ATTACHMENT 19 - Montrose.EHRM.Addendum.01.B07.20260330.pdf
PDF 25 MB Posted
- Solicitation number
- RFP-36C77626R0033
About this file
This is an architectural addendum document (Attachment 19) containing drawing index, life safety plans, infection control protocols, hazardous material abatement plans, and detailed construction drawings for the Electronic Health Record Modernization (EHRM) Infrastructure Upgrades project at Franklin Delano Roosevelt VA Hospital in Montrose, NY. The project involves interior renovations across three floors of Building 7 and a Main Computer Room (MCR) facility, with work including telecommunications room upgrades, infrastructure improvements, and hazardous material removal.
The project scope encompasses demolition and renovation of existing spaces to create new telecommunications rooms on the ground floor (Room 20, 157 SF), first floor (Room 148, 171 SF), and second floor (Room 243A, 95 SF), along with site infrastructure upgrades including utilities, grading, stormwater management, and fire protection systems. Key requirements include infection control risk assessment (ICRA) protocols for construction activities, hazardous material abatement for confirmed asbestos-containing materials (pipe insulation, flooring, transite panels) and lead-based paint, life safety compliance with 2024 NFPA 101 codes, and comprehensive telecommunications cabling infrastructure upgrades to Category 6A standards. The project maintains occupied space operations during construction, requires temporary barriers and negative air pressure systems in work areas, and includes coordination of electrical, mechanical, plumbing, and fire protection systems. Addendum #1, dated March 30, 2026, removes one sheet from construction documents and updates project information accordingly.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
STAMP
Au to de sk
D oc s:
//6
-2
2-
M on tro se V
AM
C
E H
R M
IU
/6
-2
2-
0.
M on tro se .E
H R
M .M
EP
.B
.rv t 3/
/2
:4
5:
P M
07G-001
DRAWING INDEX 620-22-700
06/27/2025 M. PERKINS K.
MCDERMOTT
ISSUED FOR
CONSTRUCTION
(EHRM) INFRASTRUCTURE
UPGRADES
2094 Albany Post Road, Montrose, NY 10548
- DRAWING INDEX -
SHEET
NUMBER SHEET NAME INCLUDED IN 35% SD INCLUDED IN 65% DD INCLUDED IN 95% CD ISSUED FOR CONSTRUCTION
GENERAL
07G-000 COVER SHEET Yes Yes Yes Yes 07G-001 DRAWING INDEX Yes Yes Yes Yes 07G-010 GENERAL PROJECT NOTES Yes Yes Yes Yes 07G-012 GENERAL INDOOR AIR QUALITY NOTES Yes Yes Yes Yes 07GC001 PROJECT PHASING PLANS Yes Yes Yes Yes 07GC002 PROJECT PHASING PLANS Yes Yes Yes Yes
HAZARDOUS
07H-100 HAZARDOUS MATERIAL ABATEMENT PLAN - GROUND LEVEL No Yes Yes Yes 07H-101 HAZARDOUS MATERIAL ABATEMENT PLAN - FIRST LEVEL No Yes Yes Yes 07H-102 HAZARDOUS MATERIAL ABATEMENT PLAN - SECOND LEVEL No Yes Yes Yes
LIFE SAFETY & ICRA
07GI100 LIFE SAFETY PLAN - GROUND FLOOR No Yes Yes Yes
07GI300 INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - GROUND FLOOR
07GI301 INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - FIRST FLOOR
07GI302 INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - SECOND FLOOR
07GI303 INFECTION CONTROL & INTERIM LIFE SAFETY DETAILS
CIVIL
07VF101 CIVIL SITE SURVEY PLAN No Yes Yes Yes 07CD101 CIVIL DEMOLITION PLAN No Yes Yes Yes 07CS101 CIVIL SITE PLAN No Yes Yes Yes 07CG101 CIVIL GRADING PLAN No Yes Yes Yes 07CG102 STORMWATER POLLUTION PROTECTION PLAN No No Yes Yes 07CG201 CIVIL ACCESS ROAD PLAN & PROFILE No No No Yes 07CG501 CIVIL DETAILS - SHEET 1 No Yes Yes Yes 07CG502 CIVIL DETAILS - SHEET 2 No Yes Yes Yes 07CG503 CIVIL EROSION CONTROL DETAILS - SHEET 1 No No Yes Yes 07CU101 CIVIL UTILITY PLAN No Yes Yes Yes 07CU102 CIVIL UTILITY PLAN - FOUNDATION DRAIN No Yes Yes Yes 07CU201 CIVIL STORM DRAIN PLAN & PROFILE No Yes Yes Yes 07CU501 CIVIL UTILITY DETAILS - SHEET 1 No Yes Yes Yes 07CU502 CIVIL UTILITY DETAILS - SHEET 2 No No No Yes
STRUCTURAL
07S-001 STRUCTURAL GENERAL NOTES No Yes Yes Yes 07S-002 STRUCTURAL GENERAL NOTES CONTINUED No Yes Yes Yes 07S-003 STRUCTURAL SPECIAL INSPECTIONS No Yes Yes Yes 07S-101 STRUCTURAL FOUNDATION PLAN No Yes Yes Yes 07S-102 STRUCTURAL ROOF FRAMING PLAN No Yes Yes Yes 07S-103 STRUCTURAL FOUNDATION PLAN -GENERATOR No Yes Yes Yes 07S-104 STRUCTURAL FRAMING PLAN -GENERATOR No Yes Yes Yes 07S-501 TYPICAL DETAILS No Yes Yes Yes 07S-502 TYPICAL DETAILS No Yes Yes Yes 07S-503 TYPICAL DETAILS No Yes Yes Yes 07S-504 TYPICAL DETAILS No Yes Yes Yes 07S-505 TYPICAL DETAILS No Yes Yes Yes 07S-506 TYPICAL DETAILS No Yes Yes Yes 07S-510 FOUNDATION DETAILS AND SCHEDULES No Yes Yes Yes 07S-520 FRAMING DETAILS No Yes Yes Yes
ARCHITECTURAL
07A-001 ARCHITECTURAL SYMBOLS, & GENERAL NOTES No Yes Yes Yes 07A-101 ARCHITECTURAL PLAN - GROUND FLOOR No Yes Yes Yes 07A-102 ARCHITECTURAL PLAN - GROUND LEVEL - MAIN COMPUTER ROOM AND ENLARGED PLANS No Yes Yes Yes 07A-103 ARCHITECTURAL FLOOR AND ROOF PLANS - GENERATOR BUILDING No Yes Yes Yes 07AC102 ARCHITECTURAL REFLECTED CEILING PLAN - GROUND LEVEL - MAIN COMPUTER ROOM No Yes Yes Yes 07A-201 EXTERIOR ELEVATIONS No Yes Yes Yes 07A-202 EXTERIOR ELEVATIONS No Yes Yes Yes 07A-301 ARCHITECTURAL BUILDING SECTIONS AND DETAILS No Yes Yes Yes 07A-302 ARCHITECTURAL BUILDING SECTIONS AND DETAILS No Yes Yes Yes 07A-401 ARCHITECTURAL ENLARGED VIEWS - GROUND AND FIRST LEVELS No Yes Yes Yes 07A-402 ARCHITECTURAL ENLARGED VIEWS - SECOND FLOOR No Yes Yes Yes 07A-501 ARCHITECTURAL ROOF PLAN & DETAILS No Yes Yes Yes 07A-511 ARCHITECTURAL PARTITION AND FRAMING DETAILS No Yes Yes Yes 07A-512 ARCHITECTURAL PARTITION HEAD DETAILS No Yes Yes Yes 07A-531 ARCHITECTURAL CEILING DETAILS No Yes Yes Yes 07A-600 SCHEDULES AND DETAILS No Yes Yes Yes 07A-601 DOOR AND LOUVER DETAILS No
RENDERINGS
07A-900 ARCHITECTURAL CONCEPT RENDERINGS No Yes Yes Yes
INTERIORS
07IN001 INTERIOR NOTES AND FINISH LEGEND No Yes Yes Yes 07IN101 INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES No Yes Yes Yes 07IN501 INTERIOR FINISH DETAILS No Yes Yes Yes
EQUIPMENT
07Q-601 INTERIOR EQUIPMENT PLAN AND SCHEDULE - GROUND LEVEL - MAIN COMPUTER ROOM Yes
FIRE PROTECTION
07FX001 FIRE PROTECTION ABBREVIATIONS, SYMBOLS, AND DETAILS No Yes Yes Yes 07FX100A FIRE PROTECTION PLAN - GROUND LEVEL AREA A No Yes Yes Yes 07FX100B FIRE PROTECTION PLAN - GROUND LEVEL AREA B No Yes Yes Yes 07FX101 FIRE PROTECTION PLAN - FIRST LEVEL No Yes Yes Yes 07FX102 FIRE PROTECTION PLAN - SECOND LEVEL No Yes Yes Yes 07FX401 FIRE PROTECTION ENLARGED PLANS No Yes Yes Yes 07FX402 FIRE PROTECTION ENLARGED PLANS No Yes Yes Yes 07FX501 FIRE PROTECTION DETAILS AND SCHEDULES No Yes Yes Yes 07FX502 FIRE PROTECTION DETAILS AND SCHEDULES No Yes Yes Yes 07FX901 FIRE PROTECTION CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 07FX902 FIRE PROTECTION CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes
PLUMBING
07P-001 PLUMBING ABBREVIATIONS AND SYMBOLS No Yes Yes Yes 07P-100 PLUMBING PLAN - GROUND LEVEL No Yes Yes Yes 07P-100B PLUMBING PLAN - GROUND LEVEL AREA B No Yes Yes Yes 07P-101B PLUMBING PLAN - ROOF LEVEL AREA B No Yes Yes Yes 07P-600 PLUMBING ISOMETRIC VIEW No Yes Yes Yes 07P-901 PLUMBING CUTSHEETS No Yes Yes Yes
MECHANICAL
07M-001 MECHANICAL ABBREVIATIONS AND SYMBOLS No Yes Yes Yes 07M-100 MECHANICAL PLAN - GROUND LEVEL No Yes Yes Yes 07M-100B MECHANICAL PLAN - GROUND LEVEL AREA B No Yes Yes Yes 07M-101 MECHANICAL PLAN - FIRST LEVEL No Yes Yes Yes 07M-102 MECHANICAL PLAN - SECOND LEVEL No Yes Yes Yes 07M-400 MECHANICAL ENLARGED PLANS No Yes Yes Yes 07M-401 MECHANICAL ENLARGED PLANS No Yes Yes Yes 07M-402 MECHANICAL ENLARGED PLANS No Yes Yes Yes 07M-403 MECHANICAL ENLARGED PLANS No Yes Yes Yes 07M-404 MECHANICAL ENLARGED PLANS No Yes Yes Yes 07M-501 MECHANICAL DETAILS No Yes Yes Yes 07M-502 MECHANICAL DETAILS No Yes Yes Yes 07M-503 MECHANICAL DETAILS No Yes Yes Yes 07M-504 MECHANICAL DETAILS No Yes Yes Yes 07M-701 MECHANICAL SCHEDULES No Yes Yes Yes
- DRAWING INDEX -
SHEET
NUMBER SHEET NAME INCLUDED IN 35% SD INCLUDED IN 65% DD INCLUDED IN 95% CD ISSUED FOR CONSTRUCTION 07M-702 MECHANICAL SCHEDULES No Yes Yes Yes 07M-801 MECHANICAL CONTROL SYMBOL LEGEND AND ABBREVIATIONS No Yes Yes Yes 07M-802 MECHANICAL CONTROL DIAGRAMS No Yes Yes Yes 07M-803 MECHANICAL CONTROL DIAGRAMS No Yes Yes Yes 07M-804 MECHANICAL CONTROL DIAGRAMS No Yes Yes Yes 07M-805 MECHANICAL CONTROL DIAGRAMS No Yes Yes Yes 07M-806 MECHANICAL CONTROLS RISER DIAGRAM No Yes Yes Yes 07M-807 MECHANICAL CONTROLS RISER DIAGRAM No Yes Yes Yes 07M-901 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 07M-902 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 07M-903 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 07M-904 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 07M-905 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes
ELECTRICAL
07E-001 ELECTRICAL ABBREVIATIONS AND SYMBOLS Yes Yes Yes Yes 07ES100 ELECTRICAL PLAN - SITE PLAN No Yes Yes Yes 07ES101 ELECTRICAL SITE PLAN - ENLARGED No Yes Yes Yes 07ES102 ELECTRICAL SITE PLAN - ENLARGED No No No Yes 07E-100 ELECTRICAL PLAN - GROUND LEVEL - BLDG 7 No Yes Yes Yes 07E-100B ELECTRICAL PLAN - GROUND LEVEL - MCR BLDG No Yes Yes Yes 07E-101 ELECTRICAL PLAN - FIRST LEVEL - BLDG 7 No Yes Yes Yes 07E-102 ELECTRICAL PLAN - SECOND LEVEL - BLDG 7 Yes Yes Yes Yes 07E-102B ELECTRICAL LIGHTNING PLAN - ROOF LEVEL - MCR BLDG No No No Yes 07E-200B ELECTRICAL REFLECTED CEILING PLAN - GROUND LEVEL - MCR BLDG No Yes Yes Yes 07E-200C ELECTRICAL REFLECTED CEILING PLAN - GROUND LEVEL - MCR LIGHTING LUMENS No Yes Yes Yes 07E-400 ELECTRICAL ENLARGED PLANS - BLDG 7 No Yes Yes Yes 07E-401 ELECTRICAL ENLARGED PLANS - BLDG 7 No Yes Yes Yes 07E-402 ELECTRICAL ENLARGED PLANS - BLDG 7 No Yes Yes Yes 07E-403 ELECTRICAL ENLARGED PLANS - MCR No Yes Yes Yes 07E-404 ELECTRICAL ENLARGED PLANS - MCR No Yes Yes Yes 07E-405 ELECTRICAL ENLARGED PLANS - MCR No Yes Yes Yes 07E-501 ELECTRICAL DETAILS Yes Yes Yes Yes 07E-502 ELECTRICAL DETAILS Yes Yes Yes Yes 07E-503 ELECTRICAL DETAILS Yes Yes Yes Yes 07E-504 ELECTRICAL DETAILS Yes Yes Yes Yes 07E-601 ELECTRICAL ONE-LINE DIAGRAMS -DEMOLITION Yes Yes Yes Yes 07E-602 ELECTRICAL ONE-LINE DIAGRAMS - NEW CONSTRUCTION No Yes Yes Yes 07E-603 ELECTRICAL ONE-LINE DIAGRAMS & DETAIL - MCR No No No Yes 07E-701 ELECTRICAL SCHEDULES - BLDG 7 No Yes Yes Yes 07E-702 ELECTRICAL SCHEDULES - BLDG 7 No Yes Yes Yes 07E-703 ELECTRICAL SCHEDULES - MCR No Yes Yes Yes 07E-704 ELECTRICAL SCHEDULES - MCR No Yes Yes Yes 07E-901 ELECTRICAL CUTSHEETS & BASIS OF DESIGN Yes Yes Yes Yes 07E-902 ELECTRICAL CUTSHEETS & BASIS OF DESIGN Yes Yes Yes Yes 07E-903 ELECTRICAL CUTSHEETS & BASIS OF DESIGN No No No Yes
TELECOMMUNICATION
07T-001 TELECOMMUNICATION ABBREVIATIONS AND SYMBOLS Yes Yes Yes Yes 07T-100 TELECOMMUNICATION PLAN - GROUND LEVEL - BLDG 7 Yes Yes Yes Yes 07T-100B TELECOMMUNICATION PLAN - GROUND LEVEL - MCR BLDG No Yes Yes Yes 07T-101 TELECOMMUNICATION PLAN - FIRST LEVEL - BLDG 7 Yes Yes Yes Yes 07T-102 TELECOMMUNICATION PLAN - SECOND LEVEL - BLDG 7 Yes Yes Yes Yes 07T-401 TELECOMMUNICATION ENLARGED PLANS - BLDG 7 No Yes Yes Yes 07T-501 TELECOMMUNICATION DETAILS Yes Yes Yes Yes 07T-502 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS Yes Yes Yes Yes 07T-503 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS Yes Yes Yes Yes 07T-504 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS No Yes Yes Yes 07T-505 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS No Yes Yes Yes 07T-601 TELECOMMUNICATION RISER DIAGRAMS Yes Yes Yes Yes 07T-603 TELECOMMUNICATION FIBER RISER DIAGRAM - NEW No Yes Yes Yes 07T-604 TELECOMMUNICATION TR ELEVATIONS RMS 20/148/243 Yes Yes Yes Yes 07T-605 TELECOMMUNICATION MCR NEW ELEVATIONS / MDA / RM 23 Yes Yes Yes Yes 07T-606 TELECOMMUNICATION MCR NEW ELEVATIONS / HDA-SVR / RM 23 Yes Yes Yes Yes 07T-607 TELECOMMUNICATION EXISTING CORE ELEVATIONS B03 RM 214 Yes Yes Yes Yes 07T-701 TELECOMMUNICATION SCHEDULES No Yes Yes Yes 07T-702 TELECOMMUNICATION SCHEDULES No Yes Yes Yes 07T-901 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN Yes Yes Yes Yes 07T-902 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN No No Yes Yes 07T-903 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN No No Yes Yes
REFERENCE
07R-900 PHOTO REFERENCES No Yes Yes Yes Grand total: 164
# Revisions: Date:
1 ADDENDUM #1 03/30/2026
07G-011 REMOVED FROM
CONSTRUCTION DOCUMENTS
Ranjan Text Box
DN DNDN
LIFE SAFETY SYMBOLS
PATH OF TRAVEL
(FOR CUMULATIVE DISTANCES
REFER TO SCHEDULE)
EXIT LIGHTING
TM
FIRE EXTINGUISHER CABINET (FEC)
FIRE EXTINGUISHERS (FE)
FIRE HOSE CABINETS (FHC)
HEAT DETECTOR
SMOKE DETECTOR
DIRECTION OF EGRESS
APPLICABLE BUILDING CODES
2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL FIRE
ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD FOR
INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF NFPA
5000 AND NFPA 900
2024 INTERNATIONAL MECHANICAL CODE (IMC)
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA)
STANDARDS.
VA SEISMIC DESIGN REQUIREMENTS, H-18-8
2026 NATIONAL ELECTRICAL CODE (NEC)
2024 INTERNATIONAL PLUMBING CODE (IPC)
ASME BOILER AND PRESSURE VESSEL CODE
ASME CODE FOR PRESSURE PIPING
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS
(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN
GUIDE (PG-18-13)
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE,
AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318)
MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE
FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL
BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION
(AISC)
ENERGY POLICY ACT OF 2005 (EPACT)
DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS
FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE
RESIDENTIAL BUILDINGS AND NEW LOW-RISE RESIDENTIAL
BUILDINGS, 10 CFR PARTS 433, 434 AND 435
FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND
SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING
(MOU)
EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL
ENVIRONMENTAL, ENERGY, AND TRANSPORTATION
MANAGEMENT
THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.
STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00 AND
01 35 26 OF THE VA MASTER CONSTRUCTION SPECIFICATION.
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE
STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE 170-2025, NON-
MEDICAL SPACES - ASHRAE 62.1-2025
SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE
STANDARD 15–2024
2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED BY
VA STANDARDS
UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE
STANDARD OR CODE SHALL BE USED
APPLICABLE BUILDING GUIDES
VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)
BUILDING CODE:
CONSTRUCTION TYPE:
TYPE II (000) PER NFPA 220, Chapter 4 TYPE OF BUILDING: Business Occupancy
Allowable Area and Allowable Stories is not Limited in NFPA by occpancy.
The buidling is supplied with 2 storage rooms set up to become future stairs to serve as 2 exits from upper floors38.2.4.1, and provided with Emergency Lighting 38.2.9.1,and a Fire Alarm system 38.3.4.1.
Current Stories: 1 Possible Future Stories: 5
FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING
ELEMENTS:
STRUCTURAL FRAME 0 HOURS
NON-BEARING WALLS 0 HOURS
BEARING WALLS 0 HOURS
FLOORS 0 HOURS
ROOFS/ CEILINGS 0 HOURS
FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)
FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY
FUNCTION:
ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)
SMOKE COMPARTMENTS 1/2 HOUR
SOILED UTILITY ROOMS 1 HOUR
VERTICAL SHAFTS / STAIRS 2 HOURS
MEDICAL GAS / HAZARDOUS
STORAGE 1 HOURS
7.1.3.2.1 (3) The separation shall have a minimum 2-hour fire resistance rating where the exit connects four or more stories.
NFPA 52.2.2.3.4 In assembly, educational, detention and correction facilities;
health care, ambulatory health care, and day care centers; and, residential board and care and residential occupancies, battery systems shall be located in a room separated from other portions of the building by a minimum of a 2-hour fire barrier. THE MCR (Main Computer Room) IS A MISSION CRITICAL
FACILITY AND PROVIDING A 2 HOUR ADDS ADDITIONAL PROTECTION
TO PROTECT THE SPACE.
MIXED BUILDING OCCUPANCY TYPE:
EXISTING GROUND FLOOR - BUSINESS OCCUPANCY
ADDITION - BUSINESS OCCUPANCY
6.1.14.1.3 Where incidental to another occupanct, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:
(1) Mercantile, BUSINESS, industrial, or storage use
6.1.14.3 Mixed Occupancies
6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.
Table 6.1.14.4.1 (a) - separation of occupanies - 2 Hr between Health Care and Business
6.2 Hazard of Contents.
6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or stucture, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.
EXIT ACCESS TRAVEL DISTANCE:
38.2.6.2 The travel distance between any point in a room and an exit shall not exceed 200 ft.
38.2.6.3 The maximum travel distance...shall not exceed 300 ft in buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7.
BUSINESS OCCUPANCY; PROTECTED = 300'-0"
OCCUPANT LOAD:
38.1.7 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.
CALCULATED OCCUPANT LOADS
PROJECT AREA = 27 TOTAL OCCUPANTS
ADJACENT AREA = N/A
MEANS OF EGRESS:
38.2.3 Capacity of Means of Egress.
38.2.3.1 The capacity of any required means of egress shall be determined in accordance with the provisions Section 7.3.
38.2.3.2 The clear width of any corridor or passageway serving an occupant load of 50 or more shall not be less than 44 in. (1120 mm).
38.2.4 Number of Means of Egress.
38.2.4.1 Means of egress shall comply with all of the flollowing: except as permitted by 38.2.4.2-6
1) the number of means of egress shall be in accordance with section 7.4
2) not less than two separate exits shall be provicded on every story.
3) Not less than two separate exits shall be accessible from every part of every story.
38.2.5.3.1 In building protected throughout by and approvide supervised autoamatic sprinkler system, Dead-end corridors shall not exceed 50 ft.
PROTECTION FROM HAZARDS:
38.3.2 Protection from Hazards.
38.3.2.1 Hazardous Areas
38.3.2.2 High Hazard Contents areas, (section 6.2) shall meet all of the following criteria:
1) The area shall be separated from other parts of the buidling by fire barriers having a minimum 1 hour fire resistance rating, with all openings therein protected by self-closing fire door assemblies having a minimum 3/4 hour fire protection rating
2) The area shall be protected by an automatic extinguishing system in accordance with 9.7.1.1(1) or 9.7.1.2
38.3.2.3 Hazardous Materials. Where hazardous materils are stored or handled, the provisions of 8.7.3.1 shall apply.
38.3.2.4 Medical Gas. Medical gas storage areas and the operation, management and maintenance of medical gases shall be in accordance with
NFPA 99.
38.3.5. Portable fire extinguishers shall be provided in every business occupancy in accordance with Section 9.9.
38.5.1 Utilities shall comply with the provisions of Section 9.1
PARKING SUMMARY:
NO ADDITIONAL PARKING ADDED.
50'-0" AGGREGATE DISTANCE
WIDTH PROVIDEDP: XX"
R: XX" WIDTH REQUIRED
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
TYPICAL ASSEMBLY INFORMATION
THERMAL REQUIREMENT SATISFY ASHRAE 90.1, CLIMATE
ZONE 5A
TYPICAL VENTED ROOF ASSEMBLY : R-30 CI
ASPHALT SHINGLES OVER ROOF UNDERLAYMENT
MEMBRANE ON VENTED NAILABLE INSULATION PANELS
(5-7/16" THICK, R-20.5 MIN), OVER ADDITIONAL 3" RIGID
POLYISO INSULATION (R-10 MIN), OVER VAPOR BARRIER
APPLIED TO METAL ROOF DECKING.
TYPICAL LOW-SLOPE MEMBRANE ROOF ASSEMBLY: R-30
CI
ASPHALT MEMBRANE, TO MATCH ASPHALT SHINGLES,
OVER ROOF UNDERLAYMENT MEMBRANE ON VENTED
NAILABLE INSULATION PANELS (5-7/16" THICK, R-20.5 MIN),
OVER ADDITIONAL 3" RIGID POLYISO INSULATION (R-10
MIN), OVER VAPOR BARRIER APPLIED TO METAL ROOF
DECKING.
TYPICAL BRICK ON STUD WALL ASSEMBLY : R-13+R-10 CI
3-5/8" BRICK WITH AIRSPACE (MAY VARY, 2" MIN) WITH
BRICK TIES SPACED AS REQUIRED. 3" RIGID INSULATION,
CONTINUOUS FLUID-APPLIED AIR BARRIER ON 8" CMU
BLOCK. PROVIDE BRICK VENTS AND INSECT SCREENS AT
16" O.C. TOP AND BOTTOM OF EACH CAVITY SPACE,
STAGGERED-HEIGHT MORTAR-CATCH MESH
CONTINUOUS AT BASE OF EACH CAVITY SPACE.
STANDARD GLAZING: MAX U VALUE =.38, MAX SHGC
VALUE = .36
STANDARD OPAQUE DOOR: MAX U VALUE = .37
Exx - xxx'
17303 SF
BUSINESS
NFPA OCCUPANCY
Business
E1 ▬ 73.4'
DIAGONAL DISTANCE
56'-2" DISTANCE BETWEEN DOORS
58'-11"
E2 ▬ 62.5'
X5
.7
X4 ▬ 113.6'
X6 ▬ 128.2'
X7 ▬ 61.9'
X1
0.
9'
X2
3.
5'
X3
6.
4'
4185 SF
BUSINESS
NEW ADDITION
EXISTING BLDG
Name Area Occupancy (NFPA) OLF Fixed Seats Occupant Load
NEW ADDITION 4,063 BUSINESS 150 NO 27
AREA OCCUPANCIES
Name Area Occupancy (NFPA) Sprinkled Other Factor Req Width NEW ADDITION 4,063 BUSINESS yes .20" 5.4"
EGRESS SIZING
Name Area Occupancy (NFPA) OLF Fixed Seats Occupant Load
EXISTING 16,868 NO CHANGE TO 150 NO 113
CURRENT Occupancy
ASSUMED BUSINESS
AREA OCCUPANCIES
No change to Exiting - multiple paths - only minor work in existing area (TR room upgrades) No change to existing plumbing fixtures provided
P:
2'
8"
R:
3"
P: 5' - 8" R: 3"
ELEVATOR
ELEVATOR
STORAGE
STORAGE
3B3B
UTILITY CL.
CORRIDOR
ELECTRICAL
DISTRIBUTION
FISCAL
STORAGE
STAIR HALL C
SERVICE
ROOM
ELECTRICAL
STORAGE
MECH ROOM
EMS CLOSET
STAIR HALL A
ENTRANCE
SOILED LINEN
1616ENTRANCE
1717DECON
1818SPD DECON
TELECOM
ROOM
MECH. RM.
CORRIDOR
22Z22Z
STAIR HALL B
CORRIDOR
24Z24Z
STORAGE
19A19A
CORRIDOR
26Z26Z
ELEVATOR
LOBBY
25Z25Z
TELE. CL.
1B1B
TELE. CL.
1A1A
TLT
3A3A
OFFICE
5AB5AB
OFFICE
5C5C
OFFICE
5E5E
OFFICE
5F5F
OFFICE
5G5G
OFFICE
5H5H
OFFICE
5J5J
OFFICE
5K5K
OFFICE
5L5L
ENTRANCE
5G15G1
CORRIDOR
23Z23Z
4A4A
9A9A
CORRIDOR
11B11B
MEDICAL
CACHE
15A15A
STORAGE
15B15B
STORAGE
15C15C
17A17A
CORRIDOR
17B17B
SPD
STORAGE
17C17C
SPD
STORAGE
17D17D
FOYER
17E17E
OFFICE
17F17F
TLT
17G17G
SPD
17I17I
17J17J
17K17K
BATHROOM
19B19B
STAIR HALL 4
STAIR HALL 5
STORAGE
EXISTING - NO WORK
MAIN
COMPUTER
ROOM
023023
STORAGE
031031
FIBER
ENTRANCE
ROOM 01
032032
PUMP ROOM
030030EMERGENCY
POWER
028028
FIBER
ENTRANCE
ROOM 02
027027
STORAGE
026026
POWER
025025 STORAGE
024024
BREAK ROOM
032032
CORRIDOR
035035
EMS
033033
TOILET
034034FEC
FEC
FEC
EXIT NOT AFFECTED
BY CONSTRUCTION
EXIT NOT AFFECTED
BY CONSTRUCTION
EXIT NOT AFFECTED
BY CONSTRUCTION
EXIT NOT AFFECTED
BY CONSTRUCTION
TEMPORARY EGRESS
PATH MUST BE
MAINTAINED DURING
CONSTRUCTION
MIN.
5'-0"
MIN.
6'-0"
TEMPORARY EGRESS
PATH MUST BE
MAINTAINED DURING
CONSTRUCTION
TEMPORARY EGRESS
PATH MUST BE
MAINTAINED DURING
CONSTRUCTION
TEMPORARY EGRESS
PATH MUST BE
MAINTAINED DURING
CONSTRUCTION
EXIT NOT AFFECTED
BY CONSTRUCTION
EXIT NOT AFFECTED
BY CONSTRUCTION
REFER TO A-100 SHEETS FOR NO
WORK AREAS - NO WORK HATCH
NOT SHOWN HERE
EXIT FROM STAIR
FOR FLOORS ABOVE
NOT AFFECTED BY
CONSTRUCTION
COVER EXISTING EXIT SIGN AND POST "NOT
AN EXIT" SIGN DURING CONSTRUCTION.
RESTORE EXISTING EXIT SIGN AFTER
CONSTRUCTION COMPLETE
RAMP DOWN2 HR SEPARATION - to allow existing to be used as Health Care Occupancy in future if needed
'-1
0"
14'-6"
23'-7"
BUILDING SEPARATION CALCULATION NFPA 80A
BLDG WIDTH / BLDG HT - 78/14.33 = 5.44
LOW SEVERITY OF INTERIOR WALL AND CEILING FINISH
OPENING TO WALL% - 0% OPENINGS
FROM TABLE 4.3.7.4 - GUIDE NUMBER = .51
GUIDE NUMBER * BLDG HT +5FT = REQUIRED SEPARATION
.51 * 14.33 +5 = 12.30
= 12'-3 3/4" MINIMUM SEPARATION OF BUILDINGS AT LONGEST
SIDE (OTHER SIDES WOULD BE LESS)
78'-8"
ELECTRICAL
DISTRIBUTION
6B6B
MI
N.
5'- 0"
TN
PN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
Au to de sk
D oc s:
//6
-2
2-
M on tro se V
AM
C
E H
R M
IU
/6
-2
2-
0.
M on tro se .E
H R
M .A
R C
H .B
.rv t
-0 3-
8:
:0
07GI100
LIFE SAFETY PLAN - GROUND FLOOR 620-22-700
06/27/2025 M. Perkins C. Raynes
ISSUED FOR
CONSTRUCTION
(EHRM) INFRASTRUCTURE
UPDATE
2094 Albany Post Road, Montrose, NY 10548
ORIGINAL BUILDING BUILT 1983 AND DESIGNED TO THE
UNIFORM BUILDING CODE 1979 EDITION
CURRENT RENOVATION DOES NOT ADD NEW SQUARE
FOOTAGE, CHANGE SMOKE COMPARTMENT
LOCATIONS, OR ALTER EXITING LOCATIONS.
CALCULATIONS REFLECT COMPLIANCE WITH THE NFPA
101 CODE 2021 EDITION
EXISTING BUILDING IS FULLY SPRINKLED
AREA OF RENOVATION: 16,560 SF
PATH OF TRAVEL SCHEDULE - GROUND FLOOR
Mark From Room To Room Type of Travel Path Length
GROUND LEVEL
(P-o-T) Distance to Exits
E1 STORAGE 024 (P-o-T) Distance to Exits 73' - 5 3/16" E2 STORAGE 031 CORRIDOR 035 (P-o-T) Distance to Exits 62' - 6 1/32" X1 FISCAL STORAGE 7 (P-o-T) Distance to Exits 70' - 10 1/4" X2 OFFICE 5J CORRIDOR 22Z (P-o-T) Distance to Exits 93' - 5 1/2" X3 OFFICE 5C (P-o-T) Distance to Exits 66' - 5 1/4" X4 SERVICE ROOM 9 (P-o-T) Distance to Exits 113' - 7 5/32" X5 MEDICAL CACHE 15A (P-o-T) Distance to Exits 109' - 7 15/16" X6 SPD 17I (P-o-T) Distance to Exits 128' - 2 5/16" X7 SPD STORAGE 17H (P-o-T) Distance to Exits 61' - 10 9/32"
1. REFER TO FIRE SPRINKLER SHEETS FOR SPRINKLER
HAZARD CLASSIFICATION AREAS
2. WORK IN BASEMENT AND SECOND LEVEL ARE
LIMITED TO MINOR REPAIR WHEN PLACING
MECHANICAL AND PLUMBING SYSTEMS. NO CHANGES
TO LIFE SAFETY ELEMENTS WILL BE REQUIRED.
New Addition - PLUMBING FIXTURES REQUIRED BY IBC TABLE 2902.1
WC UNISEX LAV UNISEX BATH/SHOWER DRINKING FOUNTAIN SERVICE SINK
Male/Female 1 PER 25 1 PER 40 0 1 PER 100 1 TOTAL Business
New Addition - PLUMBING FIXTURES REQUIRED
WC UNISEX LAV UNISEX BATH/SHOWER DRINKING FOUNTAIN SERVICE SINK
New Addition 1.08 1 0 1 0 27 occupants round to 1
New Addition - PLUMBING FIXTURES PROVIDED
WC UNISEX LAV UNISEX BATH/SHOWER DRINKING FOUNTAIN SERVICE SINK
New Addition 1 1 0 NO DF PROVIDED 1 27 occupants - WATER PROVIDED IN BREAK ROOM
KEYNOTES-
ORIGINAL CONSTRUCTION
INFORMATION
GENERAL NOTES
1/8" = 1'-0"F1 LIFE SAFETY PLAN - GROUND FLOOR
NOT USED
# Revisions: Date:
1 ADDENDUM #1 03/30/2026
DN
ELEVATOR
ELEVATOR
STORAGE
STORAGE
3B3B
UTILITY
CL.
CORRIDOR
ELECTRICAL
DISTRIBUTION
FISCAL
STORAGE
STAIR
HALL C
SERVICE
ROOM
99 ELECTRICAL
STORAGE
MECH
ROOM
STAIR
HALL A
ENTRANCE
SOILED
LINEN
ENTRANCE
DECON
SPD
DECON
MECH.
RM.
CORRIDOR
22Z22Z
STAIR
HALL B
CORRIDOR
24Z24Z
STORAGE
19A19A
CORRIDOR
26Z26Z
ELEVATOR
LOBBY
25Z25Z
TELE. CL.
1B1B
TELE. CL.
1A1A
TLT
3A3A
OFFICE
5AB5AB
OFFICE
5C5C
OFFICE
5D5D
OFFICE
5E5E
OFFICE
5F5F
OFFICE
5G5G
OFFICE
5H5H
OFFICE
5I5I
OFFICE
5J5J
OFFICE
5K5K
OFFICE
5L5L
ENTRANCE
5G15G1
CORRIDOR
23Z23Z
4A4A
MEDICAL
CACHE
15A15A
STORAGE
15B15B
STORAGE
15C15C
CORRIDOR
17B17B
SPD
STORAGE
17C17C
SPD
STORAGE
17D17D
FOYER
17E17E
OFFICE
17F17F
TLT
17G17G
SPD
STORAGE
17H17H
SPD
17I17I
17J17J
17K17K
BATHROOM
19B19B
STAIR
HALL 4
STAIR
HALL 5
STORAGE
TOILET
11B11B
CHASE
11A11A
3A
VESTIBULE
9C9C
ELECTRICAL
DISTRIBUTION
6B6B
E1 ▬ 29.7'
E2 ▬ 46.3'
INTERIM LIFE SAFETY DEAD END CORRIDOR LENGTH
9'-8"
INTERIM LIFE SAFETY DEAD END CORRIDOR LENGTH
22'-4"
SPS
DECONTAMINATION
INFECTION CONTROL / DUST
CONTROL PARTITION / BARRIER
INFECTION CONTROL/DUST CONTROL
EGRESS DOOR NON-TRANSFERRING
MULTI-SHEETED ADHESIVE FLOOR PADS
PATH OF DEMOLITION/TRASH
REMOVAL TRAVEL
CONSTRUCTION LIMIT LINE
NOT IN CONTRACT AREA
DEMOLITION
LASER PARTICLE COUNT LOCATION
LIFE SAFETY SYMBOLS
PATH OF TRAVEL
(FOR CUMULATIVE DISTANCES
REFER TO SCHEDULE)
EXIT LIGHTING
TM
FIRE EXTINGUISHER CABINET (FEC)
FIRE EXTINGUISHERS (FE)
FIRE HOSE CABINETS (FHC)
HEAT DETECTOR
SMOKE DETECTOR
DIRECTION OF EGRESS
WIDTH PROVIDEDP: XX"
R: XX" WIDTH REQUIRED
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
X - XX'
# ICRA SYMBOLSKEYNOTES
APPLICABLE BUILDING CODES
2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL FIRE
ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD FOR
INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF NFPA
5000 AND NFPA 900
2024 INTERNATIONAL MECHANICAL CODE (IMC)
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA)
STANDARDS.
VA SEISMIC DESIGN REQUIREMENTS, H-18-8
2026 NATIONAL ELECTRICAL CODE (NEC)
2024 INTERNATIONAL PLUMBING CODE (IPC)
ASME BOILER AND PRESSURE VESSEL CODE
ASME CODE FOR PRESSURE PIPING
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS
(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN
GUIDE (PG-18-13)
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE,
AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318)
MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE
FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL
BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION
(AISC)
ENERGY POLICY ACT OF 2005 (EPACT)
DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS
FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE
RESIDENTIAL BUILDINGS AND NEW LOW-RISE RESIDENTIAL
BUILDINGS, 10 CFR PARTS 433, 434 AND 435
FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND
SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING
(MOU)
EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL
ENVIRONMENTAL, ENERGY, AND TRANSPORTATION
MANAGEMENT
THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.
STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00 AND
01 35 26 OF THE VA MASTER CONSTRUCTION SPECIFICATION.
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE
STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE 170-2025, NON-
MEDICAL SPACES - ASHRAE 62.1-2025
SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE
STANDARD 15–2024
2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED BY
VA STANDARDS
UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE
STANDARD OR CODE SHALL BE USED
APPLICABLE BUILDING GUIDES
VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)
BUILDING CODE:
CONSTRUCTION TYPE:
TYPE II (000) PER NFPA 220, Chapter 4 TYPE OF BUILDING: Business Occupancy
Allowable Area and Allowable Stories is not Limited in NFPA by occpancy.
The buidling is supplied with 2 storage rooms set up to become future stairs to serve as 2 exits from upper floors38.2.4.1, and provided with Emergency Lighting 38.2.9.1,and a Fire Alarm system 38.3.4.1.
Current Stories: 1 Possible Future Stories: 5
FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING
ELEMENTS:
STRUCTURAL FRAME 0 HOURS
NON-BEARING WALLS 0 HOURS
BEARING WALLS 0 HOURS
FLOORS 0 HOURS
ROOFS/ CEILINGS 0 HOURS
FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)
FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY
FUNCTION:
ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)
SMOKE COMPARTMENTS 1/2 HOUR
SOILED UTILITY ROOMS 1 HOUR
VERTICAL SHAFTS / STAIRS 2 HOURS
MEDICAL GAS / HAZARDOUS
STORAGE 1 HOURS
7.1.3.2.1 (3) The separation shall have a minimum 2-hour fire resistance rating where the exit connects four or more stories.
NFPA 52.2.2.3.4 In assembly, educational, detention and correction facilities;
health care, ambulatory health care, and day care centers; and, residential board and care and residential occupancies, battery systems shall be located in a room separated from other portions of the building by a minimum of a 2-hour fire barrier. THE MCR (Main Computer Room) IS A MISSION CRITICAL
FACILITY AND PROVIDING A 2 HOUR ADDS ADDITIONAL PROTECTION
TO PROTECT THE SPACE.
MIXED BUILDING OCCUPANCY TYPE:
EXISTING GROUND FLOOR - BUSINESS OCCUPANCY
ADDITION - BUSINESS OCCUPANCY
6.1.14.1.3 Where incidental to another occupanct, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:
(1) Mercantile, BUSINESS, industrial, or storage use
6.1.14.3 Mixed Occupancies
6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.
Table 6.1.14.4.1 (a) - separation of occupanies - 2 Hr between Health Care and Business
6.2 Hazard of Contents.
6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or stucture, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.
EXIT ACCESS TRAVEL DISTANCE:
38.2.6.2 The travel distance between any point in a room and an exit shall not exceed 200 ft.
38.2.6.3 The maximum travel distance...shall not exceed 300 ft in buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7.
BUSINESS OCCUPANCY; PROTECTED = 300'-0"
OCCUPANT LOAD:
38.1.7 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.
CALCULATED OCCUPANT LOADS
PROJECT AREA = 27 TOTAL OCCUPANTS
ADJACENT AREA = N/A
MEANS OF EGRESS:
38.2.3 Capacity of Means of Egress.
38.2.3.1 The capacity of any required means of egress shall be determined in accordance with the provisions Section 7.3.
38.2.3.2 The clear width of any corridor or passageway serving an occupant load of 50 or more shall not be less than 44 in. (1120 mm).
38.2.4 Number of Means of Egress.
38.2.4.1 Means of egress shall comply with all of the flollowing: except as permitted by 38.2.4.2-6
1) the number of means of egress shall be in accordance with section 7.4
2) not less than two separate exits shall be provicded on every story.
3) Not less than two separate exits shall be accessible from every part of every story.
38.2.5.3.1 In building protected throughout by and approvide supervised autoamatic sprinkler system, Dead-end corridors shall not exceed 50 ft.
PROTECTION FROM HAZARDS:
38.3.2 Protection from Hazards.
38.3.2.1 Hazardous Areas
38.3.2.2 High Hazard Contents areas, (section 6.2) shall meet all of the following criteria:
1) The area shall be separated from other parts of the buidling by fire barriers having a minimum 1 hour fire resistance rating, with all openings therein protected by self-closing fire door assemblies having a minimum 3/4 hour fire protection rating
2) The area shall be protected by an automatic extinguishing system in accordance with 9.7.1.1(1) or 9.7.1.2
38.3.2.3 Hazardous Materials. Where hazardous materils are stored or handled, the provisions of 8.7.3.1 shall apply.
38.3.2.4 Medical Gas. Medical gas storage areas and the operation, management and maintenance of medical gases shall be in accordance with
NFPA 99.
38.3.5. Portable fire extinguishers shall be provided in every business occupancy in accordance with Section 9.9.
38.5.1 Utilities shall comply with the provisions of Section 9.1
PARKING SUMMARY:
NO ADDITIONAL PARKING ADDED.
TN
PN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
Au to de sk
D oc s:
//6
-2
2-
M on tro se V
AM
C
E H
R M
IU
/6
-2
2-
0.
M on tro se .E
H R
M .A
R C
H .B
.rv t
-0 3-
3:
:1
07GI300
INFECTION CONTROL PLAN & INTERIM LIFE
SAFETY - GROUND FLOOR
620-22-700
06/27/2025 M. Perkins G. Fantoni
ISSUED FOR
CONSTRUCTION
(EHRM) INFRASTRUCTURE
UPDATE
2094 Albany Post Road, Montrose, NY 10548
1/8" = 1'-0"F1
INFECTION CONTROL PLAN & INTERIM LIFE
SAFETY - GROUND FLOOR
# Revisions: Date:
1 ADDENDUM #1 03/27/2026
2 STAIRS ARE TO REMAIN OPERATIONAL AT ALL TIMES
FOR EMERGENCY EGRESS ONLY. THEY ARE NOT TO BE
USED FOR ANY CONSTRUCTION ACTIVITY.
3 ELEVATORS ARE TO REMAIN OPERATIONAL AT ALL
TIMES
A
ONE ELEVATOR TO BE DESIGNATED FOR CONTRACTOR
USE. CONTRACTOR TO PROTECT / REPAIR ALL FINISHES
AND FOLLOW PROPER ICRA REMOVAL PROTOCOLS FOR
ANY MATERIALS REMOVED FROM SITE THROUGH
ELEVATOR
4 HEPA VACUUM - PROVIDE THROUGHOUT
CONSTRUCTION AREA
5 HEPA EQUIPPED AIR FILTRATION UNIT - PROVIDE
THROUGHOUT CONSTRUCTION AREA. COORDINATE
QUANTITY TO ENSURE NEGATIVE PRESSURE IS
MAINTAINED.
6 PORTABLE CEILING ACCESS MODULE, PROVIDE
THROUGHOUT CONSTRUCTION AREA AS REQUIRED
7 FIRE EXTINGUISHER
8 TEMPORARY CONSTRUCTION BARRIER
9 ADHESIVE WALK-OFF MAT
10 COORDINATE WITH COR TO BLOCK OFF CORRIDOR (48
HR MAX) AS ALTERNATIVE - PROVIDE ICRA CLOSURES
FOR EACH SIDE OF CORRIDOR SEPARATELY - LEAVING
4'-0" MIN FOR CORRIDOR PATHWAY USE BY PUBLIC
12 DEBRIS REMOVAL PATH TOWARDS LOADING DOCK
13 PROVIDE SIGNAGE -NOT AN EXIT - PROCEED TO
CLOSEST EXIT AT STAIR HALL B
14 PROVIDE SIGNAGE -NOT AN EXIT - PROCEED TO
CLOSEST EXIT AT STAIR HALL A
NOTE:
DEBRIS REMOVAL:
COORDINATE REMOVAL OF MATERIALS ON THIS FLOOR WITH
ASBESTOS REPORT AND PLAN.
CONFIRM WITH COR FOR FINAL PLAN AND PROCEDURE OF
MATERIAL REMOVAL WITH ANTEROOMS, HEPA FILTRATION, ICRA
PROTOCOLS, AND ROUTE THRU OCCUPIED SPACES; PRIOR TO
REMOVAL OF ANY MATERIALS.
SECURE STAIRWELLS FROM UNAUTHORIZED ENTRY DURING
CONSTRUCTION.
LIFE SAFETY:
NEW WORK DOES NOT CHANGE EXISTING SMOKE
COMPARTMENTS, EXIT PATHWAYS, OR EXITS.
REFER TO GROUND FLOOR LIFE SAFETY PLAN FOR EGRESS AND
CODE INFORMATION.
PATH OF TRAVEL SCHEDULE -GROUND FLOOR
Mark From Room To Room Type of Travel Path Length
GROUND LEVEL
(P-o-T) Distance to Exits
E1 CORRIDOR 24Z STAIR HALL A 14 (P-o-T) Distance to Exits 29' - 9" E2 CORRIDOR 24Z STAIR HALL B - (P-o-T) Distance to Exits 46' - 4"
AREA OCCUPANCIES
LEVEL Name Area SF
Occupancy Requirements
OL
Occupancy
(IBC) Occupancy (NFPA) OLF Fixed Seats
GROUND LEVEL EXISTING BUSINESS 16260 SF B Business 150 SF 0 108
03/30/2026
WAITING
AREA
101101
STAIR
HALL 01
120120
STAIR
HALL 03
101101
100A100A
ELEVATOR
LOBBY
143Z143Z
101C101C
ELEVATOR
ELEVATOR
STAIR
HALL
STAIR
HALL
3A2
1 8
E1 ▬ 66.1'
CONSULT
106106
WAITING
6M6M
MI
N
4'- 0"
C
LR
VACANT
104B104B
BREAK
ROOM
6P6P PUBLIC
RESTROOM
103A103A
SUPPLIES
102102
SINGLE
ROOM
103103
SINGLE
ROOM
104104
105105
TWO BED
WARD
106106
SINGLE
ROOM
107107
TWO BED
WARD
108108
TWO BED
WARD
109109
TWO BED
WARD
110110
TWO BED
WARD
111111
SINGLE
ROOM
112112
TWO BED
WARD
113113
NURSE
OFFICE
114114
SINKS
116116
117117
TLT
118118
DAY
ROOM
119119
SINGLE
ROOM
121121
SINGLE
ROOM
122122
SINGLE
ROOM
123123
INNER
VAULT
117117
101A101A
TLT
101B101BCHANGING
AREA
115B115B
SHOWERS
115C115C
116A116A
CHANGING
AREA
118A118A
119A119A
NOURISHMENT
119B119B
CORRIDOR
141Z141Z
CORRIDOR
107Z107Z
STORAGE
149149
HD
STORAGE
6C6C
DIRTY
ANTE
ROOM
6D6D
REGULAR
BUFFER
(NON-HAZARDOUS
USP 797 )
6E6E
CHEMO
BUFFER/
STORAGE
(HAZARDOUS,
USP 800)
6F6F
CLEAN
ANTE
ROOM
120A120A
CHEMO
PRODUCTION
123A123A
BULK
STORAGE
6G6G
IP
FILLING/
ASSEMBLY
123B123B
STAFF
RESTROOM
6H6H
CORRIDOR
199C199C
NON-STERILE
COMPOUNDING
123C123C
CHEMO
BREAKOUT
123E123E
BLISTER
PACK
123D123D
STAFF
RESTROOM
6I6I
OP
SUPERVISOR
6J6J
RECEIVING/
BREAKDOWN
115115
OUTER
MAIL OUT
6K6K
BREAK
ROOM
6L6L
STAIR
380380
ELECTRICAL
CLOSET
104A104A
OUTER
VAULT
6S6S
CORRIDOR
199E199E
OP
FILLING/
ASSEMBLY
110A110A
AUTOMATED
FILLING/
STORAGE
110B110B
EXPIRED
DRUGS
6U6U
148148
INFECTION CONTROL / DUST
CONTROL PARTITION / BARRIER
INFECTION CONTROL/DUST CONTROL
EGRESS DOOR NON-TRANSFERRING
MULTI-SHEETED ADHESIVE FLOOR PADS
PATH OF DEMOLITION/TRASH
REMOVAL TRAVEL
CONSTRUCTION LIMIT LINE
NOT IN CONTRACT AREA
DEMOLITION
LASER PARTICLE COUNT LOCATION
LIFE SAFETY SYMBOLS
PATH OF TRAVEL
(FOR CUMULATIVE DISTANCES
REFER TO SCHEDULE)
EXIT LIGHTING
TM
FIRE EXTINGUISHER CABINET (FEC)
FIRE EXTINGUISHERS (FE)
FIRE HOSE CABINETS (FHC)
HEAT DETECTOR
SMOKE DETECTOR
DIRECTION OF EGRESS
WIDTH PROVIDEDP: XX"
R: XX" WIDTH REQUIRED
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
X - XX'
# ICRA SYMBOLSKEYNOTES
APPLICABLE BUILDING CODES
2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL FIRE
ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD FOR
INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF NFPA
5000 AND NFPA 900
2024 INTERNATIONAL MECHANICAL CODE (IMC)
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA)
STANDARDS.
VA SEISMIC DESIGN REQUIREMENTS, H-18-8
2026 NATIONAL ELECTRICAL CODE (NEC)
2024 INTERNATIONAL PLUMBING CODE (IPC)
ASME BOILER AND PRESSURE VESSEL CODE
ASME CODE FOR PRESSURE PIPING
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS
(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN
GUIDE (PG-18-13)
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE,
AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318)
MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE
FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL
BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION
(AISC)
ENERGY POLICY ACT OF 2005 (EPACT)
DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS
FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE
RESIDENTIAL BUILDINGS AND NEW LOW-RISE RESIDENTIAL
BUILDINGS, 10 CFR PARTS 433, 434 AND 435
FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND
SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING
(MOU)
EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL
ENVIRONMENTAL, ENERGY, AND TRANSPORTATION
MANAGEMENT
THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.
STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00 AND
01 35 26 OF THE VA MASTER CONSTRUCTION SPECIFICATION.
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE
STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE 170-2025, NON-
MEDICAL SPACES - ASHRAE 62.1-2025
SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE
STANDARD 15–2024
2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED BY
VA STANDARDS
UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE
STANDARD OR CODE SHALL BE USED
APPLICABLE BUILDING GUIDES
VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)
BUILDING CODE:
CONSTRUCTION TYPE:
TYPE II (000) PER NFPA 220, Chapter 4 TYPE OF BUILDING: Business Occupancy
Allowable Area and Allowable Stories is not Limited in NFPA by occpancy.
The buidling is supplied with 2 storage rooms set up to become future stairs to serve as 2 exits from upper floors38.2.4.1, and provided with Emergency Lighting 38.2.9.1,and a Fire Alarm system 38.3.4.1.
Current Stories: 1 Possible Future Stories: 5
FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING
ELEMENTS:
STRUCTURAL FRAME 0 HOURS
NON-BEARING WALLS 0 HOURS
BEARING WALLS 0 HOURS
FLOORS 0 HOURS
ROOFS/ CEILINGS 0 HOURS
FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)
FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY
FUNCTION:
ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)
SMOKE COMPARTMENTS 1/2 HOUR
SOILED UTILITY ROOMS 1 HOUR
VERTICAL SHAFTS / STAIRS 2 HOURS
MEDICAL GAS / HAZARDOUS
STORAGE 1 HOURS
7.1.3.2.1 (3) The separation shall have a minimum 2-hour fire resistance rating where the exit connects four or more stories.
NFPA 52.2.2.3.4 In assembly, educational, detention and correction facilities;
health care, ambulatory health care, and day care centers; and, residential board and care and residential occupancies, battery systems shall be located in a room separated from other portions of the building by a minimum of a 2-hour fire barrier. THE MCR (Main Computer Room) IS A MISSION CRITICAL
FACILITY AND PROVIDING A 2 HOUR ADDS ADDITIONAL PROTECTION
TO PROTECT THE SPACE.
MIXED BUILDING OCCUPANCY TYPE:
EXISTING GROUND FLOOR - BUSINESS OCCUPANCY
ADDITION - BUSINESS OCCUPANCY
6.1.14.1.3 Where incidental to another occupanct, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:
(1) Mercantile, BUSINESS, industrial, or storage use
6.1.14.3 Mixed Occupancies
6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.
Table 6.1.14.4.1 (a) - separation of occupanies - 2 Hr between Health Care and Business
6.2 Hazard of Contents.
6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or stucture, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.
EXIT ACCESS TRAVEL DISTANCE:
38.2.6.2 The travel distance between any point in a room and an exit shall not exceed 200 ft.
38.2.6.3 The maximum travel distance...shall not exceed 300 ft in buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7.
BUSINESS OCCUPANCY; PROTECTED = 300'-0"
OCCUPANT LOAD:
38.1.7 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.
CALCULATED OCCUPANT LOADS
PROJECT AREA = 27 TOTAL OCCUPANTS
ADJACENT AREA = N/A
MEANS OF EGRESS:
38.2.3 Capacity of Means of Egress.
38.2.3.1 The capacity of any required means of egress shall be determined in accordance with the provisions Section 7.3.
38.2.3.2 The clear width of any corridor or passageway serving an occupant load of 50 or more shall not be less than 44 in. (1120 mm).
38.2.4 Number of Means of Egress.
38.2.4.1 Means of egress shall comply with all of the flollowing: except as permitted by 38.2.4.2-6
1) the number of means of egress shall be in accordance with section 7.4
2) not less than two separate exits shall be provicded on every story.
3) Not less than two separate exits shall be accessible from every part of every story.
38.2.5.3.1 In building protected throughout by and approvide supervised autoamatic sprinkler system, Dead-end corridors shall not exceed 50 ft.
PROTECTION FROM HAZARDS:
38.3.2 Protection from Hazards.
38.3.2.1 Hazardous Areas
38.3.2.2 High Hazard Contents areas, (section 6.2) shall meet all of the following criteria:
1) The area shall be separated from other parts of the buidling by fire barriers having a minimum 1 hour fire resistance rating, with all openings therein protected by self-closing fire door assemblies having a minimum 3/4 hour fire protection rating
2) The area shall be protected by an automatic extinguishing system in accordance with 9.7.1.1(1) or 9.7.1.2
38.3.2.3 Hazardous Materials. Where hazardous materils are stored or handled, the provisions of 8.7.3.1 shall apply.
38.3.2.4 Medical Gas. Medical gas storage areas and the operation, management and maintenance of medical gases shall be in accordance with
NFPA 99.
38.3.5. Portable fire extinguishers shall be provided in every business occupancy in accordance with Section 9.9.
38.5.1 Utilities shall comply with the provisions of Section 9.1
PARKING SUMMARY:
NO ADDITIONAL PARKING ADDED.
1/8" = 1'-0"F1
INFECTION CONTROL PLAN & INTERIM LIFE
SAFETY - FIRST FLOOR TN
PN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
Au to de sk
D oc s:
//6
-2
2-
M on tro se V
AM
C
E H
R M
IU
/6
-2
2-
0.
M on tro se .E
H R
M .A
R C
H .B
.rv t
-0 3-
8:
:1
07GI301
INFECTION CONTROL PLAN & INTERIM LIFE
SAFETY - FIRST FLOOR
620-22-700
06/27/2025 M. Perkins G. Fantoni
ISSUED FOR
CONSTRUCTION
(EHRM) INFRASTRUCTURE
UPDATE
2094 Albany Post Road, Montrose, NY 10548
1 ANTEROOM - REFER TO INFECTION CONTROL &
INTERIM LIFE SAFETY DETAILS
2 STAIRS ARE TO REMAIN OPERATIONAL AT ALL TIMES
FOR EMERGENCY EGRESS ONLY. THEY ARE NOT TO
BE USED FOR ANY CONSTRUCTION ACTIVITY.
3 ELEVATORS ARE TO REMAIN OPERATIONAL AT ALL
TIMES
3A ONE ELEVATOR TO BE DESIGNATED FOR
CONTRACTOR USE. CONTRACTOR TO PROTECT /
REPAIR ALL FINISHES AND FOLLOW PROPER ICRA
REMOVAL PROTOCOLS FOR ANY MATERIALS
REMOVED FROM SITE THROUGH ELEVATOR
4 HEPA VACUUM - PROVIDE THROUGHOUT
CONSTRUCTION AREA
5 HEPA EQUIPPED AIR FILTRATION UNIT - PROVIDE
THROUGHOUT CONSTRUCTION AREA. COORDINATE
QUANTITY TO ENSURE NEGATIVE PRESSURE IS
MAINTAINED.
6 PORTABLE CEILING ACCESS MODULE, PROVIDE
THROUGHOUT CONSTRUCTION AREA AS REQUIRED
7 FIRE EXTINGUISHER
8 TEMPORARY CONSTRUCTION BARRIER
9 ADHESIVE WALK-OFF MAT
# Revisions: Date:
1 ADDENDUM #1 03/27/2026
PATH OF TRAVEL SCHEDULE - FIRST FLOOR
Mark From Room To Room Type of Travel Path Length
INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - FIRST FLOOR
(P-o-T) Distance to Exits
E1 STAIR HALL 03 101 (P-o-T) Distance to Exits 66' - 1"
NOTE:
DEBRIS REMOVAL:
COORDINATE REMOVAL OF MATERIALS ON THIS FLOOR WITH
ASBESTOS REPORT AND PLAN.
CONFIRM WITH COR FOR FINAL PLAN AND PROCEDURE OF
MATERIAL REMOVAL WITH ANTEROOMS, HEPA FILTRATION, ICRA
PROTOCOLS, AND ROUTE THRU OCCUPIED SPACES; PRIOR TO
REMOVAL OF ANY MATERIALS.
SECURE STAIRWELLS FROM UNAUTHORIZED ENTRY DURING
CONSTRUCTION.
LIFE SAFETY:
NEW WORK DOES NOT CHANGE EXISTING SMOKE
COMPARTMENTS, EXIT PATHWAYS, OR EXITS.
REFER TO GROUND FLOOR LIFE SAFETY PLAN FOR EGRESS AND
CODE INFORMATION.
AREA OCCUPANCIES
LEVEL Name Area SF
Occupancy Requirements
OL
Occupancy
(IBC) Occupancy (NFPA) OLF Fixed Seats
FIRST LEVEL EXISTING BUSINESS 16966 SF B Business 150 SF 0 113
VACANT
243243
ELEVATOR
2EV22EV2
WAITING
AREA
201201
CORRIDOR
245Z245Z
VACANT
242242
3A
ELEVATOR
LOBBY
244z244z ELEVATOR
2EV12EV1
230230
231231
VACANT
232232
VACANT
233233
E1 ▬ 70.3'
MI
N
CL
R
4'- 0"
STAIR
HALL 02
235235
CLOSET
203203
VACANT
204204
VACANT
205205
207207
VACANT
208208
VACANT
209209
VACANT
210210VACANT
211211
VACANT
212212
VACANT
213213
VACANT
214214
VACANT
215215
SINKS
216216
217A217A
TLT
218218
VACANT
219219
STAIR
HALL 01
220220
TLT
222A222A
VACANT
222222
VACANT
223223
VACANT
225225
VACANT
234234
VACANT
SINKS
236236
TLT
244244
245245
VACANT
246246
VACANT
238A238A
VACANT
238B238B
VACANT
258258
CONFERENCE
ROOM
238D238D
VACANT
251251
VACANT
252252
VACANT
253253
VACANT
254254
VACANT
255255
VACANT
256256
VACANT
TLT
204A204A
VACANT
206206
CHANGING
AREA
216A216A
SHOWERS
218B218B
217217
CHANGING
AREA
218A218A
VACANT
219F219F
CORRIDOR
246Z246Z
CORRIDOR
248Z248Z
CORRIDOR
247Z247Z
CORRIDOR
250Z250Z
CORRIDOR
238238
CORRIDOR
251Z251Z
239239
CHANGING
AREA
234A234A
SHOWERS
236A1236A1
CHANGING
AREA
236A236A
PIPE
CHASE
234B234B
VACANT
233D233D
STAIR
HALL
STAIR
HALL
VACANT
202202
214A214A
VACANT
219A1219A1
VACANT
219A219A
VACANT
219B219B
VACANT
219C219C
VACANT
219D219D
VACANT
219E219E
TLT
219C1219C1
228A228A
TLT
243243
CORRIDOR
235235
VACANT
233A233A
VACANT
237237
VACANT
238238
VACANT
233E233E
VACANT
233F233F
VACANT
242242
VACANT
242A242A
TELE. CL.
202A202A
INFECTION CONTROL / DUST
CONTROL PARTITION / BARRIER
INFECTION CONTROL/DUST CONTROL
EGRESS DOOR NON-TRANSFERRING
MULTI-SHEETED ADHESIVE FLOOR PADS
PATH OF DEMOLITION/TRASH
REMOVAL TRAVEL
CONSTRUCTION LIMIT LINE
NOT IN CONTRACT AREA
DEMOLITION
LASER PARTICLE COUNT LOCATION
LIFE SAFETY SYMBOLS
PATH OF TRAVEL
(FOR CUMULATIVE DISTANCES
REFER TO SCHEDULE)
EXIT LIGHTING
TM
FIRE EXTINGUISHER CABINET (FEC)
FIRE EXTINGUISHERS (FE)
FIRE HOSE CABINETS (FHC)
HEAT DETECTOR
SMOKE DETECTOR
DIRECTION OF EGRESS
WIDTH PROVIDEDP: XX"
R: XX" WIDTH REQUIRED
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE…