S02 - Attachment 5 - Electrical Cut Sheets.pdf
PDF 23 MB Posted
- Attached to
- EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS) Federal contract opportunity
- Solicitation number
- 36C77623B0064
About this file
This document provides details on a federal solicitation for infrastructure upgrades at the San Antonio VA Medical Center. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin for the EHRM San Antonio Infrastructure Upgrades Construction project, with a NAICS code of 236220. The solicitation number is 36C77623B0064 and it has been set aside for service-disabled veteran-owned small businesses. An attachment to the solicitation is a 23MB file with electrical cut sheets, though no other content details are provided. The opportunity type is listed as a solicitation.
View the file
Other files for this federal contract opportunity
Show all 50
EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BrandonSanchez Rectangle
REF. DWG.
CHK BY
DRAWN BY
SHEET NO.
ECN NO.
DATE REV. #
FILE NAME:
DWG. NO.LIEBERT 480VAC eXM
WITH 3 BREAKER MAINTENANCE BYPASS CABINET
SINGLE INPUT 50kVA - 250kVA
ONE-LINE DIAGRAM
ORDER NO.
I:\appl\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\A) One-Line Diagram\EXM41011-00.dwg
EXM41011
10/21/15
M. ROCKWELL
K. STACY
BATTERY
UPS CABINET
BIB
MAINTENANCE BYPASS CABINET
BYPASS
AC INPUT
3 WIRE + GRD
STATIC BYPASS
MBB
MIB
AC OUTPUT
480V
3 WIRE + GRD
NOTES:
1. INSTALL IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.
2. INPUT AND BYPASS MUST SHARE THE SAME SINGLE SOURCE.
3. GROUNDING CONDUCTORS ARE REQUIRED.
4. BYPASS AND RECTIFIER INPUTS AND OUTPUT CABLES MUST BE RUN IN
SEPARATE CONDUITS.
5. CONTROL WIRING MUST BE RUN IN SEPARATE CONDUITS.
FIELD SUPPLIED WIRING
* EXTERNAL OVERCURRENT
PROTECTION BY OTHERS
BIB - BYPASS ISOLATION BREAKER
MBB - MAINTENANCE BYPASS BREAKER
MIB - MAINTENANCE ISOLATION BREAKER
OUTPUT
BUSBAR
Document generated 24 March 2023 05:58 PM (EST).
DRAWN BY
SHEET NO.
ECN NO.
DATE REV. #
FILE NAME:
DWG. NO.
LIEBERT 480VAC EXM
50kVA - 200kVA UPS
OUTLINE DRAWING
ORDER NO.
I:\appl-DLW\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\B) Outline Dwg\EXM42001A-03.dwg
EXM42001A
4/6/18
B. SANBORN
J. SHIPMAN
DRAWN BY
SHEET NO.
ECN NO.
DATE REV. #
FILE NAME:
DWG. NO.LIEBERT 480VAC EXM
50kVA - 200kVA UPS
MAIN COMPONENTS LAYOUT
OUTLINE DRAWINGS
ORDER NO.
I:\appl-DLW\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\B) Outline Dwg\EXM42001B-03.dwg
EXM42001B
4/6/18
B. SANBORN
J. SHIPMAN
FRONT VIEW
WITH DOOR OPENED
RIGHT SIDE VIEW
WITH DOOR OPENED
(AND SIDE PANEL REMOVED)
DETAIL A
From To
TB1-6 X9J22-1 Black +12V_BCB_DRV 18G
TB1-7 X9J22-3 Brown BCB_STATE 18G
TB1-8 X9J22-5 White GND_Dry 18G
TB1-9 X9J22-7 Green BCB_ONLINE 18G
TB1-10 X9J22-11 Black GND_Dry 18G
TB1-11 X9J22-13 White TEMP_BAT 18G
TB1-12 X9J22-15 Red +12V_A 18G
Terminal Designation Color
Cable Group #3 - From UPS to Battery Cabinet #1 or MBD
Signal Name Recommended Wire
From To
TB1-1 TB1-1 Black Shunt Trip 18G
TB1-2 TB1-2 White Shunt Trip 18G
TB1-3 TB1-3 Green Aux Contact 18G
TB1-4 TB1-5 Red Aux Contact 18G
Cable Group #4 - From Battery Cabinet to Battery Cabinet
Terminal Designation Color Signal Name Recommended Wire
TITLE
DATE (LATEST REV.)
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
TM
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 43229
EXM44015
LIEBERT 480VAC EXM
UPS TO MAINTENANCE BYPASS CABINET (MBC)
G. HOGE
G. HOGE
J. SHIPMAN
11/29/2017
CABLE GROUP #10
CONTROL WIRING
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
TM
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 43229
EXM47007
LIEBERT 480VAC EXM
B. SANBORN
B. SANBORN
J. SHIPMAN
12/06/2018
150 kVA
UPS EFFICIENCY
NOTES
1. NO LOAD POWER LOSS: 1.28 kW
ECO MODE
NORMAL MODE
DRAWN BY
SHEET NO.
ECN NO.
DATE REV. #
FILE NAME:
DWG. NO.
LIEBERT 480VAC EXM
MAINTENANCE BYPASS CABINET (300mm)
BASE DETAIL
ORDER NO.
I:\appl\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\I) Seismic & Base Details\EXM49005-01.dwg
EXM49005
1/31/18
J. SHIPMAN
J. SHIPMAN
590-1307-501C/SL-52646_REV11_6-17
LIEBERT® INTELLISLOT™
UNITY PLATFORM CARDS
Product Specification/Installation Guide
The Liebert IntelliSlot Unity Platform brings SNMP, BACnet IP, BACnet MSTP, Modbus TCP, Modbus RTU, YDN23 and Web management capability to many models of Vertiv’s power and cooling equipment. The cards employ Ethernet and RS-485 networks to monitor and manage a wide range of operating parameters, alarms and notifications. The card also supports communication for LIFE™ Services by VERTIV.
ADDITIONAL FEATURES
• SNMPv1, SNMPv2c and SNMPv3 with MIB-II support
• HTTP/HTTPS 1.1
• BootP
• DHCP per RFC2131/2132
• Remote firmware updates via a Web browser
• IPv6 support for HTTP/HTTPS, DHCPv6, e-mail, SMS, SNMP v1/v2c/ v3 and Modbus TCP
• Liebert SN Environmental Sensor Support (Web, SNMP, SMS and SMTP): Temperature, Humidity, Door Closure, Contact Closure and Leak Detection: Liebert SN-2D, Liebert SN-3C, Liebert SN-L, Liebert SN-T, Liebert SN-TH, Liebert SN-Z01, Liebert SN-Z02 and Liebert SN-Z03
IntelliSlot Unity cards are a form, fit, and function replacement for several Liebert IntelliSlot Web and 485 cards.
COMPATABILITY with Liebert Equipment
IntellSlot Card Compatible with
IS-UNITY-DP
IS-UNITY-SNMP
IS-UNITY-LIFE
Alber BDSU-50™
Liebert APM™
Liebert APS™
Liebert Challenger
3000™
Liebert CRV™
Liebert CW™
Liebert DCL™
Liebert DCP™
Liebert Deluxe System/3™
Liebert DS™
Liebert DSE™
Liebert EPM™
Liebert EXC™
Liebert eXL™
Liebert EXL™ S1
Liebert eXM™
Liebert FDC™
Liebert FPC™
Liebert GXT3™
Liebert GXT4™
Liebert HPC™
Liebert HPC-S/M/R/W/Generic™
Liebert HPM™
Liebert NX™ 225-600 kVA
Liebert NXC™
Liebert NXL™ *
Liebert NXR™
Liebert PCW™/PDX™
Liebert PeX™ *
Liebert PPC™
Liebert RDC™
Liebert RX™
Liebert XDC™
Liebert XDP™
Liebert XDP-Cray™
* YDN23 supported only for Liebert PeX and Liebert NXL.
VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
590-1307-501C/SL-52646_REV11_6-17
LIEBERT® INTELLISLOT™ UNITY PLATFORM CARDS
Product Specification/Installation Guide
COMPATABILITY with Communication Protocols
Liebert IntelliSlot Card
Life Services Support
Communication Protocol
HTTP
HTTPS
Velocity Protocol
Email SMS SNMP v1, v2c, v3
BACnet IP BACnet MSTP
Modbus TCP Modbus RTU
YDN23*
IS-UNITY-DP
IS-UNITY-SNMP — — —
IS-UNITY-LIFE — — — —
* YDN23 supported only for Liebert PeX and Liebert NXL.
DIMENSIONS
SPECIFICATIONS
Power Requirements DC Inputs 7 to 12 VDC
Power Consumptions: 3.6 W maximum
Dimensions, W x D x H 2.97 x 5.2 x 1.45 in. (75.5 x 15 x 37 mm)
Weight (assembled) Net: 7 oz (0.2 kg)
Shipping: 1.3 lb (0.6 kg)
Ambient Operating Environment 32 to 104°F (0 to 40°C); 10% to 90% RH (non-condensing)
Ambient Storage Temperature –4 to 140°F (–20 to 60°C)
Communication Ports Ethernet Communication RJ-45 (LIFE™ Services requires a network connection to the Internet)
RJ-45 (RJ-45 to 2-position terminal-block adapter)
WIRING
10/100 Mb/s Ethernet connector Standard Category 5E Cable 328 ft. (100m)
RJ-45 - One-Wire Connector Liebert® Integrated One-Wire Sensor Cable or 2m Cat 5E to Modular 1-Wire
65.6 ft. (20m)
1/2” (11 mm)4-3/4” (121 mm)
2-3/8” (60.3 mm)
1-1/2” (38 mm)
3” (76 mm)
Front face
Board
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-05-S001
2/14/2019
LOGAN JOHNSON1 OF 9
MIKE OLLER
TM
FORM NO. DPN004658 Rev0
36.1"
36.7"
933 DISPLAY
81.5"
85.6"
41.4"
OPTIONAL EZ-VIEW
DOORS
OUTLINE DRAWING
SINGLE AND NO MICB
150-300KVA
LIEBERT TFX
OPTIONAL DISPLAY
NOTES:
1. ALL DIMENSIONS ARE IN INCHES [MM].
2. COOLING CLEARANCES
FRONT: FOR UNITS WITH VOLTAGES UNDER 150V TO GROUND
A MINIMUM OF 36" [914MM] IS REQUIRED FOR SERVICE ACCESS
FOR UNITS WITH VOLTAGES OVER 150V TO GROUND REQUIRE 42" [1067MM]
PER NEC 110.26.
REAR: A MINIMUM OF 6" [152.4MM] IS REQUIRED.
ONE SIDE: A MINIMUM OF 6" [152.4MM] IS REQUIRED ON ONE SIDE OF THE
TRANSFORMER CABINET.
IF LIEBERT FLX CABINETS ARE ATTACHED, REFER TO TFX-04-SXXX
FOR CLEARANCE CLARIFICATIONS.
3. KEEP CABINET WITHIN 15v OF VERTICAL.
4. ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.
5. UNIT IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.
FRONT VIEWLEFT VIEW RIGHT VIEW
in-lb Nm in-lb Nm in-lb Nm
10-32 (M5) 8 25 3 - - 62 7
1/4-20 (M6) 10 53 6 40 4.5 80 9
5/16-18 (M8) 13 107 12 90 10 180 20
3/8-16 (M10) 17 192 22 120 13.5 240 27
1/2-13 (M12) 19 428 48 480 54 - -
GRADE 5 - IMPERIAL
GRADE 8.8 - METRIC
ELECTRICAL
CONNECTIONS WITH 1
BELLEVILLE WASHERS
ELECTRICAL
CONNECTIONS WITH 2
BELLEVILLE WASHERS
BOLT SHAFT SIZE
HEX HEAD SIZE
(MM)
Document generated 24 March 2023 05:48 PM (EST).
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-01-S002
5/13/2019
LOGAN JOHNSON1 OF 1
ONE-LINE DIAGRAM
SINGLE MAIN INPUT CIRCUIT BREAKER (MICB) OPTION
LIEBERT TFX SYSTEM
SINGLE MICB CONFIGURATION
3W + G
ISOLATION
TRANSFORMER
INPUT
LIGHTNING/SURGE
ARRESTOR
(OPTIONAL)
OUTPUT
SPIKE
SUPPRESSION
MODULE
(OPTIONAL)
D
IS
T R
IB
U
T
IO
N B
U
S INTERNAL
DISTRIBUTION
(OPTIONAL)
ATTACHED
LIEBERT FLX
CABINETS
(OPTIONAL)
NOTES:
1. ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL
AND LOCAL ELECTRICAL CODES.
2. INPUT AND OUTPUT FEEDERS CAN BE THROUGH THE
TOP AND/OR BOTTOM OF THE LIEBERT TFX
TRANSFORMER CABINET.
3. CONTROL WIRING AND POWER WIRING MUST BE RUN
IN SEPERATE CONDUITS.
4. THE MICB UTILIZES A 24VDC SHUNT TRIP FOR EPO
CIRCUITRY. THE LOCAL EPO BUTTON CAN BE REMOVED
AT THE FACTORY
MAIN INPUT
CIRCUIT BREAKER
FIELD SUPPLIED WIRING
Document generated 24 March 2023 05:48 PM (EST).
BrandonSanchez Callout
(5) 250A LSI Breakers
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-05-S001
2/14/2019
LOGAN JOHNSON4 OF 9
VOLTAGE TEST POINTS
LOW VOLTAGE
MONITORING BOARDS
HIGH VOLTAGE
MONITORING BOARDS
HIGH VOLTAGE
POWER SUPPLY BOARDS
MAIN COMPONENTS
SINGLE AND NO MICB
150-300KVA
LIEBERT TFX
OPTIONAL
SINGLE
MICB
AUXILIARY
DISTRIBUTION SECTION
OPTIONAL
SINGLE
MICB
AUXILIARY
DISTRIBUTION SECTION
DISTRIBUTION SECTION 2
DISTRIBUTION SECTION 1
FRONT VIEW
DPM, TRANSFORMER & DISTRIBUTION
MONITORING OPTION
FRONT VIEW
NO MONITORING & DPM
TRANSFORMER MONITORING ONLY
(SEE NOTE 1)
DISTRIBUTION SECTION 3
(SEE NOTE 1)
NOTES:
1. DISTRIBUTION SECTION #3 IS ONLY AVAILABLE ON
UNITS WITHOUT DISTRIBUTION MONITORING.
HIGH VOLTAGE PCB FUSES
DISTRIBUTION SECTION 1
DISTRIBUTION SECTION 2
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-05-S001
2/14/2019
LOGAN JOHNSON5 OF 9
54.5"
GROUND
57.9"
NEUTRAL
73.9"
MICB BUSSING
NOTES:
1. ALL DIMENSIONS ARE IN INCHES [MM]
2. REFER TO BREAKER MANUFACTURER SUBMITTAL (TFX-03-XXXX)
FOR BREAKER AND PANELBOARD TERMINATION RECOMMENDATIONS.
3. FASTENING HARDWARE IS SUPPLIED BY OTHERS/INSTALLING CONTRACTOR.
15.2"
MICB BUSSING
29.4"
NEUTRAL
32.9"
GROUND
DETAIL B
GROUND BUSBAR
DETAIL A
MAIN INPUT CB
BUSBARS
O .56"
2.05"
1.75"
O .56"
1.75"
A
B
ELECTRICAL CONNECTIONS
SINGLE AND NO MICB
150-300KVA
LIEBERT TFX
2.00"
DETAIL C
NEUTRAL BUSBAR
1.89"
1.75"
O .56"
C
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-05-S001
2/14/2019
LOGAN JOHNSON6 OF 9
NOTES:
1. ALL DIMENSIONS ARE IN INCHES [MM]
2. REFER TO BREAKER MANUFACTURER SUBMITTAL (TFX-03-XXXX)
FOR BREAKER AND PANELBOARD TERMINATION RECOMMENDATIONS.
3. THIS DRAWING IS INTENDED FOR INSTALLER USE ONLY. IT IS INTENDED
TO SHOW THE POTENTIAL DISTRIBUTION OPTIONS WITHIN THE
TRANSFORMER CABINET. YOUR CONFIGURATION MAY HAVE A MIX OF
DISTRIBUTION OPTIONS. USE THE DIMENSIONS PROVIDED TO ESTIMATE
WIRING REQUIREMENTS.
11.6"
TYP
4.4"
14.5"
18.2"
68.6"
40.3"
55.3"
30.3"
ELECTRICAL CONNECTIONS - SUBFEEDS
SINGLE AND NO MICB
150-300KVA
LIEBERT TFX
28.0"
28.0"
SUBFEED DISTRIBUTION USING
250AF BREAKERS
SUBFEED DISTRIBUTION USING
400/600AF BREAKERS
66.93"
66.93"
MICB
OPTIONAL
MICB
OPTIONAL
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-05-S001
2/14/2019
LOGAN JOHNSON7 OF 9
12.9"
12.8"
66.9"
28.1"
66.9"
32.2"
3 PANELBOARD DISTRIBUTION
15.6"
15.6"
32.1"
67.0"
ELECTRICAL CONNECTIONS - PANELBOARDS
SINGLE AND NO MICB
150-300KVA
LIEBERT TFX
PANELBOARD DISTRIBUTION
66.9"
28.1"
NOTES:
1. ALL DIMENSIONS ARE IN INCHES [MM]
2. REFER TO BREAKER MANUFACTURER SUBMITTAL (TFX-03-XXXX)
FOR BREAKER AND PANELBOARD TERMINATION RECOMMENDATIONS.
3. THIS DRAWING IS INTENDED FOR INSTALLER USE ONLY. IT IS INTENDED
TO SHOW THE POTENTIAL DISTRIBUTION OPTIONS WITHIN THE
TRANSFORMER CABINET. YOUR CONFIGURATION MAY HAVE A MIX OF
DISTRIBUTION OPTIONS. USE THE DIMENSIONS PROVIDED TO ESTIMATE
WIRING REQUIREMENTS.
MICB OPTIONAL
MICB OPTIONAL
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-05-S001
2/14/2019
LOGAN JOHNSON8 OF 9
POWER INPUT/OUTPUT
CONDUIT PLATE
POWER INPUT/OUTPUT CONDUIT PLATE
(SEE NOTE 3, 4)
COMMUNICATIONS CONDUIT PLATE
(SEE NOTE 3)
VENTILATION PLATE
(SEE NOTE 2)
4.1"
103 TYP
TOP CONDUIT PLATE DETAILS
SINGLE AND NO MICB
150-300KVA
LIEBERT TFX
NOTES:
1. ALL DIMENSIONS ARE IN INCHES [MM].
2. VENTILATION PLATE MUST NOT BE USED AS A CONDUIT LANDING AREA.
3. REMOVE CONDUIT PLATE, PUNCH TO SUIT AND REPLACE.
4. CONDUIT PLATE CAN ACCOMODATE UP TO:
A. (3) 2.5" CONDUITS FOR INPUT, (12) 4" CONDUITS FOR SUBFEED BREAKERS.
B. (2) 4" CONDUITS FOR INPUT, (12) 3.5" AND (2) 2.0-2.5" CONDUITS FOR
SUBFEED BREAKERS.
C. WHEN A PANELBOARD IS CONFIGURED, THE CONDUIT PLATE WILL HAVE
PRE-PUNCHED CONDUIT KNOCKOUTS WITH A MIXTURE OF 1/2" KO'S AND
3/4" KO'S AND A PUNCH AREA FOR INPUTS AND OUTPUT SUBFEED BREAKERS.
ISO VIEW
TOP VIEW
FRONT VIEW
23.78"
25.98"
12.80"
3.41"
1.7" 431.4"
1.4"
6.8"
15.9"
HIGH VOLTAGE
TEST POINT BOARD
LOW VOLTAGE
MONITORING BOARD
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-05-S001
2/14/2019
LOGAN JOHNSON9 OF 9
BOTTOM CONDUIT PLATE DETAILS
SINGLE AND NO MICB
150-300KVA
LIEBERT TFX
FRONT VIEW
BOTTOM VIEW
9.1"
5.0"
26.3"
18.5" 4709.1"
5.0"
3.9"
2.4"
LOW VOLTAGE
CONDUIT
NOTES:
1. ALL DIMENSIONS ARE IN INCHES [MM].
2. VENTILATION PLATE MUST NOT BE USED AS A CONDUIT LANDING AREA.
3. REMOVE CONDUIT PLATE, PUNCH TO SUIT AND REPLACE.
4. CONDUIT PLATE MUST BE INVERTED (AS SHOWN)PRIOR TO ENERGIZING
THE PDU, EVEN IF BOTTOM INPUT IS NOT UTILIZED.
5. CONDUIT PLATE CAN ACCOMODATE UP TO:
A. (3) 2.5" CONDUITS FOR INPUT, (12) 4" CONDUITS FOR SUBFEED BREAKERS.
B. (2) 4" CONDUITS FOR INPUT, (12) 3.5" AND (2) 2.0-2.5" CONDUITS FOR
SUBFEED BREAKERS.
C. WHEN A PANELBOARD IS CONFIGURED, THE CONDUIT PLATE WILL HAVE
PRE-PUNCHED CONDUIT KNOCKOUTS WITH A MIXTURE OF 1/2" KO'S AND
3/4" KO'S AND A PUNCH AREA FOR INPUTS AND OUTPUT SUBFEED BREAKERS.
D. IN ADDITION TO THE ABOVE: (2) 9.1" ARE AVAILABLE IN SIDE FRAME WHICH
CAN BE USED WHEN CABLE PULLING IS NOT NEEDED.
7.5"
TYP
1.5"
NOTE 3, 4, 5
7.2"
TYP
1.7"
TYP
.9"
2.6"
VENTILATION PLATES
(SEE NOTE 2)
FRONT
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-10-S001
5/16/2019
LOGAN JOHNSON1 OF 2
IR SCAN PORT OPTION
150-300kVA TRANSFORMER CABINET
LIEBERT TFX
IR SCAN PORT OFFERS VIEWING TO
TRANSFORMER CONNECTION BUS STABS
IR SCAN PORT OFFERS VIEWING TO
PHASE A, B ,C, GROUND, NEUTRAL BUSBARS,
AND MICB CUSTOMER CONNECTIONS
FRONT VIEW
TRANSFORMER CABINET
LEFT SIDE VIEW
TRANSFORMER CABINET
REAR VIEW
TRANSFORMER CABINET
NOTES:
1. DASHED TRIANGLES REPRESENT SMALLEST POSSIBLE VIEWING ANGLE.
2. THIS OPTION PROHIBITS THE USE OF LEFT SIDE MOUNTED LIEBERT
FLX CABINETS.
3. VIEWING CLEARANCE REQUIREMENTS:
LEFT SIDE: 36" [914.4MM] MINIMUM.
TOP: 18" [457.2MM] MINIMUM (36" [914.4MM] RECOMMENDED)
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-10-S001
5/16/2019
LOGAN JOHNSON2 OF 2
IR SCAN PORT OPTION
150-300kVA TRANSFORMER CABINET
LIEBERT TFX
IR SCAN PORT OFFERS VIEWING TO MICB,
PHASE A, B ,C, GROUND, AND NEUTRAL BUSBARS
RIGHT SIDE VIEW
TOP VIEW
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
FLX-10-S001
2/14/2019
LOGAN JOHNSON1 OF 1
IR SCAN PORT OPTION
FLX12A CABINETS
LIEBERT FLX
IR SCAN PORT OFFERS VIEWING TO
CUSTOMER/LOAD SIDE CONNECTIONS
FRONT VIEW
FLX12A CABINET WITH (4) 250 AMP FRAME
BREAKERS MAX
IR SCAN PORT OFFERS VIEWING TO
CUSTOMER/LOAD SIDE CONNECTIONS
FRONT VIEW
FLX12A CABINET WITH (3) 600 AMP FRAME
BREAKERS MAX
SIDE VIEW
600 AMP FRAME IR PORT VIEWING AREA (TYP)
SIDE VIEW
250 AMP FRAME IR PORT VIEWING AREA (TYP)
A
A
SECTION A-A
B
B
SECTION B-B
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-19-S010
5/22/2019
LOGAN JOHNSON1 OF 1
CABLE LAYOUT
CUSTOMER CABLE ROUTING
LIEBERT TFX
LOW VOLT
WIRING TROUGH
BOTTOM OPENING
LOW VOLTAGE
WIRING TROUGH
TOP OPENING
LOW VOLTAGE
WIRING TROUGH
TOP VIEW
TRANSFORMER CABINET
TEST POINT
BOARD
(NO CUSTOMER
CONNECTIONS)
MICI BOARDS
(NO CUSTOMER
CONNECTIONS)
EXTERNAL INTERFACE
BOARD
COMM SLOT 1
CUSTOMER
PROVIDED
CABLE
LOW VOLTAGE
WIRING AREA
COMM SLOT 2
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-19-S050
5/21/2019
LOGAN JOHNSON1 OF 1
CONTROL WIRING
CABLE GROUP #1, EPO/REPO CIRCUITRY
LIEBERT TFX
TB1
TB3
TB4
EXTERNAL EPO (REPO)
EXTERNAL INTERFACE BOARD
NOTES:
1. ALL SWITCHING DEVICES ARE TO BE SUITABLE FOR SWITCHING
LOW CURRENT 24 VDC. MINIMUM RECOMMENDED WIRE SIZE IS
18 AWG STRANDED COPPER WITH 300 VOLT INSULATION. ALL
WIRING AND DEVICES ARE FIELD SUPPLIED EXCEPT WHERE NOTED.
SEE INSTALLATION MANUAL FOR DETAILED INSTALLATION PROCEDURES.
2. LOW VOLTAGES TERMINAL STRIP IS LOCATED IN THE OPTIONAL LOW VOLTAGE CONTROL
JUNCTION BOX.
3. THE TOTAL LOAD ON THE 24 VDC SUPPLY (BOTH N.O. AND N.C. REPO CIRCUITS)
MUST BE LIMITED TO 1 AMP.
4. MULTIPLE NORMALLY OPEN (N.O.) REPO SWITCHES MAY BE PARALLELED
MULTIPLE NORMALLY CLOSED (N.C.) REPO SWITCHES MAY BE CONNECTED IN
SERIES. ALL LAMPS (IF USED) ARE CONNECTED IN PARALLEL.
5. SEE CABLE LAYOUT SUBMITTAL (TFX-19-S0XX) FOR EXTERNAL INTERFACE
BOARD LOCATION.
6. USE 28-16 AWG WITH A MAXIMUM LENGTH OF 1,000 FEET (300 M)
EPO POWER 1
EPO GROUND 3
EPO NC 5 EPO NO 5
EPO GROUND 3
EPO POWER 1
TBI
REVISION
DRAWN BY:
DESIGNED BY:
APPROVED BY:
SHEET NO.
ECN NO.
REF DWG.
DWG. NO.
1050 DEARBORN DR
P.O. BOX 29186
COLUMBUS, OH 432290
TFX-19-S051
5/21/2019
LOGAN JOHNSON1 OF 1
CONTROL WIRING
CABLE GROUP #2, CUSTOMER ALARMS
LIEBERT TFX
TB1
TB3
TB4
CUSTOMER OUTPUT
ALARMS
CUSTOMER INPUT
ALARMS
EXTERNAL INTERFACE BOARD
NOTES:
1. ALL SWITCHING DEVICES ARE TO BE SUITABLE FOR SWITCHING
LOW CURRENT 24 VDC. MINIMUM RECOMMENDED WIRE SIZE IS
18 AWG STRANDED COPPER WITH 300 VOLT INSULATION. ALL
WIRING AND DEVICES ARE FIELD SUPPLIED EXCEPT WHERE NOTED.
SEE INSTALLATION MANUAL FOR DETAILED INSTALLATION PROCEDURES.
2. LOW VOLTAGES TERMINAL STRIP MAY BE LOCATED IN THE OPTIONAL
LOW VOLTAGE CONTROL JUNCTION BOX.
3. CUSTOMER LARMS 1 THROUGH 4 ARE NORMALLY OPEN (INDICATES ALARM ON
CONTACT CLOSURE). CUSTOMER ALARM 5 IS NORMALLY CLOSED (INDICATES
ALARM ON CONTACT OPENING).
4. SEE CABLE LAYOUT SUBMITTAL (TFX-19-S0XX) FOR HMI INTERFACE
BOARD LOCATION.
COM-4
INPUT FORM A/B-3
INPUT FORM A/B-1
COM-2
ALARM 2 N/O-5
ALARM 2 N/C-3
ALARM 2 COM-1ALARM 1 COM-1
ALARM 1 N/C-3
ALARM 1 N/O-5
TB3
TB4
Vertiv™ Liebert® Intellislot RDU101 Communications Card
The Liebert® Intellislot RDU101 card enables communication between Vertiv™ products such as Trellis™ Enterprise, Trellis™ Power Insight and LIFE™ Services. It provides web access, data via SNMP and Modbus TCP for Vertiv equipment. Environmental sensor data access is provided via web and SNMP.
Benefits:
y Quick, real-time view of parametric data and system statuses.
y Prompt alarm notification for fast event resolution.
y Know environmental conditions of your data center for informed, efficient decision making.
y Flexible communication regardless of device protocol.
y Peace of mind knowing data is transported in a secure manner.
y Save time configuring and updating firmware on managed devices.
Overview How It Works
The RDU101 employs Ethernet networks to monitor and manage a wide range of operating parameters, alarms and notifications.
Solving Problems
Managing disparate systems within the data center can be challenging. With responsibilities to know the conditions of your facility at all times, keeping track of all that data may require accessing multiple systems or even performing manual, time consuming data tracking. Being able to collect data from your systems is key to effectively managing the data center. The RDU101 provides remote centralized monitoring connectivity to building management systems (BMS) that use SNMP.
Adding Value
Not only does the RDU101 improve efficiency by providing a one-to-one view of the connected system, it also provides a convenient way to configure and update devices via HTTP APIs. Save time on initial deployments and improve ongoing maintenance through the mass configuration capabilities of the RDU101.
Keep Data Secure
The RDU101 keeps data secure. Basic security is provided via HTTPS web connectivity and SNMP v3. Centralized access and authorization management provides an additional layer of security via remote authentication protocols – RADIUS, TACACS+, LDAP/AD and Kerberos.
Features y Provides web access to the installed devices via popular web browsers- Microsoft Internet Explorer, Mozilla Firefox, Google Chrome and Safari.
y Provides alarm notifications via email and text messaging.
y Supports environmental monitoring via Liebert SN Sensors for temperature, humidity, leak detection, doors and contact closures.
y Supports third-party protocols for building and network management applications for status and alarms via SNMP and Modbus TCP.
y Enables Vertiv software tools and services, including Trellis™ Enterprise, Trellis™ Power Insight and LIFE Services.
y Supports high-speed file transfer to managed devices for firmware and configuration updates.
y HTTPS messages and web access encryption with installable customer provided certificates.
y Options for SNMP v3 authentication support (none, MD5 or SHA), privacy support (none, DES or AES) and Traps.
SL-31322 (R01/20)
Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2020 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications, rebates and other promotional offers are subject to change at Vertiv’s sole discretion upon notice.
Vertiv™ Liebert® Intellislot RDU101 Communications Card
Technical Specifications
Power Requirements DC Input
Power Consumption
7 to 12 VDC
3.6 W maximum
Dimensions, W x D x H 2.97 x 5.2 x 1.45 in. (75.5 x 15 x 37 mm)
Weight (assembled) Net:
Shipping:
7 oz (0.2 kg)
1.3 lb (0.6 kg)
Ambient Operating Environment 32 to 104°F (0 to 40°C), 10% to 90% RH (non-condensing)
Ambient Storage Temperature -4 to 140° F (-20 to 60°C)
Communication Ports Ethernet Communication
RJ-45
Wiring
10/100 Mb/s Ethernet Connector Standard Category 5E Cable 328 ft. (100m)
RJ-45 - One-Wire Connector Liebert® Integrated One-Wire Sensor Cable or 2m Cat 5E to Modular 1-Wire
65.6 ft. (20m)
PS519338EN page 1 October 5, 2022 9:02 AM
Project Catalog # Type
Prepared by Notes Date
Interactive Menu
• Order Information page 2
• Photometric Data page 3
• Connected Systems page 3
• Product Warranty
SNLED Base
LED Striplight
Typical Applications
Commercial • Industrial • Retail • Residential • Storage / Utility • Coves • Display Cases • Shops • Task and General Area Lighting
Top Product Features
• Standard (SL) and High lumen/High Efficacy (HL) packages
• High efficiencies - up to 153 LPW
• Three different lens types for optical control
• Two different reflectors for precise distribution control
• Available CCT: 3000K, 3500K, 4000K and 5000K
• Minimum CRI of 80; 90 CRI available
• Options to meet Trade Agreements Act requirements
Dimensional Details 2-11/16" [68mm]
1-15/16" [50mm]
1-25/32" [46mm]
2-1/4" [58mm]
2-7/8" [73mm]
24" [609mm] 2-1/2" [64mm]
14" [355mm]
Ceiling Stand-off Embossments
Hole for Toggle
2'
96" [2437mm]
K.O (2) 7/8" [22mm]
K.O (2) 7/8" [22mm]
Hole for Toggle
26-3/4" [680mm] 5" [127mm]
Ceiling Stand-off Embossments
2-1/2" [64mm]
8'
2-7/8" [73mm]
2-7/8" [73mm]
48" [1219mm] 38" [965mm]
Ceiling Stand-off Embossments
2-7/8" [73mm]
K.O (3) 7/8" [22mm]
Hole for Toggle
4'
2-1/2" [64mm]
ZW-SWPD3 Sidecar
Product Certification
Product Features
Designed to provide safe and convenient means of disconnecting power http://www.cooperlighting.com https://www.cooperlighting.com/global/brands/mws.html https://www.cooperlighting.com/global/resources/programs/rapid-response
SNLED Base
PS519338EN page 2 October 5, 2022 9:02 AM
Order Information
SAMPLE ORDER NUMBER: 4SNLED-LD5-48SL-UNV-L840-U
Domestic Preferences Length Series Lamp Type Lumen Package Voltage Options
Domestic Preferences (1) Length Series Lamp Type Lumen Package Voltage Options
[Blank]=Standard TAA=Trade Agreements Act
2=2' Length 4=4' Length 8T=8' Length
SNLED=
Commercial LED Striplight (2)(2)
LD5=LED 5.0 Stocked Lumen Packages
24SL (3)
28SL (3)
32SL
48SL
80SL
88SL
MTO Lumen Packages
20SL (3)
36SL
37HL
40SL
44SL
52SL
56SL
56HL
60SL
60HL
64SL
64HL
68SL
72SL
85HL
96SL
104SL
112SL (5)
130HL (5)
170HL (4)
UNV=Universal Voltage 120-277 347V=347V 480V=480V (6)
Emergency EL7W=7-watt, 120V-277V emergency battery pack installed (7), (9)
EL14W=14-watt 120V-277V emergency battery pack installed (7), (9)
GTR2=Bodine Generator Transfer Relay (10)
ETRD=Iota Emergency Transfer Relay with dimming control (10)
Wiring PI/CPI=Plug in and cross over plug in options (12)
PC6/515P=(NEMA 5-15P) 6' Cord with NEMA Straight Plug (11), (12)
PC6/L715=(NEMA L7-15P) 6' Cord with NEMA Twist Plug (11), (12)
Motion Sensors (13)
LB-ERMS360=360° Low Bay Motion Sensor - End of Row LB-MRMS360=360° Low Bay Motion Sensor - Middle of Row HB-ERMS360=360° High Bay Motion Sensor - End of Row (8)
HB-MRMS360=360° High Bay Motion Sensor - Middle of Row (8)
CCT / CRI
L830=3000K, 80 CRI
L835=3500K, 80 CRI
L840=4000K, 80 CRI
L850=5000K, 80 CRI
L930=3000K, 90 CRI
L935=3500K, 90 CRI
L940=4000K, 90 CRI
L950=5000K, 90 CRI
ZW-SWPD3=WaveLinx Wireless Sensor, Sidecar mount, with 1200 sq ft.
coverage (14)
WLS4=WaveLinx Lite Wireless Integrated Sensor, 15'–40' Mounting Height (14), (15)
Notes Notes Notes Notes Notes
(1) Only product configurations with this designated prefix are built to be compliant with the Trade Agreements Act of 1979 (TAA). Please refer to DOMESTIC PREFERENCES website for more information. Components shipped separately may be separately analyzed under domestic preference requirements.
(2) DesignLights Consortium® Qualified and classified for both DLC Standard and DLC Premium, refer to www.
designlights.org for details.
(3) Available in 2 ft. and 4 ft. (4) Requires two drivers. (5) DALI and Step-dim versions require two drivers.
(6) 4 ft. and 8
ft. only.
(7) 4 ft. and 8 ft. only. (8) Motion Sensor offers dimmability. (9) With integral test switch/ indicator/laser test. For approximate delivered lumens multiply the lumens per watt of the desired fixture by the wattage of the emergency battery pack (100 lm/W x 7=700 lumens). IES-format photometry for luminaire under emergency operation available. (10) Used to bypass local control during outage. Must be used in conjunction with UL 1008 device (provided by others). GTR2 option includes 2 relays on fixtures with dimming drivers. ETRD option only requires one relay when used on a dimming fixture. Must specify voltage as 120V or 277V when ordering these devices. (11) Most common C&P shown. Must specify location for cord. All “end” locations will be on the end with sensor installed. (12) Consult tech support on numerous options for this feature. (13) Sensors provided in separate externally mounted enclosure. See SRL spec sheet for fully integrated/connected sensors. (14) Not compatible with EL options. Not available with 347V, 480V, or UNC. Not available with 5LTD option. End row mounting only. (15) WaveLinx Lite devices are not currently compatible with the WaveLinx Pro Wireless Area Controller.
Driver Type Number of Drivers Packaging Accessories
Drive Type Number of Drivers Packaging Accessories (order separately) (18)
CD=0-10V Dimming Driver (10% - 100% Dimming) HCD=0-10V Dimming Driver (1% - 100% Dimming) SD=Step-dim (Bi Level) (16)
5LTD=Fifth Light (DALI) Driver (16), (17)
1=1 Driver 2=2 Drivers
U=Unit Pack (Order Separately) AYC-Chain/Set=36” Chain Hanger (Use 1 set per fixture) SCF=Fixed Stem Set (Specify Length) SCS=Swivel Stem Set (Specify Length) SCA=Adjustable 48” Stem Set EYE-CHAIN/SET-B=Eye Bolt Chain (Use 1 set per fixture) WG/SNF-2FT=2’ Wire Guard WG/SNF-4FT=4’ Wire Guard A1B/Spacer-U=Spacer 1-1/2” to 2-1/2” from ceiling (Use 2 per fixture) TOGGLE=Single Toggle No. 2 (Specify Length) Y-TOGGLE- -2PK=(2) Y-Toggle Cable Kits (Specify 10 or 30 for length in feet) SNLED-LENS-LW-2FT-U=Replacement Lens 2 ft, Full Frost SNLED-LENS-LN-2FT-U=Replacement Lens 2 ft, Semi Frost SNLED-LENS-LC-2FT-U=Replacement Lens 2 ft, Clear SNLED-LENS-LW-4FT-U=Replacement Lens 4 ft, Full Frost SNLED-LENS-LN-4FT-U=Replacement Lens 4 ft, Semi Frost SNLED-LENS-LC-4FT-U=Replacement Lens 4 ft, Clear GRP-SNF-U=Gripper Hanger CLC-SNLED-EXT-B=SNLED Long Row Aligner Extension
Notes Notes
(16) 4 ft. and 8 ft. only. (17) For a complete listing of Fifth Light products, visit www.cooperlighting.com
(18) Accessories sold separately will be separately analyzed under domestic preference requirements. Consult factory for further information.
https://www.cooperlighting.com/global/resources/programs/domestic-preferences
PS519338EN page 3 October 5, 2022 9:02 AM
Product Specifications Construction
• Die-formed of cold rolled steel with numerous knockouts for easy installation
• Groove for Tong Hanger
• Convertible end plate for continuous row alignment
• Channel/wireway cover secured with sheet metal screws
• Surface, pendant or stem mounting
Controls
• 0-10V dimming drivers to 10% or to 1% options
• Combine with energy-saving products like occupancy sensors, daylighting controls and lighting relay panels to maximize energy savings
• For motion control, reference options for both end and middle of the row applications
• Step-dimming option
• Fifth Light DALI 2.0 driver option
Electrical
• Long-life LED system with electrical driver for optimal performance
• LED’s available in 3000K, 3500K, 4000K or 5000K with CRI of 80 standard or optional 90 CRI
• TM21 rating up to L87 >60,000 hours
• Electronic drivers available for 120-277V, 347V and 480 applications
• Operating temperature of -20°C to 40°C; Ideal for cold storage environments
Emergency Battery Pack Option
• Optional 120V-277V integral emergency battery pack available in 7W or 14W
• 90-minute backup period for code compliance
• Test switch with laser pointer allows safe testing from floor
• Patented EZ Key prevents accidental discharge during construction
• Generator transfer options available
Compliance
• cULus Listed for damp locations
• RoHS compliant
• Complies with IESNA LM-79 and LM-80 standards
• NEMA 410 compliant (drivers)
• State of California Title 24 high efficacy luminaire
• DesignLights Consortium® Qualified and classified for DLC Standard and DLC Premium (refer to www.designlights.org)
• Suitable for closet use when installed to NEC
410.16 spacings standards
Warranty
• Five year warranty
Photometric Data
View IES files
WaveLinx Lite devices are not currently compatible with the WaveLinx Pro Wireless Area Controller
Control Systems
• WaveLinx Wireless
• WaveLinx Wired
• WaveLinx Lite http://www.designlights.org http://www.cooperindustries.com/content/dam/public/lighting/about%20us/terms_and_conditions/Lighting-Division-TC-Matrix.pdf https://www.cooperlighting.com/global/brands/metalux/snled-series.html https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wired https://www.cooperlighting.com/global/brands/wavelinx/lite https://www.cooperlighting.com/global/controls-wiring/building-systems
Cooper Lighting Solutions 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.cooperlighting.com
© 2022 Cooper Lighting Solutions All Rights Reserved.
Specifications and dimensions subject to change without notice.
PS519338EN page 4 October 5, 2022 9:02 AM
Energy and Performance Data
CRI
Lumen multiplier (80CRI to 90CRI)
3000K 3500K 4000K 5000K
0.805 0.840 0.846 0.901
CCT Table
Approximate Color Temperature Multiplier
2700K .93
3000K .98
3500K 1.0
4000K 1.02
5000K 1.02
Shipping Data
Length Wt.
2 ft. 3.8 lbs.
4 ft. 7.2 lbs.
8 ft. 13.1 lbs.
SNELD
Type
Lumen Type Length Catalog Number
Nominal 3500K Lumens Wattage Im/W
Base Standard 2 ft. 2SNLED-LD5-20SL-UNV-L8XX-CD1-U 2005 14 140.5
Base Standard 2 ft. 2SNLED-LD5-24SL-UNV-L8XX-CD1-U 2476 18 136.8
Base Standard 2 ft. 2SNLED-LD5-28SL-UNV-L8XX-CD1-U 2810 21 132.1
Base High 2 ft. 2SNLED-LD5-37HL-UNV-L8XX-CD1-U 3799 27 143.0
Base Standard 4 ft. 4SNLED-LD5-20SL-UNV-L8XX-CD1-U 1934 13 148.4
Base Standard 4 ft. 4SNLED-LD5-24SL-UNV-L8XX-CD1-U 2398 16 149.8
Base Standard 4 ft. 4SNLED-LD5-28SL-UNV-L8XX-CD1-U 2761 18 149.7
Base Standard 4 ft. 4SNLED-LD5-32SL-UNV-L8XX-CD1-U 3148 21 148.7
Base Standard 4 ft. 4SNLED-LD5-36SL-UNV-L8XX-CD1-U 3649 25 146.6
Base Standard 4 ft. 4SNLED-LD5-40SL-UNV-L8XX-CD1-U 4014 28 144.9
Base Standard 4 ft. 4SNLED-LD5-44SL-UNV-L8XX-CD1-U 4367 31 142.9
Base Standard 4 ft. 4SNLED-LD5-48SL-UNV-L8XX-CD1-U 4827 35 139.9
Base Standard 4 ft. 4SNLED-LD5-52SL-UNV-L8XX-CD1-U 5167 38 137.4
Base Standard 4 ft. 4SNLED-LD5-56SL-UNV-L8XX-CD1-U 5604 41 136.4
Base Standard 4 ft. 4SNLED-LD5-60SL-UNV-L8XX-CD1-U 6015 46 130.4
Base Standard 4 ft. 4SNLED-LD5-64SL-UNV-L8XX-CD1-U 6504 52 125.9
Base Standard 4 ft. 4SNLED-LD5-68SL-UNV-L8XX-CD1-U 6781 55 123
Base High 4 ft. 4SNLED-LD5-56HL-UNV-L8XX-CD1-U 5634 37 152
Base High 4 ft. 4SNLED-LD5-60HL-UNV-L8XX-CD1-U 5894 39 150.9
Base High 4 ft. 4SNLED-LD5-64HL-UNV-L8XX-CD1-U 6421 43 148.9
Base High 4 ft. 4SNLED-LD5-85HL-UNV-L8XX-CD1-U 8471 62 136.3
Base Standard 8 ft. 8TSNLED-LD5-64SL-UNV-L8XX-CD1-U 6296 42 147.8
Base Standard 8 ft. 8TSNLED-LD5-72SL-UNV-L8XX-CD1-U 7298 50 146.6
Base Standard 8 ft. 8TSNLED-LD5-80SL-UNV-L8XX-CD1-U 8028 55 144.9
Base Standard 8 ft. 8TSNLED-LD5-88SL-UNV-L8XX-CD1-U 8734 61 142.9
Base Standard 8 ft. 8TSNLED-LD5-96SL-UNV-L8XX-CD1-U 9654 69 139.9
Base Standard 8 ft. 8TSNLED-LD5-104SL-UNV-L8XX-CD1-U 10334 75 137.4
Base Standard 8 ft. 8TSNLED-LD5-112SL-UNV-L8XX-CD1-U 11208 82 136.4
Base High 8 ft. 8TSNLED-LD5-130HL-UNV-L8XX-CD1-U 12842 86 148.9
Base High 8 ft. 8TSNLED-LD5-170HL-UNV-L8XX-CD2-U 16942 124 136.3
*Stocked in either 3500K or 4000K. Check Flash for stock availability.
PS519338EN page 1 October 5, 2022 9:02 AM
Project Catalog # Type
Prepared by Notes Date
Interactive Menu
• Order Information page 2
• Photometric Data page 3
• Connected Systems page 3
• Product Warranty
SNLED Base
LED Striplight
Typical Applications
Commercial • Industrial • Retail • Residential • Storage / Utility • Coves • Display Cases • Shops • Task and General Area Lighting
Top Product Features
• Standard (SL) and High lumen/High Efficacy (HL) packages
• High efficiencies - up to 153 LPW
• Three different lens types for optical control
• Two different reflectors for precise distribution control
• Available CCT: 3000K, 3500K, 4000K and 5000K
• Minimum CRI of 80; 90 CRI available
• Options to meet Trade Agreements Act requirements
Dimensional Details 2-11/16" [68mm]
1-15/16" [50mm]
1-25/32" [46mm]
2-1/4" [58mm]
2-7/8" [73mm]
24" [609mm] 2-1/2" [64mm]
14" [355mm]
Ceiling Stand-off Embossments
Hole for Toggle
2'
96" [2437mm]
K.O (2) 7/8" [22mm]
K.O (2) 7/8" [22mm]
Hole for Toggle
26-3/4" [680mm] 5" [127mm]
Ceiling Stand-off Embossments
2-1/2" [64mm]
8'
2-7/8" [73mm]
2-7/8" [73mm]
48" [1219mm] 38" [965mm]
Ceiling Stand-off Embossments
2-7/8" [73mm]
K.O (3) 7/8" [22mm]
Hole for Toggle
4'
2-1/2" [64mm]
ZW-SWPD3 Sidecar
Product Certification
Product Features
Designed to provide safe and convenient means of disconnecting power http://www.cooperlighting.com https://www.cooperlighting.com/global/brands/mws.html https://www.cooperlighting.com/global/resources/programs/rapid-response
PS519338EN page 2 October 5, 2022 9:02 AM
Order Information
SAMPLE ORDER NUMBER: 4SNLED-LD5-48SL-UNV-L840-U
Domestic Preferences Length Series Lamp Type Lumen Package Voltage Options
Domestic Preferences (1) Length Series Lamp Type Lumen Package Voltage Options
[Blank]=Standard TAA=Trade Agreements Act
2=2' Length 4=4' Length 8T=8' Length
SNLED=
Commercial LED Striplight (2)(2)
LD5=LED 5.0 Stocked Lumen Packages
24SL (3)
28SL (3)
32SL
48SL
80SL
88SL
MTO Lumen Packages
20SL (3)
36SL
37HL
40SL
44SL
52SL
56SL
56HL
60SL
60HL
64SL
64HL
68SL
72SL
85HL
96SL
104SL
112SL (5)
130HL (5)
170HL (4)
UNV=Universal Voltage 120-277 347V=347V 480V=480V (6)
Emergency EL7W=7-watt, 120V-277V emergency battery pack installed (7), (9)
EL14W=14-watt 120V-277V emergency battery pack installed (7), (9)
GTR2=Bodine Generator Transfer Relay (10)
ETRD=Iota Emergency Transfer Relay with dimming control (10)
Wiring PI/CPI=Plug in and cross over plug in options (12)
PC6/515P=(NEMA 5-15P) 6' Cord with NEMA Straight Plug (11), (12)
PC6/L715=(NEMA L7-15P) 6' Cord with NEMA Twist Plug (11), (12)
Motion Sensors (13)
LB-ERMS360=360° Low Bay Motion Sensor - End of Row LB-MRMS360=360° Low Bay Motion Sensor - Middle of Row HB-ERMS360=360° High Bay Motion Sensor - End of Row (8)
HB-MRMS360=360° High Bay Motion Sensor - Middle of Row (8)
CCT / CRI
L830=3000K, 80 CRI
L835=3500K, 80 CRI
L840=4000K, 80 CRI
L850=5000K, 80 CRI
L930=3000K, 90 CRI
L935=3500K, 90 CRI
L940=4000K, 90 CRI
L950=5000K, 90 CRI
ZW-SWPD3=WaveLinx Wireless Sensor, Sidecar mount, with 1200 sq ft.
coverage (14)
WLS4=WaveLinx Lite Wireless Integrated Sensor, 15'–40' Mounting Height (14), (15)
Notes Notes Notes Notes Notes
(1) Only product configurations with this designated prefix are built to be compliant with the Trade Agreements Act of 1979 (TAA). Please refer to DOMESTIC PREFERENCES website for more information. Components shipped separately may be separately analyzed under domestic preference requirements.
(2) DesignLights Consortium® Qualified and classified for both DLC Standard and DLC Premium, refer to www.
designlights.org for details.
(3) Available in 2 ft. and 4 ft. (4) Requires two drivers. (5) DALI and Step-dim versions require two drivers.
(6) 4 ft. and 8
ft. only.
(7) 4 ft. and 8 ft. only. (8) Motion Sensor offers dimmability. (9) With integral test switch/ indicator/laser test. For approximate delivered lumens multiply the lumens per watt of the desired fixture by the wattage of the emergency battery pack (100 lm/W x 7=700 lumens). IES-format photometry for luminaire under emergency operation available. (10) Used to bypass local control during outage. Must be used in conjunction with UL 1008 device (provided by others). GTR2 option includes 2 relays on fixtures with dimming drivers. ETRD option only requires one relay when used on a dimming fixture. Must specify voltage as 120V or 277V when ordering these devices. (11) Most common C&P shown. Must specify location for cord. All “end” locations will be on the end with sensor installed. (12) Consult tech support on numerous options for this feature. (13) Sensors provided in separate externally mounted enclosure. See SRL spec sheet for fully integrated/connected sensors. (14) Not compatible with EL options. Not available with 347V, 480V, or UNC. Not available with 5LTD option. End row mounting only. (15) WaveLinx Lite devices are not currently compatible with the WaveLinx Pro Wireless Area Controller.
Driver Type Number of Drivers Packaging Accessories
Drive Type Number of Drivers Packaging Accessories (order separately) (18)
CD=0-10V Dimming Driver (10% - 100% Dimming) HCD=0-10V Dimming Driver (1% - 100% Dimming) SD=Step-dim (Bi Level) (16)
5LTD=Fifth Light (DALI) Driver (16), (17)
1=1 Driver 2=2 Drivers
U=Unit Pack (Order Separately) AYC-Chain/Set=36” Chain Hanger (Use 1 set per fixture) SCF=Fixed Stem Set (Specify Length) SCS=Swivel Stem Set (Specify Length) SCA=Adjustable 48” Stem Set EYE-CHAIN/SET-B=Eye Bolt Chain (Use 1 set per fixture) WG/SNF-2FT=2’ Wire Guard WG/SNF-4FT=4’ Wire Guard A1B/Spacer-U=Spacer 1-1/2” to 2-1/2” from ceiling (Use 2 per fixture) TOGGLE=Single Toggle No. 2 (Specify Length) Y-TOGGLE- -2PK=(2) Y-Toggle Cable Kits (Specify 10 or 30 for length in feet) SNLED-LENS-LW-2FT-U=Replacement Lens 2 ft, Full Frost SNLED-LENS-LN-2FT-U=Replacement Lens 2 ft, Semi Frost SNLED-LENS-LC-2FT-U=Replacement Lens 2 ft, Clear SNLED-LENS-LW-4FT-U=Replacement Lens 4 ft, Full Frost SNLED-LENS-LN-4FT-U=Replacement Lens 4 ft, Semi Frost SNLED-LENS-LC-4FT-U=Replacement Lens 4 ft, Clear GRP-SNF-U=Gripper Hanger CLC-SNLED-EXT-B=SNLED Long Row Aligner Extension
Notes Notes
(16) 4 ft. and 8 ft. only. (17) For a complete listing of Fifth Light products, visit www.cooperlighting.com
(18) Accessories sold separately will be separately analyzed under domestic preference requirements. Consult factory for further information.
PS519338EN page 3 October 5, 2022 9:02 AM
Product Specifications Construction
• Die-formed of cold rolled steel with numerous knockouts for easy installation
• Groove for Tong Hanger
• Convertible end plate for continuous row alignment
• Channel/wireway cover secured with sheet metal screws
• Surface, pendant or stem mounting
Controls
• 0-10V dimming drivers to 10% or to 1% options
• Combine with energy-saving products like occupancy sensors, daylighting controls and lighting relay panels to maximize energy savings
• For motion control, reference options for both end and middle of the row applications
• Step-dimming option
• Fifth Light DALI 2.0 driver option
Electrical
• Long-life LED system with electrical driver for optimal performance
• LED’s available in 3000K, 3500K, 4000K or 5000K with CRI of 80 standard or optional 90 CRI
• TM21 rating up to L87 >60,000 hours
• Electronic drivers available for 120-277V, 347V and 480 applications
• Operating temperature of -20°C to 40°C; Ideal for cold storage environments
Emergency Battery Pack Option
• Optional 120V-277V integral emergency battery pack available in 7W or 14W
• 90-minute backup period for code compliance
• Test switch with laser pointer allows safe testing from floor
• Patented EZ Key prevents accidental discharge during construction
• Generator transfer options available
Compliance
• cULus Listed for damp locations
• RoHS compliant
• Complies with IESNA LM-79 and LM-80 standards
• NEMA 410 compliant (drivers)
• State of California Title 24 high efficacy luminaire
• DesignLights Consortium® Qualified and classified for DLC Standard and DLC Premium (refer to www.designlights.org)
• Suitable for closet use when installed to NEC
410.16 spacings standards
Warranty
• Five year warranty
Photometric Data
View IES files
WaveLinx Lite devices are not currently compatible with the WaveLinx Pro Wireless Area Controller
Control Systems
• WaveLinx Wireless
• WaveLinx Wired
• WaveLinx Lite http://www.designlights.org http://www.cooperindustries.com/content/dam/public/lighting/about%20us/terms_and_conditions/Lighting-Division-TC-Matrix.pdf https://www.cooperlighting.com/global/brands/metalux/snled-series.html https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wired https://www.cooperlighting.com/global/brands/wavelinx/lite https://www.cooperlighting.com/global/controls-wiring/building-systems
Cooper Lighting Solutions 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.cooperlighting.com
© 2022 Cooper Lighting Solutions All Rights Reserved.
Specifications and dimensions subject to change without notice.
PS519338EN page 4 October 5, 2022 9:02 AM
Energy and Performance Data
CRI
Lumen multiplier (80CRI to 90CRI)
3000K 3500K 4000K 5000K
0.805 0.840 0.846 0.901
CCT Table
Approximate Color Temperature Multiplier
2700K .93
3000K .98
3500K 1.0
4000K 1.02
5000K 1.02
Shipping Data
Length Wt.
2 ft. 3.8 lbs.
4 ft. 7.2 lbs.
8 ft. 13.1 lbs.
SNELD
Type
Lumen Type Length Catalog Number
Nominal 3500K Lumens Wattage Im/W
Base Standard 2 ft. 2SNLED-LD5-20SL-UNV-L8XX-CD1-U 2005 14 140.5
Base Standard 2 ft. 2SNLED-LD5-24SL-UNV-L8XX-CD1-U 2476 18 136.8
Base Standard 2 ft. 2SNLED-LD5-28SL-UNV-L8XX-CD1-U 2810 21 132.1
Base High 2 ft. 2SNLED-LD5-37HL-UNV-L8XX-CD1-U 3799 27 143.0
Base Standard 4 ft. 4SNLED-LD5-20SL-UNV-L8XX-CD1-U 1934 13 148.4
Base Standard 4 ft. 4SNLED-LD5-24SL-UNV-L8XX-CD1-U 2398 16 149.8
Base Standard 4 ft. 4SNLED-LD5-28SL-UNV-L8XX-CD1-U 2761 18 149.7
Base Standard 4 ft. 4SNLED-LD5-32SL-UNV-L8XX-CD1-U 3148 21 148.7
Base Standard 4 ft. 4SNLED-LD5-36SL-UNV-L8XX-CD1-U 3649 25 146.6
Base Standard 4 ft. 4SNLED-LD5-40SL-UNV-L8XX-CD1-U 4014 28 144.9
Base Standard 4 ft. 4SNLED-LD5-44SL-UNV-L8XX-CD1-U 4367 31 142.9
Base Standard 4 ft. 4SNLED-LD5-48SL-UNV-L8XX-CD1-U 4827 35 139.9
Base Standard 4 ft. 4SNLED-LD5-52SL-UNV-L8XX-CD1-U 5167 38 137.4
Base Standard 4 ft. 4SNLED-LD5-56SL-UNV-L8XX-CD1-U 5604 41 136.4
Base Standard 4 ft. 4SNLED-LD5-60SL-UNV-L8XX-CD1-U 6015 46 130.4
Base Standard 4 ft. 4SNLED-LD5-64SL-UNV-L8XX-CD1-U 6504 52 125.9
Base Standard 4 ft. 4SNLED-LD5-68SL-UNV-L8XX-CD1-U 6781 55 123
Base High 4 ft. 4SNLED-LD5-56HL-UNV-L8XX-CD1-U 5634 37 152
Base High 4 ft. 4SNLED-LD5-60HL-UNV-L8XX-CD1-U 5894 39 150.9
Base High 4 ft. 4SNLED-LD5-64HL-UNV-L8XX-CD1-U 6421 43 148.9
Base High 4 ft. 4SNLED-LD5-85HL-UNV-L8XX-CD1-U 8471 62 136.3
Base Standard 8 ft. 8TSNLED-LD5-64SL-UNV-L8XX-CD1-U 6296 42 147.8
Base Standard 8 ft. 8TSNLED-LD5-72SL-UNV-L8XX-CD1-U 7298 50 146.6
Base Standard 8 ft. 8TSNLED-LD5-80SL-UNV-L8XX-CD1-U 8028 55 144.9
Base Standard 8 ft. 8TSNLED-LD5-88SL-UNV-L8XX-CD1-U 8734 61 142.9
Base Standard 8 ft. 8TSNLED-LD5-96SL-UNV-L8XX-CD1-U 9654 69 139.9
Base Standard 8 ft. 8TSNLED-LD5-104SL-UNV-L8XX-CD1-U 10334 75 137.4
Base Standard 8 ft. 8TSNLED-LD5-112SL-UNV-L8XX-CD1-U 11208 82 136.4
Base High 8 ft. 8TSNLED-LD5-130HL-UNV-L8XX-CD1-U 12842 86 148.9
Base High 8 ft. 8TSNLED-LD5-170HL-UNV-L8XX-CD2-U 16942 124 136.3
*Stocked in either 3500K or 4000K. Check Flash for stock availability.
General Information: 93PM UPS 20-200kW
93PM System Specifications System Voltage: 480V in, 208/120V out (3 wire in, 4 wire out) UPS Frame Capacity: 150kW
Quantity of 50kW Power Modules: 3 UPS kW Rating: 150 Internal Redundant Configuration: No Internal Battery Configuration: None Input Feed: Single Feed ESS Included: No Communication: Industrial Gateway Card Accessories: Sidecar Bypass Cabinet Side Car: 3 Breaker MBS, Left Mount Side Car Breaker Rating: 65kAIC MBS w/ Aux contact Exhaust Configuration: Top Air Exhaust Internal Estimated Runtime: None UPS Dimensions (H" x W" x D"): 74 x 36.7 x 42 UPS Weight (lbs): 1503
UPS System Dimensions Combined Matching System Dimensions (H" x W" x D", excluding non-matching panels):
74 x 101.9 x 42
93PM Integrated Distribution Cabinet IDC kW Rating: 150kW
Transformer: K13, TP1, 480/208 Delta/Wye Breaker Interrupt Rating (kAIC): High kAIC Top Distribution: 3 Subfeed Breakers + 2 Field
Provisions Bottom Distribution: No Distribution
Subfeed Breaker Rating: 100% Rated Breaker Exhaust Configuration: Top Air Exhaust Output Breaker: No OSHPD Rated: No IAC-D Dimensions (H" x W" x D"): 74 x 31.3 x 42 IAC-D Weight (lbs): 2003.5
UPS Accessories Floor Stand: None Chimney: None
93PM Battery Cabinet Battery Cabinet: IBC-LW
DC Voltage: 480 Battery Cabinet Weight (lbs): 4803 Battery Cabinet Width (in): 34.2 74" H x 42" D kW for Runtime Calculation: 150 Estimated Runtime (min) at 77 degrees F:
11.3
# of Cabinets/Strings: 1/1 Battery Manufacturer: Eaton Battery Installation: Line and Match OSHPD Rated: No
NEG-ALT Number
PREPARED BY DATE
APPROVED BY DATE
VERSION
REVISION DWG SIZE
JOB NAME
DESIGNATION
TYPE
G.O.
DRAWING TYPE
ITEM SHEET
The information on this document is created by Eaton Corporation. It is disclosed in confidence and it is only to be used for the purpose in which it is supplied.
P20T0323X3K1-0000
Conner Fisher 3/23/2023
10.0.0.0
0 A
Eaton VA Data Center At Audie Murphy (San Antonio)
93PM UPS 20-200kW Customer Appr.
Conner Fisher Text Box Solution ID # NO32323001-SWMCO-CF
Jacinto.V.Fuentes Rectangle
Jacinto.V.Fuentes Highlight 11.3
1 2 3
Structure 1 2 3 Ship-Inches Ship-MM Width-Inches Width-MM
31.00 36.70 34.20 787 932 868
Depth-Inches Depth-MM
42.00 42.00 42.00 1066 1066 1066
Height-Inches Height-MM
74.00 74.00 74.00 1879 1879 1879
Weight-Lbs Weight-Kg
2003.50 1503.00 4803.00
908.62 681.63 2178.23
NEG-ALT Number
PREPARED BY DATE
APPROVED BY DATE
VERSION
REVISION DWG SIZE
JOB NAME
DESIGNATION
TYPE
G.O.
DRAWING TYPE
ITEM SHEET
The information on this document is created by Eaton Corporation. It is disclosed in confidence and it is only to be used for the purpose in which it is supplied.
P20T0323X3K1-0000
Conner Fisher 3/23/2023
10.0.0.0
0 A
Eaton VA Data Center At Audie Murphy (San Antonio)
93PM UPS 20-200kW Customer Appr.
Jacinto.V.Fuentes Callout PDU W/ 150kW 480:208/120V K13 Rated Step-Down Transformer & (4) 250A Subfeeds / (1) Future Subfeed Provisions
Jacinto.V.Fuentes Callout 3-Breaker Sidecar (External) Maintenance Bypass
Jacinto.V.Fuentes Callout 150kW Frame 93PM UPS System Rated At 150kW Installed Capacity
Jacinto.V.Fuentes Callout
(2) VRLA Battery Cabinets
Jacinto.V.Fuentes Text Box Recommended Input Breaker Size:
150kW = 250A (80% Rated) / 200A (100% Rated)
Page: 1 of 3
GO/NEG-Alt-Date: Job Name:
Item Number: Catalog Number: Designation:
P20T0323X3K1-0000-3/23/2023 VA Data Center At Audie Murphy (San Antonio)
9PL15N0005E40R2
Jacinto.V.Fuentes Highlight
Jacinto.V.Fuentes Highlight
Jacinto.V.Fuentes Highlight
Jacinto.V.Fuentes Highlight
Jacinto.V.Fuentes Highlight
Jacinto.V.Fuentes Highlight
Jacinto.V.Fuentes Callout UPS Will Be Top Exhaust
Jacinto.V.Fuentes Rectangle
Jacinto.V.Fuentes
Page: 2 of 3
Item Number: Catalog Number: Designation:
P20T0323X3K1-0000-3/23/2023 VA Data Center At Audie Murphy (San Antonio)
9PL15N0005E40R2
Jacinto.V.Fuentes Rectangle
Jacinto.V.Fuentes Rectangle
Jacinto.V.Fuentes Callout 3-Breaker Sidecar Mounted On Left Side of UPS (Can Be On Right Side If Needed)
Page: 3 of 3
Item Number: Catalog Number: Designation:
P20T0323X3K1-0000-3/23/2023 VA Data Center At Audie Murphy (San Antonio)
9PL15N0005E40R2
Jacinto.V.Fuentes Line
Jacinto.V.Fuentes Rectangle
Page: 1 of 3
Item Number: Catalog Number: Designation:
P20T0323X3K1-0000-3/23/2023 VA Data Center At Audie Murphy (San Antonio)
9PL15N0005E40R2
Jacinto.V.Fuentes Rectangle
Jacinto.V.Fuentes Rectangle
Jacinto.V.Fuentes Callout 150kW PDU W/ (4) 250A Subfeed Breakers & (1) Future Provision Spaces
Also Contains 150kVA K-13 Rated 480:208/120V Step-Down Transformer
Page: 2 of 3
Item Number: Catalog Number: Designation:
P20T0323X3K1-0000-3/23/2023 VA Data Center At Audie…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .