S02 10 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_05212026 1.pdf

PDF 16 MB Posted

Attached to
CAMP NELSON NATIONAL CEMETERY, KY 833CM3030 – CORRECT FCA DEFICIENCIES
Solicitation number
36C78626R0058
Issued by

About this file

This document is a comprehensive bid set of engineering design drawings for electrical, fire alarm, telecommunications, and security systems at Camp Nelson National Cemetery in Kentucky. The project, numbered 833CM3030, is managed by the National Cemetery Administration and designed by Astute Engineering, PLLC, with a bid set date of January 7, 2026.

The design covers electrical grounding and lightning protection systems, complete electrical power distribution with multiple panels (A through E) serving historic maintenance, equipment storage, historic brick stable, and maintenance storage buildings. The fire alarm system includes a new addressable control panel (FACP-2) compatible with an existing panel in the public restroom building, with devices distributed across all facilities and connected via fiber optic cables. Telecommunications infrastructure consists of new Category 6a cabling, wall-mounted IT racks in multiple buildings, network equipment, and fiber optic patch panels connecting facilities. Security systems include network video recorders, access control panels with smart card readers, motion detectors, door contact monitoring, and CCTV cameras with recording capabilities. All systems include detailed conduit routing specifications, both concrete-encased and directly buried, with hand holes and pullboxes as required. The documents specify manufacturer equipment standards (Notifier fire alarm panels, Chatsworth Products IT rack enclosures, APC power supplies), installation requirements per NFPA, NEC, and NCA standards, and coordination requirements among electrical, mechanical, and structural trades. Underground utility routing requires hydro-excavation verification and maintains 12-inch vertical clearance from existing utilities.

View the file

Other files

File Type Posted
S06_36C78626R0058 Amend. 0003.pdf PDF
S02 Amendement 36C78626R0058 0002.pdf PDF
S02 amendment 2.pdf PDF
S02 Fire Alarm Panel.pdf PDF
S02 Liquidated Damages 833CM3030_CNNC FCA Corrections CONS.pdf PDF
S02 12 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_addendum01.pdf PDF
S02 Amendment 36C78626R0058 0001.pdf PDF
P07 Jessamine Camp Nelson Building.pdf PDF
S02_Price Proposal Breakdown.docx DOCX document
S02_Attachment - Past Performance Questionnaire.docx DOCX document
P07 Jessamine Camp Nelson Highway.pdf PDF
S02_Attachment - DOL Payroll Form.pdf PDF
S02 833CM3030_CNNC FCA Corrections_CONS_BD SPECIFICATIONS.pdf PDF
S02 08 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_05212026 1.pdf PDF
S02 04 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_05212026 1 (1).pdf PDF
S02_Attachment - Standard Form 1413.pdf PDF
S02 02 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_05212026 1.pdf PDF
S02 07 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_05212026 1.pdf PDF
S02 03 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_05212026 1.pdf PDF
S02 06 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_05212026 1.pdf PDF
P07 Jessamine Camp Nelson Heavy.pdf PDF
S02_Attachment - Davis-Bacon Act Poster.pdf PDF
S09 09 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_05212026 1.pdf PDF
S02 11 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 2_05212026 1.pdf PDF
S02 Camp Nelson Sol 36C78626R0058 draft 9-14-2026.pdf PDF
S02 05 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_05212026 1.pdf PDF
S02 01 from 833CM3030_CNNC FCA Corrections_CONS_BD DRAWINGS_VOL 1_05212026 1.pdf PDF
S02_Attachment - Project Sample Template.docx DOCX document
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL GROUNDING AND LIGHTNING PROTECTION PLAN1 SCALE : 1/2" = 1'-0"

G

G

G

TW

GROUNDING

TEST WELL

RUN DOWN CONDUCTOR DOWN AND

BOND TO BUILDING GROUND ROD. (TYP.)

RUN DOWN CONDUCTOR IN RIGID

CONDUIT 8' FROM GROUND UP AND

EXPOSED, MOUNTED ON WALL.

B

E-003 GROUNDING GRID

CONDUCTOR (TYP.)

LIGHTNING

CONDUCTOR

TW

"T" JOINT

CONNECTION (TYP.)

AIR TERMINAL (TYP.)E

E-003

A

LIGHTNING CONDUCTOR

RUN ALONG ROOF,

FASTENED EVERY

3 FEET MAX.

D E-003

GROUND ROD

(TYP.)

G

A E-003

AA

PANEL C

(LOCATED INSIDE

THE BUILDING)

SITE PLANS HISTORIC BRICK STABLE BLDG

ELECTRICAL GROUNDING AND

LIGHTNING PROTECTION PLAN

EN-204

NOT TO SCALE

KEY PLAN

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

0 1' 2' 4' 6'

SCALE : 1/2" = 1'-0"

HA2

GENERAL NOTES

LEGENDS

1. FOR LIGHTNING PROTECTION GENERAL NOTES, SEE DRAWING

E-003.

GROUNDING CONDUCTOR

LIGHTNING CONDUCTOR

GROUND ROD

GROUNDING TEST WELL

AIR TERMINAL

G

TW

A

AREA OF WORK

ELECTRICAL GROUNDING AND LIGHTNING PROTECTION PLAN1 SCALE : 1/4" = 1'-0"

G

G

G

TW

GROUNDING

TEST WELL

RUN DOWN CONDUCTOR DOWN AND

BOND TO BUILDING GROUND ROD. (TYP.)

RUN DOWN CONDUCTOR IN RIGID

CONDUIT 8' FROM GROUND UP AND

EXPOSED, MOUNTED ON WALL.

B

E-003 GROUNDING GRID

CONDUCTOR (TYP.)

LIGHTNING

CONDUCTOR

TW

A

"T" JOINT

CONNECTION (TYP.) AIR TERMINAL (TYP.)E

E-003

A

LIGHTNING CONDUCTOR

RUN ALONG ROOF,

FASTENED EVERY

3 FEET MAX.

A

D E-003

PANEL D

(LOCATED INSIDE

THE BUILDING)

GROUND ROD

(TYP.)

G

A E-003

KEY PLAN

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

MAINTENANCE STORAGE BLDG

ELECTRICAL GROUNDING AND

LIGHTNING PROTECTION PLAN

EN-205

0 2' 4' 8' 12'

SCALE : 1/4" = 1'-0"

GENERAL NOTES

LEGENDS

1. FOR LIGHTNING PROTECTION GENERAL NOTES, SEE DRAWING

E-003.

GROUNDING CONDUCTOR

LIGHTNING CONDUCTOR

GROUND ROD

GROUNDING TEST WELL

AIR TERMINAL

G

TW

SCALE: NONE

ELECTRICAL POWER RISER DIAGRAM - EXISTING AND DEMOLITION

POLE

MOUNTED

UTILITY

XFMR

M

OUTSIDE

1st FLOOR

40A 2P

AC UNIT

PANEL

MDP

240/120V, 1Ø, 3W, 400A BUS,

350A MAIN

BASEMENT

25A 2P

STOVE

30A 2P

WATER

HEATER

(3500W)

40A 2P

AC UNIT

100A 2P

100A 2P

50A 2P

N L

E

ATS

ADMIN BUILDING

G

10.4 KW

GENERATOR

PANEL E

240/120V, 1Ø, 3W, 100A MLO

PANEL A

240/120V, 1Ø, 3W, 225A MLO

HISTORIC MAINTENANCE

BUILDING

EXISTING

PANEL B

240/120V, 1Ø, 3W, 225A MLO

EQUIPMENT STORAGE

BUILDING

PANEL C

240/120V, 1Ø, 3W, 80A MLO

HISTORIC BRICK

STABLE BUILDING

60A 2P

PANEL D

240/120V, 1Ø, 3W, 60A MLO

MAINTENANCE

STORAGE BUILDING

1. POWER RISER DIAGRAM FOR EXISTING SYSTEM IS REPRODUCED BASED ON VISUAL,

NON-INVASIVE FIELD SURVEY ONLY, WITH LIMITED OR NO ACCESS TO ENCLOSED AND

CONCEALED SPACES. CONTRACTOR TO FIELD VERIFY THE SYSTEM CONFIGURATION.

NOTIFY COR IMMEDIATELY OF ANY DISCREPANCY, AND SEEK DIRECTIONS BEFORE

MAKING ANY MODIFICATIONS.

2. UPON COMPLETION OF WORK, UPDATE DIRECTORIES, LABELS, TAGS, ETC., OF ALL

AFFECTED EQUIPMENT, DEVICES, CABLES, CONDUITS, JUNCTION BOX, ETC., TO ENSURE

THAT ALL SYSTEM ELEMENTS CARRY CORRECT IDENTIFICATION. CONTRACTOR TO

PROVIDE IDENTIFICATION TO ALL RECEPTACLES, TELEPHONE/DATA OUTLETS AND

JUNCTION BOXES INDICATING ELECTRICAL ROOM, PANEL AND BREAKER NUMBER.

3. ALL WIRING / CONDUCTOR SHALL BE COPPER.

SCALE: NONE

ELECTRICAL POWER RISER DIAGRAM - EXISTING AND NEW WORK

OUTSIDE

1st FLOOR

40A 2P

AC UNIT

PANEL

MDP

240/120V, 1Ø, 3W, 400A BUS,

350A MAIN

BASEMENT

25A 2P

STOVE

30A 2P

WATER

HEATER

(3500W)

40A 2P

AC UNIT

100A 2P

100A 2P

50A 2P

N L

E

ATS

ADMIN BUILDING

G

10.4 KW

GENERATOR

RELOCATED

PANEL E

240/120V, 1Ø, 3W, 100A MLO

HISTORIC MAINTENANCE

BUILDING

EQUIPMENT STORAGE

BUILDING

HISTORIC BRICK

STABLE BUILDING

60A 2P

NEW PANEL D

240/120V, 1PH, 3W,

100A BUS,

60A MAIN

22 KAIC,

NEMA 12

MAINTENANCE

STORAGE BUILDING

60A 2P

MCB

PANEL B

240/120V, 1Ø, 3W, 225A BUS,

150A MAIN

RELOCATED

PANEL B

240/120V, 1Ø, 3W, 225A BUS,

150A MAIN

80A 2P

NEW

PANEL B

240/120V, 1Ø, 3W, 125A BUS,

100A

MAIN,

22 KAIC,

NEMA 12

80A 2P

POLE

MOUNTED

UTILITY

XFMR

FROM UTILITY

PUBLIC RESTROOM

& WASH HOUSE

BUILDING

PUBLIC RESTROOM

& WASH HOUSE

BUILDINGFROM UTILITY

M

GENERAL NOTES:

ALL EXISTING ELECTRICAL EQUIPMENT TO REMAIN IN-PLACE. PROTECT DURING

CONSTRUCTION.

DISCONNECT AND REMOVE EXISTING ELECTRICAL PANEL BY PERFORMING FOLLOWING:

a. PULL EXISTING INCOMING FEEDER WIRING BACK TO SOURCE AND DISPOSE OFF.

b. PROTECT EXISTING UNDERGROUND CONDUIT IN-PLACE FOR RE-USE.

c. FOR BRANCH WIRING AND LOAD DETAILS, SEE PANEL SCHEDULES.

RELOCATE EXISTING ELECTRICAL PANEL. FOR MORE DETAILS, SEE ELECTRICAL SITE PLAN,

DRAWING ES-100 AND ES-200.

PROVIDE NEW ELECTRICAL PANEL BY PERFORMING FOLLOWING:.

a. RUN NEW INCOMING FEEDER WIRING FROM SOURCE TO NEW PANEL USING

EXISTING UNDERGROUND CONDUITS.

b. PROVIDE NEW ABOVE SURFACE CONDUIT, AS REQUIRED.

c. FOR MORE DETAILS, SEE PANEL SCHEDULES.

SPLICE THE EXISTING WIRING WITH NEW AND EXTEND UPTO TO THE RELOCATED

ELECTRICAL PANEL AS INDICATED IN NEW CONDUIT. FIELD VERIFY THE EXISTING WIRING

SIZE. FOR MORE DETAILS, SEE ELECTRICAL SITE PLAN, DRAWING ES-100 AND ES-200.

DISCONNECT AND REMOVE EXISTING ELECTRICAL PANEL BY PERFORMING FOLLOWING:

a. PULL EXISTING INCOMING FEEDER WIRING BACK TO SOURCE AND DISPOSE OFF.

b. CAP BOTH END OF CONDUIT AND ABANDON IN-PLACE.

PROVIDE NEW ELECTRICAL PANEL BY PERFORMING FOLLOWING:.

a. RUN NEW INCOMING FEEDER WIRING FROM SOURCE TO NEW PANEL USING NEW

CONDUITS.

b. PROVIDE NEW PULLBOX, ALONG THE CONDUIT ROUTING, AS REQUIRED BY CODE.

c. FOR MORE DETAILS, SEE PANEL SCHEDULES.

KEY NOTES:

NEW PULLBOX

EXISTING 3-#500 KCMIL,

1-#3 GND IN 3" UG

CONDUIT

EXISTING 2#8 AWG,

1#10 GND IN 2" UG

CONDUIT

150A 2P

MCB

EXISTING

EXISTING EXISTING

EXISTING06

EXISTING 3-#500 KCMIL,

1-#3 GND IN 3" UG

CONDUIT

EXISTING 2#8 AWG,

1#10 GND IN 2" UG

CONDUIT

NEW 3#8 AWG,

1#10 GND

IN 1" C

NEW

3#3/0 AWG,

1#4 GND

IN 2 1/2"C

150A 2P

MCB

03 03

EXISTING

NEW 3-#1 AWG,

1-#6 GND IN

EXISTING UG

CONDUIT

NEW 3-#3 AWG,

1-#8 GND IN NEW

1 1/4" CONDUIT

NEW 3-#4 AWG,

1-#8 GND IN

EXISTING CONDUIT

EXISTING

EXISTING

NEW PANEL C

240/120V, 1PH, 3W,

100A BUS,

80A MAIN,

22 KAIC,

NEMA 12

NEW PANEL A

240/120V, 1PH, 3W,

125A BUS,

100A MAIN

22 KAIC,

NEMA 12

100A

2P

MCB

80A 2P

MCB

NEW 3-#1 AWG,

1-#6 GND IN

EXISTING UG

CONDUIT

EXISTING02

350A 2P

MCB

350A 2P

MCB

100A 2P

MCB

PARTIAL ELECTRICAL POWER

RISER DIAGRAM - EXISTING,

DEMOLITION AND NEW WORK

E-501

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

ALL

ELECTRICAL SCHEDULES - I

E-601

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

PROVIDE NEW ELECTRICAL PANEL. FOR MORE DETAIL SEE

ELECTRICAL POWER RISER DIAGRAM, DRAWING E-501 .

USE EXISTING AVAILABLE SPARE BREAKER, TO FEED THE NEW LOAD

AS SHOWN.

REPLACE EXISTING (1) 80A, 2P CIRCUIT BREAKER WITH THE NEW (1)

45A, 2P (COMPATIBLE WITH THE EXISTING PANEL) CIRCUIT BREAKER

TO FEED NEW LOAD AS SHOWN.

REPLACE EXISTING (2) 20A, 2P CIRCUIT BREAKER WITH THE NEW (1)

40A, 2P (COMPATIBLE WITH THE EXISTING PANEL) CIRCUIT BREAKER

TO FEED NEW LOAD AS SHOWN.

REPLACE EXISTING (1) 20A, 1P CIRCUIT BREAKER WITH THE NEW

(1) 30A, 1P (COMPATIBLE WITH THE EXISTING PANEL) CIRCUIT

BREAKER TO FEED NEW LOAD AS SHOWN.

KEY NOTES:

ALL

1. FOR ELECTRICAL POWER RISER DIAGRAM, SEE DRAWING E-501.

2. UPON COMPLETION OF WORK, UPDATE DIRECTORIES, LABELS,

TAGS, ETC., OF ALL AFFECTED EQUIPMENT, DEVICES, CABLES,

CONDUITS, JUNCTION BOX, ETC., TO ENSURE THAT ALL SYSTEM

ELEMENTS CARRY CORRECT IDENTIFICATION. CONTRACTOR TO

PROVIDE IDENTIFICATION TO ALL RECEPTACLES,

TELEPHONE/DATA OUTLETS AND JUNCTION BOXES INDICATING

ELECTRICAL ROOM, PANEL AND BREAKER NUMBER.

GENERAL NOTES:

ELECTRICAL SCHEDULES - II

E-602

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

ALL

PROVIDE NEW ELECTRICAL PANEL. FOR MORE DETAIL SEE

ELECTRICAL POWER RISER DIAGRAM, DRAWING E-501 .

KEY NOTES:

1. FOR ELECTRICAL POWER RISER DIAGRAM, SEE DRAWING E-501.

2. UPON COMPLETION OF WORK, UPDATE DIRECTORIES, LABELS,

TAGS, ETC., OF ALL AFFECTED EQUIPMENT, DEVICES, CABLES,

CONDUITS, JUNCTION BOX, ETC., TO ENSURE THAT ALL SYSTEM

ELEMENTS CARRY CORRECT IDENTIFICATION. CONTRACTOR TO

PROVIDE IDENTIFICATION TO ALL RECEPTACLES,

TELEPHONE/DATA OUTLETS AND JUNCTION BOXES INDICATING

ELECTRICAL ROOM, PANEL AND BREAKER NUMBER.

GENERAL NOTES:01

FIRE ALARM ABBREVIATIONS

AC

ACK

ACP

AF

AFF

AFG

AHU

AIC

AL

AM

AT

ATS

AUTO

AUX

AWG

BAT

BKR

BLDG

BOCA

C

CB

CC

CH

CIR,CKT

CLR

COMB

CONT'D

CPT

CR

CT

CU

DC

DIA

DIST

D/SW

DIV

DN

DP

DVR

DWG

E

EA

EC

ECB

EF

EL

EMH

EO

ER

ETM

ETR

EX

F

FA

FAAP

FACP

FDR

FLR

FOP

FSS

FUT

G

GALV

GC

GFI

GFP

GFR

GND

HH

HP

HVAC

HZ

IC

ICCB

I & C

ID

IG

INST

ITC

J, JB

AMPERE

ALTERNATING CURRENT

ACKNOWLEDGE

ACCESS CONTROL PANEL

AMPERE FRAME

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERES INTERRUPTING

CAPACITY (SYM, RMS, AMPS)

ALUMINUM

AMMETER

AMPERE TRIP

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AUXILIARY

AMERICAN WIRE GAUGE

BATTERY

BREAKER

BUILDING

BUILDING OFFICIALS AND

CODE ADMINISTRATORS

CONDUIT

CIRCUIT BREAKER

CONTROL CABLE

CABINET HEATER

CIRCUIT

CLEAR

COMBINATION

CONTINUED

CONTROL POWER TRANSFORMER

CONTROL RELAY

CURRENT TRANSFORMER

COPPER, COMPRESSOR UNIT

DIRECT CURRENT

DIAMETER

DISTRIBUTION

DISCONNECT SWITCH

DIVISION

DOWN

DISTRIBUTION PANEL

DIGITAL VIDEO RECORDER

DRAWING

EMPTY, ELECTRICAL INTERLOCK,

EXISTING

EACH

EMPTY CONDUIT

ENCLOSED CIRCUIT BREAKER

EXHAUST FAN

ELEVATION

ELECTRIC MANHOLE

ELECTRIC OPERATOR

EXISTING RELOCATED

ELAPSED TIME METER

EXISTING TO REMAIN

EXISTING

FUSE, FRAME, FRONT

FRAME AMPS

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FEEDER

FLOOR

FIBER OPTIC PATCH PANEL

FUSED SAFETY SWITCH

FUTURE

GREEN, GROUND, GROUND GRID

GALVANIZED

GENERATOR CONTACTOR,

GENERATOR CONTROL PANEL

GROUND FAULT INTERRUPTER

GROUND FAULT PROTECTION

GROUND FAULT RELAY

GROUND

HANDHOLE

HORSE POWER

HEATING VENTILATION AND AIR CONDTITION

HERTZ

INTERRUPTING CAPACITY

INSULATED CASE CIRCUIT BREAKER

INSTRUMENTATION & CONTROL

IDENTIFICATION

ISOLATED GROUND

INSTANTANEOUS

INTERFACE TERMINAL CABINET

JUNCTION BOX

K

KCMIL

KVA

KW

LA

LB

LO

LCP

MB,MCB

M/C

MFR

MH

MIN

MLO

MT

MTD

N

NA

NC

NEC

NEMA

NFPA

NFSS

NIPR

NO.

NP

NTS

NVR

OL

P

PB

PF

PH

PL

PM

PMR

PMT

PNL

PQM

PR

PRI

PT

R

RGS,GRC

RECPT

REQ'D

RMS

RM

RTU

SA

SIPR

SPD

SPO

SW

SYM

TA

TB

TDR

TJB

TSP

TSH

TS

TVSS

TYP

UG

UL

V

VA

W W/

WH

WP

WR

XFMR

Z

Ø

KEY INTERLOCK

KILO CIRCULAR MILS

KILOVOLT-AMPERE

KILOWATT

LIGHTNING ARRESTER

CONDUIT BOX, RIGHT ANGLE

LOCKOUT

LOCAL CONTROL PANEL

MAIN CIRCUIT BREAKER

MACHINE

MULTIFUNCTION RELAY

MANHOLE, MOUNTING HEIGHT

MINIMUM

MAIN LUG ONLY

MOUNT

MOUNTED

NEUTRAL

NON-AUTOMATIC

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NATIONAL FIRE PROTECTION

ASSOCIATION

NON-FUSED SAFETY SWITCH

NON-CLASSIFIED INTERNET PROTOCOL ROUTER

NUMBER

NAMEPLATE

NOT TO SCALE

NETWORK VIDEO RECORDER

OVERLOAD

POLE OR POLES

PULL BOX, PUSH BUTTON

POWER FACTOR

PHASE

PILOT LIGHT

MICROPROCESSOR BASED METERING

PHASE MONITOR RELAY

POWER MONITORING DEVICE

PANEL

POWER QUALITY MONITOR

PAIR

PRIMARY

POTENTIAL TRANSFORMER

REMOVE, RED, REAR,

RUN CONTRACTORS

RIGID GALVANIZED STEEL /

GALVANIZES RIGID CONDUIT

RECEPTACLE

REQUIRED

ROOT MEAN SQUARE

ROOM

ROOF TOP UNIT

SURGE ARRESTOR

SECRET INTERNET PROTOCOL ROUTER

SURGE PROTECTION DEVICE

SURGE PROTECTIVE DEVICE

SWITCH

SYMMETRICAL

TRIP AMPS

TERMINAL BOARD, TERMINAL BLOCK

TIME DELAY RELAY

TERMINAL JUNCTION BOX

TWISTED SHIELDED PAIR

HIGH-TEMP RELAY

TEST SWITCH

TRANSIENT VOLTAGE SURGE SUPPRESSOR

TYPICAL

UNDERGROUND

UNDERWRITERS LABORATORY

VOLTS OR VOLTAGE

VOLTAMPS

WATTS, WIRE

WITH

WATTHOUR

WEATHERPROOF

WELDING RECEPTACLE

TRANSFORMER

IMPEDANCE

PHASE, DIAMETER

NUMBER

FIRE ALARM GENERAL NOTES

1. INSTALLATION FIRE ALARM DEVICS IN ACCORDANCE WITH THE CONTRACT DOCUMENTS VERSION OF THE

NCA DESIGN CRITERIA, NFPA, NEC, AND THE AUTHORITY HAVING JURISDICTION.

2. THE FIRE ALARM PLANS ARE DIAGRAMMATIC ONLY. COORDINATE LOCATION OF DEVICES IN THE FIELD, COORDINATED WITH THE EXISTING CONDITIONS.

3. INSTALL ALL EQUIPMENT IN STRICT ACCORDANCE WITH THE U.L. LISTING OR CLASSIFICATION.

4. ALL NEW WORK INCLUDING CONDUIT SHALL BE CONCEALED IN CEILINGS, WALLS, ETC. UON.

5. COORDINATE ALL FIRE ALARM EQUIPMENT WITH ALL OTHER DISCIPLINE TO AVOID CONFLICTS. PROVIDE ALL NECESSARY FITTINGS, EQUIPMENT, HANGERS, OFFSETS, ROUTING, ETC. TO AVOID CONFLICTS.

6. SUBMIT SHOP DRAWING DESIGN BY A NICET LEVEL III OR IV FIRE ALARM TECHNICIAN OR A REGISTERED FIRE PROTECTION ENGINEER. INSTALL FIRE ALARM DEVICES ACCOMPLISHED BY AN ELECTRICAL CONTRACTOR WITH A MINIMUM OF FIVE YEARS EXPERIENCE IN THE INSTALLATION OF FIRE

ALARM SYSTEMS.

7. INSTALL ALL CONDUCTORS IN RIGID METAL CONDUIT OR ELECTRICAL-METALLIC TUBING, WITH A MINIMUM DIAMETER OF 3/4". RUN CONDUIT OR TUBING CONCEALED UNLESS SPECIFICALLY SHOWN OTHERWISE ON THE DRAWINGS. ALL WIRING FOR THE FIRE ALARM SYSTEM MUST BE INSTALLED IN SEPARATE CONDUIT. NO OTHER BUILDING WIRING IS PERMITTED IN CONDUIT THAT CONTAINS FIRE ALARM WIRING. SHORT RUNS OF 3 FEET OR LESS MAY HAVE CABLING INSTALLED IN FLEXIBLE METALLIC

CONDUIT.

8. WHERE PHYSICALLY POSSIBLE, CONCEAL ALL FIRE ALARM CONDUITS BEHIND WALLS AND CEILINGS. FIRE ALARM CONDUITS THAT MUST BE EXPOSED TO VIEW (IN FINISHED AREAS) SHALL BE PAINTED TO MATCH ADJACENT FINISH WITH 3/4 INCH RED BANDS AT INTERVALS. ALL OTHER FIRE ALARM CONDUITS MUST BE PAINTED RED.

ALL FIRE ALARM JUNCTION BOXES MUST BE PAINTED RED.

9. WHERE CONDUIT AND CABLE PENETRATE FIRE RATED FLOORS AND WALLS, PROVIDE U.L. LISTED FIRE STOPPING SYSTEM FOR EACH PENETRATION. GROUP CABLES/CONDUITS TOGETHER TO REDUCE QUANTITY OF

PENETRATIONS WHEREVER POSSIBLE.

10. INFORMATION ON THE PLAN IS DIAGRAMMATIC. CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE EXACT

LOCATION OF ALL FIRE ALARM EQUIPMENT ACCORDING TO NFPA 72.

11. PROVIDE ALL NECESSARY CONNECTIONS, DEVICES, SIGNALING LINE CIRCUITS, NOTIFICATION CIRCUITS, INITIATION DEVICE CIRCUITS AND FIRE PHONE CIRCUITS NEEDED FOR A COMPLETE FIRE ALARM SYSTEM

INSTALLATION.

12. SUBMIT SHOP DRAWINGS THAT AS A MINIMUM, INCLUDE THE FOLLOWING:

a. POINT-TO-POINT WIRING DIAGRAMS SHOWING THE POINTS OF CONNECTION AND TERMINALS USED

FOR ALL ELECTRICAL FIELD CONNECTIONS IN THE SYSTEM, INCLUDING ALL INTERCONNECTIONS

BETWEEN THE EQUIPMENT OR SYSTEMS WHICH ARE SUPERVISED OR CONTROLLED BY THE

SYSTEM.

b. INCLUDE CANDELA RATINGS FOR ALL APPLICABLE FIRE ALARM DEVOICES.

c. INCLUDE ANNOTATED CATALOG DATA SHOWING MANUFACTURER'S NAME, MODEL, VOLTAGE, AND

CATALOG NUMBERS FOR ALL EQUIPMENT AND COMPONENTS.

d. PROVIDE CALCULATIONS SHOWING THAT NO INDIVIDUAL NOTIFICATION CIRCUIT IS LOADED BEYOND

75% OF ITS FULL LOAD CAPACITY.

e. INCLUDE BATTERY CALCULATIONS FOR BOTH THE ALARM AND SUPERVISORY POWER

REQUIREMENTS. AMPERE-HOUR REQUIREMENTS FOR EACH SYSTEM COMPONENT SHALL BE

SUBMITTED WITH THE CALCULATIONS.

f. CAPACITY: PROVIDE THE BATTERIES WITH SUFFICIENT CAPACITY TO OPERATE ALL SIGNALING LINE CIRCUITS, INITIATING DEVICE CIRCUITS, AND NOTIFICATION APPLIANCE CIRCUITS IN NORMAL OR

SUPERVISORY (NON-ALARM) MODE FOR A PERIOD OF 72 HOURS. FOLLOWING THIS PERIOD OF

OPERATION ON BATTERY POWER, THE BATTERIES SHALL HAVE SUFFICIENT CAPACITY TO OPERATE

ALL COMPONENTS OF THE SYSTEM IN ALARM MODE FOR A PERIOD OF FIFTEEN (15) MINUTES.

BATTERY CAPACITY CALCULATIONS SHALL BE BASED ON EQUIPMENT CURRENT DRAW AT A MINIMUM

OPERATING VOLTAGE OF 24 VDC. PROVIDE BATTERIES SIZED AT 150% OF FIRE ALARM

MANUFACTURER'S CALCULATIONS.

g. PROVIDE A COLOR CODE SCHEDULE FOR THE WIRING AND FLOOR PLANS SHOWING THE LOCATION

OF ALL DEVICES AND EQUIPMENT.

h. THE SIGNATURE AND SEAL OF A NICET LEVEL III OR IV TECHNICIAN.

13. COORDINATE DUCT SMOKE DETECTORS AND FIRE ALARM INTERFACE DEVICES FOR MECHANICAL UNITS.

14. INSTALL EACH DUCT SMOKE DETECTOR WITH U.L. LISTED FIRE ALARM RELAY PROVIDED AND INSTALLED WITHIN THREE (3) FEET OF ASSOCIATED STARTER. FIRE ALARM RELAY SHALL BE INTERLOCKED WITH ASSOCIATED

STARTER. TYPICAL FOR ALL DUCT SMOKE DETECTORS.

15. FIRE ALARM PROGRAMMING CHANGES ARE PERMITTED ONLY WHEN CONFIRMED ACCEPTANCE TESTING IS SCHEDULED WITH THE AUTHORITY HAVING JURISDICTION. A FIRE ALARM PROGRAM CHANGE MUST BE

ACCEPTANCE TESTED WITHIN 24 HOURS OF THE CHANGE.

1'-6"

6'-8"

4'-0"

7'-6" MIN.

9'-6" MAX

COORDINATE WALL MOUNTED FIXTURE

MOUNTING HEIGHT WITH

ARCHITECTURAL ELEVATIONS AND

REFLECTED CEILING PLAN

FIRE ALARM AUDIO/VISUAL

(HORN/STROBE) DEVICE

FIRE FIGHTER'S TELEPHONE

FIRE ALARM PULL STATION

TELE/DATA OUTLETS

RECEPTACLES

NOTES:

1. INSTALL DEVICES ON A COMMON VERTICAL CENTERLINE WHEREVER POSSIBLE.

2. INSTALL ALL DEVICES AT MOUNTING HEIGHTS AS INDICATED ON THIS DETAIL UNLESS OTHERWISE NOTED.

SWITCHES/DIMMERS

1 TYPICAL DEVICE MOUNTING HEIGHT DETAIL

NONE

NOTE:

NOT ALL SYMBOLS, ABBREVIATIONS AND GENERAL NOTES ARE APPLICABLE TO THIS PROJECT.

USE ONLY THOSE PERTAINING TO THE PROJECT.

FIRE ALARM SYMBOLS

FACP

FIRE ALARM AUDIO/VISUAL NOTIFICATION APPLIANCE, ELECTRONIC HORN WITH SELECTABLE OR TEMPORAL TONE, SELECTABLE SOUND OUTPUT AND HIGH-INTENSITY STROBE, RED HOUSING WITH

WHITE LETTERING OR PICTOGRAM, SEMI-FLUSH WALL MOUNT; 24 VDC.

A3A1

AHA7

FIRE ALARM CONTROL PANEL, ADDRESSABLE SYSTEM, FEATURING INTERFACE WITH ANALOG SENSING INITIATING DEVICES, EXPANDABLE MODULAR DESIGN, MICROPROCESSOR BASED ELECTRONICS, 120

VAC OPERATION. REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.

FIRE ALARM VISUAL NOTIFICATION APPLIANCE, HIGH-INTENSITY STROBE, RED HOUSING WITH WHITE

LETTERING OR PICTOGRAM, SEMI-FLUSH WALL MOUNT; 24 VDC.V3V1

VHV7

WEATHERPROOF FIRE ALARM AUDIO/VISUAL NOTIFICATION APPLIANCE, ELECTRONIC HORN WITH

HIGH-INTENSITY STROBE, SQUARE HOUSING, SEMI-FLUSH WALL MOUNT, RED WITH WHITE

LETTERING, 75 CANDELA RATING, 24 VDC FOR WET LOCATIONS, PROVIDE WITH WEATHERPROOF

BACK BOX. CONDUIT SHALL NOT BE EXPOSED.

AW

SMOKE DETECTOR, ADDRESSABLE, ANALOG PHOTOELECTRIC SENSOR, 24 VDC, 2-PIECE DESIGN, LOW-PROFILE MOUNTING BASE WITH MULTI-FUNCTION LED INDICATOR, COMPLETE WITH

MOUNTING HARDWARE AND BACKBOX.

SD

FIRE ALARM MANUAL PULL STATION, ADDRESSABLE, SINGLE ACTION, RESET KEY LOCK,

SEMI-FLUSH MOUNT, RED HIGH-ABUSE PLASTIC OR CAST METAL CONSTRUCTION WITH WHITE

LETTERING.

F

FIRE ALARM MANUAL PULL STATION WITH COVER, ADDRESSABLE, SINGLE ACTION, RESET KEY

LOCK, SEMI-FLUSH MOUNT, RED HIGH-ABUSE PLASTIC OR CAST METAL CONSTRUCTION WITH

WHITE LETTERING. COVER SHALL BE CLEAR LEXAN TAMPER RESISTANT COVER WITH INTEGRAL

9V BATTERY-POWERED ALARM THAT SOUNDS WHEN SHIELD IS LIFTED.

FT

CANDELA RATINGS: A1=15, A3=30, A7=75, AND AH=110. CANDELA RATING SHALL BE VISIBLE

FROM THE OUTSIDE OF THE DEVICE.

CANDELA RATINGS: V1=15, V3=30, V7=75, AND VH=110. CANDELA RATING SHALL BE VISIBLE FROM

THE OUTSIDE OF THE DEVICE.

CARBON MONOXIDE SENSORCO

DUCT SMOKE DETECTORDD

FIBER OPTIC PATCH PANELFOP

FIRE ALARM LEGEND

EXISTING

NEW WORK

DEMOLITION

COMBINATION OF SMOKE DETECTOR AND CARBON MONOXIDE DETECTORSC

FIRE ALARM COVER SHEET

FA-001

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

FIRE ALARM RISER DIAGRAM

FA-002

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

KEY NOTES

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

ALL

FIRE ALARM SYSTEM RISER DIAGRAMA SCALE : NONE

SPECIFIC NOTES FOR RISER DIAGRAM:

1. FOR EXACT QUANTITY OF ALL FIRE ALARM DEVICES, SEE DRAWINGS FN-101, FN-102, FN-103, FN-104 AND FN-105.

2. FOR UNDERGROUND CONDUIT ROUTING, SEE SITE PLAN, DRAWING SS-100.

3. FIRE ALARM RISER DIAGRAM IS DIAGRAMMATIC AND DOES NOT SHOW ALL REQUIRED SYSTEM COMPONENTS. FIRE ALARM CONTRACTOR SHALL PROVIDE ALL

REQUIRED ELECTRICAL COMPONENTS, INTERFACE EQUIPMENT, PANEL MODULES, POWER SUPPLIES, SYSTEM PROGRAMMING, ETC. FOR A FULLY OPERATIONAL ADDRESSABLE FIRE ALARM SYSTEM PER NFPA 72 AND AHJ REQUIREMENTS AND PROJECT SPECIFICATIONS.

4. THIS INFORMATION IS FOR GUIDANCE ONLY. PROVIDE COMPLETE DESIGN AND SHOP DRAWINGS FOR FIRE ALARM SYSTEM. OBTAIN COR'S APPROVAL PRIOR

TO PROCUREMENT.

5. THE ENTIRE FIRE ALARM SYSTEM SHALL BE ADDRESSABLE.

6. PROVIDE BATTERIES FOR THE FIRE ALARM SYSTEM WITH 72 HOURS OF BACKUP POWER FOLLOWED BY 15 MINUTES OF ALARM OPERATION AND 60 MINUTES

OF OPERATION IMMEDIATELY AFTER LOSS OF 120V POWER UNLESS OTHERWISE APPROVED BY LOCAL AHJ FOR LOWER BACKUP POWER.

7. MANDATORY SYSTEM TESTS: TEST ALL INSTALLED SYSTEMS ON THE BATTERY BACKUP POWER SUPPLY FOR THE RATED TIME OF BACKUP POWER PROVIDED AS

PER NFPA 72 OR THE TIMES LISTED ABOVE WHICHEVER IS LONGER. ALL SYSTEMS MUST STILL BE FUNCTIONAL AFTER TESTING.

SYSTEM INPUTS

SEQUENCE OF

OPERATION

PA

NE

L/

AN

NU

NC

IA

TO

R

AL

AR

M

IN

DI

CA

TIO

N

PA

NE

L/

AN

NU

NC

IA

TO

R

SU

PE

RV

ISO

RY

IN

DI

CA

TIO

N

PA

NE

L/

AN

NU

NC

IA

TO

R

TR

OU

BL

E I

ND

IC

AT

IO

N

AU

DI

BL

E A

LA

RM

S

SE

QU

EN

CE

VI

SU

AL

A

LA

RM

S

SE

QU

EN

CE

FIRE ALARM PANEL, TRANSPONDER, NAC PANEL

LOW BATTERY

FIRE ALARM PANEL, TRANSPONDER, NAC PANEL

BATTERY OR CHARGER FAILURE

FIRE ALARM PANEL, TRANSPONDER, NAC PANEL

ABNORMAL SWITCH OR CONTROL POSITION.

FIRE ALARM PANEL, TRANSPONDER, NAC PANEL

GROUND FAULT, OPEN CIRCUIT, SHORT CIRCUIT

FIRE ALARM PANEL, TRANSPONDER, NAC PANEL

AC POWER LOSS OR IRREGULARITY

INITIATING DEVICE

FAILURE OR COMMUNICATION ERROR

FIRE ALARM PANEL

MANUAL FIRE DRILL

MANUAL PULL STATION

SMOKE DETECTOR

NOTIFICATION APPLIANCE CIRCUIT OR SLC LOOP

GROUND FAULT, OPEN CIRCUIT, SHORT CIRCUIT

HEAT DETECTOR

F

H

SD

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

FT

FIRE ALARM SYSTEM MATRIXB SCALE : NONE

X

GENERAL NOTES

1. FOR FIRE ALARM ABBREVIATIONS AND GENERAL NOTES, SEE

DRAWING FA-001.

PROVIDE NEW ADDRESSABLE TYPE FIRE ALARM CONTROL PANEL

(FACP-2), COMPATIBLE WITH EXISTING FIRE ALARM CONTROL

PANEL (NOTIFIER PANEL FACP-1) LOCATED IN PUBLIC RESTROOM

BUILDING.

PROVIDE NEW FIBER OPTIC PATCH PANEL AND CONNECT NEW

FACP-2 TO EXISTING FACP-1 LOCATED IN PUBLIC RESTROOM

BUILDING THROUGH FIBER OPTIC CABLE. FOR FIBER OPTIC CABLE

PATH, SEE DRAWING SS-100.

FOR EXISTING FIRE ALARM CONTROL PANEL (FACP-1) PERFORM

FOLLOWING:

a. PROVIDE ALL NECESSARY CONNECTIONS, MODULES, SYSTEM

PROGRAMMING, ETC. TO INTERFACE WITH NEW HISTORIC

MAINTENANCE BUILDING FIRE ALARM SYSTEM (FACP-2) WITH

NETWORK AND PROVIDE A FULLY OPERATIONAL NETWORK.

CONNECT NEW FIRE ALARM DEVICES TO NEW FIRE ALARM

CONTROL PANEL (FACP-2) AS INDICATED. USE WATER RESISTANT

AQUASEAL FIRE ALARM CABLE FOR CONNECTION. FOR CABLE

ROUTING, SEE DRAWING SS-100.

PROVIDE INTERFACE TO CONNECT NEW SECURITY DEVICES

(MOTION DETECTOR, DOOR CONTACT, CAMERA) TO EXISTING

AND NEW FIRE ALARM CONTROL PANEL. PROVIDE NEW FIRE

ALARM SYSTEM MODULE OR CONTROLLER, AS REQUIRED. FOR

SECURITY DEVICES LOCATION, SEE SECURITY DRAWINGS.

NEW FIRE ALARM CONTROL

PANEL (FACP-2)

SD

POWER

PANEL A-22

F

BATTERY

GROUND LEVEL

V A

AW

EXISTING FIRE ALARM

CONTROL PANEL

(FACP-1)

SD

F

V A

AW

PUBLIC RESTROOM / WASH BAY BUILDING HISTORIC MAINTENANCE BUILDING EQUIPMENT STORAGE BUILDING

SC

HISTORIC BRICK STABLE BUILDING

SC

MAINTENANCE STORAGE BUILDING

02 02

FOPFOP

SC

SC

COMBINATION OF SMOKE DETECTOR

AND CARBON MONOXIDE DETECTOR SC X X X

1 2 3 4 5

B

D

F

C

B.1

FIRE ALARM PLAN - EXISTING AND NEW WORK2 SCALE : 1/4" = 1'-0"

A1 A1A7

V1

V1

V1 +80" ABOVE MEZZANINE

E

RE

E

E E

E

EXISTING

FACP-1

F

E SD

SD

E

E

MULTI PURPOSE

A-100

PUBLIC

MALE

A-103

UTILITIES

A-102

IT ROOM

A-101

PUBLIC

FEMALE

A-104

WASH BAY

B-100

VESTIBULE

BW-117M

SD

SD

E

SD

E

F

RE

SD

FT

E

H E

AW

E

AW

AW

SD

RE

E

V1

RE

V1

RE

A1

RE 03

CORRIDOR

A-105

A1RE 03

STAFF

TOILET

A-106

A1

RE

SD

RE

SD

RE

SD

RE03

FIRE ALARM PLAN - EXISTING AND DEMOLITION1 SCALE : 1/4" = 1'-0"

SD

SD

SD

SD

SD

SD

SD

E

E

E

E

RE

RE

FE

FE

FE

FD FD

1 2 3 4 5

A

B

D

F

C

A1

A1 A1

A1

V1

V1

V1 V1

V1 +80" ABOVE MEZZANINE

RE

E

RE

E E

E

RE

F E

A7 E

EXISTING

FACP-1

MULTI PURPOSE

A-100

PUBLIC

MALE

A-103

UTILITIES

A-102

IT ROOM

A-101

PUBLIC

FEMALE

A-104

STAFF FEMALE

A-107

WASH BAY

B-100

VESTIBULE

BW-117M

E

SD

RE

RE

RE

F

RE

A1 RE

FT

E

H E

AW

E

(TYP.)

RE

SD

E

01 01

STAFF MALE

A-106 02

PUBLIC RESTROOM / WASH BAY

BUILDING - FIRE ALARM PLANS

FN-101

NOT TO SCALE

KEY PLAN

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

KEY NOTES

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

EXISTING FIRE ALARM DEVICES TO REMAIN IN-PLACE.

PROTECT DURING CONSTRUCTION. FOR MORE DETAILS, SEE

DRAWING FA-002.

RELOCATE EXISTING FIRE ALARM DEVICE AS SHOWN ON NEW

WORK PLAN.

RELOCATED FIRE ALARM DEVICE, CONNECT TO BUILDING'S

EXISTING MAIN FIRE ALARM CONTROL PANEL USING NEW

WIRING AND CONDUIT.

PROVIDE NEW FIRE ALARM DEVICE INCLUDING WIRING AND

CONDUIT. CONNECT TO BUILDING'S EXISTING MAIN FIRE

ALARM CONTROL PANEL.

PROVIDE INTERFACE TO CONNECT NEW SECURITY DEVICES

(MOTION DETECTOR, DOOR CONTACT, CAMERA) TO EXISTING

FIRE ALARM CONTROL PANEL. PROVIDE NEW FIRE ALARM

SYSTEM MODULE OR CONTROLLER, AS REQUIRED.

0 2' 4' 8' 12'

SCALE : 1/4" = 1'-0"

GENERAL NOTES

1. FOR FIRE ALARM ABBREVIATIONS AND GENERAL NOTES, SEE

DRAWING FA-001.

2. FOR FIRE ALARM RISER DIAGRAM, SEE DRAWING FA-002.

3. INFORMATION ON THIS PLAN IS DIAGRAMMATIC. CONTRACTOR

IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION OF

ALL FIRE ALARM DEVICES/EQUIPMENT INCLUDING ALL

NECESSARY MODULES FOR ADDRESSABLE TYPE FIRE ALARM

CONTROL SYSTEM.

LEGENDS

E - EXISTING

RE - RELOCATED

X - REMOVE

CNNEW3

FIRE ALARM PLAN - NEW WORK1 SCALE : 1/4" = 1'-0"

SC

NEW FACP-2

SC

SC

SC

SC

A3

AW

FA7

V1

A3

V1

SCF

SERVICE BAY

B1

OFFICE

B3

VESTIBULE

B4

MEN'S LOCKER RM

B2

MEN

B6

WOMEN

B7

WOMEN'S LOCKER RM

B2

A1

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

AW

AW AW

SD

(TYP.)

DOWN

FIRE ALARM PLAN - ATTIC - NEW WORK1 SCALE : 1/4" = 1'-0"

SC SC

(TYP.)

SC

A7

(TYP.) KEY PLAN

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

KEY NOTES

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

HISTORIC MAINTENANCE

BUILDING FIRE ALARM PLAN

FN-102

0 2' 4' 8' 12'

SCALE : 1/4" = 1'-0"

LEGENDS

E - EXISTING

RE - RELOCATED

X - REMOVE

GENERAL NOTES

1. FOR FIRE ALARM ABBREVIATIONS AND GENERAL NOTES, SEE

DRAWING FA-001.

2. FOR FIRE ALARM RISER DIAGRAM, SEE DRAWING FA-002.

3. INFORMATION ON THIS PLAN IS DIAGRAMMATIC. CONTRACTOR

IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION OF

ALL FIRE ALARM DEVICES/EQUIPMENT INCLUDING ALL

NECESSARY MODULES FOR ADDRESSABLE TYPE FIRE ALARM

CONTROL SYSTEM.

PROVIDE NEW ADDRESSABLE TYPE FIRE ALARM CONTROL

SYSTEM INCLUDING FIRE ALARM DEVICES AS SHOWN ON

DRAWING BY PERFORMING FOLLOWING:

a. ALL DEVICES SHALL BEAR THE U.L. LABEL FOR FIRE SERVICE

USE.

b. PROVIDE ALL ADDRESSABLE RELAY MODULE AND ALL

NECESSARY CONTROL RELAYS, INTERFACE WIRING AND

CONNECTIONS TO CONTROL ALL AIR HANDLING

EQUIPMENT SHUTDOWN. REFER TO MECHANICAL

DRAWINGS FOR UNIT LOCATION. LOCATE CONTROL RELAY

WITHIN 3 FEET OF UNIT MOTOR CONTROLLER.

c. PROVIDE DUCT SMOKE DETECTOR IN DUCTWORK IN

ACCORDANCE WITH NFPA 90A FOR HVAC UNITS WHICH

HAS TOTAL OF 2000CFM. PROVIDE REMOTE INDICATOR

LAMP DEVICE WITH TEST SWITCH MOUNTED IN

ACCESSIBLE LOCATION ADJACENT TO DETECTOR VISIBLE

FROM FLOOR.

d. PROVIDE NOTIFICATION APPLIANCE EXTENDER PANEL

WHERE NEEDED. CONTRACTOR SHALL CONFIRM NEW

APPLIANCE LOADS AND PROVIDE POWER SUPPLIES AS

REQUIRED.

e. BREAKER SERVING THE FACP AND FAAP SHALL BE

PERMANENTLY LABELED AND PROVIDED WITH LOCK-TYPE

BREAKERS.

CONNECT NEW FACP-2 TO EXISTING FACP-1 LOCATED IN PUBLIC

RESTROOM BUILDING. FOR MORE DETAILS, SEE DRAWINGS

FA-002 AND SS-100.

PROVIDE INTERFACE TO CONNECT NEW SECURITY DEVICES

(MOTION DETECTOR, CAMERA) TO NEW FIRE ALARM CONTROL

PANEL. PROVIDE NEW FIRE ALARM SYSTEM MODULE OR

CONTROLLER, AS REQUIRED.

FIRE ALARM PLAN - EXISTING AND NEW WORK2 SCALE : 1/4" = 1'-0"

SC

SC

EQUIPMENT

STORAGE

BUILDING

FIRE ALARM PLAN - EXISTING AND DEMOLITION1 SCALE : 1/4" = 1'-0"

SD

X

EQUIPMENT

STORAGE

BUILDING

KEY PLAN

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

KEY NOTES

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

EQUIPMENT STORAGE

BUILDING FIRE ALARM PLANS

FN-103

0 2' 4' 8' 12'

SCALE : 1/4" = 1'-0"

01 DISCONNECT AND REMOVE EXISTING SMOKE DETECTOR.

PROVIDE NEW FIRE ALARM DEVICES INCLUDING WIRING AND

CONDUIT.

a. CONNECT NEW DEVICES TO NEW FIRE ALARM CONTROL

PANEL (FACP-2) LOCATED IN HISTORIC MAINTENANCE

BUILDING.

b. PROVIDE INTERFACE TO CONNECT NEW SECURITY DEVICES

(MOTION DETECTOR, CAMERA) TO NEW FIRE ALARM

CONTROL PANEL. PROVIDE NEW FIRE ALARM SYSTEM

MODULE OR CONTROLLER, AS REQUIRED.

c. FOR MORE DETAILS, SEE FIRE ALARM RISER DIAGRAM, DRAWING FA-002.

d. FOR UNDERGROUND CONDUIT ROUTING, SEE DRAWING

SS-100.

CNNEW1

LEGENDS

E - EXISTING

RE - RELOCATED

X - REMOVE

GENERAL NOTES

1. FOR FIRE ALARM ABBREVIATIONS AND GENERAL NOTES, SEE

DRAWING FA-001.

2. FOR FIRE ALARM RISER DIAGRAM, SEE DRAWING FA-002.

3. INFORMATION ON THIS PLAN IS DIAGRAMMATIC. CONTRACTOR

IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION OF

ALL FIRE ALARM DEVICES/EQUIPMENT INCLUDING ALL

NECESSARY MODULES FOR ADDRESSABLE TYPE FIRE ALARM

CONTROL SYSTEM.

FIRE ALARM PLAN - EXISTING AND DEMOLITION1 SCALE : 1/2" = 1'-0"

SD

X01

HISTORIC BRICK

STABLE

FIRE ALARM PLAN - EXISTING AND NEW WORK2 SCALE : 1/2" = 1'-0"

SC SC02 02

HISTORIC BRICK

STABLE

SITE PLANS HISTORIC BRICK STABLE

FIRE ALARM PLANS

FN-104

NOT TO SCALE

KEY PLAN

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

KEY NOTES

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

0 1' 2' 4' 6'

SCALE : 1/2" = 1'-0"

HA2

LEGENDS

E - EXISTING

RE - RELOCATED

X - REMOVE

GENERAL NOTES

1. FOR FIRE ALARM ABBREVIATIONS AND GENERAL NOTES, SEE

DRAWING FA-001.

2. FOR FIRE ALARM RISER DIAGRAM, SEE DRAWING FA-002.

3. INFORMATION ON THIS PLAN IS DIAGRAMMATIC. CONTRACTOR

IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION OF

ALL FIRE ALARM DEVICES/EQUIPMENT INCLUDING ALL

NECESSARY MODULES FOR ADDRESSABLE TYPE FIRE ALARM

CONTROL SYSTEM.

AREA OF WORK

01 DISCONNECT AND REMOVE EXISTING SMOKE DETECTOR.

PROVIDE NEW FIRE ALARM DEVICES INCLUDING WIRING AND

CONDUIT.

a. CONNECT NEW DEVICES TO NEW FIRE ALARM CONTROL

PANEL (FACP-2) LOCATED IN HISTORIC MAINTENANCE

BUILDING.

b. PROVIDE INTERFACE TO CONNECT NEW SECURITY DEVICES

(MOTION DETECTOR, CAMERA) TO NEW FIRE ALARM

CONTROL PANEL. PROVIDE NEW FIRE ALARM SYSTEM

MODULE OR CONTROLLER, AS REQUIRED.

c. FOR MORE DETAILS, SEE FIRE ALARM RISER DIAGRAM, DRAWING FA-002.

d. FOR UNDERGROUND CONDUIT ROUTING, SEE DRAWING

SS-100.

FIRE ALARM PLAN - EXISTING AND DEMOLITION1 SCALE : 1/4" = 1'-0"

COCO

SD

SD

X X

X

X

(TYP.)

(TYP.)

MAINTENANCE

STORAGE BUILDING

FIRE ALARM PLAN - EXISTING AND NEW WROK2 SCALE : 1/4" = 1'-0"

SC

SC

MAINTENANCE

STORAGE BUILDING

KEY PLAN

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

KEY NOTES

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

MAINTENANCE STORAGE

BUILDING FIRE ALARM PLANS

FN-105

0 2' 4' 8' 12'

SCALE : 1/4" = 1'-0"

LEGENDS

E - EXISTING

RE - RELOCATED

X - REMOVE

GENERAL NOTES

1. FOR FIRE ALARM ABBREVIATIONS AND GENERAL NOTES, SEE

DRAWING FA-001.

2. FOR FIRE ALARM RISER DIAGRAM, SEE DRAWING FA-002.

3. INFORMATION ON THIS PLAN IS DIAGRAMMATIC. CONTRACTOR

IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION OF

ALL FIRE ALARM DEVICES/EQUIPMENT INCLUDING ALL

NECESSARY MODULES FOR ADDRESSABLE TYPE FIRE ALARM

CONTROL SYSTEM.

AREA OF WORK

01 DISCONNECT AND REMOVE EXISTING SMOKE DETECTOR.

PROVIDE NEW FIRE ALARM DEVICES INCLUDING WIRING AND

CONDUIT.

a. CONNECT NEW DEVICES TO NEW FIRE ALARM CONTROL

PANEL (FACP-2) LOCATED IN HISTORIC MAINTENANCE

BUILDING.

b. PROVIDE INTERFACE TO CONNECT NEW SECURITY DEVICES

(MOTION DETECTOR, CAMERA) TO NEW FIRE ALARM

CONTROL PANEL. PROVIDE NEW FIRE ALARM SYSTEM

MODULE OR CONTROLLER, AS REQUIRED.

c. FOR MORE DETAILS, SEE FIRE ALARM RISER DIAGRAM, DRAWING FA-002.

d. FOR UNDERGROUND CONDUIT ROUTING, SEE DRAWING

SS-100.

SYMBOLS ABBREVIATIONS

TELECOMMUNICATION (DATA AND VOICE) OUTLET - M.H. 18" AFF,

UON. PROVIDE 1" EC FROM THE OUTLET TO 6" ABOVE FINISHED

CEILING AND TERMINATE WITH 90° BEND AND INSULATED BUSHING.

X INDICATES NUMBER OF PORT

AFF

ANSI

ASME

ASTM

BICSI

EIA

FCC

ISSS

ISO

NEC

NEMA

NESC

NFPA

OSHA

POE

RUS

SMPTE

TIA

UL

UON

ABOVE FINISHED FLOOR

AMERICAN NATIONAL STANDARDS INSTITUTE

AMERICAN SOCIETY OF MECHANICAL ENGINEERS

AMERICAN SOCIETY FOR TESTING MATERIALS

BUILDING INDUSTRY CONSULTING SERVICES INTERNATIONAL

ELECTRONICS INDUSTRY ASSOCIATION

FEDERAL COMMUNICATIONS COMMISSION

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS

INTERNATIONAL STANDARDS ORGANIZATION

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION

NATIONAL ELECTRICAL SAFETY CODE

NATIONAL FIRE PROTECTION ASSOCIATION

OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION

POWER OVER ETHERNET

RURAL UTILITY SERVICE (FORMERLY AREA)

SOCIETY OF MOTION PICTURE AND TELEVISION ENGINEERS

TELECOM INDUSTRY ASSOCIATION

UNDERWRITER'S LABORATORIES, INC.

UNLESS OTHERWISE NOTED

TELECOM GENERAL NOTES

1. ALL CABLE PATHWAYS ARE DESIGNED WITH A MAXIMUM 40 PERCENT FILL RATIO UNLESS

OTHERWISE NOTED. FILL REQUIREMENTS MAY ALTER FROM INITIAL DESIGN DUE TO COR'S

REQUIREMENTS DURING INSTALLATION.

2. ALL CABLE PATHWAYS SHALL BE FREE FROM PROJECTIONS AND ROUGH OR SHARP EDGES

THROUGHOUT THE ENTIRE PATH. ROUND, PAD OR BUSH ALL POINTS OR EDGES THAT

CABLING MUST PASS, AND MAY BE SUBJECT TO INJURY OR WEAR.

3. THE TELECOM DRAWINGS INDICATE THE GENERAL LOCATION OF EQUIPMENT, CABLE

PATHWAYS, AND OUTLETS. ALTHOUGH THE DRAWINGS DO NOT NECESSARILY DICTATE THE

ACTUAL ROUTES OF CABLE TRAYS AND CONDUITS, LOCATION OF EQUIPMENT AND OUTLETS,

AND OTHER SUPPORTING ITEMS. FOLLOW THE DESIGN IN THIS DOCUMENTS AS CLOSELY AS

POSSIBLE. COORDINATE TO THE NEAREST INSTALLATION OF TELECOM ITEMS WITH THOSE OF

ALL OTHER TRADES.

4. ALL BLOCKS, PANELS AND CABLE SHALL BE ASSIGNED, LABELED AND RECORDED BY THE

INSTALLING CABLE CONTRACTOR, AND DELIVERED TO THE COR.

5. SEE NOTES ON INDIVIDUAL DRAWINGS FOR CROSS REFERENCE TO PERTINENT DETAILS,

SECTIONS, ETC. SHOWN ON OTHER DRAWINGS IN THIS DRAWING SET.

6. SCALES NOTED ON THE TELECOM DRAWING ARE FOR GENERAL INFORMATION AND USED

FOR REFERENCE ONLY.

7. ALL MOUNTING HEIGHTS SHOWN ARE MEASURED FROM FINISHED FLOOR TO BOTTOM OF

MOUNTED EQUIPMENT UNLESS OTHERWISE NOTED.

8. FIRE STOP ALL STRUCTURE PENETRATIONS WITH FIRE STOPPING MATERIAL EQUAL TO OR

GREATER THAN THAT OF PENETRATED STRUCTURE. INSTALL FIRE STOPPING MATERIAL AFTER

COMPLETE INSTALLATION OF CABLING. USE ONLY LISTED FIRE STOPPING MATERIAL IN

ACCORDANCE WITH UL, AND OTHER AUTHORITIES HAVING JURISDICTION.

9. TELECOM ROOMS SHALL NOT BE USED AS STORAGE SPACE BY ANY CONTRACTOR EXCLUDING

THE INSTALLING CONTRACTOR FOR THE TELECOM SYSTEMS. WHEN THE INSTALLATIONS OF

A TELECOM SPACE IS COMPLETE, REMOVE ALL ITEMS AND EQUIPMENT NOT SUPPORTING

THE FUNCTIONS OF THAT SPACE.

10. PROVIDE 1-HOUR FIRE RATED WALL TO ALL NEW TELECOM AND SECURITY ROOMS/CLOSETS.

SEE ARCHITECTURAL DRAWINGS FOR DETAILS.

11. THE TELECOM DRAWINGS INDICATE THE GENERAL LOCATION OF THE BACKBONE CONDUIT

FOR THE TELECOM ROOMS. VERIFY THE EXACT LOCATION OF THE CONDUIT (S). POSITION

CONDUITS SO THEY ENTER AND EXIT TELECOM ROOMS IN THE CORNERS AS SHOWN ON THE

TELECOM ROOM DRAWINGS.

12. NOT ALL HARDWARE FOR INSTALLATION IS IDENTIFIED/SHOWN. PROVIDE ALL MOUNTING

HARDWARE REQUIRED FOR A COMPLETE AND PROPERLY OPERATING INSTALLATION.

13. NOT ALL ITEMS, COMPONENTS AND SYSTEMS SPECIFIED IN THIS DRAWING SET OR THE

SPECIFICATIONS ARE DETAILED. PROVIDE MANUFACTURER'S SPECIFICATIONS AND DETAIL

SHEETS IN THE PRECONSTRUCTION SUBMITTALS FOR SELECTION PER THE SPECIFICATIONS.

14. INSTALL COMPONENTS OR SYSTEMS PER THE MANUFACTURE'S INSTALLATION

INSTRUCTIONS OR SPECIFICATIONS.

15. ALL CABLE SHALL COMPLY WITH THE SPECIFICATIONS AND SHALL BE SUITABLE AND LISTED

FOR THE ENVIRONMENT IN WHICH IT IS INSTALLED.

16. ALL CONDUIT RUNS SHALL FOLLOW BICSI STANDARDS FOR BENDS, FILL AND JUNCTION BOX

PLACEMENT. NO CONDUIT RUNS SHALL HAVE GREATER THAN 180 DEGREES OF BEND

WITHOUT A PROPERLY SIZED AND PLACED BOX.

17. ALL CONDUIT RUNS AND CABLE TRAY SHOWN ARE DIAGRAMMATICAL. REPORT ANY MAJOR

DEVIATION TO CONSTRUCTION MANAGER FOR APPROVAL..

18. STUB UP 4" A.F.F. ALL CONDUITS FROM BELOW.

19. COORDINATE FINAL SYSTEMS, EQUIPMENT LAYOUT AND CONDUIT ROUTING AS SHOWN ON

DRAWING WITH SITE CONDITIONS.

20. ENSURE PROPER SEPARATION OF CLASS 1, CLASS 2, AND CLASS 3 CIRCUITS PER NEC 725-54.

21. VERIFY THE SIZE OF ALL CONDUCTORS, CONDUIT,L AND JUNCTION BOXES (40% MAXIMUM

FILL). INSTALLATION SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE (NEC)

AND ALL LOCAL CODES HAVING JURISDICTION.

22. DO NOT INSTALL LOW VOLTAGE VOICE AND DATA CABLING IN THE SAME CONDUITS AS 120

VAC POWER CABLES.

23. PROMPTLY NOTIFY COR PRIOR TO INSTALLATION OF WORK IF ANY MOUNTING LOCATIONS

NOTED ON THE DRAWINGS ARE OBSTRUCTED AND/OR IF ANY CONFLICTS OR PROBLEMS ARE

DISCOVERED.

24. PROVIDE AND INSTALL EQUIPMENT AND HARDWARE IN ORDER TO MEET THE INTENT OF THE

DESIGN AND TO PROVIDE GOVERNMENT WITH A COMPLETE AND FULLY OPERATIONAL

CABLING SYSTEM AS SPECIFIED. PROMPTLY ADDRESS ANY QUESTIONS REGARDING THE

INTENT OF THE DESIGN TO THE COR.

25. PROVIDE A SINGLE GANG BOX WITH A CONDUIT TO THE NEAREST ACCESSIBLE CEILING FOR

ANY DEVICE SHOWN ON THESE DRAWINGS THAT IS LOCATED IN AN OPEN OR HARD CEILING

SPACE.

1. COORDINATE EXACT REQUIREMENTS FOR INCOMING SERVICE OF LOCAL UTILITIES FOR POWER AND

TELEPHONE, PAY ALL FEES, AND INSTALL A COMPLETE AND FUNCTIONAL SYSTEM.

2. COORDINATE INSTALLATION OF TELEPHONE SYSTEM INCLUDING TELEPHONE WIRING AND TELEPHONE

OUTLETS WITH THE GOVERNMENT/ENGINEER.

3. REFER TO BASE BUILDING DRAWINGS FOR LOCATION OF UTILITY SERVICE JUNCTION BOX.

COORDINATION WITH TELEPHONE COMPANIES

X

TELECOMMUNICATION COVER

SHEET

T-001

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

TELECOMMUNICATION

DETAILS - I

T-002

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

3 BOX AND CONDUIT INSTALLTION DETAIL

NONE

ACCESSIBLE

CEILING

FACE PLATE

FISHABLE WALL

SINGLE-GANG

REDUCER RING

DOUBLE-GANG BOX

MINIMUM 1" CONDUIT STUBBED TO ACCESSIBLE

CEILING (USE 1-1/4" CONDUIT FOR

MORE THAN 7 CABLES)

TELECOMMUNICATION JACK (BLUE),

WITH CAT 6a (WHITE)

SERIES: MINI COM,

CABLE TYPE: CATEGORY 6a, HUBBELL MODEL # HXJ6B OR EQUAL

2 FACE PLATE DETAILS

NONE

FACEPLATE (IVORY, PLASTIC)

MANUFACTURE: PANDUIT

1 TELECOMMUNICATION SYSTEM DIAGRAM

NONE

1. FOR TELECOMMUNICATION SYMBOLS, ABBREVIATIONS, LEGENDS AND

GENERAL NOTES, SEE DRAWING T-001.

2. FOR IT RACK DETAILS, SEE DRAWING T-003.

GENERAL NOTES

FROM ADMINISTRATION

BUILDING

EXISTING

FIBER CABLE

NEW FIBER CABLE

MODEM/ROUTER (VA/NCA)

NEW CAT 6a CABLE

NEW 48 PORT CAT6a

PATCH PANEL

TO TELECOMMUNICATION

OUTLETS

NEW WALL MOUNTED

IT RACK IN IT ROOM

(PUBLIC RESTROOM

& WASH HOUSE BUILDING)

CAT 6a CABLE

48 PORT NETWORK SWITCH

(VA/NCA)

NEW CAT 6a

CABLE

NOTE:

1. FOR CONSTRUCTION SEQUENCE, SEE THIS DRAWING.

2. COORDINATE WITH VA/OIT DEPARTMENT FOR EXACT CONNECTIONS

BEFORE ORDERING AND CONNECTING ANY EQUIPMENT.

CONSTRUCTION SEQUENCE:

1. COORDINATE WITH LOCAL VA/OIT OFFICE BEFORE COMMENCING

ANY WORK.

2. PERFORM ALL OUTAGES OUTSIDE THE NORMAL BUSINESS HOURS

UNLESS OTHERWISE AUTHORIZED BY COR.

3. PROVIDE AND INSTALL NEW WALL MOUNTED IT RACK IN IT

ROOM OF PUBLIC RESTROOM & WASH HOUSE BUILDING AND

PERFORM FOLLOWING:

a. PROVIDE AND INSTALL NEW PATCH PANEL IN THE IT RACK.

b. TERMINATE ALL INCOMING CAT 6a WIRING COMING FROM

EACH INDIVIDUAL TELECOMMUNICATION OUTLETS LOCATED

IN PUBLIC RESTROOM BUILDING TO IT RACK PATCH PANEL.

c. PROVIDE AND INSTALL ALL COPPER TERMINATIONS FOR ALL

CABLING.

d. TERMINATE AND LABEL EACH CABLE IN THE IT RACK.

e. PROVIDE AND INSTALL NEW FIBER PATCH PANEL IN IT RACK.

f. TERMINATE EXISTING FIBER CABLES COMING FROM

ADMINISTRATION BUILDING TO IT RACK FIBER PATCH

PANEL.

g. MOVE THE EXISTING ROUTER AND SWITCH EQUIPMENT

OVER TO THE NEW IT RACK.

h. PROVIDE ALL CONNECTIONS FOR ROUTER AND SWITCH AND

OTHER TELECOMMUNICATION EQUIPMENT AS SHOWN ON

DATA/TELECOM SYSTEM DIAGRAM, THIS DRAWING.

i. DO NOT DISTURB ALL SERVICES TO ADMINISTRATION

BUILDING, DURING WORK AT PUBLIC RESTROOM BUILDING.

COORDINATE WITH COR AND VA/OIT TEAM BEFORE

COMMENCING ANY WORK.

4. PROVIDE NEW FIBER OPTIC PATCH PANEL IN HISTORIC

MAINTENANCE BUILDING. RUN THE FIBER CABLE FROM NEW IT

RACK TO FOP LOCATED IN HISTORIC MAINTENANCE BUILDING.

FOR UNDERGROUND CONDUIT ROUTING, SEE DRAWING SS-100.

5. MAINTAIN EXISTING OR PROVIDE NEW UTILITIES, SYSTEMS, AND

SERVICES TO OCCUPIED SPACES AT ALL TIMES. NO OUTAGES ARE

PERMITTED DURING NORMAL BUSINESS HOURS. COORDINATE

ALL OUTAGES DURING CHANGE-OVERS BETWEEN EXISTING

BUILDING AND TEMPORARY FACILITIES WITH COR NOT LESS

THAN 7 DAYS IN ADVANCE.

SYSTEM MODEL/PART NUMBERMANUFACTURER

IT RACK CUBE-iT 12419-E24

TYPE

12RU 24"H X 24"W X 30"D

DIMENSIONS REMARKS

WALL-MOUNT ENCLOSURE WITH LOCKABLE FRONT DOOR AND SWING-OUT

REAR ACCESS TO EQUIPMENT. TEMPERED GLASS FRONT DOOR.

VERTICAL CABLE MANAGEMENT CHATSWORTH

PRODUCTS 40970-71111U 19.3"H X 0.5"D

VERTICAL CABLING SECTION FOR WALL MOUNTED IT RACK.

ONE KIT FOR THIS IT RACK

POWER STRIP APC AP9560- 19.2"H X 1.8"W X 2.7"D

110-125 VOLT, SINGLE-PHASE POWER STRIP, SURGE PROTECTED

(TWO PER IT RACK)

FRONT AND REAR RAIL KIT 12787-52412U 24"H EQUIPMENT MOUNTING RAIL KIT FOR IT RACK, ALUMINUM MATERIAL

FAN KIT 40975-001- - LOW DECIBEL DUAL-FAN, AIR FLOW 120 CFM (ONE PER RACK)

115 VOLT, NEMA 5-15P POWER CORD

APC

CHATSWORTH

PRODUCTS

CHATSWORTH

PRODUCTS

FILTER KIT 40973-001- - REPLACEMENT OF FILTER (PACK OF 5) KIT FOR IT RACK

ONE PER RACK

CHATSWORTH

PRODUCTS

LIGHT KIT 12803-701- - 4W LED LIGHT KIT FOR IT RACK

ONE PER RACK

CHATSWORTH

PRODUCTS

GROUND JUMPER 40159-019- - UL LISTED 9' GROUND JUMPER, 10 EACH

NOTES:

1. PROVIDE EQUIPMENT/DEVICES TO MEET THE SPECIFICATIONS OF NAMED MANUFACTURER OR APPROVED EQUAL.

ALL PRODUCTS, EQUIPMENT AND DEVICES PROVIDED UNDER THIS PROJECT SHALL CONFORM TO "BUY AMERICAN ACT".

BRUSH KIT 25190-000- 0.8"X 10.6"H X 2.9"D CABLE PORT BRUSH KIT, 1 PER RACK

UPS SMART UPS

3000- - RACK MOUNT UPS, L5-30 INPUT, L5-30 OUTPUTAPC

CHATSWORTH

PRODUCTS

CHATSWORTH

PRODUCTS

A SPECIFICATIONS OF IT RACK

NONE

ALL

NEW FIBER PATCH PANEL (FOP)

NEW FIBER CABLE

TO TELECOMMUNICATION

OUTLET

CAT 6a CABLE

NEW 8 PORT CAT6a

PATCH PANEL

NEW CAT 6a

CABLE

NEW WALL MOUNTED IT RACK IN

HISTORIC MAINTENANCE BUILDING

NEW FIBER PATCH PANEL (FOP)

TELECOMMUNICATION

DETAILS - II

T-003

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

B GROUNDING AND BONDING OF IT RACK

NONEA ELEVATION OF IT RACK

NONE

ALL

1. IT RACK LAYOUT DETAILS (ELEVATION AND BONDING/GROUNDING

DETAILS) INFORMATION HAS BEEN PROVIDED BY VA/OIT (OFFICE OF

INFORMATION AND TECHNOLOGY) TEAM. COORDINATE WITH VA/OIT

FOR THESE DETAILS BEFORE ORDERING ANY EQUIPMENT, RACK ETC.

GENERAL NOTES:

WASH BAY

B-100

1 2 3 4 5

A

B

D

F

C

MULTI PURPOSE

A-100

PUBLIC

MALE

A-103

UTILITIES

A-102

IT ROOM

A-101

PUBLIC

FEMALE

A-104

VESTIBULE

BW-117M

CORRIDOR

A-105

STAFF

TOILET

A-106

B.1

TELECOM AND DATA PLAN - EXISTING AND NEW WORK2 SCALE : 1/4" = 1'-0"

EXISTING

TELECOMMUNICATION

TERMINAL BOARD

(FIRE RATED PLYWOOD)

(TYP.)

EXISTING

BONDING

BUS BAR

NEW WALL

MOUNTED IT RACK

04 0405

TELECOM AND DATA PLAN - EXISTING AND DEMOLITION1 SCALE : 1/4" = 1'-0"

WASH BAY

B-100

FE

FE

FE

FD FD

1 2 3 4 5

A

B

D

F

C

MULTI PURPOSE

A-100

PUBLIC

MALE

A-103

UTILITIES IT ROOM

PUBLIC

FEMALE

A-104

VESTIBULE

BW-117MA-102 A-101

CORRIDOR

A-105

STAFF

MALE

A-106

STAFF

FEMALE

A-107

X

X

EXISTING

TELECOMMUNICATION

TERMINAL BOARD

(FIRE RATED PLYWOOD)

(TYP.)

EXISTING

BONDING

BUS BAR

EXISTING FLOOR

MOUNTED IT RACK

X

1X

PUBLIC RESTROOM / WASH BAY

BUILDING -

TELECOMMUNICATION PLANS

TN-101

NOT TO SCALE

KEY PLAN

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2022, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Correct FCA Deficiencies

CAMP NELSON NATIONAL CEMETERY

833CM3030

UB,HU SV

JANUARY 7, 2026

Bid Set

KEY NOTES

ASTUTE ENGINEERING, PLLC.

1945 OLD GALLOWS ROAD, STE 201, VIENNA, VA 22182

PH: (202) 400-2004 I WWW.ASTUTENG.COM

STUTE

ENGINEERING

Creative Designs | Intelligent Solutions

A

0 2' 4' 8' 12'

SCALE : 1/4" = 1'-0"

1. FOR SYMBOLS, ABBREVIATIONS, LEGENDS AND GENERAL NOTES,

SEE DRAWING T-001.

GENERAL NOTES

01 DISCONNECT AND REMOVE EXISTING TELECOMMUNICATION

OUTLET INCLUDING WIRING AND CONDUIT.

REMOVE EXISTING FLOOR MOUNTED IT RACK. RELOCATE ALL

EXISTING TELECOMMUNICATION DEVICES SUCH AS ROUTER,

MODEM, PATCH PANELS, LAN SWITCH, ETC. TO NEW WALL

MOUNTED IT RACK. COORDINATE WITH COR AND LOCAL

VA/OIT OFFICE BEFORE RELOCATION OF

TELECOMMUNICATION DEVICES. FOR CONSTRUCTION

SEQUENCE, SEE DRAWING T-002.

EXISTING TELECOMMUNICATION BONDING BUS BAR TO

REMAIN-IN PLACE. PROTECT DURING CONSTRUCTION.

PROVIDE NEW TELECOMMUNICATION OUTLETS AS SHOWN.

INSTALL CATEGORY 6a CABLES FOR ALL OUTLETS. AT THE DEVICE LOCATION, TERMINATE CABLES WITH CATEGORY 6a

JACKS INSTALLED IN A SINGLE-GANG FACEPLATE MOUNTED

AT 18" AFF, UON.

PROVIDE NEW LOCKABLE, WALL MOUNTED IT RACK TO

ACCOMMODATE ALL IT AND…