ATTACHMENT 21 - Montrose.EHRM.Addendum.01.B13.20260330.pdf

PDF 24 MB Posted

Attached to
Z2DA--620-22-700 Electronic Health Record Modernization Infrastructure Upgrades - Franklin Delano Roosevelt VA Hospital, Montrose, NY
Solicitation number
RFP-36C77626R0033
Issued by

About this file

This is a comprehensive set of construction design documents (Addendum #1 dated 03/30/2026) for the Electronic Health Record Modernization (EHRM) Infrastructure Upgrades project at Franklin Delano Roosevelt VA Hospital in Montrose, NY. The documents include architectural, electrical, telecommunications, life safety, and infection control plans for Building 13 renovation work across multiple levels.

The project scope encompasses infrastructure upgrades to two telecom rooms (Room 102 on the first level and Room 202 on the second level), each approximately 105-110 square feet, along with associated electrical, mechanical, and telecommunications systems installation. Key requirements include: fire-rated wall construction (1-2 hour ratings depending on application), new electrical panels with normal and emergency power distribution, uninterruptible power supply (UPS) systems rated at 5KW for 208V service, Category 6A cabling infrastructure throughout both floors (279 total data ports across all areas), new IP-based access control systems (Johnson Controls iSTAR Edge G2), Avigilon IP-addressable security cameras, and comprehensive cable tray and conduit systems. Construction must maintain operational life safety systems, elevator service, and stair accessibility at all times. The project requires strict infection control and interim life safety measures (ICRA Class IV) including construction barriers, negative air pressure systems with HEPA filtration, anteroom requirements, and debris removal protocols through designated routes with asbestos abatement coordination. All work must comply with 2024-2026 building codes including NFPA 101 Life Safety Code, 2026 National Electrical Code, and VA-specific standards. Contractor responsibilities include 30-day load measurements on panelboards, fire stopping all penetrations, coordination with existing equipment protection, and provision of laminated final documentation within telecom rooms.

View the file

Other files

File Type Posted
Amendment 5 - 36C77626R0033 0005.pdf PDF
5-4 - RFI TRACKING SHEET.pdf PDF
Amend 5 - B01.20260330.pdf PDF
Amend 5 - B16.20260330.pdf PDF
Amend 5 - B19.20260330.pdf PDF
Amend 5 - B29.20260330.pdf PDF
Amend 5 - B52.20260330.pdf PDF
Amend 5 - SITE.20260330.pdf PDF
Original attachments 1-12.zip ZIP file
Amend 5 - B02.20260330.pdf PDF
Amend 5 - B07.20260330.pdf PDF
Amend 5 - B12.20260330.pdf PDF
ATTACHMENT 3 - 01 00 00.B - Appendix B - Submittal Log.pdf PDF
ATTACHMENT 8 - 01 00 00.G - Appendix G - GPRS Triple C Montrose Full Report.pdf PDF
ATTACHMENT 16 - Montrose.EHRM.Addendum.01.B04.20260330.pdf PDF
ATTACHMENT 24 - Montrose.EHRM.Addendum.01.B16.20260330.pdf PDF
ATTACHMENT 27 - Montrose.EHRM.Addendum.01.B20.20260330.pdf PDF
ATTACHMENT 28 - Montrose.EHRM.Addendum.01.B26.20260330.pdf PDF
ATTACHMENT 28A - Montrose.EHRM.Addendum.01.B27.20260330.pdf PDF
ATTACHMENT 32 - Montrose.EHRM.Addendum.01.B52.20260330.pdf PDF
ATTACHMENT 33A - 00 41 13.10 - Construction Estimate Breakdown Template.xlsx XLSX spreadsheet
Amendment 3 - 36C77626R0033 0003.pdf PDF
ATTACHMENT 4 - 01 00 00.C - Appendix C - SOP 138-22HV CONST STD PROCEDURES QLTY ASSRNCE FOR PRJS.pdf PDF
ATTACHMENT 6 - 01 00 00.E - Appendix E - VHA ICRA-1.3 Dec 9 2024.pdf PDF
ATTACHMENT 9 - 01 00 00.H - Appendix H - J2237038 Montrose ACM and Lead Paint Inspection Report Final 8-21-2023.pdf PDF
ATTACHMENT 10 - 01 00 00.H1 - Appendix H1 - J2247041 Montrose NY VAMC_ACM Inspctn - Lead Paint Screening Rpt_Final 5-9-2024 - signed.pdf PDF
ATTACHMENT 15 - Montrose.EHRM.Addendum.01.B03.20260330.pdf PDF
ATTACHMENT 17 - Montrose.EHRM.Addendum.01.B05.20260330.pdf PDF
ATTACHMENT 19 - Montrose.EHRM.Addendum.01.B07.20260330.pdf PDF
ATTACHMENT 20 - Montrose.EHRM.Addendum.01.B12.20260330.pdf PDF
ATTACHMENT 26 - Montrose.EHRM.Addendum.01.B18.20260330.pdf PDF
Amendment 2 - 36C77626R0033 0002.pdf PDF
Amendment 1 - 36C77626R0033 0001.pdf PDF
Attachment 1 - SPECS - 620-22-700.Montrose.EHRM.Spec.IFC.20260205.pdf PDF
Attachment 6 - 01 00 00.E - Appendix E - VHA ICRA-1.3 - Dec 9 2024.pdf PDF
Attachment 7 - 01 00 00.F - Appendix F - VHA PCRA 2024 1.1 Final.Template Fillable.pdf PDF
Attachment 8 - 01 00 00.G - Appendix G - GPRS Triple C Montrose Full Report.pdf PDF
Attachment 9 - 01 00 00.H - Appendix H - J2237038 Montrose ACM Ld Pnt InspRpt Final 8-21-2023.pdf PDF
Attachment 12 - Additional Security Badging Requirements rev 2.pdf PDF
Attachment 13 - Drawing B01 20250627.pdf PDF
Attachment 31 - Drawing B31 20250627.pdf PDF
Attachment 33 - Drawing Site 20250627.pdf PDF
Attachment 10 - 01 00 00.H1 - Appendix H1 - J2247041 ACM Insp - Lead Paint Rpt_Final 5-9-2024.pdf PDF
Attachment 17 - Drawing B05 20250627.pdf PDF
Attachment 20 - Drawing B12 20250627.pdf PDF
Attachment 24 - Drawing B16 20250627.pdf PDF
Attachment 25 - Drawing B17 20250627.pdf PDF
Attachment 30 - Drawing B29 20250627.pdf PDF
Attachment 38 - PPQ.docx DOCX document
Attachment 40 - RFI TRACKING SHEET - SOLICITATION 36C77626R0033 - Project 620-22-700.xlsx XLSX spreadsheet
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

STAMP

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .M

EP

.B

.rv t 3/

/2

:3

5:

P M

13G-001

DRAWING INDEX 620-22-700

06/27/2025 M. PERKINS K.

MCDERMOTT

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

- DRAWING INDEX -

SHEET

NUMBER SHEET NAME INCLUDED IN 35% SD INCLUDED IN 65% DD INCLUDED IN 95% CD ISSUED FOR CONSTRUCTION

GENERAL

13G-000 COVER SHEET Yes Yes Yes Yes 13G-001 DRAWING INDEX Yes Yes Yes Yes 13G-010 GENERAL PROJECT NOTES Yes Yes Yes Yes 13G-012 GENERAL INDOOR AIR QUALITY NOTES Yes Yes Yes Yes

ICRA & LIFE SAFETY

13GI300 INTERIM LIFE SAFETY & INFECTION CONTROL PLAN - FIRST LEVEL Yes Yes Yes Yes 13GI301 INTERIM LIFE SAFETY & INFECTION CONTROL PLAN - SECOND LEVEL Yes Yes Yes Yes 13GI302 INTERIM LIFE SAFETY & INFECTION CONTROL DETAILS Yes Yes Yes Yes

ARCHITECTURAL

13A-001 ARCHITECTURAL SYMBOLS, & GENERAL NOTES No Yes Yes Yes 13A-400 ARCHITECTURAL ENLARGED VIEWS - FIRST & SECOND LEVELS Yes Yes Yes Yes 13A-401 ARCHITECTURAL EXTERIOR ELEVATIONS No Yes Yes Yes 13A-511 ARCHITECTURAL PARTITION AND FRAMING DETAILS No Yes Yes Yes 13A-512 ARCHITECTURAL PARTITION HEAD DETAILS No Yes Yes Yes 13A-531 ARCHITECTURAL CEILING DETAILS No Yes Yes Yes

INTERIORS

13IN101 INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES No Yes Yes Yes

FIRE PROTECTION

13FX001 FIRE PROTECTION ABBREVIATIONS, SYMBOLS, AND DETAILS No Yes Yes Yes 13FX102F FIRE PROTECTION PLAN - FIRST LEVEL No Yes Yes Yes 13FX103F FIRE PROTECTION PLAN - SECOND LEVEL No Yes Yes Yes 13FX401 FIRE PROTECTION ENLARGED PLANS No Yes Yes Yes 13FX901 FIRE PROTECTION CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes

PLUMBING

13P-001 PLUMBING ABBREVIATIONS AND SYMBOLS No Yes Yes Yes 13PD103F PLUMBING PLAN - SECOND LEVEL No Yes Yes Yes

MECHANICAL

13M-001 MECHANICAL ABBREVIATIONS AND SYMBOLS No Yes Yes Yes 13M-101 MECHANICAL PLAN - GROUND LEVEL No Yes Yes Yes 13M-102F MECHANICAL PLAN - FIRST LEVEL No Yes Yes Yes 13M-103F MECHANICAL PLAN - SECOND LEVEL No Yes Yes Yes 13M-401 MECHANICAL ENLARGED PLANS No Yes Yes Yes 13M-501 MECHANICAL DETAILS No Yes Yes Yes 13M-701 MECHANICAL SCHEDULES No Yes Yes Yes 13M-801 MECHANICAL CONTROL SYMBOL LEGEND AND ABBREVIATIONS No Yes Yes Yes 13M-802 MECHANICAL CONTROL DIAGRAMS No Yes Yes Yes 13M-901 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 13M-902 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes

ELECTRICAL

13E-001 ELECTRICAL ABBREVIATIONS AND SYMBOLS Yes Yes Yes Yes 13E-101 ELECTRICAL PLAN - GROUND LEVEL No Yes Yes Yes 13E-102F ELECTRICAL PLAN - FIRST LEVEL - FUTURE No Yes Yes Yes 13E-103F ELECTRICAL PLAN - SECOND LEVEL - FUTURE No Yes Yes Yes 13E-401 ELECTRICAL ENLARGED PLANS No Yes Yes Yes 13E-501 ELECTRICAL DETAILS Yes Yes Yes Yes 13E-601 ELECTRICAL ONE-LINE DIAGRAMS No Yes Yes Yes 13E-701 ELECTRICAL SCHEDULES No Yes Yes Yes 13E-702 ELECTRICAL SCHEDULES No Yes Yes Yes 13E-901 ELECTRICAL CUTSHEETS & BASIS OF DESIGN Yes Yes Yes Yes 13E-902 ELECTRICAL CUTSHEETS & BASIS OF DESIGN No No No Yes

TELECOMMUNICATION

13T-001 TELECOMMUNICATION ABBREVIATIONS AND SYMBOLS Yes Yes Yes Yes 13T-101 TELECOMMUNICATION PLAN - GROUND LEVEL Yes Yes Yes Yes 13T-102F TELECOMMUNICATION PLAN - FIRST LEVEL - FUTURE Yes Yes Yes Yes 13T-103F TELECOMMUNICATION PLAN - SECOND LEVEL - FUTURE Yes Yes Yes Yes 13T-401 TELECOMMUNICATION ENLARGED PLANS No Yes Yes Yes 13T-501 TELECOMMUNICATION DETAILS Yes Yes Yes Yes 13T-502 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS Yes Yes Yes Yes 13T-503 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS Yes Yes Yes Yes 13T-504 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS No Yes Yes Yes 13T-601 TELECOMMUNICATION RISER DIAGRAMS Yes Yes Yes Yes 13T-603 TELECOMMUNICATION FIBER RISER DIAGRAM - NEW No Yes Yes Yes 13T-604 TELECOMMUNICATION RACK ELEVATIONS Yes Yes Yes Yes 13T-700 TELECOMMUNICATION SCHEDULES No Yes Yes Yes 13T-701 TELECOMMUNICATION SCHEDULES No Yes Yes Yes 13T-901 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN Yes Yes Yes Yes 13T-902 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN No No Yes Yes 13T-903 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN No No Yes Yes

REFERENCE

13R-900 PHOTO REFERENCES No Yes Yes Yes Grand total: 61

# Revisions: Date:

1 ADDENDUM #1 03/30/2026

13G-011 REMOVED FROM

CONSTRUCTION DOCUMENTS

Ranjan Text Box

UP

DN

SD

INFECTION CONTROL / DUST

CONTROL PARTITION / BARRIER

INFECTION CONTROL/DUST CONTROL

EGRESS DOOR NON-TRANSFERRING

MULTI-SHEETED ADHESIVE FLOOR PADS

PATH OF DEMOLITION/TRASH

REMOVAL TRAVEL

CONSTRUCTION LIMIT LINE

NOT IN CONTRACT AREA

DEMOLITION

LASER PARTICLE COUNT LOCATION

LIFE SAFETY SYMBOLS

PATH OF TRAVEL

(FOR CUMULATIVE DISTANCES

REFER TO SCHEDULE)

EXIT LIGHTING

TM

FIRE EXTINGUISHER CABINET (FEC)

FIRE EXTINGUISHERS (FE)

FIRE HOSE CABINETS (FHC)

HEAT DETECTOR

SMOKE DETECTOR

DIRECTION OF EGRESS

APPLICABLE BUILDING CODES

2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL

FIRE ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD

FOR INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF

NFPA 5000 AND NFPA 900

2024 INTERNATIONAL MECHANICAL CODE (IPC)

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION

(OSHA) STANDARDS.

VA SEISMIC DESIGN REQUIREMENTS, H-18-8

2026 NATIONAL ELECTRICAL CODE (NEC)

2024 INTERNATIONAL PLUMBING CODE (IPC)

ASME BOILER AND PRESSURE VESSEL CODE

ASME CODE FOR PRESSURE PIPING

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS

(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN

GUIDE (PG-18-13)

BUILDING CODE REQUIREMENTS FOR REINFORCED

CONCRETE, AMERICAN CONCRETE INSTITUTE AND

COMMENTARY (ACI 318)

MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE

FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL

BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION

(AISC)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION

STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-

FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-

RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND

SUSTAINABLE BUILDINGS: MEMORANDUM OF

UNDERSTANDING (MOU)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL

ENVIRONMENTAL, ENERGY, AND TRANSPORTATION

MANAGEMENT

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.

STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00

AND 01 35 26 OF THE VA MASTER CONSTRUCTION

SPECIFICATION.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY –

ASHRAE STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE

170-2025, NON-MEDICAL SPACES - ASHRAE 62.1-2025

SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE

STANDARD 15–2024

2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED

BY VA STANDARDS

UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE

STANDARD OR CODE SHALL BE USED

APPLICABLE BUILDING GUIDES

VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)

BUILDING CODE:

CONSTRUCTION TYPE:

TYPE II (222) PER NFPA 220, Chapter 4

TYPE OF BUILDING REHABILITATION: MODIFICATION, CHAPTER 43.

FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)

FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING

ELEMENTS:

STRUCTURAL FRAME 2 HOURS

NON-BEARING WALLS 0 HOURS

BEARING WALLS 2 HOURS

FLOORS 2 HOURS

ROOFS/ CEILINGS 1 HOURS

FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)

FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY

FUNCTION:

ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)

SMOKE COMPARTMENTS 1 HOUR

SOILED UTILITY ROOMS 1 HOUR

VERTICAL SHAFTS / STAIRS 2 HOURS (4 FLOORS)

(INCL. MECHANICAL SHAFTS) 1 HOUR (1 - 3 FLOORS)

MEDICAL GAS / HAZARDOUS 1 HOUR

STORAGE

CLASSIFICATION OF OCCUPANCY:

EXISTING: RESIDENTIAL BOARD AND CARE Occupancy per Chapter 33 and BUSINESS Occupancy per Chapter 39

BUILDING OCCUPANCY TYPE:

PRIMARY - EXISTING RESIDENTIAL BOARD AND CARE, LARGE

SECONDARY - EXISTING BUSINESS OCCUPANCY

6.1.14.1.3 Where incidental to another occupant, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:

(1) Mercantile, BUSINESS, industrial, or storage use

6.1.14.3 Mixed Occupancies

6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.

Table 6.1.14.4.1 (a) - separation of occupancies - 2 Hr between Board and Care and Business

6.2 Hazard of Contents.

6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or structure, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.

EXIT ACCESS TRAVEL DISTANCE:

33.3.2.5.2 COMMON PATH OF TRAVEL 75 FT

33.3.2.5.4 DEAD END 30 FT

33.3.2.6 TRAVEL DISTANCE FROM ANY 250 FT

POINT IN ROOM TO EXIT

OCCUPANT LOAD:

33.1.4 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.

MEANS OF EGRESS:

33.3.2 Capacity of Means of Egress.

33.3.2.3.3 The clear width of any corridor or passageway required for exit access shall not be less than 60 in. (1525 mm).

PROTECTION OF VERTICAL OPENINGS:

33.3.3.1 Protection of Vertical Openings.

33.3.3.1.1 Any vertical opening shall be enclosed or protected in accordance with Section 8.6, unless otherwise permitted.

PROTECTION FROM HAZARDS:

33.3.3.2 Protection from Hazards.

33.3.3.2.1 Hazardous Areas - Any hazardous areas shall be protected in accordance with Section 9.7.1.1(1)

33.3.3.2.2 The following areas shall be considered hazardous areas and shall be protected by fire barriers having a minimum 1-hour fire resistance rating in accordance with Section 8.7:

(1) Boilder and fuel-fired heater rooms

(2) Laundries

(3) Repair Shops

(4) Rooms or spaces used for storage of combustible supplies and equipment in quantities deemed hazardous by the AHJ.

33.3.3.5.7 Portable fire extinguishers shall be provided in all health care occupancies facilities in accordance with Section 9.9.

PARKING SUMMARY:

NO ADDITIONAL PARKING ADDED

SUBDIVISION OF BUILDING SPACES:

33.3.3.7 SUBDIVISION OF BUILDING SPACES

33.3.3.7.1 EVERY STORY SHALL BE DIVIDED INTO NOT LESS THAN

TWO SMOKE COMPARTMENTS.

33.3.3.7.3 THE TRAVEL DISTANCE FROM ANY POINT TO REACH A

DOOR IN THE REQUIRED SMOKE BARRIER SHALL NOT EXCEED

200 FT.

33.3.3.7.9 SMOKE BARRIERS IN ACCORDANCE WITH SECTION 8.5

SHALL HAVE A MINIMUM 1-HOUR FIRE RESISTANCE RATING.

WIDTH PROVIDEDP: XX"

R: XX" WIDTH REQUIRED

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

X - XX'

# ICRA SYMBOLSKEYNOTES

FEC

17352 SF

EXISTING RESIDENTIAL -

E1 ▬ 28.1'

6 7

3 3A

TELECOM

ROOM

102102

CENTER

STAIR

101C101C

ELEVATOR

VESTIBULE

166Z166Z

ELEVATOR

144144

ELEVATOR

109109

ELEC

ROOM

101101

UDS TLT

165165

CORRIDOR

167Z167Z

TREATMENT

ROOM

103103

STORAGE

103A103A

RESIDENT

ROOM 1

118118

RESIDENT

ROOM 2

120120

TLT 14

105A105A

TLT 13

107A107A

RESIDENT

ROOM 13

107107

RESIDENT

ROOM 14

105105

RESIDENT

ROOM 15

104104

TLT 15

104A104A

SPS

CLOSET

163163

RESIDENT

ROOM 12

108108

RESIDENT

ROOM 11

109109

TLT 1

118A118A

TLT 2

120A120A

TLT 11

109A109A

TLT 12

108A108A

RESIDENT

ROOM 3

122122

RESIDENT

ROOM 4

117117

RESIDENT

ROOM 5

116116

RESIDENT

ROOM 6

123123

TLT 4

117A117A

TLT 3

122A122A

TLT 5

116A116A

TLT 6

123A123A

NURSE

STATION

128128

BARIATRIC

RESIDENT

RM 7

114114

TLT 7

114A114A

TLT 8

112A112A

BARIATRIC

RESIDENT

RM 8

112112

RESIDENT

ROOM 9

111111

TLT 9

111A111A

RESIDENT

ROOM 10

110110

TLT 10

110A110A

GROUP

ROOM 1

130130

GROUP

ROOM 2

156156

GROUP

ROOM 3

142142

STAFF

BREAK

ROOM

140140

PUBLIC

TLT

164164

PUBLIC

TOILET

125125

SOILED

LINEN

124124

BREAK

OUT

SPACE

159159

CORRIDOR

171Z171Z

OFFICE 3

154154

OFFICE 4

158158

SOUTH

STAIR

121121

NORTH

STAIR

139139

CLEAN

LINEN

115115

MED

ROOM

128A128A

CORRIDOR

169Z169Z

REFRIGERATOR

COVE

130A130A

NURSE

STATION 2

113113

KITCHENETTE

130B130B

TLT 16

126A126ARESIDENT

ROOM 16

126126

RESIDENT

ROOM 17

127127

TLT 17

127A127A

TLT 19

161A161A

RESIDENT

ROOM 19

160160

RESIDENT

ROOM 18

162162

TLT 18

162A162A

CLEAN

SUPPLIES

152152

TLT 20

134A134A RESIDENT

ROOM 20

134134

RESIDENT

ROOM 21

133133

TLT 21

133A133A

RESIDENT

ROOM 22

132132

TLT 22

132A132A

TLT 23

131A131A

RESIDENT

ROOM 23

131131

RESIDENT

ROOM 24

129129

OFFICE 5

153153

OFFICE 8

136136

OFFICE 9

137137

OFFICE 11

144144

OFFICE 7

146146

OFFICE 13

141141 OFFICE 12

143143

OFFICE 1

157157

OFFICE 2

155155

LAUNDRY

106106

PUBLIC

TLT 1

149149

PUBLIC

TLT 2

150150

ELECTRICAL

ROOM

135135

CORRIDOR

175Z175Z

CORRIDOR

173Z173Z

CORRIDOR

174Z174Z

RESIDENT

CORRIDOR

170Z170Z

RESIDENT

CORRIDOR

168Z168Z

CONFERENCE

ROOM

148148

OFFICE 10

145145

OFFICE 6

147147

EMS

CLOSET

151151

CORRIDOR

188188

TLT 24

129A129A

CORRIDOR

172Z172Z

NORTHWEST

STAIR

138138

SOUTHWEST

STAIR

119119

TN

PN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .A

R C

H .B

.rv t 3/

/2

5:

:4

PM

13GI300

INTERIM LIFE SAFETY & INFECTION CONTROL

PLAN - FIRST LEVEL

620-22-700

06/27/2025 M.PERKINS N.

BLANCHARD

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

1/8" = 1'-0"F1 INTERIM LIFE SAFETY & INFECTION CONTROL PLAN - FIRST LEVEL

1 TEMPORARY CONSTRUCTION BARRIER DOOR WITH

CLOSER AND LATCH AND WALK OFF MATS

2 STAIRS ARE TO REMAIN OPERATIONAL AT ALL TIMES

FOR EMERGENCY EGRESS ONLY. THEY ARE NOT TO BE

USED FOR ANY CONSTRUCTION ACTIVITY.

3 ELEVATORS ARE TO REMAIN OPERATIONAL AT ALL

TIMES

A

ONE ELEVATOR TO BE DESIGNATED FOR CONTRACTOR

USE. CONTRACTOR TO PROTECT / REPAIR ALL FINISHES

AND FOLLOW PROPER ICRA REMOVAL PROTOCOLS FOR

ANY MATERIALS REMOVED FROM SITE THROUGH

ELEVATOR

4 DEBRIS REMOVAL PATH TO EXTERIOR - COORDINATE

REMOVAL OF MATERIALS ON THIS FLOOR WITH

ASBESTOS REPORT AND PLAN

5 REMOVE EXISTING WINDOW, AC UNIT AND METAL

SUPPORT FRAME. PROVIDE TEMPORARY INFILL.

6 SOLID GRAY HATCH DENOTES LIMITED WORK AREA -

SEE MEP AND TELECOM DRAWINGS FOR CABLING

SCOPE, TYP.

7 MAINTAIN EXIT PATHWAYS FOR OCCUPANTS AT ALL

TIMES

8 COORDINATE TEMPORARY HEPA EXHAUST ROUTING

OUT OF BUILDING - MAINTAIN 25 FEET MINIMUM FROM

INTAKES, OPERABLE WINDOWS, AND ENTRANCES.

PROVIDE BLOCK-OFF PANELS IN EXISTING WINDOWS

FOR DISCHARGE, TYP.

9 TEMPORARY CONSTRUCTION BARRIER

10 ANTEROOM - SEE INFECTION CONTROL & INTERIM LIFE

SAFETY DETAILS

PATH OF TRAVEL SCHEDULE - FIRST LEVEL

Mark From Room To Room Type of Travel Path Length

FIRST FLOOR

(P-o-T) Distance to Exits

E1 TELECOM ROOM 102 CENTER STAIR 101C (P-o-T) Distance to Exits 28' - 1"

NOTE:

DEBRIS REMOVAL:

CONFIRM WITH COR FOR FINAL PLAN AND PROCEDURE OF

MATERIAL REMOVAL WITH ANTEROOMS, HEPA FILTRATION, ICRA

PROTOCOLS, AND ROUTE THRU OCCUPIED SPACES; PRIOR TO

REMOVAL OF ANY MATERIALS.

SECURE STAIRWELLS FROM UNAUTHORIZED ENTRY DURING

CONSTRUCTION.

LIFE SAFETY:

NEW WORK DOES NOT CHANGE EXISTING SMOKE

COMPARTMENTS, EXIT PATHWAYS, OR EXITS.

AREA OCCUPANCIES

LEVEL Name Area SF

Occupancy Requirements

OL

Occupancy

(IBC) Occupancy (NFPA) OLF Fixed Seats

FIRST LEVEL EXISTING RESIDENTIAL 17352 SF R4 Residential Board & Care

200 SF 0 87

# Revisions: Date:

1 ADDENDUM #1 03/27/202603/30/2026

INFECTION CONTROL / DUST

CONTROL PARTITION / BARRIER

INFECTION CONTROL/DUST CONTROL

EGRESS DOOR NON-TRANSFERRING

MULTI-SHEETED ADHESIVE FLOOR PADS

PATH OF DEMOLITION/TRASH

REMOVAL TRAVEL

CONSTRUCTION LIMIT LINE

NOT IN CONTRACT AREA

DEMOLITION

LASER PARTICLE COUNT LOCATION

LIFE SAFETY SYMBOLS

PATH OF TRAVEL

(FOR CUMULATIVE DISTANCES

REFER TO SCHEDULE)

EXIT LIGHTING

TM

FIRE EXTINGUISHER CABINET (FEC)

FIRE EXTINGUISHERS (FE)

FIRE HOSE CABINETS (FHC)

HEAT DETECTOR

SMOKE DETECTOR

DIRECTION OF EGRESS

APPLICABLE BUILDING CODES

2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL

FIRE ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD

FOR INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF

NFPA 5000 AND NFPA 900

2024 INTERNATIONAL MECHANICAL CODE (IPC)

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION

(OSHA) STANDARDS.

VA SEISMIC DESIGN REQUIREMENTS, H-18-8

2026 NATIONAL ELECTRICAL CODE (NEC)

2024 INTERNATIONAL PLUMBING CODE (IPC)

ASME BOILER AND PRESSURE VESSEL CODE

ASME CODE FOR PRESSURE PIPING

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS

(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN

GUIDE (PG-18-13)

BUILDING CODE REQUIREMENTS FOR REINFORCED

CONCRETE, AMERICAN CONCRETE INSTITUTE AND

COMMENTARY (ACI 318)

MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE

FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL

BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION

(AISC)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION

STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-

FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-

RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND

SUSTAINABLE BUILDINGS: MEMORANDUM OF

UNDERSTANDING (MOU)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL

ENVIRONMENTAL, ENERGY, AND TRANSPORTATION

MANAGEMENT

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.

STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00

AND 01 35 26 OF THE VA MASTER CONSTRUCTION

SPECIFICATION.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY –

ASHRAE STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE

170-2025, NON-MEDICAL SPACES - ASHRAE 62.1-2025

SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE

STANDARD 15–2024

2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED

BY VA STANDARDS

UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE

STANDARD OR CODE SHALL BE USED

APPLICABLE BUILDING GUIDES

VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)

BUILDING CODE:

CONSTRUCTION TYPE:

TYPE II (222) PER NFPA 220, Chapter 4

TYPE OF BUILDING REHABILITATION: MODIFICATION, CHAPTER 43.

FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)

FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING

ELEMENTS:

STRUCTURAL FRAME 2 HOURS

NON-BEARING WALLS 0 HOURS

BEARING WALLS 2 HOURS

FLOORS 2 HOURS

ROOFS/ CEILINGS 1 HOURS

FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)

FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY

FUNCTION:

ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)

SMOKE COMPARTMENTS 1 HOUR

SOILED UTILITY ROOMS 1 HOUR

VERTICAL SHAFTS / STAIRS 2 HOURS (4 FLOORS)

(INCL. MECHANICAL SHAFTS) 1 HOUR (1 - 3 FLOORS)

MEDICAL GAS / HAZARDOUS 1 HOUR

STORAGE

CLASSIFICATION OF OCCUPANCY:

EXISTING: RESIDENTIAL BOARD AND CARE Occupancy per Chapter 33 and BUSINESS Occupancy per Chapter 39

BUILDING OCCUPANCY TYPE:

PRIMARY - EXISTING RESIDENTIAL BOARD AND CARE, LARGE

SECONDARY - EXISTING BUSINESS OCCUPANCY

6.1.14.1.3 Where incidental to another occupant, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:

(1) Mercantile, BUSINESS, industrial, or storage use

6.1.14.3 Mixed Occupancies

6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.

Table 6.1.14.4.1 (a) - separation of occupancies - 2 Hr between Board and Care and Business

6.2 Hazard of Contents.

6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or structure, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.

EXIT ACCESS TRAVEL DISTANCE:

33.3.2.5.2 COMMON PATH OF TRAVEL 75 FT

33.3.2.5.4 DEAD END 30 FT

33.3.2.6 TRAVEL DISTANCE FROM ANY 250 FT

POINT IN ROOM TO EXIT

OCCUPANT LOAD:

33.1.4 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.

MEANS OF EGRESS:

33.3.2 Capacity of Means of Egress.

33.3.2.3.3 The clear width of any corridor or passageway required for exit access shall not be less than 60 in. (1525 mm).

PROTECTION OF VERTICAL OPENINGS:

33.3.3.1 Protection of Vertical Openings.

33.3.3.1.1 Any vertical opening shall be enclosed or protected in accordance with Section 8.6, unless otherwise permitted.

PROTECTION FROM HAZARDS:

33.3.3.2 Protection from Hazards.

33.3.3.2.1 Hazardous Areas - Any hazardous areas shall be protected in accordance with Section 9.7.1.1(1)

33.3.3.2.2 The following areas shall be considered hazardous areas and shall be protected by fire barriers having a minimum 1-hour fire resistance rating in accordance with Section 8.7:

(1) Boilder and fuel-fired heater rooms

(2) Laundries

(3) Repair Shops

(4) Rooms or spaces used for storage of combustible supplies and equipment in quantities deemed hazardous by the AHJ.

33.3.3.5.7 Portable fire extinguishers shall be provided in all health care occupancies facilities in accordance with Section 9.9.

PARKING SUMMARY:

NO ADDITIONAL PARKING ADDED

SUBDIVISION OF BUILDING SPACES:

33.3.3.7 SUBDIVISION OF BUILDING SPACES

33.3.3.7.1 EVERY STORY SHALL BE DIVIDED INTO NOT LESS THAN

TWO SMOKE COMPARTMENTS.

33.3.3.7.3 THE TRAVEL DISTANCE FROM ANY POINT TO REACH A

DOOR IN THE REQUIRED SMOKE BARRIER SHALL NOT EXCEED

200 FT.

33.3.3.7.9 SMOKE BARRIERS IN ACCORDANCE WITH SECTION 8.5

SHALL HAVE A MINIMUM 1-HOUR FIRE RESISTANCE RATING.

WIDTH PROVIDEDP: XX"

R: XX" WIDTH REQUIRED

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

X - XX'

# ICRA SYMBOLSKEYNOTES

FEC

17064 SF

EXISTING RESIDENTIAL -

TELECOM

ROOM

202202

ELECTRICAL

ROOM

201201

ELEVATOR

002002

ELEVATOR

001001

PUBLIC

TOILET

203203

PATIENT

BATH

204A204A

NORTH

STAIR

240240

CORRIDOR

200C5200C5

E1 ▬ 112.7'

PATIENT

BED

204204

TREATMENT

ROOM

267267

STORAGE

267A267A

PATIENT

BED

205205

ELEVATOR

LOBBY

200200

3 3A

SOUTH

STAIR

227227

NORTHWEST

STAIR

247247

PATIENT

BATH

210A210A

PATIENT

BED

220220

PATIENT

BED

219219

PATIENT

BATH

220A220A

PATIENT

BATH

218A218A

PATIENT

BATH

219A219A

PATIENT

BED

218218

PATIENT

BATH

217A217A

PATIENT

BATH

215A215A

CLEAN

SUPPLY

216216

PATIENT

BED

217217

PATIENT

BED

215215

PATIENT

BED

214214

PATIENT

BATH

214A214A

PATIENT

BED

212212

PATIENT

BATH

212A212A

PATIENT

BED

211211

PATIENT

BATH

211A211A

PATIENT

BATH

209A209A

LAUNDRY

207207

PATIENT

BED

210210

CORRIDOR

200C3200C3

PATIENT

BATH

224A224A

PATIENT

BED

224224

STAIR

PATIENT

BATH

223A223A

PATIENT

BATH

225A225A

PATIENT

BED

223223

PATIENT

BATH

222A222A

PATIENT

BED

222222

PATIENT

BATH

228A228A

PATIENT

BED

228228

PATIENT

BATH

229A229A

PATIENT

BED

229229

MED RM

231A231A

NURSE

STATION

231231

NURSE'S

OFFICE

232232

PATIENT

BATH

233A233A

PATIENT

BED

233233

PATIENT

BATH

234A234A

PATIENT

BATH

237A237A

FEMALE

PATIENT

LOUNGE

236236

HALLWAY

200C6200C6

PATIENT

BED

235235

PATIENT

BED

234234

PATIENT

BATH

235A235A

PATIENT

BED

237237

PATIENT

BATH

238A238A

PATIENT

BATH

239A239A

PATIENT

BED ADA

239239

PUBLIC

TOILET

241241

TELEHEALTH

242242

EVS

243243

CLEAN

LINEN

245245

SOILED

LINEN

246246

OFFICE

249249

STAFF

TLT

248248

GROUP

RM 1

250250

CORRIDOR

200C9200C9

OFFICE

251251

STAFF

TLT

252252

STAFF

LOUNGE

253253

OFFICE

254254

GROUP

RM 2

255255

DAY

ROOM

256256

PATIENT

BATH

257A257A

PATIENT

BED

257257

OFFICE

260260

OFFICE

258258

OFFICE

259259

STORAGE

261A261A

OFFICE

262262

OFFICE

263263

PATIENT

BATH

264A264A

PATIENT

BED

264264

PATIENT

BATH

266A266A

PATIENT

BED

266266

CLOSET

CLOSET

PATIENT

BATH

205A205A

CORRIDOR

200C4200C4

PATIENT

BATH

206A206A

PATIENT

BED

206206

PATIENT

BED

208208

PATIENT

BATH

208A208A

PATIENT

BED

209209

PATIENT

BED ADA

238238

CORRIDOR

200C8200C8

GROUP

RM 3/

CONFERENCE

RM

261261

CORRIDOR

200C7200C7

PATIENT

BED

265265

PATIENT

BATH

265A265A

PATIENT

BED

225225

ALCOVE

213213

NURSE

STATION

213A213A

TN

PN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .A

R C

H .B

.rv t 3/

/2

5:

:5

PM

13GI301

INTERIM LIFE SAFETY & INFECTION CONTROL

PLAN - SECOND LEVEL

620-22-700

06/27/2025 M.PERKINS N.

BLANCHARD

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

1/8" = 1'-0"F1 INTERIM LIFE SAFETY & INFECTION CONTROL PLAN - SECOND LEVEL

1 TEMPORARY CONSTRUCTION BARRIER DOOR WITH

CLOSER AND LATCH AND WALK OFF MATS

2 STAIRS ARE TO REMAIN OPERATIONAL AT ALL TIMES

FOR EMERGENCY EGRESS ONLY. THEY ARE NOT TO BE

USED FOR ANY CONSTRUCTION ACTIVITY.

3 ELEVATORS ARE TO REMAIN OPERATIONAL AT ALL

TIMES

A

ONE ELEVATOR TO BE DESIGNATED FOR CONTRACTOR

USE. CONTRACTOR TO PROTECT / REPAIR ALL FINISHES

AND FOLLOW PROPER ICRA REMOVAL PROTOCOLS FOR

ANY MATERIALS REMOVED FROM SITE THROUGH

ELEVATOR

4 DEBRIS REMOVAL PATH TO EXTERIOR - COORDINATE

REMOVAL OF MATERIALS ON THIS FLOOR WITH

ASBESTOS REPORT AND PLAN

5 REMOVE EXISTING WINDOW, AC UNIT AND METAL

SUPPORT FRAME. PROVIDE TEMPORARY INFILL.

6 SOLID GRAY HATCH DENOTES LIMITED WORK AREA -

SEE MEP AND TELECOM DRAWINGS FOR CABLING

SCOPE, TYP.

7 MAINTAIN EXIT PATHWAYS FOR OCCUPANTS AT ALL

TIMES

8 COORDINATE TEMPORARY HEPA EXHAUST ROUTING

OUT OF BUILDING - MAINTAIN 25 FEET MINIMUM FROM

INTAKES, OPERABLE WINDOWS, AND ENTRANCES.

PROVIDE BLOCK-OFF PANELS IN EXISTING WINDOWS

FOR DISCHARGE, TYP.

9 TEMPORARY CONSTRUCTION BARRIER

10 ANTEROOM - SEE INFECTION CONTROL & INTERIM LIFE

SAFETY DETAILS

PATH OF TRAVEL SCHEDULE - SECOND LEVEL

Mark From Room To Room Type of Travel Path Length

SECOND FLOOR

(P-o-T) Distance to Exits

E1 TELECOM ROOM 202 SOUTH STAIR 227 (P-o-T) Distance to Exits 112' - 8"

NOTE:

DEBRIS REMOVAL:

CONFIRM WITH COR FOR FINAL PLAN AND PROCEDURE OF

MATERIAL REMOVAL WITH ANTEROOMS, HEPA FILTRATION, ICRA

PROTOCOLS, AND ROUTE THRU OCCUPIED SPACES; PRIOR TO

REMOVAL OF ANY MATERIALS.

SECURE STAIRWELLS FROM UNAUTHORIZED ENTRY DURING

CONSTRUCTION.

LIFE SAFETY:

NEW WORK DOES NOT CHANGE EXISTING SMOKE

COMPARTMENTS, EXIT PATHWAYS, OR EXITS.

AREA OCCUPANCIES

LEVEL Name Area SF

Occupancy Requirements

OL

Occupancy

(IBC) Occupancy (NFPA) OLF Fixed Seats

SECOND LEVEL EXISTING RESIDENTIAL 17064 SF R4 Residential Board & Care

200 SF 0 85

TEMPORARY WALL TO EXTEND

AND BE SEALED TO DECK /

FLOOR ABOVE WHEN RATED

ENCLOSURE REQUIRED

FLOOR LINE

CEILING SYSTEM AS

SCHEDULED

EXISTING STRUCTURE

FI

NI

SH

ED

F

LO

OR

T O

UN

DE

RS

ID

E

OF

S

TR

UC

TU

RE

VE

RI

FY

F

LO

OR

T

O

FL

OO

R

HE

IG

HT

RENOVATED SPRINKLER

SYSTEM

WEEKLY CHANGED

OR MORE AS

NEEDED PRE-FILTER

FLEX DUCTMONTHLY CHANGED

HEPA FILTER

HEPA NEGATIVE AIR

UNIT

PROVIDE STICKY MATS (CHANGED END OF

EVERY SHIFT OR MORE IF NECESSARY TO

MAINTAIN CLEANLINESS).

PRESSURE INDICATOR SHALL BE AT

0.03 OR GREATER USING A DIGITAL

MANOMETER WITH DATA LOGGING. IF

NOT VERIFY ALL OPENING SUCH AS

DOOR ARE CLOSED AND/OR CHANGE

NEGATIVE AIR PRE-FILTER. DO NOT USE

A "BALL IN THE WALL" OR ANALOG

OTHER PRESSURE INDICATOR.

SUPPLY DUCTS EITHER

KEEP RUNNING OR

COVER WHEN NOT

RUNNING TO KEEP

DUST OUT.

A

V

OTAPE ALL SERVICES

TO PROTECT AGAINST

CONTAMINATION

E

FIRE EXTINGUISHER ON

PORTABLE FLOOR BRACKET

(SHALL REQUIRE MORE THAN

ONE.)

PUBLIC AREA

CONSTRUCTION AREA

ANTE ROOM

HARD BARRIER ALL THE WAY TO

DECK ABOVE

SIZE ANTE ROOM TO PROVIDE

SPACE FOR EQUIPMENT STAGING,

CART CLEANING, WORKERS' PPE

AND CLEANING, INCLUDING A HEPA

CLOTHING VACUUM

ROUTE DUCT TO EXTERIOR - SEE

PLANS FOR PROPOSED ROUTES -

CONFIRM ROUTE WITH ON-SITE

STAFF PRIOR TO INSTALLATION.

DISCHARGE AT A DISTANCE OF 25

FEET OR GREATER FROM

ENTRANCES, AIR INTAKES AND

OPERABLE WINDOWS. DO NOT

DIRECT EXHAUST INTO ANY

BUILDING SHARED EXHAUST

SYSTEM.

ANTE ROOM FAN

DOOR TO BE SELF-CLOSING AND

SELF-LATCHING - 45 MIN. FIRE

RATING PER NFPA

D7

13GI302

INFECTION CONTROL / DUST

CONTROL PARTITION / BARRIER

INFECTION CONTROL/DUST CONTROL

EGRESS DOOR NON-TRANSFERRING

MULTI-SHEETED ADHESIVE FLOOR PADS

PATH OF DEMOLITION/TRASH

REMOVAL TRAVEL

CONSTRUCTION LIMIT LINE

NOT IN CONTRACT AREA

DEMOLITION

LASER PARTICLE COUNT LOCATION

1/4" = 1'-0"F7

TYPICAL CONSTRUCTION

LAYOUT- CLASS IV

1/2" = 1'-0"D7 CROSS SECTION A'-A'- CLASS IV

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .A

R C

H .B

.rv t 3/

/2

5:

:5

PM

13GI302

INTERIM LIFE SAFETY & INFECTION CONTROL

DETAILS

620-22-700

06/27/2025 M.PERKINS N.

BLANCHARD

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

P.

Q.

R.

IMPLEMENT INFECTION CONTROL RISK ASSESSMENT (ICRA)

PROCEDURES AS PER THE MONTROSE VA ICRA PLAN AND AS

DIRECTED BY THE CONTRACTING OFFICER REPRESENTATIVE

(COR).

COORDINATE ALL DEMOLITION/ CONSTRUCTION DEBRIS PATH

OF TRAVEL AND INTERIM LIFE SAFETY MEASURES (ILSM) WITH

THE COR. ALL INTERIOR DOORS THAT LEAD TO THE

CONSTRUCTION SITE SHALL BE POSTED AS PER THE ISLM PLAN.

OBTAIN INFECTION CONTROL PERMIT PRIOR TO BEGINNING

WORK.

THE ONE HOUR FIRE RATED CONSTRUCTION BARRIERS SHALL

BE CONSTRUCTED PRIOR TO BEGINNING OTHER WORK.

CONSTRUCT ANTEROOM AT ENTRANCES TO CONSTRUCTION

AREAS AND REQUIRE ALL CONSTRUCTION PERSONNEL TO PASS

THROUGH THIS ROOM TO BE VACUUMED WITH HEPA VACUUM

CLEANER PRIOR TO LEAVING THE SITE.

FIRE PROTECTION SYSTEMS SHALL REMAIN FUNCTIONAL FOR

OCCUPIED AREAS ON THE FLOOR.

PROVIDE FIRE EXTINGUISHERS IN CONSTRUCTION AREAS;

REVIEW WITH COR AND VA SAFETY GROUP.

MAINTAIN EXIT LIGHTS IN CONSTRUCTION AREA.

MAINTAIN NEGATIVE AIR PRESSURE IN CONSTRUCTION AREA AT

ALL TIMES (24/7). WHETHER OCCUPIED OR NOT, THROUGHOUT

DURATION OF PROJECT USING HEPA EQUIPPED AIR FILTRATION

UNITS.

CONSTRUCTION AREA SHALL REMAIN ISOLATED FROM THE

OTHER AREAS OF THE MEDICAL CENTER; NO RETURN AIR OR

EXHAUST SHALL PASS INTO THE AREAS OUTSIDE THE

CONSTRUCTION AREA. ISOLATE HVAC SYSTEM WITHIN

CONSTRUCTION AREA TO PREVENT CONTAMINATION OF

EXISTING DUCT SYSTEM.

REDIRECT ALL MEDICAL CENTER PERSONNEL. PATIENTS AND

VISITORS SO THEY DO NOT EXIT THROUGH THE CONSTRUCTION

AREA. PROVIDE SIGNS ON DOORS INTO THE CONSTRUCTION

AREA THAT READS: "CONSTRUCTION AREA-DO NOT ENTER".

GENERAL CONTRACTOR SHALL MAINTAIN DAILY LOGS AND KEEP

A CURRENT HOT WORK PERMIT ON SITE.

TACKY MATS SHALL BE PLACED AT ALL DOORS INTO THE

CONSTRUCTION AREA AND SHALL BE MONITORED TO MAKE

SURE THEY REMAIN EFFECTIVE.

MAINTAIN A CLEAN AND ORDERLY CONSTRUCTION AREA. ALL

DEBRIS REMOVAL SHALL BE IN COVERED CARTS AND/OR

CONTAINERS.

SEAL ALL HOLES, PUNCTURES, AND PENETRATIONS FROM PIPES

AND CONDUITS APPROPRIATELY AND IMMEDIATELY TO MAINTAIN

DUST PROTECTION AND NEGATIVE AIR PRESSURE.

MAINTAIN STAFFING AND EQUIPMENT INCLUDING DUST MOPS,

WET MOPS, BROOMS, BUCKETS AND CLEAN WIPING RAGS FOR

CLEANING FINE DUST FROM FLOORS AND ADJACENT OCCUPIED

AREAS. ANY DUST TRACKED OUTSIDE OF CONSTRUCTION AREA

SHALL BE CLEANED IMMEDIATELY.

AFTER COMPLETION OF WORK: VACUUM CONSTRUCTION AREA

WITH HEPA FILTERED VACUUMS, WET MOP WITH DISINFECTANT,

REMOVE CONSTRUCTION BARRIERS (UPON APPROVAL). PATCH

OR REPAIR ANY DAMAGE FROM CONSTRUCTION BARRIER

REMOVAL AND REMOVE ISOLATION OF HVAC SYSTEM.

CONSTRUCTION BARRIERS SHALL NOT BE REMOVE UNTIL

PROJECT IS COMPLETED AND INSPECTED BY VA SAFETY

PERSONNEL, INFECTION CONTROL GROUP, AND COR.

ICRA NOTES:

ICRA SYMBOL LEGENDINFECTION CONTROL RISK

ASSESSMENT:

TABLE 1: CONSTRUCTION, RENOVATION AND/OR MAINTENANCE

ACTIVITY CATEGORY

IDENTIFY THE CATEGORY OF CONSTRUCTION PROJECT

CATEGORY A: INSPECTION AND/OR FACILITY UPKEEP

CATEGORY B: GENERAL MAINTENANCE AND REPAIR WORK

CATEGORY C: SMALL-SCALE CONSTRUCTION, RENOVATION, AND/OR

MAINTENANCE

CATEGORY D: LARGE-SCALE CONSTRUCTION, RENOVATION, OR

MAINTENANCE

THIS PROJECT: CATEGORY D

TABLE 2: AFFECTED AREA ASSESSMENT

TABLE 3: PATIENT RISK CATEGORY

IDENTIFY THE PATIENT RISK CATEGORY FOR EACH AREA LISTED IN

TABLE 2. OF THE PATIENT RISK CATEGORIES IDENTIFIED, THE ONE WITH

THE GREATEST RISK SHALL BE SELECTED AS THE OVERALL PATIENT

RISK CATEGORY FOR THE ACTIVITY.

LOW RISK: NON-PATIENT CARE AREAS

MEDIUM RISK: PATIENT CARE SUPPORT AREAS

HIGH RISK: PATIENT CARE AREAS

HIGHEST RISK: PROCEDURAL, INVASIVE, STERILE SUPPORT AND HIGLY

COMPROMISED PATIENT CARE AREAS

THIS PROJECT: HIGH RISK

CL

AS

S

II

Construction Activity Category

RISK GROUP

LOW RISK

MEDIUM RISK

HIGH RISK

HIGHEST RISK

I II II III

I II III IV

I II IV IV

II III IV IV

A

STEP 1:

IDENTIFY SPECIFIC SITE OF ACTIVITY, FOR EXAMPLE, PATIENT

ROOMS, MEDICATION ROOM, AND SO ON.

STEP 2:

IDENTIFY ISSUES RELATED TO: VENTILATION, PLUMBING, AND

ELECTRICAL IN TERMS OF THE OCCURRENCE OF PROBABLE

OUTAGES.

STEP 3:

IDENTIFY CONTAINMENT MEASURES, USING PRIOR

ASSESSMENT. WHAT TYPES OF BARRIERS (FOR EXAMPLE,

SOLIDS WALLS)? WILL HEPA FILTRATION BE REQUIRED?

STEP 4:

CONSIDER POTENTIAL RISK OF WATER DAMAGE. IS THERE A

RISK DUE TO COMPROMISING STRUCTURAL INTEGRITY (FOR

EXAMPLE, WALL, CEILING, ROOF)?

NOTE: RENOVATION/CONSTRUCTION AREA SHALL BE

ISOLATED FROM THE OCCUPIED AREAS DURING

CONSTRUCTION AND SHALL BE NEGATIVE WITH RESPECT TO

SURROUNDING AREAS.

STEP 5:

WORK HOURS: CAN OR WILL THE WORK BE DONE DURING

NON-PATIENT-CARE HOURS?

STEP 6:

DO PLANS ALLOW FOR ADEQUATE NUMBER OF

ISOLATION/NEGATIVE AIRFLOW ROOMS?

STEP 7:

DO THE PLANS ALLOW FOR THE REQUIRED NUMBER AND TYPE

OF HAND-WASHING SINKS?

STEP 8:

DOES THE INFECTION PREVENTION AND CONTROL STAFF AGREE

WITH THE MINIMUM NUMBER OF SINKS FOR THIS PROJECT?

(VERIFY AGAINST FACILITY GUIDELINES INSTITUTE (FGI) DESIGN

AND CONSTRUCTION GUIDELINES FOR TYPES AND AREA.)

STEP 9:

DOES THE INFECTION PREVENTION AND CONTROL STAFF

AGREE WITH THE PLANS RELATIVE TO CLEAN AND SOILED

UTILITY ROOMS?

STEP 10:

PLAN TO DISCUSS THE FOLLOWING CONTAINMENT ISSUES WITH

THE PROJECT TEAM, FOR EXAMPLE, TRAFFIC FLOW,

HOUSEKEEPING, DEBRIS REMOVAL (HOW AND WHEN).

Affected Area Assessment

AREA

Activity Area Area Above Area Below Adjacent Area

TR

SEE PLAN

SVC TYPE POC POC CONTACT INFO

SEE PLAN

SEE PLAN

Walter Hoffman (914) 208-6275

MATCH THE OVERALL PATIENT RISK CATEGORY WITH THE PLANNED

CONSTRUCTION PROJECT CATEGORY ON THE FOLLOWING MATRIX, TO

FIND THE CLASS OF PRECAUTIONS (I, II, III OR IV) OR LEVEL OF

INFECTION CONTROL ACTIVITIES REQUIRED.

THIS PROJECT: CATEGORY IV

TABLE 4: LEVEL OF INFECTION PREVENTION AND CONTROL

PRECAUTIONS

B C D

TABLE 5: REQUIRED INFECTION PREVENTION AND CONTROL MEASURES

BY LEVEL OF PRECAUTIONS

NOTE: LIST IS CUMULATIVE FROM CLASS I THROUGH CLASS IV)

TABLE 6: MINIMUM INFECTION PREVENTION AND CONTROL MEASURES

REQUIRED UPON COMPLETION OF THE ACTIVITY

1.

2.

1.

2.

A.

B.

C.

D.

E.

1.

2.

1.

2.

3.

1.

Construction areas must be inspected by an infection preventionist and engineering representative (and others as determined by the facility) for final activity/project close out and removal of infection prevention and control measures

Work Area Cleaning:

Clean work areas including all environmental surfaces, high horizontal surfaces and flooring materials Check all supply and return air registers for dust accumulation on upper surfaces as well as air diffuser surfaces

Removal of Critical Barriers:

Critical barriers must remain in place during all work involving drywall removal, creation of dust and activities beyond simple touch-up work. The barrier may NOT be removed until a work area cleaning has been performed. Additional cleaning may be needed after removal of barrier All (plastic or hard) barrier removal activities must be completed in a manner that prevents dust release. Use the following precautions when removing hard barriers:

Carefully remove screws and painter tape.

If dust will be generated during screw removal, use hand-held HEPA vacuum.

Drywall cutting is prohibited during removal process Clean all stud tracks with HEPA vacuum before removing outer hard barrier Use a plastic barrier to enclose area if dust could be generated

Negative Air Requirements:

The use of negative air must be designated to remove contaminants from the work area Negative air devices (fans, filters, monitoring and documentation equipment) must remain operational at all times and in place for a period after completion of dust creating activities to remove contaminants from the work area and before removal of critical barriers.

HVAC Systems:

Upon removal of critical barriers, remove isolation of HVAC system in areas where work is being performed Verify that HVAC systems are clean and operational.

Verify and document through a TAB the HVAC systems meets original airflow and air exchange design specifications

Water Systems:

Until the potable water system is activated and in use, flushing shall continue at least twice per week in accordance with VHA directive 1061.

CL

AS

S

III

IV

13.

14.

15.

16.

17.

18.

Ensure availability of equipment for cleaning hands Construct and complete critical barriers meeting NFPA 241 requirements.

Barriers must extend to the ceiling or if ceiling tile is removed, to deck above All (plastic or hard) barrier construction activities must be completed in a manner that prevents dust release. Plastic barriers must be effectively affixed to floor and ceiling (or floor/roof deck above) and secure from movement or damage.

Seal all penetrations in containment barriers, including floors and ceiling, using approved materials (UL schedule firestop if applicable for barrier type) Maintain .01 inches /water gauge negative pressurization of the entire workspace by use of HEPA exhaust air systems directed outdoors, or comply with the alternative method outlined in Appendix A of this document.

These control measures must be maintained continuously 24/7 for the duration of the project. HEPA filtered exhaust if discharged directly to the outdoors must be at a istance of 25 feet or greater from entrances, air intakes and operable windows. Exhausting discharged air into shared or recirculating HVAC systems, or other shared exhaust systems (e.g., bathroom exhaust) is prohibited Install a differential pressure sensing device (e.g., magnehelic, manometer, or digital monitoring) on exterior of work containment to continually monitor and document negative pressurization. The “ball in the wall” or similar apparatus are not acceptable

4.

5.

6.

7.

8.

9.

10.

11.

12.

Provide active means to control airborne dust from dispersing into occupied areas and/or water mist surface to control dust (e.g., Mobile Dust Containment Cart or some other system)Ensure worker clothing is clean and free of visible dust before leaving the work area Remove or isolate air diffusers (supply and return) to protect the HVAC system from dust and reduce air turbulence. Rebalance system to address diffuser isolation When the work involves or impacts potable water systems including stagnation due to reduced usage, the piping shall be flushed twice a week or isolated from the main system Seal doors to prevent dust migration Contain all trash and debris in the work area. Perform daily cleaning and disposal of trash (covered) from work area using an identified exit route.

Any equipment, tools, or materials removed from the work area must be in sealed containers and/or cleaned of dust and debris prior to removal from the area Nonporous/smooth and cleanable containers (with a hard lid) must be used to transport trash and debris from the construction areas. These containers must be damp-wiped cleaned and free of visible dust/debris before leaving the contained work area Install a sticky (dust collection) mat at entrance of contained work area based on facility policy. Sticky mats just be changed routinely and when visibly soiled.

Maintain clean surroundings when area is not contained by damp mopping or HEPA vacuuming surfaces at least daily

1.

2.

3.

Perform work activity in a manner that does not create dust Immediately replace ceiling tile, close access panels, etc. upon completion.

Any materials and equipment being brought into the facility must be free of contaminants and loose material

19.

20.

21.

22.

Barriers must be hard barriers unless temporary to install final barrier.

Containment must include an anteroom to ensure pressure control.

Anteroom must be large enough for equipment staging, cart cleaning, workers’ PPE and cleaning.

Worker clothing and/or PPE must be removed or clean and free of visible dust before leaving the work area anteroom. HEPA vacuuming of clothing or use of cover suits is acceptable Workers must wear shoe covers or have a method to clean shoes in anteroom. Shoe covers must be removed prior to exiting the anteroom to the occupied space (non-work area). Damaged shoe covers must be changed immediately.

CL

AS

S I

CL

AS

S

III

CL

AS

S

IV

YES

N/A

N/A

N/A

N/A

AFTER-HOURS WORK TO BE COORDINATED WITH VA COR

COORDINATE WITH VA COR ON PATIENT CARE FLOORS

TEMPORARY WALLS TO BE 1-HR RATED - PREFABRICATED

WALLS / DOOR PREFERRED

TECHNOLOGY AND ELECTRICAL FOCUSED WORK -

MINIMAL PLUMBING OR MECHANICAL IMPACT

MINOR INTERIOR RENOVATION IN EXISTING BUSINESS

OCCUPANCY AREAS - SEE PLAN

Walter Hoffman (914) 208-6275 Walter Hoffman (914) 208-6275 Walter Hoffman (914) 208-6275

NTSF2 TYPICAL ICRA PRODUCTS

DN

UP

UP

DN

UP

DN

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A1

A.

B.

C.

D.

E.

F.

G.

H.

I.

SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

NEW TELECOM ROOMS SHALL COMPLY WITH THE LATEST VA

PHYSICAL SECURITY STANDARDS, AND CAMPUS STANDARDS.

SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

SEE TYPICAL CEILING DETAILS ON SHEET A-531

PROVIDE TEMPORARY AIR TIGHT BARRIER AROUND WORK AREA

DURING ANY ACTIVITIES WHICH PRODUCE DUST, TYPICAL.

MAINTAIN CLEAR EXIT PATHS AND STAIRS AT ALL TIMES.

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

NO SCOPE

13A-400 D3

TELECOM

ROOM

110 SF

B

B B

B

EXTG VIF

9'-4"

EX

TG

V

IF

'-0

4'-3"

(EXTG V.I.F.)

1'-1"5

B1 13A-511

IT CLOSET

102102

IT CLOSET

102102

ELEVATOR

93 SF

ELEVATOR

72 SF

ELEVATOR

VESTIBULE

166Z

95 SF

CENTER

STAIR

101C101C

TELECOM

ROOM

110 SF 78

PATH OF REMOVAL

FROM ELEVATOR

TO EXTERIOR

PROVIDE DUMPSTER 35' MINIMUM FROM

ANY BUILDING, AND 6'-0" HIGH

TEMPORARY CONSTRUCTION FENCE AND

GATE. TO BE LOCKED AT ALL TIMES,

PROVIDE COR WITH KEY. COORDINATE

FINAL LOCATION WITH COR

PROVIDE CART FOR DAILY

WASTE REMOVAL

COORDINATE FINAL

LOCATION WITH COR

LOADING DOCKS WILL BE IN

USE DURING CONSTRUCTION.

COORDINATE ANY

CONSTRUCTION VEHICULAR

ACTIVITY TO ENSURE ACCESS

TO LOADING AREAS ARE NOT

IMPEDED.

TRANSITE PANELS

TP

100 SF ± TRANSITE PANELS BEHIND

RADIATOR, MASTIC AND CAULKING

(AT WINDOWS) TO BE ABATED

GROUND FLOOR

TP10

TELECOM

ROOM

105 SF

B

B

B

B

EXTG VIF

11'-2"

EX

TG

V

IF

9'- 2"

3'-10"

(EXTG V.I.F.)

4'-3" 5

B1 13A-511

IT ROOM

202202

IT ROOM

202202

13A-400 D8

TELECOM

ROOM

105 SF

TN

PN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .A

R C

H .B

.rv t 3/

/2

5:

:0

PM

13A-400

ARCHITECTURAL ENLARGED VIEWS - FIRST &

SECOND LEVELS

620-22-700

06/27/2025 M.PERKINS N.

BLANCHARD

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

1 REMOVE EXISTING DOOR AND FRAME.

2 REMOVE EXISTING FLOORING AND WALL BASE.

3 EXISTING CEILING TO REMAIN.

4 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C

FIRE EXTINGUISHER LOCATED NO GREATER THAN 75 FEET AWAY

FROM THE NEW TR. CONTRACTOR SHALL BID A NEW FEC FOR EACH

TR IN THE SCOPE OF WORK. SEE SPECIFICATION 10 44 13.

5 NEW INFILL AT EXTERIOR. NEW WALL TO MATCH EXISTING.

6 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK AREA

DURING ANY ACTIVITIES WHICH PRODUCE DUST - TYPICAL

7 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

8 REMOVE EXISTING ACOUSTICAL CEILING AND LIGHTS. MODIFY

AND/OR PROVIDE ADDITIONAL SUPPORTS AS REQUIRED FOR

EXISTING CEILING ITEMS TO REMAIN.

9 NEW DOOR. SEE DOOR SCHEDULE AND SPECIFICATIONS FOR

ADDITIONAL INFORMATION. COORDINATE DOOR AND FRAME WITH

ACCESS CONTROL HARDWARE.

10 ABATE TRANSITE PANEL BEHIND RADIATOR BELOW WINDOW

11 ACCESS DOOR PER SPECIFICATION, COR TO CONFIRM LOCATION

AND MOUNTING HEIGHT.

12 REMOVE EXISTING WINDOW. PROVIDE TEMPORARY INFILL.

13 EXISTING STAIR TO BE REMOVED BY VA, PRIOR TO START OF EHRM

PROJECT.

14 ANY NEW GROUND LEVEL CHILLER PIPES ATTACHED TO EXTERIOR

WALLS SHALL BE PAINTED IN THEIR ENTIRETY TO MATCH BRICK

COLOR. REQUIREMENT OF NEW YORK STATE PARKS, RECREATION

AND HISTORIC PRESERVATION (SHPO) DOCUMENT 24PR00345

JFXVGRV7XYPA DATED DECEMBER 9,2024.

15 AT NEW WALL INSTALLATIONS, CONTRACTOR TO PAINT NEW WALL

IN ITS ENTIRETY. INSTALL NEW WALL BASE AT ENTIRE WALL SPAN

OR APPROPRIATE TRANSITION LOCATION AS APPROVED BY THE

COR. OR CAMPUS INTERIOR DESIGNER.

1/32" = 1'-0"F3 FIRST LEVEL REFERENCE PLAN

1/4" = 1'-0"D3

ARCHITECTURAL ENLARGED FLOOR PLAN -

FIRST LEVEL - ROOM 102 - NEW

1/4" = 1'-0"D1

ARCHITECTURAL ENLARGED FLOOR PLAN -

FIRST LEVEL - ROOM 102 - DEMO

1/4" = 1'-0"B3

ARCHITECTURAL REFLECTED CEILING PLAN -

FIRST LEVEL - ROOM 102 - NEW

1/4" = 1'-0"B2

ARCHITECTURAL REFLECTED CEILING PLAN -

FIRST LEVEL - ROOM 102 - DEMO

1/32" = 1'-0"F7 SECOND LEVEL REFERENCE PLAN

1/4" = 1'-0"D8

ARCHITECTURAL ENLARGED FLOOR PLAN -

SECOND LEVEL - ROOM 202 - NEW

1/4" = 1'-0"D6

ARCHITECTURAL ENLARGED FLOOR PLAN -

SECOND LEVEL - ROOM 202 - DEMO

1/4" = 1'-0"B8

ARCHITECTURAL REFLECTED CEILING PLAN -

SECOND LEVEL - ROOM 202 - NEW

1/4" = 1'-0"B6

ARCHITECTURAL REFLECTED CEILING PLAN -

SECOND LEVEL - ROOM 202 - DEMO

NTSF4 SITE DIAGRAM - BUILDING 13

SUMMARY OF ESTIMATED QUANTITY OF ASBESTOS CONTAINING

MATERIAL TO BE REMOVED

1.

2.

3.

4.

FLOORING 0 SF ANTICIPATED

LEAD-CONTAINING PAINT 0 SF ANTICIPATED

NOTES:

ABATEMENT SCOPE INCLUDES DEMO WORK AS REQUIRED TO ACCESS ACM.

CONTRACTOR TO FIELD VERIFY QUANTITIES.

CONTRACTOR TO AVOID DISRUPTION OF ACM WIRING LOCATIONS. PROVIDE

COORDINATION DRAWINGS TO LOCATE ANY ACM CONTAINING ITEMS IN CHASES

OR PLENUMS THAT CANNOT BE AVOIDED.

REFER TO ACM REPORTS IN SPECIFICATIONS.

CONFERENCE ROOM

15E

OFFICE

15F

OFFICE

15D

OFFICE

15C

OFFICE

15G

MENTAL HEALTH

15H

TOILET

15B

STAFF LOUNGE

15AMECHANICAL CLOSET

OFFICE

15I

UNION OFFICE

UNION OFFICE

STORAGE

ELEV. SERVICE ROOM

STAIRS

PHONE CLOSET

1A

OFFICE

14D

GYM / REHAB CLINIC

NORTH STAIR

HOUSE-KEEPING

SHOWER ROOM

11A

MALE LOCKER ROOM

TRANSFORMER ROOM

14E

TOILET

14B

STORAGE

STORAGE

4D

VACANT

OFFICE

4A

OFFICE

4B

STORAGE

4C

RECEIVING AREA

TOILET

6B

HALL

6D

TOILET

6C

TOILET

6A1

PIPE CHASE

6A

CANTEEN RETAIL STORE

6E

SOUTH STAIR

OFFICE

OFFICE

TOILET

10B

SUPPLY CLOSET

10A

MENTAL HEALTH

OFFICE

10G

OFFICE

10F

OFFICE

10E1

CONFERENCE ROOM

10E

OFFICE

6F

KITCHEN

6G

HALLWAY

STORAGE

STORAGE

9A

TELEPHONE CLOSET

1B

CANTEEN DINING AREA

PIPE SPACE

14A

PIPE SPACE

14F

CLOSET

3A

CLOSET

9B

SOUTHWEST STAIR

Room

Room

CLOSET

15K

TOILET

14G

GYM / REHAB CLINIC

B13-MDPB

13E-401 F3

13E-401 F1

TN

PN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

STAMP

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .M

EP

.B

.rv t 3/

/2

5:

:2

PM

13E-101

ELECTRICAL PLAN - GROUND LEVEL 620-22-700

06/27/2025 M. Perkins J. Castenir

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

27.

28.

29.

30.

PROVIDE NEW 16" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF

BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE

AND CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V 3-PHASE

CIRCUIT AND RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES

SHEETS FOR MORE DETAILS. ADDITIONALLY PROVIDE ADEQUATE RACK RAIL KIT

AND NIC FOR THE ASSOCIATED UPS.

PROVIDE ONE NEW EMERGENCY AND ONE NEW NORMAL POWER BRANCH

120/208 TPST CIRCUIT BREAKER FED FROM ABOVE FOR EACH RACK UPS

CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS, AND DEVICES TO SUPPLY

EACH NEW RECEPTACLE. SEE T-500 SERIES SHEETS FOR MORE DETAILS.

NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR

ADDITIONAL INFORMATION.

NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A

WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.

NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS

FOR ADDITIONAL INFORMATION.

NOT USED.

NOT USED.

PROVIDE AND INSTALL NEW JOHNSON CONTROLS iSTAR EDGE G2 IP-BASED

ACCESS CONTROL PANEL. PROVIDE LIFESAFETY POWER (LSP) PSX UNIFIED

ENCLOSURE WITH INTEGRATED BACKUP BATTERIES PROVIDING A MINIMUM OF 4

HOURS OF STANDBY POWER.