S02 - Attachment 6(c) - Mechanical Cut Sheets - Clean Agent Data Sheet.pdf

PDF 26 KB Posted

Attached to
EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS)
Solicitation number
36C77623B0064
Issued by

About this file

This document includes a mechanical cut sheet and data sheet for a NOVEC 1230 Fire Protection Fluid. The cut sheet provides technical specifications for the NOVEC 1230 fluid, including its chemical formula, molecular weight, boiling point, freezing point, density in both liquid and gas states, heat of vaporization, and solubility in water. It describes the fluid as an effective total flooding clean agent for fire protection that leaves no residue and is suitable for use in occupied spaces. The fluid is listed for use in SAPPHIRE Suppression Systems and complies with NFPA 2001 standards for clean agent fire extinguishing systems.

The related federal contract opportunity is a solicitation from the Department of Veterans Affairs Technology Acquisition Center Austin for infrastructure upgrades at the EHRM facility in San Antonio, Texas. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses and has a NAICS code of 236220 for commercial and institutional building construction. It does not specify pricing terms or response dates.

View the file

Other files

File Type Posted
S07 - Bid Abstract Page 2_OF1419A_EHRM San Antonio_06SEP2023.pdf PDF
S07 - Bid Abstract Page 1_OF1419_EHRM San Antonio_6SEP2023.pdf PDF
Amendment 0005_36C77623B0064_31AUG2023.pdf PDF
S02 - Attchment 24 - EHRM San Antonio Bid Breakdown Table_31AUG2023.xlsx XLSX spreadsheet
Amendment 0004_36C77623B0064_25AUG2023.pdf PDF
S02 - Attachment 21 - Addendum 1 - Technology.pdf PDF
S02 - Attachment 19 - 02821321 Asbestos Roofing Abatement.pdf PDF
S02 - Attachment 16 - STX Addendum 1.pdf PDF
S02 - Attachment 22 - SF 25 Performance Bond Form.pdf PDF
S02 - Attachment 15 - STX Addendum 1 (Composite).pdf PDF
S02 - Attachment 18 - 320523 Cement and Concrete for Exterior Improvements.pdf PDF
S02 - Attachment 23 - SF 25A Payment Bond Form.pdf PDF
S02 - Attachment 20 - Addendum 1 - Mechanical.pdf PDF
S02 - Attachment 17 - 075100 Roofing Repair.pdf PDF
Amendment 0003 Attachment Warranty RoofCAD-VA San Antonio-RFI Q100.pdf PDF
Amendment 0003_36C77623B0064_23AUG2023.pdf PDF
Amendment 0002_36C77623B0064_18AUG2023.pdf PDF
S02 - Attachment 6(e) - Mechanical Cut Sheets - Data Center CRAC - N 1 Operation (8000 cfm).pdf PDF
S02 - Attachment 6(d) - Mechanical Cut Sheets - Data Center CRAC Dimensions.pdf PDF
S02 - Attachment 6(a) - Mechanical Cut Sheets - 3.0 Ton Split System.pdf PDF
S02 - Attachment 6(b) - Mechanical Cut Sheets - Data Center CRAC - Normal Operation (6000 cfm).pdf PDF
S02 - Attachment 6(f) - Mechanical Cut Sheets - 2.0 Ton Split System.pdf PDF
Site Visit Attendees Sign-In Sheet_11AUG2023_EHRM San Antonio.xlsx XLSX spreadsheet
Pre-bid Site Visit Sign-in Sheet_11AUG2023.pdf PDF
Amendment 0001_36C77623B0064_02AUG2023.pdf PDF
S02 - Attachment 7(a) - Technology Cut Sheets - Part 1 of 11 APC.pdf PDF
S02 - Attachment 14(a) - Asbestos Survey Results 1st-4th Floors.pdf PDF
S02 - Attachment 7(g) - Technology Cut Sheets - Part 7 of 11 Panduit.pdf PDF
S02 - Attachment 5 - Electrical Cut Sheets.pdf PDF
S02 - Attachment 4 - 230501 SAT_EHRM_100 percent final TechnicalReport.pdf PDF
S02 - Attachment 7(k) - Technology Cut Sheets - Part 11 of 11 Hubbell.pdf PDF
S02 - Attachment 1(c) - 671-22-700 DRAWINGS Mechanical.pdf PDF
S02 - Attachment 11 - Wage Determination_Bexar CountyTX_14APR2023.pdf PDF
S02 - Attachment 9 - Contractor Safety and Environmental Record Form.docx DOCX document
S02 - Attachment 12 - Submittal Register ENG Form 4288-R.pdf PDF
S02 - Attachment 7(h) - Technology Cut Sheets - Part 8 of 11 Axis.pdf PDF
S02 - Attachment 13 - VA OEHRM Site Infrastructure and EUD Reqmts 2.0.pdf PDF
S02 - Attachment 1(e) - 671-22-700 DRAWINGS Technology.pdf PDF
Solicitation 36C77623B0064_28JUL2023.pdf PDF
S02 - Attachment 1(d) - 671-22-700 DRAWINGS Electrical.pdf PDF
S02 - Attachment 1(f) 671-22-700 DRAWINGS Physical Security.pdf PDF
S02 - Attachment 2 - 671-22-700 100 percent final BID SPECIFICATIONS.pdf PDF
S02 - Attachment 8(b) - OIT-InfrastrucStdTelecomSpaces_Part 2 of 3.pdf PDF
S02 - Attachment 7(d) - Technology Cut Sheets - Part 4 of 11 CPI Cabinet.pdf PDF
S02 - Attachment 7(j) - Technology Cut Sheets - Part 10 of 11 HID.pdf PDF
S02 - Attachment 7(b) - Technology Cut Sheets - Part 2 of 11 Corning.pdf PDF
S02 - Attachment 7(e) - Technology Cut Sheets - Part 5 of 11 Leviton.pdf PDF
S02 - Attachment 8(a) - OIT-InfrastrucStdTelecomSpaces_Part 1 of 3.pdf PDF
S02 - Attachment 7(i) - Technology Cut Sheets - Part 9 of 11 Cablofil.pdf PDF
S02 - Attachment 7(f) - Technology Cut Sheets - Part 6 of 11 Ortronics.pdf PDF
Show 40 more

Latest 50 of 58 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

n UL/ULC listed as a component of the SAPPHIRE® Suppression System n Effective, total flooding performance on Class A, B, and C fires n Long-term, sustainable alternative to Halons, HFCs and PFCs n Clean agent suitable for protection of high-value assets

3M™ NOVEC™ 1230 Fire Protection Fluid, referenced as FK-5-1-12 in NFPA 2001 and ISO 14250, is a fluorinated ketone (or fluoroketone) with a chemical structure of CF3CF2C(O)CF(CF3)2. It is a clear, color-less, odorless, liquid that is super-pressurized with nitrogen and stored in high-pressure cylinders as part of a SAPPHIRE Suppression System.

Although stored in liquid form, NOVEC 1230 fluid will turn to a gas upon discharge making it an effective total flooding agent for a variety of hazards. As a clean agent, it leaves no residue behind and will not affect sensitive high-value electronics. Typical applications include:

n Telecommunication switch rooms n Computer and electronic control rooms n Hazards aboard ships n Critical military applications

NOVEC 1230 fluid has 0.0 ozone depletion potential, an atmospheric lifetime of just five days, and a global warming potential of 1.0.

NOVEC 1230 fluid is registered with the U.S. EPA under TSCA (Toxic Substances Control Act) and ELINCS (European List of Notified Chemical Substances). It has met the requirements of registration under SNAP (Significant New Alternatives Policy) and is approved for use as an alternative to Halon 1301 for flooding applications in occupied spaces.

NOVEC 1230 fluid suppresses fires via its cooling effect. It has been tested and listed at a design concentration of 4.2% (Class A, B, and C hazards) in conjunction with a SAPPHIRE total flooding system. With the NOAEL (No Observable Adverse Effect Level) measured at 10%, NOVEC 1230 fluid provides a substantial margin of safety in occupied spaces.

NOVEC 1230 Fire Protection Fluid complies with NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems. It is listed by Underwriters Laboratories (UL) and Underwriters Laboratories of Canada (ULC) as a component of the SAPPHIRE™ Suppression System. Containers meet the applicable U.S. Department of Transportation (DOT) specifications.

Chemical formula . . . . . . . . . . . . . . CF3CF2C(O)CF(CF3)2 Molecular weight. . . . . . . . . . . . . . . 316.04

Boiling point @ 1 atm . . . . . . . . . . . . 49.2 °C (120.6 °F)

Freezing point . . . . . . . . . . . . . . . . –108 °C (–162.4 °F)

Density, sat. liquid . . . . . . . . . . . . . . 1.60 g/ml (99.9 lbm/ft3)

Density, gas 1 atm . . . . . . . . . . . . . . 0.0136 g/ml (0.851 lbm/ft3)

Specific volume, 1 atm . . . . . . . . . . . 0.0733 m3/kg (1.175 ft3/lb)

Liquid viscosity @ 0 °C/25 °C . . . . . . . . 0.56/0.39 centistokes

Heat of vaporization @ BP . . . . . . . . . 88.1 kJ/kg (37.9 BTU/lb)

Solubility of H2O in NOVEC 1230 liquid . . . <0.001% by wt.

Vapor pressure @ 25 °C . . . . . . . . . . 0.40 bar (5.85 psig)

Dielectric strength relative to N2 @ 25 °C. . 2.3

PHYSICAL PROPERTIES

APPROVALS

PERFORMANCE

ENVIRONMENTAL IMPACT

APPLICATIONS

DESCRIPTION

FEATURES

Copyright ©2008 Ansul Incorporated Form No. F-2003127-2

Ansul Incorporated Marinette, WI 54143-2542

715-735-7411 www.ansul.com

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

3M and NOVEC are trademarks of 3M Company.

3M™ NOVEC™ 1230 FIRE PROTECTION FLUID

Data/Specifications

File details come from the government source that posted it. Updated .