EX 4" VTR
EX 4" VENT
EX 3" VENT
EX 11
2" VENT
EX 2" VENT
EX 4" VTR
EX 3" VENT
EX 2" VENT
UTILITIES
A-102
MULTI PURPOSE
A-100
EX
FCO
LAV-1
LAV-1
LAV-1
LAV-1
MS-1
UR-1
WC-1
FD-1
EX 4" SAN
WC-1
WC-1
FCO
4" SAN
EX 4" SAN
WC-1
EX 4" SAN
EX 4" SAN
EX 2" SAN
FCO
EX 2" VENT
EX 4" SAN
PUBLIC
MALE
A-103
IT ROOM
B-100
VESTIBULE
BW-117MA-101 PUBLIC
FEMALE
A-104
WASH BAY
STAFF
TOILET
A-106
CORRIDOR
A-105
EX
EWS
DF-1 DF-2
ICE-1
HD-1
2" VENT
LAV-1
WC-1
SHW-1
EX 3" SAN
2" VENT
FD-1
2" VENT
EX
FD
EX
FD
2" VENT
EX 11
2" SAN
CG-1
CG-1
1 2 3 4 5
CG-1
CG-1
CG-1 CG-1
FE
FE
FE
CG-1
EXISTING
GENERATOR
EXISTING 500 GAL
PROPANE TANK
GWH-1
50-GAL
EX 1" CW
EX 3 4" CW
EX 3 4" HW
EX 1" HW
EX 11
2" HW
EX 2" CW
EX 11
2" HW
EX 2" CW
EX 11
2" CW
EX 11
4" HW
EX 1" CW
EX
" H W
EX 3 4" CW
EX 3 4" HW
EX 1" HW
EX 2" CW
EX
SNK
MS-1
EX
HB
EX
HB
EX
REF
EX 3 4" HWR
EX
EWS
EX
WALL
HYDRANT
2" INCOMING CW. REFER
TO CIVIL PLANS FOR
CONTINUATION.
2" CW
2" CW TO EXISTING
DRINKING FOUNTAIN.
REFER TO CIVIL PLANS
FOR EXACT LOCATION.
PUBLIC
MALE
A-103
UTILITIES
A-102
IT ROOM
B-100
VESTIBULE
BW-117M
MULTI PURPOSE
A-100
A-101 PUBLIC
FEMALE
A-104
WASH BAY
G G
G G
G G
GGGG
GG
G
EX 1" GAS
EX 3 4" GAS
EX 3 4" GAS
EXISTING RADIANT
TUBE HEATER
EX BACKFLOW
PREVENTER
EX GAS
BELOW
GRADE
4" GAS TO EX
WATER HEATER
LAV-1
LAV-1
LAV-1
LAV-1
UR-1
WC-1
WC-1 WC-1
STAFF
TOILET
A-106
CORRIDOR
A-105
RTH-1
40,000 BTU
RTH-2
40,000 BTU
EX
PW
G G
G G
G
4" GAS
G
4" GAS
4" GAS
4" GAS
1" HW
2" CW
LAV-1
WC-1
DF-1
ICE
MACHINE
EX 1" CW
2" HW
1" CW
EX PUMP
SHW-1
LEGEND
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
Correct FCA Deficiencies
CAMP NELSON NATIONAL CEMETERY
833CM3030
SA AB, MM
JANUARY 7, 2026
Bid Set
BID SET 1-7-2026
NOTES
NOT TO SCALE
KEY PLAN
1 SANITARY AND VENT PIPING PLAN - EXISTING AND NEW WORK
SCALE: 1/4" = 1'-0"
PUBLIC RESTROOM AND WASH
HOUSE BUILDING PLUMBING
PLAN - EXISTING & NEW WORK
PN-101
1. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO START OF
ANY WORK AND ADVISE ENGINEER OF ANY DISCREPANCIES.
2. SANITARY PIPING SHOWN SHALL BE BELOW THE SLAB, VENT PIPING SHALL BE
INSTALLED TIGHT TO CEILING ABOVE.
3. INSTALL WATER HAMMER ARRESTERS ON THE HOT & COLD SUPPLY FOR ALL
LAVATORIES AND SINKS ON THE HIGHEST POINT AT THE END OF EACH BRANCH.
4. SLOPE ALL SANITARY PIPING, 3" AND ABOVE AT 18" PER FOOT (MIN), AND 2" AND
SMALLER AT 14" PER FOOT (MIN).
5. ALL LAVATORIES AND SINKS SHALL HAVE MIXING VALVES, SEE DETAIL SHEET.
DISCHARGE SHALL BE SET TO 110°F (ADJUSTABLE).
6. HOT WATER PIPING HAS BEEN DESIGNED TO MEET IECC 404.5. INSTALL PIPING AS
PER DRAWINGS SUCH THAT HOT WATER TERMINATION POINT TO ALL PUBLIC
LAVATORIES ARE WITHIN 24" OF HOT WATER LOOP.
2 DOMESTIC WATER AND GAS PIPING PLAN - EXISTING AND NEW WORK
SCALE: 1/4" = 1'-0"
NEW LOCATION OF EXISTING BACKFLOW PREVENTER. SEE DETAIL ON SHEET
PN-002 FOR WATER SERVICE ENTRANCE AND BACKFLOW INSTALLTION
INFORMATION.
EXTEND EXISTING WATER SERVICE AND DRINKING FOUNTAIN WATER FEED
PIPING BELOW GRADE TO NEW EQUIPMENT ROOM LOCATION.
DROP 3 4" COLD WATER IN WALL FOR RESTROOM LAVATORIES. INSTALL
SHUT-OFF VALVE IN DROP, PROVIDE ACCESS PANEL FOR VALVES.
DROP 11
2" COLD WATER IN WALL FOR RESTROOM WATER CLOSETS. INSTALL
SHUT-OFF VALVE IN DROP, PROVIDE ACCESS PANEL FOR VALVES.
INSTALL WATER HAMMER ARRESTORS IN COLD AND HOT WATER LINES. PROVIDE
ACCESS PANEL.
INSTALL GWH-1 WITH DRAIN PAN. ROUTE DRAIN PAN TO NEAREST FLOOR DRAIN.
INSULATE ALL NEW AND EXISTING WATER
PIPING ACCORDING TO SPECIFICATION
SECTION 22 07 11 -PLUMBING INSULATION
INSULATE ALL NEW AND EXISTING WATER
PIPING ACCORDING TO SPECIFICATION
SECTION 22 07 11 -PLUMBING INSULATION
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
EX
HB
EX
WC
EX
LAV
EX 3 4" CW
EX 3 4" HW
EX 3 4" HW
EX 12" CW
SERVICE BAY
B1
OFFICE
B3
MEN'S
LOCKER
ROOM
B5
MEN
B7
WOMEN'S
LOCKER
ROOM
B4
WOMEN
B6
EX 12" CW
& HW
4" HW DN
IN WALL
SNK-1
DF-1 EWH-1
IN ATTIC
2" HWR
PUMP-1
IN ATTIC
4" HW
EX
WC
EX
LAV
DRAINPAN
4" OVERFLOW
4" OVERFLOW
DN TO SPLASHBLOCK
EXPANSION TANK
IN ATTIC
EWS-13
OPEN OFFICE
B2
EX 4" VTR
EX
CO
EX
CO
EX 4" SAN TO
EX SEPTIC TANK
EX 4" SANEX 2" SAN
EX 3" SAN
EX
FD
EX 2" SAN
EX 2" VENT UP
EX 4" SAN
EX 2" VENT
EX
FD
FD-1
SERVICE BAY
B1
OFFICE
B3
MEN'S
LOCKER
ROOM
B5
MEN
B7
WOMEN'S
LOCKER
ROOM
B4
WOMEN
B6
EX
WC
EX
LAV
SNK-1
DF-1
EX
WC
EX
LAV
2" VENT UP
EX 2" VENTFCO
2" VENT UP
EX 2" VENT
EWS-1
OPEN OFFICE
B2
FCO
INSTALL EWH-1 AND PUMP-1 IN ATTIC ABOVE MEN'S RESTROOM.
CONNECT 12" CW & HW PIPING TO EXISTING CW & HW PIPING INSIDE
WALL.
EMERGENCY EYEWASH TO BE PROVIDED WITH POINT-OF-USE MIXING
VALVE. DISCHARGE TO BE SET TO 90° (ADJUSTABLE).
ENGINEER HAS NOT VERIFIED EXISTING SANITARY PIPING BELOW
GRADE. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS
PRIOR TO START OF ANY WORK AND ADVISE ENGINEER OF ANY
DISCREPANCIES.
1. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO START OF
ANY WORK AND ADVISE ENGINEER OF ANY DISCREPANCIES.
2. SANITARY PIPING SHOWN SHALL BE BELOW THE SLAB, VENT PIPING SHALL BE
INSTALLED TIGHT TO CEILING ABOVE.
3. SLOPE ALL SANITARY PIPING, 3" AND ABOVE AT 18" PER FOOT (MIN), AND 2" AND
SMALLER AT 14" PER FOOT (MIN).
4. ALL EYE WASH STATIONS HAVE MIXING VALVES. DISCHARGE SHALL BE SET TO
90°F (ADJUSTABLE).
LEGEND
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
Correct FCA Deficiencies
CAMP NELSON NATIONAL CEMETERY
833CM3030
SA AB, MM
JANUARY 7, 2026
Bid Set
BID SET 1-7-2026
NOTES
NOT TO SCALE
KEY PLAN
2 DOMESTIC WATER PIPING PLAN - EXISTING AND NEW WORK
SCALE: 1/4" = 1'-0"
HISTORIC MAINTENANCE
BUILDING PLUMBING PLAN -
EXISTING AND NEW WORK
PN-102
1 SANITARY AND VENT PIPING PLAN - EXISTING AND NEW WORK
SCALE: 1/4" = 1'-0"
INSULATE ALL NEW AND EXISTING WATER
PIPING ACCORDING TO SPECIFICATION
SECTION 22 07 11 -PLUMBING INSULATION
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
GROUND
ROOF
CEILING
EX
GWH-1
LAV-1 LAV-1 LAV-1LAV-1WC-1UR-1WC-1WC-1LAV-1 WC-1 EX
HB
EX
EWS
EX
HB
EX
PW
EX
SNK
EX
REF
EX
HB
MS-1
EX 3 4" HWR
EX 2" CW SERVICE
2" CW
SERVICE
2" CW
EX 2" CWEX 2" CWEX 1" CW EX 1" CW
EX 11
2" HWEX 1" HW
EX 1" HWEX 3 4" CW
EX 3 4" HW NEW LOCATION
OF EX BACKFLOW
PREVENTERS
4" CW
4" HW
2" CW11
2" CW
2" CW
2" HW
2" CW
2" HW
SHW-1 DF-1
DF-2
ICE
EX 12" CW TO FOUNTAIN
EX WATER HAMMER ARRESTER
GROUND
ROOF
CEILING
LAV-1
(1-DFU)
WC-1
(4 DFU)
LAV-1
(1-DFU)
LAV-1
(1-DFU)
LAV-1
(1-DFU)
FD-1 EX
FCO
UR-1
(4 DFU)FD-1FD-1 3" STAND
PIPE FCOMS-1
(2-DFU)
WC-1
(4 DFU)
WC-1
(4 DFU)
EX
FCO
EX SNK
(2-DFU)
WC-1
(4 DFU) FCO
EX EWS
(1-DFU)
EX OIL/ WATER
SEPERATOR
EX 4" SAN. REFER
TO CIVIL PLANS FOR
CONTINUATION.
EX 4" VTR EX 4" VTR
EX 4" SAN
(30-DFU)
EX 4" SAN
(28-DFU)
EX 4" SAN
(14-DFU)
EX 4" SANEX 4" SAN
(12-DFU)
2" SAN
(4-DFU)
EX 4" SAN4" SAN
(8-DFU)
EX 2" SAN
(2-DFU)
EX 4" SAN
2" VENT
EX 3" VENTEX 4" VENTEX 3" VENT
4" VENT
EX 2" VENT
2" V 2" V 2" V 2" V 3" V 2" V 2" V
2" VENT
EX 3" VENTEX 2" VENT
2" VENT 2" VENT
SHW-1
(2-DFU)
DF-1
DF-2
(1-DFU)
HD-1
(1-DFU)
LAV-1
(1-DFU)
2" V
FD-1
(2-DFU)
2" V
GROUND
ROOF
CEILING
EXISTING PROPANE TANK
(500 GALLONS)
PP
EXISTING
GENERATOR
(203 MBH)
FIRST STAGE
REGULATOR
EX SECOND STAGE REGULATOR
(OUTLET PRESSURE 11" WC)
BELOW GRADE
PIPING
EX 3 4" GAS
P
EX SECOND STAGE
REGULATOR (OUTLET
PRESSURE 11" WC)
RTH-1
40 MBH
EX GWH-1
(45 MBH)
EX
4" G
AS EX
" G
AS3
4" GAS
UTILITY ROOM WASHBAY
EXTERIOR
EX RTH
40 MBH
RTH-2
40 MBH
4" GAS
RRR
4" GAS 3
4" GAS3
4" GAS
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
Correct FCA Deficiencies
CAMP NELSON NATIONAL CEMETERY
833CM3030
SA AB, MM
JANUARY 7, 2026
Bid Set
BID SET 1-7-2026
2 PUBLIC RESTROOM/WASHBAY BUILDING DOMESTIC WATER PIPING RISER DIAGRAM
SCALE: NTS
PLUMBING SCHEDULES AND
RISER DIAGRAMS
PN-601
1 PUBLIC RESTROOM/WASHBAY BUILDING SANITARY AND VENT PIPING RISER DIAGRAM
SCALE: NTS
3 PUBLIC RESTROOM/WASHBAY BUILDING GAS PIPING RISER DIAGRAM
SCALE: NTS
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
G
(3)
ELECTRICAL SYMBOLS ELECTRICAL ABBREVIATIONS
SINGLE POLE TOGGLE SWITCH - 20 AMP, 120V OR 277V, M.H. 48" AFF, UON.
THREE WAY TOGGLE SWITCH - 20 AMP, 120V OR 277V, M.H. 48" AFF, UON.
WEATHER PROOF SWITCH - 20 AMP, 120V OR 277V, M.H. 48" AFF, UON.
LIGHT SWITCH WITH BUILT-IN OCCUPANCY SENSOR.
OCCUPANCY SENSOR
MOTION SENSOR
MOTOR OPERATED SWITCH
SINGLE/DUPLEX TYPE RECEPTACLE - 20 AMP, 120 VOLT, NEMA 5-20R,
M.H. 18" AFF, UON.
QUADRUPLEX TYPE RECEPTACLE - 20 AMP, 120 VOLT, NEMA 5-20R,
M.H. 18" AFF, UON.
DUPLEX WEATHER PROOF RECEPTACLE WITH GROUND FAULT CIRCUIT
INTERRUPTER PROTECTION - 20 AMP, 120 VOLT, NEMA 5-20R, M.H. 18"
AFF, UON.
QUADRUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT
INTERRUPTER PROTECTION - 20 AMP, 120 VOLT, NEMA 5-20R, M.H. 18"
AFF, UON.
DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER
PROTECTION - 20 AMP, 120 VOLT, NEMA 5-20R, M.H. 18" AFF, UON.
SPECIAL TYPE RECEPTACLE - 120 VOLT , 1PHASE, L5-30A
SPECIAL TYPE RECEPTACLE - 240 VOLT , 1PHASE
CEILING MOUNTED DUPLEX RECEPTACLE - 20 AMP, 120 VOLT, NEMA
5-20R
CEILING MOUNTED DUPLEX GFCI RECEPTACLE - 20 AMP, 120 VOLT,
NEMA 5-20R
FLOOR BOX WITH (4) POWER, (2) CAT 6E, (1) HDMI AND (1) DUAL USB
PORT TYPE OUTLET
DISCONNECT SWITCH, AMP/ POLES / ENCLOSURE NEMA RATING / FUSE
PER NAME PLATE.
COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH
MOTOR STARTER
ELECTRIC MOTOR
PANELBOARD
JUNCTION BOX, PULL BOX WALL/CEILING MOUNTED
M
HOMERUN WIRING WITH A DEDICATED EQUIPMENT GROUND WIRE TO
THE REFERENCED PANELBOARD. ARROW HEADS AND NUMERALS
INDICATE THE CIRCUIT NUMBERS.
CONDUIT DOWN OR AWAY
CONDUIT UP OR TOWARD VIEWER
CONDUIT, STUBBED AND CAPPED AS SHOWN
GROUND GRID CABLE
UNDERGROUND ELECTRIC
CIRCUIT BREAKER, THERMAL MAGNETIC TRIP SHOWN,
3 POLE UON.
FUSE - RATING INDICATED
DELTA CONNECTION, THREE PHASE
DELTA CONNECTION, SINGLE PHASE
WYE CONNECTION - UNGROUNDED, GROUNDED, THREE PHASE
WYE CONNECTION - UNGROUNDED, GROUNDED, SINGLE PHASE,
FUSED SWITCH, MEDIUM VOLTAGE
SURGE ARRESTER/LIGHTNING ARRESTER
DRY CONTACTS - NO, NC
GROUND
POTENTIAL TRANSFORMER
TRANSFORMER
CURRENT TRANSFORMER,
NUMBER INDICATED
CORE BALANCE CURRENT TRANSFORMER
MH-X
EXISTING, NEW ELECTRIC MANHOLE OR
HANDHOLE AND NUMBER
INTERLOCKED RECEPTACLE WITH
DISCONNECT SWITCH
FIELD PHOTOGRAPHPX
EX.XX
TERMINATION
GROUNDING RESISTOR
A
AC
AF
AFF
AFG
AHU
AIC
AL
AM
AT
ATS
AUTO
AUX
AWG
BAT
BKR
BLDG
BOCA
C
CB
CC
CH
CIR,CKT
CLR
COMB
CONT'D
CPT
CR
CT
CU
DC
DIA
DIST
DIV
DN
DP
DSW
DWG
E
EA
EC
ECB
EF
EL
EMH
EO
ER
ETM
ETR
EX
F
FA
FAAP
FACP
FDR
FLR
FSS
FUT
G
GALV
GC
GFI
GFP
GFR
GND
HH
HP
HVAC
HZ
IC
ICCB
I & C
ID
IG
INST
ITC
JB
K
KCMIL
KVA
KW
LA
LB
LO
LCP
LOS
LVL
AMPERE
ALTERNATING CURRENT
AMPERE FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERES INTERRUPTING
CAPACITY (SYM, RMS, AMPS)
ALUMINIUM
AMMETER
AMPERE TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUXILIARY
AMERICAN WIRE GAUGE
BATTERY
BREAKER
BUILDING
BUILDING OFFICIALS AND
CODE ADMINISTRATORS
CONDUIT
CIRCUIT BREAKER
CONTROL CABLE
CABINET HEATER
CIRCUIT
CLEAR
COMBINATION
CONTINUED
CONTROL POWER TRANSFORMER
CONTROL RELAY
CURRENT TRANSFORMER
COPPER, COMPRESSOR UNIT
DIRECT CURRENT
DIAMETER
DISTRIBUTION
DIVISION
DOWN
DISTRIBUTION PANEL
DISCONNECTING SWITCH
DRAWING
EMPTY, ELECTRICAL INTERLOCK,
EXISTING
EACH
EMPTY CONDUIT
ENCLOSED CIRCUIT BREAKER
EXHAUST FAN
ELEVATION
ELECTRIC MANHOLE
ELECTRIC OPERATOR
EXISTING RELOCATED
ELAPSED TIME METER
EXISTING TO REMAIN
EXISTING
FUSE, FRAME, FRONT
FRAME AMPS
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FEEDER
FLOOR
FUSED SAFETY SWITCH
FUTURE
GREEN, GROUND, GROUND GRID
GALVANIZED
GENERATOR CONTACTOR,
GENERATOR CONTROL PANEL
GROUND FAULT INTERRUPTER
GROUND FAULT PROTECTION
GROUND FAULT RELAY
GROUND
HANDHOLE
HORSE POWER
HEATING VENTILATION AND AIR
CONDITION
HERTZ
INTERRUPTING CAPACITY
INSULATED CASE CIRCUIT BREAKER
INSTRUMENTATION & CONTROL
IDENTIFICATION
ISOLATED GROUND
INSTANTANEOUS
INTERFACE TERMINAL CABINET
JUNCTION BOX
KEY INTERLOCK
KILO CIRCULAR MILS
KILOVOLT-AMPERE
KILOWATT
LIGHTNING ARRESTER
CONDUIT BOX, RIGHT ANGLE
LOCKOUT
LOCAL CONTROL PANEL
LOCKOUT STOP PUSH BUTTON
LEVEL
MAIN CIRCUIT BREAKER
MACHINE
MULTIFUNCTION RELAY
MANHOLE, MOUNTING HEIGHT
MINIMUM
MAIN LUG ONLY
MOUNT
MOUNTED
NEUTRAL
NON-AUTOMATIC
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NON-FUSED SAFETY SWITCH
NORMALLY OPEN
NUMBER
NAMEPLATE
NOT TO SCALE
OVERLOAD
POLE OR POLES
PULL BOX, PUSH BUTTON
POWER FACTOR
PHASE
PILOT LIGHT
MICROPROCESSOR BASED METERING
PHASE MONITOR RELAY
POWER MONITORING DEVICE
PANEL
POWER QUALITY MONITOR
PAIR
PRIMARY
POTENTIAL TRANSFORMER
REMOVE, RED, REAR, RUN CONTRACTORS
RIGID GALVANIZED STEEL / GALVANIZED RIGID
CONDUIT
RECEPTACLE
REQUIRED
ROOT MEAN SQUARE
ROOM
ROOF TOP UNIT
SURGE ARRESTOR
SURGE PROTECTION DEVICE
SWITCH
SYMMETRICAL
TRIP AMPS
TERMINAL BOARD, TERMINAL BLOCK
TIME DELAY RELAY
TERMINAL JUNCTION BOX
TWISTED SHIELDED PAIR
HIGH-TEMP RELAY
TEST SWITCH
TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYPICAL
UNDERGROUND
UNDERWRITERS LABORATORY
UNLESS OTHERWISE NOTED
VOLTS OR VOLTAGE
VOLTAMPS
MB,MCB
M/C
MFR
MH
MIN
MLO
MT
MTD
N
NA
NC
NEC
NEMA
NFPA
NFSS
NO
NO.
NP
NTS
OL
P
PB
PF
PH
PL
PM
PMR
PMT
PNL
PQM
PR
PRI
PT
R
RGS,GRC
RECPT
REQ'D
RMS
RM
RTU
SA
SPD
SW
SYM
TA
TB
TDR
TJB
TSP
TSH
TS
TVSS
TYP
UG
UL
UON
V
VA
W W/
WH
WP
WR
XFMR
Z
O
WATTS, WIRE
WITH
WATTHOUR
WEATHERPROOF
WELDING RECEPTACLE
TRANSFORMER
IMPEDANCE
PHASE, DIAMETER
NUMBER
ELECTRICAL GENERAL NOTES
1. IT IS THE INTENT OF THESE DRAWINGS AND OTHER RELATED DOCUMENTS TO PRODUCE A
COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM. PROVIDE ALL LABOR, MATERIAL, TESTS,
AND OTHER SERVICES AS MAY BE NECESSARY TO ACHIEVE THIS PRODUCT. ACKNOWLEDGE
ACCEPTANCE OF THE PLANS AS AN ADEQUATE DEFINITION OF THE SCOPE OF WORK. EXTRA
COST CLAIMS BASED ON DISCREPANCIES ON THE PLANS WILL NOT BE CONSIDERED.
2. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE
(NEC) AND ALL LOCAL CODES HAVING JURISDICTION. ALL EQUIPMENT, DEVICES, AND
MATERIAL SHALL BE LISTED WITH UNDERWRITERS LABORATORIES FOR ITS APPLICATION AS
INSTALLED AND SHALL BEAR THE UL LABEL.
3. OBTAIN THE REQUIRED BUILDING AND TRADES PERMIT AND COORDINATE WITH THE
GOVERNMENT.
4. VISIT THE SITE AND EXAMINE CONDITIONS OF THE PREMISES AND THE CHARACTER AND
EXTENT OF WORK REQUIRED PRIOR TO CONSTRUCTION. BRING TO THE ATTENTION OF
GOVERNMENT FOR FURTHER DIRECTIONS, IF THERE ARE DIFFICULTIES IN COMPLYING WITH
DRAWINGS/SPECIFICATIONS.
5. ELECTRICAL PLANS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS.
6. CONSULT PLANS, IF ANY, OF ALL OTHER AFFECTED AREAS FOR COORDINATION AND RELATED
WORK.
7. CONSULT EXISTING AS BUILT ARCHITECTURAL AND STRUCTURAL PLANS AND DETAILS FOR
CONSTRUCTION TYPE, HEADROOM, ROOM FINISHES, CEILINGS, ETC. COORDINATE WITH
GOVERNMENT, AS REQUIRED.
8. CIRCUIT NUMBERS ARE FOR IDENTIFICATION PURPOSES ONLY. CONTRACTOR SHALL BE
RESPONSIBLE FOR CORRECTLY SPACING THE CIRCUITS IN THE PANEL AND BALANCE THE
LOAD ON THE PHASES UNDER NORMAL OPERATING CONDITIONS.
9. SUBMIT SHOP DRAWINGS FOR ALL ELECTRICAL EQUIPMENT, FIXTURES, DEVICES AND
MATERIALS TO OBTAIN COR'S APPROVAL BEFORE DELIVERY TO THE JOB SITE. REPLACE ALL
NON-CONFIRMING EQUIPMENT AND DEVICES, AT NOT EXTRA CHARGE TO GOVERNMENT.
10. VERIFY WIRE SIZES, CB AND FUSE RATINGS FOR ALL EQUIPMENT, AND BRING TO THE
ATTENTION OF THE GOVERNMENT ANY DISCREPANCIES AFFECTING THE WORK PRIOR TO
PROCEEDING.
11. ALL WORK SHALL BE DONE AT SUCH TIMES AND IN SUCH A MANNER AS WILL LEAST
INTERFERE WITH THE MAINTENANCE AND OPERATION OF ALL RELATED OR AFFECTED
SYSTEMS. COORDINATE ALL POWER OUTAGES, FIRE ALARM SHUT DOWNS, ETC. WITH
GOVERNMENT.
12. WHERE APPLICABLE, CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SIZING OF ALL
MOTOR OVERLOAD DEVICES (HEATERS) IN STARTERS BASED ON ACTUAL NAMEPLATE
RATINGS ON THE MOTORS BEING INSTALLED.
13. HORSEPOWER / WATTAGE INDICATED ON DRAWINGS MAY DIFFER FROM ACTUAL
EQUIPMENT FURNISHED. IF FURNISHED EQUIPMENT DIFFERS FROM RATINGS ON
DRAWINGS, MARK THE DRAWINGS FOR AS BUILT CONDITION.
14. THE EXACT NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE
WHERE CLARIFICATION IS NECESSARY. PROVIDE ALL WIRES NECESSARY FOR THE PROPER
FUNCTIONING OF THE SYSTEM WHETHER INDICATED ON DRAWINGS OR NOT.
15. PROVIDE PULL WIRE AND FISH CORD FOR ALL NEW EMPTY CONDUIT RUNS IN EXCESS OF 10
FEET.
1. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO COORDINATE EXACT REQUIREMENTS FOR INCOMING SERVICE OF LOCAL UTILITIES FOR POWER AND TELEPHONE, PAY ALL
FEES, AND INSTALL A COMPLETE AND FUNCTIONAL SYSTEM.
2. COORDINATE INSTALLATION OF TELEPHONE SYSTEM INCLUDING TELEPHONE WIRING AND TELEPHONE
OUTLETS WITH THE GOVERNMENT/ENGINEER.
3. REFER TO BASE BUILDING DRAWINGS FOR LOCATION OF UTILITY SERVICE JUNCTION BOX.
COORDINATION WITH POWER AND TELEPHONE COMPANIES:
1. COORDINATE ALL MOUNTING HEIGHTS FOR SWITCHES, RECEPTACLES, WALL MOUNTED LIGHT
FIXTURES, AND TELEPHONE OUTLETS BY THE USE OF THE ARCHITECTURAL AND ENGINEERING
DRAWINGS. SHOULD ANY CONFLICTS BECOME APPARENT, REQUEST CLARIFICATION PRIOR TO
INSTALLATION. IF THE WORK IS NOT COORDINATED, PROVIDE ANY REMEDIAL WORK, AS
APPROVED BY COR, AT NO ADDITIONAL COST TO THE GOVERNMENT.
WIRING DEVICES
1. BALLAST FOR LIGHTING FIXTURES SHALL OPERATE THE SPECIFIED LAMPS. ELECTRONIC BALLAST
SHALL HAVE A POWER FACTOR GREATER THAN .95, LESS THAN 10% HARMONIC DISTORTION.
LIGHT FIXTURES:
16. CONCEAL ALL CONDUCTORS, RACEWAYS AND CABLES IN CEILING OR WALL UNLESS OTHERWISE
INDICATED.
17. DO NOT CUT OPENINGS IN EXISTING BUILDING STRUCTURE FOR PASSAGE OF CONDUITS/CABLES
WITHOUT WRITTEN APPROVAL FROM THE GOVERNMENT.
18. FURNISH AND INSTALL NEW LIGHTING FIXTURES COMPLETE WITH ALL ACCESSORIES (INCLUDING
LAMPS).
19. SYMBOLS SHOWN ON THIS SHEET ARE STANDARD SYMBOLS. ALL OF THEM MAY NOT BE
APPLICABLE TO THIS PROJECT.
20. GUARANTEE ALL WORK AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE BY
GOVERNMENT.
21. FIRE STOP ALL NEW PENETRATIONS THROUGH FLOOR AND WALLS IN ACCORDANCE WITH BOCA, NEC, AND NFPA.
22. INSTALL CONDUCTORS CONTINUOUS BETWEEN DEVICES, WITH SPLICES LOCATED ONLY IN
JUNCTION BOXES OR IN CABINETS, AS SHOWN. CONDUCTORS SHALL BE OF SUFFICIENT LENGTH
TO REACH THE FARTHEST POINT. A MINIMUM OF 6" LOOPS SHALL REMAIN WHERE
CONNECTIONS OR TAPS ARE TO BE MADE.
23. PROVIDE AN UPDATED TYPEWRITTEN PANEL DIRECTORY IN THE PANEL AFTER COMPLETION OF
WORK.
24. PROVIDE AS BUILT DRAWINGS, ALL MANUFACTURERS' DATA AND WARRANTY LITERATURE AT THE
COMPLETION OF THE CONTRACT.
XX/X/XX/FPN
AV
S
S3
SOS
SM
OS
WP
PBJ
SW
OC OCCUPANCY SENSOR, CEILING MOUNTED 360 DEGREE, DUAL TECHNOLOGY
PASSIVE INFRARED/ULTRASONIC FREQUENCY GREATER THAN 40 KHz, DUAL
SENSING VERIFICATIONS (REQUIRES BOTH TECHNOLOGIES TO ACTIVATE), EITHER
TECHNOLOGY MAINTAINS ON STATUS,…