ATTACHMENT 13 - Montrose.EHRM.Addendum.01.B01.20260330.pdf

PDF 26 MB Posted

Attached to
Z2DA--620-22-700 Electronic Health Record Modernization Infrastructure Upgrades - Franklin Delano Roosevelt VA Hospital, Montrose, NY
Solicitation number
RFP-36C77626R0033
Issued by

About this file

This file is an architectural and construction drawing addendum for the Electronic Health Record Modernization (EHRM) Infrastructure Upgrades project at Franklin Delano Roosevelt VA Hospital in Montrose, New York. The addendum, dated March 30, 2026, modifies construction documents for a building renovation affecting ground, first, second, and third floors with total areas ranging from 7,486 to 18,836 square feet per level. Key scope items include creation of four new telecommunications rooms (146 SF at ground level, 138 SF at first level, 148 SF at second level, and 145 SF at third level) with associated electrical and data infrastructure; hazardous material abatement including asbestos-containing transite panels, pipe insulation, and lead-based paint removal; infection control and interim life safety measures with negative pressure containment, HEPA filtration, and dedicated construction barriers; and mechanical systems installation including new chiller units. The project is classified as Type II construction (222) per NFPA 220, requires 1-2 hour fire-rated partitions and smoke barriers, and maintains business occupancy throughout construction with maximum exit travel distances of 300 feet in sprinklered areas.

Construction requirements emphasize coordination with the Contracting Officer Representative (COR) for phasing, debris removal routing, and ICRA (Infection Control Risk Assessment) compliance per Category D (large-scale construction) protocols. Electrical work includes new circuit breakers, panel installations, access control systems, and fiber optic cabling to support telecommunications equipment. Telecommunications infrastructure requires new Category 6A cabling, cable trays, 4-post equipment racks with redundant PDUs, UPS systems, and Avigilon IP-addressable cameras integrated with C-Cure 9000 event management systems. The project must maintain operational continuity for occupied spaces, secure all stairwells during construction, coordinate utility system shutdowns in advance, and complete work outside normal hours only with COR approval. All existing mechanical, electrical, and telecommunications equipment to remain must be protected in place, with transfer of operational devices to new infrastructure completed before demolition of existing systems.

View the file

Other files

File Type Posted
Amend 5 - B04.20260330.pdf PDF
Amend 5 - B14.20260330.pdf PDF
Amend 5 - B15.20260330.pdf PDF
Amend 5 - B17.20260330.pdf PDF
Amend 5 - B20.20260330.pdf PDF
Amend 5 - B28.20260330.pdf PDF
Amendment 4 - 36C77626R0033 0004.pdf PDF
Clause 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS - APR 2026.pdf PDF
RFI TRACKING SHEET - SOLICITATION 36C77626R0033.pdf PDF
ATTACHMENT 1 - SPECS - 620-22-700.Montrose.EHRM.Spec.IFC.20260410.pdf PDF
ATTACHMENT 5 - 01 00 00.D - Appendix D - SOP 138-06HV OCCUPATIONAL SAFETY AND HEALTH PROGRAM.pdf PDF
ATTACHMENT 11 - 01 00 00.I - Appendix I - K9245005 VAMC EHRM Montrose NY GeoReport 4.12.2024.pdf PDF
ATTACHMENT 12A - Summary.Log.Add01_20260410.pdf PDF
ATTACHMENT 14 - Montrose.EHRM.Addendum.01.B02.20260330.pdf PDF
ATTACHMENT 22 - Montrose.EHRM.Addendum.01.B14.20260330.pdf PDF
ATTACHMENT 25 - Montrose.EHRM.Addendum.01.B17.20260330.pdf PDF
ATTACHMENT 26A - Montrose.EHRM.Addendum.01.B19.20260330.pdf PDF
ATTACHMENT 30 - Montrose.EHRM.Addendum.01.B29.20260330.pdf PDF
ATTACHMENT 31 - Montrose.EHRM.Addendum.01.B31.20260330.pdf PDF
ATTACHMENT 3 - 01 00 00.B - Appendix B - Submittal Log.pdf PDF
ATTACHMENT 8 - 01 00 00.G - Appendix G - GPRS Triple C Montrose Full Report.pdf PDF
ATTACHMENT 16 - Montrose.EHRM.Addendum.01.B04.20260330.pdf PDF
ATTACHMENT 21 - Montrose.EHRM.Addendum.01.B13.20260330.pdf PDF
ATTACHMENT 24 - Montrose.EHRM.Addendum.01.B16.20260330.pdf PDF
ATTACHMENT 27 - Montrose.EHRM.Addendum.01.B20.20260330.pdf PDF
ATTACHMENT 28 - Montrose.EHRM.Addendum.01.B26.20260330.pdf PDF
ATTACHMENT 28A - Montrose.EHRM.Addendum.01.B27.20260330.pdf PDF
ATTACHMENT 32 - Montrose.EHRM.Addendum.01.B52.20260330.pdf PDF
Amendment 2 - 36C77626R0033 0002.pdf PDF
Site visit sign-in sheet 3-23-26.pdf PDF
RFP - 36C77626R0033.pdf PDF
Attachment 3 - 01 00 00.B - Appendix B - Submittal Log.pdf PDF
Attachment 4 - 01 00 00.C - Appendix C1 SOP 138-22HV CONST STD PROCEDURES QA FOR PROJECTS.pdf PDF
Attachment 5 - 01 00 00.D - Appendix D1 SOP 138-06HV OCCUPATIONAL SAFETY AND HEALTH PROGRAM.pdf PDF
Attachment 16 - Drawing B04 20250627.pdf PDF
Attachment 18 - Drawing B06 20250627.pdf PDF
Attachment 22 - Drawing B14 20250627.pdf PDF
Attachment 27 - Drawing B20 20250627.pdf PDF
Attachment 29 - Drawing B28 20250627.pdf PDF
Attachment 32 - Drawing B52 20250627.pdf PDF
Attachment 36 - Division Cost Breakdown.xlsx XLSX spreadsheet
Attachment 1 - SPECS - 620-22-700.Montrose.EHRM.Spec.IFC.20260205.pdf PDF
Attachment 6 - 01 00 00.E - Appendix E - VHA ICRA-1.3 - Dec 9 2024.pdf PDF
Attachment 7 - 01 00 00.F - Appendix F - VHA PCRA 2024 1.1 Final.Template Fillable.pdf PDF
Attachment 8 - 01 00 00.G - Appendix G - GPRS Triple C Montrose Full Report.pdf PDF
Attachment 9 - 01 00 00.H - Appendix H - J2237038 Montrose ACM Ld Pnt InspRpt Final 8-21-2023.pdf PDF
Attachment 12 - Additional Security Badging Requirements rev 2.pdf PDF
Attachment 13 - Drawing B01 20250627.pdf PDF
Attachment 31 - Drawing B31 20250627.pdf PDF
Attachment 33 - Drawing Site 20250627.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

STAMP

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .M

EP

.B

.rv t 3/

/2

:2

0:

P M

01G-001

DRAWING INDEX 620-22-700

06/27/2025 M. PERKINS M. RIFFLE

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

- DRAWING INDEX -

SHEET

NUMBER SHEET NAME INCLUDED IN 35% SD INCLUDED IN 65% DD INCLUDED IN 95% CD ISSUED FOR CONSTRUCTION

GENERAL

01G-000 COVER SHEET Yes Yes Yes Yes 01G-001 DRAWING INDEX Yes Yes Yes Yes 01G-010 GENERAL PROJECT NOTES Yes Yes Yes Yes 01G-012 GENERAL INDOOR AIR QUALITY NOTES Yes Yes Yes Yes

ICRA & LIFE SAFETY

01GI300 INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - GROUND FLOOR No No No No 01GI301 INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - FIRST FLOOR No No No No 01GI302 INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - SECOND FLOOR No No No No 01GI303 INFECTION CONTROL PLAN & INTERIM LIFE SAFETY - THIRD FLOOR No No No No 01GI304 INFECTION CONTROL & INTERIM LIFE SAFETY DETAILS No No No No

HAZARDOUS

01H-101 HAZARDOUS MATERIAL ABATEMENT PLAN - FIRST LEVEL No Yes Yes 01H-102 HAZARDOUS MATERIAL ABATEMENT PLAN - SECOND LEVEL No Yes Yes Yes 01H-103 HAZARDOUS MATERIAL ABATEMENT PLAN - THIRD LEVEL No Yes Yes

ARCHITECTURAL

01A-001 ARCHITECTURAL SYMBOLS, & GENERAL NOTES No Yes Yes Yes 01A-400 ARCHITECTURAL ENLARGED VIEWS - GROUND & FIRST LEVEL No Yes Yes Yes 01A-401 ARCHITECTURAL ENLARGED VIEWS - SECOND LEVEL No Yes Yes Yes 01A-402 ARCHITECTURAL ENLARGED VIEWS - THIRD LEVEL No Yes Yes Yes 01A-403 ARCHITECTURAL EXTERIOR ELEVATIONS No Yes Yes Yes 01A-511 ARCHITECTURAL PARTITION AND FRAMING DETAILS No Yes Yes Yes 01A-512 ARCHITECTURAL PARTITION HEAD DETAILS No Yes Yes Yes 01A-531 ARCHITECTURAL CEILING DETAILS No Yes Yes Yes

INTERIORS

01IN101 INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES No Yes Yes Yes

FIRE PROTECTION

01FX001 FIRE PROTECTION ABBREVIATIONS, SYMBOLS, AND DETAILS No Yes Yes Yes 01FX100 FIRE PROTECTION PLAN - GROUND LEVEL No Yes Yes Yes 01FX101 FIRE PROTECTION PLAN - FIRST LEVEL No Yes Yes Yes 01FX102 FIRE PROTECTION PLAN - SECOND LEVEL No Yes Yes Yes 01FX103 FIRE PROTECTION PLAN - THIRD LEVEL No Yes Yes Yes 01FX401 FIRE PROTECTION ENLARGED PLANS No Yes Yes Yes 01FX901 FIRE PROTECTION CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes

PLUMBING

01P-001 PLUMBING ABBREVIATIONS AND SYMBOLS No Yes Yes Yes 01PD100 PLUMBING DEMOLITION PLAN - GROUND LEVEL No No No Yes

MECHANICAL

01M-001 MECHANICAL ABBREVIATIONS AND SYMBOLS No Yes Yes Yes 01M-100 MECHANICAL PLAN - GROUND LEVEL No Yes Yes Yes 01M-101 MECHANICAL PLAN - FIRST LEVEL No Yes Yes Yes 01M-102 MECHANICAL PLAN - SECOND LEVEL No Yes Yes Yes 01M-103 MECHANICAL PLAN - THIRD LEVEL & SITE PLAN No Yes Yes Yes 01M-401 MECHANICAL ENLARGED PLANS No Yes Yes Yes 01M-501 MECHANICAL DETAILS No Yes Yes Yes 01M-701 MECHANICAL SCHEDULES No Yes Yes Yes 01M-801 MECHANICAL CONTROL SYMBOL LEGEND AND ABBREVIATIONS No Yes Yes Yes 01M-802 MECHANICAL CONTROL DIAGRAMS No Yes Yes Yes 01M-901 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes 01M-902 MECHANICAL CUTSHEETS & BASIS OF DESIGN No Yes Yes Yes

ELECTRICAL

01E-001 ELECTRICAL ABBREVIATIONS AND SYMBOLS Yes Yes Yes Yes 01E-100 ELECTRICAL PLAN - GROUND LEVEL No Yes Yes Yes 01E-101 ELECTRICAL PLAN - FIRST LEVEL No Yes Yes Yes 01E-102 ELECTRICAL PLAN - SECOND LEVEL No Yes Yes Yes 01E-103 ELECTRICAL PLAN - THIRD LEVEL No Yes Yes Yes 01E-401 ELECTRICAL ENLARGED PLANS No Yes Yes Yes 01E-402 ELECTRICAL ENLARGED PLANS No Yes Yes Yes 01E-501 ELECTRICAL DETAILS Yes Yes Yes Yes 01E-601 ELECTRICAL ONE-LINE DIAGRAMS - DEMOLITION Yes Yes Yes Yes 01E-602 ELECTRICAL ONE-LINE DIAGRAMS - NEW CONSTRUCTION No No No No 01E-701 ELECTRICAL SCHEDULES No Yes Yes Yes 01E-702 ELECTRICAL SCHEDULES No Yes Yes Yes 01E-703 ELECTRICAL SCHEDULES No Yes Yes Yes 01E-901 ELECTRICAL CUTSHEETS & BASIS OF DESIGN Yes Yes Yes Yes 01E-902 ELECTRICAL CUTSHEETS & BASIS OF DESIGN No No No Yes

TELECOMMUNICATION

01T-001 TELECOMMUNICATION ABBREVIATIONS AND SYMBOLS Yes Yes Yes Yes 01T-100 TELECOMMUNICATION PLAN - GROUND LEVEL Yes Yes Yes Yes 01T-101 TELECOMMUNICATION PLAN - FIRST LEVEL Yes Yes Yes Yes 01T-102 TELECOMMUNICATION PLAN - SECOND LEVEL Yes Yes Yes Yes 01T-103 TELECOMMUNICATION PLAN - THIRD LEVEL Yes Yes Yes Yes 01T-401 TELECOMMUNICATION ENLARGED PLANS No Yes Yes Yes 01T-402 TELECOMMUNICATION ENLARGED PLANS No Yes Yes Yes 01T-501 TELECOMMUNICATION DETAILS Yes Yes Yes Yes 01T-502 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS Yes Yes Yes Yes 01T-503 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS Yes Yes Yes Yes 01T-504 TELECOMMUNICATION ROOM OIT TEMPLATE DETAILS No Yes Yes Yes 01T-601 TELECOMMUNICATION RISER DIAGRAMS Yes Yes Yes Yes 01T-603 TELECOMMUNICATION FIBER RISER DIAGRAM - NEW No Yes Yes Yes 01T-604 TELECOMMUNICATION RACK EXISTING/NEW ELEVATIONS Yes Yes Yes Yes 01T-605 TELECOMMUNICATION RACK EXISTING/NEW ELEVATIONS Yes Yes Yes Yes 01T-700 TELECOMMUNICATION SCHEDULES No Yes Yes Yes 01T-701 TELECOMMUNICATION SCHEDULE No Yes Yes Yes 01T-702 TELECOMMUNICATION SCHEDULES No Yes Yes Yes 01T-901 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN Yes Yes Yes Yes 01T-902 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN No No Yes Yes 01T-903 TELECOMMUNICATION CUTSHEETS & BASIS OF DESIGN No No Yes Yes

REFERENCE

01R-900 PHOTO REFERENCES No Yes Yes Yes 01R-901 PHOTO REFERENCES No Yes Yes Yes Grand total: 80

# Revisions: Date:

1 ADDENDUM #1 03/30/2026

01G-011 REMOVED FROM

CONSTRUCTION DOCUMENTS

03/30/2026

Ranjan Text Box

INFECTION CONTROL / DUST

CONTROL PARTITION / BARRIER

INFECTION CONTROL/DUST CONTROL

EGRESS DOOR NON-TRANSFERRING

MULTI-SHEETED ADHESIVE FLOOR PADS

PATH OF DEMOLITION/TRASH

REMOVAL TRAVEL

CONSTRUCTION LIMIT LINE

NOT IN CONTRACT AREA

DEMOLITION

LASER PARTICLE COUNT LOCATION

LIFE SAFETY SYMBOLS

PATH OF TRAVEL

(FOR CUMULATIVE DISTANCES

REFER TO SCHEDULE)

EXIT LIGHTING

TM

FIRE EXTINGUISHER CABINET (FEC)

FIRE EXTINGUISHERS (FE)

FIRE HOSE CABINETS (FHC)

HEAT DETECTOR

SMOKE DETECTOR

DIRECTION OF EGRESS

APPLICABLE BUILDING CODES

2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL

FIRE ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD

FOR INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF

NFPA 5000 AND NFPA 900

2024 INTERNATIONAL MECHANICAL CODE (IPC)

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION

(OSHA) STANDARDS.

VA SEISMIC DESIGN REQUIREMENTS, H-18-8

2026 NATIONAL ELECTRICAL CODE (NEC)

2024 INTERNATIONAL PLUMBING CODE (IPC)

ASME BOILER AND PRESSURE VESSEL CODE

ASME CODE FOR PRESSURE PIPING

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS

(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN

GUIDE (PG-18-13)

BUILDING CODE REQUIREMENTS FOR REINFORCED

CONCRETE, AMERICAN CONCRETE INSTITUTE AND

COMMENTARY (ACI 318)

MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE

FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL

BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION

(AISC)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION

STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-

FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-

RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND

SUSTAINABLE BUILDINGS: MEMORANDUM OF

UNDERSTANDING (MOU)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL

ENVIRONMENTAL, ENERGY, AND TRANSPORTATION

MANAGEMENT

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.

STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00

AND 01 35 26 OF THE VA MASTER CONSTRUCTION

SPECIFICATION.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY –

ASHRAE STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE

170-2025, NON-MEDICAL SPACES - ASHRAE 62.1-2025

SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE

STANDARD 15–2024

2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED

BY VA STANDARDS

UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE

STANDARD OR CODE SHALL BE USED

APPLICABLE BUILDING GUIDES

VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)

BUILDING CODE:

CONSTRUCTION TYPE:

TYPE II (222) PER NFPA 220, Chapter 4

TYPE OF BUILDING REHABILITATION: MODIFICATION, CHAPTER 43.

FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)

FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING

ELEMENTS:

STRUCTURAL FRAME 2 HOURS

NON-BEARING WALLS 0 HOURS

BEARING WALLS 2 HOURS

FLOORS 2 HOURS

ROOFS/ CEILINGS 1 HOURS

FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)

FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY

FUNCTION:

ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)

SMOKE COMPARTMENTS 1/2 HOUR

SOILED UTILITY ROOMS 1 HOUR

VERTICAL SHAFTS / STAIRS 2 HOURS

MEDICAL GAS / HAZARDOUS 1 HOUR

STORAGE

CLASSIFICATION OF OCCUPANCY:

EXISTING: BUSINESS Occupancy per Chapter 39

39.1.1.6 Where construction, alteration, or demolition operations are conducted, the provisions of 4.6.10.2 shall apply

39.1.2 Business occupancies shall include all buildings and structures or parts thereof with occupancy defined in 6.1.11

BUILDING OCCUPANCY TYPE:

EXISTING - BUSINESS OCCUPANCY

6.1.14.1.3 Where incidental to another occupant, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:

(1) Mercantile, BUSINESS, industrial, or storage use

6.1.14.3 Mixed Occupancies

6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.

Table 6.1.14.4.1 (a) - separation of occupancies - 2 Hr between Health Care and Business

6.2 Hazard of Contents.

6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or structure, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.

EXIT ACCESS TRAVEL DISTANCE:

39.2.6.2 The travel distance between any point in a room and an exit shall not exceed 200 ft.

39.2.6.3 The maximum travel distance...shall not exceed 300 ft in buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7.

BUSINESS OCCUPANCY; PROTECTED = 300'-0"

OCCUPANT LOAD:

39.1.7 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.

MEANS OF EGRESS:

39.2.3 Capacity of Means of Egress.

39.2.3.1 The capacity of any required means of egress shall be determined in accordance with the provisions Section 7.3.

39.2.3.2 The clear width of any corridor or passageway serving an occupant load of 50 or more shall not be less than 44 in. (1120 mm).

39.2.4 Number of Means of Egress.

39.2.4.1 Means of egress shall comply with all of the following: except as permitted by 39.2.4.2-6

1) the number of means of egress shall be in accordance with section 7.4

2) not less than two separate exits shall be provided on every story.

3) Not less than two separate exits shall be accessible from every part of every story.

39.2.5.3 In building protected throughout by and approved supervised automatic sprinkler system, Dead-end corridors shall not exceed 50 ft.

PROTECTION OF VERTICAL OPENINGS:

39.3.1 Protection of Vertical Openings.

39.3.1.1 Any vertical opening shall be enclosed or protected in accordance with Section 8.6, unless otherwise permitted.

PROTECTION FROM HAZARDS:

39.3.2 Protection from Hazards.

39.3.2.1 Hazardous Areas - Any hazardous areas shall be protected in accordance with Section 8.7

39.3.2.2 The following areas shall be considered hazardous areas and shall be protected by fire barriers having a minimum 1-hour fire resistance rating in accordance with Section 8.3:

(1) Boilder and fuel-fired heater rooms

(2) Central/bulk laundries larger than 100 ft2

(3) Paint Shops

(4) Physical plant maintenance shops

(5) Rooms with soiled linen in volume exceeding 64 gal

(6) Rooms with collected trashed in volume exceeding 64 gal.

(7) Storage rooms larger than 100 ft2 and storing combustible material

The following areas shall be considered hazardous areas and shall be protected by smoke partitions in accordance with Section 8.4:

(1) Laboratories employing flammable or combustible materials in quantities less than those that would be considered a severe hazard.

(2) Storage rooms larger than 50 ft2 but not exceeding 100 ft2 and storing combustible material.

39.3.2.5 Medical Gas. Medical gas storage shall be in accordance with Section 8.7 and the provisions of NFPA 99, Health Care Facilities Code, applicable to operation, maintenance, and testing.

39.3.5 Portable fire extinguishers shall be provided in all health care occupancies facilities in accordance with Section 9.9.

PARKING SUMMARY:

NO ADDITIONAL PARKING ADDED

WIDTH PROVIDEDP: XX"

R: XX" WIDTH REQUIRED

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

X - XX'

# ICRA SYMBOLSKEYNOTES

18824 SF

B - EXISTING BUSINESS

MI

N.

5'- 0"

C

LR

FEC

TELECOM

ROOM

15A

ENTRANCE

AUTOPSY

CORR.

39Z

ELEVATOR

BANK

ELEV

CRAWL

SPACE

X

E2 ▬ 58.3'

ADMIN.

SUPPORT

SUPPORT

STAFF

30B

CORR.

40Z

COMMON

AREA

E1 ▬ 110.9'

STAIR HALL

A

E3 ▬ 57.6'

CUBICAL

SPACE

OFFICE

OFFICE

ADMIN.

STAFF

12OFFICE

TLT

8A

TLT

7B

PIPE CL.

7B1

STAIR HALL

B

STOR.

13A

CORR.

37Z

OFFICE

7A

CORR.

38Z

OFFICE

LOUNGE

6F

OFFICE

6E

OFFICE

6D

CONFERENCE

ROOM

6C

OFFICE

6B

OFFICE

6A

ADMIN

SUPPORT

OFFICE

5A

UTILITY CL.

4B

CL.

4A

STORAGE

TLT

3A

CL.

3B

LOCKER

ROOM

STARBUCK'S

COFFEE

TELE CL.

2A

TELE CL.

SERVICE

AREA

1A

STORAGE

1B

TELEPHONE

ROOM

CREDIT

UNION

VAULT

TELE.

COMM. CL.

35B

CONFERENCE

ROOM

TELE CL.

35A

TELEPHONE

ROOM

UTILITY

CLOSET

CL.

34B

SUPPORT

STAFF

ACQUISITIONS

32E

OFFICE

32A

OFFICE

32B

OFFICE

32C

OFFICE

32D

STAFF

LOUNGE

COMMON

AREA

30E

TLT

30G

TLT

30F

PIPE CL.

30D

COPY AREA

30C

SUPPORT

STAFF

30A

OFFICE

26B

CL.

STOR.

28A

SUPPORT

STAFF

OFFICE

29C

CHIEF

OFFICE

29B

OFFICE

29A

OFFICE

26A

CL.

26A1

OFFICE

FOYER

STAIR HALL

C

ELEC.

STOR

23A

ENTRANCE

ELEVATOR

LOBBY

41Z

MECH.

ROOM

CORR.

42Z

HSKP

OFFICE

20A

CREDIT

UNION

LOBBY

20B

OFFICE OF

VETERAN

AFFAIRS

19AWAITING

AREA

CL.

19B

OFFICE OF

VETERAN

AFFAIRS

ELEC.

ROOM

PLATFORM

15C

CL.

7C

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .A

R C

H .B

.rv t

-0 3-

5:

:3

01GI300

INFECTION CONTROL PLAN & INTERIM LIFE

SAFETY - GROUND FLOOR

620-22-700

06/27/2025 M. Perkins S POLLARD

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

NOTE:

DEBRIS REMOVAL:

COORDINATE REMOVAL OF MATERIALS ON THIS FLOOR WITH

ASBESTOS REPORT AND PLAN.

CONFIRM WITH COR FOR FINAL PLAN AND PROCEDURE OF

MATERIAL REMOVAL WITH ANTEROOMS, HEPA FILTRATION, ICRA

PROTOCOLS, AND ROUTE THRU OCCUPIED SPACES; PRIOR TO

REMOVAL OF ANY MATERIALS.

SECURE STAIRWELLS FROM UNAUTHORIZED ENTRY DURING

CONSTRUCTION.

LIFE SAFETY:

NEW WORK DOES NOT CHANGE EXISTING SMOKE

COMPARTMENTS, EXIT PATHWAYS, OR EXITS.

1 TEMPORARY CONSTRUCTION BARRIER

2 ANTEROOM - SEE INFECTION CONTROL & INTERIM

LIFE SAFETY DETAILS

3 TEMPORARY CONSTRUCTION BARRIER DOOR WITH

CLOSER AND LATCH AND WALK OFF MATS

4 DEBRIS REMOVAL PATH TO EXTERIOR -

COORDINATE REMOVAL OF MATERIALS ON THIS

FLOOR WITH ASBESTOS REPORT AND PLAN

5 REMOVE EXISTING WINDOW, AC UNIT AND METAL

SUPPORT FRAME. PROVIDE TEMPORARY INFILL.

6 SOLID GRAY HATCH DENOTES LIMITED WORK AREA -

SEE MEP AND TELECOM DRAWINGS FOR CABLING

SCOPE, TYP.

7 MAINTAIN EXIT PATHWAYS FOR OCCUPANTS AT ALL

TIMES

8 COORDINATE TEMPORARY HEPA EXHAUST ROUTING

OUT OF BUILDING - MAINTAIN 25 FEET MINIMUM

FROM INTAKES, OPERABLE WINDOWS, AND

ENTRANCES. PROVIDE BLOCK-OFF PANELS IN

EXISTING WINDOWS FOR DISCHARGE, TYP.

# Revisions: Date:

1 ADDENDUM #1 03/27/2026

1/8" = 1'-0"F1

INFECTION CONTROL PLAN & INTERIM

LIFE SAFETY - GROUND FLOOR

PATH OF TRAVEL SCHEDULE - GROUND FLOOR

Mark From Room To Room Type of Travel Path Length

GROUND LEVEL

(P-o-T) Distance to Exits

E1 ADMIN SUPPORT 6 ENTRANCE 38 (P-o-T) Distance to Exits 110' - 10" E2 TELECOM ROOM 15A ENTRANCE 38 (P-o-T) Distance to Exits 58' - 3" E3 SUPPORT STAFF 30B STAIR HALL A 28 (P-o-T) Distance to Exits 57' - 7"

AREA OCCUPANCIES

LEVEL Name Area SF

Occupancy Requirements

OL

Occupancy

(IBC) Occupancy (NFPA) OLF Fixed Seats

GROUND FLOOR EXISTING BUSINESS 18824 SF B Business 150 SF 0 125

03/30/2026

INFECTION CONTROL/DUST CONTROL

EGRESS DOOR NON-TRANSFERRING

MULTI-SHEETED ADHESIVE FLOOR PADS

PATH OF DEMOLITION/TRASH

REMOVAL TRAVEL

CONSTRUCTION LIMIT LINE

NOT IN CONTRACT AREA

DEMOLITION

LASER PARTICLE COUNT LOCATION

LIFE SAFETY SYMBOLS

PATH OF TRAVEL

(FOR CUMULATIVE DISTANCES

REFER TO SCHEDULE)

EXIT LIGHTING

TM

FIRE EXTINGUISHER CABINET (FEC)

FIRE EXTINGUISHERS (FE)

FIRE HOSE CABINETS (FHC)

HEAT DETECTOR

SMOKE DETECTOR

DIRECTION OF EGRESS

APPLICABLE BUILDING CODES

2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL

FIRE ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD

FOR INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF

NFPA 5000 AND NFPA 900

2024 INTERNATIONAL MECHANICAL CODE (IPC)

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION

(OSHA) STANDARDS.

VA SEISMIC DESIGN REQUIREMENTS, H-18-8

2026 NATIONAL ELECTRICAL CODE (NEC)

2024 INTERNATIONAL PLUMBING CODE (IPC)

ASME BOILER AND PRESSURE VESSEL CODE

ASME CODE FOR PRESSURE PIPING

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS

(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN

GUIDE (PG-18-13)

BUILDING CODE REQUIREMENTS FOR REINFORCED

CONCRETE, AMERICAN CONCRETE INSTITUTE AND

COMMENTARY (ACI 318)

MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE

FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL

BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION

(AISC)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION

STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-

FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-

RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND

SUSTAINABLE BUILDINGS: MEMORANDUM OF

UNDERSTANDING (MOU)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL

ENVIRONMENTAL, ENERGY, AND TRANSPORTATION

MANAGEMENT

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.

STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00

AND 01 35 26 OF THE VA MASTER CONSTRUCTION

SPECIFICATION.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY –

ASHRAE STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE

170-2025, NON-MEDICAL SPACES - ASHRAE 62.1-2025

SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE

STANDARD 15–2024

2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED

BY VA STANDARDS

UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE

STANDARD OR CODE SHALL BE USED

APPLICABLE BUILDING GUIDES

VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)

BUILDING CODE:

CONSTRUCTION TYPE:

TYPE II (222) PER NFPA 220, Chapter 4

TYPE OF BUILDING REHABILITATION: MODIFICATION, CHAPTER 43.

FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)

FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING

ELEMENTS:

STRUCTURAL FRAME 2 HOURS

NON-BEARING WALLS 0 HOURS

BEARING WALLS 2 HOURS

FLOORS 2 HOURS

ROOFS/ CEILINGS 1 HOURS

FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)

FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY

FUNCTION:

ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)

SMOKE COMPARTMENTS 1/2 HOUR

SOILED UTILITY ROOMS 1 HOUR

VERTICAL SHAFTS / STAIRS 2 HOURS

MEDICAL GAS / HAZARDOUS 1 HOUR

STORAGE

CLASSIFICATION OF OCCUPANCY:

EXISTING: BUSINESS Occupancy per Chapter 39

39.1.1.6 Where construction, alteration, or demolition operations are conducted, the provisions of 4.6.10.2 shall apply

39.1.2 Business occupancies shall include all buildings and structures or parts thereof with occupancy defined in 6.1.11

BUILDING OCCUPANCY TYPE:

EXISTING - BUSINESS OCCUPANCY

6.1.14.1.3 Where incidental to another occupant, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:

(1) Mercantile, BUSINESS, industrial, or storage use

6.1.14.3 Mixed Occupancies

6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.

Table 6.1.14.4.1 (a) - separation of occupancies - 2 Hr between Health Care and Business

6.2 Hazard of Contents.

6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or structure, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.

EXIT ACCESS TRAVEL DISTANCE:

39.2.6.2 The travel distance between any point in a room and an exit shall not exceed 200 ft.

39.2.6.3 The maximum travel distance...shall not exceed 300 ft in buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7.

BUSINESS OCCUPANCY; PROTECTED = 300'-0"

OCCUPANT LOAD:

39.1.7 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.

MEANS OF EGRESS:

39.2.3 Capacity of Means of Egress.

39.2.3.1 The capacity of any required means of egress shall be determined in accordance with the provisions Section 7.3.

39.2.3.2 The clear width of any corridor or passageway serving an occupant load of 50 or more shall not be less than 44 in. (1120 mm).

39.2.4 Number of Means of Egress.

39.2.4.1 Means of egress shall comply with all of the following: except as permitted by 39.2.4.2-6

1) the number of means of egress shall be in accordance with section 7.4

2) not less than two separate exits shall be provided on every story.

3) Not less than two separate exits shall be accessible from every part of every story.

39.2.5.3 In building protected throughout by and approved supervised automatic sprinkler system, Dead-end corridors shall not exceed 50 ft.

PROTECTION OF VERTICAL OPENINGS:

39.3.1 Protection of Vertical Openings.

39.3.1.1 Any vertical opening shall be enclosed or protected in accordance with Section 8.6, unless otherwise permitted.

PROTECTION FROM HAZARDS:

39.3.2 Protection from Hazards.

39.3.2.1 Hazardous Areas - Any hazardous areas shall be protected in accordance with Section 8.7

39.3.2.2 The following areas shall be considered hazardous areas and shall be protected by fire barriers having a minimum 1-hour fire resistance rating in accordance with Section 8.3:

(1) Boilder and fuel-fired heater rooms

(2) Central/bulk laundries larger than 100 ft2

(3) Paint Shops

(4) Physical plant maintenance shops

(5) Rooms with soiled linen in volume exceeding 64 gal

(6) Rooms with collected trashed in volume exceeding 64 gal.

(7) Storage rooms larger than 100 ft2 and storing combustible material

The following areas shall be considered hazardous areas and shall be protected by smoke partitions in accordance with Section 8.4:

(1) Laboratories employing flammable or combustible materials in quantities less than those that would be considered a severe hazard.

(2) Storage rooms larger than 50 ft2 but not exceeding 100 ft2 and storing combustible material.

39.3.2.5 Medical Gas. Medical gas storage shall be in accordance with Section 8.7 and the provisions of NFPA 99, Health Care Facilities Code, applicable to operation, maintenance, and testing.

39.3.5 Portable fire extinguishers shall be provided in all health care occupancies facilities in accordance with Section 9.9.

PARKING SUMMARY:

NO ADDITIONAL PARKING ADDED

WIDTH PROVIDEDP: XX"

R: XX" WIDTH REQUIRED

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

X - XX'

# ICRA SYMBOLSKEYNOTES

1 4

3A

MI

N.

5'- 0"

C

LR

STAIR HALL

CORR.

157Z

CORR.

156Z

TELECOM

ROOM

ELEVATOR

BANK

ELEV

ELEVATOR

LOBBY

158Z

LOBBY

ENTRANCE

E1 ▬ 80.2'

FEC

18836 SF

EXISTING BUSINESS -

OFFICE

OFFICE

110TLT

110B

OFFICE

109C

STORAGE

109B

OFFICE

OFFICE

OFFICE

111A

STORAGE

CONFERENCE

ROOM

OFFICE

OFFICE

114A

OFFICE

CL.

120A

CL.

120B

CL.

HSKP

TLT

105B

OFFICE

116C

OFFICE

116B

HALL/FILE

116A

OFFICE

116D

STAFF

LOUNGE

116E

OFFICE

SUPPLIES

ADMIN.

SUPPORT

CORR.

OFFICE

SWING

SPACE

119A TLT

119C

CONFERENCE

ROOM

119B

OFFICE

115A

OFFICE

115B

WOMENS

TLT

OFFICE

OFFICE

124A

OFFICE

STOR.

105A

OFFICE

OFFICE

OFFICES

TLT

102B

TELE.

CLOSET

102A

VESTIBULE

101A

CORR.

159Z

ELEC. CL.

133CL.

133A

INFORMATION

OFFICE

155A

INFORMATION

TLT

155B

OFFICE

OFFICE

CLOSET

MENS TLT

WOMENS

TLT

TLT

134B

CLOSET

134A

OFFICE

OFFICE

OFFICE

CL

152B

CL.

KITCHEN

STAIR HALL

STAFF

LOUNGE

131B

STOR.

131C

OFFICE

CORR.

160Z

OFFICE

126A

OFFICE

131A

OFFICE

OFFICE

OFFICE

127A

OFFICE

OFFICE

OFFICE

128B

OFFICE

OFFICE

128A

DIRECTOR'S

OFFICE

TLT

147C

HALL

147A

CL.

147B

CL.

146B

ASSOC.

DIRECTOR'S

OFFICE

ADMIN.

SUPPORT

146A

Room

162Z

ADMIN

SUPPORT

COPY

ROOM

CORR.

161Z

ADMIN

SUPPORT

139B

LOBBY

ADMIN

SUPPORT

139C

CHIELF OF

STATE

OFFICE

ADMIN.

ASSISTANT

OFFICE

STAIR HALL

139B

CL.

139A

STORAGE

140A

CL.

140B

OFFICE

142A

CUBICALS

CORR.

163Z

OFFICE

CLOSET

140C

CONFERENCE

ROOM

PUBLIC

AFFAIRS

CORR.

OFFICE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .A

R C

H .B

.rv t

-0 3-

5:

:4

01GI301

INFECTION CONTROL PLAN & INTERIM LIFE

SAFETY - FIRST FLOOR

620-22-700

06/27/2025 M. Perkins S POLLARD

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

# Revisions: Date:

1 ADDENDUM #1 03/27/2026

1/8" = 1'-0"F1

INFECTION CONTROL PLAN & INTERIM

LIFE SAFETY - FIRST FLOOR

PATH OF TRAVEL SCHEDULE - FIRST FLOOR

Mark From Room To Room Type of Travel Path Length

LEVEL 01

(P-o-T) Distance to Exits

E1 TELECOM ROOM 122 STAIR HALL 2 120 (P-o-T) Distance to Exits 80' - 3"

1 TEMPORARY CONSTRUCTION BARRIER DOOR WITH

CLOSER AND LATCH AND WALK OFF MATS

2 STAIRS ARE TO REMAIN OPERATIONAL AT ALL TIMES

FOR EMERGENCY EGRESS ONLY. THEY ARE NOT TO BE

USED FOR ANY CONSTRUCTION ACTIVITY.

3 ELEVATORS ARE TO REMAIN OPERATIONAL AT ALL

TIMES

A

ONE ELEVATOR TO BE DESIGNATED FOR CONTRACTOR

USE. CONTRACTOR TO PROTECT / REPAIR ALL FINISHES

AND FOLLOW PROPER ICRA REMOVAL PROTOCOLS FOR

ANY MATERIALS REMOVED FROM SITE THROUGH

ELEVATOR

4 DEBRIS REMOVAL PATH TO EXTERIOR - COORDINATE

REMOVAL OF MATERIALS ON THIS FLOOR WITH

ASBESTOS REPORT AND PLAN

5 REMOVE EXISTING WINDOW, AC UNIT AND METAL

SUPPORT FRAME. PROVIDE TEMPORARY INFILL.

6 SOLID GRAY HATCH DENOTES LIMITED WORK AREA -

SEE MEP AND TELECOM DRAWINGS FOR CABLING

SCOPE, TYP.

7 MAINTAIN EXIT PATHWAYS FOR OCCUPANTS AT ALL

TIMES

8 COORDINATE TEMPORARY HEPA EXHAUST ROUTING

OUT OF BUILDING - MAINTAIN 25 FEET MINIMUM FROM

INTAKES, OPERABLE WINDOWS, AND ENTRANCES.

PROVIDE BLOCK-OFF PANELS IN EXISTING WINDOWS

FOR DISCHARGE, TYP.

9 TEMPORARY CONSTRUCTION BARRIER

10 ANTEROOM - SEE INFECTION CONTROL & INTERIM LIFE

SAFETY DETAILS

NOTE:

DEBRIS REMOVAL:

COORDINATE REMOVAL OF MATERIALS ON THIS FLOOR WITH

ASBESTOS REPORT AND PLAN.

CONFIRM WITH COR FOR FINAL PLAN AND PROCEDURE OF

MATERIAL REMOVAL WITH ANTEROOMS, HEPA FILTRATION, ICRA

PROTOCOLS, AND ROUTE THRU OCCUPIED SPACES; PRIOR TO

REMOVAL OF ANY MATERIALS.

SECURE STAIRWELLS FROM UNAUTHORIZED ENTRY DURING

CONSTRUCTION.

LIFE SAFETY:

NEW WORK DOES NOT CHANGE EXISTING SMOKE

COMPARTMENTS, EXIT PATHWAYS, OR EXITS.

AREA OCCUPANCIES

LEVEL Name Area SF

Occupancy Requirements

OL

Occupancy

(IBC) Occupancy (NFPA) OLF Fixed Seats

FIRST FLOOR EXISTING BUSINESS 18836 SF B Business 150 SF 0 126

INFECTION CONTROL/DUST CONTROL

EGRESS DOOR NON-TRANSFERRING

MULTI-SHEETED ADHESIVE FLOOR PADS

PATH OF DEMOLITION/TRASH

REMOVAL TRAVEL

CONSTRUCTION LIMIT LINE

NOT IN CONTRACT AREA

DEMOLITION

LASER PARTICLE COUNT LOCATION

LIFE SAFETY SYMBOLS

PATH OF TRAVEL

(FOR CUMULATIVE DISTANCES

REFER TO SCHEDULE)

EXIT LIGHTING

TM

FIRE EXTINGUISHER CABINET (FEC)

FIRE EXTINGUISHERS (FE)

FIRE HOSE CABINETS (FHC)

HEAT DETECTOR

SMOKE DETECTOR

DIRECTION OF EGRESS

APPLICABLE BUILDING CODES

2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL

FIRE ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD

FOR INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF

NFPA 5000 AND NFPA 900

2024 INTERNATIONAL MECHANICAL CODE (IPC)

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION

(OSHA) STANDARDS.

VA SEISMIC DESIGN REQUIREMENTS, H-18-8

2026 NATIONAL ELECTRICAL CODE (NEC)

2024 INTERNATIONAL PLUMBING CODE (IPC)

ASME BOILER AND PRESSURE VESSEL CODE

ASME CODE FOR PRESSURE PIPING

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS

(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN

GUIDE (PG-18-13)

BUILDING CODE REQUIREMENTS FOR REINFORCED

CONCRETE, AMERICAN CONCRETE INSTITUTE AND

COMMENTARY (ACI 318)

MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE

FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL

BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION

(AISC)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION

STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-

FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-

RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND

SUSTAINABLE BUILDINGS: MEMORANDUM OF

UNDERSTANDING (MOU)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL

ENVIRONMENTAL, ENERGY, AND TRANSPORTATION

MANAGEMENT

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.

STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00

AND 01 35 26 OF THE VA MASTER CONSTRUCTION

SPECIFICATION.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY –

ASHRAE STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE

170-2025, NON-MEDICAL SPACES - ASHRAE 62.1-2025

SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE

STANDARD 15–2024

2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED

BY VA STANDARDS

UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE

STANDARD OR CODE SHALL BE USED

APPLICABLE BUILDING GUIDES

VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)

BUILDING CODE:

CONSTRUCTION TYPE:

TYPE II (222) PER NFPA 220, Chapter 4

TYPE OF BUILDING REHABILITATION: MODIFICATION, CHAPTER 43.

FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)

FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING

ELEMENTS:

STRUCTURAL FRAME 2 HOURS

NON-BEARING WALLS 0 HOURS

BEARING WALLS 2 HOURS

FLOORS 2 HOURS

ROOFS/ CEILINGS 1 HOURS

FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)

FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY

FUNCTION:

ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)

SMOKE COMPARTMENTS 1/2 HOUR

SOILED UTILITY ROOMS 1 HOUR

VERTICAL SHAFTS / STAIRS 2 HOURS

MEDICAL GAS / HAZARDOUS 1 HOUR

STORAGE

CLASSIFICATION OF OCCUPANCY:

EXISTING: BUSINESS Occupancy per Chapter 39

39.1.1.6 Where construction, alteration, or demolition operations are conducted, the provisions of 4.6.10.2 shall apply

39.1.2 Business occupancies shall include all buildings and structures or parts thereof with occupancy defined in 6.1.11

BUILDING OCCUPANCY TYPE:

EXISTING - BUSINESS OCCUPANCY

6.1.14.1.3 Where incidental to another occupant, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:

(1) Mercantile, BUSINESS, industrial, or storage use

6.1.14.3 Mixed Occupancies

6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.

Table 6.1.14.4.1 (a) - separation of occupancies - 2 Hr between Health Care and Business

6.2 Hazard of Contents.

6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or structure, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.

EXIT ACCESS TRAVEL DISTANCE:

39.2.6.2 The travel distance between any point in a room and an exit shall not exceed 200 ft.

39.2.6.3 The maximum travel distance...shall not exceed 300 ft in buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7.

BUSINESS OCCUPANCY; PROTECTED = 300'-0"

OCCUPANT LOAD:

39.1.7 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.

MEANS OF EGRESS:

39.2.3 Capacity of Means of Egress.

39.2.3.1 The capacity of any required means of egress shall be determined in accordance with the provisions Section 7.3.

39.2.3.2 The clear width of any corridor or passageway serving an occupant load of 50 or more shall not be less than 44 in. (1120 mm).

39.2.4 Number of Means of Egress.

39.2.4.1 Means of egress shall comply with all of the following: except as permitted by 39.2.4.2-6

1) the number of means of egress shall be in accordance with section 7.4

2) not less than two separate exits shall be provided on every story.

3) Not less than two separate exits shall be accessible from every part of every story.

39.2.5.3 In building protected throughout by and approved supervised automatic sprinkler system, Dead-end corridors shall not exceed 50 ft.

PROTECTION OF VERTICAL OPENINGS:

39.3.1 Protection of Vertical Openings.

39.3.1.1 Any vertical opening shall be enclosed or protected in accordance with Section 8.6, unless otherwise permitted.

PROTECTION FROM HAZARDS:

39.3.2 Protection from Hazards.

39.3.2.1 Hazardous Areas - Any hazardous areas shall be protected in accordance with Section 8.7

39.3.2.2 The following areas shall be considered hazardous areas and shall be protected by fire barriers having a minimum 1-hour fire resistance rating in accordance with Section 8.3:

(1) Boilder and fuel-fired heater rooms

(2) Central/bulk laundries larger than 100 ft2

(3) Paint Shops

(4) Physical plant maintenance shops

(5) Rooms with soiled linen in volume exceeding 64 gal

(6) Rooms with collected trashed in volume exceeding 64 gal.

(7) Storage rooms larger than 100 ft2 and storing combustible material

The following areas shall be considered hazardous areas and shall be protected by smoke partitions in accordance with Section 8.4:

(1) Laboratories employing flammable or combustible materials in quantities less than those that would be considered a severe hazard.

(2) Storage rooms larger than 50 ft2 but not exceeding 100 ft2 and storing combustible material.

39.3.2.5 Medical Gas. Medical gas storage shall be in accordance with Section 8.7 and the provisions of NFPA 99, Health Care Facilities Code, applicable to operation, maintenance, and testing.

39.3.5 Portable fire extinguishers shall be provided in all health care occupancies facilities in accordance with Section 9.9.

PARKING SUMMARY:

NO ADDITIONAL PARKING ADDED

WIDTH PROVIDEDP: XX"

R: XX" WIDTH REQUIRED

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

X - XX'

# ICRA SYMBOLSKEYNOTES

1 4

3A

E1 ▬ 81.1'

FEC

STAIR HALL

CORR.

245Z

CORR.

244Z

TELECOM

ROOM

ELEVATOR

BANK

ELEV

ELEVATOR

LOBBY

247Z

OFFICE

MI

N.

5'- 0"

C

LR

18689 SF

EXISTING BUSINESS -

FILE ROOM

213A

FILE ROOM

TLT

VACANT

HSKP

M.B.

211A

211B

VACANT

VACANT

FILE ROOM

209A209B

VC

209C

CL.

206A

FILE ROOM

TLT

215C

VACANT

VACANT

VACANT

POLICE AND

SECURITY

STORAGE

SUPPORT

OFFICE

VACANT

OFFICE

OFFICE

203 OFFICE

VACANT

STORAGE

246A

TLT

246B ENTRY

STAIR HALL

STORAGE

STAFF

TOILET

222A

SUPERVISORS

OFFICE

222B

STAFF

OFFICE

UTILITY

TLT

TLT

226A

P.S.

225A

CONFERENCE

ROOM

OFFICE

OFFICE

CORR.

250Z

CORR.

248Z

OFFICE

OFFICE

OFFICE

STOR. 1

STOR. 2

WAITING

ROOM

STAFF

LOUNGE

STAIR HALL

229A

VACANT

VACANT

HSKP

M.B.

233A

SHOWERS

235A

STOR.

235B

TLT

H.A.S.

OFFICES

FILE ROOM

231A

FILE ROOM

ELEC. CL.

223B

CL.

223A

CORR.

249Z

LAVATORIES

235C

TLTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .A

R C

H .B

.rv t

-0 3-

5:

:4

01GI302

INFECTION CONTROL PLAN & INTERIM LIFE

SAFETY - SECOND FLOOR

620-22-700

06/27/2025 M. Perkins S POLLARD

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

# Revisions: Date:

1 ADDENDUM #1 03/27/2026

1/8" = 1'-0"F1

INFECTION CONTROL PLAN & INTERIM

LIFE SAFETY - SECOND FLOOR

PATH OF TRAVEL SCHEDULE - SECOND FLOOR

Mark From Room To Room Type of Travel Path Length

LEVEL 02

(P-o-T) Distance to Exits

E1 TELECOM ROOM 218 STAIR HALL 2 215 (P-o-T) Distance to Exits 81' - 1"

1 TEMPORARY CONSTRUCTION BARRIER DOOR WITH

CLOSER AND LATCH AND WALK OFF MATS

2 STAIRS ARE TO REMAIN OPERATIONAL AT ALL TIMES

FOR EMERGENCY EGRESS ONLY. THEY ARE NOT TO

BE USED FOR ANY CONSTRUCTION ACTIVITY.

3 ELEVATORS ARE TO REMAIN OPERATIONAL AT ALL

TIMES

3A ONE ELEVATOR TO BE DESIGNATED FOR

CONTRACTOR USE. CONTRACTOR TO PROTECT /

REPAIR ALL FINISHES AND FOLLOW PROPER ICRA

REMOVAL PROTOCOLS FOR ANY MATERIALS

REMOVED FROM SITE THROUGH ELEVATOR

4 DEBRIS REMOVAL PATH TO EXTERIOR -

COORDINATE REMOVAL OF MATERIALS ON THIS

FLOOR WITH ASBESTOS REPORT AND PLAN

5 REMOVE EXISTING WINDOW, AC UNIT AND METAL

SUPPORT FRAME. PROVIDE TEMPORARY INFILL.

6 SOLID GRAY HATCH DENOTES LIMITED WORK AREA -

SEE MEP AND TELECOM DRAWINGS FOR CABLING

SCOPE, TYP.

7 MAINTAIN EXIT PATHWAYS FOR OCCUPANTS AT ALL

TIMES

8 COORDINATE TEMPORARY HEPA EXHAUST ROUTING

OUT OF BUILDING - MAINTAIN 25 FEET MINIMUM

FROM INTAKES, OPERABLE WINDOWS, AND

ENTRANCES. PROVIDE BLOCK-OFF PANELS IN

EXISTING WINDOWS FOR DISCHARGE, TYP.

9 TEMPORARY CONSTRUCTION BARRIER

10 ANTEROOM - SEE INFECTION CONTROL & INTERIM

LIFE SAFETY DETAILS

NOTE:

DEBRIS REMOVAL:

COORDINATE REMOVAL OF MATERIALS ON THIS FLOOR WITH

ASBESTOS REPORT AND PLAN.

CONFIRM WITH COR FOR FINAL PLAN AND PROCEDURE OF

MATERIAL REMOVAL WITH ANTEROOMS, HEPA FILTRATION, ICRA

PROTOCOLS, AND ROUTE THRU OCCUPIED SPACES; PRIOR TO

REMOVAL OF ANY MATERIALS.

SECURE STAIRWELLS FROM UNAUTHORIZED ENTRY DURING

CONSTRUCTION.

LIFE SAFETY:

NEW WORK DOES NOT CHANGE EXISTING SMOKE

COMPARTMENTS, EXIT PATHWAYS, OR EXITS.

AREA OCCUPANCIES

LEVEL Name Area SF

Occupancy Requirements

OL

Occupancy

(IBC) Occupancy (NFPA) OLF Fixed Seats

SECOND FLOOR EXISTING BUSINESS 18689 SF B Business 150 SF 0 125

INFECTION CONTROL/DUST CONTROL

EGRESS DOOR NON-TRANSFERRING

MULTI-SHEETED ADHESIVE FLOOR PADS

PATH OF DEMOLITION/TRASH

REMOVAL TRAVEL

CONSTRUCTION LIMIT LINE

NOT IN CONTRACT AREA

DEMOLITION

LASER PARTICLE COUNT LOCATION

LIFE SAFETY SYMBOLS

PATH OF TRAVEL

(FOR CUMULATIVE DISTANCES

REFER TO SCHEDULE)

EXIT LIGHTING

TM

FIRE EXTINGUISHER CABINET (FEC)

FIRE EXTINGUISHERS (FE)

FIRE HOSE CABINETS (FHC)

HEAT DETECTOR

SMOKE DETECTOR

DIRECTION OF EGRESS

APPLICABLE BUILDING CODES

2024 NFPA 101 LIFE SAFETY CODE & 2025 NFPA 72 NATIONAL

FIRE ALARM AND SIGNALING CODE & 2025 NFPA 13 STANDARD

FOR INSTALLATION OF SPRINKLER SYSTEMS. EXCEPTION OF

NFPA 5000 AND NFPA 900

2024 INTERNATIONAL MECHANICAL CODE (IPC)

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION

(OSHA) STANDARDS.

VA SEISMIC DESIGN REQUIREMENTS, H-18-8

2026 NATIONAL ELECTRICAL CODE (NEC)

2024 INTERNATIONAL PLUMBING CODE (IPC)

ASME BOILER AND PRESSURE VESSEL CODE

ASME CODE FOR PRESSURE PIPING

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS

(ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN

GUIDE (PG-18-13)

BUILDING CODE REQUIREMENTS FOR REINFORCED

CONCRETE, AMERICAN CONCRETE INSTITUTE AND

COMMENTARY (ACI 318)

MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE

FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL

BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION

(AISC)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION

STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-

FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-

RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND

SUSTAINABLE BUILDINGS: MEMORANDUM OF

UNDERSTANDING (MOU)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL

ENVIRONMENTAL, ENERGY, AND TRANSPORTATION

MANAGEMENT

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS.

STATED IN THE GENERAL REQUIREMENTS SECTION 01 00 00

AND 01 35 26 OF THE VA MASTER CONSTRUCTION

SPECIFICATION.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY –

ASHRAE STANDARD 62.1-2025; MEDICAL SPACES - ASHRAE

170-2025, NON-MEDICAL SPACES - ASHRAE 62.1-2025

SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE

STANDARD 15–2024

2024 INTERNATIONAL BUILDING CODE (IBC) WHERE DIRECTED

BY VA STANDARDS

UNLESS NOTED OTHERWISE, CURRENT EDITION OF APPLICABLE

STANDARD OR CODE SHALL BE USED

APPLICABLE BUILDING GUIDES

VA FIRE PROTECTION DESIGN GUIDE, 9TH EDITION (2023)

BUILDING CODE:

CONSTRUCTION TYPE:

TYPE II (222) PER NFPA 220, Chapter 4

TYPE OF BUILDING REHABILITATION: MODIFICATION, CHAPTER 43.

FIRE RESISTIVE CONSTRUCTION (NFPA 220 Table 4.1.1)

FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING

ELEMENTS:

STRUCTURAL FRAME 2 HOURS

NON-BEARING WALLS 0 HOURS

BEARING WALLS 2 HOURS

FLOORS 2 HOURS

ROOFS/ CEILINGS 1 HOURS

FIRE RESISTIVE CONSTRUCTION FOR OCCUPANCY (VA & NFPA 101)

FIRE RESISTANCE RATING REQUIREMENTS FOR SPACES BY

FUNCTION:

ELECTRICAL CLOSETS (DEPENDENT ON EQUIPMENT SIZE)

SMOKE COMPARTMENTS 1/2 HOUR

SOILED UTILITY ROOMS 1 HOUR

VERTICAL SHAFTS / STAIRS 2 HOURS

MEDICAL GAS / HAZARDOUS 1 HOUR

STORAGE

CLASSIFICATION OF OCCUPANCY:

EXISTING: BUSINESS Occupancy per Chapter 39

39.1.1.6 Where construction, alteration, or demolition operations are conducted, the provisions of 4.6.10.2 shall apply

39.1.2 Business occupancies shall include all buildings and structures or parts thereof with occupancy defined in 6.1.11

BUILDING OCCUPANCY TYPE:

EXISTING - BUSINESS OCCUPANCY

6.1.14.1.3 Where incidental to another occupant, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy:

(1) Mercantile, BUSINESS, industrial, or storage use

6.1.14.3 Mixed Occupancies

6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.

Table 6.1.14.4.1 (a) - separation of occupancies - 2 Hr between Health Care and Business

6.2 Hazard of Contents.

6.2.1.3 For the purpose of this Code, where difference degrees of hazard of contents exist in different parts of a building or structure, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.

EXIT ACCESS TRAVEL DISTANCE:

39.2.6.2 The travel distance between any point in a room and an exit shall not exceed 200 ft.

39.2.6.3 The maximum travel distance...shall not exceed 300 ft in buildings protected throughout by an approved automatic sprinkler system in accordance with Section 9.7.

BUSINESS OCCUPANCY; PROTECTED = 300'-0"

OCCUPANT LOAD:

39.1.7 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.

MEANS OF EGRESS:

39.2.3 Capacity of Means of Egress.

39.2.3.1 The capacity of any required means of egress shall be determined in accordance with the provisions Section 7.3.

39.2.3.2 The clear width of any corridor or passageway serving an occupant load of 50 or more shall not be less than 44 in. (1120 mm).

39.2.4 Number of Means of Egress.

39.2.4.1 Means of egress shall comply with all of the following: except as permitted by 39.2.4.2-6

1) the number of means of egress shall be in accordance with section 7.4

2) not less than two separate exits shall be provided on every story.

3) Not less than two separate exits shall be accessible from every part of every story.

39.2.5.3 In building protected throughout by and approved supervised automatic sprinkler system, Dead-end corridors shall not exceed 50 ft.

PROTECTION OF VERTICAL OPENINGS:

39.3.1 Protection of Vertical Openings.

39.3.1.1 Any vertical opening shall be enclosed or protected in accordance with Section 8.6, unless otherwise permitted.

PROTECTION FROM HAZARDS:

39.3.2 Protection from Hazards.

39.3.2.1 Hazardous Areas - Any hazardous areas shall be protected in accordance with Section 8.7

39.3.2.2 The following areas shall be considered hazardous areas and shall be protected by fire barriers having a minimum 1-hour fire resistance rating in accordance with Section 8.3:

(1) Boilder and fuel-fired heater rooms

(2) Central/bulk laundries larger than 100 ft2

(3) Paint Shops

(4) Physical plant maintenance shops

(5) Rooms with soiled linen in volume exceeding 64 gal

(6) Rooms with collected trashed in volume exceeding 64 gal.

(7) Storage rooms larger than 100 ft2 and storing combustible material

The following areas shall be considered hazardous areas and shall be protected by smoke partitions in accordance with Section 8.4:

(1) Laboratories employing flammable or combustible materials in quantities less than those that would be considered a severe hazard.

(2) Storage rooms larger than 50 ft2 but not exceeding 100 ft2 and storing combustible material.

39.3.2.5 Medical Gas. Medical gas storage shall be in accordance with Section 8.7 and the provisions of NFPA 99, Health Care Facilities Code, applicable to operation, maintenance, and testing.

39.3.5 Portable fire extinguishers shall be provided in all health care occupancies facilities in accordance with Section 9.9.

PARKING SUMMARY:

NO ADDITIONAL PARKING ADDED

WIDTH PROVIDEDP: XX"

R: XX" WIDTH REQUIRED

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

X - XX'

# ICRA SYMBOLSKEYNOTES

8 2

3A

MI

N.

5'- 0"

C

LR

FEC

TELECOM

ROOM

CORR.

333Z

ELEVATOR

BANK

ELEV

STAIR HALL

ELEVATOR

LOBBY

334Z

E1 ▬ 109.9'

7486 SF

EXISTING BUSINESS -

OFFICE

STAFF

LOUNGE

STORAGE

CL.

310A

TLT

CL.

310B

OFFICE

OFFICE

OFFICE

CL

303A

OFFICE

OFFICE

TLT

332A

TLT

301A

OFFICE

OFFICE

CL.

OFFICE

SUPPLY

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

ROOM

322B

E.M.S.

CLOSET

SUPPLY

CLOSET

ELEC.

Room

CL.

319A

STAIR HALL

325A

ATTIC

325B

CL.

311B

TLT

311A

OFFICE

OFFICE

CORR.

335Z

OFFICE

OFFICE

OFFICE

OFFICE

EMPLOYEE

RECORDS

PAYROLL

ATTIC

306A

CL.

320A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

Au to de sk

D oc s:

//6

-2

2-

M on tro se V

AM

C

E H

R M

IU

/6

-2

2-

0.

M on tro se .E

H R

M .A

R C

H .B

.rv t

-0 3-

5:

:4

01GI303

INFECTION CONTROL PLAN & INTERIM LIFE

SAFETY - THIRD FLOOR

620-22-700

06/27/2025 M. Perkins S POLLARD

ISSUED FOR

CONSTRUCTION

(EHRM) INFRASTRUCTURE

UPGRADES

2094 Albany Post Road, Montrose, NY 10548

# Revisions: Date:

1 ADDENDUM #1 03/27/2026

1/8" = 1'-0"F1

INFECTION CONTROL PLAN & INTERIM

LIFE SAFETY - THIRD FLOOR

PATH OF TRAVEL SCHEDULE - THIRD FLOOR

Mark From Room To Room Type of Travel Path Length

LEVEL 03

(P-o-T) Distance to Exits

E1 TELECOM ROOM 307 STAIR HALL 1 319 (P-o-T) Distance to Exits 109' - 11"

1 TEMPORARY CONSTRUCTION BARRIER DOOR WITH

CLOSER AND LATCH AND WALK OFF MATS

2 STAIRS ARE TO REMAIN OPERATIONAL AT ALL TIMES

FOR EMERGENCY EGRESS ONLY. THEY ARE NOT TO

BE USED FOR ANY CONSTRUCTION ACTIVITY.

3 ELEVATORS ARE TO REMAIN OPERATIONAL AT ALL

TIMES

3A ONE ELEVATOR TO BE DESIGNATED FOR

CONTRACTOR USE. CONTRACTOR TO PROTECT /

REPAIR ALL FINISHES AND FOLLOW PROPER ICRA

REMOVAL PROTOCOLS FOR ANY MATERIALS

REMOVED FROM SITE THROUGH ELEVATOR

4 DEBRIS REMOVAL PATH TO EXTERIOR -

COORDINATE REMOVAL OF MATERIALS ON THIS

FLOOR WITH ASBESTOS REPORT AND PLAN

5 REMOVE EXISTING WINDOW, AC UNIT AND METAL

SUPPORT FRAME. PROVIDE TEMPORARY INFILL.

6 SOLID GRAY HATCH DENOTES LIMITED WORK AREA -

SEE MEP AND TELECOM DRAWINGS FOR CABLING

SCOPE, TYP.

7 MAINTAIN EXIT PATHWAYS FOR OCCUPANTS AT ALL

TIMES

8 COORDINATE TEMPORARY HEPA EXHAUST ROUTING

OUT OF BUILDING - MAINTAIN 25 FEET MINIMUM

FROM INTAKES, OPERABLE WINDOWS, AND

ENTRANCES. PROVIDE BLOCK-OFF PANELS IN

EXISTING WINDOWS FOR DISCHARGE, TYP.

9 TEMPORARY CONSTRUCTION BARRIER

10…