The RFP seeks to construct the remaining work at the Manhattan VA Medical Center campus, including details on the 1-hour and 2-hour rated wall and roof deck assemblies, firestopping requirements, electrical conduit and sprinkler pipe penetrations, and vehicle height restriction signage. The RFP also provides technical specifications, drawings, and UL design systems for the required construction work. Responses to this solicitation, numbered QSE-36C10F24R50018, are due on a specific future date not provided in the document. The incumbent contractor is not specified.
View the file
Other files
Show 40 more
Latest 50 of 281 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hilti Firestop Systems
System No. W-L-3396
SECTION A-A
W L
Page: 1 of 2
3. Firestop Device* — Firestop device consisting of a steel collar with plug to be centered over opening and mounted to face of gypsum board on both sides of wall. Each flange of collar is secured to wall with No. 10 by 1-1/2 in. (38 mm) steel laminating screw and min 9/16 in. (15 mm) diam steel washer through prepunched hole in flange. As an alternate, min 3/16 in. (4.8 mm) diam by 2-1/2 in. (64 mm) long steel toggle bolts in conjunction with min 9/16 in. (15 mm) diam steel washers may be used. For openings with cables, plug within collar cut to fit tightly around the cable bundle. For blank openings (no cables), the hourly F and FH Ratings of the firestop system are equal to the hourly rating of the wall in which it is installed.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-CC 4" Firestop Cable Collar L Ratings apply to blank the openings only per indicated in Table below.
A
A
Page: 2 of 2
C
CL
ASS I F IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 23, 2015
W L
1A 1B
2 3
4. Fill, Void or Cavity Material* (Optional, Not Shown) — Fill material applied to fill interstices between and around the cable bundle at both sides of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant, CP 618 Putty
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
System No. W-L-3396
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1)
T Ratings - 0, 1 and 2 Hr (See Items 2 and 3) FT Ratings - 0, 1 and 2 Hr (See Items 2 and 3)
L Rating At Ambient - See Item 3 FH Ratings - 1 and 2 Hr (See Item 1)
L Rating At 400F - See Item 3 FTH Ratings - 0, 1 and 2 Hr (See Items 2 and 3)
L Rating At Ambient - See Item 3
L Rating At 400F - See Item 3
Opening CFM (per device) CFM/Sq Ft Opening
Ambient 400F Ambient 400F Blank Opening Only (no cables) Less Than 1 Less Than 1 Less Than 1 4 Max 100% visual fill with Cat 5 and/or Cat 6 cables 1.2 Less Than 1 13.2 8.9
Hilti Firestop Systems
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 23, 2015
1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs — Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* — Nom 5/8 in. (16 mm) thick gypsum board as specified in the individual Wall and Partition Design. Opening in gypsum board to be max 4 in. (102 mm) diam.
The hourly F and FH Ratings of the firestop system are dependent upon the hourly rating of the wall in which it is installed.
1A. Sleeve — (Not Shown, Required) - Nom 4 in. (102 mm) diam (or smaller) sleeve friction fit into wall opening, flush with both wall surfaces.
The following types of sleeves may be used: Schedule 5 (or heavier) steel pipe, min 28 ga steel sleeve, or Schedule 40 solid or cellular core polyvinyl chloride (PVC).
2. Cables — Cables may be installed within opening for a 0 to 100 percent visual fill. When PVC sleeve (Item 1A) is used, the aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. Cables to be tightly bundled and rigidly supported on both sides of wall assembly. Any combination of the following types of cables may be used:
A. Max 100 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation.
B. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.
C. Max 4/0 AWG Type RHH ground cable.
D. Max 4 pr No. 22 AWG Cat 5 or Cat 6 computer cables.
E. Max RG 6/U coaxial cable with fluorinated ethylene insulation and jacketing.
F. Fiber optic cable with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation having a max diam of 1/2 in. (13 mm).
G. Max 3/C No 12 AWG MC Cable.
For opening with cables, when the hourly rating of the wall assembly is 1 hr, the T, FT and FTH Ratings are 0 hr. For opening with cables, when the hourly rating of the wall assembly is 2 hr, the T, FT and FTH Ratings are 1 hr.
Hilti Firestop Systems Hilti Firestop Systems Hilti Firestop Systems Hilti Firestop Systems
System No. W-L-3395
SECTION B-B
W L
Page: 1 of 4
1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs — Wall framing shall consist of steel channel studs. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* — Nom 5/8 in. (16 mm) thick gypsum board as specified in the individual Wall and Partition Design. Maximum size of opening in gypsum board is dependent on the mounting of the gangplate firestop device (Item 2). Openings for gangplates that are surface mounted to the gypsum board may be oriented vertically or horizontally. Openings for gangplates that are stud mounted direct to the wall studs prior to gypsum board layers are oriented horizontally. Maximum opening sizes are specified in Table below.
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
March 21, 2017
AA
Page: 2 of 4 Page: 3 of 4 Page: 4 of 4
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-SL SK 4" Firestop Retrofit Sleeve 3D. Firestop Device* — Firestop device consists of a corrugated steel tube with an inner plastic housing, intumescent material rings and twisted inner fabric smoke seal. The device flanges are to be spun counterclockwise and removed since they are not used. Device tube slid into gang plate port opening and centered within wall such that ends of device tube project an approximate equal distance from the gang plate on each side of wall. The two integral screws within the flange of the gang plate port at each side of wall are tightened to firmly bear against the device sleeve to retain it in position. The inner fabric seal shall be twisted to completely close off any unused opening within the device.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 653 4" Speed Sleeve
4 Fill, Void or Cavity Material* - Plug — Plugs are required to be used with the CFS-SL RK and SK firestop devices (Items 3B and 3C). Nom 4" diam plug friction fit within the device sleeve flush with each end of the device on both sides of wall. Plug cut to fit around the cable bundle (if used) and installed tightly within the device sleeve.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-PL Firestop Plug 4"
5. Cables — Within the loading area for each firestop device (Items 3B through 3D), a tightly bundled cable may be installed. The aggregate cross-sectional area of cables shall be min 0 to max 60 percent fill for each CFS-SL RK and CFS-SL SK firestop device (Items 3B and 3C). For the CP 653 Speed Sleeve firestop device (Item 3D), the cables can be used for a 0 to 100 percent visual fill. Cables to be rigidly supported on both sides of wall assembly. Any combination of the following types of cables may be used:
A. Max 100 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation.
B. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.
C. Max 4/0 AWG Type RHH ground cable.
D. Max 4 pr No. 22 AWG Cat 5 or Cat 6 computer cables.
E. Max RG 6/U coaxial cable with fluorinated ethylene insulation and jacketing.
F. Fiber optic cable with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation having a max diam of 1/2 in. (13 mm).
G. Max 3/C No 12 AWG MC Cable.
H. Through Penetrating Product* — Any Cables, Metal-Clad Cable+ or Armored Cable+ currently Classified under the Through Penetrating
Products category.
See Through Penetrating Product (XHLY) category in the Fire Resistance Directory for names of manufacturers.
I. Max 3/C No 12 AWG MC Cable.
The L Ratings are dependent on the type and number of devices within the gang plate and the cable type and fill. For devices with cable bundle, the cable bundle shall be nominally centered within the device to attain the L Ratings. The L Ratings in CFM per GP device (Table 1) and in CFM per ft2 of opening (Table 2) are specified below:
Table 1 - CFM per CFS-SL GP Gangplate Device at Ambient and 400F
Table 2 - CFM per FT2 of Opening at Ambient and 400FC
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
W L
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
March 21, 2017
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings - 1 and 2 Hr (See Items 1 and 2) F Ratings - 1 and 2 Hr (See Items 1 and 2)
T Rating - 1/4 Hr FT Rating - 1/4 Hr
L Rating At Ambient - See Item 5 FH Ratings - 1 and 2 Hr (See Items 1 and 2)
L Rating At 400F - See Item 5 FTH Ratings - 1/4 Hr
L Rating At Ambient - See Item 5
L Rating At 400F - See Item 5
BB
SECTION A-A
2 3D 5
2 5 3B 3C 4
1A1B 3B
3C
2 5
1B 1A
3D
Firestop Device (Item 2) Maximum Opening Size, in. (mm) Gangplate Mounting
Surface Mounted Stud Mounted
24" Gangplate :
Single 20-1/2" x 5-1/2" (521 x 140) 23" x 6-3/4" (584 x 171)
Double (Stacked) 20-1/2" x 13-1/4" (521 x 337) 23" x 14-1/4" (584 x 362)
16" Gangplate :
Single 15" x 5-1/2" (381 x 140) 15-3/16" x 6-3/4" (386 x 171)
Double (Stacked) 15" x 13-1/4" (381 x 337) 15-3/16" x 14-1/4" (386 x 362)
The hourly F and FH Ratings of the firestop system are dependent upon the hourly rating of the wall in which it is installed.
2. Firestop Device* — The firestop device consists of a steel plate sandwich construction with three (16" device size) or four (24" device size) circular opening ports which are each nom 4 in. (102 mm) diam. The firestop device is intended to be oriented vertically or horizontally and mounted to the face of the opening on both sides of wall. The 16" and 24" firestop devices when oriented horizontally are attached to the 16 in.
(406 mm) and 24 in. (610 mm), respectively, center to center spaced wall studs at each side of opening, over the gypsum board. As an option, up to two devices may be installed adjacent to each other with a nom 13/16 in. (2 cm) overlap to protect larger sized openings (see Item 1B, double device). As an option, single and double 16" and 24" gang plates may be attached directly against the studs prior to installation of the gypsum board layers. When 16" gang plate is installed horizontally in 24" stud cavity, attachment of plate to wall studs is optional. As an option, two devices may be installed end to end in adjacent stud cavities, over the gypsum board layers or directly attached to the wall studs when installed in accordance with the Hilti Installation Instructions and min one layer of gypsum board each side of wall is continuous across the two stud cavities. Each device shall be secured to gypsum board with min No. 10 by 1-1/2 in. (38 mm) steel drywall screws through prepunched holes around periphery of steel device plates; min three (16" gang plate) or four (24" gang plate) screws are used at each long dimension and three screws at each end. When device is secured direct to studs prior to installation of gypsum board layers, the fasteners along each long dimension of opening are spaced max 2-1/2 in. (64 mm) from corners and max 6 in. (152 mm) on center unless otherwise noted in Hilti Installation Instructions. Min screw length is 3/4 in. (19 mm) where device is secured direct to studs and at the overlapping plate to plate joint for double devices. The device shall be installed in accordance with the accompanying installation instructions. When the hourly rating of the wall assembly is 1 hr, blank gang plates (no cables) may be installed vertically or horizontally for single gang plate openings only, and double gang plates are limited to installation horizontally with fasteners at ends of plates penetrating into wall studs.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-SL GP 16" and 24" Firestop Gangplate
3. Firestop Device — Within each circular opening port of the CFS-SL GP firestop gang plates (Item 2), one of the following firestop devices shall be installed. Any combination of these firestop devices may be used within each gang plate.
3A. Firestop Device* — Rectangular steel plate designed to close port openings with no penetrants. Plate is field installed in accordance with Hilti
Installation Instructions. Flanges of gang plate over port opening are removed by loosening GP nuts, the steel plate cap installed with prepunched holes aligned with GP fasteners, and the flanges of GP then reinstalled and nuts reinstalled to tighten the plates in position.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-SL GP CAP Firestop Gangplate CAP 3B. Firestop Device* — Firestop device consists of a corrugated steel tube. The device flanges are removed by spinning counterclockwise and are not used. Device tube slid into gang plate port opening and centered within wall such that ends of device tube project an approximate equal distance from the gang plate on each side of wall. The two integral screws within the flange of the gang plate port at each side of wall are tightened to firmly bear against the device sleeve to retain it in position. Device is designed to allow installation before or after the cable penetrants (if employed) are in place. Device is used in combination with the firestop plugs described in Item 4.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-SL RK 4" Firestop Sleeve 3C. Firestop Device* — Firestop device consists of a corrugated steel tube. The device flanges are removed by spinning counterclockwise and are not used. Device tube slid into gang plate port opening and centered within wall such that ends of device tube project an approximate equal distance from the gang plate on each side of wall. The two integral screws within the flange of the gang plate port at each side of wall are tightened to firmly bear against the device sleeve to retain it in position. Device is used in combination with the firestop plugs described in Item 4.
W L
Type and Number of Devices in CFS-SL GP (CAP - Item 3A; Devices - Any combination of Items 3B through 3D except as noted)
Cap(S) Only Cap(S) and One Device
Cap(S) and Two Devices
Cap (Opt) and Three Devices Four Devices
Blank Opening (no cables): Less Than 1 1 2 2.5 3.5
Openings with any combination of Item 5 cables for max 33% aggregate fill in device types 3B and 3C, and/or max 100% visual cable fill in device type 3D
- 2 4 6 8
Cap(S) only Cap(S) and one CP 653 Device
(Item 3D)
Cap(S) and Two CP 653 Devices
(Item 3D)
Cap (Opt) and Three CP 653
Devices (ITEM 3D)
Four CP 653 Devices
(Item 3D)
Openings with max 100% visual cable fill with cable type 5D only and CP 653 only
- 1.5 3 4 5.5
Type and Number of Devices in CFS-SL GP (CAP - Item 3A; Devices - Any combination of Items 3B through 3D except as noted)
Cap(S) only Cap(S) and One Device
Cap(S) and Two Device
Cap(Opt) and Three Device Four Devices
Blank Opening (no cables) 1.2 1.3 2.6 3.2 4.5
Openings with any combination of Item 5 cables for max 33% aggregate fill in device types 3B and 3C, and/or max 100% visual cable fill in device type 3D.
- 2.6 5.1 7.7 10.2
Cap(S) only Cap(S) and One CP 653 Device
(Item 3D)
Cap(S) and Two CP 653 Ddevices
(Item 3D)
Cap (Opt) and Three CP 653
Devices (Item 3D)
Four CP 653 Devices
(Item 3D)
Openings with max 100% visual cable fill with cable type 5D only and CP 653 only
- 1.9 3.8 5.1 7.0
W L
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
March 21, 2017
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
March 21, 2017
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
Hilti Firestop Systems Hilti Firestop Systems
System No. W-L-3414
SECTION A-A
W L
Page: 1 of 2
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
October 14, 2015
A
Page: 2 of 2
1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 in. (51 mm) by 4 in. (102
mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (1219 cm) wide with square or tappered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Opening may be round, rectangular or irregular with a max diam or dimension of 1 in. (25 mm).
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
2. Cables — Single or tight bundle of cables to be installed within the opening. Aggregate cross-sectional area of cables in opening to have a visual fill of min 0% to max 100%. The annular space between the cable bundle and the periphery of the opening to be min 0 in. (point contact). Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types and sizes of cables may be used:
A. Max 3/C No. 8 AWG NM copper conductor cable (Romex) with PVC insulation and jacket.
B. Max 7/C-No. 12 AWG copper conductor control cable with PVC or XLPE insulation and jacket.
C. Max 100 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with PVC or plenum rated insulation and jacketing.
D. Max 4 pr No. 22 AWG (or smaller) Cat 5 or Cat 6 computer cables with PVC or plenum rated insulation and jacketing.
E. Type RG/U coaxial cable with fluorinated ethylene or PVC insulation and jacketing having a max outside diameter of ½ in. (13 mm).
F. Max 24 fiber optic cable with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation.
G. Through Penetrating Product* — Max two copper conductor No. 18 AWG (or smaller) Power or Non-Power Limited Fire Alarm Cable with or without a jacket under a metal armor.
AFC CABLE SYSTEMS INC
H. Maximum 3/C No. 10 AWG copper conductor metal-clad cable.
The hourly T, FT and FTH Ratings of the firestop system are dependent on cable type and hourly wall rating as specified in Table below.
C
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings — 1 and 2 Hr (See Item 1) F Ratings — 1 and 2 Hr (See Item 1)
T Ratings — 0, ½, 1 and 2 Hr (See Item 2) FT Ratings — 0, ½, 1 and 2 Hr (See Item 2)
L Rating at Ambient — Less than 1 CFM/Opening FH Ratings — 1 and 2 Hr (See Item 1)
L Rating at 400 F — Less than 1 CFM/Opening FTH Ratings — 0, ½, 1 and 2 Hr (See Item 2)
L Rating at Ambient — Less than 1 CFM/Opening
L Rating at 400 F — Less than 1 CFM/Opening
System No. W-L-3414
W L
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
October 14, 2015
Cable Type Hourly Wall Rating
Hourly T, FT and FTH Rating
None (Blank Opening) 1 and 2 1 and 2
A 1 and 2 1 and 2
B 1 0
2 1/2
C 1 0
2 1/2
D 1 and 2 1 and 2
E 1 and 2 1 and 2
F 1 and 2 1 and 2
G 1 and 2 1 and 2
H 1 and 2 1 and 2
3. Fill, Void or Cavity Material* — Nom 60 mm diam by 3 mm thick putty disc with one seam at radius. Paper-backer of disc to be removed and disc firmly pressed around the cable/cable bundle lapping nom 5 mm onto cables to completely cover opening and firmly pressed to lap onto the wall around periphery of opening. Disc seam to be firmly pressed and sealed tight, Disc to be installed at both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-D 1" Firestop Cable Disc
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
1B
1A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
ISSUED FOR
CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA NY Manhattan Campus
423 E 23RD Street, New York, NY 10010
630-600A
Project Director
Revisions: Date:
A/E:
AECOM
3101 WILSON BLVD, SUITE 900
ARLINGTON, VA. 22201
703-682-4900
WWW.AECOM.COM
Construction Document Refresh
1 & GEN PLTFRM
Key Plan
Balance of Work
9/12/2022
C-AE515
FIRESTOPPING DETAILS - 9
DZ JH
1. Refer to the following specifications for firestopping.
a. 07 84 00 Firestopping
b. 21 21 13 Wet-pipe Sprinkler Systems
c. 21 13 16 Dry-pipe Sprinkler Systems d.Division 22 00 00 Plumbing (all sections) e.Division 23 00 00 HVAC (all sections)
f. Division 26 00 00 Electrical (all sections)
g. 27 05 33 Raceways and Boxes for Communication Systems
h. 28 31 00 Fire Detection and Alarm
For Quality Control requirements, refer to the Quality Assurance portion of the specification.
2. Manufacturer's trade names and UL assembly used here-in are only to identify basis of design / level of performance requirements required.
Products of other manufacturer's equivalent to basis of design / performance requirements that meet requirements of the technical specification will be acceptable once submitted / approved as a shop drawing submittal.
3. Details shown are typical details and are not meant to be inclusive of all field conditions that may be present.
Contractor shall submit additional firestop system assemblies for penetrations through rated construction as required for review and approval.
4. Details shown are typical details.
Always refer to the listed system detail for complete system requirements. If field conditions do not match requirements of details, approved alternate details shall be utilized / submitted for review / approval. Design requirements, field conditions and dimensions need to be verified for compliance with the details, including but not limited to the following:
* Fire Rating (F-Rating)
* Leakage Rating (L-Rating)
* Water Rating (W-Rating)
* Annular Space
* Percent Fill
* Movement
* Type and thickness of fire-rated construction.
4. If alternate details matching the field conditions are not available, manufacturer's engineering judgment drawings are acceptable subject to approval by the Authority Having Jurisdiction (AHJ). Contact Hilti Inc. for alternative systems or Engineering Judgment (800-879-8000). Drawings shall follow the International Firestop Council (IFC) Guidelines for Evaluating Firestop Systems Engineering Judgments.
5. References:
* 2017 Underwriter's Laboratories
Fire Resistance Directory, Volumes 1 & 2.
* NFPA 101 Life Safety Code
* NFPA 70 – National Electric Code
* All governing local and regional building codes.
6. Systems C-AJ-3095, C-AJ-3216 and C-AJ-3283 are permitted for use at existing cables thru new construction only. All new cables passing thru new walls use system C-AJ-3285.
7. Firestop System installation must meet requirements of ASTM E-814 (UL 1479) tested assemblies that provide a fire rating equal or greater to that of construction being penetrated.
8. Systems W-L-5028, W-L-1054, W-L-1389, W-L-3396 and W-L-8079 are permitted for use at existing pipes and cables through new GWB construction only. All new pipes and cables through new GWB walls shall use W-L-2078, W-L-2128 and W-L-3334.
9. During construction all empty core holes through elevated floor slabs are required to be temporarily closed.
Provide Hilti CFS-PL Firestop Plug or Hilti CFS-BL Firestop Block /approved equal sized for core hole. Plugs are to be provided immediately after core hole has been created and be maintained until core is in-filled with it's intended penetrant.
10. All pipe and conduit through -slab penetration assemblies are required to have water barriers. Water barriers are not to be considered optional in any firestop system assembly.
11. All "new" pipe and "new" conduit rated through - penetration assemblies greater than 50mm (2") are required to have steel / metallic sleeves. Steel / metallic sleeves are not to be considered optional in any firestop system assembly.
12. All rated through-penetration assemblies shall be prominently labeled with a Hilti Firestop Label equipped with a QR code with the following information:
* Warning! - Do Not Disturb
* Through Penetration Firestop
System. Notify VAMC of any damage.
* UL System # * Product(s) used
* Hourly Rating (F-Rating)
* Installation Date
* Contractor's Name
FIRESTOPPING ASSEMBLY NOTES
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text F I R S T A V E N U E
AutoCAD SHX Text A S S E R L E V Y P L A C E
AutoCAD SHX Text E A S T 2 3 r d. S T R E E T
AutoCAD SHX Text
BLDG 3
AutoCAD SHX Text
BLDG 2
AutoCAD SHX Text
BLDG 4 / 5
AutoCAD SHX Text
E A S T 25 TH STREET
AutoCAD SHX Text
BLDG 1
AutoCAD SHX Text N
AutoCAD SHX Text
BLDG 6
Hilti Firestop Systems Hilti Firestop Systems
System No. W-L-5028
SECTION A-A
W L
Page: 1 of 2
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 27, 2015 Page: 2 of 2
W L
A
C
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
1B
1A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 27, 2015
System No. W-L-5028
1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 7-1/2 in.
(191 mm).
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrants — One metallic pipe or tubing to be centered within the firestop system. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 40 (or heavier) steel pipe.
B. Copper Tubing — Nom 2 in. (51 mm) diam (or smaller) Type L (or heavier) copper tubing.
C. Copper Pipe — Nom 2 in. (51 mm) diam (or smaller) Regular (or heavier) copper pipe.
3. Tube Insulation — Plastics+ — Min 1/2 in. (13 mm) to max 1 in. (25 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. An annular space of min 0 in. (point contact) to max 1-1/2 in. (38 mm) is required within the firestop system. The T, FT and FTH Ratings are 1 hr when the 1 in. (25 mm) thick tube insulation is used and 3/4 hr when the 3/4 in. (19 mm) thick tube insulation is used.
When tube insulation thickness is less than 3/4 in. (19 mm), the T, FT and FTH Ratings are 0 Hr.
See Plastics+ (QMFZ2) category in the Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used.
4. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall.
At the point contact location between pipe covering and gypsum board, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the pipe covering/gypsum board interface on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings — 1 and 2 Hr (See Item 1) F Ratings — 1 and 2 Hr (See Item 1)
T Ratings — 0, 3/4 and 1 Hr (See Item 3) FT Ratings — 0, ¾ and 1 Hr (See Item 3)
L Rating At Ambient — Less Than 1 CFM/sq ft FH Ratings — 1 and 2 Hr (See Item 1)
L Rating At 400 F — Less Than 1 CFM/sq ft FTH Ratings — 0, 3/4 and 1 Hr (See Item 3)
L Rating At Ambient — Less Than 1 CFM/sq ft
L Rating At 400 F — Less Than 1 CFM/sq ft
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
Hilti Firestop Systems Hilti Firestop Systems
System No. W-L-5028
SECTION A-A
W L
Page: 1 of 2
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 27, 2015 Page: 2 of 2
W L
A
C
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
1B
1A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 27, 2015
System No. W-L-5028
1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 7-1/2 in.
(191 mm).
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrants — One metallic pipe or tubing to be centered within the firestop system. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 40 (or heavier) steel pipe.
B. Copper Tubing — Nom 2 in. (51 mm) diam (or smaller) Type L (or heavier) copper tubing.
C. Copper Pipe — Nom 2 in. (51 mm) diam (or smaller) Regular (or heavier) copper pipe.
3. Tube Insulation — Plastics+ — Min 1/2 in. (13 mm) to max 1 in. (25 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. An annular space of min 0 in. (point contact) to max 1-1/2 in. (38 mm) is required within the firestop system. The T, FT and FTH Ratings are 1 hr when the 1 in. (25 mm) thick tube insulation is used and 3/4 hr when the 3/4 in. (19 mm) thick tube insulation is used.
When tube insulation thickness is less than 3/4 in. (19 mm), the T, FT and FTH Ratings are 0 Hr.
See Plastics+ (QMFZ2) category in the Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used.
4. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall.
At the point contact location between pipe covering and gypsum board, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the pipe covering/gypsum board interface on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings — 1 and 2 Hr (See Item 1) F Ratings — 1 and 2 Hr (See Item 1)
T Ratings — 0, 3/4 and 1 Hr (See Item 3) FT Ratings — 0, ¾ and 1 Hr (See Item 3)
L Rating At Ambient — Less Than 1 CFM/sq ft FH Ratings — 1 and 2 Hr (See Item 1)
L Rating At 400 F — Less Than 1 CFM/sq ft FTH Ratings — 0, 3/4 and 1 Hr (See Item 3)
L Rating At Ambient — Less Than 1 CFM/sq ft
L Rating At 400 F — Less Than 1 CFM/sq ft
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
System No. W-L-5029
SECTION A-A
W L
Page: 1 of 2
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
March 30, 2015
A
Page: 2 of 2
W L
4 3
Hilti Firestop Systems
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
March 30, 2015Hilti Firestop Systems
C
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings — 1, 2 and 3 Hr (See Items 1, 3 and 4) F Ratings — 1, 2 and 3 Hr (See Items 1, 3 and 4)
T Ratings — 0, 1/2, 1 and 1-1/4 Hr (See Item 3) FT Ratings — 0, 1/2, 1 and 1-1/4 Hr (See Item 3)
L Rating At Ambient — 4 CFM/Sq Ft FH Ratings — 1, 2 and 3 Hr (See Items 1, 2 and 4)
L Rating At 400 F — Less Than 1 CFM/Sq Ft FTH Ratings — 0, 1/2, 1 and 1-1/4 Hr (See Item 3)
L Rating At Ambient — 4 CFM/Sq Ft
L Rating At 400 F — Less Than 1 CFM/Sq Ft
1. Wall Assembly — The 1, 2 or 3 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide for 1 and 2 hr F and FH rating and 3-1/2 in. (89 mm) wide for 3 hr F and FH rating and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* — Min 5/8 in. (16 mm) thick with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 18-5/8 in. (473 mm).
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrants — One metallic pipe or tubing to be installed within the firestop system. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe — Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe.
C. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. When the hourly F or FH Rating of the firestop system is 3 hr, the nom diam of copper tube shall not exceed 4 in. (102 mm).
D. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. When the hourly F or FH Rating of the firestop system is 3 hr, the nom diam of copper pipe shall not exceed 4 in. (102 mm).
3. Pipe Covering* — Nom 1, 1-1/2 or 2 in. (25, 38 or 51 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape.
Transverse joints secured with metal fasteners or with butt tape supplied with the product. For 1 and 2 hr F and FH Ratings, the annular space between insulated penetrant and periphery of opening shall be min 0 in. (point contact) to max 1-7/8 in. (48 mm). For 3 hr F and FH Ratings, the annular space shall be min 0 in. (point contact) to max 1-1/4 in. (32 mm).
See Pipe and Equipment Covering — Materials (BRGU) category in the Building Material Directory for the names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.
The hourly T, FT, FTH Ratings of the firestop system are 1/2 hr for 1 hr rated walls and 1 hr for 2 hr rated walls. For 3 hr rated walls, the hourly T, FT and FTH Ratings when steel and iron pipes are used are 1 hr. For 3 hr rated walls, the hourly T, FT and FTH Ratings when copper penetrants are used are 1-1/4 hr for 2 in. (51 mm) thick pipe covering and 0 hr for pipe covering thickness less than 2 in. (51 mm).
3A. Pipe Covering* — (Not Shown) — As an alternate to Item 3, max 2 in. (51 mm) thick cylindrical calcium silicate (min 14 pcf) units sized to the outside diam of the pipe or tube may be used. Pipe insulation secured with stainless steel bands or min 18 AWG stainless steel wire spaced max 12 in. (305 mm) OC. When the alternate pipe covering is used, the T and FT Rating shall be as specified in item 3 above.
See Pipe and Equipment Covering — Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.
4. Fill, Void or Cavity Material* — Sealant — For 1 and 2 hr F and FH Rating, min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. For 3 hr F and FH Rating, min 1 in. (25 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point contact location between pipe covering and gypsum board, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the pipe covering/gypsum board interface on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
System No. W-L-5029
Hilti Firestop Systems
System No. W-L-7042
SECTION A-A
W L
1. Wall Assembly — The 1 or 2 hr fire rated wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features.
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced 24 in. (610 mm) OC.
B. Gypsum Board* — For 1 hr assembly, one layer of min 5/8 in. (16 mm) thick wallboard as required in the individual Wall and Partition Design.
For 2 hr assembly, two layers of min 5/8 in. (16 mm) thick wallboard as required in the individual Wall and Partition Design. Max diam of opening is 14-1/2 in. (368 mm) for wood stud walls and 21-3/4 in. (552 mm) for steel stud walls.
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrant — Galv steel duct to be installed concentrically or eccentrically within the firestop system. The annular space between the duct and periphery of opening shall be 0 in. (0 mm, point contact) and max 1-1/2 in. (64 mm) Duct to be rigidly supported on both sides of wall assembly.
A. Spiral Wound HVAC Duct — Nom 20 in. (502 mm) diam (or smaller) No. 24 MSG (or heavier) galv steel spriral wound duct.
B. Sheet Metal Duct — Nom 12 in. (305 mm) diam (or smaller) No. 28 MSG (or heavier) galv sheet steel duct.
3. Fill, Void or Cavity Material*—Sealant — Min 5/8 in. (16 mm) and 1-1/4 in. (32 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly for 1 or 2 hr rated walls, respectively. At the point contact location between duct and wallboard, a min 1/2 in. (13 mm) diam bead of sealant shall be applied at the wallboard/duct interface on both surfaces of wall assembly.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP601S Elastomeric Firestop Sealant, FS-ONE Sealant, FS-ONE MAX Intumescent
Sealant or CP606 Flexible Firestop Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 27, 2015
A
1A3
3 1B
C
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings - 1 and 2 Hr (See Items 1 and 3) F Ratings - 1 and 2 Hr (See Items 1 and 3)
T Rating - 0 Hr FT Rating - 0 Hr
FH Ratings - 1 and 2 Hr (See Items 1 and 3)
FTH Rating - 0 Hr
Hilti Firestop Systems
System No. W-L-7155
SECTION A-A
W L
1. Wall Assembly — The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400, V400 or W400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing shall consist of min 3-1/2 in. (89 mm) wide steel channel studs spaced max 24 in. (610 mm) OC. Additional steel studs shall be used to completely frame the opening.
B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design in the UL Fire Resistance Directory.
Max area of opening is 73.7 sq ft (6.85 m2) with a max dimension of 104 in. (2.64 m).
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
2. Steel Duct — Max 100 in. by 100 in. (2.5 by 2.5 m) galv steel duct to be installed either concentrically or eccentrically within the firestop system.
The duct shall be constructed and reinforced in accordance with SMACNA construction standards. The space between the steel duct and periphery of opening shall be min 0 in. (point contact) to max 2 in. (51 mm). Steel duct to be rigidly supported on both sides of the wall assembly.
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 27, 2015
A
3B 1A 3C
1A
3B
1B
Page: 2 of 2
2A1. Through-Pentrating Product* — As an alterate to Item 2. Fiber cement with galvanized steel facing, 3/8 in.(10 mm) thick composite metallic duct, with a max cross-sectional area of 43.0 sq ft, (4 m2) and a max individual dimension of 78 3/4 in. (2 m). Duct to be installed either concentrically or eccentrically within the firestop system such that the annular space is min 0 in. (point contact) to max 2 in. (51 mm). Duct to be rigidly supported on both sides of wall assembly. Refer to Ventilation Duct Assemblies in Vol. 2 of the Fire Resistance Directory.
DURASYSTEMS BARRIERS INC — Type DuraDuct HP.
2A2. Through-Pentrating Product* — As an alternate to Item 2. Fiber cement with galvanized steel facing, 1/4 in. (6 mm) thick, with a max cross-sectional area of 1764 sq in. (1.14 m2), and a max individual dimension of 42 in. (1067 mm). Duct to be installed either concentrically or eccentrically within the firestop system such that the annular space is min 0 in. (point contact) to max 2 in. (51 mm). Duct to be rigidly supported on both sides of wall assembly and installed in accordance. Refer to Ventilation Duct Assemblies in Vol. 2 of the Fire Resistance Directory.
DURASYSTEMS BARRIERS INC — Type DuraDuct SD.
2A3. Through-Pentrating Product* — As an alternate to Item 2. Galvanized steel faced duct panel, with a max cross-sectional area of 2450 sq in.
(1.58 m2), and a max individual dimension of 49-1/2 in. (1258 mm) Duct to be installed either concentrically or eccentrically within the firestop system such that the annular space is min 0 in. (point contact) to max 2 in. (51 mm). Duct to be rigidly supported on both sides wall assembly.
Refer to Ventilation Duct Assemblies in Vol. 2 of the Fire Resistance Directory.
DURASYSTEMS BARRIERS INC — Type DuraDuct GNX.
3 Firestop System — The firestop system shall consist of the following:
A. Packing Material — (Optional, Not Shown) — Polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fitted into annular space. Packing material to be recessed from both surfaces of wall to accommodate the required thickness of fill material.
A1. Packing Material — Required as specified in Table below. Min 3-3/4 in. (95 mm) or 5 in. (127 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form for 1 and 2 hr rated assemblies, respectively. Packing material to be recessed from both surfaces of wall to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of fill material shall be applied at the point contact location between the steel duct and the gypsum board.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-S SIL GG Sealant, FS-ONE Sealant, FS-ONE MAX Intumescent Sealant or CP606 Flexible Firestop Sealant C. Steel Retaining Angles — Min No. 16 gauge galv steel angles sized to lap steel duct a min of 2 in. (51 mm) and to lap wall surfaces a min of 1 in. (25 mm). When max duct dimension does not exceed 48 in. (122 cm) and duct area does not exceed 1300 in2 (8387 cm2), angles may be min No. 18 gauge galv steel. Angles attached to steel duct on both sides of wall with min No. 10 by 1/2 in. (13 mm) long steel sheet metal screws located a max of 1 in. (25 mm) from each end of steel duct and spaced a max of 6 in. (152 mm) OC. Steel angles are optional for those sides of duct that do not exceed the dimension specified in Table below, dependent on packing material, sealant and annular space as specified.
Hilti Firestop Systems
W L
Page: 1 of 2
Max Duct Dimension Duct Thickness Annular Space
Packing Material
Angle (Item 3C) Required
24 in. 24 ga or heavier 1/2 in. min to 1 in. max Item 3A1 No
(610 mm) (13 to 25 mm)
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
C
CL
ASS I F IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings — 1 and 2 Hr (See Item 1) F Ratings — 1 and 2 Hr (See Item 1)
T Ratings — 0 Hr FT Ratings — 0 Hr
L Rating at Ambient — Less Than 1 CFM/sq ft FH Ratings — 1 and 2 Hr (See Item 1)
L Rating at 400 F — Less Than 1 CFM/sq ft FTH Ratings — 0 Hr
L Rating at Ambient — Less Than 1 CFM/sq ft
L Rating at 400 F — Less Than 1 CFM/sq ft
System No. W-L-7155
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 27, 2015Hilti Firestop Systems
System No. W-L-7155
SECTION A-A
W L
1. Wall Assembly — The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400, V400 or W400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing shall consist of min 3-1/2 in. (89 mm) wide steel channel studs spaced max 24 in. (610 mm) OC. Additional steel studs shall be used to completely frame the opening.
B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design in the UL Fire Resistance Directory.
Max area of opening is 73.7 sq ft (6.85 m2) with a max dimension of 104 in. (2.64 m).
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
2. Steel Duct — Max 100 in. by 100 in. (2.5 by 2.5 m) galv steel duct to be installed either concentrically or eccentrically within the firestop system.
The duct shall be constructed and reinforced in accordance with SMACNA construction standards. The space between the steel duct and periphery of opening shall be min 0 in. (point contact) to max 2 in. (51 mm). Steel duct to be rigidly supported on both sides of the wall assembly.
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 27, 2015
A
3B 1A 3C
1A
3B
1B
Page: 2 of 2
2A1. Through-Pentrating Product* — As an alterate to Item 2. Fiber cement with galvanized steel facing, 3/8 in.(10 mm) thick composite metallic duct, with a max cross-sectional area of 43.0 sq ft, (4 m2) and a max individual dimension of 78 3/4 in. (2 m). Duct to be installed either concentrically or eccentrically within the firestop system such that the annular space is min 0 in. (point contact) to max 2 in. (51 mm). Duct to be rigidly supported on both sides of wall assembly. Refer to Ventilation Duct Assemblies in Vol. 2 of the Fire Resistance Directory.
DURASYSTEMS BARRIERS INC — Type DuraDuct HP.
2A2. Through-Pentrating Product* — As an alternate to Item 2. Fiber cement with galvanized steel facing, 1/4 in.