ATTACHMENT 19 - Montrose.EHRM.Addendum.01.B07.20260330.pdf

PDF 25 MB Posted

Attached to
Z2DA--620-22-700 Electronic Health Record Modernization Infrastructure Upgrades - Franklin Delano Roosevelt VA Hospital, Montrose, NY
Solicitation number
RFP-36C77626R0033
Issued by

About this file

This is an architectural addendum document (Attachment 19) containing drawing index, life safety plans, infection control protocols, hazardous material abatement plans, and detailed construction drawings for the Electronic Health Record Modernization (EHRM) Infrastructure Upgrades project at Franklin Delano Roosevelt VA Hospital in Montrose, NY. The project involves interior renovations across three floors of Building 7 and a Main Computer Room (MCR) facility, with work including telecommunications room upgrades, infrastructure improvements, and hazardous material removal.

The project scope encompasses demolition and renovation of existing spaces to create new telecommunications rooms on the ground floor (Room 20, 157 SF), first floor (Room 148, 171 SF), and second floor (Room 243A, 95 SF), along with site infrastructure upgrades including utilities, grading, stormwater management, and fire protection systems. Key requirements include infection control risk assessment (ICRA) protocols for construction activities, hazardous material abatement for confirmed asbestos-containing materials (pipe insulation, flooring, transite panels) and lead-based paint, life safety compliance with 2024 NFPA 101 codes, and comprehensive telecommunications cabling infrastructure upgrades to Category 6A standards. The project maintains occupied space operations during construction, requires temporary barriers and negative air pressure systems in work areas, and includes coordination of electrical, mechanical, plumbing, and fire protection systems. Addendum #1, dated March 30, 2026, removes one sheet from construction documents and updates project information accordingly.

View the file

Other files

File Type Posted
Amendment 5 - 36C77626R0033 0005.pdf PDF
5-4 - RFI TRACKING SHEET.pdf PDF
Amend 5 - B01.20260330.pdf PDF
Amend 5 - B16.20260330.pdf PDF
Amend 5 - B19.20260330.pdf PDF
Amend 5 - B29.20260330.pdf PDF
Amend 5 - B52.20260330.pdf PDF
Amend 5 - SITE.20260330.pdf PDF
Original attachments 1-12.zip ZIP file
ATTACHMENT 3 - 01 00 00.B - Appendix B - Submittal Log.pdf PDF
ATTACHMENT 8 - 01 00 00.G - Appendix G - GPRS Triple C Montrose Full Report.pdf PDF
ATTACHMENT 16 - Montrose.EHRM.Addendum.01.B04.20260330.pdf PDF
ATTACHMENT 21 - Montrose.EHRM.Addendum.01.B13.20260330.pdf PDF
ATTACHMENT 24 - Montrose.EHRM.Addendum.01.B16.20260330.pdf PDF
ATTACHMENT 27 - Montrose.EHRM.Addendum.01.B20.20260330.pdf PDF
ATTACHMENT 28 - Montrose.EHRM.Addendum.01.B26.20260330.pdf PDF
ATTACHMENT 28A - Montrose.EHRM.Addendum.01.B27.20260330.pdf PDF
ATTACHMENT 32 - Montrose.EHRM.Addendum.01.B52.20260330.pdf PDF
ATTACHMENT 33A - 00 41 13.10 - Construction Estimate Breakdown Template.xlsx XLSX spreadsheet
RFI TRACKING SHEET - SOLICITATION 36C77626R0033.pdf PDF
ATTACHMENT 1 - SPECS - 620-22-700.Montrose.EHRM.Spec.IFC.20260410.pdf PDF
ATTACHMENT 5 - 01 00 00.D - Appendix D - SOP 138-06HV OCCUPATIONAL SAFETY AND HEALTH PROGRAM.pdf PDF
ATTACHMENT 11 - 01 00 00.I - Appendix I - K9245005 VAMC EHRM Montrose NY GeoReport 4.12.2024.pdf PDF
ATTACHMENT 12A - Summary.Log.Add01_20260410.pdf PDF
ATTACHMENT 13 - Montrose.EHRM.Addendum.01.B01.20260330.pdf PDF
ATTACHMENT 14 - Montrose.EHRM.Addendum.01.B02.20260330.pdf PDF
ATTACHMENT 22 - Montrose.EHRM.Addendum.01.B14.20260330.pdf PDF
ATTACHMENT 25 - Montrose.EHRM.Addendum.01.B17.20260330.pdf PDF
Amendment 2 - 36C77626R0033 0002.pdf PDF
Site visit sign-in sheet 3-23-26.pdf PDF
Attachment 1 - SPECS - 620-22-700.Montrose.EHRM.Spec.IFC.20260205.pdf PDF
Attachment 6 - 01 00 00.E - Appendix E - VHA ICRA-1.3 - Dec 9 2024.pdf PDF
Attachment 7 - 01 00 00.F - Appendix F - VHA PCRA 2024 1.1 Final.Template Fillable.pdf PDF
Attachment 8 - 01 00 00.G - Appendix G - GPRS Triple C Montrose Full Report.pdf PDF
Attachment 9 - 01 00 00.H - Appendix H - J2237038 Montrose ACM Ld Pnt InspRpt Final 8-21-2023.pdf PDF
Attachment 12 - Additional Security Badging Requirements rev 2.pdf PDF
Attachment 13 - Drawing B01 20250627.pdf PDF
Attachment 31 - Drawing B31 20250627.pdf PDF
Attachment 33 - Drawing Site 20250627.pdf PDF
RFP - 36C77626R0033.pdf PDF
Attachment 3 - 01 00 00.B - Appendix B - Submittal Log.pdf PDF
Attachment 4 - 01 00 00.C - Appendix C1 SOP 138-22HV CONST STD PROCEDURES QA FOR PROJECTS.pdf PDF
Attachment 5 - 01 00 00.D - Appendix D1 SOP 138-06HV OCCUPATIONAL SAFETY AND HEALTH PROGRAM.pdf PDF
Attachment 16 - Drawing B04 20250627.pdf PDF
Attachment 18 - Drawing B06 20250627.pdf PDF
Attachment 22 - Drawing B14 20250627.pdf PDF
Attachment 27 - Drawing B20 20250627.pdf PDF
Attachment 29 - Drawing B28 20250627.pdf PDF
Attachment 32 - Drawing B52 20250627.pdf PDF
Attachment 36 - Division Cost Breakdown.xlsx XLSX spreadsheet
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

STAMP

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .M

EP

.B

.rv t 3/

/2

:4

5:

P M

07G-001

DRAWING INDEX 620-22-700

06/27/2025 M. PERKINS K.

MCDERMOTT

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

- DRAWING INDEX -

SHEET

NUMBER SHEET NAME INCLUDED IN 35% SD INCLUDED IN 65% DD INCLUDED IN 95% CD ISSUED FOR CONSTRUCTION

GENERAL

07G-000 COVER SHEET Yes Yes Yes Yes 07G-001 DRAWING INDEX Yes Yes Yes Yes 07G-010 GENERAL PROJECT NOTES Yes Yes Yes Yes 07G-012 GENERAL INDOOR AIR QUALITY NOTES Yes Yes Yes Yes 07GC001 PROJECT PHASING PLANS Yes Yes Yes Yes 07GC002 PROJECT PHASING PLANS Yes Yes Yes Yes

HAZARDOUS

07H-100 HAZARDOUS MATERIAL ABATEMENT PLAN - GROUND LEVEL No Yes Yes Yes 07H-101 HAZARDOUS MATERIAL ABATEMENT PLAN - FIRST LEVEL No Yes Yes Yes 07H-102 HAZARDOUS MATERIAL ABATEMENT PLAN - SECOND LEVEL No Yes Yes Yes

LIFE SAFETY & ICRA

07GI100 LIFE SAFETY PLAN - GROUND FLOOR No Yes Yes Yes

07GI300 INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - GROUND FLOOR

07GI301 INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - FIRST FLOOR

07GI302 INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - SECOND FLOOR

07GI303 INFECTION CONTROL & INTERIM LIFE SAFETY DETAILS

CIVIL

07VF101 CIVIL SITE SURVEY PLAN No Yes Yes Yes 07CD101 CIVIL DEMOLITION PLAN No Yes Yes Yes 07CS101 CIVIL SITE PLAN No Yes Yes Yes 07CG101 CIVIL GRADING PLAN No Yes Yes Yes 07CG102 STORMWATER POLLUTION PROTECTION PLAN No No Yes Yes 07CG201 CIVIL ACCESS ROAD PLAN & PROFILE No No No Yes 07CG501 CIVIL DETAILS - SHEET 1 No Yes Yes Yes 07CG502 CIVIL DETAILS - SHEET 2 No Yes Yes Yes 07CG503 CIVIL EROSION CONTROL DETAILS - SHEET 1 No No Yes Yes 07CU101 CIVIL UTILITY PLAN No Yes Yes Yes 07CU102 CIVIL UTILITY PLAN - FOUNDATION DRAIN No Yes Yes Yes 07CU201 CIVIL STORM DRAIN PLAN & PROFILE No Yes Yes Yes 07CU501 CIVIL UTILITY DETAILS - SHEET 1 No Yes Yes Yes 07CU502 CIVIL UTILITY DETAILS - SHEET 2 No No No Yes

STRUCTURAL

07S-001 STRUCTURAL GENERAL NOTES No Yes Yes Yes 07S-002 STRUCTURAL GENERAL NOTES CONTINUED No Yes Yes Yes 07S-003 STRUCTURAL SPECIAL INSPECTIONS No Yes Yes Yes 07S-101 STRUCTURAL FOUNDATION PLAN No Yes Yes Yes 07S-102 STRUCTURAL ROOF FRAMING PLAN No Yes Yes Yes 07S-103 STRUCTURAL FOUNDATION PLAN -GENERATOR No Yes Yes Yes 07S-104 STRUCTURAL FRAMING PLAN -GENERATOR No Yes Yes Yes 07S-501 TYPICAL DETAILS No Yes Yes Yes 07S-502 TYPICAL DETAILS No Yes Yes Yes 07S-503 TYPICAL DETAILS No Yes Yes Yes 07S-504 TYPICAL DETAILS No Yes Yes Yes 07S-505 TYPICAL DETAILS No Yes Yes Yes 07S-506 TYPICAL DETAILS No Yes Yes Yes 07S-510 FOUNDATION DETAILS AND SCHEDULES No Yes Yes Yes 07S-520 FRAMING DETAILS No Yes Yes Yes

ARCHITECTURAL

07A-001 ARCHITECTURAL SYMBOLS, & GENERAL NOTES No Yes Yes Yes 07A-101 ARCHITECTURAL PLAN - GROUND FLOOR No Yes Yes Yes 07A-102 ARCHITECTURAL PLAN - GROUND LEVEL - MAIN COMPUTER ROOM AND ENLARGED PLANS No Yes Yes Yes 07A-103 ARCHITECTURAL FLOOR AND ROOF PLANS - GENERATOR BUILDING No Yes Yes Yes 07AC102 ARCHITECTURAL REFLECTED CEILING PLAN - GROUND LEVEL - MAIN COMPUTER ROOM No Yes Yes Yes 07A-201 EXTERIOR ELEVATIONS No Yes Yes Yes 07A-202 EXTERIOR ELEVATIONS No Yes Yes Yes 07A-301 ARCHITECTURAL BUILDING SECTIONS AND DETAILS No Yes Yes Yes 07A-302 ARCHITECTURAL BUILDING SECTIONS AND DETAILS No Yes Yes Yes 07A-401 ARCHITECTURAL ENLARGED VIEWS - GROUND AND FIRST LEVELS No Yes Yes Yes 07A-402 ARCHITECTURAL ENLARGED VIEWS - SECOND FLOOR No Yes Yes Yes 07A-501 ARCHITECTURAL ROOF PLAN & DETAILS No Yes Yes Yes 07A-511 ARCHITECTURAL PARTITION AND FRAMING DETAILS No Yes Yes Yes 07A-512 ARCHITECTURAL PARTITION HEAD DETAILS No Yes Yes Yes 07A-531 ARCHITECTURAL CEILING DETAILS No Yes Yes Yes 07A-600 SCHEDULES AND DETAILS No Yes Yes Yes 07A-601 DOOR AND LOUVER DETAILS No

RENDERINGS

07A-900 ARCHITECTURAL CONCEPT RENDERINGS No Yes Yes Yes

INTERIORS

07IN001 INTERIOR NOTES AND FINISH LEGEND No Yes Yes Yes 07IN101 INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES No Yes Yes Yes 07IN501 INTERIOR FINISH DETAILS No Yes Yes Yes

EQUIPMENT

07Q-601 INTERIOR EQUIPMENT PLAN AND SCHEDULE - GROUND LEVEL - MAIN COMPUTER ROOM Yes

FIRE PROTECTION

07FX001 FIRE PROTECTION ABBREVIATIONS, SYMBOLS, AND DETAILS No Yes Yes Yes 07FX100A FIRE PROTECTION PLAN - GROUND LEVEL AREA A No Yes Yes Yes 07FX100B FIRE PROTECTION PLAN - GROUND LEVEL AREA B No Yes Yes Yes 07FX101 FIRE PROTECTION PLAN - FIRST LEVEL No Yes Yes Yes 07FX102 FIRE PROTECTION PLAN - SECOND LEVEL No Yes Yes Yes 07FX401 FIRE PROTECTION ENLARGED PLANS No Yes Yes Yes 07FX402 FIRE PROTECTION ENLARGED PLANS No Yes Yes Yes 07FX501 FIRE PROTECTION DETAILS AND SCHEDULES No Yes Yes Yes 07FX502 FIRE PROTECTION DETAILS AND SCHEDULES No Yes Yes Yes 07FX901 FIRE PROTECTION CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 07FX902 FIRE PROTECTION CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes

PLUMBING

07P-001 PLUMBING ABBREVIATIONS AND SYMBOLS No Yes Yes Yes 07P-100 PLUMBING PLAN - GROUND LEVEL No Yes Yes Yes 07P-100B PLUMBING PLAN - GROUND LEVEL AREA B No Yes Yes Yes 07P-101B PLUMBING PLAN - ROOF LEVEL AREA B No Yes Yes Yes 07P-600 PLUMBING ISOMETRIC VIEW No Yes Yes Yes 07P-901 PLUMBING CUTSHEETS No Yes Yes Yes

MECHANICAL

07M-001 MECHANICAL ABBREVIATIONS AND SYMBOLS No Yes Yes Yes 07M-100 MECHANICAL PLAN - GROUND LEVEL No Yes Yes Yes 07M-100B MECHANICAL PLAN - GROUND LEVEL AREA B No Yes Yes Yes 07M-101 MECHANICAL PLAN - FIRST LEVEL No Yes Yes Yes 07M-102 MECHANICAL PLAN - SECOND LEVEL No Yes Yes Yes 07M-400 MECHANICAL ENLARGED PLANS No Yes Yes Yes 07M-401 MECHANICAL ENLARGED PLANS No Yes Yes Yes 07M-402 MECHANICAL ENLARGED PLANS No Yes Yes Yes 07M-403 MECHANICAL ENLARGED PLANS No Yes Yes Yes 07M-404 MECHANICAL ENLARGED PLANS No Yes Yes Yes 07M-501 MECHANICAL DETAILS No Yes Yes Yes 07M-502 MECHANICAL DETAILS No Yes Yes Yes 07M-503 MECHANICAL DETAILS No Yes Yes Yes 07M-504 MECHANICAL DETAILS No Yes Yes Yes 07M-701 MECHANICAL SCHEDULES No Yes Yes Yes

- DRAWING INDEX -

SHEET

NUMBER SHEET NAME INCLUDED IN 35% SD INCLUDED IN 65% DD INCLUDED IN 95% CD ISSUED FOR CONSTRUCTION 07M-702 MECHANICAL SCHEDULES No Yes Yes Yes 07M-801 MECHANICAL CONTROL SYMBOL LEGEND AND ABBREVIATIONS No Yes Yes Yes 07M-802 MECHANICAL CONTROL DIAGRAMS No Yes Yes Yes 07M-803 MECHANICAL CONTROL DIAGRAMS No Yes Yes Yes 07M-804 MECHANICAL CONTROL DIAGRAMS No Yes Yes Yes 07M-805 MECHANICAL CONTROL DIAGRAMS No Yes Yes Yes 07M-806 MECHANICAL CONTROLS RISER DIAGRAM No Yes Yes Yes 07M-807 MECHANICAL CONTROLS RISER DIAGRAM No Yes Yes Yes 07M-901 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 07M-902 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 07M-903 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 07M-904 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 07M-905 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes

ELECTRICAL

07E-001 ELECTRICAL ABBREVIATIONS AND SYMBOLS Yes Yes Yes Yes 07ES100 ELECTRICAL PLAN - SITE PLAN No Yes Yes Yes 07ES101 ELECTRICAL SITE PLAN - ENLARGED No Yes Yes Yes 07ES102 ELECTRICAL SITE PLAN - ENLARGED No No No Yes 07E-100 ELECTRICAL PLAN - GROUND LEVEL - BLDG 7 No Yes Yes Yes 07E-100B ELECTRICAL PLAN - GROUND LEVEL - MCR BLDG No Yes Yes Yes 07E-101 ELECTRICAL PLAN - FIRST LEVEL - BLDG 7 No Yes Yes Yes 07E-102 ELECTRICAL PLAN - SECOND LEVEL - BLDG 7 Yes Yes Yes Yes 07E-102B ELECTRICAL LIGHTNING PLAN - ROOF LEVEL - MCR BLDG No No No Yes 07E-200B ELECTRICAL REFLECTED CEILING PLAN - GROUND LEVEL - MCR BLDG No Yes Yes Yes 07E-200C ELECTRICAL REFLECTED CEILING PLAN - GROUND LEVEL - MCR LIGHTING LUMENS No Yes Yes Yes 07E-400 ELECTRICAL ENLARGED PLANS - BLDG 7 No Yes Yes Yes 07E-401 ELECTRICAL ENLARGED PLANS - BLDG 7 No Yes Yes Yes 07E-402 ELECTRICAL ENLARGED PLANS - BLDG 7 No Yes Yes Yes 07E-403 ELECTRICAL ENLARGED PLANS - MCR No Yes Yes Yes 07E-404 ELECTRICAL ENLARGED PLANS - MCR No Yes Yes Yes 07E-405 ELECTRICAL ENLARGED PLANS - MCR No Yes Yes Yes 07E-501 ELECTRICAL DETAILS Yes Yes Yes Yes 07E-502 ELECTRICAL DETAILS Yes Yes Yes Yes 07E-503 ELECTRICAL DETAILS Yes Yes Yes Yes 07E-504 ELECTRICAL DETAILS Yes Yes Yes Yes 07E-601 ELECTRICAL ONE-LINE DIAGRAMS -DEMOLITION Yes Yes Yes Yes 07E-602 ELECTRICAL ONE-LINE DIAGRAMS - NEW CONSTRUCTION No Yes Yes Yes 07E-603 ELECTRICAL ONE-LINE DIAGRAMS & DETAIL - MCR No No No Yes 07E-701 ELECTRICAL SCHEDULES - BLDG 7 No Yes Yes Yes 07E-702 ELECTRICAL SCHEDULES - BLDG 7 No Yes Yes Yes 07E-703 ELECTRICAL SCHEDULES - MCR No Yes Yes Yes 07E-704 ELECTRICAL SCHEDULES - MCR No Yes Yes Yes 07E-901 ELECTRICAL CUTSHEETS & BASIS OF DESIGN Yes Yes Yes Yes 07E-902 ELECTRICAL CUTSHEETS & BASIS OF DESIGN Yes Yes Yes Yes 07E-903 ELECTRICAL CUTSHEETS & BASIS OF DESIGN No No No Yes

TELECOMMUNICATION

07T-001 TELECOMMUNICATION ABBREVIATIONS AND SYMBOLS Yes Yes Yes Yes 07T-100 TELECOMMUNICATION PLAN - GROUND LEVEL - BLDG 7 Yes Yes Yes Yes 07T-100B TELECOMMUNICATION PLAN - GROUND LEVEL - MCR BLDG No Yes Yes Yes 07T-101 TELECOMMUNICATION PLAN - FIRST LEVEL - BLDG 7 Yes Yes Yes Yes 07T-102 TELECOMMUNICATION PLAN - SECOND LEVEL - BLDG 7 Yes Yes Yes Yes 07T-401 TELECOMMUNICATION ENLARGED PLANS - BLDG 7 No Yes Yes Yes 07T-501 TELECOMMUNICATION DETAILS Yes Yes Yes Yes 07T-502 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS Yes Yes Yes Yes 07T-503 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS Yes Yes Yes Yes 07T-504 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS No Yes Yes Yes 07T-505 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS No Yes Yes Yes 07T-601 TELECOMMUNICATION RISER DIAGRAMS Yes Yes Yes Yes 07T-603 TELECOMMUNICATION FIBER RISER DIAGRAM - NEW No Yes Yes Yes 07T-604 TELECOMMUNICATION TR ELEVATIONS RMS 20/148/243 Yes Yes Yes Yes 07T-605 TELECOMMUNICATION MCR NEW ELEVATIONS / MDA / RM 23 Yes Yes Yes Yes 07T-606 TELECOMMUNICATION MCR NEW ELEVATIONS / HDA-SVR / RM 23 Yes Yes Yes Yes 07T-607 TELECOMMUNICATION EXISTING CORE ELEVATIONS B03 RM 214 Yes Yes Yes Yes 07T-701 TELECOMMUNICATION SCHEDULES No Yes Yes Yes 07T-702 TELECOMMUNICATION SCHEDULES No Yes Yes Yes 07T-901 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN Yes Yes Yes Yes 07T-902 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN No No Yes Yes 07T-903 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN No No Yes Yes

REFERENCE

07R-900 PHOTO REFERENCES No Yes Yes Yes Grand total: 164

# Revisions: Date:

1 ADDENDUM #1 03/30/2026

07G-011 REMOVED FROM

CONSTRUCTION DOCUMENTS

Ranjan Text Box

DN DNDN

LIFE SAFETY SYMBOLS

PATH OF TRAVEL

(FOR CUMULATIVE DISTANCES

REFER TO SCHEDULE)

EXIT LIGHTING

TM

FIRE EXTINGUISHER CABINET (FEC)

FIRE EXTINGUISHERS (FE)

FIRE HOSE CABINETS (FHC)

HEAT DETECTOR

SMOKE DETECTOR

DIRECTION OF EGRESS

APPLICABLE BUILDING CODES

2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL FIRE

ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD FOR

INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF NFPA

5000 AND NFPA 900

2024 INTERNATIONAL MECHANICAL CODE (IMC)

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA)

STANDARDS.

VA SEISMIC DESIGN REQUIREMENTS, H-18-8

2026 NATIONAL ELECTRICAL CODE (NEC)

2024 INTERNATIONAL PLUMBING CODE (IPC)

ASME BOILER AND PRESSURE VESSEL CODE

ASME CODE FOR PRESSURE PIPING

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS

(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN

GUIDE (PG-18-13)

BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE,

AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318)

MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE

FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL

BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION

(AISC)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS

FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE

RESIDENTIAL BUILDINGS AND NEW LOW-RISE RESIDENTIAL

BUILDINGS, 10 CFR PARTS 433, 434 AND 435

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND

SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING

(MOU)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL

ENVIRONMENTAL, ENERGY, AND TRANSPORTATION

MANAGEMENT

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.

STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00 AND

01 35 26 OF THE VA MASTER CONSTRUCTION SPECIFICATION.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE

STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE 170-2025, NON-

MEDICAL SPACES - ASHRAE 62.1-2025

SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE

STANDARD 15–2024

2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED BY

VA STANDARDS

UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE

STANDARD OR CODE SHALL BE USED

APPLICABLE BUILDING GUIDES

VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)

BUILDING CODE:

CONSTRUCTION TYPE:

TYPE II (000) PER NFPA 220, Chapter 4 TYPE OF BUILDING: Business Occupancy

Allowable Area and Allowable Stories is not Limited in NFPA by occpancy.

The buidling is supplied with 2 storage rooms set up to become future stairs to serve as 2 exits from upper floors38.2.4.1, and provided with Emergency Lighting 38.2.9.1,and a Fire Alarm system 38.3.4.1.

Current Stories: 1 Possible Future Stories: 5

FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)

FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING

ELEMENTS:

STRUCTURAL FRAME 0 HOURS

NON-BEARING WALLS 0 HOURS

BEARING WALLS 0 HOURS

FLOORS 0 HOURS

ROOFS/ CEILINGS 0 HOURS

FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)

FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY

FUNCTION:

ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)

SMOKE COMPARTMENTS 1/2 HOUR

SOILED UTILITY ROOMS 1 HOUR

VERTICAL SHAFTS / STAIRS 2 HOURS

MEDICAL GAS / HAZARDOUS

STORAGE 1 HOURS

7.1.3.2.1 (3) The separation shall have a minimum 2-hour fire resistance rating where the exit connects four or more stories.

NFPA 52.2.2.3.4 In assembly, educational, detention and correction facilities;

health care, ambulatory health care, and day care centers; and, residential board and care and residential occupancies, battery systems shall be located in a room separated from other portions of the building by a minimum of a 2-hour fire barrier. THE MCR (Main Computer Room) IS A MISSION CRITICAL

FACILITY AND PROVIDING A 2 HOUR ADDS ADDITIONAL PROTECTION

TO PROTECT THE SPACE.

MIXED BUILDING OCCUPANCY TYPE:

EXISTING GROUND FLOOR - BUSINESS OCCUPANCY

ADDITION - BUSINESS OCCUPANCY

6.1.14.1.3 Where incidental to another occupanct, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:

(1) Mercantile, BUSINESS, industrial, or storage use

6.1.14.3 Mixed Occupancies

6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.

Table 6.1.14.4.1 (a) - separation of occupanies - 2 Hr between Health Care and Business

6.2 Hazard of Contents.

6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or stucture, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.

EXIT ACCESS TRAVEL DISTANCE:

38.2.6.2 The travel distance between any point in a room and an exit shall not exceed 200 ft.

38.2.6.3 The maximum travel distance...shall not exceed 300 ft in buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7.

BUSINESS OCCUPANCY; PROTECTED = 300'-0"

OCCUPANT LOAD:

38.1.7 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.

CALCULATED OCCUPANT LOADS

PROJECT AREA = 27 TOTAL OCCUPANTS

ADJACENT AREA = N/A

MEANS OF EGRESS:

38.2.3 Capacity of Means of Egress.

38.2.3.1 The capacity of any required means of egress shall be determined in accordance with the provisions Section 7.3.

38.2.3.2 The clear width of any corridor or passageway serving an occupant load of 50 or more shall not be less than 44 in. (1120 mm).

38.2.4 Number of Means of Egress.

38.2.4.1 Means of egress shall comply with all of the flollowing: except as permitted by 38.2.4.2-6

1) the number of means of egress shall be in accordance with section 7.4

2) not less than two separate exits shall be provicded on every story.

3) Not less than two separate exits shall be accessible from every part of every story.

38.2.5.3.1 In building protected throughout by and approvide supervised autoamatic sprinkler system, Dead-end corridors shall not exceed 50 ft.

PROTECTION FROM HAZARDS:

38.3.2 Protection from Hazards.

38.3.2.1 Hazardous Areas

38.3.2.2 High Hazard Contents areas, (section 6.2) shall meet all of the following criteria:

1) The area shall be separated from other parts of the buidling by fire barriers having a minimum 1 hour fire resistance rating, with all openings therein protected by self-closing fire door assemblies having a minimum 3/4 hour fire protection rating

2) The area shall be protected by an automatic extinguishing system in accordance with 9.7.1.1(1) or 9.7.1.2

38.3.2.3 Hazardous Materials. Where hazardous materils are stored or handled, the provisions of 8.7.3.1 shall apply.

38.3.2.4 Medical Gas. Medical gas storage areas and the operation, management and maintenance of medical gases shall be in accordance with

NFPA 99.

38.3.5. Portable fire extinguishers shall be provided in every business occupancy in accordance with Section 9.9.

38.5.1 Utilities shall comply with the provisions of Section 9.1

PARKING SUMMARY:

NO ADDITIONAL PARKING ADDED.

50'-0" AGGREGATE DISTANCE

WIDTH PROVIDEDP: XX"

R: XX" WIDTH REQUIRED

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

TYPICAL ASSEMBLY INFORMATION

THERMAL REQUIREMENT SATISFY ASHRAE 90.1, CLIMATE

ZONE 5A

TYPICAL VENTED ROOF ASSEMBLY : R-30 CI

ASPHALT SHINGLES OVER ROOF UNDERLAYMENT

MEMBRANE ON VENTED NAILABLE INSULATION PANELS

(5-7/16" THICK, R-20.5 MIN), OVER ADDITIONAL 3" RIGID

POLYISO INSULATION (R-10 MIN), OVER VAPOR BARRIER

APPLIED TO METAL ROOF DECKING.

TYPICAL LOW-SLOPE MEMBRANE ROOF ASSEMBLY: R-30

CI

ASPHALT MEMBRANE, TO MATCH ASPHALT SHINGLES,

OVER ROOF UNDERLAYMENT MEMBRANE ON VENTED

NAILABLE INSULATION PANELS (5-7/16" THICK, R-20.5 MIN),

OVER ADDITIONAL 3" RIGID POLYISO INSULATION (R-10

MIN), OVER VAPOR BARRIER APPLIED TO METAL ROOF

DECKING.

TYPICAL BRICK ON STUD WALL ASSEMBLY : R-13+R-10 CI

3-5/8" BRICK WITH AIRSPACE (MAY VARY, 2" MIN) WITH

BRICK TIES SPACED AS REQUIRED. 3" RIGID INSULATION,

CONTINUOUS FLUID-APPLIED AIR BARRIER ON 8" CMU

BLOCK. PROVIDE BRICK VENTS AND INSECT SCREENS AT

16" O.C. TOP AND BOTTOM OF EACH CAVITY SPACE,

STAGGERED-HEIGHT MORTAR-CATCH MESH

CONTINUOUS AT BASE OF EACH CAVITY SPACE.

STANDARD GLAZING: MAX U VALUE =.38, MAX SHGC

VALUE = .36

STANDARD OPAQUE DOOR: MAX U VALUE = .37

Exx - xxx'

17303 SF

BUSINESS

NFPA OCCUPANCY

Business

E1 ▬ 73.4'

DIAGONAL DISTANCE

56'-2" DISTANCE BETWEEN DOORS

58'-11"

E2 ▬ 62.5'

X5

.7

X4 ▬ 113.6'

X6 ▬ 128.2'

X7 ▬ 61.9'

X1

0.

9'

X2

3.

5'

X3

6.

4'

4185 SF

BUSINESS

NEW ADDITION

EXISTING BLDG

Name Area Occupancy (NFPA) OLF Fixed Seats Occupant Load

NEW ADDITION 4,063 BUSINESS 150 NO 27

AREA OCCUPANCIES

Name Area Occupancy (NFPA) Sprinkled Other Factor Req Width NEW ADDITION 4,063 BUSINESS yes .20" 5.4"

EGRESS SIZING

Name Area Occupancy (NFPA) OLF Fixed Seats Occupant Load

EXISTING 16,868 NO CHANGE TO 150 NO 113

CURRENT Occupancy

ASSUMED BUSINESS

AREA OCCUPANCIES

No change to Exiting - multiple paths - only minor work in existing area (TR room upgrades) No change to existing plumbing fixtures provided

P:

2'

8"

R:

3"

P: 5' - 8" R: 3"

ELEVATOR

ELEVATOR

STORAGE

STORAGE

3B3B

UTILITY CL.

CORRIDOR

ELECTRICAL

DISTRIBUTION

FISCAL

STORAGE

STAIR HALL C

SERVICE

ROOM

ELECTRICAL

STORAGE

MECH ROOM

EMS CLOSET

STAIR HALL A

ENTRANCE

SOILED LINEN

1616ENTRANCE

1717DECON

1818SPD DECON

TELECOM

ROOM

MECH. RM.

CORRIDOR

22Z22Z

STAIR HALL B

CORRIDOR

24Z24Z

STORAGE

19A19A

CORRIDOR

26Z26Z

ELEVATOR

LOBBY

25Z25Z

TELE. CL.

1B1B

TELE. CL.

1A1A

TLT

3A3A

OFFICE

5AB5AB

OFFICE

5C5C

OFFICE

5E5E

OFFICE

5F5F

OFFICE

5G5G

OFFICE

5H5H

OFFICE

5J5J

OFFICE

5K5K

OFFICE

5L5L

ENTRANCE

5G15G1

CORRIDOR

23Z23Z

4A4A

9A9A

CORRIDOR

11B11B

MEDICAL

CACHE

15A15A

STORAGE

15B15B

STORAGE

15C15C

17A17A

CORRIDOR

17B17B

SPD

STORAGE

17C17C

SPD

STORAGE

17D17D

FOYER

17E17E

OFFICE

17F17F

TLT

17G17G

SPD

17I17I

17J17J

17K17K

BATHROOM

19B19B

STAIR HALL 4

STAIR HALL 5

STORAGE

EXISTING - NO WORK

MAIN

COMPUTER

ROOM

023023

STORAGE

031031

FIBER

ENTRANCE

ROOM 01

032032

PUMP ROOM

030030EMERGENCY

POWER

028028

FIBER

ENTRANCE

ROOM 02

027027

STORAGE

026026

POWER

025025 STORAGE

024024

BREAK ROOM

032032

CORRIDOR

035035

EMS

033033

TOILET

034034FEC

FEC

FEC

EXIT NOT AFFECTED

BY CONSTRUCTION

EXIT NOT AFFECTED

BY CONSTRUCTION

EXIT NOT AFFECTED

BY CONSTRUCTION

EXIT NOT AFFECTED

BY CONSTRUCTION

TEMPORARY EGRESS

PATH MUST BE

MAINTAINED DURING

CONSTRUCTION

MIN.

5'-0"

MIN.

6'-0"

TEMPORARY EGRESS

PATH MUST BE

MAINTAINED DURING

CONSTRUCTION

TEMPORARY EGRESS

PATH MUST BE

MAINTAINED DURING

CONSTRUCTION

TEMPORARY EGRESS

PATH MUST BE

MAINTAINED DURING

CONSTRUCTION

EXIT NOT AFFECTED

BY CONSTRUCTION

EXIT NOT AFFECTED

BY CONSTRUCTION

REFER TO A-100 SHEETS FOR NO

WORK AREAS - NO WORK HATCH

NOT SHOWN HERE

EXIT FROM STAIR

FOR FLOORS ABOVE

NOT AFFECTED BY

CONSTRUCTION

COVER EXISTING EXIT SIGN AND POST "NOT

AN EXIT" SIGN DURING CONSTRUCTION.

RESTORE EXISTING EXIT SIGN AFTER

CONSTRUCTION COMPLETE

RAMP DOWN2 HR SEPARATION - to allow existing to be used as Health Care Occupancy in future if needed

'-1

0"

14'-6"

23'-7"

BUILDING SEPARATION CALCULATION NFPA 80A

BLDG WIDTH / BLDG HT - 78/14.33 = 5.44

LOW SEVERITY OF INTERIOR WALL AND CEILING FINISH

OPENING TO WALL% - 0% OPENINGS

FROM TABLE 4.3.7.4 - GUIDE NUMBER = .51

GUIDE NUMBER * BLDG HT +5FT = REQUIRED SEPARATION

.51 * 14.33 +5 = 12.30

= 12'-3 3/4" MINIMUM SEPARATION OF BUILDINGS AT LONGEST

SIDE (OTHER SIDES WOULD BE LESS)

78'-8"

ELECTRICAL

DISTRIBUTION

6B6B

MI

N.

5'- 0"

TN

PN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .A

R C

H .B

.rv t

-0 3-

8:

:0

07GI100

LIFE SAFETY PLAN - GROUND FLOOR 620-22-700

06/27/2025 M. Perkins C. Raynes

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPDATE

2094 Albany Post Road, Montrose, NY 10548

ORIGINAL BUILDING BUILT 1983 AND DESIGNED TO THE

UNIFORM BUILDING CODE 1979 EDITION

CURRENT RENOVATION DOES NOT ADD NEW SQUARE

FOOTAGE, CHANGE SMOKE COMPARTMENT

LOCATIONS, OR ALTER EXITING LOCATIONS.

CALCULATIONS REFLECT COMPLIANCE WITH THE NFPA

101 CODE 2021 EDITION

EXISTING BUILDING IS FULLY SPRINKLED

AREA OF RENOVATION: 16,560 SF

PATH OF TRAVEL SCHEDULE - GROUND FLOOR

Mark From Room To Room Type of Travel Path Length

GROUND LEVEL

(P-o-T) Distance to Exits

E1 STORAGE 024 (P-o-T) Distance to Exits 73' - 5 3/16" E2 STORAGE 031 CORRIDOR 035 (P-o-T) Distance to Exits 62' - 6 1/32" X1 FISCAL STORAGE 7 (P-o-T) Distance to Exits 70' - 10 1/4" X2 OFFICE 5J CORRIDOR 22Z (P-o-T) Distance to Exits 93' - 5 1/2" X3 OFFICE 5C (P-o-T) Distance to Exits 66' - 5 1/4" X4 SERVICE ROOM 9 (P-o-T) Distance to Exits 113' - 7 5/32" X5 MEDICAL CACHE 15A (P-o-T) Distance to Exits 109' - 7 15/16" X6 SPD 17I (P-o-T) Distance to Exits 128' - 2 5/16" X7 SPD STORAGE 17H (P-o-T) Distance to Exits 61' - 10 9/32"

1. REFER TO FIRE SPRINKLER SHEETS FOR SPRINKLER

HAZARD CLASSIFICATION AREAS

2. WORK IN BASEMENT AND SECOND LEVEL ARE

LIMITED TO MINOR REPAIR WHEN PLACING

MECHANICAL AND PLUMBING SYSTEMS. NO CHANGES

TO LIFE SAFETY ELEMENTS WILL BE REQUIRED.

New Addition - PLUMBING FIXTURES REQUIRED BY IBC TABLE 2902.1

WC UNISEX LAV UNISEX BATH/SHOWER DRINKING FOUNTAIN SERVICE SINK

Male/Female 1 PER 25 1 PER 40 0 1 PER 100 1 TOTAL Business

New Addition - PLUMBING FIXTURES REQUIRED

WC UNISEX LAV UNISEX BATH/SHOWER DRINKING FOUNTAIN SERVICE SINK

New Addition 1.08 1 0 1 0 27 occupants round to 1

New Addition - PLUMBING FIXTURES PROVIDED

WC UNISEX LAV UNISEX BATH/SHOWER DRINKING FOUNTAIN SERVICE SINK

New Addition 1 1 0 NO DF PROVIDED 1 27 occupants - WATER PROVIDED IN BREAK ROOM

KEYNOTES-

ORIGINAL CONSTRUCTION

INFORMATION

GENERAL NOTES

1/8" = 1'-0"F1 LIFE SAFETY PLAN - GROUND FLOOR

NOT USED

# Revisions: Date:

1 ADDENDUM #1 03/30/2026

DN

ELEVATOR

ELEVATOR

STORAGE

STORAGE

3B3B

UTILITY

CL.

CORRIDOR

ELECTRICAL

DISTRIBUTION

FISCAL

STORAGE

STAIR

HALL C

SERVICE

ROOM

99 ELECTRICAL

STORAGE

MECH

ROOM

STAIR

HALL A

ENTRANCE

SOILED

LINEN

ENTRANCE

DECON

SPD

DECON

MECH.

RM.

CORRIDOR

22Z22Z

STAIR

HALL B

CORRIDOR

24Z24Z

STORAGE

19A19A

CORRIDOR

26Z26Z

ELEVATOR

LOBBY

25Z25Z

TELE. CL.

1B1B

TELE. CL.

1A1A

TLT

3A3A

OFFICE

5AB5AB

OFFICE

5C5C

OFFICE

5D5D

OFFICE

5E5E

OFFICE

5F5F

OFFICE

5G5G

OFFICE

5H5H

OFFICE

5I5I

OFFICE

5J5J

OFFICE

5K5K

OFFICE

5L5L

ENTRANCE

5G15G1

CORRIDOR

23Z23Z

4A4A

MEDICAL

CACHE

15A15A

STORAGE

15B15B

STORAGE

15C15C

CORRIDOR

17B17B

SPD

STORAGE

17C17C

SPD

STORAGE

17D17D

FOYER

17E17E

OFFICE

17F17F

TLT

17G17G

SPD

STORAGE

17H17H

SPD

17I17I

17J17J

17K17K

BATHROOM

19B19B

STAIR

HALL 4

STAIR

HALL 5

STORAGE

TOILET

11B11B

CHASE

11A11A

3A

VESTIBULE

9C9C

ELECTRICAL

DISTRIBUTION

6B6B

E1 ▬ 29.7'

E2 ▬ 46.3'

INTERIM LIFE SAFETY DEAD END CORRIDOR LENGTH

9'-8"

INTERIM LIFE SAFETY DEAD END CORRIDOR LENGTH

22'-4"

SPS

DECONTAMINATION

INFECTION CONTROL / DUST

CONTROL PARTITION / BARRIER

INFECTION CONTROL/DUST CONTROL

EGRESS DOOR NON-TRANSFERRING

MULTI-SHEETED ADHESIVE FLOOR PADS

PATH OF DEMOLITION/TRASH

REMOVAL TRAVEL

CONSTRUCTION LIMIT LINE

NOT IN CONTRACT AREA

DEMOLITION

LASER PARTICLE COUNT LOCATION

LIFE SAFETY SYMBOLS

PATH OF TRAVEL

(FOR CUMULATIVE DISTANCES

REFER TO SCHEDULE)

EXIT LIGHTING

TM

FIRE EXTINGUISHER CABINET (FEC)

FIRE EXTINGUISHERS (FE)

FIRE HOSE CABINETS (FHC)

HEAT DETECTOR

SMOKE DETECTOR

DIRECTION OF EGRESS

WIDTH PROVIDEDP: XX"

R: XX" WIDTH REQUIRED

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

X - XX'

# ICRA SYMBOLSKEYNOTES

APPLICABLE BUILDING CODES

2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL FIRE

ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD FOR

INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF NFPA

5000 AND NFPA 900

2024 INTERNATIONAL MECHANICAL CODE (IMC)

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA)

STANDARDS.

VA SEISMIC DESIGN REQUIREMENTS, H-18-8

2026 NATIONAL ELECTRICAL CODE (NEC)

2024 INTERNATIONAL PLUMBING CODE (IPC)

ASME BOILER AND PRESSURE VESSEL CODE

ASME CODE FOR PRESSURE PIPING

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS

(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN

GUIDE (PG-18-13)

BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE,

AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318)

MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE

FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL

BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION

(AISC)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS

FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE

RESIDENTIAL BUILDINGS AND NEW LOW-RISE RESIDENTIAL

BUILDINGS, 10 CFR PARTS 433, 434 AND 435

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND

SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING

(MOU)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL

ENVIRONMENTAL, ENERGY, AND TRANSPORTATION

MANAGEMENT

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.

STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00 AND

01 35 26 OF THE VA MASTER CONSTRUCTION SPECIFICATION.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE

STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE 170-2025, NON-

MEDICAL SPACES - ASHRAE 62.1-2025

SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE

STANDARD 15–2024

2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED BY

VA STANDARDS

UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE

STANDARD OR CODE SHALL BE USED

APPLICABLE BUILDING GUIDES

VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)

BUILDING CODE:

CONSTRUCTION TYPE:

TYPE II (000) PER NFPA 220, Chapter 4 TYPE OF BUILDING: Business Occupancy

Allowable Area and Allowable Stories is not Limited in NFPA by occpancy.

The buidling is supplied with 2 storage rooms set up to become future stairs to serve as 2 exits from upper floors38.2.4.1, and provided with Emergency Lighting 38.2.9.1,and a Fire Alarm system 38.3.4.1.

Current Stories: 1 Possible Future Stories: 5

FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)

FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING

ELEMENTS:

STRUCTURAL FRAME 0 HOURS

NON-BEARING WALLS 0 HOURS

BEARING WALLS 0 HOURS

FLOORS 0 HOURS

ROOFS/ CEILINGS 0 HOURS

FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)

FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY

FUNCTION:

ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)

SMOKE COMPARTMENTS 1/2 HOUR

SOILED UTILITY ROOMS 1 HOUR

VERTICAL SHAFTS / STAIRS 2 HOURS

MEDICAL GAS / HAZARDOUS

STORAGE 1 HOURS

7.1.3.2.1 (3) The separation shall have a minimum 2-hour fire resistance rating where the exit connects four or more stories.

NFPA 52.2.2.3.4 In assembly, educational, detention and correction facilities;

health care, ambulatory health care, and day care centers; and, residential board and care and residential occupancies, battery systems shall be located in a room separated from other portions of the building by a minimum of a 2-hour fire barrier. THE MCR (Main Computer Room) IS A MISSION CRITICAL

FACILITY AND PROVIDING A 2 HOUR ADDS ADDITIONAL PROTECTION

TO PROTECT THE SPACE.

MIXED BUILDING OCCUPANCY TYPE:

EXISTING GROUND FLOOR - BUSINESS OCCUPANCY

ADDITION - BUSINESS OCCUPANCY

6.1.14.1.3 Where incidental to another occupanct, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:

(1) Mercantile, BUSINESS, industrial, or storage use

6.1.14.3 Mixed Occupancies

6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.

Table 6.1.14.4.1 (a) - separation of occupanies - 2 Hr between Health Care and Business

6.2 Hazard of Contents.

6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or stucture, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.

EXIT ACCESS TRAVEL DISTANCE:

38.2.6.2 The travel distance between any point in a room and an exit shall not exceed 200 ft.

38.2.6.3 The maximum travel distance...shall not exceed 300 ft in buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7.

BUSINESS OCCUPANCY; PROTECTED = 300'-0"

OCCUPANT LOAD:

38.1.7 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.

CALCULATED OCCUPANT LOADS

PROJECT AREA = 27 TOTAL OCCUPANTS

ADJACENT AREA = N/A

MEANS OF EGRESS:

38.2.3 Capacity of Means of Egress.

38.2.3.1 The capacity of any required means of egress shall be determined in accordance with the provisions Section 7.3.

38.2.3.2 The clear width of any corridor or passageway serving an occupant load of 50 or more shall not be less than 44 in. (1120 mm).

38.2.4 Number of Means of Egress.

38.2.4.1 Means of egress shall comply with all of the flollowing: except as permitted by 38.2.4.2-6

1) the number of means of egress shall be in accordance with section 7.4

2) not less than two separate exits shall be provicded on every story.

3) Not less than two separate exits shall be accessible from every part of every story.

38.2.5.3.1 In building protected throughout by and approvide supervised autoamatic sprinkler system, Dead-end corridors shall not exceed 50 ft.

PROTECTION FROM HAZARDS:

38.3.2 Protection from Hazards.

38.3.2.1 Hazardous Areas

38.3.2.2 High Hazard Contents areas, (section 6.2) shall meet all of the following criteria:

1) The area shall be separated from other parts of the buidling by fire barriers having a minimum 1 hour fire resistance rating, with all openings therein protected by self-closing fire door assemblies having a minimum 3/4 hour fire protection rating

2) The area shall be protected by an automatic extinguishing system in accordance with 9.7.1.1(1) or 9.7.1.2

38.3.2.3 Hazardous Materials. Where hazardous materils are stored or handled, the provisions of 8.7.3.1 shall apply.

38.3.2.4 Medical Gas. Medical gas storage areas and the operation, management and maintenance of medical gases shall be in accordance with

NFPA 99.

38.3.5. Portable fire extinguishers shall be provided in every business occupancy in accordance with Section 9.9.

38.5.1 Utilities shall comply with the provisions of Section 9.1

PARKING SUMMARY:

NO ADDITIONAL PARKING ADDED.

TN

PN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .A

R C

H .B

.rv t

-0 3-

3:

:1

07GI300

INFECTION CONTROL PLAN & INTERIM LIFE

SAFETY - GROUND FLOOR

620-22-700

06/27/2025 M. Perkins G. Fantoni

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPDATE

2094 Albany Post Road, Montrose, NY 10548

1/8" = 1'-0"F1

INFECTION CONTROL PLAN & INTERIM LIFE

SAFETY - GROUND FLOOR

# Revisions: Date:

1 ADDENDUM #1 03/27/2026

2 STAIRS ARE TO REMAIN OPERATIONAL AT ALL TIMES

FOR EMERGENCY EGRESS ONLY. THEY ARE NOT TO BE

USED FOR ANY CONSTRUCTION ACTIVITY.

3 ELEVATORS ARE TO REMAIN OPERATIONAL AT ALL

TIMES

A

ONE ELEVATOR TO BE DESIGNATED FOR CONTRACTOR

USE. CONTRACTOR TO PROTECT / REPAIR ALL FINISHES

AND FOLLOW PROPER ICRA REMOVAL PROTOCOLS FOR

ANY MATERIALS REMOVED FROM SITE THROUGH

ELEVATOR

4 HEPA VACUUM - PROVIDE THROUGHOUT

CONSTRUCTION AREA

5 HEPA EQUIPPED AIR FILTRATION UNIT - PROVIDE

THROUGHOUT CONSTRUCTION AREA. COORDINATE

QUANTITY TO ENSURE NEGATIVE PRESSURE IS

MAINTAINED.

6 PORTABLE CEILING ACCESS MODULE, PROVIDE

THROUGHOUT CONSTRUCTION AREA AS REQUIRED

7 FIRE EXTINGUISHER

8 TEMPORARY CONSTRUCTION BARRIER

9 ADHESIVE WALK-OFF MAT

10 COORDINATE WITH COR TO BLOCK OFF CORRIDOR (48

HR MAX) AS ALTERNATIVE - PROVIDE ICRA CLOSURES

FOR EACH SIDE OF CORRIDOR SEPARATELY - LEAVING

4'-0" MIN FOR CORRIDOR PATHWAY USE BY PUBLIC

12 DEBRIS REMOVAL PATH TOWARDS LOADING DOCK

13 PROVIDE SIGNAGE -NOT AN EXIT - PROCEED TO

CLOSEST EXIT AT STAIR HALL B

14 PROVIDE SIGNAGE -NOT AN EXIT - PROCEED TO

CLOSEST EXIT AT STAIR HALL A

NOTE:

DEBRIS REMOVAL:

COORDINATE REMOVAL OF MATERIALS ON THIS FLOOR WITH

ASBESTOS REPORT AND PLAN.

CONFIRM WITH COR FOR FINAL PLAN AND PROCEDURE OF

MATERIAL REMOVAL WITH ANTEROOMS, HEPA FILTRATION, ICRA

PROTOCOLS, AND ROUTE THRU OCCUPIED SPACES; PRIOR TO

REMOVAL OF ANY MATERIALS.

SECURE STAIRWELLS FROM UNAUTHORIZED ENTRY DURING

CONSTRUCTION.

LIFE SAFETY:

NEW WORK DOES NOT CHANGE EXISTING SMOKE

COMPARTMENTS, EXIT PATHWAYS, OR EXITS.

REFER TO GROUND FLOOR LIFE SAFETY PLAN FOR EGRESS AND

CODE INFORMATION.

PATH OF TRAVEL SCHEDULE -GROUND FLOOR

Mark From Room To Room Type of Travel Path Length

GROUND LEVEL

(P-o-T) Distance to Exits

E1 CORRIDOR 24Z STAIR HALL A 14 (P-o-T) Distance to Exits 29' - 9" E2 CORRIDOR 24Z STAIR HALL B - (P-o-T) Distance to Exits 46' - 4"

AREA OCCUPANCIES

LEVEL Name Area SF

Occupancy Requirements

OL

Occupancy

(IBC) Occupancy (NFPA) OLF Fixed Seats

GROUND LEVEL EXISTING BUSINESS 16260 SF B Business 150 SF 0 108

03/30/2026

WAITING

AREA

101101

STAIR

HALL 01

120120

STAIR

HALL 03

101101

100A100A

ELEVATOR

LOBBY

143Z143Z

101C101C

ELEVATOR

ELEVATOR

STAIR

HALL

STAIR

HALL

3A2

1 8

E1 ▬ 66.1'

CONSULT

106106

WAITING

6M6M

MI

N

4'- 0"

C

LR

VACANT

104B104B

BREAK

ROOM

6P6P PUBLIC

RESTROOM

103A103A

SUPPLIES

102102

SINGLE

ROOM

103103

SINGLE

ROOM

104104

105105

TWO BED

WARD

106106

SINGLE

ROOM

107107

TWO BED

WARD

108108

TWO BED

WARD

109109

TWO BED

WARD

110110

TWO BED

WARD

111111

SINGLE

ROOM

112112

TWO BED

WARD

113113

NURSE

OFFICE

114114

SINKS

116116

117117

TLT

118118

DAY

ROOM

119119

SINGLE

ROOM

121121

SINGLE

ROOM

122122

SINGLE

ROOM

123123

INNER

VAULT

117117

101A101A

TLT

101B101BCHANGING

AREA

115B115B

SHOWERS

115C115C

116A116A

CHANGING

AREA

118A118A

119A119A

NOURISHMENT

119B119B

CORRIDOR

141Z141Z

CORRIDOR

107Z107Z

STORAGE

149149

HD

STORAGE

6C6C

DIRTY

ANTE

ROOM

6D6D

REGULAR

BUFFER

(NON-HAZARDOUS

USP 797 )

6E6E

CHEMO

BUFFER/

STORAGE

(HAZARDOUS,

USP 800)

6F6F

CLEAN

ANTE

ROOM

120A120A

CHEMO

PRODUCTION

123A123A

BULK

STORAGE

6G6G

IP

FILLING/

ASSEMBLY

123B123B

STAFF

RESTROOM

6H6H

CORRIDOR

199C199C

NON-STERILE

COMPOUNDING

123C123C

CHEMO

BREAKOUT

123E123E

BLISTER

PACK

123D123D

STAFF

RESTROOM

6I6I

OP

SUPERVISOR

6J6J

RECEIVING/

BREAKDOWN

115115

OUTER

MAIL OUT

6K6K

BREAK

ROOM

6L6L

STAIR

380380

ELECTRICAL

CLOSET

104A104A

OUTER

VAULT

6S6S

CORRIDOR

199E199E

OP

FILLING/

ASSEMBLY

110A110A

AUTOMATED

FILLING/

STORAGE

110B110B

EXPIRED

DRUGS

6U6U

148148

INFECTION CONTROL / DUST

CONTROL PARTITION / BARRIER

INFECTION CONTROL/DUST CONTROL

EGRESS DOOR NON-TRANSFERRING

MULTI-SHEETED ADHESIVE FLOOR PADS

PATH OF DEMOLITION/TRASH

REMOVAL TRAVEL

CONSTRUCTION LIMIT LINE

NOT IN CONTRACT AREA

DEMOLITION

LASER PARTICLE COUNT LOCATION

LIFE SAFETY SYMBOLS

PATH OF TRAVEL

(FOR CUMULATIVE DISTANCES

REFER TO SCHEDULE)

EXIT LIGHTING

TM

FIRE EXTINGUISHER CABINET (FEC)

FIRE EXTINGUISHERS (FE)

FIRE HOSE CABINETS (FHC)

HEAT DETECTOR

SMOKE DETECTOR

DIRECTION OF EGRESS

WIDTH PROVIDEDP: XX"

R: XX" WIDTH REQUIRED

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

X - XX'

# ICRA SYMBOLSKEYNOTES

APPLICABLE BUILDING CODES

2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL FIRE

ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD FOR

INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF NFPA

5000 AND NFPA 900

2024 INTERNATIONAL MECHANICAL CODE (IMC)

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA)

STANDARDS.

VA SEISMIC DESIGN REQUIREMENTS, H-18-8

2026 NATIONAL ELECTRICAL CODE (NEC)

2024 INTERNATIONAL PLUMBING CODE (IPC)

ASME BOILER AND PRESSURE VESSEL CODE

ASME CODE FOR PRESSURE PIPING

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS

(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN

GUIDE (PG-18-13)

BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE,

AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318)

MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE

FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL

BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION

(AISC)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS

FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE

RESIDENTIAL BUILDINGS AND NEW LOW-RISE RESIDENTIAL

BUILDINGS, 10 CFR PARTS 433, 434 AND 435

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND

SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING

(MOU)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL

ENVIRONMENTAL, ENERGY, AND TRANSPORTATION

MANAGEMENT

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.

STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00 AND

01 35 26 OF THE VA MASTER CONSTRUCTION SPECIFICATION.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE

STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE 170-2025, NON-

MEDICAL SPACES - ASHRAE 62.1-2025

SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE

STANDARD 15–2024

2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED BY

VA STANDARDS

UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE

STANDARD OR CODE SHALL BE USED

APPLICABLE BUILDING GUIDES

VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)

BUILDING CODE:

CONSTRUCTION TYPE:

TYPE II (000) PER NFPA 220, Chapter 4 TYPE OF BUILDING: Business Occupancy

Allowable Area and Allowable Stories is not Limited in NFPA by occpancy.

The buidling is supplied with 2 storage rooms set up to become future stairs to serve as 2 exits from upper floors38.2.4.1, and provided with Emergency Lighting 38.2.9.1,and a Fire Alarm system 38.3.4.1.

Current Stories: 1 Possible Future Stories: 5

FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)

FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING

ELEMENTS:

STRUCTURAL FRAME 0 HOURS

NON-BEARING WALLS 0 HOURS

BEARING WALLS 0 HOURS

FLOORS 0 HOURS

ROOFS/ CEILINGS 0 HOURS

FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)

FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY

FUNCTION:

ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)

SMOKE COMPARTMENTS 1/2 HOUR

SOILED UTILITY ROOMS 1 HOUR

VERTICAL SHAFTS / STAIRS 2 HOURS

MEDICAL GAS / HAZARDOUS

STORAGE 1 HOURS

7.1.3.2.1 (3) The separation shall have a minimum 2-hour fire resistance rating where the exit connects four or more stories.

NFPA 52.2.2.3.4 In assembly, educational, detention and correction facilities;

health care, ambulatory health care, and day care centers; and, residential board and care and residential occupancies, battery systems shall be located in a room separated from other portions of the building by a minimum of a 2-hour fire barrier. THE MCR (Main Computer Room) IS A MISSION CRITICAL

FACILITY AND PROVIDING A 2 HOUR ADDS ADDITIONAL PROTECTION

TO PROTECT THE SPACE.

MIXED BUILDING OCCUPANCY TYPE:

EXISTING GROUND FLOOR - BUSINESS OCCUPANCY

ADDITION - BUSINESS OCCUPANCY

6.1.14.1.3 Where incidental to another occupanct, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:

(1) Mercantile, BUSINESS, industrial, or storage use

6.1.14.3 Mixed Occupancies

6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.

Table 6.1.14.4.1 (a) - separation of occupanies - 2 Hr between Health Care and Business

6.2 Hazard of Contents.

6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or stucture, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.

EXIT ACCESS TRAVEL DISTANCE:

38.2.6.2 The travel distance between any point in a room and an exit shall not exceed 200 ft.

38.2.6.3 The maximum travel distance...shall not exceed 300 ft in buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7.

BUSINESS OCCUPANCY; PROTECTED = 300'-0"

OCCUPANT LOAD:

38.1.7 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.

CALCULATED OCCUPANT LOADS

PROJECT AREA = 27 TOTAL OCCUPANTS

ADJACENT AREA = N/A

MEANS OF EGRESS:

38.2.3 Capacity of Means of Egress.

38.2.3.1 The capacity of any required means of egress shall be determined in accordance with the provisions Section 7.3.

38.2.3.2 The clear width of any corridor or passageway serving an occupant load of 50 or more shall not be less than 44 in. (1120 mm).

38.2.4 Number of Means of Egress.

38.2.4.1 Means of egress shall comply with all of the flollowing: except as permitted by 38.2.4.2-6

1) the number of means of egress shall be in accordance with section 7.4

2) not less than two separate exits shall be provicded on every story.

3) Not less than two separate exits shall be accessible from every part of every story.

38.2.5.3.1 In building protected throughout by and approvide supervised autoamatic sprinkler system, Dead-end corridors shall not exceed 50 ft.

PROTECTION FROM HAZARDS:

38.3.2 Protection from Hazards.

38.3.2.1 Hazardous Areas

38.3.2.2 High Hazard Contents areas, (section 6.2) shall meet all of the following criteria:

1) The area shall be separated from other parts of the buidling by fire barriers having a minimum 1 hour fire resistance rating, with all openings therein protected by self-closing fire door assemblies having a minimum 3/4 hour fire protection rating

2) The area shall be protected by an automatic extinguishing system in accordance with 9.7.1.1(1) or 9.7.1.2

38.3.2.3 Hazardous Materials. Where hazardous materils are stored or handled, the provisions of 8.7.3.1 shall apply.

38.3.2.4 Medical Gas. Medical gas storage areas and the operation, management and maintenance of medical gases shall be in accordance with

NFPA 99.

38.3.5. Portable fire extinguishers shall be provided in every business occupancy in accordance with Section 9.9.

38.5.1 Utilities shall comply with the provisions of Section 9.1

PARKING SUMMARY:

NO ADDITIONAL PARKING ADDED.

1/8" = 1'-0"F1

INFECTION CONTROL PLAN & INTERIM LIFE

SAFETY - FIRST FLOOR TN

PN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .A

R C

H .B

.rv t

-0 3-

8:

:1

07GI301

INFECTION CONTROL PLAN & INTERIM LIFE

SAFETY - FIRST FLOOR

620-22-700

06/27/2025 M. Perkins G. Fantoni

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPDATE

2094 Albany Post Road, Montrose, NY 10548

1 ANTEROOM - REFER TO INFECTION CONTROL &

INTERIM LIFE SAFETY DETAILS

2 STAIRS ARE TO REMAIN OPERATIONAL AT ALL TIMES

FOR EMERGENCY EGRESS ONLY. THEY ARE NOT TO

BE USED FOR ANY CONSTRUCTION ACTIVITY.

3 ELEVATORS ARE TO REMAIN OPERATIONAL AT ALL

TIMES

3A ONE ELEVATOR TO BE DESIGNATED FOR

CONTRACTOR USE. CONTRACTOR TO PROTECT /

REPAIR ALL FINISHES AND FOLLOW PROPER ICRA

REMOVAL PROTOCOLS FOR ANY MATERIALS

REMOVED FROM SITE THROUGH ELEVATOR

4 HEPA VACUUM - PROVIDE THROUGHOUT

CONSTRUCTION AREA

5 HEPA EQUIPPED AIR FILTRATION UNIT - PROVIDE

THROUGHOUT CONSTRUCTION AREA. COORDINATE

QUANTITY TO ENSURE NEGATIVE PRESSURE IS

MAINTAINED.

6 PORTABLE CEILING ACCESS MODULE, PROVIDE

THROUGHOUT CONSTRUCTION AREA AS REQUIRED

7 FIRE EXTINGUISHER

8 TEMPORARY CONSTRUCTION BARRIER

9 ADHESIVE WALK-OFF MAT

# Revisions: Date:

1 ADDENDUM #1 03/27/2026

PATH OF TRAVEL SCHEDULE - FIRST FLOOR

Mark From Room To Room Type of Travel Path Length

INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - FIRST FLOOR

(P-o-T) Distance to Exits

E1 STAIR HALL 03 101 (P-o-T) Distance to Exits 66' - 1"

NOTE:

DEBRIS REMOVAL:

COORDINATE REMOVAL OF MATERIALS ON THIS FLOOR WITH

ASBESTOS REPORT AND PLAN.

CONFIRM WITH COR FOR FINAL PLAN AND PROCEDURE OF

MATERIAL REMOVAL WITH ANTEROOMS, HEPA FILTRATION, ICRA

PROTOCOLS, AND ROUTE THRU OCCUPIED SPACES; PRIOR TO

REMOVAL OF ANY MATERIALS.

SECURE STAIRWELLS FROM UNAUTHORIZED ENTRY DURING

CONSTRUCTION.

LIFE SAFETY:

NEW WORK DOES NOT CHANGE EXISTING SMOKE

COMPARTMENTS, EXIT PATHWAYS, OR EXITS.

REFER TO GROUND FLOOR LIFE SAFETY PLAN FOR EGRESS AND

CODE INFORMATION.

AREA OCCUPANCIES

LEVEL Name Area SF

Occupancy Requirements

OL

Occupancy

(IBC) Occupancy (NFPA) OLF Fixed Seats

FIRST LEVEL EXISTING BUSINESS 16966 SF B Business 150 SF 0 113

VACANT

243243

ELEVATOR

2EV22EV2

WAITING

AREA

201201

CORRIDOR

245Z245Z

VACANT

242242

3A

ELEVATOR

LOBBY

244z244z ELEVATOR

2EV12EV1

230230

231231

VACANT

232232

VACANT

233233

E1 ▬ 70.3'

MI

N

CL

R

4'- 0"

STAIR

HALL 02

235235

CLOSET

203203

VACANT

204204

VACANT

205205

207207

VACANT

208208

VACANT

209209

VACANT

210210VACANT

211211

VACANT

212212

VACANT

213213

VACANT

214214

VACANT

215215

SINKS

216216

217A217A

TLT

218218

VACANT

219219

STAIR

HALL 01

220220

TLT

222A222A

VACANT

222222

VACANT

223223

VACANT

225225

VACANT

234234

VACANT

SINKS

236236

TLT

244244

245245

VACANT

246246

VACANT

238A238A

VACANT

238B238B

VACANT

258258

CONFERENCE

ROOM

238D238D

VACANT

251251

VACANT

252252

VACANT

253253

VACANT

254254

VACANT

255255

VACANT

256256

VACANT

TLT

204A204A

VACANT

206206

CHANGING

AREA

216A216A

SHOWERS

218B218B

217217

CHANGING

AREA

218A218A

VACANT

219F219F

CORRIDOR

246Z246Z

CORRIDOR

248Z248Z

CORRIDOR

247Z247Z

CORRIDOR

250Z250Z

CORRIDOR

238238

CORRIDOR

251Z251Z

239239

CHANGING

AREA

234A234A

SHOWERS

236A1236A1

CHANGING

AREA

236A236A

PIPE

CHASE

234B234B

VACANT

233D233D

STAIR

HALL

STAIR

HALL

VACANT

202202

214A214A

VACANT

219A1219A1

VACANT

219A219A

VACANT

219B219B

VACANT

219C219C

VACANT

219D219D

VACANT

219E219E

TLT

219C1219C1

228A228A

TLT

243243

CORRIDOR

235235

VACANT

233A233A

VACANT

237237

VACANT

238238

VACANT

233E233E

VACANT

233F233F

VACANT

242242

VACANT

242A242A

TELE. CL.

202A202A

INFECTION CONTROL / DUST

CONTROL PARTITION / BARRIER

INFECTION CONTROL/DUST CONTROL

EGRESS DOOR NON-TRANSFERRING

MULTI-SHEETED ADHESIVE FLOOR PADS

PATH OF DEMOLITION/TRASH

REMOVAL TRAVEL

CONSTRUCTION LIMIT LINE

NOT IN CONTRACT AREA

DEMOLITION

LASER PARTICLE COUNT LOCATION

LIFE SAFETY SYMBOLS

PATH OF TRAVEL

(FOR CUMULATIVE DISTANCES

REFER TO SCHEDULE)

EXIT LIGHTING

TM

FIRE EXTINGUISHER CABINET (FEC)

FIRE EXTINGUISHERS (FE)

FIRE HOSE CABINETS (FHC)

HEAT DETECTOR

SMOKE DETECTOR

DIRECTION OF EGRESS

WIDTH PROVIDEDP: XX"

R: XX" WIDTH REQUIRED

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE…