S02 - Attachment 1(d) - 671-22-700 DRAWINGS Electrical.pdf

PDF 12 MB Posted

Attached to
EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS) Federal contract opportunity
Solicitation number
36C77623B0064
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document provides details for a federal contract opportunity for infrastructure upgrades at the San Antonio VA Medical Center. The solicitation number is 36C77623B0064 and is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. It is a SDVOSB set-aside for construction services under NAICS code 236220. The opportunity involves upgrading electrical systems as denoted by the 12MB Attachment 1(d) file which contains drawings for the electrical work. Responses are due based on the timing outlined in the full solicitation. The award is expected to be made to a service-disabled veteran-owned small business to complete infrastructure upgrades to electrical systems at the San Antonio VA Medical Center facility.

View the file

Other files for this federal contract opportunity

Other files attached to EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS), newest first.
File Type Posted
S07 - Bid Abstract Page 1_OF1419_EHRM San Antonio_6SEP2023.pdf PDF
S07 - Bid Abstract Page 2_OF1419A_EHRM San Antonio_06SEP2023.pdf PDF
Amendment 0005_36C77623B0064_31AUG2023.pdf PDF
S02 - Attchment 24 - EHRM San Antonio Bid Breakdown Table_31AUG2023.xlsx XLSX spreadsheet
S02 - Attachment 16 - STX Addendum 1.pdf PDF
Amendment 0004_36C77623B0064_25AUG2023.pdf PDF
S02 - Attachment 21 - Addendum 1 - Technology.pdf PDF
S02 - Attachment 19 - 02821321 Asbestos Roofing Abatement.pdf PDF
S02 - Attachment 15 - STX Addendum 1 (Composite).pdf PDF
S02 - Attachment 22 - SF 25 Performance Bond Form.pdf PDF
S02 - Attachment 18 - 320523 Cement and Concrete for Exterior Improvements.pdf PDF
Amendment 0003_36C77623B0064_23AUG2023.pdf PDF
S02 - Attachment 6(b) - Mechanical Cut Sheets - Data Center CRAC - Normal Operation (6000 cfm).pdf PDF
S02 - Attachment 6(d) - Mechanical Cut Sheets - Data Center CRAC Dimensions.pdf PDF
Amendment 0002_36C77623B0064_18AUG2023.pdf PDF
S02 - Attachment 6(c) - Mechanical Cut Sheets - Clean Agent Data Sheet.pdf PDF
S02 - Attachment 6(e) - Mechanical Cut Sheets - Data Center CRAC - N 1 Operation (8000 cfm).pdf PDF
S02 - Attachment 6(a) - Mechanical Cut Sheets - 3.0 Ton Split System.pdf PDF
S02 - Attachment 6(f) - Mechanical Cut Sheets - 2.0 Ton Split System.pdf PDF
Site Visit Attendees Sign-In Sheet_11AUG2023_EHRM San Antonio.xlsx XLSX spreadsheet
Pre-bid Site Visit Sign-in Sheet_11AUG2023.pdf PDF
Solicitation 36C77623B0064_28JUL2023.pdf PDF
S02 - Attachment 14(b) - Asbestos Survey Results Ground and 5th-7th Floors.pdf PDF
S02 - Attachment 13 - VA OEHRM Site Infrastructure and EUD Reqmts 2.0.pdf PDF
S02 - Attachment 10 - VA Notice Limitations on Subcontracting - Construction (JAN 2023) (DEV).docx DOCX document
S02 - Attachment 7(d) - Technology Cut Sheets - Part 4 of 11 CPI Cabinet.pdf PDF
S02 - Attachment 1(e) - 671-22-700 DRAWINGS Technology.pdf PDF
S02 - Attachment 2 - 671-22-700 100 percent final BID SPECIFICATIONS.pdf PDF
S02 - Attachment 1(f) 671-22-700 DRAWINGS Physical Security.pdf PDF
S02 - Attachment 14(a) - Asbestos Survey Results 1st-4th Floors.pdf PDF
S02 - Attachment 11 - Wage Determination_Bexar CountyTX_14APR2023.pdf PDF
S02 - Attachment 12 - Submittal Register ENG Form 4288-R.pdf PDF
S02 - Attachment 9 - Contractor Safety and Environmental Record Form.docx DOCX document
S02 - Attachment 7(h) - Technology Cut Sheets - Part 8 of 11 Axis.pdf PDF
S02 - Attachment 1(a) - 671-22-700 DRAWINGS General Sheets.pdf PDF
S02 - Attachment 8(b) - OIT-InfrastrucStdTelecomSpaces_Part 2 of 3.pdf PDF
S02 - Attachment 8(a) - OIT-InfrastrucStdTelecomSpaces_Part 1 of 3.pdf PDF
S02 - Attachment 7(b) - Technology Cut Sheets - Part 2 of 11 Corning.pdf PDF
S02 - Attachment 7(f) - Technology Cut Sheets - Part 6 of 11 Ortronics.pdf PDF
S02 - Attachment 7(j) - Technology Cut Sheets - Part 10 of 11 HID.pdf PDF
S02 - Attachment 7(e) - Technology Cut Sheets - Part 5 of 11 Leviton.pdf PDF
S02 - Attachment 7(k) - Technology Cut Sheets - Part 11 of 11 Hubbell.pdf PDF
S02 - Attachment 7(i) - Technology Cut Sheets - Part 9 of 11 Cablofil.pdf PDF
S02 - Attachment 1(c) - 671-22-700 DRAWINGS Mechanical.pdf PDF
S02 - Attachment 4 - 230501 SAT_EHRM_100 percent final TechnicalReport.pdf PDF
S02 - Attachment 8(c) - OIT-InfrastrucStdTelecomSpaces_Part 3 of 3.pdf PDF
S02 - Attachment 7(c) - Technology Cut Sheets - Part 3 of 11 CPI.pdf PDF
S02 - Attachment 7(g) - Technology Cut Sheets - Part 7 of 11 Panduit.pdf PDF
S02 - Attachment 1(b) - 671-22-700 DRAWINGS Architectural.pdf PDF
S02 - Attachment 6 - Mechanical Cut Sheets.pdf PDF
Show all 50

EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS) has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL ABBREVIATION KEY

AFF ABOVE FINISHED FLOOR

N.C. NORMALLY CLOSED

NIC NOT IN CONTRACT

N.O. NORMALLY OPEN

SV SOLENOID VALVE

ABBR: DESCRIPTION:

TYP TYPICAL

C CONDUIT

UON UNLESS OTHERWISE NOTED

GFI GROUND FAULT INTERRUPTER

AFF ABOVE FINISHED FLOOR

N.C. NORMALLY CLOSED

NIC NOT IN CONTRACT

N.O. NORMALLY OPEN

SV SOLENOID VALVE

TYP TYPICAL

C CONDUIT

UON UNLESS OTHERWISE NOTED

GFI GROUND FAULT INTERRUPTER

AFF ABOVE FINISHED FLOOR

N.C. NORMALLY CLOSED

NIC NOT IN CONTRACT

N.O. NORMALLY OPEN

SV SOLENOID VALVE

TYP TYPICAL

C CONDUIT

UON UNLESS OTHERWISE NOTED

GFI GROUND FAULT INTERRUPTER

AFF ABOVE FINISHED FLOOR

N.C. NORMALLY CLOSED

NIC NOT IN CONTRACT

N.O. NORMALLY OPEN

SV SOLENOID VALVE

TYP TYPICAL

C CONDUIT

UON UNLESS OTHERWISE NOTED

GFI GROUND FAULT INTERRUPTER

AFF ABOVE FINISHED FLOOR

N.C. NORMALLY CLOSED

NIC NOT IN CONTRACT

N.O. NORMALLY OPEN

SV SOLENOID VALVE

TYP TYPICAL

C CONDUIT

UON UNLESS OTHERWISE NOTED

GFI GROUND FAULT INTERRUPTER

AFF ABOVE FINISHED FLOOR

N.C. NORMALLY CLOSED

NIC NOT IN CONTRACT

N.O. NORMALLY OPEN

SV SOLENOID VALVE

TYP TYPICAL

C CONDUIT

UON UNLESS OTHERWISE NOTED

GFI GROUND FAULT INTERRUPTER

ELECTRICAL INSTALLATION NOTES:

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR

ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON

THIS PAGE FOR ADDITIONAL INFORMATION.

2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE

WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR

BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH

PHASE.

3. EMERGENCY AND CRITICAL, EQUIPMENT BRANCH WIRING FOR FEEDERS AND BRANCH

CIRCUITS SHALL BE ROUTED IN SEPARATE RACEWAY, JUNCTION BOXES, PULL BOXES, AND

CABINETS. WIRING FOR EACH BRANCH SHALL BE INDEPENDENT FROM OTHER BRANCHES,

INCLUDING THE NORMAL BRANCH.

4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE

DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED

WHEN CONDUIT IS SPECIFIED EXPOSED.

5. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM

FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND

OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED. MOUNT

EXTERIOR LOCATED RECEPTACLES WITH WHILE-IN-USE COVERS AT +20" FROM FINISHED

GRADE (CENTER DIMENSIONS) TO MAINTAIN INSTALLATION ADA COMPLIANCE.

6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL

BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF

THROUGH-PENETRATION FIRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL INFORMATION

AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.

7. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)

EXCEPT WHERE OTHERWISE NOTED.

8. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED

FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE

NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.

9. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND

EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES

IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS SHALL

BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.

10. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT

LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.

PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL

ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE

FURNITURE AND/OR EQUIPMENT.

11. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,

OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL

MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT

SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER

CONTRACTOR.

12. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL

OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE

EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR

SEALED INTO OPENINGS.

13. ALL WELDING SHALL BE ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS.

CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER CERTIFICATES QUALIFYING

EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE

RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT THE CONTRACTOR'S EXPENSE, OF

ANY WELDERS ASSIGNED TO THE JOB.

14. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE

WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE

IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND

FINISH.

15. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY

AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING

MOUNTED DEVICES, OTHER THAN SPRINKLERS.

16. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR

COLOR/LABEL REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.

LUMINAIRE SYMBOL KEY

SYMBOL: DESCRIPTION:

NORMAL BRANCH LUMINAIRE

EMERGENCY BRANCH LUMINAIRE

'NL' - UNSWITCHED FOR NIGHT LIGHT

'*E' - BATTERY BACK-UP

ELECTRICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD

SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND

REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING

CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAY AND CONDUITS

BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING

FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND

SHALL NOTIFY THE CONSTRUCTION MANAGER PRIOR TO BIDDING IF OTHER UTILITIES ARE

REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.

5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF

ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.

CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.

6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF

CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL

CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO

BIDDING.

7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW

EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER

ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES

NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO

ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

ELECTRICAL PHASING NOTES:

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER

TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS

FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.

MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL

DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT

THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.

WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN

SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED

SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER

TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS

FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.

MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL

DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT

THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.

WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN

SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED

SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER

TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS

FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.

MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL

DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT

THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.

WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN

SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED

SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER

TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS

FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.

MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL

DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT

THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.

WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN

SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED

SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER

TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS

FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.

MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL

DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT

THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.

WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN

SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED

SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER

TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS

FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.

MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL

DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT

THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.

WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN

SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED

SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

SIMSIM

INDICATES SIMILAR DETAIL REFERENCED

IN MULTIPLE LOCATIONS

LEVEL NAME

10'-0" HEIGHT ABOVE

PROJECT 0'-0"

1 INDICATES NOTE USED TO DESCRIBE

ADDITIONAL INFORMATION ABOUT

WORK REQUIRED, SPECIFIC TO THE

SHEET AND/OR DETAIL

VIEW KEY

LINE TYPE AND TAG KEY:

NEW WORK BY THIS CONTRACTOR (WIDE LINE)

NEW

EXISTING TO BE REMOVED (SHORT DASHED PATTERN)

NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)

EXISTING

EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)

EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

HALFTONING DOES NOT MODIFY SCOPE.

'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING

(SEE TECHNOLOGY CALBING PLAN)

'TAG'-D TAGS WITH DASH 'D' INDICATES THE REFERENCED OBJECT IS DEMOLISHED

(SEE TECHNOLOGY CALBING PLAN)

TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL

INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST

INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL

T101

ELECTRICAL MOUNTING SUBSCRIPT KEY:

A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH

C MOUNT AT CEILING

H MOUNT ORIENTED HORIZONTALLY

L MOUNT IN CASEWORK

M MOUNT IN MODULAR FURNITURE

R MOUNT IN SURFACE RACEWAY

EWC ELECTRIC WATER COOLER

ELECTRICAL GENERAL NOTES:

LUMINAIRE

DEVICE

A = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

LUMINAIRE KEY:

DEVICE KEY:

ELECTRICAL MOUNTING SUBSCRIPT KEY:

A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH

C MOUNT AT CEILING

H MOUNT ORIENTED HORIZONTALLY

L MOUNT IN CASEWORK

M MOUNT IN MODULAR FURNITURE

R MOUNT IN SURFACE RACEWAY

EWC ELECTRIC WATER COOLER

LUMINAIRE

DEVICE

A = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

LUMINAIRE KEY:

DEVICE KEY:

ELECTRICAL MOUNTING SUBSCRIPT KEY:

A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH

C MOUNT AT CEILING

H MOUNT ORIENTED HORIZONTALLY

L MOUNT IN CASEWORK

M MOUNT IN MODULAR FURNITURE

R MOUNT IN SURFACE RACEWAY

EWC ELECTRIC WATER COOLER

LUMINAIRE

DEVICE

A = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

LUMINAIRE KEY:

DEVICE KEY:

1. "NL" INDICATES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.

2. SHADED LUMINAIRE OR DEVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN

EMERGENCY CIRCUIT.

3. REFER TO SHEET E400 FOR LUMINAIRE SCHEDULE.

4. { L##} DENOTES THE LIGHTING SEQUENCE OF OPERATIONS FOR THIS SPACE. REFER TO

SHEET E400.

5. VACANCY/OCCUPANCY SENSOR LAYOUT: SENSORS ARE SHOWN ON THE PLANS FOR

DESIGN INTENT AND MAY NOT REPRESENT EVERY DEVICE. PROVIDE MANUFACTURER

SPECIFIC FLOOR PLAN LAYOUTS SHOWING LOCATION, ORIENTATION, AND COVERAGE AREA

OF EACH CONTROL DEVICE, SENSOR, AND CONTROLLER/INTERFACE. AREAS REQUIRING

MULTIPLE SENSOR DEVICES FOR APPROPRIATE COVERAGE, SUBMIT SPECIFIC

MANUFACTURER-APPROVED SENSOR LAYOUT AS AN OVERLAY DIRECTLY ON THE PROJECT

DRAWINGS, EITHER IN PRINT OR APPROVED ELECTRONIC FORM.

ELECTRICAL MOUNTING SUBSCRIPT KEY:

A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH

C MOUNT AT CEILING

H MOUNT ORIENTED HORIZONTALLY

L MOUNT IN CASEWORK

M MOUNT IN MODULAR FURNITURE

R MOUNT IN SURFACE RACEWAY

EWC ELECTRIC WATER COOLER

LUMINAIRE

F1 = FIXTURE TAG

1 = CIRCUIT NUMBER

a = SWITCH DESIGNATION

NL = SUBSCRIPT (IF APPLICABLE)

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: F1 / 1 / a / NL

DEVICE

A = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

LUMINAIRE KEY:

DEVICE KEY:

ELECTRICAL MOUNTING SUBSCRIPT KEY:

A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH

C MOUNT AT CEILING

H MOUNT ORIENTED HORIZONTALLY

L MOUNT IN CASEWORK

M MOUNT IN MODULAR FURNITURE

R MOUNT IN SURFACE RACEWAY

EWC ELECTRIC WATER COOLER

LUMINAIRE

DEVICE

A = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

LUMINAIRE KEY:

DEVICE KEY:

ELECTRICAL MOUNTING SUBSCRIPT KEY:

A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH

C MOUNT AT CEILING

H MOUNT ORIENTED HORIZONTALLY

L MOUNT IN CASEWORK

M MOUNT IN MODULAR FURNITURE

R MOUNT IN SURFACE RACEWAY

EWC ELECTRIC WATER COOLER

LUMINAIRE

DEVICE

A = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

LUMINAIRE KEY:

DEVICE KEY:

TYPICAL REMODEL:

1. ALL LUMINAIRES SHOWN TO BE DEMOLISHED SHALL BE DISPOSED OF IF NOT REQUIRED BY

OWNER FOR ATTIC STOCK. CONFIRM WITH OWNER PRIOR TO DISPOSAL IF THE LAMPS,

LENS OR SUBSET OF LUMINAIRES SHOULD BE TURNED OVER FOR ATTIC STOCK.

2. REMOVE EXISTING LUMINAIRES AND WALL SWITCHES WHERE SHOWN. LOCATE AND

IDENTIFY ELECTRICAL CIRCUIT SERVING REMOVED LUMINAIRES FOR REUSE WITH NEW

DEVICES.

3. COORDINATE HOURS OF ACCESS WITH OWNER.

4. EXISTING EMERGENCY LIGHTING AND EXIT SIGNAGE SHALL REMAIN.

5. REMOVE EXISTING LUMINAIRE AND PREPARE FOR INSTALLATION OF NEW LUMINAIRE IN

NEW LOCATION.

6. MATCH EXISTING FACEPLATE FINISH AND TYPE FOR ALL LOCATIONS WHERE NEW WALL

CONTROL DEVICE IS BEING INSTALLED.

7. WHERE WALL SWITCH DEVICE IS REMOVED AND NOT REPLACED. PROVIDE WITH BLANK

SWITCH PLATE.

8. EXPOSED 3/4" CONDUIT TO NEW OR EXISTING FIXTURES OR DEVICES IS ACCEPTABLE AS

LONG AS IT IS INSTALLED IN A NEAT AND ORDERLY METHOD AND MEETS ADOPTED CODES.

COORDINATE NEW RUNS WITH OWNER PRIOR TO INSTALLATIONS.

9. REUSE EXISTING CONDUIT, WIRE, CONTROL AND JUNCTION BOXES. PROVIDE NEW IF

REQUIRED TO INSTALL THE NEW LUMINAIRE.

10. PROVIDE (1) UNSWITCHED LEG FROM PANEL SERVING THE EMERGENCY FIXTURES TO THE

SENSOR LEG SERVING THE NEW BATTERY BACK UP IN NEW LUMINAIRES.

11. CONNECT NEW LUMINAIRES TO CIRCUIT THAT SERVED PREVIOUSLY REMOVED LUMINAIRE

USING 2#12 &1#12 GND IN 3/4" C. EXTEND CONDUIT AND CONDUCTORS AS REQUIRED TO

MAKE CONNECTION. CONDUIT IN GOOD CONDITION SHALL BE REUSED IN PLACE.

12. NEW OCCUPANCY SENSORS TO BE INSTALLED IN A MANUAL ON/AUTO OFF'

CONFIGURATION.

13. REPLACE CEILING TILES WITH LIKE IN AREAS WITH A REDUCTION IN LUMINAIRE. REUSE

EXISTING CEILING TILES WHERE APPLICABLE. PROVIDE NEW TO MATCH EXISTING IF

REQUIRED. ADJUST AND MOVE AIR RETURN GRILLS AS REQUIRED TO COORDINATE WITH

REVISED LUMINAIRE LAYOUT IN AREAS WITH A LAYIN CEILING.

14. COORDINATE LOCATIONS OF NEW LUMINAIRES WITH EXISTING DUCT, PIPING, STRUCTURAL

AND CEILING MOUNTED DEVICES.

ELECTRICAL SYMBOL LIST

SYMBOL: TAG: SPEC

SECTION:

DESCRIPTION:

26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26 DUPLEX GFI RECEPTACLE, 125V

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26

26 27 26

ELECTRICAL SYMBOL LIST

SYMBOL: SPEC

SECTION:

DESCRIPTION:

REFER TO LUMINAIRE

SCHEDULE

DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V

26 09 23 WALL SWITCH

O

OC

D

CIRCUIT BREAKER - SURFACE MOUNTED.

REFER TO DISC/STA SCHEDULE

26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.

REFER TO DISC/STA SCHEDULE

ELECTRICAL SYMBOL LIST

SYMBOL: SPEC

SECTION:

DESCRIPTION:

26 05 33 JUNCTION BOX

J

J

26 05 33 ELECTRICAL CONNECTION

E

E

26 24 16 PANELBOARD - SURFACE MOUNT

26 24 16 PANELBOARD - RECESS MOUNT

26 05 26 GROUND BUSGB

26 05 26 INTERSYSTEM BONDING TERMINATIONIBT

ELECTRICAL SYMBOL LIST

SYMBOL: SPEC

SECTION:

DESCRIPTION:

26 22 00 TRANSFORMER. REFER TO

TRANSFORMER SCHEDULE

26 09 23

26 09 23

26 09 23

26 09 23

WALL SWITCH - THREE WAY

DIMMER - LED

OCCUPANCY SENSOR - DUAL TECHNOLOGY

26 29 21

ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO

TRANSFER SWITCH SCHEDULE

26 36 00

DP-# DISTRIBUTION PANEL 26 24 16

26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE

RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00

SB-# SWITCHBOARD 26 24 13

ELECTRICAL EQUIPMENT TAGS

TAG: DESCRIPTION:

RELATED

SPECIFICATION

26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26 DUPLEX GFI RECEPTACLE, 125V

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26

26 27 26

REFER TO LUMINAIRE

SCHEDULE

DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V

26 09 23 WALL SWITCH

O

D

CIRCUIT BREAKER - SURFACE MOUNTED.

REFER TO DISC/STA SCHEDULE

26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.

REFER TO DISC/STA SCHEDULE

26 05 33 JUNCTION BOX

26 05 33 ELECTRICAL CONNECTION

26 24 16 PANELBOARD - SURFACE MOUNT

26 24 16 PANELBOARD - RECESS MOUNT

26 05 26 GROUND BUS

26 05 26 INTERSYSTEM BONDING TERMINATION

26 22 00 TRANSFORMER. REFER TO

TRANSFORMER SCHEDULE

26 09 23

26 09 23

26 09 23

26 09 23

SWITCH - OCCUPANCY SENSOR WALL SWITCH

WALL SWITCH - THREE WAY

DIMMER - LED

OCCUPANCY SENSOR - DUAL TECHNOLOGY

26 29 21

ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO

TRANSFER SWITCH SCHEDULE

26 36 00

DP-# DISTRIBUTION PANEL 26 24 16

26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE

RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00

SB-# SWITCHBOARD 26 24 13

RELATED

SPECIFICATION

26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26 DUPLEX GFI RECEPTACLE, 125V

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26

26 27 26

REFER TO LUMINAIRE

SCHEDULE

DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V

26 09 23 WALL SWITCH

O

D

CIRCUIT BREAKER - SURFACE MOUNTED.

REFER TO DISC/STA SCHEDULE

26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.

REFER TO DISC/STA SCHEDULE

26 05 33 JUNCTION BOX

26 05 33 ELECTRICAL CONNECTION

26 24 16 PANELBOARD - SURFACE MOUNT

26 24 16 PANELBOARD - RECESS MOUNT

26 05 26 GROUND BUS

26 05 26 INTERSYSTEM BONDING TERMINATION

26 22 00 TRANSFORMER. REFER TO

TRANSFORMER SCHEDULE

26 09 23

26 09 23

26 09 23

26 09 23

SWITCH - OCCUPANCY SENSOR WALL SWITCH

WALL SWITCH - THREE WAY

DIMMER - LED

OCCUPANCY SENSOR - DUAL TECHNOLOGY

26 29 21

ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO

TRANSFER SWITCH SCHEDULE

26 36 00

DP-# DISTRIBUTION PANEL 26 24 16

26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE

RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00

SB-# SWITCHBOARD 26 24 13

RELATED

SPECIFICATION

INDUSTRIAL LUMINAIRE

26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26 DUPLEX GFI RECEPTACLE, 125V

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26

26 27 26

WP

REFER TO LUMINAIRE

SCHEDULE

2 X 4 TROFFER

DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V

26 09 23 WALL SWITCH

O

D

CIRCUIT BREAKER - SURFACE MOUNTED.

REFER TO DISC/STA SCHEDULE

26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.

REFER TO DISC/STA SCHEDULE

26 05 33 JUNCTION BOX

26 05 33 ELECTRICAL CONNECTION

26 24 16 PANELBOARD - SURFACE MOUNT

26 24 16 PANELBOARD - RECESS MOUNT

26 05 26 GROUND BUS

26 05 26

26 22 00 TRANSFORMER. REFER TO

TRANSFORMER SCHEDULE

BUSWAY SYSTEM - WITH END-FEED AND

BUSWAY TAP SHOWN

26 09 23

26 09 23

26 09 23

26 09 23

DIMMER - LED

OCCUPANCY SENSOR - DUAL TECHNOLOGY

26 29 21

ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO

TRANSFER SWITCH SCHEDULE

26 36 00

DP-# DISTRIBUTION PANEL 26 24 16

26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE

RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00

SB-# SWITCHBOARD 26 24 13

RELATED

SPECIFICATION

26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26 DUPLEX GFI RECEPTACLE, 125V

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26

26 27 26

REFER TO LUMINAIRE

SCHEDULE

DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V

26 09 23 WALL SWITCH

O

D

CIRCUIT BREAKER - SURFACE MOUNTED.

REFER TO DISC/STA SCHEDULE

26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.

REFER TO DISC/STA SCHEDULE

26 05 33 JUNCTION BOX

26 05 33 ELECTRICAL CONNECTION

26 24 16 PANELBOARD - SURFACE MOUNT

26 24 16 PANELBOARD - RECESS MOUNT

26 05 26 GROUND BUS

26 05 26 INTERSYSTEM BONDING TERMINATION

26 22 00 TRANSFORMER. REFER TO

TRANSFORMER SCHEDULE

26 09 23

26 09 23

26 09 23

26 09 23

SWITCH - OCCUPANCY SENSOR WALL SWITCH

WALL SWITCH - THREE WAY

DIMMER - LED

OCCUPANCY SENSOR - DUAL TECHNOLOGY

26 29 21

ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO

TRANSFER SWITCH SCHEDULE

26 36 00

DP-# DISTRIBUTION PANEL 26 24 16

26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE

RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00

SB-# SWITCHBOARD 26 24 13

RELATED

SPECIFICATION

26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26 DUPLEX GFI RECEPTACLE, 125V

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26

26 27 26

REFER TO LUMINAIRE

SCHEDULE

DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V

26 09 23 WALL SWITCH

O

D

CIRCUIT BREAKER - SURFACE MOUNTED.

REFER TO DISC/STA SCHEDULE

26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.

REFER TO DISC/STA SCHEDULE

26 05 33 JUNCTION BOX

26 05 33 ELECTRICAL CONNECTION

26 24 16 PANELBOARD - SURFACE MOUNT

26 24 16 PANELBOARD - RECESS MOUNT

26 05 26 GROUND BUS

26 05 26 INTERSYSTEM BONDING TERMINATION

26 22 00 TRANSFORMER. REFER TO

TRANSFORMER SCHEDULE

26 09 23

26 09 23

26 09 23

26 09 23

SWITCH - OCCUPANCY SENSOR WALL SWITCH

WALL SWITCH - THREE WAY

DIMMER - LED

OCCUPANCY SENSOR - DUAL TECHNOLOGY

26 29 21

ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO

TRANSFER SWITCH SCHEDULE

26 36 00

DP-# DISTRIBUTION PANEL 26 24 16

26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE

RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00

SB-# SWITCHBOARD 26 24 13

RELATED

SPECIFICATION26 27 2626 27 26 RECEPTACLE, LOCKING L21-30R, 120/208V, 3PH26 27 2626 27 2626 27 2626 27 26

EMERGENCY STOP, N.O. CONTACTEPO EMERGENCY STOP, N.O. CONTACTEMERGENCY STOP, N.O. CONTACTEMERGENCY STOP, N.O. CONTACTEMERGENCY STOP, N.O. CONTACTEMERGENCY STOP, N.O. CONTACT

26 25 11

26 27 26 RECEPTACLE, LOCKING L5-30R, 125V

RECEPTACLE, LOCKING L5-20R, 125V

ELECTRICAL SYMBOL LIST

SYMBOL: TAG: SPEC

SECTION:

DESCRIPTION:

FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR

VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER

NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT

PANEL

AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM

FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET

S

FA-120 28 31 00 S

S FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR

# = EQUIP OR SYSTEM

S

AS

ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE

DETECTION

H

H

FA-140 28 31 00 FIRE ALARM HEAT DETECTOR

BLANK = COMBINATION RATE OF RISE

/ FIXED TEMP

AT = ATTIC (LOCATED IN)

F = FIXED TEMP

RC = RATE COMPENSATED

X - EXPLOSION PROOF

FA-130 28 31 00 FIRE ALARM MANUAL PULL STATIONF

FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVERFT

FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING

OR WALL MOUNT

# = CANDELA RATING.

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

F

F

FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING

OR WALL MOUNTED

M = MINI-HORN

S = SLEEPING / PATIENT ROOM

FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND

VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

S

S

FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR

WALL MOUNTED

FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL

ALARM DEVICE, CEILING OR WALL MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

M

M

FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)

AND VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-241 28 31 00 FIRE ALARM REMOTE INDICATORRI

FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR

W/ TEST SWITCH

RT

FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

KB = KNOX BOX

FS

FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

PIV = POST INDICATOR VALVE

TS

FA-161 28 31 00 FIRE ALARM ADDRESSABLE

CONTROL MODULE

BLANK = REFER TO PLANS

LC = LIGHTING CONTROL

OVERRIDE

DH = DOOR HOLD OPEN

PD = HOLD OPEN OVERRIDE

CM

FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY OTHERS, WIRED BY E.C.)

DH - ELECTROMAGNETIC DOOR

HOLD DEVICE

PD - HOLD OPEN OVERRIDE

CONNECTION

FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY E.C.)

DH

FA-250 28 31 00 FIRE ALARM SMOKE OR

FIRE/SMOKE DAMPER CONTROL

WITH DETECTOR, AND

ADDRESSABLE MODULE, AND

REMOTE INDICATOR (WITH TEST

SWITCH WHEN APPLICABLE)

# = INDICATES EQUIP OR SYSTEM

FSD

COMMON AND

SEQUENCE OF

OPERATION

SUBSCRIPTS

FACP-# 28 31 00 FIRE ALARM CONTROL PANEL

FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR

VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER

NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT

PANEL

AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM

FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET

FA-120 28 31 00 FIRE ALARM SMOKE DETECTOR,

CEILING OR WALL MOUNT

BLANK - PHOTOELECTRIC

AT = ATTIC (LOCATED IN)

CO = COMBINATION SMOKE / CARBON

MONOXIDE

COH = COMBINATION SMOKE /

CARBON MONOXIDE / HEAT

COS = COMBINATION SMOKE /

CARBON MONOXIDE / STROBE

H = COMBINATION SMOKE / HEAT

DETECTOR

ID = IN DUCT DETECTOR

FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR

# = EQUIP OR SYSTEM

ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE

DETECTION

FA-140 28 31 00 FIRE ALARM HEAT DETECTOR

BLANK = COMBINATION RATE OF RISE

/ FIXED TEMP

AT = ATTIC (LOCATED IN)

F = FIXED TEMP

RC = RATE COMPENSATED

X - EXPLOSION PROOF

FA-130 28 31 00 FIRE ALARM MANUAL PULL STATION

FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVER

FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING

OR WALL MOUNT

# = CANDELA RATING.

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING

OR WALL MOUNTED

M = MINI-HORN

S = SLEEPING / PATIENT ROOM

FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND

VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR

WALL MOUNTED

FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL

ALARM DEVICE, CEILING OR WALL MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)

AND VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-241 28 31 00 FIRE ALARM REMOTE INDICATOR

FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR

W/ TEST SWITCH

FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

KB = KNOX BOX

FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

PIV = POST INDICATOR VALVE

FA-161 28 31 00 FIRE ALARM ADDRESSABLE

CONTROL MODULE

BLANK = REFER TO PLANS

LC = LIGHTING CONTROL

OVERRIDE

DH = DOOR HOLD OPEN

PD = HOLD OPEN OVERRIDE

FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY OTHERS, WIRED BY E.C.)

DH - ELECTROMAGNETIC DOOR

HOLD DEVICE

PD - HOLD OPEN OVERRIDE

CONNECTION

FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY E.C.)

FA-250 28 31 00 FIRE ALARM SMOKE OR

FIRE/SMOKE DAMPER CONTROL

WITH DETECTOR, AND

ADDRESSABLE MODULE, AND

REMOTE INDICATOR (WITH TEST

SWITCH WHEN APPLICABLE)

# = INDICATES EQUIP OR SYSTEM

FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR

VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER

NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT

PANEL

AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM

FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET

FA-120 28 31 00

FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR

# = EQUIP OR SYSTEM

ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE

DETECTION

FA-140 28 31 00 FIRE ALARM HEAT DETECTOR

BLANK = COMBINATION RATE OF RISE

/ FIXED TEMP

AT = ATTIC (LOCATED IN)

F = FIXED TEMP

RC = RATE COMPENSATED

X - EXPLOSION PROOF

FA-130 28 31 00 FIRE ALARM MANUAL PULL STATION

FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVER

FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING

OR WALL MOUNT

# = CANDELA RATING.

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING

OR WALL MOUNTED

M = MINI-HORN

S = SLEEPING / PATIENT ROOM

FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND

VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR

WALL MOUNTED

FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL

ALARM DEVICE, CEILING OR WALL MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)

AND VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-241 28 31 00 FIRE ALARM REMOTE INDICATOR

FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR

W/ TEST SWITCH

FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

KB = KNOX BOX

FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

PIV = POST INDICATOR VALVE

FA-161 28 31 00 FIRE ALARM ADDRESSABLE

CONTROL MODULE

BLANK = REFER TO PLANS

LC = LIGHTING CONTROL

OVERRIDE

DH = DOOR HOLD OPEN

PD = HOLD OPEN OVERRIDE

FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY OTHERS, WIRED BY E.C.)

DH - ELECTROMAGNETIC DOOR

HOLD DEVICE

PD - HOLD OPEN OVERRIDE

CONNECTION

FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY E.C.)

FA-250 28 31 00 FIRE ALARM SMOKE OR

FIRE/SMOKE DAMPER CONTROL

WITH DETECTOR, AND

ADDRESSABLE MODULE, AND

REMOTE INDICATOR (WITH TEST

SWITCH WHEN APPLICABLE)

# = INDICATES EQUIP OR SYSTEM

SUBSCRIPTS: TYPE / PROGRAMMING

WG = WIRE GUARD IS REQUIRED

W = WEATHERPROOF

CR = COMPUTER ROOM

E = ELEVATOR RECALL

D = HVAC CONTROL

DH = DOOR HOLD RELEASE

DIPS = DUAL INTERLOCK PREACTION SYS

FD = FIRE DOOR RELEASE

SW = STAIRWELL

# = 15, 30, 75, 110, 177 CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR

VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER

NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT

PANEL

AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM

FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET

FA-120 28 31 00

FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR

# = EQUIP OR SYSTEM

ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE

DETECTION

FA-140 28 31 00 FIRE ALARM HEAT DETECTOR

BLANK = COMBINATION RATE OF RISE

/ FIXED TEMP

AT = ATTIC (LOCATED IN)

F = FIXED TEMP

RC = RATE COMPENSATED

X - EXPLOSION PROOF

FA-130 28 31 00 FIRE ALARM MANUAL PULL STATION

FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVER

FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING

OR WALL MOUNT

# = CANDELA RATING.

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING

OR WALL MOUNTED

M = MINI-HORN

S = SLEEPING / PATIENT ROOM

FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND

VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR

WALL MOUNTED

FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL

ALARM DEVICE, CEILING OR WALL MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)

AND VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-241 28 31 00 FIRE ALARM REMOTE INDICATOR

FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR

W/ TEST SWITCH

FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

KB = KNOX BOX

FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

PIV = POST INDICATOR VALVE

FA-161 28 31 00 FIRE ALARM ADDRESSABLE

CONTROL MODULE

BLANK = REFER TO PLANS

LC = LIGHTING CONTROL

OVERRIDE

DH = DOOR HOLD OPEN

PD = HOLD OPEN OVERRIDE

FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY OTHERS, WIRED BY E.C.)

DH - ELECTROMAGNETIC DOOR

HOLD DEVICE

PD - HOLD OPEN OVERRIDE

CONNECTION

FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY E.C.)

FA-250 28 31 00 FIRE ALARM SMOKE OR

FIRE/SMOKE DAMPER CONTROL

WITH DETECTOR, AND

ADDRESSABLE MODULE, AND

REMOTE INDICATOR (WITH TEST

SWITCH WHEN APPLICABLE)

# = INDICATES EQUIP OR SYSTEM

FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR

VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER

NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT

PANEL

AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM

FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET

FA-120 28 31 00

FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR

# = EQUIP OR SYSTEM

ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE

DETECTION

FA-140 28 31 00 FIRE ALARM HEAT DETECTOR

BLANK = COMBINATION RATE OF RISE

/ FIXED TEMP

AT = ATTIC (LOCATED IN)

F = FIXED TEMP

RC = RATE COMPENSATED

X - EXPLOSION PROOF

FA-130 28 31 00 FIRE ALARM MANUAL PULL STATION

FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVER

FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING

OR WALL MOUNT

# = CANDELA RATING.

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING

OR WALL MOUNTED

M = MINI-HORN

S = SLEEPING / PATIENT ROOM

FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND

VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR

WALL MOUNTED

FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL

ALARM DEVICE, CEILING OR WALL MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)

AND VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-241 28 31 00 FIRE ALARM REMOTE INDICATOR

FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR

W/ TEST SWITCH

FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

KB = KNOX BOX

FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

PIV = POST INDICATOR VALVE

FA-161 28 31 00 FIRE ALARM ADDRESSABLE

CONTROL MODULE

BLANK = REFER TO PLANS

LC = LIGHTING CONTROL

OVERRIDE

DH = DOOR HOLD OPEN

PD = HOLD OPEN OVERRIDE

FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY OTHERS, WIRED BY E.C.)

DH - ELECTROMAGNETIC DOOR

HOLD DEVICE

PD - HOLD OPEN OVERRIDE

CONNECTION

FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY E.C.)

FA-250 28 31 00 FIRE ALARM SMOKE OR

FIRE/SMOKE DAMPER CONTROL

WITH DETECTOR, AND

ADDRESSABLE MODULE, AND

REMOTE INDICATOR (WITH TEST

SWITCH WHEN APPLICABLE)

# = INDICATES EQUIP OR SYSTEM

FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR

VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER

NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT

PANEL

AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM

FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET

FA-120 28 31 00

FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR

# = EQUIP OR SYSTEM

ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE

DETECTION

FA-140 28 31 00 FIRE ALARM HEAT DETECTOR

BLANK = COMBINATION RATE OF RISE

/ FIXED TEMP

AT = ATTIC (LOCATED IN)

F = FIXED TEMP

RC = RATE COMPENSATED

X - EXPLOSION PROOF

FA-130 28 31 00 FIRE ALARM MANUAL PULL STATION

FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVER

FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING

OR WALL MOUNT

# = CANDELA RATING.

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING

OR WALL MOUNTED

M = MINI-HORN

S = SLEEPING / PATIENT ROOM

FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND

VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR

WALL MOUNTED

FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL

ALARM DEVICE, CEILING OR WALL MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)

AND VISUAL ALARM DEVICE, CEILING OR WALL

MOUNTED

# = CANDELA RATING

CD = CANDELA RATING SELECTED BY NICET

DESIGNER

FA-241 28 31 00 FIRE ALARM REMOTE INDICATOR

FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR

W/ TEST SWITCH

FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

KB = KNOX BOX

FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO

MONITOR SPRINKLER SYSTEM

BLANK = REFER TO PLANS

PIV = POST INDICATOR VALVE

FA-161 28 31 00 FIRE ALARM ADDRESSABLE

CONTROL MODULE

BLANK = REFER TO PLANS

LC = LIGHTING CONTROL

OVERRIDE

DH = DOOR HOLD OPEN

PD = HOLD OPEN OVERRIDE

FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY OTHERS, WIRED BY E.C.)

DH - ELECTROMAGNETIC DOOR

HOLD DEVICE

PD - HOLD OPEN OVERRIDE

CONNECTION

FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE

(BY E.C.)

FA-250 28 31 00 FIRE ALARM SMOKE OR

FIRE/SMOKE DAMPER CONTROL

WITH DETECTOR, AND

ADDRESSABLE MODULE, AND

REMOTE INDICATOR (WITH TEST

SWITCH WHEN APPLICABLE)

# = INDICATES EQUIP OR SYSTEM

THE LINE TYPES SHOWN ARE FOR THE CONVENIENCE OF THE CONTRACTOR. THE CONTRACTOR

SHALL VERIFY RATINGS WITH THE LATEST SET OF ARCHITECTURAL PLANS AND FURNISH ALL

MATERIALS REQUIRED TO COMPLY WITH THOSE RATINGS WHETHER SHOWN OR NOT.

ALL [FLOOR, FLOOR CEILING, AND ROOF CEILING] ASSEMBLIES SHALL BE DESIGNATED AS [1], [2], [3], [4] HOUR FIRE [/SMOKE], BARRIER(S), UNLESS NOTED OTHERWISE ON THE PLANS. RATINGS

WERE ACQUIRED FROM THE ARCHITECTURAL PLANS DATED [**/**/**].

FIRE / SMOKE BARRIER DESIGNATIONS

1 HOUR FIRE BARRIER

SMOKE BARRIER

1 HOUR FIRE/SMOKE BARRIER

OR SHAFT ENCLOSURE

2 HOUR FIRE/SMOKE BARRIER

OR SHAFT ENCLOSURE

3 HOUR FIRE/SMOKE BARRIER

4 HOUR FIRE/SMOKE BARRIER

SMOKE PARTITION

FIRE PARTITION

2 HOUR FIRE BARRIER OR WALL

3 HOUR FIRE BARRIER OR WALL

4 HOUR FIRE BARRIER OR WALL

PANELBOARD NOTATION

PANELBOARD CIRCUIT BREAKER LOCATIONS

480/277V - A C E G I K M O Q S U W Y AA...AAA...

120/208V - B D F H J L N P R T V X Z BB...BBB...

FLOOR ON WHICH PANEL IS LOCATED

L = NORMAL POWER E = EMERGENCY POWER C = CRITICAL POWER

L 1 BB-#

NUMBER AND ADDRESS

SUITE NO.

CITY, STATE ZIP CODE

P: 555.555.555 F: 555.555.5555 www.imegcorp.com

PROJECT #22006633.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

100%

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

B

IM

/A u d ie L

M u rp h y V

A M e d ic a l C e n te r

(S A

M

E P

T

.0

V A

-S a n A n to n io

T

X -E

H R

M

C .r v t

/1

/2

:2

:5

A

M

E000

ELECTRICAL COVERSHEET

Awen Solutions Group

4196 Merchant Plaza, Suite 711

Woodbridge, VA 22192

06/09/2023

EHRM INFRASTRUCTURE

UPGRADES 1

Audie L Murphy VA Medical Center (San Antonio) 7400 Merton Minter, San Antonio, TX 78229

671-22-700

ELECTRICAL SHEET INDEX

E000 ELECTRICAL COVERSHEET

E001 SITE PLAN - ELECTRICAL

E400 ELECTRICAL SCHEDULES

E401 ELECTRICAL SCHEDULES

E402 ELECTRICAL SCHEDULES

E500 ELECTRICAL DETAILS

E501 ELECTRICAL DETAILS

ED100 GROUND FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL

ED101 1ST FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL

ED102 2ND FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL

ED103 3RD FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL

ED104 4TH FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL

ED105 5TH FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL

ED106 6TH FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL

ED107 7TH FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL

EN100 GROUND FLOOR PLAN - ELECTRICAL - OVERALL

EN100.5 GROUND FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE

EN101 1ST FLOOR PLAN - ELECTRICAL - OVERALL

EN101.5 1ST FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE

EN102 2ND FLOOR PLAN - ELECTRICAL - OVERALL

EN102.5 2ND FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE

EN103 3RD FLOOR PLAN - ELECTRICAL - OVERALL

EN103.5 3RD FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE

EN104 4TH FLOOR PLAN - ELECTRICAL - OVERALL

EN104.5 4TH FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE

EN105 5TH FLOOR PLAN - ELECTRICAL - OVERALL

EN105.5 5TH FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE

EN106 6TH FLOOR PLAN - ELECTRICAL - OVERALL

EN106.5 6TH FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE

EN107 7TH FLOOR PLAN - ELECTRICAL - OVERALL

EN107.5 7TH FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE

EN190 BLDG 4 PLAN - ELECTRICAL

EN400 GROUND FLOOR - TR L010.2 - ELECTRICAL - ENLARGED PLANS

EN401 GROUND FLOOR - TR 030 - ELECTRICAL - ENLARGED PLANS

EN402 GROUND FLOOR - TR GB126.1 - ELECTRICAL - ENLARGED PLANS

EN403 GROUND FLOOR - TR F004 - ELECTRICAL - ENLARGED PLANS

EN404 GROUND FLOOR - TR C015.1 - ELECTRICAL - ENLARGED PLANS

EN405 GROUND FLOOR - TR 020 - ELECTRICAL - ENLARGED PLANS

EN406 GROUND FLOOR - TR 1A138 - ELECTRICAL - ENLARGED PLANS

EN407 GROUND LEVEL – H031 – ELECTRICAL – ENLARGED PLANS

EN410 1ST FLOOR - TR S101R - ELECTRICAL - ENLARGED PLANS

EN411 1ST FLOOR - TR J104 - ELECTRICAL - ENLARGED PLANS

EN412 1ST FLOOR - TR H118.2 - ELECTRICAL - ENLARGED PLANS

EN413 1ST FLOOR - TR 105 - ELECTRICAL - ENLARGED PLANS

EN414 1ST FLOOR - TR G101 - ELECTRICAL - ENLARGED PLANS

EN415 1ST FLOOR - TR 157 - ELECTRICAL - ENLARGED PLANS

EN416 1ST FLOOR - TR P125 - ELECTRICAL - ENLARGED PLANS

EN417 1ST FLOOR - TR 2A137 - ELECTRICAL - ENLARGED PLANS

EN418 1ST FLOOR - TR Y102.7 - ELECTRICAL - ENLARGED PLANS

EN419 1ST FLOOR - TR T119.2 - ELECTRICAL - ENLARGED PLANS

EN420 2ND FLOOR - TR R201 - ELECTRICAL - ENLARGED PLANS

EN421 2ND FLOOR - TR SP238 - ELECTRICAL - ENLARGED PLANS

EN422 2ND FLOOR - TR Z221.28A - ELECTRICAL - ENLARGED PLANS

EN423 2ND FLOOR - TR E221 - ELECTRICAL - ENLARGED PLANS

EN424 2ND FLOOR - TR A200 - ELECTRICAL - ENLARGED PLANS

EN425 2ND FLOOR - TR 258 - ELECTRICAL - ENLARGED PLANS

EN430 3RD FLOOR - TR C301.1 - ELECTRICAL - ENLARGED PLANS

EN431 3RD FLOOR - TR D320 - ELECTRICAL - ENLARGED PLANS

EN440 4TH FLOOR - TR C402 - ELECTRICAL - ENLARGED PLANS

EN450 5TH FLOOR - TR C511 - ELECTRICAL - ENLARGED PLANS

EN460 6TH FLOOR - TR C602 - ELECTRICAL - ENLARGED PLANS

EN470 7TH FLOOR - TR C702.1 - ELECTRICAL - ENLARGED PLANS

EN490 ELECTRICAL - ENLARGED PLAN

EN491 1ST FLOOR - IT SUITE DEMO - ELECTRICAL - ENLARGED PLAN

EN492 1ST FLOOR - DATA CENTER - ELECTRICAL - ENLARGED PLAN

EN493 1ST FLOOR - DATA CENTER - ELECTRICAL - ENLARGED PLAN

EN494 1ST FLOOR - EXISTING DATA CENTER - ELECTRICAL - EXISTING ENLARGED PLAN

EN495 1ST FLOOR - EXISTING DATA CENTER - ELECTRICAL - NEW ENLARGED PLAN

EN496 1ST FLOOR - EXISTING DATA CENTER - ELECTRICAL - NEW ENLARGED PLAN

EN497 ELECTRICAL RISER DIAGRAM

EN498 ELECTRICAL DETAILS

EN499 ELECTRICAL SCHEDULES

GRAND TOTAL: 72

Revisions: Date: SHEET 183 of 431

ClarkGarrettAIANCARB Snapshot

COMMUNITY LIVING CENTER

POLYTRAUMA

MAIN HOSPITAL

CANTEENMAIN ENTRANCE

TOWER

SCI

BLDG

BLDG

MERTON MINTER

M E

R T

O N

M

IN

T E

R

VON SCHEELE RD W

U

R

ZB

A C

H R

D

W

URZBACH R

D

M

ELRO

SE HO

LM

G

REE RD

M

ELRO

SE HO

LM

G

REE RD MERTON M

IN

TER

EN490

GENERATOR BUILDING

NUMBER AND ADDRESS

SUITE NO.

CITY, STATE ZIP CODE

P: 555.555.555 F: 555.555.5555 www.imegcorp.com

PROJECT #22006633.00

60 60 120

1" = 60'-0"

FEETSCALE

P L A

N N

O R

T H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

100%

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

B

IM

/A u d ie L

M u rp h y V

A M e d ic a l C e n te r

(S A

M

E P

T

.0

V A

-S a n A n to n io

T

X -E

H R

M

C .r v t

/1

/2

:2

:0

A

M

E001

SITE PLAN - ELECTRICAL

Awen Solutions Group

4196 Merchant Plaza, Suite 711

Woodbridge, VA 22192

06/09/2023

EHRM INFRASTRUCTURE

UPGRADES 1

Audie L Murphy VA Medical Center (San Antonio) 7400 Merton Minter, San Antonio, TX 78229

671-22-700

N O R

HT

1" = 60'-0"

SITE PLAN - ELECTRICAL - OVERALL

GENERAL NOTES:

A. CONDUIT ROUTING INDICATED FOR REFERENCE ONLY. CONTRACTOR IS

RESPONSIBLE FOR SUBMITTING CONDUIT ROUTING COORDINATION DRAWINGS

WITH ELECTRICAL EQUIPMENT/RACEWAY SUBMITTAL FOR REVIEW.

COORDINATION DRAWINGS SHALL INCLUDE BENDS, PULLBOXES, CONDUIT

BODIES, PENETRATIONS (INCLUDING RELEVANT LIFE SAFETY SMOKE AND FIRE

BARRIERS), ETC. CONTRACTOR SHALL INCLUDE EXISTING CONDITIONS WHERE

NECESSARY TO CONVEY ROUTING INFORMATION, MAINTAIN NEC REQUIRED

CLEARANCES AND ACCESSIBILITY TO ALL EXISTING PULLBOXES, JUNCTION

BOXES, ETC. TO REMAIN. ELECTRICAL EQUIPMENT SUBMITTALS WILL NOT BE

APPROVED WITHOUT CONDUIT ROUTING COORDINATION DRAWINGS.

B. SITE PLAN INTENT IS TO DISPLAY APPROXIMATE CONDUIT ROUTING FOR NEW

ELECTRICAL FEEDERS BETWEEN BUILDINGS. SEE BUILDING FOR NEW

ELECTRICAL FEEDERS RUN ENTIRELY WITHIN WITHIN A SINGLE BUILDING.

C. ALL CONDUITS ON THE ELECTRICAL PLANS ARE SHOWN AS SINGLE LINE FOR

CLARITY BUT MAY CONSIST OF MULTIPLE CONDUITS IN PARALLEL. REFER TO ALL

PARTIAL ELECTRICAL RISER DRAWINGS FOR CONDUIT CONFIGURATIONS.

D. REFER TO SPECIFICATIONS AND SHEET E500 FOR DUCT BANK CONSTRUCTION

DETAIL.

KEYNOTE:

1. FROM GENERATOR BUILDING; PROPOSED ROUTING CONDUIT ON EXTERIOR

WALL, VERIFY IF EXISTING EXTERIOR JUNCTION BOX MAY BE UTILZED, IF

REQUIRED PROVIDE NEW J-BOX. REFER TO ENLARGED VIEW FOR

CONTINUATION.

2. PROPOSED ROUTING OF UNDERGROUND EMERGENCY FEEDER DUCT BANK, FED

FROM EXISTING SWBD AGDP-3 TO NEW ATB-OIT-B TRANSFER SWITCH, REFER TO

EN497 ELECTRICAL RISER DIAGRAM FOR CONDUIT AND CONDUCTOR SIZE.

ROUTE NEW ELECTRICAL DUCT BANK ADJACENT TO EXISTING DUCT BANK.

3. UNDERGROUND EMERGENCY FEEDER; PROPOSED PENETRATING THROUGH

EXTERIOR WALL BELOW GRADE INTO SUB-LEVEL PIPING SPACE INTO INTERIOR

BUILDING SPACE (INSULATION SHOP) THEN TO GROUND LEVEL WAREHOUSE

SPACE. FIELD COORDINATE EXACT ROUTING WITH OTHER UTILITIES. REFER TO

EN100 FOR CONTINUATION.

Revisions: Date: SHEET 184 of 431

NUMBER AND ADDRESS

SUITE NO.

CITY, STATE ZIP CODE

P: 555.555.555 F: 555.555.5555 www.imegcorp.com

PROJECT #22006633.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

100%

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

B

IM

/A u d ie L

M u rp h y V

A M e d ic a l C e n te r

(S A

M

E P

T

.0

V A

-S a n A n to n io

T

X -E

H R

M

C .r v t

/1

/2

:2

:0

A

M

E400

ELECTRICAL SCHEDULES

Awen Solutions Group

4196 Merchant Plaza, Suite 711

Woodbridge, VA 22192

06/09/2023

EHRM INFRASTRUCTURE

UPGRADES 1

Audie L Murphy VA Medical Center (San Antonio) 7400 Merton Minter, San Antonio, TX 78229

671-22-700

REFER TO SPECIFICATION SECTIONS LED LIGHTING 26 51 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

INTERIOR CORRELATED COLOR TEMPERATURE 4000K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.

CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY.