S02 - Attachment 1(d) - 671-22-700 DRAWINGS Electrical.pdf
PDF 12 MB Posted
- Attached to
- EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS) Federal contract opportunity
- Solicitation number
- 36C77623B0064
About this file
This document provides details for a federal contract opportunity for infrastructure upgrades at the San Antonio VA Medical Center. The solicitation number is 36C77623B0064 and is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. It is a SDVOSB set-aside for construction services under NAICS code 236220. The opportunity involves upgrading electrical systems as denoted by the 12MB Attachment 1(d) file which contains drawings for the electrical work. Responses are due based on the timing outlined in the full solicitation. The award is expected to be made to a service-disabled veteran-owned small business to complete infrastructure upgrades to electrical systems at the San Antonio VA Medical Center facility.
View the file
Other files for this federal contract opportunity
Show all 50
EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
SV SOLENOID VALVE
ABBR: DESCRIPTION:
TYP TYPICAL
C CONDUIT
UON UNLESS OTHERWISE NOTED
GFI GROUND FAULT INTERRUPTER
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
SV SOLENOID VALVE
TYP TYPICAL
C CONDUIT
UON UNLESS OTHERWISE NOTED
GFI GROUND FAULT INTERRUPTER
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
SV SOLENOID VALVE
TYP TYPICAL
C CONDUIT
UON UNLESS OTHERWISE NOTED
GFI GROUND FAULT INTERRUPTER
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
SV SOLENOID VALVE
TYP TYPICAL
C CONDUIT
UON UNLESS OTHERWISE NOTED
GFI GROUND FAULT INTERRUPTER
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
SV SOLENOID VALVE
TYP TYPICAL
C CONDUIT
UON UNLESS OTHERWISE NOTED
GFI GROUND FAULT INTERRUPTER
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
SV SOLENOID VALVE
TYP TYPICAL
C CONDUIT
UON UNLESS OTHERWISE NOTED
GFI GROUND FAULT INTERRUPTER
ELECTRICAL INSTALLATION NOTES:
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON
THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH
PHASE.
3. EMERGENCY AND CRITICAL, EQUIPMENT BRANCH WIRING FOR FEEDERS AND BRANCH
CIRCUITS SHALL BE ROUTED IN SEPARATE RACEWAY, JUNCTION BOXES, PULL BOXES, AND
CABINETS. WIRING FOR EACH BRANCH SHALL BE INDEPENDENT FROM OTHER BRANCHES,
INCLUDING THE NORMAL BRANCH.
4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
5. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM
FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND
OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED. MOUNT
EXTERIOR LOCATED RECEPTACLES WITH WHILE-IN-USE COVERS AT +20" FROM FINISHED
GRADE (CENTER DIMENSIONS) TO MAINTAIN INSTALLATION ADA COMPLIANCE.
6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
7. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)
EXCEPT WHERE OTHERWISE NOTED.
8. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED
FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE
NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.
9. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS SHALL
BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.
10. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT
LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.
PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE
FURNITURE AND/OR EQUIPMENT.
11. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
13. ALL WELDING SHALL BE ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS.
CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER CERTIFICATES QUALIFYING
EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE
RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT THE CONTRACTOR'S EXPENSE, OF
ANY WELDERS ASSIGNED TO THE JOB.
14. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE
IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
15. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
16. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR
COLOR/LABEL REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.
LUMINAIRE SYMBOL KEY
SYMBOL: DESCRIPTION:
NORMAL BRANCH LUMINAIRE
EMERGENCY BRANCH LUMINAIRE
'NL' - UNSWITCHED FOR NIGHT LIGHT
'*E' - BATTERY BACK-UP
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING
CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAY AND CONDUITS
BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING
FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND
SHALL NOTIFY THE CONSTRUCTION MANAGER PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF
ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.
CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
ELECTRICAL PHASING NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER
TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS
FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.
MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL
DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT
THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER
TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS
FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.
MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL
DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT
THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER
TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS
FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.
MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL
DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT
THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER
TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS
FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.
MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL
DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT
THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER
TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS
FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.
MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL
DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT
THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER
TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS
FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK.
MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL
DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT
THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
(SEE TECHNOLOGY CALBING PLAN)
'TAG'-D TAGS WITH DASH 'D' INDICATES THE REFERENCED OBJECT IS DEMOLISHED
(SEE TECHNOLOGY CALBING PLAN)
TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
C MOUNT AT CEILING
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
R MOUNT IN SURFACE RACEWAY
EWC ELECTRIC WATER COOLER
ELECTRICAL GENERAL NOTES:
LUMINAIRE
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
LUMINAIRE KEY:
DEVICE KEY:
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
C MOUNT AT CEILING
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
R MOUNT IN SURFACE RACEWAY
EWC ELECTRIC WATER COOLER
LUMINAIRE
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
LUMINAIRE KEY:
DEVICE KEY:
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
C MOUNT AT CEILING
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
R MOUNT IN SURFACE RACEWAY
EWC ELECTRIC WATER COOLER
LUMINAIRE
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
LUMINAIRE KEY:
DEVICE KEY:
1. "NL" INDICATES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.
2. SHADED LUMINAIRE OR DEVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN
EMERGENCY CIRCUIT.
3. REFER TO SHEET E400 FOR LUMINAIRE SCHEDULE.
4. { L##} DENOTES THE LIGHTING SEQUENCE OF OPERATIONS FOR THIS SPACE. REFER TO
SHEET E400.
5. VACANCY/OCCUPANCY SENSOR LAYOUT: SENSORS ARE SHOWN ON THE PLANS FOR
DESIGN INTENT AND MAY NOT REPRESENT EVERY DEVICE. PROVIDE MANUFACTURER
SPECIFIC FLOOR PLAN LAYOUTS SHOWING LOCATION, ORIENTATION, AND COVERAGE AREA
OF EACH CONTROL DEVICE, SENSOR, AND CONTROLLER/INTERFACE. AREAS REQUIRING
MULTIPLE SENSOR DEVICES FOR APPROPRIATE COVERAGE, SUBMIT SPECIFIC
MANUFACTURER-APPROVED SENSOR LAYOUT AS AN OVERLAY DIRECTLY ON THE PROJECT
DRAWINGS, EITHER IN PRINT OR APPROVED ELECTRONIC FORM.
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
C MOUNT AT CEILING
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
R MOUNT IN SURFACE RACEWAY
EWC ELECTRIC WATER COOLER
LUMINAIRE
F1 = FIXTURE TAG
1 = CIRCUIT NUMBER
a = SWITCH DESIGNATION
NL = SUBSCRIPT (IF APPLICABLE)
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: F1 / 1 / a / NL
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
LUMINAIRE KEY:
DEVICE KEY:
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
C MOUNT AT CEILING
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
R MOUNT IN SURFACE RACEWAY
EWC ELECTRIC WATER COOLER
LUMINAIRE
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
LUMINAIRE KEY:
DEVICE KEY:
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
C MOUNT AT CEILING
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
R MOUNT IN SURFACE RACEWAY
EWC ELECTRIC WATER COOLER
LUMINAIRE
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
LUMINAIRE KEY:
DEVICE KEY:
TYPICAL REMODEL:
1. ALL LUMINAIRES SHOWN TO BE DEMOLISHED SHALL BE DISPOSED OF IF NOT REQUIRED BY
OWNER FOR ATTIC STOCK. CONFIRM WITH OWNER PRIOR TO DISPOSAL IF THE LAMPS,
LENS OR SUBSET OF LUMINAIRES SHOULD BE TURNED OVER FOR ATTIC STOCK.
2. REMOVE EXISTING LUMINAIRES AND WALL SWITCHES WHERE SHOWN. LOCATE AND
IDENTIFY ELECTRICAL CIRCUIT SERVING REMOVED LUMINAIRES FOR REUSE WITH NEW
DEVICES.
3. COORDINATE HOURS OF ACCESS WITH OWNER.
4. EXISTING EMERGENCY LIGHTING AND EXIT SIGNAGE SHALL REMAIN.
5. REMOVE EXISTING LUMINAIRE AND PREPARE FOR INSTALLATION OF NEW LUMINAIRE IN
NEW LOCATION.
6. MATCH EXISTING FACEPLATE FINISH AND TYPE FOR ALL LOCATIONS WHERE NEW WALL
CONTROL DEVICE IS BEING INSTALLED.
7. WHERE WALL SWITCH DEVICE IS REMOVED AND NOT REPLACED. PROVIDE WITH BLANK
SWITCH PLATE.
8. EXPOSED 3/4" CONDUIT TO NEW OR EXISTING FIXTURES OR DEVICES IS ACCEPTABLE AS
LONG AS IT IS INSTALLED IN A NEAT AND ORDERLY METHOD AND MEETS ADOPTED CODES.
COORDINATE NEW RUNS WITH OWNER PRIOR TO INSTALLATIONS.
9. REUSE EXISTING CONDUIT, WIRE, CONTROL AND JUNCTION BOXES. PROVIDE NEW IF
REQUIRED TO INSTALL THE NEW LUMINAIRE.
10. PROVIDE (1) UNSWITCHED LEG FROM PANEL SERVING THE EMERGENCY FIXTURES TO THE
SENSOR LEG SERVING THE NEW BATTERY BACK UP IN NEW LUMINAIRES.
11. CONNECT NEW LUMINAIRES TO CIRCUIT THAT SERVED PREVIOUSLY REMOVED LUMINAIRE
USING 2#12 &1#12 GND IN 3/4" C. EXTEND CONDUIT AND CONDUCTORS AS REQUIRED TO
MAKE CONNECTION. CONDUIT IN GOOD CONDITION SHALL BE REUSED IN PLACE.
12. NEW OCCUPANCY SENSORS TO BE INSTALLED IN A MANUAL ON/AUTO OFF'
CONFIGURATION.
13. REPLACE CEILING TILES WITH LIKE IN AREAS WITH A REDUCTION IN LUMINAIRE. REUSE
EXISTING CEILING TILES WHERE APPLICABLE. PROVIDE NEW TO MATCH EXISTING IF
REQUIRED. ADJUST AND MOVE AIR RETURN GRILLS AS REQUIRED TO COORDINATE WITH
REVISED LUMINAIRE LAYOUT IN AREAS WITH A LAYIN CEILING.
14. COORDINATE LOCATIONS OF NEW LUMINAIRES WITH EXISTING DUCT, PIPING, STRUCTURAL
AND CEILING MOUNTED DEVICES.
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26 DUPLEX GFI RECEPTACLE, 125V
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26
26 27 26
ELECTRICAL SYMBOL LIST
SYMBOL: SPEC
SECTION:
DESCRIPTION:
REFER TO LUMINAIRE
SCHEDULE
DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V
26 09 23 WALL SWITCH
O
OC
D
CIRCUIT BREAKER - SURFACE MOUNTED.
REFER TO DISC/STA SCHEDULE
26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.
REFER TO DISC/STA SCHEDULE
ELECTRICAL SYMBOL LIST
SYMBOL: SPEC
SECTION:
DESCRIPTION:
26 05 33 JUNCTION BOX
J
J
26 05 33 ELECTRICAL CONNECTION
E
E
26 24 16 PANELBOARD - SURFACE MOUNT
26 24 16 PANELBOARD - RECESS MOUNT
26 05 26 GROUND BUSGB
26 05 26 INTERSYSTEM BONDING TERMINATIONIBT
ELECTRICAL SYMBOL LIST
SYMBOL: SPEC
SECTION:
DESCRIPTION:
26 22 00 TRANSFORMER. REFER TO
TRANSFORMER SCHEDULE
26 09 23
26 09 23
26 09 23
26 09 23
WALL SWITCH - THREE WAY
DIMMER - LED
OCCUPANCY SENSOR - DUAL TECHNOLOGY
26 29 21
ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO
TRANSFER SWITCH SCHEDULE
26 36 00
DP-# DISTRIBUTION PANEL 26 24 16
26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE
RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00
SB-# SWITCHBOARD 26 24 13
ELECTRICAL EQUIPMENT TAGS
TAG: DESCRIPTION:
RELATED
SPECIFICATION
26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26 DUPLEX GFI RECEPTACLE, 125V
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26
26 27 26
REFER TO LUMINAIRE
SCHEDULE
DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V
26 09 23 WALL SWITCH
O
D
CIRCUIT BREAKER - SURFACE MOUNTED.
REFER TO DISC/STA SCHEDULE
26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.
REFER TO DISC/STA SCHEDULE
26 05 33 JUNCTION BOX
26 05 33 ELECTRICAL CONNECTION
26 24 16 PANELBOARD - SURFACE MOUNT
26 24 16 PANELBOARD - RECESS MOUNT
26 05 26 GROUND BUS
26 05 26 INTERSYSTEM BONDING TERMINATION
26 22 00 TRANSFORMER. REFER TO
TRANSFORMER SCHEDULE
26 09 23
26 09 23
26 09 23
26 09 23
SWITCH - OCCUPANCY SENSOR WALL SWITCH
WALL SWITCH - THREE WAY
DIMMER - LED
OCCUPANCY SENSOR - DUAL TECHNOLOGY
26 29 21
ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO
TRANSFER SWITCH SCHEDULE
26 36 00
DP-# DISTRIBUTION PANEL 26 24 16
26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE
RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00
SB-# SWITCHBOARD 26 24 13
RELATED
SPECIFICATION
26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26 DUPLEX GFI RECEPTACLE, 125V
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26
26 27 26
REFER TO LUMINAIRE
SCHEDULE
DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V
26 09 23 WALL SWITCH
O
D
CIRCUIT BREAKER - SURFACE MOUNTED.
REFER TO DISC/STA SCHEDULE
26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.
REFER TO DISC/STA SCHEDULE
26 05 33 JUNCTION BOX
26 05 33 ELECTRICAL CONNECTION
26 24 16 PANELBOARD - SURFACE MOUNT
26 24 16 PANELBOARD - RECESS MOUNT
26 05 26 GROUND BUS
26 05 26 INTERSYSTEM BONDING TERMINATION
26 22 00 TRANSFORMER. REFER TO
TRANSFORMER SCHEDULE
26 09 23
26 09 23
26 09 23
26 09 23
SWITCH - OCCUPANCY SENSOR WALL SWITCH
WALL SWITCH - THREE WAY
DIMMER - LED
OCCUPANCY SENSOR - DUAL TECHNOLOGY
26 29 21
ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO
TRANSFER SWITCH SCHEDULE
26 36 00
DP-# DISTRIBUTION PANEL 26 24 16
26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE
RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00
SB-# SWITCHBOARD 26 24 13
RELATED
SPECIFICATION
INDUSTRIAL LUMINAIRE
26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26 DUPLEX GFI RECEPTACLE, 125V
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26
26 27 26
WP
REFER TO LUMINAIRE
SCHEDULE
2 X 4 TROFFER
DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V
26 09 23 WALL SWITCH
O
D
CIRCUIT BREAKER - SURFACE MOUNTED.
REFER TO DISC/STA SCHEDULE
26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.
REFER TO DISC/STA SCHEDULE
26 05 33 JUNCTION BOX
26 05 33 ELECTRICAL CONNECTION
26 24 16 PANELBOARD - SURFACE MOUNT
26 24 16 PANELBOARD - RECESS MOUNT
26 05 26 GROUND BUS
26 05 26
26 22 00 TRANSFORMER. REFER TO
TRANSFORMER SCHEDULE
BUSWAY SYSTEM - WITH END-FEED AND
BUSWAY TAP SHOWN
26 09 23
26 09 23
26 09 23
26 09 23
DIMMER - LED
OCCUPANCY SENSOR - DUAL TECHNOLOGY
26 29 21
ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO
TRANSFER SWITCH SCHEDULE
26 36 00
DP-# DISTRIBUTION PANEL 26 24 16
26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE
RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00
SB-# SWITCHBOARD 26 24 13
RELATED
SPECIFICATION
26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26 DUPLEX GFI RECEPTACLE, 125V
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26
26 27 26
REFER TO LUMINAIRE
SCHEDULE
DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V
26 09 23 WALL SWITCH
O
D
CIRCUIT BREAKER - SURFACE MOUNTED.
REFER TO DISC/STA SCHEDULE
26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.
REFER TO DISC/STA SCHEDULE
26 05 33 JUNCTION BOX
26 05 33 ELECTRICAL CONNECTION
26 24 16 PANELBOARD - SURFACE MOUNT
26 24 16 PANELBOARD - RECESS MOUNT
26 05 26 GROUND BUS
26 05 26 INTERSYSTEM BONDING TERMINATION
26 22 00 TRANSFORMER. REFER TO
TRANSFORMER SCHEDULE
26 09 23
26 09 23
26 09 23
26 09 23
SWITCH - OCCUPANCY SENSOR WALL SWITCH
WALL SWITCH - THREE WAY
DIMMER - LED
OCCUPANCY SENSOR - DUAL TECHNOLOGY
26 29 21
ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO
TRANSFER SWITCH SCHEDULE
26 36 00
DP-# DISTRIBUTION PANEL 26 24 16
26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE
RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00
SB-# SWITCHBOARD 26 24 13
RELATED
SPECIFICATION
26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26 DUPLEX GFI RECEPTACLE, 125V
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26
26 27 26
REFER TO LUMINAIRE
SCHEDULE
DUPLEX GFI WEATHERPROOF RECEPTACLE, 125V
26 09 23 WALL SWITCH
O
D
CIRCUIT BREAKER - SURFACE MOUNTED.
REFER TO DISC/STA SCHEDULE
26 29 21 CIRCUIT BREAKER - FLUSH MOUNTED.
REFER TO DISC/STA SCHEDULE
26 05 33 JUNCTION BOX
26 05 33 ELECTRICAL CONNECTION
26 24 16 PANELBOARD - SURFACE MOUNT
26 24 16 PANELBOARD - RECESS MOUNT
26 05 26 GROUND BUS
26 05 26 INTERSYSTEM BONDING TERMINATION
26 22 00 TRANSFORMER. REFER TO
TRANSFORMER SCHEDULE
26 09 23
26 09 23
26 09 23
26 09 23
SWITCH - OCCUPANCY SENSOR WALL SWITCH
WALL SWITCH - THREE WAY
DIMMER - LED
OCCUPANCY SENSOR - DUAL TECHNOLOGY
26 29 21
ATS-# AUTOMATIC TRANSFER SWITCH, REFER TO
TRANSFER SWITCH SCHEDULE
26 36 00
DP-# DISTRIBUTION PANEL 26 24 16
26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE
RA-ATS-# REMOTE ANNUNCIATOR FOR ATS 26 36 00
SB-# SWITCHBOARD 26 24 13
RELATED
SPECIFICATION26 27 2626 27 26 RECEPTACLE, LOCKING L21-30R, 120/208V, 3PH26 27 2626 27 2626 27 2626 27 26
EMERGENCY STOP, N.O. CONTACTEPO EMERGENCY STOP, N.O. CONTACTEMERGENCY STOP, N.O. CONTACTEMERGENCY STOP, N.O. CONTACTEMERGENCY STOP, N.O. CONTACTEMERGENCY STOP, N.O. CONTACT
26 25 11
26 27 26 RECEPTACLE, LOCKING L5-30R, 125V
RECEPTACLE, LOCKING L5-20R, 125V
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR
VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER
NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT
PANEL
AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM
FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET
S
FA-120 28 31 00 S
S FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR
# = EQUIP OR SYSTEM
S
AS
ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE
DETECTION
H
H
FA-140 28 31 00 FIRE ALARM HEAT DETECTOR
BLANK = COMBINATION RATE OF RISE
/ FIXED TEMP
AT = ATTIC (LOCATED IN)
F = FIXED TEMP
RC = RATE COMPENSATED
X - EXPLOSION PROOF
FA-130 28 31 00 FIRE ALARM MANUAL PULL STATIONF
FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVERFT
FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING
OR WALL MOUNT
# = CANDELA RATING.
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
F
F
FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING
OR WALL MOUNTED
M = MINI-HORN
S = SLEEPING / PATIENT ROOM
FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND
VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
S
S
FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR
WALL MOUNTED
FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL
ALARM DEVICE, CEILING OR WALL MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
M
M
FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)
AND VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-241 28 31 00 FIRE ALARM REMOTE INDICATORRI
FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR
W/ TEST SWITCH
RT
FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
KB = KNOX BOX
FS
FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
PIV = POST INDICATOR VALVE
TS
FA-161 28 31 00 FIRE ALARM ADDRESSABLE
CONTROL MODULE
BLANK = REFER TO PLANS
LC = LIGHTING CONTROL
OVERRIDE
DH = DOOR HOLD OPEN
PD = HOLD OPEN OVERRIDE
CM
FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY OTHERS, WIRED BY E.C.)
DH - ELECTROMAGNETIC DOOR
HOLD DEVICE
PD - HOLD OPEN OVERRIDE
CONNECTION
FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY E.C.)
DH
FA-250 28 31 00 FIRE ALARM SMOKE OR
FIRE/SMOKE DAMPER CONTROL
WITH DETECTOR, AND
ADDRESSABLE MODULE, AND
REMOTE INDICATOR (WITH TEST
SWITCH WHEN APPLICABLE)
# = INDICATES EQUIP OR SYSTEM
FSD
COMMON AND
SEQUENCE OF
OPERATION
SUBSCRIPTS
FACP-# 28 31 00 FIRE ALARM CONTROL PANEL
FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR
VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER
NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT
PANEL
AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM
FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET
FA-120 28 31 00 FIRE ALARM SMOKE DETECTOR,
CEILING OR WALL MOUNT
BLANK - PHOTOELECTRIC
AT = ATTIC (LOCATED IN)
CO = COMBINATION SMOKE / CARBON
MONOXIDE
COH = COMBINATION SMOKE /
CARBON MONOXIDE / HEAT
COS = COMBINATION SMOKE /
CARBON MONOXIDE / STROBE
H = COMBINATION SMOKE / HEAT
DETECTOR
ID = IN DUCT DETECTOR
FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR
# = EQUIP OR SYSTEM
ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE
DETECTION
FA-140 28 31 00 FIRE ALARM HEAT DETECTOR
BLANK = COMBINATION RATE OF RISE
/ FIXED TEMP
AT = ATTIC (LOCATED IN)
F = FIXED TEMP
RC = RATE COMPENSATED
X - EXPLOSION PROOF
FA-130 28 31 00 FIRE ALARM MANUAL PULL STATION
FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVER
FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING
OR WALL MOUNT
# = CANDELA RATING.
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING
OR WALL MOUNTED
M = MINI-HORN
S = SLEEPING / PATIENT ROOM
FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND
VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR
WALL MOUNTED
FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL
ALARM DEVICE, CEILING OR WALL MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)
AND VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-241 28 31 00 FIRE ALARM REMOTE INDICATOR
FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR
W/ TEST SWITCH
FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
KB = KNOX BOX
FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
PIV = POST INDICATOR VALVE
FA-161 28 31 00 FIRE ALARM ADDRESSABLE
CONTROL MODULE
BLANK = REFER TO PLANS
LC = LIGHTING CONTROL
OVERRIDE
DH = DOOR HOLD OPEN
PD = HOLD OPEN OVERRIDE
FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY OTHERS, WIRED BY E.C.)
DH - ELECTROMAGNETIC DOOR
HOLD DEVICE
PD - HOLD OPEN OVERRIDE
CONNECTION
FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY E.C.)
FA-250 28 31 00 FIRE ALARM SMOKE OR
FIRE/SMOKE DAMPER CONTROL
WITH DETECTOR, AND
ADDRESSABLE MODULE, AND
REMOTE INDICATOR (WITH TEST
SWITCH WHEN APPLICABLE)
# = INDICATES EQUIP OR SYSTEM
FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR
VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER
NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT
PANEL
AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM
FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET
FA-120 28 31 00
FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR
# = EQUIP OR SYSTEM
ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE
DETECTION
FA-140 28 31 00 FIRE ALARM HEAT DETECTOR
BLANK = COMBINATION RATE OF RISE
/ FIXED TEMP
AT = ATTIC (LOCATED IN)
F = FIXED TEMP
RC = RATE COMPENSATED
X - EXPLOSION PROOF
FA-130 28 31 00 FIRE ALARM MANUAL PULL STATION
FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVER
FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING
OR WALL MOUNT
# = CANDELA RATING.
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING
OR WALL MOUNTED
M = MINI-HORN
S = SLEEPING / PATIENT ROOM
FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND
VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR
WALL MOUNTED
FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL
ALARM DEVICE, CEILING OR WALL MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)
AND VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-241 28 31 00 FIRE ALARM REMOTE INDICATOR
FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR
W/ TEST SWITCH
FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
KB = KNOX BOX
FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
PIV = POST INDICATOR VALVE
FA-161 28 31 00 FIRE ALARM ADDRESSABLE
CONTROL MODULE
BLANK = REFER TO PLANS
LC = LIGHTING CONTROL
OVERRIDE
DH = DOOR HOLD OPEN
PD = HOLD OPEN OVERRIDE
FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY OTHERS, WIRED BY E.C.)
DH - ELECTROMAGNETIC DOOR
HOLD DEVICE
PD - HOLD OPEN OVERRIDE
CONNECTION
FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY E.C.)
FA-250 28 31 00 FIRE ALARM SMOKE OR
FIRE/SMOKE DAMPER CONTROL
WITH DETECTOR, AND
ADDRESSABLE MODULE, AND
REMOTE INDICATOR (WITH TEST
SWITCH WHEN APPLICABLE)
# = INDICATES EQUIP OR SYSTEM
SUBSCRIPTS: TYPE / PROGRAMMING
WG = WIRE GUARD IS REQUIRED
W = WEATHERPROOF
CR = COMPUTER ROOM
E = ELEVATOR RECALL
D = HVAC CONTROL
DH = DOOR HOLD RELEASE
DIPS = DUAL INTERLOCK PREACTION SYS
FD = FIRE DOOR RELEASE
SW = STAIRWELL
# = 15, 30, 75, 110, 177 CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR
VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER
NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT
PANEL
AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM
FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET
FA-120 28 31 00
FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR
# = EQUIP OR SYSTEM
ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE
DETECTION
FA-140 28 31 00 FIRE ALARM HEAT DETECTOR
BLANK = COMBINATION RATE OF RISE
/ FIXED TEMP
AT = ATTIC (LOCATED IN)
F = FIXED TEMP
RC = RATE COMPENSATED
X - EXPLOSION PROOF
FA-130 28 31 00 FIRE ALARM MANUAL PULL STATION
FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVER
FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING
OR WALL MOUNT
# = CANDELA RATING.
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING
OR WALL MOUNTED
M = MINI-HORN
S = SLEEPING / PATIENT ROOM
FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND
VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR
WALL MOUNTED
FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL
ALARM DEVICE, CEILING OR WALL MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)
AND VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-241 28 31 00 FIRE ALARM REMOTE INDICATOR
FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR
W/ TEST SWITCH
FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
KB = KNOX BOX
FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
PIV = POST INDICATOR VALVE
FA-161 28 31 00 FIRE ALARM ADDRESSABLE
CONTROL MODULE
BLANK = REFER TO PLANS
LC = LIGHTING CONTROL
OVERRIDE
DH = DOOR HOLD OPEN
PD = HOLD OPEN OVERRIDE
FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY OTHERS, WIRED BY E.C.)
DH - ELECTROMAGNETIC DOOR
HOLD DEVICE
PD - HOLD OPEN OVERRIDE
CONNECTION
FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY E.C.)
FA-250 28 31 00 FIRE ALARM SMOKE OR
FIRE/SMOKE DAMPER CONTROL
WITH DETECTOR, AND
ADDRESSABLE MODULE, AND
REMOTE INDICATOR (WITH TEST
SWITCH WHEN APPLICABLE)
# = INDICATES EQUIP OR SYSTEM
FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR
VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER
NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT
PANEL
AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM
FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET
FA-120 28 31 00
FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR
# = EQUIP OR SYSTEM
ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE
DETECTION
FA-140 28 31 00 FIRE ALARM HEAT DETECTOR
BLANK = COMBINATION RATE OF RISE
/ FIXED TEMP
AT = ATTIC (LOCATED IN)
F = FIXED TEMP
RC = RATE COMPENSATED
X - EXPLOSION PROOF
FA-130 28 31 00 FIRE ALARM MANUAL PULL STATION
FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVER
FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING
OR WALL MOUNT
# = CANDELA RATING.
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING
OR WALL MOUNTED
M = MINI-HORN
S = SLEEPING / PATIENT ROOM
FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND
VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR
WALL MOUNTED
FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL
ALARM DEVICE, CEILING OR WALL MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)
AND VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-241 28 31 00 FIRE ALARM REMOTE INDICATOR
FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR
W/ TEST SWITCH
FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
KB = KNOX BOX
FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
PIV = POST INDICATOR VALVE
FA-161 28 31 00 FIRE ALARM ADDRESSABLE
CONTROL MODULE
BLANK = REFER TO PLANS
LC = LIGHTING CONTROL
OVERRIDE
DH = DOOR HOLD OPEN
PD = HOLD OPEN OVERRIDE
FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY OTHERS, WIRED BY E.C.)
DH - ELECTROMAGNETIC DOOR
HOLD DEVICE
PD - HOLD OPEN OVERRIDE
CONNECTION
FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY E.C.)
FA-250 28 31 00 FIRE ALARM SMOKE OR
FIRE/SMOKE DAMPER CONTROL
WITH DETECTOR, AND
ADDRESSABLE MODULE, AND
REMOTE INDICATOR (WITH TEST
SWITCH WHEN APPLICABLE)
# = INDICATES EQUIP OR SYSTEM
FAA-# 28 31 00 FIRE ALARM ANNUNCIATOR
VCC-# 28 31 00 DIGITIZED VOICE COMMAND CENTER
NAC-# 28 31 00 NOTIFICATION APPLIANCE CIRCUIT
PANEL
AMP-# 28 31 00 AMPLIFIER RACK, FIRE ALARM
FATC-# 28 31 00 FIRE ALARM TERMINAL CABINET
FA-120 28 31 00
FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR
# = EQUIP OR SYSTEM
ASSD-# 28 31 50 FIRE ALARM AIR SAMPLING SMOKE
DETECTION
FA-140 28 31 00 FIRE ALARM HEAT DETECTOR
BLANK = COMBINATION RATE OF RISE
/ FIXED TEMP
AT = ATTIC (LOCATED IN)
F = FIXED TEMP
RC = RATE COMPENSATED
X - EXPLOSION PROOF
FA-130 28 31 00 FIRE ALARM MANUAL PULL STATION
FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVER
FA-200 28 31 00 FIRE ALARM VISUAL ALARM DEVICE, CEILING
OR WALL MOUNT
# = CANDELA RATING.
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING
OR WALL MOUNTED
M = MINI-HORN
S = SLEEPING / PATIENT ROOM
FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND
VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-220 28 31 00 AUDIO (SPEAKER) ALARM DEVICE, CEILING OR
WALL MOUNTED
FA-221 28 31 00 COMBINATION AUDIO (VOICE) AND VISUAL
ALARM DEVICE, CEILING OR WALL MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-230 28 31 00 EMERGENCY COMBINATION AUDIO (VOICE)
AND VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FA-241 28 31 00 FIRE ALARM REMOTE INDICATOR
FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR
W/ TEST SWITCH
FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
KB = KNOX BOX
FA-261 28 31 00 FIRE ALARM TAMPER SWITCH TO
MONITOR SPRINKLER SYSTEM
BLANK = REFER TO PLANS
PIV = POST INDICATOR VALVE
FA-161 28 31 00 FIRE ALARM ADDRESSABLE
CONTROL MODULE
BLANK = REFER TO PLANS
LC = LIGHTING CONTROL
OVERRIDE
DH = DOOR HOLD OPEN
PD = HOLD OPEN OVERRIDE
FA-271 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY OTHERS, WIRED BY E.C.)
DH - ELECTROMAGNETIC DOOR
HOLD DEVICE
PD - HOLD OPEN OVERRIDE
CONNECTION
FA-270 28 31 00 FIRE ALARM DOOR HOLD DEVICE
(BY E.C.)
FA-250 28 31 00 FIRE ALARM SMOKE OR
FIRE/SMOKE DAMPER CONTROL
WITH DETECTOR, AND
ADDRESSABLE MODULE, AND
REMOTE INDICATOR (WITH TEST
SWITCH WHEN APPLICABLE)
# = INDICATES EQUIP OR SYSTEM
THE LINE TYPES SHOWN ARE FOR THE CONVENIENCE OF THE CONTRACTOR. THE CONTRACTOR
SHALL VERIFY RATINGS WITH THE LATEST SET OF ARCHITECTURAL PLANS AND FURNISH ALL
MATERIALS REQUIRED TO COMPLY WITH THOSE RATINGS WHETHER SHOWN OR NOT.
ALL [FLOOR, FLOOR CEILING, AND ROOF CEILING] ASSEMBLIES SHALL BE DESIGNATED AS [1], [2], [3], [4] HOUR FIRE [/SMOKE], BARRIER(S), UNLESS NOTED OTHERWISE ON THE PLANS. RATINGS
WERE ACQUIRED FROM THE ARCHITECTURAL PLANS DATED [**/**/**].
FIRE / SMOKE BARRIER DESIGNATIONS
1 HOUR FIRE BARRIER
SMOKE BARRIER
1 HOUR FIRE/SMOKE BARRIER
OR SHAFT ENCLOSURE
2 HOUR FIRE/SMOKE BARRIER
OR SHAFT ENCLOSURE
3 HOUR FIRE/SMOKE BARRIER
4 HOUR FIRE/SMOKE BARRIER
SMOKE PARTITION
FIRE PARTITION
2 HOUR FIRE BARRIER OR WALL
3 HOUR FIRE BARRIER OR WALL
4 HOUR FIRE BARRIER OR WALL
PANELBOARD NOTATION
PANELBOARD CIRCUIT BREAKER LOCATIONS
480/277V - A C E G I K M O Q S U W Y AA...AAA...
120/208V - B D F H J L N P R T V X Z BB...BBB...
FLOOR ON WHICH PANEL IS LOCATED
L = NORMAL POWER E = EMERGENCY POWER C = CRITICAL POWER
L 1 BB-#
NUMBER AND ADDRESS
SUITE NO.
CITY, STATE ZIP CODE
P: 555.555.555 F: 555.555.5555 www.imegcorp.com
PROJECT #22006633.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
100%
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
B
IM
/A u d ie L
M u rp h y V
A M e d ic a l C e n te r
(S A
M
E P
T
.0
V A
-S a n A n to n io
T
X -E
H R
M
C .r v t
/1
/2
:2
:5
A
M
E000
ELECTRICAL COVERSHEET
Awen Solutions Group
4196 Merchant Plaza, Suite 711
Woodbridge, VA 22192
06/09/2023
EHRM INFRASTRUCTURE
UPGRADES 1
Audie L Murphy VA Medical Center (San Antonio) 7400 Merton Minter, San Antonio, TX 78229
671-22-700
ELECTRICAL SHEET INDEX
E000 ELECTRICAL COVERSHEET
E001 SITE PLAN - ELECTRICAL
E400 ELECTRICAL SCHEDULES
E401 ELECTRICAL SCHEDULES
E402 ELECTRICAL SCHEDULES
E500 ELECTRICAL DETAILS
E501 ELECTRICAL DETAILS
ED100 GROUND FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL
ED101 1ST FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL
ED102 2ND FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL
ED103 3RD FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL
ED104 4TH FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL
ED105 5TH FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL
ED106 6TH FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL
ED107 7TH FLOOR DEMOLITION PLAN - ELECTRICAL - OVERALL
EN100 GROUND FLOOR PLAN - ELECTRICAL - OVERALL
EN100.5 GROUND FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE
EN101 1ST FLOOR PLAN - ELECTRICAL - OVERALL
EN101.5 1ST FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE
EN102 2ND FLOOR PLAN - ELECTRICAL - OVERALL
EN102.5 2ND FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE
EN103 3RD FLOOR PLAN - ELECTRICAL - OVERALL
EN103.5 3RD FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE
EN104 4TH FLOOR PLAN - ELECTRICAL - OVERALL
EN104.5 4TH FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE
EN105 5TH FLOOR PLAN - ELECTRICAL - OVERALL
EN105.5 5TH FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE
EN106 6TH FLOOR PLAN - ELECTRICAL - OVERALL
EN106.5 6TH FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE
EN107 7TH FLOOR PLAN - ELECTRICAL - OVERALL
EN107.5 7TH FLOOR PLAN - ELECTRICAL - INTERSTITIAL SPACE
EN190 BLDG 4 PLAN - ELECTRICAL
EN400 GROUND FLOOR - TR L010.2 - ELECTRICAL - ENLARGED PLANS
EN401 GROUND FLOOR - TR 030 - ELECTRICAL - ENLARGED PLANS
EN402 GROUND FLOOR - TR GB126.1 - ELECTRICAL - ENLARGED PLANS
EN403 GROUND FLOOR - TR F004 - ELECTRICAL - ENLARGED PLANS
EN404 GROUND FLOOR - TR C015.1 - ELECTRICAL - ENLARGED PLANS
EN405 GROUND FLOOR - TR 020 - ELECTRICAL - ENLARGED PLANS
EN406 GROUND FLOOR - TR 1A138 - ELECTRICAL - ENLARGED PLANS
EN407 GROUND LEVEL – H031 – ELECTRICAL – ENLARGED PLANS
EN410 1ST FLOOR - TR S101R - ELECTRICAL - ENLARGED PLANS
EN411 1ST FLOOR - TR J104 - ELECTRICAL - ENLARGED PLANS
EN412 1ST FLOOR - TR H118.2 - ELECTRICAL - ENLARGED PLANS
EN413 1ST FLOOR - TR 105 - ELECTRICAL - ENLARGED PLANS
EN414 1ST FLOOR - TR G101 - ELECTRICAL - ENLARGED PLANS
EN415 1ST FLOOR - TR 157 - ELECTRICAL - ENLARGED PLANS
EN416 1ST FLOOR - TR P125 - ELECTRICAL - ENLARGED PLANS
EN417 1ST FLOOR - TR 2A137 - ELECTRICAL - ENLARGED PLANS
EN418 1ST FLOOR - TR Y102.7 - ELECTRICAL - ENLARGED PLANS
EN419 1ST FLOOR - TR T119.2 - ELECTRICAL - ENLARGED PLANS
EN420 2ND FLOOR - TR R201 - ELECTRICAL - ENLARGED PLANS
EN421 2ND FLOOR - TR SP238 - ELECTRICAL - ENLARGED PLANS
EN422 2ND FLOOR - TR Z221.28A - ELECTRICAL - ENLARGED PLANS
EN423 2ND FLOOR - TR E221 - ELECTRICAL - ENLARGED PLANS
EN424 2ND FLOOR - TR A200 - ELECTRICAL - ENLARGED PLANS
EN425 2ND FLOOR - TR 258 - ELECTRICAL - ENLARGED PLANS
EN430 3RD FLOOR - TR C301.1 - ELECTRICAL - ENLARGED PLANS
EN431 3RD FLOOR - TR D320 - ELECTRICAL - ENLARGED PLANS
EN440 4TH FLOOR - TR C402 - ELECTRICAL - ENLARGED PLANS
EN450 5TH FLOOR - TR C511 - ELECTRICAL - ENLARGED PLANS
EN460 6TH FLOOR - TR C602 - ELECTRICAL - ENLARGED PLANS
EN470 7TH FLOOR - TR C702.1 - ELECTRICAL - ENLARGED PLANS
EN490 ELECTRICAL - ENLARGED PLAN
EN491 1ST FLOOR - IT SUITE DEMO - ELECTRICAL - ENLARGED PLAN
EN492 1ST FLOOR - DATA CENTER - ELECTRICAL - ENLARGED PLAN
EN493 1ST FLOOR - DATA CENTER - ELECTRICAL - ENLARGED PLAN
EN494 1ST FLOOR - EXISTING DATA CENTER - ELECTRICAL - EXISTING ENLARGED PLAN
EN495 1ST FLOOR - EXISTING DATA CENTER - ELECTRICAL - NEW ENLARGED PLAN
EN496 1ST FLOOR - EXISTING DATA CENTER - ELECTRICAL - NEW ENLARGED PLAN
EN497 ELECTRICAL RISER DIAGRAM
EN498 ELECTRICAL DETAILS
EN499 ELECTRICAL SCHEDULES
GRAND TOTAL: 72
Revisions: Date: SHEET 183 of 431
ClarkGarrettAIANCARB Snapshot
COMMUNITY LIVING CENTER
POLYTRAUMA
MAIN HOSPITAL
CANTEENMAIN ENTRANCE
TOWER
SCI
BLDG
BLDG
MERTON MINTER
M E
R T
O N
M
IN
T E
R
VON SCHEELE RD W
U
R
ZB
A C
H R
D
W
URZBACH R
D
M
ELRO
SE HO
LM
G
REE RD
M
ELRO
SE HO
LM
G
REE RD MERTON M
IN
TER
EN490
GENERATOR BUILDING
NUMBER AND ADDRESS
SUITE NO.
CITY, STATE ZIP CODE
P: 555.555.555 F: 555.555.5555 www.imegcorp.com
PROJECT #22006633.00
60 60 120
1" = 60'-0"
FEETSCALE
P L A
N N
O R
T H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
100%
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
B
IM
/A u d ie L
M u rp h y V
A M e d ic a l C e n te r
(S A
M
E P
T
.0
V A
-S a n A n to n io
T
X -E
H R
M
C .r v t
/1
/2
:2
:0
A
M
E001
SITE PLAN - ELECTRICAL
Awen Solutions Group
4196 Merchant Plaza, Suite 711
Woodbridge, VA 22192
06/09/2023
EHRM INFRASTRUCTURE
UPGRADES 1
Audie L Murphy VA Medical Center (San Antonio) 7400 Merton Minter, San Antonio, TX 78229
671-22-700
N O R
HT
1" = 60'-0"
SITE PLAN - ELECTRICAL - OVERALL
GENERAL NOTES:
A. CONDUIT ROUTING INDICATED FOR REFERENCE ONLY. CONTRACTOR IS
RESPONSIBLE FOR SUBMITTING CONDUIT ROUTING COORDINATION DRAWINGS
WITH ELECTRICAL EQUIPMENT/RACEWAY SUBMITTAL FOR REVIEW.
COORDINATION DRAWINGS SHALL INCLUDE BENDS, PULLBOXES, CONDUIT
BODIES, PENETRATIONS (INCLUDING RELEVANT LIFE SAFETY SMOKE AND FIRE
BARRIERS), ETC. CONTRACTOR SHALL INCLUDE EXISTING CONDITIONS WHERE
NECESSARY TO CONVEY ROUTING INFORMATION, MAINTAIN NEC REQUIRED
CLEARANCES AND ACCESSIBILITY TO ALL EXISTING PULLBOXES, JUNCTION
BOXES, ETC. TO REMAIN. ELECTRICAL EQUIPMENT SUBMITTALS WILL NOT BE
APPROVED WITHOUT CONDUIT ROUTING COORDINATION DRAWINGS.
B. SITE PLAN INTENT IS TO DISPLAY APPROXIMATE CONDUIT ROUTING FOR NEW
ELECTRICAL FEEDERS BETWEEN BUILDINGS. SEE BUILDING FOR NEW
ELECTRICAL FEEDERS RUN ENTIRELY WITHIN WITHIN A SINGLE BUILDING.
C. ALL CONDUITS ON THE ELECTRICAL PLANS ARE SHOWN AS SINGLE LINE FOR
CLARITY BUT MAY CONSIST OF MULTIPLE CONDUITS IN PARALLEL. REFER TO ALL
PARTIAL ELECTRICAL RISER DRAWINGS FOR CONDUIT CONFIGURATIONS.
D. REFER TO SPECIFICATIONS AND SHEET E500 FOR DUCT BANK CONSTRUCTION
DETAIL.
KEYNOTE:
1. FROM GENERATOR BUILDING; PROPOSED ROUTING CONDUIT ON EXTERIOR
WALL, VERIFY IF EXISTING EXTERIOR JUNCTION BOX MAY BE UTILZED, IF
REQUIRED PROVIDE NEW J-BOX. REFER TO ENLARGED VIEW FOR
CONTINUATION.
2. PROPOSED ROUTING OF UNDERGROUND EMERGENCY FEEDER DUCT BANK, FED
FROM EXISTING SWBD AGDP-3 TO NEW ATB-OIT-B TRANSFER SWITCH, REFER TO
EN497 ELECTRICAL RISER DIAGRAM FOR CONDUIT AND CONDUCTOR SIZE.
ROUTE NEW ELECTRICAL DUCT BANK ADJACENT TO EXISTING DUCT BANK.
3. UNDERGROUND EMERGENCY FEEDER; PROPOSED PENETRATING THROUGH
EXTERIOR WALL BELOW GRADE INTO SUB-LEVEL PIPING SPACE INTO INTERIOR
BUILDING SPACE (INSULATION SHOP) THEN TO GROUND LEVEL WAREHOUSE
SPACE. FIELD COORDINATE EXACT ROUTING WITH OTHER UTILITIES. REFER TO
EN100 FOR CONTINUATION.
Revisions: Date: SHEET 184 of 431
NUMBER AND ADDRESS
SUITE NO.
CITY, STATE ZIP CODE
P: 555.555.555 F: 555.555.5555 www.imegcorp.com
PROJECT #22006633.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
100%
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
B
IM
/A u d ie L
M u rp h y V
A M e d ic a l C e n te r
(S A
M
E P
T
.0
V A
-S a n A n to n io
T
X -E
H R
M
C .r v t
/1
/2
:2
:0
A
M
E400
ELECTRICAL SCHEDULES
Awen Solutions Group
4196 Merchant Plaza, Suite 711
Woodbridge, VA 22192
06/09/2023
EHRM INFRASTRUCTURE
UPGRADES 1
Audie L Murphy VA Medical Center (San Antonio) 7400 Merton Minter, San Antonio, TX 78229
671-22-700
REFER TO SPECIFICATION SECTIONS LED LIGHTING 26 51 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
INTERIOR CORRELATED COLOR TEMPERATURE 4000K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.
CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .