S02 - Attachment 1(c) - 671-22-700 DRAWINGS Mechanical.pdf
PDF 9 MB Posted
- Attached to
- EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS) Federal contract opportunity
- Solicitation number
- 36C77623B0064
About this file
This solicitation is for EHRM San Antonio Infrastructure Upgrades Construction services with a SDVOSB set-aside and NAICS code 236220. The solicitation seeks mechanical, electrical, and plumbing construction services at the Audie L Murphy VA Medical Center in San Antonio, Texas, including infrastructure upgrades, mechanical equipment replacement, and data center renovations. The period of performance is 720 calendar days from NTP. The government will issue a firm-fixed-price task order to the responsible SDVOSB offeror whose offer conforming to the solicitation will be most advantageous to the government. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The closing date for proposals is listed as July 15, 2023.
View the file
Other files for this federal contract opportunity
Show all 50
EHRM San Antonio Infrastructure Upgrades Construction (SDVOSB Set-Aside and 236220 NAICS) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H
C
C
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.
CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR
FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO
THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS
RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN
THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES
PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE
BASIS OF DESIGN.
3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL
APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.
4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874
5. INVERT ELEVATIONS ARE FROM EXISTING DRAWINGS AND MAY NOT BE ACCURATE. VERIFY
ALL ELEVATIONS BEFORE BEGINNING WORK.
6. VERIFY UNDERGROUND PIPE SIZES, INVERT ELEVATIONS, AND LOCATIONS PRIOR TO
BEGINNING ANY WORK.
7. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO
PLUMBING FIXTURES.
8. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL
SCOPE OF ITEMS TO BE REMOVED. REFER TO SPECIFICATION SECTION 22 05 05 FOR
ADDITIONAL DEMOLITION INFORMATION.
9. P.C. SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK
UNLESS NOTED OTHERWISE. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL
INFORMATION.
PLUMBING GENERAL NOTES:
1. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN.
2. INSTALL ALL REFRIGERANT LIQUID AND SUCTION PIPING SIZED PER EQUIPMENT
MANUFACTURER RECOMMENDATIONS.
PIPING GENERAL NOTES:
1. UNLESS NOTED OTHERWISE, THE SIZE OF EACH BRANCH DUCT TO AN AIR TERMINAL SHALL
MATCH THE INLET SIZE.
2. ALIGN TEMPERATURE SENSORS WITH LIGHT SWITCHES AND WHEN IN CLOSE PROXIMITY TO
EACH OTHER.
VENTILATION GENERAL NOTES:
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE
CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR
EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE
GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE
PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS
PANELS PRIOR TO BIDDING.
10. SEAL ALL PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE.
PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH
WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,
PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE
TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS
WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL
RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,
PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.
15. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL
EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT
LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,
TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.
16. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH
OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE
EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO
THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED
ELECTRICAL SPACE INCLUDING; DUCTWORK, PIPING, ETC.
17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE
CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE
CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS
BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE
FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD
CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND
SHALL NOTIFY THE ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF
ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.
CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH
NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL
EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT
DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL
SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT
REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT
THAT HAS BEEN REMOVED.
MECHANICAL PHASING NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE
CONTROL.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO
CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S INSTRUCTIONS FOR
MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL,
ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE
MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND
METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE
ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF
PROJECT.
4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP
ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
(SEE TECHNOLOGY CALBING PLAN)
'TAG'-D TAGS WITH DASH 'D' INDICATES THE REFERENCED OBJECT IS DEMOLISHED
(SEE TECHNOLOGY CALBING PLAN)
TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
THE LINE TYPES SHOWN ARE FOR THE CONVENIENCE OF THE CONTRACTOR. THE CONTRACTOR
SHALL VERIFY RATINGS WITH THE LATEST SET OF ARCHITECTURAL PLANS AND FURNISH ALL
MATERIALS REQUIRED TO COMPLY WITH THOSE RATINGS WHETHER SHOWN OR NOT.
ALL [FLOOR, FLOOR CEILING, AND ROOF CEILING] ASSEMBLIES SHALL BE DESIGNATED AS [1], [2], [3], [4] HOUR FIRE [/SMOKE], BARRIER(S), UNLESS NOTED OTHERWISE ON THE PLANS. RATINGS
WERE ACQUIRED FROM THE ARCHITECTURAL PLANS DATED [**/**/**].
FIRE / SMOKE BARRIER DESIGNATIONS
1 HOUR FIRE BARRIER
SMOKE BARRIER
1 HOUR FIRE/SMOKE BARRIER
OR SHAFT ENCLOSURE
2 HOUR FIRE/SMOKE BARRIER
OR SHAFT ENCLOSURE
3 HOUR FIRE/SMOKE BARRIER
4 HOUR FIRE/SMOKE BARRIER
SMOKE PARTITION
FIRE PARTITION
2 HOUR FIRE BARRIER OR WALL
3 HOUR FIRE BARRIER OR WALL
4 HOUR FIRE BARRIER OR WALL
TEMPERATURE CONTROLS CONTRACTORT.C.C.
ASBESTOS ABATEMENT CONTRACTOR
FIRE PROTECTION CONTRACTORF.P.C.
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
E.O.R ENGINEER OF RECORD
C.O.R. CONTRACTING OFFICER'S REPRESENTATIVE
PLUMBING SLOPE REQUIREMENTS:
INTERIOR:
SANITARY WASTE: ≤2-1/2”ø=1/4” PER FOOT ≥3”ø = 1/8” PER FOOT ≥8”ø = 1/16” PER FOOT
CONDENSATE AND INDIRECT DRAINAGE: 1/8” PER FOOT
DOMESTIC WATER: NO SPECIFIC PITCH, PITCH TO FIXTURES
BASED ON PLUMBING CODE: IPC-2018
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE
CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS
REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID
TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS
RESPONSIBLE FOR COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND
IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL
TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER IS THE
BASIS OF DESIGN.
3. CENTER SPRINKLERS IN CEILING TILES IN BOTH DIRECTIONS IN ALL AREAS. IN AREAS
WITH 2’X4’ CEILING TILES CENTERING USING A 2’X2’ CEILING PATTERN IS ACCEPTABLE.
SPRINKLER HEADS SHALL BE ALIGNED WITH OTHER SPRINKLER HEADS, LIGHTING,
DIFFUSERS, AND ANY OTHER FEATURES IN THE CEILING.
4. NEW SPRINKLERS SHALL BE QUICK RESPONSE TYPE, UNLESS OTHERWISE NOTED.
CONTRACTOR SHALL NOT MIX STANDARD RESPONSE SPRINKLERS WITH QUICK
RESPONSE SPRINKLERS IN UNPARTITIONED SPACES.
5. FIRE PROTECTION PIPE ROUTING IS SHOWN FOR GENERAL LAYOUT. DETERMINE EXACT
NUMBER OF SPRINKLERS, PIPE SIZING, AND PIPE ROUTING.
6. THE FIRE PROTECTION SYSTEM SHALL BE DESIGNED TO MEET OWNER'S INSURANCE
COMPANY STANDARDS WHERE APPLICABLE. THE MORE STRINGENT OF THE OWNER'S
INSURANCE UNDERWRITER'S DESIGN CRITERIA AND THE NFPA STANDARDS SHALL BE
USED.
7. WHERE FEASIBLE INSTALL PIPES HIGH AS POSSIBLE TO AVOID CONFLICT WITH OTHER
DISCIPLINES.
8. PROVIDE INTERMEDIATE TEMPERATURE SPRINKLER HEADS WHERE REQUIRED BY NFPA
13 UNLESS OTHERWISE NOTED.
9. FINAL HEAD LOCATION, TYPE AND FINISH SHALL BE REVIEWED AND APPROVED BY THE
ARCHITECT.
10. A GRAPHIC ANNUNCIATOR PANEL SHALL BE PROVIDED TO INCLUDE AREAS BEING
PROVIDED WITH A CLEAN AGENT SYSTEM WHICH HAS CONCEALED AREAS.
11. EXACT LOCATION OF THE ALL PANELS SHALL BE VERIFIED ON SITE AND COORDINATED
WITH THE ELECTRICAL CONTRACTOR.
12. PAINT ALL EXPOSED PIPING TO MATCH BACKGROUND OR AS DIRECTED BY THE
ARCHITECT.
13. THE OWNER MUST BE NOTIFIED PRIOR TO EACH AND EVERY DRAINING OR RECHARGING
OF THE SPRINKLER SYSTEM.
14. THE CONTRACTOR SHALL PREPARE A COORDINATED SET OF SHOP DRAWINGS AND
SHALL OBTAIN APPROVAL FROM THE AUTHORITIES HAVING JURISDICTION AND THE
LOCAL FIRE DEPARTMENT PRIOR TO ANY INSTALLATION.
15. DRAWING SHOW LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT,
ETC. AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
16. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,
SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW
ALL DRAWINGS. INCLUDING THOSE OF OTHER TRADES.
FIRE PROTECTION GENERAL NOTES:
OCCUPANCY SENSORO
HUMIDISTAT SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
H HUMIDISTAT / SENSOR
TEMPERATURE SENSOR WITH WELL
T
THERMOMETER WITH WELL (DIAL TYPE)T
THERMOMETER WITH WELL (FILLED TYPE)
DIRECTION OF AIR FLOW
FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RISE IN DIRECTION OF AIR FLOWR
DUCT CAP
DROP IN DIRECTION OF AIR FLOWD
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST/RELIEF AIR DUCT SECTION
4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION
SD-1
6/115
AIR TERMINAL PROPERTIES SYMBOL
NECK SIZE/CFM
TERMINAL AIR BOX (REFER TO SCHEDULE)###
### TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
HUMIDIFIERH
OPPOSED BLADE DAMPER (REFER TO SCHEDULE)
PARALLEL BLADE DAMPER (REFER TO SCHEDULE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR/MONITORP
PRESSURE SENSOR (DUCT MOUNTED)P
THERMOSTAT/SENSORT
TEMPERATURE SENSORT
THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURET
MECHANICAL SYMBOL LIST
SYMBOL: DESCRIPTION:
AIRFLOW MEASUREMENT SYMBOL
XX - AHU SYMBOL
Y - SEQUENTIAL NUMBER
XX-Y
NOT ALL SYMBOLS MAY APPLY.
FAN POWERED TERMINAL AIR BOX w/REHEAT COIL
(REFER TO SCHEDULE)
CONTROL VALVE (TWO-WAY)
PITCH PIPE IN DIRECTION
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
THROTTLING VALVE
AUTOMATIC BALANCING VALVE
MIXING VALVE
CONTROL VALVE (THREE-WAY)
SOLENOID VALVE
CHECK VALVE
SAFETY/RELIEF VALVE
PRESSURE REDUCING VALVE (LIQUID/GAS)
PRESSURE REDUCING VALVE (STEAM)
TRIPLE DUTY VALVE (ANGLE TYPE)
TRIPLE DUTY VALVE (IN-LINE TYPE)
VACUUM BREAKER
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE AND HOSE CONNECTION WITH CAP
BASKET STRAINER
FLEXIBLE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
SUCTION DIFFUSER WITH SUPPORT FOOT
AUTOMATIC AIR VENT
MANUAL AIR VENT
DRAIN VALVE WITH HOSE CONNECTION AND CAP
BOILER BLOW DOWNBD
BOILER FEED WATERBF
COMPRESSED AIRCA
HEATING/CHILLED WATER RETURNHCR
HIGH PRESSURE CLEAN STEAM (>125 TO 250 PSIG)HCS
CONDENSER WATER RETURNCR
CONDENSER WATER SUPPLYCS
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
NATURAL GASG
GLYCOL WATER RETURNGWR
GLYCOL WATER SUPPLYGWS
REFRIGERANT HOT GASHG
HIGH PRESSURE CONDENSATE (>125 TO 250 PSIG)HPC
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
REFRIGERANT LIQUIDLIQ
LOW PRESSURE CONDENSATE (0 TO 15 PSIG)LPC
FUEL OIL RETURNFOR
FUEL OIL SUPPLYFOS
PUMPED CONDENSATEPC
PUMPED DISCHARGEPD
REHEAT WATER RETURNRWR
REHEAT WATER SUPPLYRWS
REFRIGERANT SUCTIONSUC
SAFETY RELIEF VENTSV
HIGH PRESSURE STEAM (>125 TO 250 PSIG)HPS
LOW PRESSURE STEAM (0 TO 15 PSIG)LPS
DRAINDPP
LOW PRESSURE CLEAN STEAM (0 TO 15 PSIG) LCS
LOOP WATER RETURNLWR
LOOP WATER SUPPLYLWS
GAS REGULATOR VENTGV
LAB VACUUMVAC
MEDICAL VACUUMMV
PUMP
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P
MECHANICAL SYMBOL LIST
SYMBOL: DESCRIPTION:
NOT ALL SYMBOLS MAY APPLY.
BACKFLOW PREVENTER
CHILLED BEAM RETURNCBR
CHILLED BEAM SUPPLYCBS
RADIANT COOLING RETURNRCR
RADIANT COOLING SUPPLYRCS
MEDIUM PRESSURE CLEAN STEAM (>15 TO 125 PSIG)MCS
MEDIUM PRESSURE CONDENSATE (>15 TO 125 PSIG)MPC
MEDIUM PRESSURE STEAM (>15 TO 125 PSIG)MPS
REFRIGERANTREF
OCCUPANCY SENSORO
HUMIDISTAT SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT / SENSOR
TEMPERATURE SENSOR WITH WELL
THERMOMETER WITH WELL (DIAL TYPE)
THERMOMETER WITH WELL (FILLED TYPE)
DIRECTION OF AIR FLOW
FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RISE IN DIRECTION OF AIR FLOWR
DUCT CAP
DROP IN DIRECTION OF AIR FLOWD
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST/RELIEF AIR DUCT SECTION
4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION
SD-1
6/115
AIR TERMINAL PROPERTIES SYMBOL
NECK SIZE/CFM
TERMINAL AIR BOX (REFER TO SCHEDULE)
TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
HUMIDIFIERH
OPPOSED BLADE DAMPER (REFER TO SCHEDULE)
PARALLEL BLADE DAMPER (REFER TO SCHEDULE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR/MONITORP
PRESSURE SENSOR (DUCT MOUNTED)P
THERMOSTAT/SENSOR
TEMPERATURE SENSOR
THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURE
AIRFLOW MEASUREMENT SYMBOL
XX - AHU SYMBOL
Y - SEQUENTIAL NUMBER
XX-Y
NOT ALL SYMBOLS MAY APPLY.
FAN POWERED TERMINAL AIR BOX w/REHEAT COIL
(REFER TO SCHEDULE)
CONTROL VALVE (TWO-WAY)
PITCH PIPE IN DIRECTION
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
THROTTLING VALVE
AUTOMATIC BALANCING VALVE
MIXING VALVE
CONTROL VALVE (THREE-WAY)
SOLENOID VALVE
CHECK VALVE
SAFETY/RELIEF VALVE
PRESSURE REDUCING VALVE (LIQUID/GAS)
PRESSURE REDUCING VALVE (STEAM)
TRIPLE DUTY VALVE (ANGLE TYPE)
TRIPLE DUTY VALVE (IN-LINE TYPE)
VACUUM BREAKER
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE AND HOSE CONNECTION WITH CAP
BASKET STRAINER
FLEXIBLE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
SUCTION DIFFUSER WITH SUPPORT FOOT
AUTOMATIC AIR VENT
MANUAL AIR VENT
DRAIN VALVE WITH HOSE CONNECTION AND CAP
BOILER BLOW DOWNBD
BOILER FEED WATERBF
COMPRESSED AIRCA
HEATING/CHILLED WATER RETURNHCR
HIGH PRESSURE CLEAN STEAM (>125 TO 250 PSIG)HCS
CONDENSER WATER RETURNCR
CONDENSER WATER SUPPLYCS
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
NATURAL GASG
GLYCOL WATER RETURNGWR
GLYCOL WATER SUPPLYGWS
REFRIGERANT HOT GASHG
HIGH PRESSURE CONDENSATE (>125 TO 250 PSIG)HPC
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
REFRIGERANT LIQUIDLIQ
LOW PRESSURE CONDENSATE (0 TO 15 PSIG)LPC
FUEL OIL RETURNFOR
FUEL OIL SUPPLYFOS
PUMPED CONDENSATEPC
PUMPED DISCHARGEPD
REHEAT WATER RETURNRWR
REHEAT WATER SUPPLYRWS
REFRIGERANT SUCTIONSUC
SAFETY RELIEF VENTSV
HIGH PRESSURE STEAM (>125 TO 250 PSIG)HPS
LOW PRESSURE STEAM (0 TO 15 PSIG)LPS
DRAINDPP
LOW PRESSURE CLEAN STEAM (0 TO 15 PSIG) LCS
LOOP WATER RETURNLWR
LOOP WATER SUPPLYLWS
GAS REGULATOR VENTGV
LAB VACUUMVAC
MEDICAL VACUUMMV
PUMP
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)
NOT ALL SYMBOLS MAY APPLY.
BACKFLOW PREVENTER
CHILLED BEAM RETURNCBR
CHILLED BEAM SUPPLYCBS
RADIANT COOLING RETURNRCR
RADIANT COOLING SUPPLYRCS
MEDIUM PRESSURE CLEAN STEAM (>15 TO 125 PSIG)MCS
MEDIUM PRESSURE CONDENSATE (>15 TO 125 PSIG)MPC
MEDIUM PRESSURE STEAM (>15 TO 125 PSIG)MPS
REFRIGERANTREF
OCCUPANCY SENSORO
HUMIDISTAT SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT / SENSOR
TEMPERATURE SENSOR WITH WELL
THERMOMETER WITH WELL (DIAL TYPE)
THERMOMETER WITH WELL (FILLED TYPE)
DIRECTION OF AIR FLOW
FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RISE IN DIRECTION OF AIR FLOWR
DUCT CAP
DROP IN DIRECTION OF AIR FLOWD
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST/RELIEF AIR DUCT SECTION
4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION
SD-1
6/115
AIR TERMINAL PROPERTIES SYMBOL
NECK SIZE/CFM
TERMINAL AIR BOX (REFER TO SCHEDULE)
TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
HUMIDIFIERH
OPPOSED BLADE DAMPER (REFER TO SCHEDULE)
PARALLEL BLADE DAMPER (REFER TO SCHEDULE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR/MONITORP
PRESSURE SENSOR (DUCT MOUNTED)P
THERMOSTAT/SENSOR
TEMPERATURE SENSOR
THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURE
AIRFLOW MEASUREMENT SYMBOL
XX - AHU SYMBOL
Y - SEQUENTIAL NUMBER
XX-Y
NOT ALL SYMBOLS MAY APPLY.
FAN POWERED TERMINAL AIR BOX w/REHEAT COIL
(REFER TO SCHEDULE)
CONTROL VALVE (TWO-WAY)
PITCH PIPE IN DIRECTION
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
THROTTLING VALVE
AUTOMATIC BALANCING VALVE
MIXING VALVE
CONTROL VALVE (THREE-WAY)
SOLENOID VALVE
CHECK VALVE
SAFETY/RELIEF VALVE
PRESSURE REDUCING VALVE (LIQUID/GAS)
PRESSURE REDUCING VALVE (STEAM)
TRIPLE DUTY VALVE (ANGLE TYPE)
TRIPLE DUTY VALVE (IN-LINE TYPE)
VACUUM BREAKER
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE AND HOSE CONNECTION WITH CAP
BASKET STRAINER
FLEXIBLE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
SUCTION DIFFUSER WITH SUPPORT FOOT
AUTOMATIC AIR VENT
MANUAL AIR VENT
DRAIN VALVE WITH HOSE CONNECTION AND CAP
BOILER BLOW DOWNBD
BOILER FEED WATERBF
COMPRESSED AIRCA
HEATING/CHILLED WATER RETURNHCR
HIGH PRESSURE CLEAN STEAM (>125 TO 250 PSIG)HCS
CONDENSER WATER RETURNCR
CONDENSER WATER SUPPLYCS
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
NATURAL GASG
GLYCOL WATER RETURNGWR
GLYCOL WATER SUPPLYGWS
REFRIGERANT HOT GASHG
HIGH PRESSURE CONDENSATE (>125 TO 250 PSIG)HPC
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
REFRIGERANT LIQUIDLIQ
LOW PRESSURE CONDENSATE (0 TO 15 PSIG)LPC
FUEL OIL RETURNFOR
FUEL OIL SUPPLYFOS
PUMPED CONDENSATEPC
PUMPED DISCHARGEPD
REHEAT WATER RETURNRWR
REHEAT WATER SUPPLYRWS
REFRIGERANT SUCTIONSUC
SAFETY RELIEF VENTSV
HIGH PRESSURE STEAM (>125 TO 250 PSIG)HPS
LOW PRESSURE STEAM (0 TO 15 PSIG)LPS
DRAINDPP
LOW PRESSURE CLEAN STEAM (0 TO 15 PSIG) LCS
LOOP WATER RETURNLWR
LOOP WATER SUPPLYLWS
GAS REGULATOR VENTGV
LAB VACUUMVAC
MEDICAL VACUUMMV
PUMP
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)
NOT ALL SYMBOLS MAY APPLY.
BACKFLOW PREVENTER
CHILLED BEAM RETURNCBR
CHILLED BEAM SUPPLYCBS
RADIANT COOLING RETURNRCR
RADIANT COOLING SUPPLYRCS
MEDIUM PRESSURE CLEAN STEAM (>15 TO 125 PSIG)MCS
MEDIUM PRESSURE CONDENSATE (>15 TO 125 PSIG)MPC
MEDIUM PRESSURE STEAM (>15 TO 125 PSIG)MPS
REFRIGERANTREF
OCCUPANCY SENSORO
HUMIDISTAT SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT / SENSOR
TEMPERATURE SENSOR WITH WELL
THERMOMETER WITH WELL (DIAL TYPE)
THERMOMETER WITH WELL (FILLED TYPE)
DIRECTION OF AIR FLOW
FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RISE IN DIRECTION OF AIR FLOWR
DUCT CAP
DROP IN DIRECTION OF AIR FLOWD
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST/RELIEF AIR DUCT SECTION
4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION
SD-1
6/115
AIR TERMINAL PROPERTIES SYMBOL
NECK SIZE/CFM
TERMINAL AIR BOX (REFER TO SCHEDULE)
TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
HUMIDIFIERH
OPPOSED BLADE DAMPER (REFER TO SCHEDULE)
PARALLEL BLADE DAMPER (REFER TO SCHEDULE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR/MONITORP
PRESSURE SENSOR (DUCT MOUNTED)P
THERMOSTAT/SENSOR
TEMPERATURE SENSOR
THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURE
AIRFLOW MEASUREMENT SYMBOL
XX - AHU SYMBOL
Y - SEQUENTIAL NUMBER
XX-Y
NOT ALL SYMBOLS MAY APPLY.
FAN POWERED TERMINAL AIR BOX w/REHEAT COIL
(REFER TO SCHEDULE)
CONTROL VALVE (TWO-WAY)
PITCH PIPE IN DIRECTION
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
THROTTLING VALVE
AUTOMATIC BALANCING VALVE
MIXING VALVE
CONTROL VALVE (THREE-WAY)
SOLENOID VALVE
CHECK VALVE
SAFETY/RELIEF VALVE
PRESSURE REDUCING VALVE (LIQUID/GAS)
PRESSURE REDUCING VALVE (STEAM)
TRIPLE DUTY VALVE (ANGLE TYPE)
TRIPLE DUTY VALVE (IN-LINE TYPE)
VACUUM BREAKER
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE AND HOSE CONNECTION WITH CAP
BASKET STRAINER
FLEXIBLE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
SUCTION DIFFUSER WITH SUPPORT FOOT
AUTOMATIC AIR VENT
MANUAL AIR VENT
DRAIN VALVE WITH HOSE CONNECTION AND CAP
BOILER BLOW DOWNBD
BOILER FEED WATERBF
COMPRESSED AIRCA
HEATING/CHILLED WATER RETURNHCR
HIGH PRESSURE CLEAN STEAM (>125 TO 250 PSIG)HCS
CONDENSER WATER RETURNCR
CONDENSER WATER SUPPLYCS
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
NATURAL GASG
GLYCOL WATER RETURNGWR
GLYCOL WATER SUPPLYGWS
REFRIGERANT HOT GASHG
HIGH PRESSURE CONDENSATE (>125 TO 250 PSIG)HPC
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
REFRIGERANT LIQUIDLIQ
LOW PRESSURE CONDENSATE (0 TO 15 PSIG)LPC
FUEL OIL RETURNFOR
FUEL OIL SUPPLYFOS
PUMPED CONDENSATEPC
PUMPED DISCHARGEPD
REHEAT WATER RETURNRWR
REHEAT WATER SUPPLYRWS
REFRIGERANT SUCTIONSUC
SAFETY RELIEF VENTSV
HIGH PRESSURE STEAM (>125 TO 250 PSIG)HPS
LOW PRESSURE STEAM (0 TO 15 PSIG)LPS
DRAINDPP
LOW PRESSURE CLEAN STEAM (0 TO 15 PSIG) LCS
LOOP WATER RETURNLWR
LOOP WATER SUPPLYLWS
GAS REGULATOR VENTGV
LAB VACUUMVAC
MEDICAL VACUUMMV
PUMP
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)
NOT ALL SYMBOLS MAY APPLY.
BACKFLOW PREVENTER
CHILLED BEAM RETURNCBR
CHILLED BEAM SUPPLYCBS
RADIANT COOLING RETURNRCR
RADIANT COOLING SUPPLYRCS
MEDIUM PRESSURE CLEAN STEAM (>15 TO 125 PSIG)MCS
MEDIUM PRESSURE CONDENSATE (>15 TO 125 PSIG)MPC
MEDIUM PRESSURE STEAM (>15 TO 125 PSIG)MPS
REFRIGERANTREF
OCCUPANCY SENSORO
HUMIDISTAT SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT / SENSOR
TEMPERATURE SENSOR WITH WELL
THERMOMETER WITH WELL (DIAL TYPE)
THERMOMETER WITH WELL (FILLED TYPE)
DIRECTION OF AIR FLOW
FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RISE IN DIRECTION OF AIR FLOWR
DUCT CAP
DROP IN DIRECTION OF AIR FLOWD
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST/RELIEF AIR DUCT SECTION
4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION
SD-1
6/115
AIR TERMINAL PROPERTIES SYMBOL
NECK SIZE/CFM
TERMINAL AIR BOX (REFER TO SCHEDULE)
TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
HUMIDIFIERH
OPPOSED BLADE DAMPER (REFER TO SCHEDULE)
PARALLEL BLADE DAMPER (REFER TO SCHEDULE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR/MONITORP
PRESSURE SENSOR (DUCT MOUNTED)P
THERMOSTAT/SENSOR
TEMPERATURE SENSOR
THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURE
AIRFLOW MEASUREMENT SYMBOL
XX - AHU SYMBOL
Y - SEQUENTIAL NUMBER
XX-Y
NOT ALL SYMBOLS MAY APPLY.
FAN POWERED TERMINAL AIR BOX w/REHEAT COIL
(REFER TO SCHEDULE)
CONTROL VALVE (TWO-WAY)
PITCH PIPE IN DIRECTION
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
THROTTLING VALVE
AUTOMATIC BALANCING VALVE
MIXING VALVE
CONTROL VALVE (THREE-WAY)
SOLENOID VALVE
CHECK VALVE
SAFETY/RELIEF VALVE
PRESSURE REDUCING VALVE (LIQUID/GAS)
PRESSURE REDUCING VALVE (STEAM)
TRIPLE DUTY VALVE (ANGLE TYPE)
TRIPLE DUTY VALVE (IN-LINE TYPE)
VACUUM BREAKER
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE AND HOSE CONNECTION WITH CAP
BASKET STRAINER
FLEXIBLE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
SUCTION DIFFUSER WITH SUPPORT FOOT
AUTOMATIC AIR VENT
MANUAL AIR VENT
DRAIN VALVE WITH HOSE CONNECTION AND CAP
BOILER BLOW DOWNBD
BOILER FEED WATERBF
COMPRESSED AIRCA
HEATING/CHILLED WATER RETURNHCR
HIGH PRESSURE CLEAN STEAM (>125 TO 250 PSIG)HCS
CONDENSER WATER RETURNCR
CONDENSER WATER SUPPLYCS
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
NATURAL GASG
GLYCOL WATER RETURNGWR
GLYCOL WATER SUPPLYGWS
REFRIGERANT HOT GASHG
HIGH PRESSURE CONDENSATE (>125 TO 250 PSIG)HPC
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
REFRIGERANT LIQUIDLIQ
LOW PRESSURE CONDENSATE (0 TO 15 PSIG)LPC
FUEL OIL RETURNFOR
FUEL OIL SUPPLYFOS
PUMPED CONDENSATEPC
PUMPED DISCHARGEPD
REHEAT WATER RETURNRWR
REHEAT WATER SUPPLYRWS
REFRIGERANT SUCTIONSUC
SAFETY RELIEF VENTSV
HIGH PRESSURE STEAM (>125 TO 250 PSIG)HPS
LOW PRESSURE STEAM (0 TO 15 PSIG)LPS
DRAINDPP
LOW PRESSURE CLEAN STEAM (0 TO 15 PSIG) LCS
LOOP WATER RETURNLWR
LOOP WATER SUPPLYLWS
GAS REGULATOR VENTGV
LAB VACUUMVAC
MEDICAL VACUUMMV
PUMP
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)
NOT ALL SYMBOLS MAY APPLY.
BACKFLOW PREVENTER
CHILLED BEAM RETURNCBR
CHILLED BEAM SUPPLYCBS
RADIANT COOLING RETURNRCR
RADIANT COOLING SUPPLYRCS
MEDIUM PRESSURE CLEAN STEAM (>15 TO 125 PSIG)MCS
MEDIUM PRESSURE CONDENSATE (>15 TO 125 PSIG)MPC
MEDIUM PRESSURE STEAM (>15 TO 125 PSIG)MPS
REFRIGERANTREF
OCCUPANCY SENSORO
HUMIDISTAT SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT / SENSOR
TEMPERATURE SENSOR WITH WELL
THERMOMETER WITH WELL (DIAL TYPE)
THERMOMETER WITH WELL (FILLED TYPE)
DIRECTION OF AIR FLOW
FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RISE IN DIRECTION OF AIR FLOWR
DUCT CAP
DROP IN DIRECTION OF AIR FLOWD
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST/RELIEF AIR DUCT SECTION
4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION
SD-1
6/115
AIR TERMINAL PROPERTIES SYMBOL
NECK SIZE/CFM
TERMINAL AIR BOX (REFER TO SCHEDULE)
TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
HUMIDIFIERH
OPPOSED BLADE DAMPER (REFER TO SCHEDULE)
PARALLEL BLADE DAMPER (REFER TO SCHEDULE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR/MONITORP
PRESSURE SENSOR (DUCT MOUNTED)P
THERMOSTAT/SENSOR
TEMPERATURE SENSOR
THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURE
AIRFLOW MEASUREMENT SYMBOL
XX - AHU SYMBOL
Y - SEQUENTIAL NUMBER
XX-Y
NOT ALL SYMBOLS MAY APPLY.
FAN POWERED TERMINAL AIR BOX w/REHEAT COIL
(REFER TO SCHEDULE)
CONTROL VALVE (TWO-WAY)
PITCH PIPE IN DIRECTION
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
THROTTLING VALVE
AUTOMATIC BALANCING VALVE
MIXING VALVE
CONTROL VALVE (THREE-WAY)
SOLENOID VALVE
CHECK VALVE
SAFETY/RELIEF VALVE
PRESSURE REDUCING VALVE (LIQUID/GAS)
PRESSURE REDUCING VALVE (STEAM)
TRIPLE DUTY VALVE (ANGLE TYPE)
TRIPLE DUTY VALVE (IN-LINE TYPE)
VACUUM BREAKER
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE AND HOSE CONNECTION WITH CAP
BASKET STRAINER
FLEXIBLE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
SUCTION DIFFUSER WITH SUPPORT FOOT
AUTOMATIC AIR VENT
MANUAL AIR VENT
DRAIN VALVE WITH HOSE CONNECTION AND CAP
BOILER BLOW DOWNBD
BOILER FEED WATERBF
COMPRESSED AIRCA
HEATING/CHILLED WATER RETURNHCR
HIGH PRESSURE CLEAN STEAM (>125 TO 250 PSIG)HCS
CONDENSER WATER RETURNCR
CONDENSER WATER SUPPLYCS
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
NATURAL GASG
GLYCOL WATER RETURNGWR
GLYCOL WATER SUPPLYGWS
REFRIGERANT HOT GASHG
HIGH PRESSURE CONDENSATE (>125 TO 250 PSIG)HPC
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
REFRIGERANT LIQUIDLIQ
LOW PRESSURE CONDENSATE (0 TO 15 PSIG)LPC
FUEL OIL RETURNFOR
FUEL OIL SUPPLYFOS
PUMPED CONDENSATEPC
PUMPED DISCHARGEPD
REHEAT WATER RETURNRWR
REHEAT WATER SUPPLYRWS
REFRIGERANT SUCTIONSUC
SAFETY RELIEF VENTSV
HIGH PRESSURE STEAM (>125 TO 250 PSIG)HPS
LOW PRESSURE STEAM (0 TO 15 PSIG)LPS
DRAINDPP
LOW PRESSURE CLEAN STEAM (0 TO 15 PSIG) LCS
LOOP WATER RETURNLWR
LOOP WATER SUPPLYLWS
GAS REGULATOR VENTGV
LAB VACUUMVAC
MEDICAL VACUUMMV
PUMP
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)
NOT ALL SYMBOLS MAY APPLY.
BACKFLOW PREVENTER
CHILLED BEAM RETURNCBR
CHILLED BEAM SUPPLYCBS
RADIANT COOLING RETURNRCR
RADIANT COOLING SUPPLYRCS
MEDIUM PRESSURE CLEAN STEAM (>15 TO 125 PSIG)MCS
MEDIUM PRESSURE CONDENSATE (>15 TO 125 PSIG)MPC
MEDIUM PRESSURE STEAM (>15 TO 125 PSIG)MPS
REFRIGERANTREF
MECHANICAL ABBREVIATION KEY
ABBR: DESCRIPTION:
DIFFERENTIAL PRESSURE GAUGE (RANGE)DPG (0-2")
DIFFERENTIAL PRESSURE SWITCHDPS
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
NOT IN CONTRACTNIC
CFSD CONTROL/FIRE/SMOKE DAMPER
EA EXHAUST/RELIEF AIR
FD FIRE DAMPER
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FSD FIRE/SMOKE DAMPER
MA MIXED AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
SD SMOKE DAMPER
TRANSFER DUCTTD
UC-1 DOOR UNDERCUT BY OTHERS (1" TYPICAL)
ECFSD EXISTING CONTROL FIRE SMOKE DAMPER
EFD EXISTING FIRE DAMPER
EFSD EXISTING FIRE SMOKE DAMPER
ESD EXISTING SMOKE DAMPER
TERMINAL AIR BOXTAB
TYPICALTYP
UON UNLESS OTHERWISE NOTES
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
PRESSURE SWITCHPS
MIXING VALVEMV
ELECTRICAL TO PNEUMATIC VALVEEP
CO CLEANOUT
C COMMON
SCCR SHORT CIRCUIT CURRENT RATING
DIFFERENTIAL PRESSURE GAUGE (RANGE)DPG (0-2")
DIFFERENTIAL PRESSURE SWITCHDPS
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
NOT IN CONTRACTNIC
CFSD CONTROL/FIRE/SMOKE DAMPER
EA EXHAUST/RELIEF AIR
FD FIRE DAMPER
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FSD FIRE/SMOKE DAMPER
MA MIXED AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
SD SMOKE DAMPER
TRANSFER DUCTTD
UC-1 DOOR UNDERCUT BY OTHERS (1" TYPICAL)
ECFSD EXISTING CONTROL FIRE SMOKE DAMPER
EFD EXISTING FIRE DAMPER
EFSD EXISTING FIRE SMOKE DAMPER
ESD EXISTING SMOKE DAMPER
TERMINAL AIR BOXTAB
TYPICALTYP
UON UNLESS OTHERWISE NOTES
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
PRESSURE SWITCHPS
MIXING VALVEMV
ELECTRICAL TO PNEUMATIC VALVEEP
CO CLEANOUT
C COMMON
SCCR SHORT CIRCUIT CURRENT RATING
DIFFERENTIAL PRESSURE GAUGE (RANGE)DPG (0-2")
DIFFERENTIAL PRESSURE SWITCHDPS
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
NOT IN CONTRACTNIC
CFSD CONTROL/FIRE/SMOKE DAMPER
EA EXHAUST/RELIEF AIR
FD FIRE DAMPER
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FSD FIRE/SMOKE DAMPER
MA MIXED AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
SD SMOKE DAMPER
TRANSFER DUCTTD
UC-1 DOOR UNDERCUT BY OTHERS (1" TYPICAL)
ECFSD EXISTING CONTROL FIRE SMOKE DAMPER
EFD EXISTING FIRE DAMPER
EFSD EXISTING FIRE SMOKE DAMPER
ESD EXISTING SMOKE DAMPER
TERMINAL AIR BOXTAB
TYPICALTYP
UON UNLESS OTHERWISE NOTES
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
PRESSURE SWITCHPS
MIXING VALVEMV
ELECTRICAL TO PNEUMATIC VALVEEP
CO CLEANOUT
C COMMON
SCCR SHORT CIRCUIT CURRENT RATING
DIFFERENTIAL PRESSURE GAUGE (RANGE)DPG (0-2")
DIFFERENTIAL PRESSURE SWITCHDPS
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
NOT IN CONTRACTNIC
CFSD CONTROL/FIRE/SMOKE DAMPER
EA EXHAUST/RELIEF AIR
FD FIRE DAMPER
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FSD FIRE/SMOKE DAMPER
MA MIXED AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
SD SMOKE DAMPER
TRANSFER DUCTTD
UC-1 DOOR UNDERCUT BY OTHERS (1" TYPICAL)
ECFSD EXISTING CONTROL FIRE SMOKE DAMPER
EFD EXISTING FIRE DAMPER
EFSD EXISTING FIRE SMOKE DAMPER
ESD EXISTING SMOKE DAMPER
TERMINAL AIR BOXTAB
TYPICALTYP
UON UNLESS OTHERWISE NOTES
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
PRESSURE SWITCHPS
MIXING VALVEMV
ELECTRICAL TO PNEUMATIC VALVEEP
CO CLEANOUT
C COMMON
SCCR SHORT CIRCUIT CURRENT RATING
DIFFERENTIAL PRESSURE GAUGE (RANGE)DPG (0-2")
DIFFERENTIAL PRESSURE SWITCHDPS
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
NOT IN CONTRACTNIC
CFSD CONTROL/FIRE/SMOKE DAMPER
EA EXHAUST/RELIEF AIR
FD FIRE DAMPER
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FSD FIRE/SMOKE DAMPER
MA MIXED AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
SD SMOKE DAMPER
TRANSFER DUCTTD
UC-1 DOOR UNDERCUT BY OTHERS (1" TYPICAL)
ECFSD EXISTING CONTROL FIRE SMOKE DAMPER
EFD EXISTING FIRE DAMPER
EFSD EXISTING FIRE SMOKE DAMPER
ESD EXISTING SMOKE DAMPER
TERMINAL AIR BOXTAB
TYPICALTYP
UON UNLESS OTHERWISE NOTES
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
PRESSURE SWITCHPS
MIXING VALVEMV
ELECTRICAL TO PNEUMATIC VALVEEP
CO CLEANOUT
C COMMON
SCCR SHORT CIRCUIT CURRENT RATING
DIFFERENTIAL PRESSURE GAUGE (RANGE)DPG (0-2")
DIFFERENTIAL PRESSURE SWITCHDPS
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
NOT IN CONTRACTNIC
CFSD CONTROL/FIRE/SMOKE DAMPER
EA EXHAUST/RELIEF AIR
FD FIRE DAMPER
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FSD FIRE/SMOKE DAMPER
MA MIXED AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
SD SMOKE DAMPER
TRANSFER DUCTTD
UC-1 DOOR UNDERCUT BY OTHERS (1" TYPICAL)
ECFSD EXISTING CONTROL FIRE SMOKE DAMPER
EFD EXISTING FIRE DAMPER
EFSD EXISTING FIRE SMOKE DAMPER
ESD EXISTING SMOKE DAMPER
TERMINAL AIR BOXTAB
TYPICALTYP
UON UNLESS OTHERWISE NOTES
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
PRESSURE SWITCHPS
MIXING VALVEMV
ELECTRICAL TO PNEUMATIC VALVEEP
CO CLEANOUT
C COMMON
SCCR SHORT CIRCUIT CURRENT RATING
APPLICABLE CODES AND STANDARDS:
THE DESIGN CRITERIA FOR THIS PROJECT SHALL CONSIST OF THE FOLLOWING LIST OF
DOCUMENTS:
1. PG-18-1, MASTER CONSTRUCTION SPECIFICATION INDEX
2. VHA REQUIRED DIVISION 01 SPECIFICATION SECTION LIST (SOW ATTACHMENT 01)
3. PG-18-3, DESIGN AND CONSTRUCTION PROCEDURES
4. PG-18-4, STANDARD DETAILS AND CAD STANDARDS
5. PG-18-5, EQUIPMENT GUIDE LIST
6. H-18-8 SEISMIC DESIGN HANDBOOK
7. PG-18-9, SPACE PLANNING CRITERIA
8. PG-18-10, DESIGN MANUALS (BY DISCIPLINE)
9. PG-18-12, DESIGN GUIDES (GRAPHICAL, BY FUNCTION)
10. PG-18-13, BARRIER-FREE DESIGN GUIDE
11. PG-18-14, ROOM FINISHES, DOOR, AND HARDWARE SCHEDULES
12. PG-18-15, A-E SUBMISSION REQUIREMENTS
13. PG-18-17, NEPA INTERIM GUIDANCE FOR PROJECTS
14. H-7545, VA CULTURAL RESOURCE MANAGEMENT PROCEDURES
15. OIT INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES
16. 00 VA OEHRM SITE INFRASTRUCTURE REQUIREMENTS V2.0 (SOW ATTACHMENT 02)
17. HEPF SEP (SOCAMES 6) DESIGN ALERTS 1-4 (SOW ATTACHMENT 03)
NUMBER AND ADDRESS
SUITE NO.
CITY, STATE ZIP CODE
P: 555.555.555 F: 555.555.5555 www.imegcorp.com
PROJECT #22006633.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
100%
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
B
IM
/A u d ie L
M u rp h y V
A M e d ic a l C e n te r
(S A
M
E P
T
.0
V A
-S a n A n to n io
T
X -E
H R
M
C .r v t
/1
/2
:1
:2
A
M
M000
MECHANICAL COVERSHEET
Awen Solutions Group
4196 Merchant Plaza, Suite 711
Woodbridge, VA 22192
06/09/2023
EHRM INFRASTRUCTURE
UPGRADES 1
Audie L Murphy VA Medical Center (San Antonio) 7400 Merton Minter, San Antonio, TX 78229
671-22-700
MECHANICAL SHEET INDEX
M000 MECHANICAL COVERSHEET
M500 MECHANICAL DETAILS
M600 MECHANICAL SCHEDULES
M700 CONTROL DIAGRAMS
MD100 GROUND LEVEL DEMOLITION PLAN - MECHANICAL - OVERALL
MD101 1ST FLOOR DEMOLITION PLAN - MECHANICAL - OVERALL
MD102 2ND FLOOR DEMOLITION PLAN - MECHANICAL - OVERALL
MD103 3RD FLOOR DEMOLITION PLAN - MECHANICAL - OVERALL
MD104 4TH FLOOR DEMOLITION PLAN - MECHANICAL - OVERALL
MD105 5TH FLOOR DEMOLITION PLAN - MECHANICAL - OVERALL
MD106 6TH FLOOR DEMOLITION PLAN - MECHANICAL - OVERALL
MD107 7TH FLOOR DEMOLITION PLAN - MECHANICAL - OVERALL
MD400 1ST FLOOR - DATA CENTER - MECHANICAL - ENLARGED DEMOLITION PLANS
MN100 GROUND LEVEL PLAN - MECHANICAL - OVERALL
MN101 1ST FLOOR PLAN - MECHANICAL - OVERALL
MN102 2ND FLOOR PLAN - MECHANICAL - OVERALL
MN103 3RD FLOOR PLAN - MECHANICAL - OVERALL
MN104 4TH FLOOR PLAN - MECHANICAL - OVERALL
MN105 5TH FLOOR PLAN - MECHANICAL - OVERALL
MN106 6TH FLOOR PLAN - MECHANICAL - OVERALL
MN107 7TH FLOOR PLAN - MECHANICAL - OVERALL
MN400 GROUND LEVEL - TR C015.1 - MECHANICAL - ENLARGED PLANS
MN401 GROUND LEVEL - TR GB126.1 - MECHANICAL - ENLARGED PLANS
MN402 GROUND LEVEL - TR F004 - MECHANICAL - ENLARGED PLANS
MN403 GROUND LEVEL - TR 030 - MECHANICAL - ENLARGED PLANS
MN404 GROUND LEVEL - TR L010.2 - MECHANICAL - ENLARGED PLANS
MN405 GROUND LEVEL - TR 1A138 - MECHANICAL - ENLARGED PLANS
MN406 1ST FLOOR - TR G101 - MECHANICAL - ENLARGED PLANS
MN407 1ST FLOOR - TR 119.2 - MECHANICAL - ENLARGED PLANS
MN408 1ST FLOOR - TR H118.2 - MECHANICAL - ENLARGED PLANS
MN409 1ST FLOOR - TR P125 - MECHANICAL - ENLARGED PLANS
MN410 1ST FLOOR - TR 105 - MECHANICAL - ENLARGED PLANS
MN411 1ST FLOOR - TR J104 - MECHANICAL - ENLARGED PLANS
MN412 1ST FLOOR - TR S101R - MECHANICAL - ENLARGED PLANS
MN413 1ST FLOOR - TR 2A137 - MECHANICAL - ENLARGED PLANS
MN414 1ST FLOOR - Y102.7 - MECHANICAL - ENLARGED PLANS
MN415 2ND FLOOR - TR Z221.28A - MECHANICAL - ENLARGED PLANS
MN416 2ND FLOOR - TR A200 - MECHANICAL - ENLARGED PLANS
MN417 2ND FLOOR - TR SP238 - MECHANICAL - ENLARGED PLANS
MN418 2ND FLOOR - TR R201 - MECHANICAL - ENLARGED PLANS
MN419 3RD FLOOR - TR D320 - MECHANICAL - ENLARGED PLANS
MN420 4TH FLOOR - TR C402 - MECHANICAL - ENLARGED PLANS
MN421 5TH FLOOR - TR C511 - MECHANICAL - ENLARGED PLANS
MN422 6TH FLOOR - TR C602.1 - MECHANICAL - ENLARGED PLANS
MN423 7TH FLOOR - TR A702.1 - MECHANICAL - ENLARGED PLANS
MN424 1ST FLOOR - DATA CENTER - MECHANICAL - ENLARGED NEW WORK PLANS
GRAND TOTAL: 46
Revisions: Date:
04/28/2023
SHEET 137 of 431
6" MIN.
M
IN
8" Ø PIERS MAXIMUM
48" APART.
UNIT WIDTH +12"
CONDENSING
U N
IT
L
E N
G T
H
C O
N D
E N
S
IN
G
6x6-W2.9xW2.9 WWF
WIRE MESH
M
IN
M
IN
M
IN
M
IN
GRADE
(1) - #4
REBAR
12"
REINFORCED
CONCRETE POURED IN
PLACE & TROWELED
SMOOTH.
8" Ø PIERS MAXIMUM
48" APART.
6x6-W2.9xW2.9 WWF
WIRE MESH
GRADE
(1) - #4
REBAR
12"
8" Ø PIERS MAXIMUM
48" APART.
6x6-W2.9xW2.9 WWF
WIRE MESH
GRADE
(1) - #4
REBAR
12"
6x6-W2.9xW2.9 WWF
WIRE MESH
GRADE
(1) - #4
REBAR
12"
6x6-W2.9xW2.9 WWF
WIRE MESH
GRADE
(1) - #4
REBAR
12"
6x6-W2.9xW2.9 WWF
WIRE MESH
GRADE
(1) - #4
REBAR
12"
ELASTOFORM FLASHING
CADMIUM PLATED LAG SCREWS 12" O.C.
PIPING
COVER BOTTOM OF CURB
OPENING WITH MINIMUM 18
GAUGE SHEETMETAL.
PREFABRICATED CURB
WITH WOOD NAILER.
18 GAUGE GALVANIZED SHEETMETAL
BOX WITH SOLDERED JOINTS.
GALVANIZED SHEETMETAL CAP. CROSS
BREAK TO PROVIDE DRAINAGE. FASTEN
CAP TO BOX WITH SHEETMETAL SCREWS.
SEAL JOINT WITH SILICONE CAULKING.
PIPE SLEEVE SOLDERED
TO SHEET METAL BOX.
SEAL PIPING WATERTIGHT
BY CAULKING BETWEEN
PIPE & SHEETMETAL
SLEEVE WITH SILICONE
CAULK.
CURB HEIGHT 12"
ABOVE ROOF DECK
SINGLE MEMBRANE
ROOFING.
FRAMING, ROOF, &
ROOFING BY G.C.
10"MIN
MIN.
6"
BATT INSULATION.
PROVIDE THICKNESS
TO MATCH ROOF
INSULATION. MINIMUM
OF 6" THICK
ELASTOFORM FLASHING
CADMIUM PLATED LAG SCREWS 12" O.C.
PIPING
COVER BOTTOM OF CURB
OPENING WITH MINIMUM 18
GAUGE SHEETMETAL.
18 GAUGE GALVANIZED SHEETMETAL
BOX WITH SOLDERED JOINTS.
GALVANIZED SHEETMETAL CAP. CROSS
BREAK TO PROVIDE DRAINAGE. FASTEN
CAP TO BOX WITH SHEETMETAL SCREWS.
SEAL JOINT WITH SILICONE CAULKING.
PIPE SLEEVE SOLDERED
TO SHEET METAL BOX.
SEAL PIPING WATERTIGHT
BY CAULKING BETWEEN
PIPE & SHEETMETAL
SLEEVE WITH SILICONE
CAULK.
CURB HEIGHT 12"
ABOVE ROOF DECK
SINGLE MEMBRANE
ROOFING.
ELASTOFORM FLASHING
CADMIUM PLATED LAG SCREWS 12" O.C.
PIPING
COVER BOTTOM OF CURB
OPENING WITH MINIMUM 18
GAUGE SHEETMETAL.
18 GAUGE GALVANIZED SHEETMETAL
BOX WITH SOLDERED JOINTS.
GALVANIZED SHEETMETAL CAP. CROSS
BREAK TO PROVIDE DRAINAGE. FASTEN
CAP TO BOX WITH SHEETMETAL SCREWS.
SEAL JOINT WITH SILICONE CAULKING.
PIPE SLEEVE SOLDERED
TO SHEET METAL BOX.
SEAL PIPING WATERTIGHT
BY CAULKING BETWEEN
PIPE & SHEETMETAL
SLEEVE WITH SILICONE
CAULK.
CURB HEIGHT 12"
ABOVE ROOF DECK
SINGLE MEMBRANE
ROOFING.
ELASTOFORM FLASHING
CADMIUM PLATED LAG SCREWS 12" O.C.
PIPING
COVER BOTTOM OF CURB
OPENING WITH MINIMUM 18
GAUGE SHEETMETAL.
18 GAUGE GALVANIZED SHEETMETAL
BOX WITH SOLDERED JOINTS.
GALVANIZED SHEETMETAL CAP. CROSS
BREAK TO PROVIDE DRAINAGE. FASTEN
CAP TO BOX WITH SHEETMETAL SCREWS.
SEAL JOINT WITH SILICONE CAULKING.
PIPE SLEEVE SOLDERED
TO SHEET METAL BOX.
SEAL PIPING WATERTIGHT
BY CAULKING BETWEEN
PIPE & SHEETMETAL
SLEEVE WITH SILICONE
CAULK.
CURB HEIGHT 12"
ABOVE ROOF DECK
SINGLE MEMBRANE
ROOFING.
ELASTOFORM FLASHING
CADMIUM PLATED LAG SCREWS 12" O.C.
PIPING
COVER BOTTOM OF CURB
OPENING WITH MINIMUM 18
GAUGE SHEETMETAL.
18 GAUGE GALVANIZED SHEETMETAL
BOX WITH SOLDERED JOINTS.
GALVANIZED SHEETMETAL CAP. CROSS
BREAK TO PROVIDE DRAINAGE. FASTEN
CAP TO BOX WITH SHEETMETAL SCREWS.
SEAL JOINT WITH SILICONE CAULKING.
PIPE SLEEVE SOLDERED
TO SHEET METAL BOX.
SEAL PIPING WATERTIGHT
BY CAULKING BETWEEN
PIPE & SHEETMETAL
SLEEVE WITH SILICONE
CAULK.
CURB HEIGHT 12"
ABOVE ROOF DECK
SINGLE MEMBRANE
ROOFING.
ELASTOFORM FLASHING
CADMIUM PLATED LAG SCREWS 12" O.C.
PIPING
COVER BOTTOM OF CURB
OPENING WITH MINIMUM 18
GAUGE SHEETMETAL.
18 GAUGE GALVANIZED SHEETMETAL
BOX WITH SOLDERED JOINTS.
GALVANIZED SHEETMETAL CAP. CROSS
BREAK TO PROVIDE DRAINAGE. FASTEN
CAP TO BOX WITH SHEETMETAL SCREWS.
SEAL JOINT WITH SILICONE CAULKING.
PIPE SLEEVE SOLDERED
TO SHEET METAL BOX.
SEAL PIPING WATERTIGHT
BY CAULKING BETWEEN
PIPE & SHEETMETAL
SLEEVE WITH SILICONE
CAULK.
CURB HEIGHT 12"
ABOVE ROOF DECK
SINGLE MEMBRANE
ROOFING.
9-24 MBH AIR COOLED
CONDENSING UNIT
5/16" ZINC-PLATED LAG
SCREWS. (TYP. 4)
MOUNTING FEET (TYP.)
INSULATION AND
ROOFING
ROOF STRUCTURE
PREFABRICATED EQUIPMENT
SUPPORT CURB (TYP). VERIFY
ROOFING MATERIAL AND PROVIDE
WITH OR WITHOUT CANT AS
REQUIRED.
TOP OF CURB
CURB HEIGHT
12" ABOVE
ROOF DECK
9-24 MBH AIR COOLED
CONDENSING UNIT
5/16" ZINC-PLATED LAG
SCREWS. (TYP. 4)
MOUNTING FEET (TYP.)
9-24 MBH AIR COOLED
CONDENSING UNIT
5/16" ZINC-PLATED LAG
SCREWS. (TYP. 4)
MOUNTING FEET (TYP.)
9-24 MBH AIR COOLED
CONDENSING UNIT
5/16" ZINC-PLATED LAG
SCREWS. (TYP. 4)
MOUNTING FEET (TYP.)
NOTES:
1. VERIFY DIAMETER OF ANCHOR BOLT REQUIRED TO FIT WITHIN MOUNTING FEET ANCHOR HOLES.
9-24 MBH AIR COOLED
CONDENSING UNIT
5/16" ZINC-PLATED LAG
SCREWS. (TYP. 4)
MOUNTING FEET (TYP.)
9-24 MBH AIR COOLED
CONDENSING UNIT
5/16" ZINC-PLATED LAG
SCREWS. (TYP. 4)
MOUNTING FEET (TYP.)
OVERSIZE HANGER TO ALLOW LONGITUDINAL
PIPE EXPANSION AND PIPE INSULATION TO
PASS THROUGH UNBROKEN (TYP)
INSULATION SHIELD [AND ROLLED SUPPORT
PLATE AS REQUIRED PER SPECS]
THREADED ROD
INSULATION
CLEVIS HANGER
HIGH DENSITY INSULATION INSERT
FOR 1 1/2" PIPES AND LARGER
AS REQUIRED IN SPECIFICATIONS
INSULATION SHIELD (TYP)
BOLT (TYP)
PIPE
RISER CLAMP
PIPE SLEEVE
PLAN
BOLT (TYP)
FIRESTOPPING
MATERIAL. REFER
TO SPECS
FLOOR SLAB PIPE SLEEVE
RISER CLAMP
RISER
INSULATION
ELEVATION
FIRESTOPPING
MATERIAL. REFER
TO SPECS
FLOOR SLAB
INSULATION PIPE SLEEVE
INSULATE CLAMP AND
BOLTS WITH ELASTOMERIC
FOAM. SEAL ALL
INSULATION VAPOR TIGHTRISER
PLAN
RISER CLAMP
NEOPRENE MOUNT
BENEATH RISER CLAMP
RISER CLAMP
PIPE SLEEVE
PIPE
BOLT (TYP)
ELEVATION
INSULATED COLD PIPE RISER SUPPORTINSULATED HOT PIPE RISER SUPPORT
WELD LUG OR HUB TO PIPE
INSULATED COLD PIPE HANGER
UNI-STRUT OR EQUIVALENT
HIGH DENSITY INSULATION INSERT
FOR 1 1/2" PIPES AND LARGER
AS REQUIRED IN SPECIFICATIONS
THREADED ROD (TYP)
PIPE INSULATION (TYP)
TRAPEZE HANGER
TOP OF SUPPORT APPLICATION
BOTTOM OF SUPPORT APPLICATION
INSTALL CLAMP ON ALL
PIPES LESS THAN 4"Ø
FIRE SEALANT
FIRE SEALANT
NOTE 2
NOTE 3
PENETRATING ITEM
NOTE 4
NOTE 3
NOTE 4
PENETRATING ITEM
NOTE 2
NOTE 3
RATED WALL
(CONSTRUCTION
VARIES)
RATED FLOOR
(CONSTRUCTION
VARIES)
NOTES:
1. THIS GENERAL DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL MOVEMENT. REFER TO SPECIFICATION SECTION 07840 (07 84 00) (SECTION 21 05 03 - FIRE PROTECTION, SECTION 22 05 03 - PLUMBING , SECTION 23 05 03 - HVAC) FOR SELECTION OF THROUGH PENETRATION FIRE STOPPING.
2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH CONTRACTOR FURNISHES SLEEVE TO G.C., COORDINATES SLEEVE LOCATIONS AND DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND SLEEVE.
IF SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR SHALL INSTALL SLEEVE. SLEEVE SIZE SHALL ALLOW ANNULAR
SPACE REQUIRED BY THE SELECTED FIRE STOP SYSTEM.
3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING. SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL MOVEMENT OF PENETRATING ITEM WITHOUT
MOVEMENT OF FIRE BARRIER.
4. WATERTIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS. MULTIPLE PENETRATING ITEMS MAY BE ENCLOSED IN ONE FRAME.
DUCT LINER (REFER TO
SPECIFICATION SECTION
23 31 00 - DUCTWORK)
REFER TO DRAWING
FOR SIZE
FLOOR OR ROOF
CEILING
WALL
X
/2
X
6".
D1>D2
45 DEGREE
BUTT FLANGE
STRAIGHT TAP
ENTRY Θ 45°
45 DEGREE CONICAL
CLINCH LOCK
CORNER FILLER
PIECE OR USE
GASKET (TYP.)
45 DEGREE LEAD IN
DOVETAIL JOINT
LINED DUCT CONNECTION
(NO EXPOSED LINER EDGES)
DUCT LINER
FLANGED
NOTE:STRAIGHT TAP WITH BUTT
FLANGE FOR BRANCH AND TEE
CONNECTION IN RECTANGULAR DUCTS
UNDER 1" PRESSURE CLASS ONLY.
ENTRY Θ 45°
D
W
L
Θ
D
(L = 4" OR W/4; WHICHEVER IS LARGER)
NOTES:
1. DO NOT USE CONNECTIONS WITH SCOOPS.
2. FIT ALL CONNECTIONS TO AVOID VISIBLE OPENINGS AND SECURE THEM
SUITABLY FOR THE PRESSURE CLASS.
3. ADDITIONAL MECHANICAL FASTENERS ARE REQUIRED FOR 4"W.G. AND OVER.
4. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
RECTANGULAR
MITERED ELBOW
WITH VANES
TYPE RE2
RECTANGULAR
MITERED ELBOW
TYPE RE6
USE ONLY AS PART OF OFFSETS
AND TRANSITIONS PER FIGURE 4-7
TYPE 2 OR AS SHOWN ON
DRAWINGS. OFFSETS ABOVE 30°
SHALL BE TYPE RE1.
RECTANGULAR
RADIUS ELBOW
TYPE RE1
R/W = 1.0 (MINIMUM)
R/W < 1.0 SHALL BE TYPE
RE3
RECTANGULAR
RADIUS ELBOW WITH VANES
TYPE RE3
REFER TO SMACNA HVAC SYSTEMS DUCT DESIGN MANUAL,
FOURTH EDITION, SECTION 5.14 "SPLITTER VANES" AND SMACNA
HVAC DUCT CONSTRUCTION STANDARDS, THIRD EDITION,
FIGURES 4-2 AND 4-9 AND CHARTS 4-1 AND 4-1M. ELBOW SHALL
HAVE THREE…
This is the start of the file's text. The full file is on GovTribe.