S02 - Attachment 5 - Electrical Cut Sheets.pdf

PDF 23 MB Posted

Attached to
EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS) Federal contract opportunity
Solicitation number
36C77623B0064
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document provides details on a federal solicitation for infrastructure upgrades at the San Antonio VA Medical Center. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin for the EHRM San Antonio Infrastructure Upgrades Construction project, with a NAICS code of 236220. The solicitation number is 36C77623B0064 and it has been set aside for service-disabled veteran-owned small businesses. An attachment to the solicitation is a 23MB file with electrical cut sheets, though no other content details are provided. The opportunity type is listed as a solicitation.

View the file

Other files for this federal contract opportunity

Other files attached to EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS), newest first.
File Type Posted
S07 - Bid Abstract Page 2_OF1419A_EHRM San Antonio_06SEP2023.pdf PDF
S02 - Attchment 24 - EHRM San Antonio Bid Breakdown Table_31AUG2023.xlsx XLSX spreadsheet
Amendment 0004_36C77623B0064_25AUG2023.pdf PDF
S02 - Attachment 21 - Addendum 1 - Technology.pdf PDF
S02 - Attachment 19 - 02821321 Asbestos Roofing Abatement.pdf PDF
S02 - Attachment 15 - STX Addendum 1 (Composite).pdf PDF
S02 - Attachment 22 - SF 25 Performance Bond Form.pdf PDF
S02 - Attachment 18 - 320523 Cement and Concrete for Exterior Improvements.pdf PDF
S02 - Attachment 23 - SF 25A Payment Bond Form.pdf PDF
S02 - Attachment 20 - Addendum 1 - Mechanical.pdf PDF
S02 - Attachment 17 - 075100 Roofing Repair.pdf PDF
Amendment 0003 Attachment Warranty RoofCAD-VA San Antonio-RFI Q100.pdf PDF
Amendment 0003_36C77623B0064_23AUG2023.pdf PDF
Amendment 0002_36C77623B0064_18AUG2023.pdf PDF
S02 - Attachment 6(c) - Mechanical Cut Sheets - Clean Agent Data Sheet.pdf PDF
S02 - Attachment 6(e) - Mechanical Cut Sheets - Data Center CRAC - N 1 Operation (8000 cfm).pdf PDF
S02 - Attachment 6(a) - Mechanical Cut Sheets - 3.0 Ton Split System.pdf PDF
S02 - Attachment 6(f) - Mechanical Cut Sheets - 2.0 Ton Split System.pdf PDF
Pre-bid Site Visit Sign-in Sheet_11AUG2023.pdf PDF
Amendment 0001_36C77623B0064_02AUG2023.pdf PDF
S02 - Attachment 14(a) - Asbestos Survey Results 1st-4th Floors.pdf PDF
S02 - Attachment 11 - Wage Determination_Bexar CountyTX_14APR2023.pdf PDF
S02 - Attachment 12 - Submittal Register ENG Form 4288-R.pdf PDF
S02 - Attachment 9 - Contractor Safety and Environmental Record Form.docx DOCX document
S02 - Attachment 7(h) - Technology Cut Sheets - Part 8 of 11 Axis.pdf PDF
S02 - Attachment 1(a) - 671-22-700 DRAWINGS General Sheets.pdf PDF
S02 - Attachment 8(b) - OIT-InfrastrucStdTelecomSpaces_Part 2 of 3.pdf PDF
S02 - Attachment 8(a) - OIT-InfrastrucStdTelecomSpaces_Part 1 of 3.pdf PDF
S02 - Attachment 7(b) - Technology Cut Sheets - Part 2 of 11 Corning.pdf PDF
S02 - Attachment 7(f) - Technology Cut Sheets - Part 6 of 11 Ortronics.pdf PDF
S02 - Attachment 7(j) - Technology Cut Sheets - Part 10 of 11 HID.pdf PDF
S02 - Attachment 7(e) - Technology Cut Sheets - Part 5 of 11 Leviton.pdf PDF
S02 - Attachment 7(k) - Technology Cut Sheets - Part 11 of 11 Hubbell.pdf PDF
S02 - Attachment 7(i) - Technology Cut Sheets - Part 9 of 11 Cablofil.pdf PDF
S02 - Attachment 1(c) - 671-22-700 DRAWINGS Mechanical.pdf PDF
S02 - Attachment 4 - 230501 SAT_EHRM_100 percent final TechnicalReport.pdf PDF
S02 - Attachment 8(c) - OIT-InfrastrucStdTelecomSpaces_Part 3 of 3.pdf PDF
S02 - Attachment 7(c) - Technology Cut Sheets - Part 3 of 11 CPI.pdf PDF
S02 - Attachment 7(g) - Technology Cut Sheets - Part 7 of 11 Panduit.pdf PDF
S02 - Attachment 1(b) - 671-22-700 DRAWINGS Architectural.pdf PDF
S02 - Attachment 6 - Mechanical Cut Sheets.pdf PDF
S02 - Attachment 7(a) - Technology Cut Sheets - Part 1 of 11 APC.pdf PDF
S02 - Attachment 3 - 671-22-700 EHRM Infrastructure Upgrades- SOW Construction.pdf PDF
Solicitation 36C77623B0064_28JUL2023.pdf PDF
S02 - Attachment 14(b) - Asbestos Survey Results Ground and 5th-7th Floors.pdf PDF
S02 - Attachment 13 - VA OEHRM Site Infrastructure and EUD Reqmts 2.0.pdf PDF
S02 - Attachment 10 - VA Notice Limitations on Subcontracting - Construction (JAN 2023) (DEV).docx DOCX document
S02 - Attachment 7(d) - Technology Cut Sheets - Part 4 of 11 CPI Cabinet.pdf PDF
S02 - Attachment 1(e) - 671-22-700 DRAWINGS Technology.pdf PDF
S02 - Attachment 1(d) - 671-22-700 DRAWINGS Electrical.pdf PDF
Show all 50

EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS) has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BrandonSanchez Rectangle

REF. DWG.

CHK BY

DRAWN BY

SHEET NO.

ECN NO.

DATE REV. #

FILE NAME:

DWG. NO.LIEBERT 480VAC eXM

WITH 3 BREAKER MAINTENANCE BYPASS CABINET

SINGLE INPUT 50kVA - 250kVA

ONE-LINE DIAGRAM

ORDER NO.

I:\appl\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\A) One-Line Diagram\EXM41011-00.dwg

EXM41011

10/21/15

M. ROCKWELL

K. STACY

BATTERY

UPS CABINET

BIB

MAINTENANCE BYPASS CABINET

BYPASS

AC INPUT

3 WIRE + GRD

STATIC BYPASS

MBB

MIB

AC OUTPUT

480V

3 WIRE + GRD

NOTES:

1. INSTALL IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.

2. INPUT AND BYPASS MUST SHARE THE SAME SINGLE SOURCE.

3. GROUNDING CONDUCTORS ARE REQUIRED.

4. BYPASS AND RECTIFIER INPUTS AND OUTPUT CABLES MUST BE RUN IN

SEPARATE CONDUITS.

5. CONTROL WIRING MUST BE RUN IN SEPARATE CONDUITS.

FIELD SUPPLIED WIRING

* EXTERNAL OVERCURRENT

PROTECTION BY OTHERS

BIB - BYPASS ISOLATION BREAKER

MBB - MAINTENANCE BYPASS BREAKER

MIB - MAINTENANCE ISOLATION BREAKER

OUTPUT

BUSBAR

Document generated 24 March 2023 05:58 PM (EST).

DRAWN BY

SHEET NO.

ECN NO.

DATE REV. #

FILE NAME:

DWG. NO.

LIEBERT 480VAC EXM

50kVA - 200kVA UPS

OUTLINE DRAWING

ORDER NO.

I:\appl-DLW\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\B) Outline Dwg\EXM42001A-03.dwg

EXM42001A

4/6/18

B. SANBORN

J. SHIPMAN

DRAWN BY

SHEET NO.

ECN NO.

DATE REV. #

FILE NAME:

DWG. NO.LIEBERT 480VAC EXM

50kVA - 200kVA UPS

MAIN COMPONENTS LAYOUT

OUTLINE DRAWINGS

ORDER NO.

I:\appl-DLW\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\B) Outline Dwg\EXM42001B-03.dwg

EXM42001B

4/6/18

B. SANBORN

J. SHIPMAN

FRONT VIEW

WITH DOOR OPENED

RIGHT SIDE VIEW

WITH DOOR OPENED

(AND SIDE PANEL REMOVED)

DETAIL A

From To

TB1-6 X9J22-1 Black +12V_BCB_DRV 18G

TB1-7 X9J22-3 Brown BCB_STATE 18G

TB1-8 X9J22-5 White GND_Dry 18G

TB1-9 X9J22-7 Green BCB_ONLINE 18G

TB1-10 X9J22-11 Black GND_Dry 18G

TB1-11 X9J22-13 White TEMP_BAT 18G

TB1-12 X9J22-15 Red +12V_A 18G

Terminal Designation Color

Cable Group #3 - From UPS to Battery Cabinet #1 or MBD

Signal Name Recommended Wire

From To

TB1-1 TB1-1 Black Shunt Trip 18G

TB1-2 TB1-2 White Shunt Trip 18G

TB1-3 TB1-3 Green Aux Contact 18G

TB1-4 TB1-5 Red Aux Contact 18G

Cable Group #4 - From Battery Cabinet to Battery Cabinet

Terminal Designation Color Signal Name Recommended Wire

TITLE

DATE (LATEST REV.)

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

TM

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 43229

EXM44015

LIEBERT 480VAC EXM

UPS TO MAINTENANCE BYPASS CABINET (MBC)

G. HOGE

G. HOGE

J. SHIPMAN

11/29/2017

CABLE GROUP #10

CONTROL WIRING

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

TM

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 43229

EXM47007

LIEBERT 480VAC EXM

B. SANBORN

B. SANBORN

J. SHIPMAN

12/06/2018

150 kVA

UPS EFFICIENCY

NOTES

1. NO LOAD POWER LOSS: 1.28 kW

ECO MODE

NORMAL MODE

DRAWN BY

SHEET NO.

ECN NO.

DATE REV. #

FILE NAME:

DWG. NO.

LIEBERT 480VAC EXM

MAINTENANCE BYPASS CABINET (300mm)

BASE DETAIL

ORDER NO.

I:\appl\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\I) Seismic & Base Details\EXM49005-01.dwg

EXM49005

1/31/18

J. SHIPMAN

J. SHIPMAN

590-1307-501C/SL-52646_REV11_6-17

LIEBERT® INTELLISLOT™

UNITY PLATFORM CARDS

Product Specification/Installation Guide

The Liebert IntelliSlot Unity Platform brings SNMP, BACnet IP, BACnet MSTP, Modbus TCP, Modbus RTU, YDN23 and Web management capability to many models of Vertiv’s power and cooling equipment. The cards employ Ethernet and RS-485 networks to monitor and manage a wide range of operating parameters, alarms and notifications. The card also supports communication for LIFE™ Services by VERTIV.

ADDITIONAL FEATURES

• SNMPv1, SNMPv2c and SNMPv3 with MIB-II support

• HTTP/HTTPS 1.1

• BootP

• DHCP per RFC2131/2132

• Remote firmware updates via a Web browser

• IPv6 support for HTTP/HTTPS, DHCPv6, e-mail, SMS, SNMP v1/v2c/ v3 and Modbus TCP

• Liebert SN Environmental Sensor Support (Web, SNMP, SMS and SMTP): Temperature, Humidity, Door Closure, Contact Closure and Leak Detection: Liebert SN-2D, Liebert SN-3C, Liebert SN-L, Liebert SN-T, Liebert SN-TH, Liebert SN-Z01, Liebert SN-Z02 and Liebert SN-Z03

IntelliSlot Unity cards are a form, fit, and function replacement for several Liebert IntelliSlot Web and 485 cards.

COMPATABILITY with Liebert Equipment

IntellSlot Card Compatible with

IS-UNITY-DP

IS-UNITY-SNMP

IS-UNITY-LIFE

Alber BDSU-50™

Liebert APM™

Liebert APS™

Liebert Challenger

3000™

Liebert CRV™

Liebert CW™

Liebert DCL™

Liebert DCP™

Liebert Deluxe System/3™

Liebert DS™

Liebert DSE™

Liebert EPM™

Liebert EXC™

Liebert eXL™

Liebert EXL™ S1

Liebert eXM™

Liebert FDC™

Liebert FPC™

Liebert GXT3™

Liebert GXT4™

Liebert HPC™

Liebert HPC-S/M/R/W/Generic™

Liebert HPM™

Liebert NX™ 225-600 kVA

Liebert NXC™

Liebert NXL™ *

Liebert NXR™

Liebert PCW™/PDX™

Liebert PeX™ *

Liebert PPC™

Liebert RDC™

Liebert RX™

Liebert XDC™

Liebert XDP™

Liebert XDP-Cray™

* YDN23 supported only for Liebert PeX and Liebert NXL.

VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.

590-1307-501C/SL-52646_REV11_6-17

LIEBERT® INTELLISLOT™ UNITY PLATFORM CARDS

Product Specification/Installation Guide

COMPATABILITY with Communication Protocols

Liebert IntelliSlot Card

Life Services Support

Communication Protocol

HTTP

HTTPS

Velocity Protocol

Email SMS SNMP v1, v2c, v3

BACnet IP BACnet MSTP

Modbus TCP Modbus RTU

YDN23*

IS-UNITY-DP

IS-UNITY-SNMP — — —

IS-UNITY-LIFE — — — —

* YDN23 supported only for Liebert PeX and Liebert NXL.

DIMENSIONS

SPECIFICATIONS

Power Requirements DC Inputs 7 to 12 VDC

Power Consumptions: 3.6 W maximum

Dimensions, W x D x H 2.97 x 5.2 x 1.45 in. (75.5 x 15 x 37 mm)

Weight (assembled) Net: 7 oz (0.2 kg)

Shipping: 1.3 lb (0.6 kg)

Ambient Operating Environment 32 to 104°F (0 to 40°C); 10% to 90% RH (non-condensing)

Ambient Storage Temperature –4 to 140°F (–20 to 60°C)

Communication Ports Ethernet Communication RJ-45 (LIFE™ Services requires a network connection to the Internet)

RJ-45 (RJ-45 to 2-position terminal-block adapter)

WIRING

10/100 Mb/s Ethernet connector Standard Category 5E Cable 328 ft. (100m)

RJ-45 - One-Wire Connector Liebert® Integrated One-Wire Sensor Cable or 2m Cat 5E to Modular 1-Wire

65.6 ft. (20m)

1/2” (11 mm)4-3/4” (121 mm)

2-3/8” (60.3 mm)

1-1/2” (38 mm)

3” (76 mm)

Front face

Board

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-05-S001

2/14/2019

LOGAN JOHNSON1 OF 9

MIKE OLLER

TM

FORM NO. DPN004658 Rev0

36.1"

36.7"

933 DISPLAY

81.5"

85.6"

41.4"

OPTIONAL EZ-VIEW

DOORS

OUTLINE DRAWING

SINGLE AND NO MICB

150-300KVA

LIEBERT TFX

OPTIONAL DISPLAY

NOTES:

1. ALL DIMENSIONS ARE IN INCHES [MM].

2. COOLING CLEARANCES

FRONT: FOR UNITS WITH VOLTAGES UNDER 150V TO GROUND

A MINIMUM OF 36" [914MM] IS REQUIRED FOR SERVICE ACCESS

FOR UNITS WITH VOLTAGES OVER 150V TO GROUND REQUIRE 42" [1067MM]

PER NEC 110.26.

REAR: A MINIMUM OF 6" [152.4MM] IS REQUIRED.

ONE SIDE: A MINIMUM OF 6" [152.4MM] IS REQUIRED ON ONE SIDE OF THE

TRANSFORMER CABINET.

IF LIEBERT FLX CABINETS ARE ATTACHED, REFER TO TFX-04-SXXX

FOR CLEARANCE CLARIFICATIONS.

3. KEEP CABINET WITHIN 15v OF VERTICAL.

4. ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.

5. UNIT IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.

FRONT VIEWLEFT VIEW RIGHT VIEW

in-lb Nm in-lb Nm in-lb Nm

10-32 (M5) 8 25 3 - - 62 7

1/4-20 (M6) 10 53 6 40 4.5 80 9

5/16-18 (M8) 13 107 12 90 10 180 20

3/8-16 (M10) 17 192 22 120 13.5 240 27

1/2-13 (M12) 19 428 48 480 54 - -

GRADE 5 - IMPERIAL

GRADE 8.8 - METRIC

ELECTRICAL

CONNECTIONS WITH 1

BELLEVILLE WASHERS

ELECTRICAL

CONNECTIONS WITH 2

BELLEVILLE WASHERS

BOLT SHAFT SIZE

HEX HEAD SIZE

(MM)

Document generated 24 March 2023 05:48 PM (EST).

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-01-S002

5/13/2019

LOGAN JOHNSON1 OF 1

ONE-LINE DIAGRAM

SINGLE MAIN INPUT CIRCUIT BREAKER (MICB) OPTION

LIEBERT TFX SYSTEM

SINGLE MICB CONFIGURATION

3W + G

ISOLATION

TRANSFORMER

INPUT

LIGHTNING/SURGE

ARRESTOR

(OPTIONAL)

OUTPUT

SPIKE

SUPPRESSION

MODULE

(OPTIONAL)

D

IS

T R

IB

U

T

IO

N B

U

S INTERNAL

DISTRIBUTION

(OPTIONAL)

ATTACHED

LIEBERT FLX

CABINETS

(OPTIONAL)

NOTES:

1. ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL

AND LOCAL ELECTRICAL CODES.

2. INPUT AND OUTPUT FEEDERS CAN BE THROUGH THE

TOP AND/OR BOTTOM OF THE LIEBERT TFX

TRANSFORMER CABINET.

3. CONTROL WIRING AND POWER WIRING MUST BE RUN

IN SEPERATE CONDUITS.

4. THE MICB UTILIZES A 24VDC SHUNT TRIP FOR EPO

CIRCUITRY. THE LOCAL EPO BUTTON CAN BE REMOVED

AT THE FACTORY

MAIN INPUT

CIRCUIT BREAKER

FIELD SUPPLIED WIRING

Document generated 24 March 2023 05:48 PM (EST).

BrandonSanchez Callout

(5) 250A LSI Breakers

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-05-S001

2/14/2019

LOGAN JOHNSON4 OF 9

VOLTAGE TEST POINTS

LOW VOLTAGE

MONITORING BOARDS

HIGH VOLTAGE

MONITORING BOARDS

HIGH VOLTAGE

POWER SUPPLY BOARDS

MAIN COMPONENTS

SINGLE AND NO MICB

150-300KVA

LIEBERT TFX

OPTIONAL

SINGLE

MICB

AUXILIARY

DISTRIBUTION SECTION

OPTIONAL

SINGLE

MICB

AUXILIARY

DISTRIBUTION SECTION

DISTRIBUTION SECTION 2

DISTRIBUTION SECTION 1

FRONT VIEW

DPM, TRANSFORMER & DISTRIBUTION

MONITORING OPTION

FRONT VIEW

NO MONITORING & DPM

TRANSFORMER MONITORING ONLY

(SEE NOTE 1)

DISTRIBUTION SECTION 3

(SEE NOTE 1)

NOTES:

1. DISTRIBUTION SECTION #3 IS ONLY AVAILABLE ON

UNITS WITHOUT DISTRIBUTION MONITORING.

HIGH VOLTAGE PCB FUSES

DISTRIBUTION SECTION 1

DISTRIBUTION SECTION 2

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-05-S001

2/14/2019

LOGAN JOHNSON5 OF 9

54.5"

GROUND

57.9"

NEUTRAL

73.9"

MICB BUSSING

NOTES:

1. ALL DIMENSIONS ARE IN INCHES [MM]

2. REFER TO BREAKER MANUFACTURER SUBMITTAL (TFX-03-XXXX)

FOR BREAKER AND PANELBOARD TERMINATION RECOMMENDATIONS.

3. FASTENING HARDWARE IS SUPPLIED BY OTHERS/INSTALLING CONTRACTOR.

15.2"

MICB BUSSING

29.4"

NEUTRAL

32.9"

GROUND

DETAIL B

GROUND BUSBAR

DETAIL A

MAIN INPUT CB

BUSBARS

O .56"

2.05"

1.75"

O .56"

1.75"

A

B

ELECTRICAL CONNECTIONS

SINGLE AND NO MICB

150-300KVA

LIEBERT TFX

2.00"

DETAIL C

NEUTRAL BUSBAR

1.89"

1.75"

O .56"

C

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-05-S001

2/14/2019

LOGAN JOHNSON6 OF 9

NOTES:

1. ALL DIMENSIONS ARE IN INCHES [MM]

2. REFER TO BREAKER MANUFACTURER SUBMITTAL (TFX-03-XXXX)

FOR BREAKER AND PANELBOARD TERMINATION RECOMMENDATIONS.

3. THIS DRAWING IS INTENDED FOR INSTALLER USE ONLY. IT IS INTENDED

TO SHOW THE POTENTIAL DISTRIBUTION OPTIONS WITHIN THE

TRANSFORMER CABINET. YOUR CONFIGURATION MAY HAVE A MIX OF

DISTRIBUTION OPTIONS. USE THE DIMENSIONS PROVIDED TO ESTIMATE

WIRING REQUIREMENTS.

11.6"

TYP

4.4"

14.5"

18.2"

68.6"

40.3"

55.3"

30.3"

ELECTRICAL CONNECTIONS - SUBFEEDS

SINGLE AND NO MICB

150-300KVA

LIEBERT TFX

28.0"

28.0"

SUBFEED DISTRIBUTION USING

250AF BREAKERS

SUBFEED DISTRIBUTION USING

400/600AF BREAKERS

66.93"

66.93"

MICB

OPTIONAL

MICB

OPTIONAL

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-05-S001

2/14/2019

LOGAN JOHNSON7 OF 9

12.9"

12.8"

66.9"

28.1"

66.9"

32.2"

3 PANELBOARD DISTRIBUTION

15.6"

15.6"

32.1"

67.0"

ELECTRICAL CONNECTIONS - PANELBOARDS

SINGLE AND NO MICB

150-300KVA

LIEBERT TFX

PANELBOARD DISTRIBUTION

66.9"

28.1"

NOTES:

1. ALL DIMENSIONS ARE IN INCHES [MM]

2. REFER TO BREAKER MANUFACTURER SUBMITTAL (TFX-03-XXXX)

FOR BREAKER AND PANELBOARD TERMINATION RECOMMENDATIONS.

3. THIS DRAWING IS INTENDED FOR INSTALLER USE ONLY. IT IS INTENDED

TO SHOW THE POTENTIAL DISTRIBUTION OPTIONS WITHIN THE

TRANSFORMER CABINET. YOUR CONFIGURATION MAY HAVE A MIX OF

DISTRIBUTION OPTIONS. USE THE DIMENSIONS PROVIDED TO ESTIMATE

WIRING REQUIREMENTS.

MICB OPTIONAL

MICB OPTIONAL

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-05-S001

2/14/2019

LOGAN JOHNSON8 OF 9

POWER INPUT/OUTPUT

CONDUIT PLATE

POWER INPUT/OUTPUT CONDUIT PLATE

(SEE NOTE 3, 4)

COMMUNICATIONS CONDUIT PLATE

(SEE NOTE 3)

VENTILATION PLATE

(SEE NOTE 2)

4.1"

103 TYP

TOP CONDUIT PLATE DETAILS

SINGLE AND NO MICB

150-300KVA

LIEBERT TFX

NOTES:

1. ALL DIMENSIONS ARE IN INCHES [MM].

2. VENTILATION PLATE MUST NOT BE USED AS A CONDUIT LANDING AREA.

3. REMOVE CONDUIT PLATE, PUNCH TO SUIT AND REPLACE.

4. CONDUIT PLATE CAN ACCOMODATE UP TO:

A. (3) 2.5" CONDUITS FOR INPUT, (12) 4" CONDUITS FOR SUBFEED BREAKERS.

B. (2) 4" CONDUITS FOR INPUT, (12) 3.5" AND (2) 2.0-2.5" CONDUITS FOR

SUBFEED BREAKERS.

C. WHEN A PANELBOARD IS CONFIGURED, THE CONDUIT PLATE WILL HAVE

PRE-PUNCHED CONDUIT KNOCKOUTS WITH A MIXTURE OF 1/2" KO'S AND

3/4" KO'S AND A PUNCH AREA FOR INPUTS AND OUTPUT SUBFEED BREAKERS.

ISO VIEW

TOP VIEW

FRONT VIEW

23.78"

25.98"

12.80"

3.41"

1.7" 431.4"

1.4"

6.8"

15.9"

HIGH VOLTAGE

TEST POINT BOARD

LOW VOLTAGE

MONITORING BOARD

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-05-S001

2/14/2019

LOGAN JOHNSON9 OF 9

BOTTOM CONDUIT PLATE DETAILS

SINGLE AND NO MICB

150-300KVA

LIEBERT TFX

FRONT VIEW

BOTTOM VIEW

9.1"

5.0"

26.3"

18.5" 4709.1"

5.0"

3.9"

2.4"

LOW VOLTAGE

CONDUIT

NOTES:

1. ALL DIMENSIONS ARE IN INCHES [MM].

2. VENTILATION PLATE MUST NOT BE USED AS A CONDUIT LANDING AREA.

3. REMOVE CONDUIT PLATE, PUNCH TO SUIT AND REPLACE.

4. CONDUIT PLATE MUST BE INVERTED (AS SHOWN)PRIOR TO ENERGIZING

THE PDU, EVEN IF BOTTOM INPUT IS NOT UTILIZED.

5. CONDUIT PLATE CAN ACCOMODATE UP TO:

A. (3) 2.5" CONDUITS FOR INPUT, (12) 4" CONDUITS FOR SUBFEED BREAKERS.

B. (2) 4" CONDUITS FOR INPUT, (12) 3.5" AND (2) 2.0-2.5" CONDUITS FOR

SUBFEED BREAKERS.

C. WHEN A PANELBOARD IS CONFIGURED, THE CONDUIT PLATE WILL HAVE

PRE-PUNCHED CONDUIT KNOCKOUTS WITH A MIXTURE OF 1/2" KO'S AND

3/4" KO'S AND A PUNCH AREA FOR INPUTS AND OUTPUT SUBFEED BREAKERS.

D. IN ADDITION TO THE ABOVE: (2) 9.1" ARE AVAILABLE IN SIDE FRAME WHICH

CAN BE USED WHEN CABLE PULLING IS NOT NEEDED.

7.5"

TYP

1.5"

NOTE 3, 4, 5

7.2"

TYP

1.7"

TYP

.9"

2.6"

VENTILATION PLATES

(SEE NOTE 2)

FRONT

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-10-S001

5/16/2019

LOGAN JOHNSON1 OF 2

IR SCAN PORT OPTION

150-300kVA TRANSFORMER CABINET

LIEBERT TFX

IR SCAN PORT OFFERS VIEWING TO

TRANSFORMER CONNECTION BUS STABS

IR SCAN PORT OFFERS VIEWING TO

PHASE A, B ,C, GROUND, NEUTRAL BUSBARS,

AND MICB CUSTOMER CONNECTIONS

FRONT VIEW

TRANSFORMER CABINET

LEFT SIDE VIEW

TRANSFORMER CABINET

REAR VIEW

TRANSFORMER CABINET

NOTES:

1. DASHED TRIANGLES REPRESENT SMALLEST POSSIBLE VIEWING ANGLE.

2. THIS OPTION PROHIBITS THE USE OF LEFT SIDE MOUNTED LIEBERT

FLX CABINETS.

3. VIEWING CLEARANCE REQUIREMENTS:

LEFT SIDE: 36" [914.4MM] MINIMUM.

TOP: 18" [457.2MM] MINIMUM (36" [914.4MM] RECOMMENDED)

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-10-S001

5/16/2019

LOGAN JOHNSON2 OF 2

IR SCAN PORT OPTION

150-300kVA TRANSFORMER CABINET

LIEBERT TFX

IR SCAN PORT OFFERS VIEWING TO MICB,

PHASE A, B ,C, GROUND, AND NEUTRAL BUSBARS

RIGHT SIDE VIEW

TOP VIEW

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

FLX-10-S001

2/14/2019

LOGAN JOHNSON1 OF 1

IR SCAN PORT OPTION

FLX12A CABINETS

LIEBERT FLX

IR SCAN PORT OFFERS VIEWING TO

CUSTOMER/LOAD SIDE CONNECTIONS

FRONT VIEW

FLX12A CABINET WITH (4) 250 AMP FRAME

BREAKERS MAX

IR SCAN PORT OFFERS VIEWING TO

CUSTOMER/LOAD SIDE CONNECTIONS

FRONT VIEW

FLX12A CABINET WITH (3) 600 AMP FRAME

BREAKERS MAX

SIDE VIEW

600 AMP FRAME IR PORT VIEWING AREA (TYP)

SIDE VIEW

250 AMP FRAME IR PORT VIEWING AREA (TYP)

A

A

SECTION A-A

B

B

SECTION B-B

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-19-S010

5/22/2019

LOGAN JOHNSON1 OF 1

CABLE LAYOUT

CUSTOMER CABLE ROUTING

LIEBERT TFX

LOW VOLT

WIRING TROUGH

BOTTOM OPENING

LOW VOLTAGE

WIRING TROUGH

TOP OPENING

LOW VOLTAGE

WIRING TROUGH

TOP VIEW

TRANSFORMER CABINET

TEST POINT

BOARD

(NO CUSTOMER

CONNECTIONS)

MICI BOARDS

(NO CUSTOMER

CONNECTIONS)

EXTERNAL INTERFACE

BOARD

COMM SLOT 1

CUSTOMER

PROVIDED

CABLE

LOW VOLTAGE

WIRING AREA

COMM SLOT 2

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-19-S050

5/21/2019

LOGAN JOHNSON1 OF 1

CONTROL WIRING

CABLE GROUP #1, EPO/REPO CIRCUITRY

LIEBERT TFX

TB1

TB3

TB4

EXTERNAL EPO (REPO)

EXTERNAL INTERFACE BOARD

NOTES:

1. ALL SWITCHING DEVICES ARE TO BE SUITABLE FOR SWITCHING

LOW CURRENT 24 VDC. MINIMUM RECOMMENDED WIRE SIZE IS

18 AWG STRANDED COPPER WITH 300 VOLT INSULATION. ALL

WIRING AND DEVICES ARE FIELD SUPPLIED EXCEPT WHERE NOTED.

SEE INSTALLATION MANUAL FOR DETAILED INSTALLATION PROCEDURES.

2. LOW VOLTAGES TERMINAL STRIP IS LOCATED IN THE OPTIONAL LOW VOLTAGE CONTROL

JUNCTION BOX.

3. THE TOTAL LOAD ON THE 24 VDC SUPPLY (BOTH N.O. AND N.C. REPO CIRCUITS)

MUST BE LIMITED TO 1 AMP.

4. MULTIPLE NORMALLY OPEN (N.O.) REPO SWITCHES MAY BE PARALLELED

MULTIPLE NORMALLY CLOSED (N.C.) REPO SWITCHES MAY BE CONNECTED IN

SERIES. ALL LAMPS (IF USED) ARE CONNECTED IN PARALLEL.

5. SEE CABLE LAYOUT SUBMITTAL (TFX-19-S0XX) FOR EXTERNAL INTERFACE

BOARD LOCATION.

6. USE 28-16 AWG WITH A MAXIMUM LENGTH OF 1,000 FEET (300 M)

EPO POWER 1

EPO GROUND 3

EPO NC 5 EPO NO 5

EPO GROUND 3

EPO POWER 1

TBI

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 432290

TFX-19-S051

5/21/2019

LOGAN JOHNSON1 OF 1

CONTROL WIRING

CABLE GROUP #2, CUSTOMER ALARMS

LIEBERT TFX

TB1

TB3

TB4

CUSTOMER OUTPUT

ALARMS

CUSTOMER INPUT

ALARMS

EXTERNAL INTERFACE BOARD

NOTES:

1. ALL SWITCHING DEVICES ARE TO BE SUITABLE FOR SWITCHING

LOW CURRENT 24 VDC. MINIMUM RECOMMENDED WIRE SIZE IS

18 AWG STRANDED COPPER WITH 300 VOLT INSULATION. ALL

WIRING AND DEVICES ARE FIELD SUPPLIED EXCEPT WHERE NOTED.

SEE INSTALLATION MANUAL FOR DETAILED INSTALLATION PROCEDURES.

2. LOW VOLTAGES TERMINAL STRIP MAY BE LOCATED IN THE OPTIONAL

LOW VOLTAGE CONTROL JUNCTION BOX.

3. CUSTOMER LARMS 1 THROUGH 4 ARE NORMALLY OPEN (INDICATES ALARM ON

CONTACT CLOSURE). CUSTOMER ALARM 5 IS NORMALLY CLOSED (INDICATES

ALARM ON CONTACT OPENING).

4. SEE CABLE LAYOUT SUBMITTAL (TFX-19-S0XX) FOR HMI INTERFACE

BOARD LOCATION.

COM-4

INPUT FORM A/B-3

INPUT FORM A/B-1

COM-2

ALARM 2 N/O-5

ALARM 2 N/C-3

ALARM 2 COM-1ALARM 1 COM-1

ALARM 1 N/C-3

ALARM 1 N/O-5

TB3

TB4

Vertiv™ Liebert® Intellislot RDU101 Communications Card

The Liebert® Intellislot RDU101 card enables communication between Vertiv™ products such as Trellis™ Enterprise, Trellis™ Power Insight and LIFE™ Services. It provides web access, data via SNMP and Modbus TCP for Vertiv equipment. Environmental sensor data access is provided via web and SNMP.

Benefits:

y Quick, real-time view of parametric data and system statuses.

y Prompt alarm notification for fast event resolution.

y Know environmental conditions of your data center for informed, efficient decision making.

y Flexible communication regardless of device protocol.

y Peace of mind knowing data is transported in a secure manner.

y Save time configuring and updating firmware on managed devices.

Overview How It Works

The RDU101 employs Ethernet networks to monitor and manage a wide range of operating parameters, alarms and notifications.

Solving Problems

Managing disparate systems within the data center can be challenging. With responsibilities to know the conditions of your facility at all times, keeping track of all that data may require accessing multiple systems or even performing manual, time consuming data tracking. Being able to collect data from your systems is key to effectively managing the data center. The RDU101 provides remote centralized monitoring connectivity to building management systems (BMS) that use SNMP.

Adding Value

Not only does the RDU101 improve efficiency by providing a one-to-one view of the connected system, it also provides a convenient way to configure and update devices via HTTP APIs. Save time on initial deployments and improve ongoing maintenance through the mass configuration capabilities of the RDU101.

Keep Data Secure

The RDU101 keeps data secure. Basic security is provided via HTTPS web connectivity and SNMP v3. Centralized access and authorization management provides an additional layer of security via remote authentication protocols – RADIUS, TACACS+, LDAP/AD and Kerberos.

Features y Provides web access to the installed devices via popular web browsers- Microsoft Internet Explorer, Mozilla Firefox, Google Chrome and Safari.

y Provides alarm notifications via email and text messaging.

y Supports environmental monitoring via Liebert SN Sensors for temperature, humidity, leak detection, doors and contact closures.

y Supports third-party protocols for building and network management applications for status and alarms via SNMP and Modbus TCP.

y Enables Vertiv software tools and services, including Trellis™ Enterprise, Trellis™ Power Insight and LIFE Services.

y Supports high-speed file transfer to managed devices for firmware and configuration updates.

y HTTPS messages and web access encryption with installable customer provided certificates.

y Options for SNMP v3 authentication support (none, MD5 or SHA), privacy support (none, DES or AES) and Traps.

SL-31322 (R01/20)

Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA

© 2020 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications, rebates and other promotional offers are subject to change at Vertiv’s sole discretion upon notice.

Vertiv™ Liebert® Intellislot RDU101 Communications Card

Technical Specifications

Power Requirements DC Input

Power Consumption

7 to 12 VDC

3.6 W maximum

Dimensions, W x D x H 2.97 x 5.2 x 1.45 in. (75.5 x 15 x 37 mm)

Weight (assembled) Net:

Shipping:

7 oz (0.2 kg)

1.3 lb (0.6 kg)

Ambient Operating Environment 32 to 104°F (0 to 40°C), 10% to 90% RH (non-condensing)

Ambient Storage Temperature -4 to 140° F (-20 to 60°C)

Communication Ports Ethernet Communication

RJ-45

Wiring

10/100 Mb/s Ethernet Connector Standard Category 5E Cable 328 ft. (100m)

RJ-45 - One-Wire Connector Liebert® Integrated One-Wire Sensor Cable or 2m Cat 5E to Modular 1-Wire

65.6 ft. (20m)

PS519338EN page 1 October 5, 2022 9:02 AM

Project Catalog # Type

Prepared by Notes Date

Interactive Menu

• Order Information page 2

• Photometric Data page 3

• Connected Systems page 3

• Product Warranty

SNLED Base

LED Striplight

Typical Applications

Commercial • Industrial • Retail • Residential • Storage / Utility • Coves • Display Cases • Shops • Task and General Area Lighting

Top Product Features

• Standard (SL) and High lumen/High Efficacy (HL) packages

• High efficiencies - up to 153 LPW

• Three different lens types for optical control

• Two different reflectors for precise distribution control

• Available CCT: 3000K, 3500K, 4000K and 5000K

• Minimum CRI of 80; 90 CRI available

• Options to meet Trade Agreements Act requirements

Dimensional Details 2-11/16" [68mm]

1-15/16" [50mm]

1-25/32" [46mm]

2-1/4" [58mm]

2-7/8" [73mm]

24" [609mm] 2-1/2" [64mm]

14" [355mm]

Ceiling Stand-off Embossments

Hole for Toggle

2'

96" [2437mm]

K.O (2) 7/8" [22mm]

K.O (2) 7/8" [22mm]

Hole for Toggle

26-3/4" [680mm] 5" [127mm]

Ceiling Stand-off Embossments

2-1/2" [64mm]

8'

2-7/8" [73mm]

2-7/8" [73mm]

48" [1219mm] 38" [965mm]

Ceiling Stand-off Embossments

2-7/8" [73mm]

K.O (3) 7/8" [22mm]

Hole for Toggle

4'

2-1/2" [64mm]

ZW-SWPD3 Sidecar

Product Certification

Product Features

Designed to provide safe and convenient means of disconnecting power http://www.cooperlighting.com https://www.cooperlighting.com/global/brands/mws.html https://www.cooperlighting.com/global/resources/programs/rapid-response

SNLED Base

PS519338EN page 2 October 5, 2022 9:02 AM

Order Information

SAMPLE ORDER NUMBER: 4SNLED-LD5-48SL-UNV-L840-U

Domestic Preferences Length Series Lamp Type Lumen Package Voltage Options

Domestic Preferences (1) Length Series Lamp Type Lumen Package Voltage Options

[Blank]=Standard TAA=Trade Agreements Act

2=2' Length 4=4' Length 8T=8' Length

SNLED=

Commercial LED Striplight (2)(2)

LD5=LED 5.0 Stocked Lumen Packages

24SL (3)

28SL (3)

32SL

48SL

80SL

88SL

MTO Lumen Packages

20SL (3)

36SL

37HL

40SL

44SL

52SL

56SL

56HL

60SL

60HL

64SL

64HL

68SL

72SL

85HL

96SL

104SL

112SL (5)

130HL (5)

170HL (4)

UNV=Universal Voltage 120-277 347V=347V 480V=480V (6)

Emergency EL7W=7-watt, 120V-277V emergency battery pack installed (7), (9)

EL14W=14-watt 120V-277V emergency battery pack installed (7), (9)

GTR2=Bodine Generator Transfer Relay (10)

ETRD=Iota Emergency Transfer Relay with dimming control (10)

Wiring PI/CPI=Plug in and cross over plug in options (12)

PC6/515P=(NEMA 5-15P) 6' Cord with NEMA Straight Plug (11), (12)

PC6/L715=(NEMA L7-15P) 6' Cord with NEMA Twist Plug (11), (12)

Motion Sensors (13)

LB-ERMS360=360° Low Bay Motion Sensor - End of Row LB-MRMS360=360° Low Bay Motion Sensor - Middle of Row HB-ERMS360=360° High Bay Motion Sensor - End of Row (8)

HB-MRMS360=360° High Bay Motion Sensor - Middle of Row (8)

CCT / CRI

L830=3000K, 80 CRI

L835=3500K, 80 CRI

L840=4000K, 80 CRI

L850=5000K, 80 CRI

L930=3000K, 90 CRI

L935=3500K, 90 CRI

L940=4000K, 90 CRI

L950=5000K, 90 CRI

ZW-SWPD3=WaveLinx Wireless Sensor, Sidecar mount, with 1200 sq ft.

coverage (14)

WLS4=WaveLinx Lite Wireless Integrated Sensor, 15'–40' Mounting Height (14), (15)

Notes Notes Notes Notes Notes

(1) Only product configurations with this designated prefix are built to be compliant with the Trade Agreements Act of 1979 (TAA). Please refer to DOMESTIC PREFERENCES website for more information. Components shipped separately may be separately analyzed under domestic preference requirements.

(2) DesignLights Consortium® Qualified and classified for both DLC Standard and DLC Premium, refer to www.

designlights.org for details.

(3) Available in 2 ft. and 4 ft. (4) Requires two drivers. (5) DALI and Step-dim versions require two drivers.

(6) 4 ft. and 8

ft. only.

(7) 4 ft. and 8 ft. only. (8) Motion Sensor offers dimmability. (9) With integral test switch/ indicator/laser test. For approximate delivered lumens multiply the lumens per watt of the desired fixture by the wattage of the emergency battery pack (100 lm/W x 7=700 lumens). IES-format photometry for luminaire under emergency operation available. (10) Used to bypass local control during outage. Must be used in conjunction with UL 1008 device (provided by others). GTR2 option includes 2 relays on fixtures with dimming drivers. ETRD option only requires one relay when used on a dimming fixture. Must specify voltage as 120V or 277V when ordering these devices. (11) Most common C&P shown. Must specify location for cord. All “end” locations will be on the end with sensor installed. (12) Consult tech support on numerous options for this feature. (13) Sensors provided in separate externally mounted enclosure. See SRL spec sheet for fully integrated/connected sensors. (14) Not compatible with EL options. Not available with 347V, 480V, or UNC. Not available with 5LTD option. End row mounting only. (15) WaveLinx Lite devices are not currently compatible with the WaveLinx Pro Wireless Area Controller.

Driver Type Number of Drivers Packaging Accessories

Drive Type Number of Drivers Packaging Accessories (order separately) (18)

CD=0-10V Dimming Driver (10% - 100% Dimming) HCD=0-10V Dimming Driver (1% - 100% Dimming) SD=Step-dim (Bi Level) (16)

5LTD=Fifth Light (DALI) Driver (16), (17)

1=1 Driver 2=2 Drivers

U=Unit Pack (Order Separately) AYC-Chain/Set=36” Chain Hanger (Use 1 set per fixture) SCF=Fixed Stem Set (Specify Length) SCS=Swivel Stem Set (Specify Length) SCA=Adjustable 48” Stem Set EYE-CHAIN/SET-B=Eye Bolt Chain (Use 1 set per fixture) WG/SNF-2FT=2’ Wire Guard WG/SNF-4FT=4’ Wire Guard A1B/Spacer-U=Spacer 1-1/2” to 2-1/2” from ceiling (Use 2 per fixture) TOGGLE=Single Toggle No. 2 (Specify Length) Y-TOGGLE- -2PK=(2) Y-Toggle Cable Kits (Specify 10 or 30 for length in feet) SNLED-LENS-LW-2FT-U=Replacement Lens 2 ft, Full Frost SNLED-LENS-LN-2FT-U=Replacement Lens 2 ft, Semi Frost SNLED-LENS-LC-2FT-U=Replacement Lens 2 ft, Clear SNLED-LENS-LW-4FT-U=Replacement Lens 4 ft, Full Frost SNLED-LENS-LN-4FT-U=Replacement Lens 4 ft, Semi Frost SNLED-LENS-LC-4FT-U=Replacement Lens 4 ft, Clear GRP-SNF-U=Gripper Hanger CLC-SNLED-EXT-B=SNLED Long Row Aligner Extension

Notes Notes

(16) 4 ft. and 8 ft. only. (17) For a complete listing of Fifth Light products, visit www.cooperlighting.com

(18) Accessories sold separately will be separately analyzed under domestic preference requirements. Consult factory for further information.

https://www.cooperlighting.com/global/resources/programs/domestic-preferences

PS519338EN page 3 October 5, 2022 9:02 AM

Product Specifications Construction

• Die-formed of cold rolled steel with numerous knockouts for easy installation

• Groove for Tong Hanger

• Convertible end plate for continuous row alignment

• Channel/wireway cover secured with sheet metal screws

• Surface, pendant or stem mounting

Controls

• 0-10V dimming drivers to 10% or to 1% options

• Combine with energy-saving products like occupancy sensors, daylighting controls and lighting relay panels to maximize energy savings

• For motion control, reference options for both end and middle of the row applications

• Step-dimming option

• Fifth Light DALI 2.0 driver option

Electrical

• Long-life LED system with electrical driver for optimal performance

• LED’s available in 3000K, 3500K, 4000K or 5000K with CRI of 80 standard or optional 90 CRI

• TM21 rating up to L87 >60,000 hours

• Electronic drivers available for 120-277V, 347V and 480 applications

• Operating temperature of -20°C to 40°C; Ideal for cold storage environments

Emergency Battery Pack Option

• Optional 120V-277V integral emergency battery pack available in 7W or 14W

• 90-minute backup period for code compliance

• Test switch with laser pointer allows safe testing from floor

• Patented EZ Key prevents accidental discharge during construction

• Generator transfer options available

Compliance

• cULus Listed for damp locations

• RoHS compliant

• Complies with IESNA LM-79 and LM-80 standards

• NEMA 410 compliant (drivers)

• State of California Title 24 high efficacy luminaire

• DesignLights Consortium® Qualified and classified for DLC Standard and DLC Premium (refer to www.designlights.org)

• Suitable for closet use when installed to NEC

410.16 spacings standards

Warranty

• Five year warranty

Photometric Data

View IES files

WaveLinx Lite devices are not currently compatible with the WaveLinx Pro Wireless Area Controller

Control Systems

• WaveLinx Wireless

• WaveLinx Wired

• WaveLinx Lite http://www.designlights.org http://www.cooperindustries.com/content/dam/public/lighting/about%20us/terms_and_conditions/Lighting-Division-TC-Matrix.pdf https://www.cooperlighting.com/global/brands/metalux/snled-series.html https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wired https://www.cooperlighting.com/global/brands/wavelinx/lite https://www.cooperlighting.com/global/controls-wiring/building-systems

Cooper Lighting Solutions 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.cooperlighting.com

© 2022 Cooper Lighting Solutions All Rights Reserved.

Specifications and dimensions subject to change without notice.

PS519338EN page 4 October 5, 2022 9:02 AM

Energy and Performance Data

CRI

Lumen multiplier (80CRI to 90CRI)

3000K 3500K 4000K 5000K

0.805 0.840 0.846 0.901

CCT Table

Approximate Color Temperature Multiplier

2700K .93

3000K .98

3500K 1.0

4000K 1.02

5000K 1.02

Shipping Data

Length Wt.

2 ft. 3.8 lbs.

4 ft. 7.2 lbs.

8 ft. 13.1 lbs.

SNELD

Type

Lumen Type Length Catalog Number

Nominal 3500K Lumens Wattage Im/W

Base Standard 2 ft. 2SNLED-LD5-20SL-UNV-L8XX-CD1-U 2005 14 140.5

Base Standard 2 ft. 2SNLED-LD5-24SL-UNV-L8XX-CD1-U 2476 18 136.8

Base Standard 2 ft. 2SNLED-LD5-28SL-UNV-L8XX-CD1-U 2810 21 132.1

Base High 2 ft. 2SNLED-LD5-37HL-UNV-L8XX-CD1-U 3799 27 143.0

Base Standard 4 ft. 4SNLED-LD5-20SL-UNV-L8XX-CD1-U 1934 13 148.4

Base Standard 4 ft. 4SNLED-LD5-24SL-UNV-L8XX-CD1-U 2398 16 149.8

Base Standard 4 ft. 4SNLED-LD5-28SL-UNV-L8XX-CD1-U 2761 18 149.7

Base Standard 4 ft. 4SNLED-LD5-32SL-UNV-L8XX-CD1-U 3148 21 148.7

Base Standard 4 ft. 4SNLED-LD5-36SL-UNV-L8XX-CD1-U 3649 25 146.6

Base Standard 4 ft. 4SNLED-LD5-40SL-UNV-L8XX-CD1-U 4014 28 144.9

Base Standard 4 ft. 4SNLED-LD5-44SL-UNV-L8XX-CD1-U 4367 31 142.9

Base Standard 4 ft. 4SNLED-LD5-48SL-UNV-L8XX-CD1-U 4827 35 139.9

Base Standard 4 ft. 4SNLED-LD5-52SL-UNV-L8XX-CD1-U 5167 38 137.4

Base Standard 4 ft. 4SNLED-LD5-56SL-UNV-L8XX-CD1-U 5604 41 136.4

Base Standard 4 ft. 4SNLED-LD5-60SL-UNV-L8XX-CD1-U 6015 46 130.4

Base Standard 4 ft. 4SNLED-LD5-64SL-UNV-L8XX-CD1-U 6504 52 125.9

Base Standard 4 ft. 4SNLED-LD5-68SL-UNV-L8XX-CD1-U 6781 55 123

Base High 4 ft. 4SNLED-LD5-56HL-UNV-L8XX-CD1-U 5634 37 152

Base High 4 ft. 4SNLED-LD5-60HL-UNV-L8XX-CD1-U 5894 39 150.9

Base High 4 ft. 4SNLED-LD5-64HL-UNV-L8XX-CD1-U 6421 43 148.9

Base High 4 ft. 4SNLED-LD5-85HL-UNV-L8XX-CD1-U 8471 62 136.3

Base Standard 8 ft. 8TSNLED-LD5-64SL-UNV-L8XX-CD1-U 6296 42 147.8

Base Standard 8 ft. 8TSNLED-LD5-72SL-UNV-L8XX-CD1-U 7298 50 146.6

Base Standard 8 ft. 8TSNLED-LD5-80SL-UNV-L8XX-CD1-U 8028 55 144.9

Base Standard 8 ft. 8TSNLED-LD5-88SL-UNV-L8XX-CD1-U 8734 61 142.9

Base Standard 8 ft. 8TSNLED-LD5-96SL-UNV-L8XX-CD1-U 9654 69 139.9

Base Standard 8 ft. 8TSNLED-LD5-104SL-UNV-L8XX-CD1-U 10334 75 137.4

Base Standard 8 ft. 8TSNLED-LD5-112SL-UNV-L8XX-CD1-U 11208 82 136.4

Base High 8 ft. 8TSNLED-LD5-130HL-UNV-L8XX-CD1-U 12842 86 148.9

Base High 8 ft. 8TSNLED-LD5-170HL-UNV-L8XX-CD2-U 16942 124 136.3

*Stocked in either 3500K or 4000K. Check Flash for stock availability.

PS519338EN page 1 October 5, 2022 9:02 AM

Project Catalog # Type

Prepared by Notes Date

Interactive Menu

• Order Information page 2

• Photometric Data page 3

• Connected Systems page 3

• Product Warranty

SNLED Base

LED Striplight

Typical Applications

Commercial • Industrial • Retail • Residential • Storage / Utility • Coves • Display Cases • Shops • Task and General Area Lighting

Top Product Features

• Standard (SL) and High lumen/High Efficacy (HL) packages

• High efficiencies - up to 153 LPW

• Three different lens types for optical control

• Two different reflectors for precise distribution control

• Available CCT: 3000K, 3500K, 4000K and 5000K

• Minimum CRI of 80; 90 CRI available

• Options to meet Trade Agreements Act requirements

Dimensional Details 2-11/16" [68mm]

1-15/16" [50mm]

1-25/32" [46mm]

2-1/4" [58mm]

2-7/8" [73mm]

24" [609mm] 2-1/2" [64mm]

14" [355mm]

Ceiling Stand-off Embossments

Hole for Toggle

2'

96" [2437mm]

K.O (2) 7/8" [22mm]

K.O (2) 7/8" [22mm]

Hole for Toggle

26-3/4" [680mm] 5" [127mm]

Ceiling Stand-off Embossments

2-1/2" [64mm]

8'

2-7/8" [73mm]

2-7/8" [73mm]

48" [1219mm] 38" [965mm]

Ceiling Stand-off Embossments

2-7/8" [73mm]

K.O (3) 7/8" [22mm]

Hole for Toggle

4'

2-1/2" [64mm]

ZW-SWPD3 Sidecar

Product Certification

Product Features

Designed to provide safe and convenient means of disconnecting power http://www.cooperlighting.com https://www.cooperlighting.com/global/brands/mws.html https://www.cooperlighting.com/global/resources/programs/rapid-response

PS519338EN page 2 October 5, 2022 9:02 AM

Order Information

SAMPLE ORDER NUMBER: 4SNLED-LD5-48SL-UNV-L840-U

Domestic Preferences Length Series Lamp Type Lumen Package Voltage Options

Domestic Preferences (1) Length Series Lamp Type Lumen Package Voltage Options

[Blank]=Standard TAA=Trade Agreements Act

2=2' Length 4=4' Length 8T=8' Length

SNLED=

Commercial LED Striplight (2)(2)

LD5=LED 5.0 Stocked Lumen Packages

24SL (3)

28SL (3)

32SL

48SL

80SL

88SL

MTO Lumen Packages

20SL (3)

36SL

37HL

40SL

44SL

52SL

56SL

56HL

60SL

60HL

64SL

64HL

68SL

72SL

85HL

96SL

104SL

112SL (5)

130HL (5)

170HL (4)

UNV=Universal Voltage 120-277 347V=347V 480V=480V (6)

Emergency EL7W=7-watt, 120V-277V emergency battery pack installed (7), (9)

EL14W=14-watt 120V-277V emergency battery pack installed (7), (9)

GTR2=Bodine Generator Transfer Relay (10)

ETRD=Iota Emergency Transfer Relay with dimming control (10)

Wiring PI/CPI=Plug in and cross over plug in options (12)

PC6/515P=(NEMA 5-15P) 6' Cord with NEMA Straight Plug (11), (12)

PC6/L715=(NEMA L7-15P) 6' Cord with NEMA Twist Plug (11), (12)

Motion Sensors (13)

LB-ERMS360=360° Low Bay Motion Sensor - End of Row LB-MRMS360=360° Low Bay Motion Sensor - Middle of Row HB-ERMS360=360° High Bay Motion Sensor - End of Row (8)

HB-MRMS360=360° High Bay Motion Sensor - Middle of Row (8)

CCT / CRI

L830=3000K, 80 CRI

L835=3500K, 80 CRI

L840=4000K, 80 CRI

L850=5000K, 80 CRI

L930=3000K, 90 CRI

L935=3500K, 90 CRI

L940=4000K, 90 CRI

L950=5000K, 90 CRI

ZW-SWPD3=WaveLinx Wireless Sensor, Sidecar mount, with 1200 sq ft.

coverage (14)

WLS4=WaveLinx Lite Wireless Integrated Sensor, 15'–40' Mounting Height (14), (15)

Notes Notes Notes Notes Notes

(1) Only product configurations with this designated prefix are built to be compliant with the Trade Agreements Act of 1979 (TAA). Please refer to DOMESTIC PREFERENCES website for more information. Components shipped separately may be separately analyzed under domestic preference requirements.

(2) DesignLights Consortium® Qualified and classified for both DLC Standard and DLC Premium, refer to www.

designlights.org for details.

(3) Available in 2 ft. and 4 ft. (4) Requires two drivers. (5) DALI and Step-dim versions require two drivers.

(6) 4 ft. and 8

ft. only.

(7) 4 ft. and 8 ft. only. (8) Motion Sensor offers dimmability. (9) With integral test switch/ indicator/laser test. For approximate delivered lumens multiply the lumens per watt of the desired fixture by the wattage of the emergency battery pack (100 lm/W x 7=700 lumens). IES-format photometry for luminaire under emergency operation available. (10) Used to bypass local control during outage. Must be used in conjunction with UL 1008 device (provided by others). GTR2 option includes 2 relays on fixtures with dimming drivers. ETRD option only requires one relay when used on a dimming fixture. Must specify voltage as 120V or 277V when ordering these devices. (11) Most common C&P shown. Must specify location for cord. All “end” locations will be on the end with sensor installed. (12) Consult tech support on numerous options for this feature. (13) Sensors provided in separate externally mounted enclosure. See SRL spec sheet for fully integrated/connected sensors. (14) Not compatible with EL options. Not available with 347V, 480V, or UNC. Not available with 5LTD option. End row mounting only. (15) WaveLinx Lite devices are not currently compatible with the WaveLinx Pro Wireless Area Controller.

Driver Type Number of Drivers Packaging Accessories

Drive Type Number of Drivers Packaging Accessories (order separately) (18)

CD=0-10V Dimming Driver (10% - 100% Dimming) HCD=0-10V Dimming Driver (1% - 100% Dimming) SD=Step-dim (Bi Level) (16)

5LTD=Fifth Light (DALI) Driver (16), (17)

1=1 Driver 2=2 Drivers

U=Unit Pack (Order Separately) AYC-Chain/Set=36” Chain Hanger (Use 1 set per fixture) SCF=Fixed Stem Set (Specify Length) SCS=Swivel Stem Set (Specify Length) SCA=Adjustable 48” Stem Set EYE-CHAIN/SET-B=Eye Bolt Chain (Use 1 set per fixture) WG/SNF-2FT=2’ Wire Guard WG/SNF-4FT=4’ Wire Guard A1B/Spacer-U=Spacer 1-1/2” to 2-1/2” from ceiling (Use 2 per fixture) TOGGLE=Single Toggle No. 2 (Specify Length) Y-TOGGLE- -2PK=(2) Y-Toggle Cable Kits (Specify 10 or 30 for length in feet) SNLED-LENS-LW-2FT-U=Replacement Lens 2 ft, Full Frost SNLED-LENS-LN-2FT-U=Replacement Lens 2 ft, Semi Frost SNLED-LENS-LC-2FT-U=Replacement Lens 2 ft, Clear SNLED-LENS-LW-4FT-U=Replacement Lens 4 ft, Full Frost SNLED-LENS-LN-4FT-U=Replacement Lens 4 ft, Semi Frost SNLED-LENS-LC-4FT-U=Replacement Lens 4 ft, Clear GRP-SNF-U=Gripper Hanger CLC-SNLED-EXT-B=SNLED Long Row Aligner Extension

Notes Notes

(16) 4 ft. and 8 ft. only. (17) For a complete listing of Fifth Light products, visit www.cooperlighting.com

(18) Accessories sold separately will be separately analyzed under domestic preference requirements. Consult factory for further information.

PS519338EN page 3 October 5, 2022 9:02 AM

Product Specifications Construction

• Die-formed of cold rolled steel with numerous knockouts for easy installation

• Groove for Tong Hanger

• Convertible end plate for continuous row alignment

• Channel/wireway cover secured with sheet metal screws

• Surface, pendant or stem mounting

Controls

• 0-10V dimming drivers to 10% or to 1% options

• Combine with energy-saving products like occupancy sensors, daylighting controls and lighting relay panels to maximize energy savings

• For motion control, reference options for both end and middle of the row applications

• Step-dimming option

• Fifth Light DALI 2.0 driver option

Electrical

• Long-life LED system with electrical driver for optimal performance

• LED’s available in 3000K, 3500K, 4000K or 5000K with CRI of 80 standard or optional 90 CRI

• TM21 rating up to L87 >60,000 hours

• Electronic drivers available for 120-277V, 347V and 480 applications

• Operating temperature of -20°C to 40°C; Ideal for cold storage environments

Emergency Battery Pack Option

• Optional 120V-277V integral emergency battery pack available in 7W or 14W

• 90-minute backup period for code compliance

• Test switch with laser pointer allows safe testing from floor

• Patented EZ Key prevents accidental discharge during construction

• Generator transfer options available

Compliance

• cULus Listed for damp locations

• RoHS compliant

• Complies with IESNA LM-79 and LM-80 standards

• NEMA 410 compliant (drivers)

• State of California Title 24 high efficacy luminaire

• DesignLights Consortium® Qualified and classified for DLC Standard and DLC Premium (refer to www.designlights.org)

• Suitable for closet use when installed to NEC

410.16 spacings standards

Warranty

• Five year warranty

Photometric Data

View IES files

WaveLinx Lite devices are not currently compatible with the WaveLinx Pro Wireless Area Controller

Control Systems

• WaveLinx Wireless

• WaveLinx Wired

• WaveLinx Lite http://www.designlights.org http://www.cooperindustries.com/content/dam/public/lighting/about%20us/terms_and_conditions/Lighting-Division-TC-Matrix.pdf https://www.cooperlighting.com/global/brands/metalux/snled-series.html https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wireless https://www.cooperlighting.com/global/brands/wavelinx/wired https://www.cooperlighting.com/global/brands/wavelinx/lite https://www.cooperlighting.com/global/controls-wiring/building-systems

Cooper Lighting Solutions 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.cooperlighting.com

© 2022 Cooper Lighting Solutions All Rights Reserved.

Specifications and dimensions subject to change without notice.

PS519338EN page 4 October 5, 2022 9:02 AM

Energy and Performance Data

CRI

Lumen multiplier (80CRI to 90CRI)

3000K 3500K 4000K 5000K

0.805 0.840 0.846 0.901

CCT Table

Approximate Color Temperature Multiplier

2700K .93

3000K .98

3500K 1.0

4000K 1.02

5000K 1.02

Shipping Data

Length Wt.

2 ft. 3.8 lbs.

4 ft. 7.2 lbs.

8 ft. 13.1 lbs.

SNELD

Type

Lumen Type Length Catalog Number

Nominal 3500K Lumens Wattage Im/W

Base Standard 2 ft. 2SNLED-LD5-20SL-UNV-L8XX-CD1-U 2005 14 140.5

Base Standard 2 ft. 2SNLED-LD5-24SL-UNV-L8XX-CD1-U 2476 18 136.8

Base Standard 2 ft. 2SNLED-LD5-28SL-UNV-L8XX-CD1-U 2810 21 132.1

Base High 2 ft. 2SNLED-LD5-37HL-UNV-L8XX-CD1-U 3799 27 143.0

Base Standard 4 ft. 4SNLED-LD5-20SL-UNV-L8XX-CD1-U 1934 13 148.4

Base Standard 4 ft. 4SNLED-LD5-24SL-UNV-L8XX-CD1-U 2398 16 149.8

Base Standard 4 ft. 4SNLED-LD5-28SL-UNV-L8XX-CD1-U 2761 18 149.7

Base Standard 4 ft. 4SNLED-LD5-32SL-UNV-L8XX-CD1-U 3148 21 148.7

Base Standard 4 ft. 4SNLED-LD5-36SL-UNV-L8XX-CD1-U 3649 25 146.6

Base Standard 4 ft. 4SNLED-LD5-40SL-UNV-L8XX-CD1-U 4014 28 144.9

Base Standard 4 ft. 4SNLED-LD5-44SL-UNV-L8XX-CD1-U 4367 31 142.9

Base Standard 4 ft. 4SNLED-LD5-48SL-UNV-L8XX-CD1-U 4827 35 139.9

Base Standard 4 ft. 4SNLED-LD5-52SL-UNV-L8XX-CD1-U 5167 38 137.4

Base Standard 4 ft. 4SNLED-LD5-56SL-UNV-L8XX-CD1-U 5604 41 136.4

Base Standard 4 ft. 4SNLED-LD5-60SL-UNV-L8XX-CD1-U 6015 46 130.4

Base Standard 4 ft. 4SNLED-LD5-64SL-UNV-L8XX-CD1-U 6504 52 125.9

Base Standard 4 ft. 4SNLED-LD5-68SL-UNV-L8XX-CD1-U 6781 55 123

Base High 4 ft. 4SNLED-LD5-56HL-UNV-L8XX-CD1-U 5634 37 152

Base High 4 ft. 4SNLED-LD5-60HL-UNV-L8XX-CD1-U 5894 39 150.9

Base High 4 ft. 4SNLED-LD5-64HL-UNV-L8XX-CD1-U 6421 43 148.9

Base High 4 ft. 4SNLED-LD5-85HL-UNV-L8XX-CD1-U 8471 62 136.3

Base Standard 8 ft. 8TSNLED-LD5-64SL-UNV-L8XX-CD1-U 6296 42 147.8

Base Standard 8 ft. 8TSNLED-LD5-72SL-UNV-L8XX-CD1-U 7298 50 146.6

Base Standard 8 ft. 8TSNLED-LD5-80SL-UNV-L8XX-CD1-U 8028 55 144.9

Base Standard 8 ft. 8TSNLED-LD5-88SL-UNV-L8XX-CD1-U 8734 61 142.9

Base Standard 8 ft. 8TSNLED-LD5-96SL-UNV-L8XX-CD1-U 9654 69 139.9

Base Standard 8 ft. 8TSNLED-LD5-104SL-UNV-L8XX-CD1-U 10334 75 137.4

Base Standard 8 ft. 8TSNLED-LD5-112SL-UNV-L8XX-CD1-U 11208 82 136.4

Base High 8 ft. 8TSNLED-LD5-130HL-UNV-L8XX-CD1-U 12842 86 148.9

Base High 8 ft. 8TSNLED-LD5-170HL-UNV-L8XX-CD2-U 16942 124 136.3

*Stocked in either 3500K or 4000K. Check Flash for stock availability.

General Information: 93PM UPS 20-200kW

93PM System Specifications System Voltage: 480V in, 208/120V out (3 wire in, 4 wire out) UPS Frame Capacity: 150kW

Quantity of 50kW Power Modules: 3 UPS kW Rating: 150 Internal Redundant Configuration: No Internal Battery Configuration: None Input Feed: Single Feed ESS Included: No Communication: Industrial Gateway Card Accessories: Sidecar Bypass Cabinet Side Car: 3 Breaker MBS, Left Mount Side Car Breaker Rating: 65kAIC MBS w/ Aux contact Exhaust Configuration: Top Air Exhaust Internal Estimated Runtime: None UPS Dimensions (H" x W" x D"): 74 x 36.7 x 42 UPS Weight (lbs): 1503

UPS System Dimensions Combined Matching System Dimensions (H" x W" x D", excluding non-matching panels):

74 x 101.9 x 42

93PM Integrated Distribution Cabinet IDC kW Rating: 150kW

Transformer: K13, TP1, 480/208 Delta/Wye Breaker Interrupt Rating (kAIC): High kAIC Top Distribution: 3 Subfeed Breakers + 2 Field

Provisions Bottom Distribution: No Distribution

Subfeed Breaker Rating: 100% Rated Breaker Exhaust Configuration: Top Air Exhaust Output Breaker: No OSHPD Rated: No IAC-D Dimensions (H" x W" x D"): 74 x 31.3 x 42 IAC-D Weight (lbs): 2003.5

UPS Accessories Floor Stand: None Chimney: None

93PM Battery Cabinet Battery Cabinet: IBC-LW

DC Voltage: 480 Battery Cabinet Weight (lbs): 4803 Battery Cabinet Width (in): 34.2 74" H x 42" D kW for Runtime Calculation: 150 Estimated Runtime (min) at 77 degrees F:

11.3

# of Cabinets/Strings: 1/1 Battery Manufacturer: Eaton Battery Installation: Line and Match OSHPD Rated: No

NEG-ALT Number

PREPARED BY DATE

APPROVED BY DATE

VERSION

REVISION DWG SIZE

JOB NAME

DESIGNATION

TYPE

G.O.

DRAWING TYPE

ITEM SHEET

The information on this document is created by Eaton Corporation. It is disclosed in confidence and it is only to be used for the purpose in which it is supplied.

P20T0323X3K1-0000

Conner Fisher 3/23/2023

10.0.0.0

0 A

Eaton VA Data Center At Audie Murphy (San Antonio)

93PM UPS 20-200kW Customer Appr.

Conner Fisher Text Box Solution ID # NO32323001-SWMCO-CF

Jacinto.V.Fuentes Rectangle

Jacinto.V.Fuentes Highlight 11.3

1 2 3

Structure 1 2 3 Ship-Inches Ship-MM Width-Inches Width-MM

31.00 36.70 34.20 787 932 868

Depth-Inches Depth-MM

42.00 42.00 42.00 1066 1066 1066

Height-Inches Height-MM

74.00 74.00 74.00 1879 1879 1879

Weight-Lbs Weight-Kg

2003.50 1503.00 4803.00

908.62 681.63 2178.23

NEG-ALT Number

PREPARED BY DATE

APPROVED BY DATE

VERSION

REVISION DWG SIZE

JOB NAME

DESIGNATION

TYPE

G.O.

DRAWING TYPE

ITEM SHEET

The information on this document is created by Eaton Corporation. It is disclosed in confidence and it is only to be used for the purpose in which it is supplied.

P20T0323X3K1-0000

Conner Fisher 3/23/2023

10.0.0.0

0 A

Eaton VA Data Center At Audie Murphy (San Antonio)

93PM UPS 20-200kW Customer Appr.

Jacinto.V.Fuentes Callout PDU W/ 150kW 480:208/120V K13 Rated Step-Down Transformer & (4) 250A Subfeeds / (1) Future Subfeed Provisions

Jacinto.V.Fuentes Callout 3-Breaker Sidecar (External) Maintenance Bypass

Jacinto.V.Fuentes Callout 150kW Frame 93PM UPS System Rated At 150kW Installed Capacity

Jacinto.V.Fuentes Callout

(2) VRLA Battery Cabinets

Jacinto.V.Fuentes Text Box Recommended Input Breaker Size:

150kW = 250A (80% Rated) / 200A (100% Rated)

Page: 1 of 3

GO/NEG-Alt-Date: Job Name:

Item Number: Catalog Number: Designation:

P20T0323X3K1-0000-3/23/2023 VA Data Center At Audie Murphy (San Antonio)

9PL15N0005E40R2

Jacinto.V.Fuentes Highlight

Jacinto.V.Fuentes Highlight

Jacinto.V.Fuentes Highlight

Jacinto.V.Fuentes Highlight

Jacinto.V.Fuentes Highlight

Jacinto.V.Fuentes Highlight

Jacinto.V.Fuentes Callout UPS Will Be Top Exhaust

Jacinto.V.Fuentes Rectangle

Jacinto.V.Fuentes

Page: 2 of 3

Item Number: Catalog Number: Designation:

P20T0323X3K1-0000-3/23/2023 VA Data Center At Audie Murphy (San Antonio)

9PL15N0005E40R2

Jacinto.V.Fuentes Rectangle

Jacinto.V.Fuentes Rectangle

Jacinto.V.Fuentes Callout 3-Breaker Sidecar Mounted On Left Side of UPS (Can Be On Right Side If Needed)

Page: 3 of 3

Item Number: Catalog Number: Designation:

P20T0323X3K1-0000-3/23/2023 VA Data Center At Audie Murphy (San Antonio)

9PL15N0005E40R2

Jacinto.V.Fuentes Line

Jacinto.V.Fuentes Rectangle

Page: 1 of 3

Item Number: Catalog Number: Designation:

P20T0323X3K1-0000-3/23/2023 VA Data Center At Audie Murphy (San Antonio)

9PL15N0005E40R2

Jacinto.V.Fuentes Rectangle

Jacinto.V.Fuentes Rectangle

Jacinto.V.Fuentes Callout 150kW PDU W/ (4) 250A Subfeed Breakers & (1) Future Provision Spaces

Also Contains 150kVA K-13 Rated 480:208/120V Step-Down Transformer

Page: 2 of 3

Item Number: Catalog Number: Designation:

P20T0323X3K1-0000-3/23/2023 VA Data Center At Audie…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .