This document appears to be a set of architectural and construction details related to a federal contract opportunity for balance of work at the VA NY Manhattan Campus. The details include information on suspended ceilings, gypsum board ceilings, acoustic ceiling systems, roof access ladders and hatches, handrails, bollards, stairs, and various firestopping requirements. The details reference specific products and installation methods, and provide dimensional drawings and specifications. This appears to be part of the construction documents for the solicitation referenced in the related federal contract opportunity, which is for constructing the balance of work at the VA NY Manhattan Campus as part of the Hurricane Sandy Recovery Program.
View the file
Other files
Show 40 more
Latest 50 of 281 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WIRE HANGER
CEILING
UNDERSIDE OF SLAB
FLOOR
WALL
48" TYP. 8" MAX.
8" MAX 8" MAX
HANGER WIRE
ATTACHED AT STARTING
AND ONE ADJACENT WALL
CLEARANCE AT OPPOSITE
WALLS (NOT ATTACHED)
No.12 GA HANGER WIRE
@ 4' - 0" OC WHERE OCCURS
SPLAY WIRES No.12 GA SPLAY WIRE
BRACING IN LINE W/
RUNNER (TYP)
2" MAX TYP
CROSS TEE
45° MAX
TYP FOR
MAIN RUNNER
W N
S
E
No.12 GA. HANGER WIRE
@ 4' - 0" OC WHERE OCCURS
SPLAY WIRES PARALLEL W/ GROSS RUNNER
No.12 GA. SPLAY WIRE
IN LINE W/ MAIN RUNNER
2" MAX (TYP)
CROSS RUNNER
MAIN RUNNER
METAL CUP OR
SADDLE WIRE TIE
45° MAX
TYP FOR
N
S
EW
NOTE:
1. HANGER WIRES "N" AND "S" ARE IN THE SAME VERTICAL PLANE AS THE MAIN RUNNER. HANGER WIRES "E"
AND "W" ARE IN THE VERTICAL PLANES PERPENDICULAR TO THE MAIN RUNNER
2. CONTRACTOR TO DESIGN AND CONSTRUCT CEILING COMPONENTS TO MEET SEISMIC RESTRAINT
REQUIREMENTS.
TYPICAL CEILING BRACING
RUNNERS AT WALLS
NOTE:
1. MAIN RUNNERS AND CROSS RUNNERS SHALL BE ATTACHED TO THE PERIMETER MEMBERS ON TWO ADJACENT WALLS. A CLEARANCE OF 1/4" IN. SHALL BE MAINTAINED BETWEEN THE MAIN RUNNERS AND THE CROSS RUNNERS
AND THE PERIMETER MEMBERS ON THE TWO REMAINING WALLS
2. LIGHTING FIXTURES, SPRINKLER HEADS, AND AIR TERMINALS (DIFFUSERS AND DUCTED GRILLES) SHALL BE INDEPENDENTLY SUPPORTED FROM THE STRUCTURE ABOVE. SMOKE DETECTORS, SPEAKERS, AND ITEMS WEIGHING LESS THAN 20 LBS. SHALL BE DIRECTLY SECURED TO THE CEILING SUSPENSION SYSTEM, OR
INDEPENDENTLY SUPPORTED FROM STRUCTURE ABOVE.
3. WIRES SHALL BE ATTACHED TO SUSPENDED MEMBERS WITH A MINIMUM OF THREE TURNS.
4. VERTICAL STRUT SHALL BE INSTALLED AT EACH SET OF SPLAY WIRES - 200 POUND DESIGN FORCE.
PROVIDE CONTINUOUS METAL
RUNNER @ WALL
1 1/2" METAL CHANNELS @ 4'-0" O.C.
7/8" HAT CHANNELS @ 16" O.C.
-WIRE TIE TO METAL STUDS
5/8" GYP. BD. TYP. (MR AT TOILET ROOMS)
METAL J-BEAD / SPACKLE SMOOTH
SEALANT & BACKER ROD
PARTITION AS SCHEDULED
3/8"
2' - 0" (MAX)
UNDERSIDE OF STRUCTURE
CLIP ANGLE SECURED TO
STRUCTURE
1/4" DIA RODS @ 4' - 0" OC
(BOTH DIRECTIONS)
CLIP SUPPORT
1 1/2" BLACK IRON CHANNELS
@ 4' - 0" OC
BSA CLIP
BEVELED TEGULAR ACOUTICAL
PANEL - SEE FINISH PLAN
BEVELED TEGULAR CUT PANEL AT ALL
NON-FULL PANELS, MFG. PAINT ALL
CUTS. TEG TABS ARE NOT ACCEPTABLE
CONTINUOUS REVEAL WALL
ANGLE
2' - 0" (MAX)
UNDERSIDE OF STRUCTURE
CLIP ANGLE SECURED TO STRUCTURE
1/4" DIA RODS @ 4' - 0" OC
(BOTH DIRECTIONS)
CLIP SUPPORT
MAIN CHANNELS @ 4' - 0" OC
7/8" HAT CHANNELS @ 16" OC
5/8" GYP BD CEILING
(MR TYPE AT TOILET
ROOMS)
TYP
A-AE502
E9
2'-0"
ELEVATION SECTION
INSULATED ROOF
ACCESS HATCH
1'- 0"
TY
P
A-AE502
C4
OSHA COMPLIANT
WALL-MOUNTED LADDER
NOTE: LADDER SHALL BE
PRIMED AND PAINTED
FEDERAL SAFETY YELLOW
LADDER ASSIST POST
STEEL BRACKETS WITH EXP
BOLTS INTO FULLY GROUTED
CMU. EXP BOLT SIZE BY
DELEGATED DESIGN.
ROOF HATCH SAFETY
RAILING SYSTEM
DU
CT
*CONTRACTOR TO FIELD
VERIFY ROOF INSULATION
THICKNESS AND ADD TO 12"
ABOVE FINISHED ROOF
REQUIREMENT FOR
OVERALL EQUIPMENT
CURB SUPPORT HEIGHT
PACK ANNULAR SPACE WITH
UN-FACED MINERAL WOOL
INSULATION (ALL SIDES)
PRE MANUF INSULATED
EQUIPMENT SUPPORT CURB; SEE
SPEC. 07 72 00 FOR REQUIREMENTS &
COORD. WITH MECHANICAL DWGS.
EXISTING BALLASTED ROOF SYSTEM
EXISTING THERMAL
INSULATION
EXISTING ROOF
STRUCTURE
CANT
FILL VOID WITH RIGID
INSULATION TO MATCH
EXISTING
DETAIL STRIP EXTENDED 8" MIN. VERTICAL
AND 18" MIN. ONTO FIELD OR EXISTING
ROOF. ADHERE TO ROOF CURB IN A CONT.
BED OF BITUMINOUS MASTIC
NEW ROOFING MEMBRANE TO
MATCH EXISTING, EXTEND 24" MIN.
ONTO FIELD
OF EXISTING ROOF (ALL SIDES)
SFRM ON STL FRAMING TO
OBTAIN 2 HOUR RATING
EXHAUST FAN - PER
MECHANICAL
VIBRATION ISOLATOR (WHERE
SPECIFIED BY MECH.)
PRESSURE TREATED WOOD NAILER
SECURELY FASTEN VIBRATION
ISOLATOR
TO WOOD NAILER WITH S/S FASTNERS
DAMPER PER MECHANICAL
SEALANT
18 GAUGE GALVANIZED
STEEL COUNTER FLASHING
NT
S)
A
BO
VE
F
IN
IS
HE
D
RO
OF
DU
CT
ANCHOR SUPPORT TO DECK
REFER TO STRUCTURAL FOR
OPENING STEEL FRAMING AND
CONNECTION REQUIREMENTS.
18 GAUGE GALVANIZED
STEEL FLASHING
SEALANT
SSTL SCREW WITH EPDM WASHER AT 12" 0.C. MAX.
*CONTRACTOR TO FIELD
VERIFY ROOF ASSEMBLY
TYPE / CONSTRUCTION
BEFORE MODIFICATIONS
TO EXISTING ROOF
ASSEMBLY. IF CONDITIONS
VARY FROM WHAT IS
SHOWN; INFORM RESIDENT
ENGINEER FOR DIRECTION.
HD GALV. STL BAR GRATE TREAD
W/ TRACTION NOSING EDGE
STEEL STRINGER EXPANSION
BOLTED TO LANDING
" STEEL KICK PLATE
STEEL STRINGER EXPANSION
BOLTED TO FACE OF LOADING
DOCK PLATFORM. EXP BOLT SIZE
BY DELEGATED DESIGN
5 E
QU
AL
R
IS
ER
S (7
" M
AX
11"TREAD1"
2'-
"T
YP
6"
FACE OF LOADING DOCK
1'- 0"
1"
NOTE:
1) ALL STEEL SHALL BE HD GALVANIZED AND PAINTED P6. (EXCLUDE PAINT AT BAR GRATE TREADS)
2) STAIR IS A DELEGATED DESIGN; REFER TO SPECIFICATION SECTION 05 51 00 FOR REQUIREMENTS.
TYP
A8
A-AE502
ALIGN
EXPANSION BOLT SCREWS
PER MANUFACTURER
1 1/2" O.D. DIAMETER PAINTED
HANDRAIL IN SEATED
CONNECTION TO STL. ROD
SUPPORT BRACKET
R
" 2 1 4"3 8"
NOTE: DESIGN BY
HANDRAIL
MANUFACTURER
4'- 0"
3'- 0"
6"
CONCRETE FILLED BOLLARD
6" 6"
2'-0"
COMPRESSIBLE FILLER STRIP
W/ SEALANT
CONCRETE FOOTING
CONTINUOUSLY SHOP
WELDED STEEL CAP
HD GALV. 6" DIA.
STEEL PIPE
SLOPE CONCRETE AT BASE
PAINT AS NOTED
BELOW
PAVMENT, TYP
SEALANT
NOTES: HD GALV. POST BARRICADES SHALL BE PAINTED WITH ONE COAT OF
GALVANIZED PRIMER AND TWO COATS OF FLAT BLACK ENAMEL PER
SPECIFICATIONS. STRIPES CONSISTING OF 4" BANDS OF YELLOW
REFLECTORIZED TAPE SHALL BE APPLIED CONTINUOUSLY UP THE POST.
COMPACTED GRANULAR
FILL 8"
M
IN
. STEEL ANGLES 5"x3"x12" (12 GA) @ 24" OC
2 POWDER ACTUATED
FASTENERS 0.157 x 1"
MINERAL WOOL FORMING MATERIAL
FIRE STOP SPRAY
CUT TOP COURSE AS REQUIRED
LADDER EXPANSION BOLTED TO PARTITION INTO
FULLY GROUTED CELL (SEE PLANS FOR PARTITION
TYPE)
FRAME CURB WITH INSULATION
LOCK STRIKE AND PADLOCK HASP
EXISTING BALLASTED ROOF SYSTEM
FLASHING INCLUDED WITH ROOF
HATCH
EXISTING THERMAL INSULATION
SEALANT
CANT
NEW ROOFING MEMBRANE EXTEND 24" MIN.
ONTO FIELD OF EXISTING ROOF (ALL SIDES)
DETAIL STRIP EXTEND 8" MIN. VERTICAL AND
18" MIN. ONTO FIELD OF EXISTING ROOF
" M
IN
7" MIN.
LADDER ASSIST POST
*CONTRACTOR TO FIELD
VERIFY ROOF INSULATION
THICKNESS AND ADD TO 12"
ABOVE FINISHED ROOF
REQUIREMENT FOR OVERALL
ROOF HATCH CURB HEIGHT
EXISTING CMU WALL
ROOF HATCH SAFETY
RAILING SYSTEM
HINGED DOOR ELECTRICAL
PULL-BOX; PAINT ALL EXPOSED
SURFACES P-1 (SG)
FRT WOOD
BLOCKING (CONT)
CAULK
PRE-FINISHED
WHITE BRAKE
METAL TRIM TO
MATCH CEILING
GRID
8" GWB ON 3 58"
METAL STUDS AT
16" OC TO DECK
ABOVE. PAINT
GWB P-1
SCHEDULED ACT
SHADOW MOLDING
LINE OF GWB BEYOND
FIN CLG
AS SCHEDULED
TO BE COORDINATED WITH
FINAL PULL BOX SIZE
STAINLESS STEEL PIANO
HINGE
RECESSED ALUM COVER
/ FLOOR ACCESS DOOR
WITH CONCRETE FILL **
REMOVABLE COVER
PLUG AND KEY WRENCH
HOLD OPEN / SELF CLOSING
PNEUMATIC CYLINDER
ALUMINUM CHANNEL W/
ANCHOR FLANGE
CONCRETE COLLAR - SEE
STRUCTURALDWGS.FOR
REQUIREMENTS 9
16" THICK MIN. INTUMESCENT
MASTIC FIRE PROOF COATING
ALL AROUND CONCRETE
COLLAR
SLAM LOCK W/ CABLE AND PULL
HANDLE
2 HR RATED SLAB - SEE STRUCTURAL
FOR SLAB / OPENING MODIFICATIONS
** NOTE: FLOOR ACCESS DOOR
SHALL HAVE A 2 HR FIRE RATING.
30" x 30" FRAME OPENING4" 4"
2'-
AF
F
1'-0"
11"
TYP
A8
A-AE502
EXISTING
CONCRETE
STAIR
12"
WHERE HANDRAIL CAN
NOT BE SECURED TO
WALL, RETURN HANDRAIL
TO FLOOR. SET HANDRAIL
IN SLEEVE AND
NON-SHRINK GROUT
6"
NOTE:
1. STEEL HANDRAIL - EXTERIOR COMPONENTS
SHALL BE HD GALVANIZED AND PAINTED P-6.
2. STEEL HANDRAILS - INTERIOR COMPONENTS
SHALL BE SHOP PRIMED AND PAINTED P-4.
HANDRAIL
BRACKET
SECURED TO
WALL (TYP)
SIM
A-AE502
A9
SIM
A-AE502
A9
1 1/2" O.D. DIAMETER PAINTED
HANDRAIL EXPANSION BOLTED TO
EXISTING LOADING DOCK CONC.
OR THROUGH SCREW SECURED TO
METAL PANEL WITH A BACKING
PLATE.
2'-
1'-11"
1'-0"
1'-0"
1'- 0"
EXISTING TO
REMAIN
ANTI-SLIP
TREAD
NOSING, TYP. EXISTING
CONCRETE
STAIR
SET HANDRAIL IN CORE
DRILLED HOLE WITH
NON-SHRINK GROUT
6"
1 12" DIA. STL PIPE HANDRAIL
PAINTED P-4.
1 1/2" O.D. DIAMETER PAINTED
EXP. BOLT SCREWS
PAINTED STEEL TUBE WITH PAINTED
ELBOW BRACKET ASSEMBLY
2 14" 1 12"
NOTE: REFER TO A9 / A-AE502 FOR TYPICAL
HANDRAIL PLAN AT END.
HANDRAIL RETURN BEYOND
NOTE: DESIGN BY HANDRAIL
MANUFACTURER
3" = 1'-0"F6 SUSPENDED CEILING RESTRAINT
6" = 1'-0"E9 GYPSUM BOARD CEILING DETAIL AT WALL
1 1/2" = 1'-0"C6 TYP ACOUSTIC CEILING DETAIL
1 1/2" = 1'-0"A6 TYP GYP BD HUNG CEILING DETAIL
0 6" 1'-0" 1'-6"
0 1" 2" 4"
0 6" 1'-0" 1'-6"
1/2" = 1'-0"C2 ROOF ACCESS LADDER
3" = 1'-0"F3 ROOF CURB DETAIL AT MECHANICAL DUCT
0 3" 6" 9" 0 3" 6" 9"
1" = 1'-0"C8 STAIR DETAIL
A8 HANDRAIL DETAIL AT WALL
0 6" 1'-0" 1'-6"
0 6" 1'-0" 1'-6"
3/4" = 1'-0"C1 TYPICAL BOLLARD DETAIL
0 1'-0" 2'-0" 3'-0"
0 1'-0" 2'-0" 4'-0" 1 1/2" = 1'-0"C4 ROOF ACCESS HATCH DETAIL
0 6" 1'-0" 1'-6"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA NY Manhattan Campus
423 E 23RD Street, New York, NY 10010
630-600A
Project Director
Revisions: Date:
A/E:
AECOM
3101 WILSON BLVD, SUITE 900
ARLINGTON, VA. 22201
703-682-4900
WWW.AECOM.COM
Construction Document Refresh
Key Plan
Balance of Work
9/12/2022
A-AE502
DETAILS - 2
DZ JH / DZ
3" = 1'-0"F5 DETAIL - ELECTRIC PULL BOX - CEILING
0 3" 6" 9"
1 1/2" = 1'-0"E5 FLOOR ACCESS DOOR DETAIL
0 6" 1'-0" 1'-6"
1" = 1'-0"F1 EXTERIOR / INTERIOR HANDRAIL DETAIL
0 6" 1'-0" 1'-6"
E1 CENTER HANDRAIL DETAIL
1 1/2" = 1'-0"A9 HANDRAIL PLAN DETAIL
3" = 1'-0"
0 3" 6" 9"
1" = 1'-0" 0 6" 1'-0" 1'-6"
AutoCAD SHX Text 15'-0"
AutoCAD SHX Text + 23'-0"
AutoCAD SHX Text
1ST FLOOR
AutoCAD SHX Text + 8'-0"
AutoCAD SHX Text
GRD FLOOR
AutoCAD SHX Text 70°
AutoCAD SHX Text
EXIST. STORAGE AREA
john.haselby Stamp
NEW CONCRETE
SHIM LEVEL AND PACK WITH 1-1/2"
THK MAX. NON-SHRINK GROUT
ADJUST IN FIELD AS REQUIRED
4" X 12" X 3/4" THK BASE PLATE WITH 4
1/2" DIA EXPANSION ANCHORS, WITH
3-1/2" EMBEDMENT
C10 X 15.3
GRATING WITH 1-1/4" X 1/8" BEARING BARS
SPACED 7/16" O.C. MIN. 0.90 COEFFICIENT
OF FRICTION SLIP RESISTANT FINISH.
3/8" THK STIFF PLATE
L3X3X1/4" X 3" LONG WITH 1/2" DIA.
EXPN ANCHORS EACH STRINGER,
INSIDE FACE (3-1/2" EMBEDMENT) 3 SIDES
TYP.
2'-0"3'-7"
6"
/2"
MA
X.
10"
EQ
7" M
AX
EQ
EQ
EQ
1-1/2" DIA. PIPE RAIL & POSTS
GALV. STEEL.
4" HIGH TOE KICK
2'-
4"
FI
EL
D
VE
RI
FY
NOTES:
1) ALL STEEL TO BE GALVANIZED AND PAINTED.
2) FULL DEPTH SHEAR CONNECTIONS USING 3/4" DIA MIN. BOLTS, TYP.
3) STAIR IS A DELEGATED DESIGN; SEE SPECIFICATION SECTION 05 51 00 FOR REQUIREMENTS.
4" 4" 4" 2"
TYP.
HSS 4 X 2 X 3/16
(FY = 46 KSI)
3'-
6" 1/2" MAXIMUM BETWEEN EXTERIOR DOOR
THRESHOLD AND TOP OF GRATING.
11"
TYP.
1"
STEEL KICK PLATE
STAIR TREADS TO MATCH
PLATFORM GRATING
GROUND FLOOR
GRADE
2"
3'- 6"
8" O.D. STEEL PICKET (EQUAL SPACE MAX
CLEAR BETWEEN PICKETS 3 15
16"). COPE TO
T/B RAILS / WELD
3'- 6"
2'-
1'-0"
11"12"
2'-
0"19" MAX
19" MAX
4x4x3/8" STEEL ANGLE
NOTE : INSTALL FRAME PRIOR TO CUTTING FLOOR / ROOF OPENING.
PROVIDE STL FRAME AROUND
OPENINGS AND AT LOCATIONS OF
ROOF CURBS SUPPORTING
EQUIPMENT; APPLY SFRM TO STL
FOR A 2 HR RATING. SEE
STRUCTURAL FOR MEMBER SIZES
L 6X4X3/8" (LLV) WITH
2 - 3/4"Ø A325-N BOLTS IN
HORIZONTAL SLOTTED
HOLES, TYP
1/4
TYP.
COORDINATE WITH
MECHANICAL CONTRACTORS INSULATED ROOF CURB - PROVIDE
TIE-IN INTERFACE / REPAIR TO
EXISTING ROOF ASSEMBLY
FOR SIZE AND LOCATION
EXISTING BEAM
ENCASED IN
CONCRETE
EXISTING BEAM ENCASED
IN CONCRETE CHIP AS
REQUIRED TO EXPOSE FOR
CONNECTION
EXISTING ROOF
A-AE502
F3
3'- 6"
3/4
CAP PLATE STEEL
" NOMINAL DIAMETER SCHEDULE 80 STEEL
PIPE POST WELDED TO BASE PLATE
8"x8"x
" THICK STEEL BASE PLATE WITH
CHAMFERED EDGES. BASE PLATE TO BE
INSTALLED OVER WIRE MESH PARTITION BASE
PLATE
(4)
" DIAM. EXPANSION BOLTS WITH 4"
MINIMUM EMBEDMENT
EXISTING CONCRETE
SLAB
NON SHRINK GROUT
4" OD
NOTE: GUARD POST AND BASE PLATE
SHALL BE PAINTED FEDERAL SAFETY
YELLOW
LINE OF OPENING BEYOND
PALLET JACK (NIC)
6"x6"x3
8" STEEL ANGLE EXPANSION
BOLTED TO FLOOR AT 12" O.C.
PAINT SAFETY YELLOW
WALL GUARD CRASH RAIL
9"
3"
LINE OF IMPACT FLOOR RAIL
BEYOND. PROVIDE MITERED
CORNERS AND RETURN TO
WALL
2" DIA. EXP BOLTS AT 12" O.C.
(MIN 4" EMBEDMENT)
EXISTING EXTERIOR WALL
" GWB ON 3
" METAL
STUD FRAMING PAINT P-1
WINDOW SHADE WITH BRACKET
SCHEDULED WINDOW
ACT REVEAL WALL
ANGLE
KICKER @ 4'-0" OC TO
DECK ABOVE
T
O
SE
E
PL
AN
+/- 10"
LINE OF
COLUMN
BEYOND
EXISTING WALL
2" DIA. HD GALV STEEL REMOVABLE
PIPE GUARDRAIL - PTD (48" HIGH)
PROVIDE MIN. 6" EMBEDMENT INTO
HD GALV STL SLEEVE
DOUBLE ACTING SAFETY
DOOR / GATE
SLAB TO UNDERSIDE OF STRUCTURE
6"x4"x3
8" H.D. GALVANIZED STEEL TUBE
WELDED TO 8"x10"x1
4" STEEL PLATE
EXPANSION BOLTED TO SLAB. PAINT STEEL
BLACK.
LIMITING POST (EACH SIDE)
EXISTING WALL
SCHEDULED WINDOW
3"
8" 3'-
6" 1"
- 1
'-4 3 4"
3"
- 5
'-1 0 3 4"
(V
IF
F5
A-AI201
1 12" O STEEL PIPE TOP RAIL (COPE
TO POST / WELD)
WEEP
8" O.D. STEEL PICKET (EQUAL SPACE MAX
CLEAR BETWEEN PICKETS 3 15
16"). COPE TO
T/B RAILS / WELD
WEEP
1 12" O STEEL PIPE BOTTOM RAIL
(COPE TO POST / WELD)
1 12" O POST AT 4'-0" O.C. MAX.
CORE DRILL
NON SHRINK / NON METALLIC
GROUT
EXISTING CONCRETE WALL.
INFILL GROUT SOLID ALL
UNUSED PREVIOUS CORE
DRILLS
3 15 16
3'- 6"
3"
MIN
3"
MIN
2 1/2"
1 2" 5 1
/2"
NOTE: ALL STEEL SHALL BE H.D.
GALVANIZED AFTER FABRICATION
AND PAINTED P-5
POST
EXISTING
CONCRETE SLAB
9" X 9" X 1/2" THICK
BASE PLATE. PAINT P-4
1/4
1" + NON-SHRINK GROUT
1" TYP
1/2" Ø EXPANSION ANCHORS, WITH 4"
MIN EMBEDMENT. TOTAL 4 BOLTS
FACE OF EXISTING
PARTITON (WHEN
OCCURRING)
4" TYP
3"O SCHEDULE 40
PIPE. PAINTED P-4
TOP OF STEEL
W 10 X 12 @
PERIMETER (TYP)
3/8" THK PL TYPICAL
3/16
WP
TYP
(2) 3 X 3 1/4" ANGLES
DIAGONAL BRACE, TYPICAL,
EACH CORNER OF PLATFORM
3'-0" TYP
A-AE503
A93" Ø SCHEDULE 40 PIPE
TYP
3/16
5/16 3 X 3 X 1/4" ANGLE
3/8" THK PLATE
D7
A-AE503
GRATING BEARING BAR SPAN
1'- 6"
EA
CH
C
OR
NE
R
W 8 X 10
@ 36" OC
NOTE: FULL DEPTH SHEAR CONNECTION
USING 3/4" DIA. MIN. A325-N BOLTS, TYP.
AE503
C9
STEEL PIPE GUARDRAIL (WHERE
SCHEDULED)
OPEN GRATING (FIBERGLASS
REINFORCED POLYMER AT
ELECTRIC CLOSETS)
NOTE: ALL STEEL SHALL BE
PAINTED P-4. STEEL SHALL BE
PAINTED PRIOR TO
INSTALLATION OF GRATING
2'- 0"
3'- 6"
5'-0" MAX. 5'-0" MAX.
A-AE503
C9
D5
A-AE503
3'- 6"
RAILING BRACKET
FINISHED FLOOR
STEEL BEAM
FRP GRATING
1 14" DIA. STEEL PIPE
GUARDRAIL
2'- 0"
NOTE: ALL STEEL
SHALL BE PAINTED P-4
" M
AX
" M
AX
1 1/4" DIA. SCHEDULE
80 PIPE POST
FRP GRATING. SEE
SPECS.
3/16
3/8" THICK BENT PLATE
1/2"TYP
5 1 /2"
2"
3/8" THICK STIFFENER
STEEL BEAM
NOTE: PAINT ALL STEEL P-4
PRIOR TO INSTALLATION OF
GRATING
EXISTING FLOOR
SLAB
OPEN GRATING ( FIBERGLASS
REINFORCED POLYMER
AT ELEC CLOSETS)
12" TREADS
1'- 9"
BEAM
3'- 6"
D5
A-AE503
2'- 0"
3" X 3" X 1/4" X 6" ANGLE WITH 1/2" DIA. EXPANSION
ANCHOR W/ 3" MIN EMBEDMENT(EACH STRINGER, IN SIDE FACE)
MI
N
12"
LINE OF PLATFORM
BEYOND
LINE OF GUARDRAIL
BEYOND (WHERE
SCHEDULED)
11" 12"
4 E Q.
R
IS
ER
S
6"
1"
NOTE:
1) ALL STEEL SHALL BE PAINTED P-4.
2) STAIR IS A DELEGATED DESIGN; SEE SPECIFICATION SECTION 05 51 00 FOR REQUIREMENTS.
2'-
2'-
3'- 6"
2'-
11"
" M
AX
" M
AX
" M
AX
" M
AX
EXISTING CONCRETE
SLAB ON GRADE
APPLY BONDING AGENT
BEFORE POURING NEW
CONCRETE
NEW CONCRETE INFILL SLAB
(6" MIN. THICKNESS) f'c = 5,000
PSI @ 28 DAYS, FINISH TO
MATCH EXISTING SLAB
SAWCUT EXISTING
SLAB AND EXCAVATE
TO INSTALL NEW PIPE
EXISTING CONCRETE
SLAB ON GRADE
#3 @ 24" OC DOWELS
STAGGERED, DRILL AND
INSTALL USING ADHESIVE
ANCHORING SYSTEM
NEW UTILITY PIPE,
REFER TO PLUMBING
DRAWINGS 1
4 1/2"
EXISTING CONCRETE
SLAB ON GRADE
APPLY BONDING AGENT
BEFORE POURING NEW
CONCRETE
NEW CONCRETE INFILL SLAB
(6" MIN. THICKNESS) f'c = 4,000
PSI @ 28 DAYS, FINISH TO
MATCH EXISTING SLAB
SAWCUT EXISTING
SLAB AND EXCAVATE
TO INSTALL NEW PIPE
EXISTING CONCRETE
SLAB ON GRADE
#3 @ 24" OC DOWELS
STAGGERED, DRILL AND
INSTALL USING ADHESIVE
ANCHORING SYSTEM
NEW FLOOR BOX,
REFER TO ELEC
DRAWINGS
4 1/2"
TYPE B
13'-9" OUT TO OUT OF BASE PLATES
BOLLARD AFOREBOLLARD AFORE
3'- 6"
9'- 8"
C
LE
AR
* VERIFY EXISTING OVERHEAD CLEARANCES FOR NO INTERFERENCE BEFORE FABRICATION
TYPE A
11'-9" OUT TO OUT OF BASE PLATES
BOLLARD AFOREBOLLARD AFORE
3'- 6"
8'- 8"
C
LE
AR
CMU BOND BEAM. SEE
F4/A-AE603
8" GWB CEILING ON
METAL FRAMING -
PAINTED
FIRE STANDPIPE WITH FIRE HOSE
CONNECTION. SEE FIRE
PROTECTION FOR LOCATION AND
HOSE CONNECTION
REQUIREMENTS.
HM DOOR AND FRAME AS
SCHEDULED
WALL MOUNTED FIRE
EXTINGUISHER
SCHEDULED PARTITION
SCHEDULED FLOOR AND
BASE FINISHES
4"x3"x1
2" LLH STEEL ANGLE WITH
MINIMUM OF (2) 12" DIA. STUD ANCHORS.
ANGLE SHALL BE SET FLUSH
HORIZONTAL INTO SLAB, AND EXTEND 12"
BEYOND FACE OF SLAB. COPE / EXTEND
VERTICAL LEG OF ANGLE 2" BEYOND
FACE OF SLAB FOR TERMINATION
INTERFACE WITH DOOR FRAME (EACH
SIDE). PAINT ANGLE TO MATCH DOOR
FRAME.
REINFORCED CONCRETE BASE
EXISTING CONCRETE SLAB
WELDED WIRE FABRIC
#4 CONT.
#4 EPOXY DOWEL @ 12" O.C.
WITH 4" EMBEDMENT
T/O SLAB
8" 6'-
8"
FIN CLG
8" 2"
1/2"
SCHEDULED PARTITION
HM FRAME; SEE DETAIL F1 / A-AE601
0 1'-0" 2'-0" 3'-0"
3/4" = 1'-0"A1 TYPICAL EXTERIOR STAIR DETAIL
1" = 1'-0"A5 TYPICAL OPENING AND EQUIPMENT SUPPORT FRAMING DETAIL
0 6" 1'-0" 2'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA NY Manhattan Campus
423 E 23RD Street, New York, NY 10010
630-600A
Project Director
Revisions: Date:
A/E:
AECOM
3101 WILSON BLVD, SUITE 900
ARLINGTON, VA. 22201
703-682-4900
WWW.AECOM.COM
Construction Document Refresh
Key Plan
Balance of Work
9/12/2022
A-AE503
DETAILS - 3
DZ JH / DZ
1 1/2" = 1'-0"D3 GUARD POST DETAIL
0 6" 1'-0" 1'-6"
1" = 1'-0"C5 IMPACT FLOOR RAIL DETAIL
0 6" 1'-0" 2'-0"
1 1/2" = 1'-0"D1 SHADE POCKET DETAIL
0 6" 1'-0" 1'-6"
0 1'-0" 2'-0" 3'-0"
3/4" = 1'-0"F1 DOUBLE - ACTING SAFETY DOOR GATE
3" = 1'-0"F4 DETAIL - GUARD RAIL
0 3" 6" 9"
0 1'-0" 2'-0" 3'-0" 3/4" = 1'-0"A9 DETAIL - PLATFORM POST BASE CONNECTION
1 1/2" = 1'-0"C9 DETAIL - PLATFORM RAILING BRACKET
0 6" 1'-0" 1'-6"
0 1'-0" 2'-0" 3'-0" 3/4" = 1'-0"F7 SECTION - PLATFORM STAIR
0 1'-0" 2'-0" 3'-0" 3/4" = 1'-0"D7 DETAIL - PARTIAL RAILING ELEVATION
D5 DETAIL - PLATFORM SECTION AT POST
1" = 1'-0"A7 UNDERSLAB PIPING DETAIL
0 6" 1'-0" 2'-0"
1" = 1'-0"C7 UNDERSLAB FLOOR BOX DETAIL
0 6" 1'-0" 2'-0"
0 2'-0" 4'-0" 8'-0" 1/4" = 1'-0"F5 DOCK GATE ELEVATIONS
0 1'-0" 2'-0" 3'-0" 3/4" = 1'-0"
0 1'-0" 2'-0" 3'-0" 3/4" = 1'-0"F9 SECTION - FIRE PROTECTION NICHE
6" CMU WITH VP-3 PLASTER
FINISH / P-1 PAINT - EACH SIDE
S
S
S
S
S S
S
S
UNDERSIDE OF STRUCTURE
LINE OF SMOKE BARRIER "S"
EXISTING CMU WALL - DEMO PER PLANS.
SEAL ALL THROUGH-WALL PENETRATIONS -
BOTH SIDES OF WALL
6"x3 12"x3
8" STEEL ANGLE
LINTEL WITH 6" BEARING
EACH SIDE 1
2" GWB ON LIGHT GAUGE
FRAMING. SEAL TERMINATION
TIGHT AT CMU TO FORM
SMOKE BARRIER. PAINT P-1
(EGGSHELL).
SCHEDULED DOOR AND FRAME
WITH ADO
CORNER GUARD
TERRAZZO BASE / FLOOR
EXTENSION INTO RECESSED
DOOR ENTRY
SCHEDULED BASE / FINISHES
EXISTING ACT CEILING
ASSEMBLY. MODIFY /
REPAIR AS REQUIRED.
8'- 0"
VP-3 PLASTER FINISH AND P-1
PAINT - EACH SIDE.
LINTEL SEE F4/A-AE603
HM FRAME HEAD; SEE F1/A-AE601
6" 3" 3"
S.S. FASTENERS WITH
NEOPRENE GASKET @ 12" O.C.
ROOF ASSEMBLY
(MATCH EXISTING)
2 PLIES COVER STRIP
CANT STRIP
8" (M
IN
INSULATED ROOF CURB
ABS COVER
INSULATED PREFABRICATED
ROOF CURB WITH CANT (ALL
SIDES)
MECHANICAL PIPE OR ELECTRICAL
CONDUIT THROUGH ROOF
2"
STEPPED RUBBER BOOT SEALED TO COVER
STAINLESS STEEL DRAWBAND
CORE DRILL EXISTING SLAB
2 HOUR RATED FIRESTOP
PENETRATION ASSEMBLY
CAP
SAFETY DISCONNECT, SEE
ELECTRICAL
STRUT CHANNEL CROSS BRACE
W/ HOLES WELDED TO 6" LENGTH
OF 2" x 2" SQUARE TUBE
BOLT (PER MFG.)
STRUT CHANNEL UPRIGHT
W/ HOLES
1 3/4" ROUND BAR WELDED
TO PLATE AND PLUG
WELDED
TO STL UPRIGHT
GFCI RECEPTACLE IN
WEATHERPROOF ENCLOSURE.
SECURE TO VERTICAL STRUT
CHANNEL CROSS BARCE; SEE
ELECTRICAL
CONDUIT. SEE ELECTRICAL
EXTEND CONDUITS TO PIPE
PORTAL FLASHING SYSTEM.
1'- 4"
1'- 8"
C6
C-AE504
8" DIA x 1/4" THICK STL PLATE W/
EXP BOLTS
CONCRETE ROOF SLAB
1/2" EXPANSION ANCHORS WITH 4"
MIN EMBED
GALVANIZED CONDUIT SUPPORT /
STRAP ANCHOR PER ELECTRICAL
PRESSURE TREATED WOOD
NAILERS NAILED TOGETHER
AND SECURED TO ROOF DECK
VERTICAL AND DIAGONAL STEEL
ROOF MOUNTING MEMBER
PENETRATION ROOF.
(CLEANED AND PREPPED)
NEW OR EXISTING ROOF DECK
2 PLY SBS ROOFING
ASSEMBLY
POLYURETHANE - BITUMEN FINISH
COAT WITH BROADCAST MINERAL
GRANULES
8"
MI
N.
REINFORCING FABRIC SET IN
POLYURETHANE BITUMEN
LIQUID
8" MIN.
STL PLATE SECURED TO
DECK WITH EXP BOLTS
NOTE: FLASHING DETAIL TO
CONFORM TO ROOFING
MANUFACTURER'S REQUIREMENTS
1/2" EXPANSION ANCHORS WITH 4"
MIN EMBED
FREE STANDING ROOF EDGE PROTECTION,
(KEEGUARD OR APPROVED EQUAL.)
(PROVIDE AND INSTALL ROOF EDGE FALL
PROTECTION SYSTEM INCLUDING PIPE
RAILINGS, UPRIGHTS, BASES,
COUNTERWEIGHTS, FITTINGS AND DELIVERY
TO THE SITE. MATERIALS SHALL BE
GALVANIZED WITH POWDER COAT FINISH
TO THE REQUIREMENTS OF THE ASTM 53.
FITTINGS SHALL BE GALVANIZED WITH
POWDER COAT FINISH TO MEET ASTM
A153. RAILING ASSEMBLY SHALL BE
CAPABLE TO WITHSTAND A LOAD OF AT
LEAST 200 LBS. APPLIED IN ANY
DIRECTION AT ANY POINT ON THE TOP
RAIL.
1'-6"
EXISTING ROOF ASSEMBLY. SEE PLAN FOR AREAS TO BE
DEMOLISHED / REPLACED
EXISTING STRUCTURE / FACADE
" M
IN
IM
UM
2" HIGH PITCH POCKET COLLAR (FOUR SIDED W/
SOLDERED LAP SEAM JT. SECURE TO PLYWOOD
AND SET COLLAR IN A BED OF SEALANT
HENRY #208 (OR EQUAL) WET PATCH
ROOF CEMENT
ROOFING MATERIAL CAP SHEET TO RUN UP
UNDER SHEET METAL CAP
EXISTING ROOF
ASSEMBLY
EXISTING THERMAL
INSULATION
EXISTING ROOF
STRUCTURE
CANT
DETAIL STRIP EXTENDED 8" MIN.
VERTICAL AND 18" MIN.
ONTO FIELD OF EXISTING ROOF
PRESSURE TREATED WOOD NAILER
SEALANT
ANCHOR SUPPORT TO
DECK
0.031 THICK
STAINLESS STEEL
ENCLOSURE (4 SIDES)
W/ CONT. SOLDERED
LAP SEAM JT
18 GA. GALVANIZED STEEL SHEET METAL CAP.
CAP IS CONTINUOUS ACROSS ENTIRE CURB.
PROVIDE DOWN TURNED LEGS OVER EQUIPMENT
CURB. PROVIDE LAPPED AND SOLDERED SEAMS.
8" x 16 GA STUD FRAMING SECURED
TO CURB (EACH SIDE). COORDINATE
LOCATIONS WITH PITCH POCKET
PRE MANUFACTURED INSULATED EQUIPMENT
SUPPORT CURB. COORDINATE WITH
CONDENSER UNIT.
*CONTRACTOR TO FIELD
VERIFY ROOF INSULATION
THICKNESS AND ADD TO 24"
ABOVE FINISHED ROOF
REQUIREMENT FOR OVERALL
ROOF SUPPORT HEIGHT
" A
BO
VE
F
IN
IS
HE
D
RO
OF
TRIPLE EXPANDABLE FOAM INSULATION
CONDENSER UNIT; SECURED TO CURB
3/4" EXTERIOR GRADE PLYWOOD
SHEET METAL PLATE SCREW
ATTACHED TO UNDERSIDE OF
STRUCTURE TO HOLD FOAM IN
PLACE
2"
4" HEM FOLD PITCH POCKET ENCLOSURE
OVER COLLAR
NEW ROOF ASSEMBLY
TO MATCH EXISTING.
EXTEND MEMBRANE A
MIN. OF 24" ONTO FIELD
OF EXISTING ROOF
INSULATED REFRIGERANT PIPING
HIGH TEMPERATURE SELF-ADHERING BITUMINOUS
SHEET UNDERLAYMENT (CONT. UNDER MTL CAP /
EXTEND DOWN OVER FACE OF NAILER)
BITUMINOUS
MASTIC
141" (COORDINATE SIZE WITH FINAL EQUIP SELECTION)
4"
PITCH POCKET OPENING FOR
REFRIGERATION LINES
PITCH POCKET OPENING FOR
ELECTRICAL LINES
OUTLINE OF
REFRIGERATION RACK
120" RACK LENGTH 2"12"
8"
6"
6" 6"
4" 6"
F6
A-AE504
18 GA. GALVANIZED STEEL SHEET METAL CAP
OVER HIGH TEMPERATURE SELF-ADHERING
BITUMINOUS SHEET UNDERLAYMENT
2" HIGH PITCH
COLLARS WITH
WATER-TIGHT
SOLDERED
JOINTS
OP
EN
T
HR
U
OP
EN
T
HR
U
F6
A-AE504
SIM
8" x 16 GA STUD FRAMING
SECURED TO CURB (EACH
SIDE)
16" 3/4" EXTERIOR GRADE
PLYWOOD
NOTES:
1. EQUIPMENT SUPPORT CURB SHALL BE INSTALLED LEVEL AT 24" MIN. ABOVE TOP OF EXISTING ROOF SURFACE LEVEL.
2. COORDINATE PITCH POCKETS IN PLATFORM WITH FINAL EQUIPMENT SELECTION.
3. SHEET METAL CAP SHALL BE FABRICATED TO BE WATER TIGHT WITH CONT. SOLDERED JOINTS.
4. AFTER INSTALLATION OF RACK, ELECTRICAL CONNECTIONS AND REFRIGERANT LINE CONNECTIONS, THE PITCH POCKETS SHALL BE COMPLETELY
FILLED WITH EXPANDED FOAM AND CAPPED WITH ROOF SEALANT FOR A WATERTIGHT SEAL.
SECTION VIEW
E9
A-AE504
D9
A-AE504
F6
A-AE504
MAX
LINE OF INTERIOR FACE OF EQUIPMENT SUPPORT
CURB BELOW
3 1/2" 3 1/2"
" 29
3 1
/2"
3 1 /2"
INSULATED
EQUIPMENT
SUPPORT CURB
CO
OR
DI
NA
TE
S
IZ
E
W
IT
H
FI
NA
L E
QU
IP
S
EL
EC
TI
ON
" M
IN
PLAN VIEW - EQUIPMENT SUPPORT CURB
(SECURE TO CURB TO
RESIST WIND LOADS)F6
A-AE504
SIM
CONDENSING UNIT # 2;FUSIBLE DISCONNECT
FRONT SIDE
PLAN VIEW
FRONT VIEW - SECTION
AIR INTAKE
56"
12" 42" 2"
2"
NEW ROOF
ASSEMBLY; PATCH
/ REPAIR INTO
EXISTING
ASSEMBLY
INSULATED
REFRIGERATION
PIPING / CONNECTION56"x42" INSULATED
EQUIPMENT SUPPORT CURB
MINIMUM 6" CLEARANCE AT
REAR OF UNIT FOR FRESH
AIR INTAKE
CONDENSING UNIT # 2
POWER CONNECTION SEE
ELECTRICAL
(SECURE TO EQUIPMENT SUPPORT
CURB TO RESIST WIND LOADS)
ELECTRICAL
CONTROL PANEL
MAIN FUSIBLE
DISCONNECT
RAIN-TIGHT FLEXIBLE
CONDUITS
POWER FEEDER
WIRING CONDUIT
CONTROL CIRCUIT
WIRING CONDUIT
IINSULATED EQUIPMENT
SUPPORT CURB
NEW ROOF
ASSEMBLY;
PATCH /
REPAIR INTO
EXISTING
ASSEMBLY
MAIN FUSIBLE
DISCONNECT
ACCESS PANEL
REFRIGERATION LINES
TO RUN INSIDE OF RACK
AT THIS END
INSULATED EQUIPMENT
SUPPORT CURB
NEW ROOF
ASSEMBLY; PATCH /
REPAIR INTO
EXISTING
ASSEMBLY
6" 1'-
0"
23" 3"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA NY Manhattan Campus
423 E 23RD Street, New York, NY 10010
630-600A
Project Director
Revisions: Date:
A/E:
AECOM
3101 WILSON BLVD, SUITE 900
ARLINGTON, VA. 22201
703-682-4900
WWW.AECOM.COM
Construction Document Refresh
Key Plan
Balance of Work
9/12/2022 DZ JH / DZ
A-AE504
DETAILS - 4
SCALE: 3" = 1'-0"
3"0 6" 1'
FLASHING DETAIL
C6
SCALE: 3" = 1'-0"
3"0 6" 1'
DETAIL - PIPE PORTAL FLASHING SYSTEM
C3
SCALE: 3" = 1'-0"
3"0 6" 1'
DETAIL - DISCONNECT/ELECTRICAL DEVICE SUPPORT
F1
SCALE: 3/4" = 1'-0"
0 1' 2' 3'
SECTION - ENTRY
C1
SCALE: 1 1/2" = 1'-0" 0 1' 2'
DETAIL - ROOF EDGE PROTECTION
F4
SCALE: 1 1/2" = 1'-0" 0 1' 2'
ROOF CURB / PITCH POCKET DETAIL AT EQUIPMENT SUPPORT CURB
F6
1/2" = 1'-0" C8
PLATFORM DETAIL - CONDENSER UNIT #1
0 1'-0" 2'-0" 4'-0"
1/2" = 1'-0" D9
ELEVATION - ELECTRICAL CONTROL PANEL
0 1'-0" 2'-0" 4'-0"
1/2" = 1'-0" E9
ELEVATION - REFRIGERATION PIPING CONNECTION
0 1'-0" 2'-0" 4'-0"
1/2" = 1'-0" F9
PLATFORM DETAIL - CONDENSER UNIT # 2
0 1'-0" 2'-0" 4'-0"
BUT JOINT W/ CONTINUOUS
3/16" STEEL PLATE STRIP
WELDED TO SHEET
1"
3/16" HD GALVANIZED STEEL
PLATE WELDED TO ANGLE
FRAMING
CONT. 3 1/2" x 5" x 5/16" (LLH)
STEEL ANGLE W/ 1/2" 0 EPOXY
BOLTS AT 24" O.C. W/ 4" EMBEDMENT
LINE OF 3 1/2" x 5" x 5/16"
STEEL ANGLE WELDED TO
SEALANT
3 1/2" x 3 1/2" x 5/16" VERTICAL
STEEL ANGLE BEYOND AT 24" O.C..
COPE / WELDED TO HEAD AND
BASE ANGLES. WELD W/ 1/4" FILLET
WELD ALL AROUND
LINE OF EXISTING COLUMN
BEYOND
3 1/2" x 5" x 5/16" LLH
HEAD ANGLE (CONT.)
WELD TO L 6x6 W/ 1/4"
FILLET WELD ALL
AROUND
6" x 6" x 5/16" x 12" (L)
STEEL ANGLE WELDED
TO ANGLE AND TO
STRUCTURE AT 48" O.C.
MAX. W/ 2" LONG 1/4"
FILLET WELD MIN.
BRAKE METAL TRIM TO
MATCH EXISTING
EXISTING STEEL STRUCTURE (PAINTED
P-6 WHERE EXPOSED TO VIEW)
EXISTING METAL
PANEL
NOTE: ALL STEEL SHALL BE HD
GALVANIZED AND PAINTED P6
DOCK
+/- 8'-0"
-1
2'- 0"
(V .I.F
4"
STEEL COLUMN (BEYOND)
4" MIN EDGE
DIST.
FASTENERS PER SPECIFICATION
SECTION 10 28 00 REQUIREMENTS
FOR SUBSTRATE.
GRAB BAR
CONCEALED MOUNTING
FLANGE COVER PLATE - BEYOND
(SECURED W/ SETS SCREWS)
FLANGE / PLATE
1 1/2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA NY Manhattan Campus
423 E 23RD Street, New York, NY 10010
630-600A
Project Director
Revisions: Date:
A/E:
AECOM
3101 WILSON BLVD, SUITE 900
ARLINGTON, VA. 22201
703-682-4900
WWW.AECOM.COM
Construction Document Refresh
Key Plan
Balance of Work
9/12/2022
1 1/2" = 1'-0"F8 DETAIL - LOADING DOCK ENCLOSURE PANEL
0 6" 1'-0" 1'-6"
DETAILS - 5
A-AE505
DZ JH / DZ
B9 GRAB BAR MOUNTING DETAIL
3" = 1'-0"
0 3" 6" 9"
Hilti Firestop Systems Hilti Firestop Systems
System No. F-A-1016
SECTION A-A
FA
Page: 1 of 3
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
June 29, 2015
A
A
Page: 2 of 3
The firestop device and metallic penetrant shall be sized as follows:
System No. F-A-1016
FA
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
June 29, 2015
Nom Pipe Diam +, ++ Firestop Device
1-1/2 to 2-1/2 in.(38 to 64 mm) - Other than copper pipe or tubing CP680N-75/2.5"or CP682-75/2.5" 1-1/2 to 2 in.(38 to 51 mm) - Other than copper pipe or tubing CP 680-M 2", CP 680-P 2, CP 680-PX 2"
2 to 2-1/2 in. (51 to 64 mm) - Copper pipe or tubing CP680N-75/2.5"or CP682-75/2.5"
CP 680-M 2", CP 680-P 2", CP 680-PX 2"
2-1/2 to 3 in. (64 to 76 mm) CP 680-M 3", CP 680-P 3", CP 680-PX 3"
4 in. (102 mm) CP680N-110/4"or CP682-110/4"
CP 680-M 4", CP 680-P 4"
6 in. (152 mm)
CP680N-160/6"
CP 680-M 6", CP 680-P 6"
1. Floor Assembly — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
1A. Floor Assembly — (Optional, Not Shown)—The fire rated unprotected concrete and steel floor assembly shall be constructed of the materials and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below:
A. Concrete — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
B. Steel Floor and Form Units* — Composite or non-composite max 3 in. (76 mm) deep galv steel fluted units as specified in the individual
Floor-Ceiling Design.
2. Firestop Device* — Cast in place firestop device permanently embedded during concrete placement or grouted in concrete floor assembly in accordance with accompanying installation instructions. The devices may extend a max of 2 in. (51 mm) above the top surface of the concrete.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 680N-75/2.5", CP 680N-110/4", CP 680N-160/6", CP 682-75/2.5", CP
682-110/4", CP 680-M 2", CP 680-M 3", CP 680-M 4", CP 680-M 6", CP 680-P 2",
CP 680-P 3", CP 680-P 4", CP 680-P 6", CP 680-PX 2", CP 680-PX 3"
3. Through Penetrants — One metallic pipe, conduit or tubing to be installed within the firestop device. Pipe, conduit or tubing to be rigidly supported on both sides of floor assembly. The following types of pipe, conduit or tubing may be used:
A. Steel Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 6 in. (152 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit — Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit.
D. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing.
E. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
F. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular) or heavier copper pipe.
+ When metallic pipes of diameters smaller than those shown above are installed within the device, CP618 Firestop Putty Stick or mineral wool insulation shall be installed within the device.
++ L Rating applies only to CP 680-M and -P(X) devices and only when the nom diam of pipe equals size of device (2 in. diam pipe in 2" device etc.). L Rating does not apply to CP 680N and CP682 devices.
4. Fill, Void or Cavity Material* - Putty (Not Shown) — Min 1 in. (25 mm) thickness of fill material applied within annulus flush with top surface of device.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 618 Firestop Putty Stick
4A. Packing Material (Not Shown) — As an alternate to Item 4, min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3) mineral wool insulation firmly packed to the fullest extent possible within annulus flush with top surface of device.
4B. Firestop Device* - Top Seal Plug — (Optional. Not Shown) - Top seal plug for use with CP 680-M 2" and CP 680-P 2" devices and nom pipe, conduit or tubing sizes of 1/2 in. (13 mm) to 2 in. (51 mm) diam. Plug is friction fit into top of firestop device (Item 2) in accordance with the manufacturer's instructions. When top seal plug is used, no putty (Item 4) or packing material (Item 4A) is required. W Rating applies only to nom 1, 1-1/4, 1-1/2 and 2 in. (25, 32, 38 and 51 mm) diam copper pipe/tube in conjunction with 2" CPS Top Seal and CP 680-M 2" or CP 680-P(X) 2" devices.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CPS Top Seal Plug
Hilti Firestop Systems Page: 3 of 3
4B1. Firestop Device* - Water Barrier Module — (Optional, Not Shown) - Used as an alternate to the top seal plug (Item 4B) and in combination with the CP 680-M and CP 680-P(X) devices to achieve a W Rating. Module is threaded onto top of device. See Table below for sizes of device/module and penetrants covered. When water barrier module is used, a W Rating applies to the water barrier module, device and penetrant sizes specified in Table below. For W Rating with Water Barrier Module, pipe shall be installed from bottom of device.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — Water Barrier Module
Penetrant Type (See Item 3 above) Nom Penetrant Diam Size of Device/Module A, B, C, D 2" 2"
2-1/2" 3"
3" 3"
4" 4"
6" 6" E, F 2" 2"
3" 3"
4" 4"
6" 6"
System No. F-A-1016
FA
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
June 29, 2015
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
C
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Rating — 2 Hr F Rating — 2 Hr
T Rating — 0 Hr FT Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM/sq ft (See Item
3) FH Rating — 2 Hr
L Rating At 400 F — Less Than 1 CFM/sq ft (See Item 3) FTH Rating — 0 Hr
W Rating — Class 1 (See Items 4B and 4B1) L Rating At Ambient — Less Than 1 CFM/sq ft (See Item 3)
L Rating At 400 F — Less Than 1 CFM/sq ft (See Item 3)
Hilti Firestop Systems
System No. F-A-2025
FA
Page: 1 of 2
1. Floor Assembly — The fire-rated unprotected concrete and steel floor assembly shall be constructed of the materials and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below:
A. Normal Weight Concrete — Min 2-1/2 in. (64 mm) thickness of lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete topping as measured over the crests of the steel floor units.
B. Steel Floor and Form Units* — Composite or noncomposite 3 in. (76 mm) deep fluted galv units as specified in the individual Floor-Ceiling design. Max diam of opening core-drilled through floor assembly is 8 in. (203 mm).
2. Through Penetrants — One nonmetallic pipe to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe and periphery of opening shall be min 0 in. ( 0 mm, point contact) to max 1-1/2 in. (38 mm). Pipe to be rigidly supported on both sides of floor assembly. The following types and sizes of nonmetallic pipes may be used:
A. Polyvinyl Chloride (PVC) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid-core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 6 in. (152 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid-core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
D. Flame Retardant Polypropylene (FRPP) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed (process or supply) or vented drain, waste or vent) piping systems.
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 15, 2015
F Rating — 2 Hr T Rating — 2 Hr
SECTION A-A
B
A
B
A
5 2
6 1B 6
1A
SECTION B-B
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479
Hilti Firestop Systems Page: 2 of 2
3. Metal Plate Enclosure — Min 18 ga steel. Width of plate to be min 12 in. (305 mm). Length of plate (transverse to steel floor unit direction) to extend to steel floor unit valley beyond each side of core-drilled hole with a min lap of 1-1/2 in. (38 mm) on the floor unit valley at each end.
Both ends of plate perpendicular to floor unit valleys to be cut to permit the ends to be bent upwards 90 F deg to follow the contour of the floor unit, enclosing the packing material (Item 4) within the areas of the flutes. The contoured plate ends shall be such that the gap between the floor unit and the plate ends is no greater than 1/4 in. (6 mm). As an alternate to bending up ends of plate, min 1/4 in. (6 mm) thickness of fill material (Item 5) shall be applied to completely cover the surface of the mineral wool packing material within the flutes of the steel floor units, between the two ends of the metal enclosure plate and the steel floor units. Circular cutout in plate to tightly follow circumference of nonmetallic pipe with side edges of plate at least 3 in. (76 mm) from circular cutout on all sides. Slit made in plate to permit installation around the nonmetallic pipe to be located at end of plate beneath floor unit valley nearest to the circular cutout. Plate secured to valleys of floor unit using min 1/4 in. (6 mm) diam by 1-3/4 in. (45 mm) long steel expansion bolts, or equivalent, in conjunction with min 3/4 in. (19 mm) diam steel washers or min 0.145 in. (4 mm) diam by 1-1/4 in. (32 mm) long powder actuated fasteners utilizing a 1-7/16 in. (36 mm) diam by 1/16
in. (2 mm) thick steel washer. As alternates to the anchors specified above, Hilti 1/4 in. (6 mm) diam by 1-1/4 in. (32 mm) long KWIK-CON II+ concrete screw anchor, Hilti 1/4 in. (6 mm) diam by 1-3/4 in. (44 mm) long KWIK-BOLT 3 steel expansion anchor or Hilti X-DNI 27 P8 S15 powder actuated floor pin with integral nom 9/16 in. (15 mm) diam washer may be used . Fasteners to be located approx 1 in. (25 mm) from edges of plate at each corner, at each plate/valley intersection and at both sides of slit made to permit installation around nonmetallic pipe.
Spacing of fasteners no to exceed 10 in. (254 mm) OC.
4. Packing Material — Mineral wool batt insulation having min density of 4 pcf (64 kg/m3), firmly packed into flutes of steel floor units above metal plate enclosure (Item 3) to completely fill cavities. When ends of metal plate enclosure perpendicular to floor unit valleys are not bent up to enclose packing material within flutes (see Item 3), packing material to be recessed from ends of plate to accommodate the required thickness of the fill material.
5. Fill, Void or Cavity Material* — Sealant — Nom 1/2 in. (13 mm) bead of fill material applied around the perimeter of the metal plate enclosure at the interface of the enclosure and steel deck. When ends of metal plate enclosure (Item 3) are not bent up to enclose packing material within flutes, min 1/4 in. (6 mm) thickness of fill material shall be applied to completely cover the surface of the mineral wool packing material within the flutes of the steel floor units, between the two ends of the metal enclosure plate and the steel floor units.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant
6. Firestop Device* — Firestop Collar — Firestop collar shall be installed in accordance with the accompanying installation instructions. Collar to be installed and latched around the pipe and secured to the valley of the steel deck and to the metal plate enclosure using the anchor hooks provided with the collar. Min of two anchor hooks required for 1-1/2 and 2 in. (38 and 51 mm) diam pipes, min of three anchor hooks required for 3 and 4 in. (76 and 102 mm) diam pipes, and min of four anchor hooks required for 6 in. (152 mm) diam pipes. Where the anchor hooks are beneath the valley of the steel floor unit, the anchor tabs are to be secured with 1/4 in. (6 mm) diam by min 1-1/2 in. (38 mm) long steel expansion bolts, or equivalent, in conjunction with steel nuts and min 3/4 in. (19 mm) diam steel washers with one anchor bolt in each anchor hook. Where the anchor hooks are beneath the crest of the steel deck, the anchor hooks are to be secured to the metal enclosure with No. 10 by min 1/2 in. (13 mm) long self-drilling, self-tapping steel screws and min 3/4 in. (19 mm) diam steel washers.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 643 50/1.5"N, CP 643 63/2"N, CP643 90/3"N, CP 643 110/4"N or CP 643 160/6"N Firestop Collar.
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
System No. F-A-2025
FA
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 15, 2015
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479
Hilti Firestop Systems
System No. F-A-2053
SECTION A-A
FA
1. Floor Assembly — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
1A. Floor Assembly - (Optional - Not Shown) — The fire rated unprotected concrete and steel floor assembly shall be constructed of the materials and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below:
A. Concrete — Min 2-1/2 in (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
B. Steel Floor and Form Units* — Composite or non-composite max 3 in. (76 mm) deep galv steel fluted units as specified in the individual
Floor-Ceiling Design.
2. Firestop Device* — Cast in place firestop device permanently embedded during concrete placement or grouted in concrete assembly in accordance with accompanying installation instructions. The 3, 4 and 6 in. devices may extend a max 2 in. (51 mm) above the top surface of the concrete. The max extension above the slab for the 2 and 2.5 in. devices is not restricted.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 680-75/2.5"N, CP 680-110/4"N, CP 680-160/6"N, CP 680-P 2", CP 680-P 3", CP 680-P 4", CP 680-P 6", CP 680-PX 2", CP 680-PX 3"
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
June 29, 2015
F Rating — 2 Hr T Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM/sq ft (See Item 3) L Rating At 400 F — Less Than 1 CFM/sq ft (See Item 3)
W Ratings — Class 1 (See Items 3, 4 and 4A)
A
Page: 1 of 2
2 3
CL
ASS I F IED
Classified by Underwriters Laboratories, Inc.
to UL 1479
Hilti Firestop Systems
System No. F-A-2058
SECTION A-A
FA
1. Floor Assembly — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Max diam of opening is 4 in. (102 mm).
1A. Floor Assembly — (Optional — Not Shown) — The fire-rated unprotected concrete and steel floor assembly shall be constructed of the materials and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below:
A. Concrete — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
B. Steel Floor and Form Units* — Composite or non-composite max 3 in. (76 mm) deep galv steel fluted units as specified in the individual
Floor-Ceiling Design. Max diam of opening is 4 in. (102 mm).
2. Through Penetrants — One nonmetallic pipe to be installed concentrically or eccentrically within the firestop system. Annular space between pipe or conduit and edge of opening to be min 3/8 in. and max 1 in. (9.5 to 25 mm). Pipe to be rigidly supported on both sides of floor-ceiling assembly.
The following types and sizes of nonmetallic pipes or conduits may be used:
A. Polyvinyl Chloride (PVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
3. Fill, Void or Cavity Materials*-Sealant — Min 2-1/2 in. (64 mm) thickness of sealant applied within annular space, flush with top surface of floor.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant.
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 15, 2015
F Rating — 2 Hr T Rating — 0 Hr
A
1 2
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479
Nom Pipe Diameter Firestop Device
1/2 in. to 2 in. (19 mm to 51 mm)
CP 680-75/2.5"N
CP 680-P 2" CP 680-PX 2"
3 in. (76 mm) CP 680-P 3" CP 680-PX 3"
3 in. to 4 in. (76 mm to 102 mm)
CP 680-110/4"N
CP 680-P 4"
6 in. (152 mm)
CP 680-160/6"N
CP 680-P 6"
Hilti Firestop Systems
System No. F-A-2053
FA
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
June 29, 2015 Page: 2 of 2
++ L Rating applies only to CP 680-P(X) devices and only when the nom diam of pipe equals size of device (2 in. diam pipe in 2" device etc.) L Rating does not apply to CP 680N devices.
4. Firestop Device* — (Not shown) -Top Seal Plug for use with CP 680-P(X) 2" device Installed in accordance with the manufacturer's instructions.
The Top Seal Plug is optional for nom 1-1/2 in. (38 mm) pipes and conduits. Top Seal Plugs are required for all pipes and conduits less than nom 1-1/2 in. (38 mm). W Rating applies only to the IPS Top Seal Plug and nom 2 in. diam penetrants, and to CPS Top Seal Plugs with nom 1/2 to 2
in. (13 to 51 mm) diam penetrants.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CPS and IPS Top Seal Plugs
4A. Firestop Device* - Water Barrier Module — (Optional, Not Shown) - Used as an alternate to the top seal plug (Item 4). Applies to nom 2", 3", 4" and 6" water barrier modules used in combination with the CP 680-P(X) 2", CP 680-P(X) 3", CP 680-P 4" CP 680-P 6" devices, respectively, and supplied by device manufacturer. Module is threaded onto top of device. W Rating applies only when water barrier module is used and nom diam of penetrant equals size of device.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — Water Barrier Module
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
+Bearing the UL Listing Mark
3. Through Penetrants — One nonmetallic pipe or conduit to be installed within the firestop system. Pipe or conduit to be rigidly supported on both sides of floor assembly. For W Rating with Water Barrier Module, pipe shall be installed from bottom of device. The following types and sizes of nonmetallic pipes or conduits may be used:
A. Polyvinyl Chloride (PVC) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 6 in. (152 mm) diam (or smaller) SDR11 or SDR13.5 CPVC pipe for use in closed (process or supply) piping systems.
C. Rigid Nonmetallic Conduit+ — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA No. 70).
The firestop devices and nonmetallic penetrants shall be sized as follows:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
ISSUED FOR
CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA NY Manhattan Campus
423 E 23RD Street, New York, NY 10010
630-600A
Project Director
Revisions: Date:
A/E:
AECOM
3101 WILSON BLVD, SUITE 900
ARLINGTON, VA. 22201
703-682-4900
WWW.AECOM.COM
Construction Document Refresh
Key Plan
Balance of Work
9/12/2022
A-AE506
FIRESTOPPING DETAILS - 1
DZ JH / DZ
1. Refer to the following specifications for firestopping.
a. 07 84 00 Firestopping
b. 21 21 13 Wet-pipe Sprinkler Systems
c. 21 13 16 Dry-pipe Sprinkler Systems d.Division 22 00 00 Plumbing (all sections) e.Division 23 00 00 HVAC (all sections)
f. Division 26 00 00 Electrical (all sections)
g. 27 05 33 Raceways and Boxes for Communication Systems
h. 28 31 00 Fire Detection and Alarm
For Quality Control requirements, refer to the Quality Assurance portion of the specification.
2. Manufacturer's trade names and UL assembly used here-in are only to identify basis of design / level of performance requirements required.
Products of other manufacturer's equivalent to basis of design / performance requirements that meet requirements of the technical specification will be acceptable once submitted / approved as a shop drawing submittal.
3. Details shown are typical details and are not meant to be inclusive of all field conditions that may be present.
Contractor shall submit additional firestop system assemblies for penetrations through rated construction as required for review and approval.
4. Details shown are typical details.
Always refer to the listed system detail for complete system requirements. If field conditions do not match requirements of details, approved alternate details shall be utilized / submitted for review / approval. Design requirements, field conditions and dimensions need to be verified for compliance with the details, including but not limited to the following:
* Fire Rating (F-Rating)
* Leakage Rating (L-Rating)
* Water Rating (W-Rating)
* Annular Space
* Percent Fill
* Movement
* Type and thickness of fire-rated construction.
4. If alternate details matching the field conditions are not available, manufacturer's engineering judgment drawings are acceptable subject to approval by the Authority Having Jurisdiction (AHJ). Contact Hilti Inc. for alternative systems or Engineering Judgment (800-879-8000). Drawings shall follow the International Firestop Council (IFC) Guidelines for Evaluating Firestop Systems Engineering Judgments.
5. References:
* 2017 Underwriter's Laboratories
Fire Resistance Directory, Volumes 1 & 2.
* NFPA 101 Life Safety Code
* NFPA 70 – National Electric Code
* All governing local and regional building codes.
6. Systems C-AJ-3095, C-AJ-3216 and C-AJ-3283 are permitted for use at existing cables thru new construction only. All new cables passing thru new walls use system C-AJ-3285.
7. Firestop System installation must meet requirements of ASTM E-814 (UL 1479) tested assemblies that provide a fire rating equal or greater to that of construction being penetrated.
8. Systems W-L-5028, W-L-1054, W-L-1389, W-L-3396 and W-L-8079 are permitted for use at existing pipes and cables through new GWB construction only. All new pipes and cables through new GWB walls shall use W-L-2078, W-L-2128 and W-L-3334.
9. During construction all empty core holes through elevated floor slabs are required to be temporarily closed.
Provide Hilti CFS-PL Firestop Plug or Hilti CFS-BL Firestop Block /approved equal sized for core hole. Plugs are to be provided immediately after core hole has been created and be maintained until core is in-filled with it's intended penetrant.
10. All pipe and conduit through -slab penetration…
This is the start of the file's text. The full file is on GovTribe.