C-Architecture- Part 4.pdf
PDF 3 MB Posted
- Solicitation number
- QSE--36C10F24R50018
About this file
This document appears to be a set of construction drawings and details related to a federal contract opportunity to construct the Manhattan Hurricane Sandy Recovery Program Balance of Work at the VAMC Manhattan Campus of the VA NY Healthcare System.
The key details include:
- The construction drawings provide detailed design information and technical specifications for various components of the project, including electrical equipment, concrete pads, chain link fences, firestopping assemblies, expansion joints, and pipe and conduit penetration details.
- The project involves renovations and new construction at the VA NY Manhattan Campus located at 423 E 23rd Street, New York, NY.
- The contract opportunity is solicitation number QSE--36C10F24R50018, named "36C10F24R50018 Balance of Work VAMC Manhattan, NY -- Y1DA".
- The work is being procured by the Department of Veterans Affairs Office of Construction and Facilities Management.
View the file
Other files
Show 40 more
Latest 50 of 281 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
6'-
ELECTRICAL EQUIPMENT - SEE ELECTRICAL
T.O. MAIN ELECTRICAL ROOM
FLOOR SLAB EL. +23'-0" (VIF)
2 LAYERS OF 58" TYPE X
GWB,TAPED AND SPACKLED
STEEL STUD. 2-1
2", # 20 GA. STL.
CH STUDS @ 16" O.C.
1" GWB SHAFTWALL LINER
INTUMESCENT SEALANT AND
BACKER ROD OR FIRE-STOP SPRAY
AT INTERFACE JOINT (ALL SIDES) T.O. EXISTING ROOF SLAB
EL. +/- 21'-0"
EXISTING CONC ENCASED STEEL BEAM /
LIGHTWEIGHT CONCRETE ROOF SLABSTEEL FRAMING AT
OPENING WITH 2 HR
SFRM AT ENTIRE
ASSEMBLY - SEE
STRUCTURAL
CUTOUT / REMOVAL OF
EXISTING ROOF SLAB.
COORDINATE OPN'G
SIZE WITH ELECTRICAL
CONDUITS - SEE
ELECTRICAL FOR
QUANTITY AND SIZE
14 GA. STEEL PLATE WITH
PRE-CUT KNOCKOUTS FOR
CONDUITS. SECURED TO
DECK.
"FIRE BARRIER" PARTITION
IDENTIFICATION (ALL WALLS)
CONDUIT SUPPORT AS REQUIRED.
SUPPORTS SHALL BE HUNG FROM
INDEPENDENT STEEL FRAMING
ASSEMBLIES FROM EXISTING BLDG
STEEL / NOT EXISTING ROOF DECK
2 HOUR THROUGH PENETRATION
FIRESTOP ASSEMBLY SYSTEM NO.
C-AJ-8114 (OR APPROVED EQUAL)
MINIMUM 3.5" FIRESTOP
MORTAR INFILL
POUR STOPCONDUIT OR PIPE FULLY
SUPPORTED
INTUMESCENT SEALANT
WITH MINERAL WOOL
BACKING
SINGLE PENETRATION -
2 HOUR THROUGH
PENETRATION FIRESTOP
ASSEMBLY SYSTEM F-A-1093
(OR APPROVED EQUAL)
CUTOUT IN
SLAB
4"
2 HR FIRE RESISTANCE
RATING UL NO. U415
"J" TRACK
NOTE: CONDITIONS / OPENING SIZES VARY PER SLAB OPENING
AREA. DESIGN INTENT IS TO PROVIDE 2 HR PROTECTED STEEL
AND A 2 HR RATED SHAFTWALL ENCLOSURE AT THE OPENING(S)
TO ISOLATE INTERSTITIAL SPACE BETWEEN THE SLABS.
STEEL FRAMING CONNECTION TO
EXISTING CONC ENCASED STEEL BEAM ;
SEE STRUCTURAL FOR REQUIREMENTS
STEEL FRAMING AT OPN'G
WITH 2 HR PROTECTION
(UL NO. N307) AT ENTIRE
ASSEMBLY - SEE STRUCT
8"
CONCRETE PAD; SEE DETAIL D5 / C-AE504
4"
VI
F
4"
3 4"
6" SEE ELECTRICAL DRAWING 6"
6"
SE
E
EL
EC
TR
IC
AL
DR
AW
IN
G
6"
8"
6" 8"
3"
AL
IG
N
1'- 0"
11 2" 1'-
0"3'- 6"
EQ 1'-4" EQ
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
ISSUED FOR
CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA NY Manhattan Campus
423 E 23RD Street, New York, NY 10010
630-600A
Project Director
Revisions: Date:
A/E:
AECOM
3101 WILSON BLVD, SUITE 900
ARLINGTON, VA. 22201
703-682-4900
WWW.AECOM.COM
Construction Document Refresh
1 & GEN PLTFRM
Key Plan
Balance of Work
9/12/2022
BUILDING 1 - TYP. 2 HR OCCUPANCY SEPARATION - NEW WORK
F3
TYPICAL UL RATED FLOOR DECK ASSEMBLY DETAILS - NEW WORK
B8
C-AE504
BUILDING 1 - DETAILS 4
DZ JH / DZ
BUILDING 1 - CHAIN LINK FENCE PANEL - SECTION
D8
BUILDING 1 - CHAIN LINK FENCE PANEL - PARTIAL ELEVATION
F8
HORIZONTAL 2 HOUR RATED ENCLOSURE DETAIL - INTERIOR
B1
BUILDING 1-TYPICAL FIRESTOP / OPENING DETAIL
E1
CONCRETE PAD DETAIL
B6
CONCRETE PAD DETAIL
D5
DETAIL - FALL PROTECTION GUARD
F1
F6
BUILDING 1 - TYP. 2 HR COLUMN - NEW WORK
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING ROOF SLAB
AutoCAD SHX Text UL DESIGN NO. N307 / D929 RESTRAINED BEAM RATING = 2 HRS UNRESTRAINED BEAM RATING = 2 HRS UNRESTRAINED CHANNEL BEAM RATING (W/D .59) = 2 HRS STEEL BEAM OR CHANNEL (SEE STRUCTURAL DWGS.) LIGHTWEIGHT CONCRETE (SEE STRUCTURAL DWGS.) WELDED WIRE FABRIC (SEE STRUCTURAL DWGS.) SHEAR CONNECTOR (SEE STRUCTURAL DWGS.) STEEL FLOOR AND FORM UNITS (SEE STRUCTURAL DWGS.) MINERAL AND FIBER BOARDS (THICKNESS PER RATING) NOGGINGS FASTENERS MINERAL WOOL AT FLUTES (4# CUBIC FT MIN DENSITY)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
VAULT 1 FLOOR SLAB
AutoCAD SHX Text UL DESIGN No. D916 RESTRAINED ASSEMBLY RATING = 2 HRS UNRESTRAINED BEAM RATING = 2 HRS 1 LIGHTWEIGHT CONCRETE (SEE STRUCTURAL DRAWINGS) LIGHTWEIGHT CONCRETE (SEE STRUCTURAL DRAWINGS) 2 WELDED WIRE FABRIC = (SEE STRUCTURAL DWGS.) WELDED WIRE FABRIC = (SEE STRUCTURAL DWGS.) 3 STEEL FLOOR AND FORM UNITS - (SEE STRUCTURAL DRAWINGS) STEEL FLOOR AND FORM UNITS - (SEE STRUCTURAL DRAWINGS) 4A SPRAY-APPLIED FIRE RESISTIVE MATERIALS SPRAY-APPLIED FIRE RESISTIVE MATERIALS (SPRAY THE AREA BETWEEN BEAM TOP FLANGE AND STEEL DECK) 5 SHEAR-CONNECTOR STUDS (SEE STRUCTURAL DRAWINGS) SHEAR-CONNECTOR STUDS (SEE STRUCTURAL DRAWINGS)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 4A
AutoCAD SHX Text
AutoCAD SHX Text
STEEL BEAM (SEE STRUCTURAL DRAWINGS)
AutoCAD SHX Text
EXISTING WIRE FENCE FABRIC
AutoCAD SHX Text
EXISTING TOP RAIL BEYOND
AutoCAD SHX Text
EXISTING WIRE FENCE FABRIC
AutoCAD SHX Text
EXISTING TERMINAL POST BEYOND (TYP.)
AutoCAD SHX Text EXISTING BOTTOM RAIL 1 " x .047" 58" x .047" (TYP.)
AutoCAD SHX Text "A"
AutoCAD SHX Text "A"
AutoCAD SHX Text
ALUM. "U" TRIM (WELDED 90DEG CORNERS),ALL SIDES
AutoCAD SHX Text PERFORATED ALUM. (3003 H14) " ROUND 332" ROUND HOLES X " 316" STAGGERED PITCH X .050 THICK, CLOSED FINISH END PATTERN (23% OPEN AREA)
AutoCAD SHX Text
SCHEDULED WALL MTD LIGHT FIXTURE
AutoCAD SHX Text
EXISTING CHAIN LINK INTERMMEDIATE POST
AutoCAD SHX Text
DETAIL "A-A"
AutoCAD SHX Text
ALUM. "U" TRIM (ALL SIDES)
AutoCAD SHX Text PERFORATED ALUM. PANEL (3003 H-14) " ROUND 332" ROUND HOLES X " STAGGERED PITCH 316" STAGGERED PITCH X .050 THICK X CLOSED "FINISHED" END PATTERN (28% OPEN AREA)
AutoCAD SHX Text
BOLT/NUT ASSEMBLY THROUGH "U" TRIM
AutoCAD SHX Text
STL PLATE POST BAND (HD. GALV.) SECURED TO POST, EACH SIDE
AutoCAD SHX Text
EXISTING WIRE FENCE FABRIC
AutoCAD SHX Text
NOTE: COORDINATE POST BAND FABRICATION WITH EXISTING CONDITIONS
AutoCAD SHX Text NOTE: THIS IS AN EXISTING CHAIN LINK FENCE WITH A "NEW" PERFORATED PANEL OVERLAY ASSEMBLY
AutoCAD SHX Text
ALUM. TWIN DIVIDER TRIM WELDED TO PERIMETER "U" TRIM
AutoCAD SHX Text
HD. GALV. STL. PLATE POST BAND BRACKET (ALL SIDES)
AutoCAD SHX Text
C-AE504
AutoCAD SHX Text D8
AutoCAD SHX Text
ALUM. "U" TRIM W/ WELDED CORNERS
AutoCAD SHX Text PERFORATED ALUM. PANEL (3003 H-14) " 332" ROUND HOLES X " 316" STAGGERED PITCH X .050 THICK X CLOSED "FINISHED" END PATTERN (28% OPEN AREA)
AutoCAD SHX Text NOTE: THIS IS AN EXISTING CHAIN LINK FENCE WITH A "NEW" PERFORATED PANEL OVERLAY ASSEMBLY
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
VERIFY REQUIRED DISTANCE IN FIELD AFTER ELEC. CONDUITS ARE INSTALLED
AutoCAD SHX Text
VARIES (7'-2" MAX. WIDTH)
AutoCAD SHX Text
VERIFY REQUIRED DISTANCE IN FIELD AFTER ELEC. CONDUITS ARE INSTALLED
AutoCAD SHX Text
1" SHAFTLINER
AutoCAD SHX Text 2 " x 25 GA I-STUD 12" x 25 GA I-STUD 24" O.C.
AutoCAD SHX Text
J TRACK
AutoCAD SHX Text
EXISTING FLOOR SLAB
AutoCAD SHX Text
1/2" GWB (TYPE 'X') - 3 LAYERS AT HORIZONTAL AND 2 LAYERS AT VERTICAL SIDES
AutoCAD SHX Text
POWER DRIVEN FASTENERS @ 24" O.C.
AutoCAD SHX Text ELEC. CONDUITS AND RACK SUPPORT, SEE ELECTRICAL DETAILS FOR SUPPORT / ASSEMBLY REQUIREMENTS
AutoCAD SHX Text
CONT. INTUMESCENT SEALANT
AutoCAD SHX Text
J TRACK
AutoCAD SHX Text
PAINT ALL SIDES OF ENCLOSURE P-8.
AutoCAD SHX Text NOTE: REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS / ROUTE OF CONDUITS REQUIRING RATED ENCLOSURE
AutoCAD SHX Text
TEST ASSEMBLY: WHI 694-0300.1 (SIM)
AutoCAD SHX Text
CONCRETE PAD
AutoCAD SHX Text
CONCRETE PAD
AutoCAD SHX Text
CHAMFERED CORNER (ALL SIDES)
AutoCAD SHX Text
POURED REINFORCED CONCRETE PAD (SEE STRUCTURAL DRAWINGS)
AutoCAD SHX Text
EPOXY DOWELS; SEE STRUCTURAL FOR REQUIREMENTS
AutoCAD SHX Text
NEW OR EXISTING CONCRETE SLAB TO REMAIN
AutoCAD SHX Text
PAINT P-7 SAFETY YELLOW (MIN 4 WEEKS AFTER POURING PAD)
AutoCAD SHX Text
ELECTRICAL / HVAC EQUIPMENT SEE ELECTRICAL / MECHANICAL DRAWINGS
AutoCAD SHX Text
C-AE504
AutoCAD SHX Text B6
AutoCAD SHX Text
PLAN
AutoCAD SHX Text
ELEVATION
AutoCAD SHX Text
REMOVABLE GUARD - 1 " O 12" O STEEL PIPE PAINTED SAFETY YELLOW
AutoCAD SHX Text
SIGN TYPE IN-01.21B SECURED WITH FASTENERS TO PLATE
AutoCAD SHX Text
18" STEEL PLATE WELDED TO PIPE RAIL (PTD)
AutoCAD SHX Text
2" O STEEL PIPE SLEEVE WELDED TO PLATE
AutoCAD SHX Text
12" BOLT AND NUT (EACH SIDE)
AutoCAD SHX Text
FINISHED FLOOR
AutoCAD SHX Text 38" STEEL PLATE WITH (4) " O EXPANSION 12" O EXPANSION BOLTS. 4" MINIMUM EMBEDMENT. PAINT SAFETY YELLOW
AutoCAD SHX Text
FACE OF WALL / OPENING
AutoCAD SHX Text UL DESIGN NO. X313 COLUMN RATING = 2 HRS STEEL COLUMN (SEE STRUCTURAL DWGS.) MINERAL AND FIBER BOARDS NOGGINGS FASTENERS NOTE: DETAIL IS APPLICABLE TO PORTIONS OF STEEL COLUMNS BETWEEN THE EXISTING ROOF SLAB AND THE "NEW" VAULT 1 SLAB
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F I R S T A V E N U E
AutoCAD SHX Text A S S E R L E V Y P L A C E
AutoCAD SHX Text E A S T 2 3 r d. S T R E E T
AutoCAD SHX Text
BLDG 3
AutoCAD SHX Text
BLDG 2
AutoCAD SHX Text
BLDG 4 / 5
AutoCAD SHX Text
E A S T 25 TH STREET
AutoCAD SHX Text
BLDG 1
AutoCAD SHX Text N
AutoCAD SHX Text
BLDG 6
AutoCAD SHX Text
SCALE: 1 1/2" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text
SCALE: 1 1/2" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text
SCALE: 3/4" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 3'
AutoCAD SHX Text
SCALE: 3/4" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 3'
AutoCAD SHX Text
SCALE: 1 1/2" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text
SCALE: 3/4" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 3'
AutoCAD SHX Text
SCALE: 1 1/2" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text
SCALE: 1 1/2" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text
SCALE: 1" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text
NTS
REGLET AND FLASHING AS REQUIRED
SEALANT
4" x 1 34" SS MASONRY ANCHOR
WITH SEALING WASHER 16" OC.
EXPANSION JOINT (TYPE EJ-1/SRJW-500 W/FB)
CONTINUOUS MOISTURE SEAL
4" x 2 " SS LAG SCREW W/ SEALING WASHER 16" OC
CONTINUOUS EXTRUDED ALUMINUM FRAME
2 HOUR FIRE BARRIER
16" WIDE POLYETHYLENE VAPOR BARRIER
PT WOOD BLOCKING
9 14"
5"
4"
EXISTING MASONRY WALL ASSEMBLY (2 HOUR RATING)
8" STAINLESS STEEL PLATE CEJ-3 / PCW-S)
4" x 1 34" SS MASONRY ANCHOR 16" OC
3 4" FACTORY APPLIED SILICONE
FACE (COLOR: DECK GRAY)
FIELD APPLIED SILICONE CORNER BEAD
FIELD APPLIED EPOXY ADHESIVE
(EACH SIDE)
PRECOMPRESSED FIRE RETARDANT IMPREGNATED FOAM (TYPE EJ-3 / 2HR RATING)
1 4"
3"
4"
4"
CONCRETE ON METAL DECK
FLOOR SLAB (2 HOUR RATING)
2 HOUR EXTERIOR WALL ASSEMBLY
EXPANSION JOINT (TYPE EJ-2 / SF500)
2 HOUR FIRE BARRIER
PRE-FINISHED BRAKE METAL PLATE
CLOSURE TRIM
EXISTING MASONRY WALL
CONSTRUCTION (2 HOUR RATING)
(2) LAYERS 58" GYPSUM SHEATHING RETURN
8" SS COVER PLATE (TYPE EJ-2 / PCW-S)
SECURED WITH 14" x 1 34" MASONRY
ANCHOR AT 18" OC
4"3"
1'- 07 8"
5"
CONTINUOUS SECONDARY
SEAL
5" x 5" x 5
16" STEEL ANGLE
WELDED TO STEEL TUBE
(FULL HEIGHT OF
EXPANSION JOINT)
1 12" STEEL WALL PANEL
4" x 4" x 14" STEEL TUBE
PRE-FINISHED BRAKE
METAL CLOSURE TRIM
EXPANSION JOINT (TYPE
EJ-5 / SC-700). EXPANSION
JOINT TO EXTEND BEHIND
SRJ-700 AT DOOR ABOVE
3" 3" 7"
1"
NOTE: ALL STEEL TO BE
HOT DIPPED GALVANIZED
FLOOR EXP JOINT
COVER PLATE EJ-6
BELOW
31 2"
1'-2 12"
LINE OF FLOOR EXP
JOINT BELOW
4"
VERTICAL RAILING POST
EXPANSION JOINT (TYPE EJ-4 / SRJ-700)
PRE-FINISHED TO MATCH METAL PANEL
PRE-FINISHED METAL FLASHING. EXTEND
UNDER EXPANSION JOINT MOUNT
4" STEEL PLATE WELDED TO ANGLES
4" x 4" x 5
16" STEEL ANGLE WITH
CLIP ANGLES TO STEEL TUBE
2 12" x 9 12" x 5
16" BENT STEEL PLATE
(CONT)- WELD TO STEEL TUBE
1 12" STEEL ROOF PANEL
6" x 4" x 5
16" STEEL ANGLE
SECURED TO STEEL TUBE
(BEYOND)
4" x 4" x 14" STEEL TUBE
VERTICAL TRANSITION COVER OVER
SC-700 / EXP JT EJ-5 BEYOND
SECONDARY MOISTURE BARRIER
NOTE: ALL STEEL SHALL BE
HOT DIPPED GALVANIZED
1'-41 2"
45°
3" 7" 3"
11 2" 4"
EXPANSION JOINT(TYPE EJ-6 / PC-S)
(SECURE AT ONE SIDE ONLY)
7"
STEEL FRAMING
8" GALV STEEL DIAMOND FLOOR PLATE
SECUREMENT PER MFG. STD (ONE SIDE ONLY)
FORMED ALUMINUM ROOF END
CAP AT TRANSITION TO WALL
COVER
NOTE: VAPOR BARRIER OF ROOF
COVER TO BE DRAPED INTO THE
SECONDARY SEAL OF THE WALL
COVER AT ROOF LEVEL OR SLIGHTLY
BELOW TO DIVERT WATER DOWN THE
VERTICAL.
6"
6"
1 1/2"
EXPANSION JOINT
EJ-1 / SRJW-500 W/FB
SBS ROOF ASSEMBLY
EXPANSION JOINT EJ-2
(EXTERIOR) ASSEMBLY
SEE DETAIL D9 / C-AE505
EXISTING MASONRY WALL
FORMED ALUMINUM
SPLICE COVER
EXP JT EJ-1
(SRJW-500
W/FB ROOF
COVER)
12"
6"
FACE OF PARAPET
WALL
EXP JT EJ-4B
(SRJ-1200 MOD W/ FB
ROOF COVER)
FLASHING OVER
EXPANSION
JOINT COVER
12"
" (VIF)
24"
THE LEADING EDGE / FACE OF
THE SRJW-500 AND THE SRJ-1200
MOD ROOF COVERS SHALL ALIGN.
FIELD VERIFY ALL DIMENSIONS.
FACE OF
PLYWOOD
EXP JT EJ-2 (SF-500)
WALL COVER
EXP JT EJ-4B
(SRJ-1200
MOD - W/FB)
ROOF COVER
FACTORY FABRICATED
ALUMINUM ENDCAP
NOTE: VAPOR BARRIER OF ROOF
COVER TO BE DRAPED INTO THE
SECONDARY SEAL OF THE WALL
COVER AT ROOF LEVEL OR SLIGHTLY
BELOW TO DIVERT WATER DOWN THE
VERTICAL.
6"
6"
METAL PANEL AS
SCHEDULED
PRE-FINISHED METAL
FASCIA BELOW
24"
PRE-COMPRESSED FIRE RETARDANT
IMPREGNATED FOAM - CONTINUOUS @
HORIZONTAL AND VERTICAL JOINT - EJ-3 (2 HR)
8" FRT PLYWOOD
RETURN FACE BRICK TO CLOSE OFF CAVITY
METAL PANEL - REMOVED AS NECESSARY
FOR NEW CONSTRUCTION
PRE-FINISHED BRAKE METAL TRIM
TO MATCH EXISTING METAL PANEL
SEALANT AND BACKER ROD
1 12" MINERAL WOOL INSULATION BOARD
CMU - 8" & 6" (REINFORCED &
GROUTED)
FACE BRICK TO MATCH EXISTING
1"
2"
CAP SCREW WITH
SEALING WASHER
CONTINUOUS MOISTURE
SEAL
FORMED ALUMINUM COVER
PLATE
4" x 2" S/S LAG SCREW
CONTINUOUS EXTRUDED
ALUMINUM FRAME
PRE-FINISHED METAL
FASCIA WITH CLEATS
PRESSURE TREATED
WOOD BLOCKING (CONT)
SPRING STEEL TURN BAR
2 HOUR FIRE BARRIER
SECONDARY MOSTURE
BARRIER
24"
EXISTING MASONRY WALL
ASSEMBLY (2 HOUR RATING)
1/4" x 1 3/4" MASONRY ANCHOR 18" O.C.
3 4"
4"
1/8" STAINLESS STEEL COVER PLATE - PCW-S
(FULL HEIGHT OF WALL)
MODEL RFX-3W FIRE BARRIER (1 HR MIN.)
UL# WW-D-1068 (CMU)
1 HR RATED PARTITION AS SCHEDULED
3"
MODEL RFX-3W FIRE BARRIER 2 HOUR - SEE SPEC.
UL# WW-D-1067 (GWB)
2 HR RATED PARTITION AS SCHEDULED; WRAP
RETURN GWB AT PARTITION TERMINATION
1/4" x 1 3/4" MASONRY ANCHOR 18" O.C.
1/8" STAINLESS STEEL COVER PLATE - PCW-S
(FULL HEIGHT OF WALL)
EXISTING MASONRY WALL
ASSEMBLY (2 HOUR RATING)
3 4"
4"
3"
6"x4"x3/8" STL ANGLE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
ISSUED FOR
CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA NY Manhattan Campus
423 E 23RD Street, New York, NY 10010
630-600A
Project Director
Revisions: Date:
A/E:
AECOM
3101 WILSON BLVD, SUITE 900
ARLINGTON, VA. 22201
703-682-4900
WWW.AECOM.COM
Construction Document Refresh
1 & GEN PLTFRM
Key Plan
Balance of Work
9/12/2022
C-AE505
DZ JH / DZ
DETAIL - ROOF TO WALL EXPANSION JOINT (EJ-1)
B8
DETAIL - FLOOR TO WALL EXPANSION JOINT (EJ-3)
F9
DETAIL - WALL TO WALL EXPANSION JOINT (EJ-2)
D9
DETAIL - WALL TO WALL EXPANSION JOINT (EJ-5)
D7
DETAIL - ROOF TO ROOF EXPANSION JOINT (EJ-4)
B6
DETAIL - FLOOR TO FLOOR EXPANSION JOINT (EJ-6)
F7
ISOMETRIC DETAIL - EJ-2 (EXTERIOR) TO EJ-1
B4
BUILDING 1 & GENERATOR
PLATFORM - DETAILS 5
ISOMETRIC DETAIL - EJ-1 TO EJ4B
B1
ISOMETRIC DETAIL - EJ--4B TO EJ-2
D1
DETAIL - WALL TO WALL EXP JT (EJ-3)
D4
DETAIL - ROOf TO ROOF EXPANSION JOINT (EJ-4B)
F1
DETAIL - WALL TO WALL EXPANSION JOINT (EJ-7)
F3
DETAIL - WALL TO WALL EXPANSION JOINT (EJ-8)
F5
AutoCAD SHX Text F I R S T A V E N U E
AutoCAD SHX Text A S S E R L E V Y P L A C E
AutoCAD SHX Text E A S T 2 3 r d. S T R E E T
AutoCAD SHX Text
BLDG 3
AutoCAD SHX Text
BLDG 2
AutoCAD SHX Text
BLDG 4 / 5
AutoCAD SHX Text
E A S T 25 TH STREET
AutoCAD SHX Text
BLDG 1
AutoCAD SHX Text N
AutoCAD SHX Text
BLDG 6
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
1'
S.S. FASTENERS WITH
NEOPRENE GASKET @ 12" O.C.
ROOF ASSEMBLY
(SEE DETAIL B1/C-AE571)
2 PLIES COVER STRIP
CANT STRIP
ABS COVER
INSULATED PREFABRICATED
METAL ROOF CURB WITH CANT
(ALL SIDES)
MECHANICAL PIPE OR ELECTRICAL
CONDUIT THROUGH ROOF
STEPPED RUBBER BOOT
STAINLESS STEEL DRAWBAND
LIGHTNING PROTECTION AIR
TERMINAL ASSEMBLY
HARDWARE ADHERED TO PROTECTION PAD
WITH MASTIC (SOPREMA SOPRAMASTIC SP1)
OR AS REQUIRED BY LIGHTNING PROTECTION
MANUFACTURER
ADHERE PROTECTION PAD
TO MEMBRANE WITH
MASTIC (SOPREMA
SOPRAMASTIC SP1 OR
EQUAL)
CABLE LOOP
PER
ELECTRICAL
NOTE: COORDINATE LOCATIONS OF AIR
TERMINALS WITH ELECTRICAL
DRAWINGS.
ADHERE PROTECTION PAD TO
MEMBRANE WITH MASTIC
(SOPREMA SOPRAMASTIC SP1 OR
EQUAL)
ROOF WALKWAY PAD (SOPREMA
SOPRAWALK OR EQUAL)
CAP
STRUT CHANNEL CROSS BRACE
W/ HOLES WELDED TO 6"
LENGTH OF 2" x 2" SQUARE TUBE
BOLT (PER MFG.)
STRUT CHANNEL UPRIGHT
W/ HOLES
1 3/4" ROUND BAR WELDED
TO PLATE AND PLUG WELDED
TO STL UPRIGHT
8" DIA x 1/4" THICK STL PLATE W/
EXP BOLTS
CONCRETE ROOF SLAB
1'- 4"
16" DIA (TYP)
NO
TE
: E
LE
VA
TI
ON
O
F
CW
S
AN
D
CW
R P
IP
IN
G
MO
UN
TE
D
ON
PI
PI
NG
S
UP
PO
RT
R
AC
K
RE
LA
TI
VE
A
CC
U- 1 T
O
BE
IN
CO
NF
OR
MA
NC
E W
IT
H
MF
G'
S
IN
ST
AL
LA
TI
ON
RE
CO
MM
EN
DA
TI
ON
S.
8" M
IN
POLYURETHANE - BITUMEN FINISH
COAT WITH BROADCAST MINERAL
GRANULES
PRESSURE TREATED WOOD
NAILERS NAILED TOGETHER
AND SECURED TO ROOF DECK
REINFORCING FABRIC SET IN
POLYURETHANE BITUMEN
LIQUID
8" MIN 2 PLY SBS ROOFING
ASSEMBLY
ELECTRICAL SERVICE / CONDUIT TO
PLATFORM MECHANICAL. SEE ELECTRICAL.
CHILLED WATER SUPPLY / RETURN
PIPES; SEE MECHANICAL
F6
C-AE502
1/2" EXPANSION ANCHORS WITH 4"
MIN EMBED
CAP
SAFETY DISCONNECT, SEE
ELECTRICAL AND MECHANICAL
STRUT CHANNEL CROSS BRACE
W/ HOLES WELDED TO 6" LENGTH
OF 2" x 2" SQUARE TUBE
BOLT (PER MFG.)
STRUT CHANNEL UPRIGHT
W/ HOLES
1 3/4" ROUND BAR WELDED
TO PLATE AND PLUG
WELDED
TO STL UPRIGHT
GFCI RECEPTACLE IN
WEATHERPROOF ENCLOSURE.
SECURE TO VERTICAL STRUT
CHANNEL CROSS BARCE; SEE
ELECTRICAL
CONDUIT. SEE ELECTRICAL
EXTEND CONDUITS TO PIPE
PORTAL FLASHING SYSTEM.
1'- 4"
1'- 8"
8" M
IN
8" MIN
F6
C-AE502
8" DIA x 1/4" THICK STL PLATE W/
EXP BOLTS
CONCRETE ROOF SLAB
FOR REQUIREMENTS
GALVANIZED CONDUIT SUPPORT /
STRAP ANCHOR PER ELECTRICAL
METAL ROOF PANEL
AS SCHEDULED
THRU ROOF AIR
TERMINAL
EPDM / SILICONE PIPE FLASH
BOOT; CUT TO AIR TERMINAL
SIZE IN FIELD SO THAT
FLASHING FITS TIGHT AROUND
AIR TERMINAL; SET BASE IN
CONTINUOUS BEAD OF
APPROVED SEALANT. FORM
BASE TO METAL PANEL
PROFILE.
#12 HEX HEAD LAP SCREW W/
NEO. WASHER
-OR-
3/16" BULB-TITE BLIND RIVETS
W/ SEALING WASHERS @ 2" O.C.
PRIOR TO SLIDING FLASHING
BOOT DOWN OVER AIR TERMINAL,
PLACE A CONTINUOUS BEAD OF
APPROVED SEALANT AROUND AIR
TERMINAL AT THE HEIGHT OF THE
BOOT SO THAT WHEN THE BOOT IS
IN PLACE THE TOP OF THE BOOT
ENGAGES THE SEALANT (SEE
NOTE 3 BELOW)
NOTES:
1) THE PIPE FLASHING BOOT MUST BE FASTENED TO
THE PANEL ONLY AND NOT INTO THE ROOF SUBSTRATE TO
ALLOW THE PANEL TO MOVE THERMALLY.
2) ADEQUATE CLEARANCE MUST BE LEFT BETWEEN THE
AIR TERMINAL AND THE PANEL TO ALLOW FOR THERMAL
MOVEMENT WITHOUT INTERFERENCE.
3) DO NOT ATTEMPT TO SEAL FLASHING BOOT TO
THREADED AREA OF AIR TERMINAL. APPLY A SEALED,
SMOOTH COLLAR ON AIR TERMINAL, AND, AT PIPE FLASHING
BOOT INTERFACE TO INSURE PROPER SEAL
2'-9"11
2" 11" 5" 2'-2" 5 12" 9 TR. @ 11"=8'-3" 11"
3'- 6"
11 2" 71 2"
11 2" 1'-
6" 1'-
0" 91 2"
7"
3'- 0"
1'- 9"
1 2"
3'- 0"
12"
3'- 2 1
/2"
EQ
3 1 2"
EQ
3'- 6"
2'-0"
2" 11
2"
1'- 0"
VA
RI
ES
2"11
2"1'-6"
11 2" M
IN
1 2"
EQEQ
CL
3'-6"
9"
4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
ISSUED FOR
CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA NY Manhattan Campus
423 E 23RD Street, New York, NY 10010
630-600A
Project Director
Revisions: Date:
A/E:
AECOM
3101 WILSON BLVD, SUITE 900
ARLINGTON, VA. 22201
703-682-4900
WWW.AECOM.COM
Construction Document Refresh
1 & GEN PLTFRM
Key Plan
Balance of Work
9/12/2022 DZ JH / DZ
DETAIL - PIPE PORTAL FLASHING SYSTEM
C1
DETAIL - LIGHTNING PROTECTION SYSTEM
B7
DETAIL - PIPE SUPPORT RACK
F1
DETAIL - DISCONNECT / ELECTRICAL DEVICE SUPPORT
F3
C-AE506
BUILDING 1 & GENERATOR
PLATFORM - DETAILS 6
DETAIL - LIGHTNING PROTECTION SYSTEM
B4
SCALE: 1/2" = 1'-0"
0 1' 2'
C5
ENLARGED PLAN AT METAL STAIR
3'
4'
HORIZONTAL 2 HOUR RATED ENCLOSURE DETAIL - EXTERIOR
F8
HORIZONTAL 2 HOUR RATED ENCLOSURE DETAIL - EXTERIOR
D8
ELEVATION AT METAL STAIR
F5
AutoCAD SHX Text 6"
AutoCAD SHX Text 3"
AutoCAD SHX Text 3"
AutoCAD SHX Text
8" (MIN.)
AutoCAD SHX Text 2"
AutoCAD SHX Text
CORE DRILL EXISTING SLAB
AutoCAD SHX Text
2 HOUR RATED FIRESTOP PENETRATION ASSEMBLY
AutoCAD SHX Text
C-AE502
AutoCAD SHX Text D5
AutoCAD SHX Text HSS 3x3x
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
" POST
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text 8"x
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text "x3'-0"(W) STEEL
AutoCAD SHX Text
CHECKER PLATE WITH
AutoCAD SHX Text
BEVELED EDGES.
AutoCAD SHX Text
WELD ONE SIDE ONLY
AutoCAD SHX Text
STEEL BAR GRATE (BANDED
AutoCAD SHX Text
ALL SIDES) W/ STEEL
AutoCAD SHX Text
ANGLE SUPPORTS AT SIDES.
AutoCAD SHX Text
STEEL BAR GRATE TREAD
AutoCAD SHX Text
WITH CHECKER PLATE
AutoCAD SHX Text
NOSING (TYP)
AutoCAD SHX Text
C-AE373
AutoCAD SHX Text C1
AutoCAD SHX Text
SIM
AutoCAD SHX Text
C-AE506
AutoCAD SHX Text F5
AutoCAD SHX Text
NOTE: STAIR IS A DELEGATED DESIGN; REFER TO
AutoCAD SHX Text
SPECIFICATION SECTION 05 51 00 FOR REQUIREMENTS
AutoCAD SHX Text
1 " O STEEL POST 12" O STEEL POST GUARDRAIL
AutoCAD SHX Text
STEEL BAR GRATE (BANDED ALL SIDES) W/ STEEL ANGLE SUPPORTS AT SIDES.
AutoCAD SHX Text C12x20.7. COPE CUT END CHANNEL 12" BELOW BAR GRATE.
AutoCAD SHX Text
38" STEEL PLATE BRACKET WELDED TO ANGLE
AutoCAD SHX Text
34" O ROD WITH ABRASIVE COATING
AutoCAD SHX Text ANGLE 3x3x @ 45 14 @ 45 DEGREES (EACH WAY)
AutoCAD SHX Text 7"x3"x1/4" PLATE
AutoCAD SHX Text
MEMBRANE FLASHING. SEE DETAIL F6/C-AE502
AutoCAD SHX Text
ROOF ASSEMBLY
AutoCAD SHX Text HSS 3"x3"x " POST14" POST
AutoCAD SHX Text 9"x9"x " STEEL PLATE 12" STEEL PLATE WITH (4) " O 12" O EXPANSION BOLTS - MINIMUM 2 " 12" EMBEDMENT
AutoCAD SHX Text
TOP OF CONCRETE ROOF SLAB
AutoCAD SHX Text NOTE: ALL STEEL SHALL BE H.D. GALVANIZED AND PAINTED P-6. DO NOT PAINT STEEL BAR GRATE.
AutoCAD SHX Text
1" GWB SHAFT-LINER (MOISTURE RESISTANT)
AutoCAD SHX Text 2 " x 25 GA I-STUD 12" x 25 GA I-STUD 24" O.C.
AutoCAD SHX Text
J TRACK
AutoCAD SHX Text
1/2" TYPE 'X' GYPSUM SHEATHING
AutoCAD SHX Text
POWER DRIVEN FASTENERS @ 24" O.C.
AutoCAD SHX Text EXISTING ELEC. CONDUITS AND RACK SUPPORT. WHERE CONDUITS EXIT ENCLOSURE PROVIDE A 2 HOUR RATED FIRESTOP PENETRATION ASSEMBLY
AutoCAD SHX Text
CONT. INTUMESCENT SEALANT
AutoCAD SHX Text NOTE: PAINT ALL SIDES OF MTL ENCLOSURE 'FEDERAL SAFETY ORANGE'. PROVIDE 2" HIGH PAINTED BLACK STENCILED MESSAGE '4160V' AT 20 FEET MAX. OC.. WHERE ENCLOSURE PASSES THROUGH WALLS PROVIDE TEXT WITHIN 12" OF WALL (EACH SIDE OF WALL)
AutoCAD SHX Text
TEST ASSEMBLY: WHI694-0300.1(SIM)
AutoCAD SHX Text
EXISTING EXTERIOR CEILING ASSEMBLY
AutoCAD SHX Text
EXISTING FACE OF WALL
AutoCAD SHX Text
PREP AND PAINT EXISTING STEEL ANGLE LINTEL TO MATCH EXISTING
AutoCAD SHX Text
PRE-FINISHED TRIM
AutoCAD SHX Text CORRUGATED METAL PANEL-18GA. GALVALUME STEEL, " DEPTH, 12" 78" DEPTH, 12" PANEL WIDTH, WITH CONCEALED CLIP FASTENERS.
AutoCAD SHX Text
J TRACK
AutoCAD SHX Text
1 " GALVANIZED SUB 12" GALVANIZED SUB FRAMING
AutoCAD SHX Text NOTE: GWB SHAFT WALL AND METAL PANEL WRAP ENCLOSURE SHALL HAVE RETURNED ENDS / ENCLOSURES AT THE PULL BOX AND THE CONDUIT / PIPE CHASE.
AutoCAD SHX Text SELF-ADHERING BITUMINOUS SHEET WATERPROOFING (WR GRACE ICE & WATER SHIELD OR EQUAL) LAP TO INTERNAL GYP SHEATHING
AutoCAD SHX Text
12" TYPE "X" SHEATHING W/ SEALED JOINTS
AutoCAD SHX Text 2 " x 25 GA I-STUD 12" x 25 GA I-STUD 24" O.C.
AutoCAD SHX Text
J TRACK
AutoCAD SHX Text
1/2" TYPE 'X' GYPSUM SHEATHING
AutoCAD SHX Text NOTE: PAINT ALL SIDES OF MTL ENCLOSURE 'FEDERAL SAFETY ORANGE'. PROVIDE 2" HIGH PAINTED BLACK STENCILED MESSAGE '4160V' AT 20 FEET MAX. OC.. WHERE ENCLOSURE PASSES THROUGH WALLS PROVIDE TEXT WITHIN 12" OF WALL (EACH SIDE OF WALL)
AutoCAD SHX Text
TEST ASSEMBLY: WHI694-0300.1(SIM)
AutoCAD SHX Text
EXISTING EXTERIOR SOFFIT ASSEMBLY
AutoCAD SHX Text
EXISTING FACE OF WALL
AutoCAD SHX Text NOTE: GWB SHAFT WALL AND METAL PANEL WRAP ENCLOSURE SHALL HAVE RETURNED ENDS / ENCLOSURES AT THE PULL BOX.
AutoCAD SHX Text SAW-CUT BRICK JOINT. INSERT S. STL FLASHING TO FORM A HOOD. ALL JOINTS IN FLASHING SHALL BE SOLDERED.
AutoCAD SHX Text
SEALANT/TERMINATION BAR
AutoCAD SHX Text
EXISTING EXTERIOR WALL ASSEMBLY
AutoCAD SHX Text SELF ADHERING BITUMINOUS SHEET WATERPROOFING. (WR GRACE ICE WATER-SHIELD OR EQUAL).
AutoCAD SHX Text
12" TYPE "X" GYP. SHEATHING WITH SEALED JOINTS
AutoCAD SHX Text
CONTINUOUS PT WOOD CANT STRIP
AutoCAD SHX Text
LINE OF FLASHING BEYOND
AutoCAD SHX Text
1" GWB SHAFT-LINER (MOISTURE RESISTANT)
AutoCAD SHX Text EXISTING ELEC. CONDUITS AND RACK SUPPORT. WHERE CONDUITS EXIT ENCLOSURE AND THE EXTERIOR MASONRY WALL ASSEMBLY; PROVIDE A 2 HOUR RATED FIRESTOP PENETRATION ASSEMBLY
AutoCAD SHX Text
EXISTING FACE OF WALL
AutoCAD SHX Text
CONTINUOUS INTUMESCENT SEALANT
AutoCAD SHX Text F I R S T A V E N U E
AutoCAD SHX Text A S S E R L E V Y P L A C E
AutoCAD SHX Text E A S T 2 3 r d. S T R E E T
AutoCAD SHX Text
BLDG 3
AutoCAD SHX Text
BLDG 2
AutoCAD SHX Text
BLDG 4 / 5
AutoCAD SHX Text
E A S T 25 TH STREET
AutoCAD SHX Text
BLDG 1
AutoCAD SHX Text N
AutoCAD SHX Text
BLDG 6
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'
AutoCAD SHX Text
SCALE: 1 1/2" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 1'
2'
Hilti Firestop Systems Hilti Firestop Systems
System No. F-A-1016
SECTION A-A
FA
Page: 1 of 3
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
June 29, 2015
A
A
Page: 2 of 3
The firestop device and metallic penetrant shall be sized as follows:
System No. F-A-1016
FA
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
June 29, 2015
Nom Pipe Diam +, ++ Firestop Device
1-1/2 to 2-1/2 in.(38 to 64 mm) - Other than copper pipe or tubing CP680N-75/2.5"or CP682-75/2.5" 1-1/2 to 2 in.(38 to 51 mm) - Other than copper pipe or tubing CP 680-M 2", CP 680-P 2, CP 680-PX 2"
2 to 2-1/2 in. (51 to 64 mm) - Copper pipe or tubing CP680N-75/2.5"or CP682-75/2.5"
CP 680-M 2", CP 680-P 2", CP 680-PX 2"
2-1/2 to 3 in. (64 to 76 mm) CP 680-M 3", CP 680-P 3", CP 680-PX 3"
4 in. (102 mm) CP680N-110/4"or CP682-110/4"
CP 680-M 4", CP 680-P 4"
6 in. (152 mm)
CP680N-160/6"
CP 680-M 6", CP 680-P 6"
1. Floor Assembly — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
1A. Floor Assembly — (Optional, Not Shown)—The fire rated unprotected concrete and steel floor assembly shall be constructed of the materials and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below:
A. Concrete — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
B. Steel Floor and Form Units* — Composite or non-composite max 3 in. (76 mm) deep galv steel fluted units as specified in the individual
Floor-Ceiling Design.
2. Firestop Device* — Cast in place firestop device permanently embedded during concrete placement or grouted in concrete floor assembly in accordance with accompanying installation instructions. The devices may extend a max of 2 in. (51 mm) above the top surface of the concrete.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 680N-75/2.5", CP 680N-110/4", CP 680N-160/6", CP 682-75/2.5", CP
682-110/4", CP 680-M 2", CP 680-M 3", CP 680-M 4", CP 680-M 6", CP 680-P 2",
CP 680-P 3", CP 680-P 4", CP 680-P 6", CP 680-PX 2", CP 680-PX 3"
3. Through Penetrants — One metallic pipe, conduit or tubing to be installed within the firestop device. Pipe, conduit or tubing to be rigidly supported on both sides of floor assembly. The following types of pipe, conduit or tubing may be used:
A. Steel Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 6 in. (152 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit — Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit.
D. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing.
E. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
F. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular) or heavier copper pipe.
+ When metallic pipes of diameters smaller than those shown above are installed within the device, CP618 Firestop Putty Stick or mineral wool insulation shall be installed within the device.
++ L Rating applies only to CP 680-M and -P(X) devices and only when the nom diam of pipe equals size of device (2 in. diam pipe in 2" device etc.). L Rating does not apply to CP 680N and CP682 devices.
4. Fill, Void or Cavity Material* - Putty (Not Shown) — Min 1 in. (25 mm) thickness of fill material applied within annulus flush with top surface of device.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 618 Firestop Putty Stick
4A. Packing Material (Not Shown) — As an alternate to Item 4, min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3) mineral wool insulation firmly packed to the fullest extent possible within annulus flush with top surface of device.
4B. Firestop Device* - Top Seal Plug — (Optional. Not Shown) - Top seal plug for use with CP 680-M 2" and CP 680-P 2" devices and nom pipe, conduit or tubing sizes of 1/2 in. (13 mm) to 2 in. (51 mm) diam. Plug is friction fit into top of firestop device (Item 2) in accordance with the manufacturer's instructions. When top seal plug is used, no putty (Item 4) or packing material (Item 4A) is required. W Rating applies only to nom 1, 1-1/4, 1-1/2 and 2 in. (25, 32, 38 and 51 mm) diam copper pipe/tube in conjunction with 2" CPS Top Seal and CP 680-M 2" or CP 680-P(X) 2" devices.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CPS Top Seal Plug
Hilti Firestop Systems Page: 3 of 3
4B1. Firestop Device* - Water Barrier Module — (Optional, Not Shown) - Used as an alternate to the top seal plug (Item 4B) and in combination with the CP 680-M and CP 680-P(X) devices to achieve a W Rating. Module is threaded onto top of device. See Table below for sizes of device/module and penetrants covered. When water barrier module is used, a W Rating applies to the water barrier module, device and penetrant sizes specified in Table below. For W Rating with Water Barrier Module, pipe shall be installed from bottom of device.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — Water Barrier Module
Penetrant Type (See Item 3 above) Nom Penetrant Diam Size of Device/Module A, B, C, D 2" 2"
2-1/2" 3"
3" 3"
4" 4"
6" 6" E, F 2" 2"
3" 3"
4" 4"
6" 6"
System No. F-A-1016
FA
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
June 29, 2015
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
C
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Rating — 2 Hr F Rating — 2 Hr
T Rating — 0 Hr FT Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM/sq ft (See Item
3) FH Rating — 2 Hr
L Rating At 400 F — Less Than 1 CFM/sq ft (See Item 3) FTH Rating — 0 Hr
W Rating — Class 1 (See Items 4B and 4B1) L Rating At Ambient — Less Than 1 CFM/sq ft (See Item 3)
L Rating At 400 F — Less Than 1 CFM/sq ft (See Item 3)
Hilti Firestop Systems
System No. F-A-2025
FA
Page: 1 of 2
1. Floor Assembly — The fire-rated unprotected concrete and steel floor assembly shall be constructed of the materials and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below:
A. Normal Weight Concrete — Min 2-1/2 in. (64 mm) thickness of lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete topping as measured over the crests of the steel floor units.
B. Steel Floor and Form Units* — Composite or noncomposite 3 in. (76 mm) deep fluted galv units as specified in the individual Floor-Ceiling design. Max diam of opening core-drilled through floor assembly is 8 in. (203 mm).
2. Through Penetrants — One nonmetallic pipe to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe and periphery of opening shall be min 0 in. ( 0 mm, point contact) to max 1-1/2 in. (38 mm). Pipe to be rigidly supported on both sides of floor assembly. The following types and sizes of nonmetallic pipes may be used:
A. Polyvinyl Chloride (PVC) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid-core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 6 in. (152 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid-core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
D. Flame Retardant Polypropylene (FRPP) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed (process or supply) or vented drain, waste or vent) piping systems.
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 15, 2015
F Rating — 2 Hr T Rating — 2 Hr
SECTION A-A
B
A
B
A
5 2
6 1B 6
1A
SECTION B-B
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479
Hilti Firestop Systems Page: 2 of 2
3. Metal Plate Enclosure — Min 18 ga steel. Width of plate to be min 12 in. (305 mm). Length of plate (transverse to steel floor unit direction) to extend to steel floor unit valley beyond each side of core-drilled hole with a min lap of 1-1/2 in. (38 mm) on the floor unit valley at each end.
Both ends of plate perpendicular to floor unit valleys to be cut to permit the ends to be bent upwards 90 F deg to follow the contour of the floor unit, enclosing the packing material (Item 4) within the areas of the flutes. The contoured plate ends shall be such that the gap between the floor unit and the plate ends is no greater than 1/4 in. (6 mm). As an alternate to bending up ends of plate, min 1/4 in. (6 mm) thickness of fill material (Item 5) shall be applied to completely cover the surface of the mineral wool packing material within the flutes of the steel floor units, between the two ends of the metal enclosure plate and the steel floor units. Circular cutout in plate to tightly follow circumference of nonmetallic pipe with side edges of plate at least 3 in. (76 mm) from circular cutout on all sides. Slit made in plate to permit installation around the nonmetallic pipe to be located at end of plate beneath floor unit valley nearest to the circular cutout. Plate secured to valleys of floor unit using min 1/4 in. (6 mm) diam by 1-3/4 in. (45 mm) long steel expansion bolts, or equivalent, in conjunction with min 3/4 in. (19 mm) diam steel washers or min 0.145 in. (4 mm) diam by 1-1/4 in. (32 mm) long powder actuated fasteners utilizing a 1-7/16 in. (36 mm) diam by 1/16
in. (2 mm) thick steel washer. As alternates to the anchors specified above, Hilti 1/4 in. (6 mm) diam by 1-1/4 in. (32 mm) long KWIK-CON II+ concrete screw anchor, Hilti 1/4 in. (6 mm) diam by 1-3/4 in. (44 mm) long KWIK-BOLT 3 steel expansion anchor or Hilti X-DNI 27 P8 S15 powder actuated floor pin with integral nom 9/16 in. (15 mm) diam washer may be used . Fasteners to be located approx 1 in. (25 mm) from edges of plate at each corner, at each plate/valley intersection and at both sides of slit made to permit installation around nonmetallic pipe.
Spacing of fasteners no to exceed 10 in. (254 mm) OC.
4. Packing Material — Mineral wool batt insulation having min density of 4 pcf (64 kg/m3), firmly packed into flutes of steel floor units above metal plate enclosure (Item 3) to completely fill cavities. When ends of metal plate enclosure perpendicular to floor unit valleys are not bent up to enclose packing material within flutes (see Item 3), packing material to be recessed from ends of plate to accommodate the required thickness of the fill material.
5. Fill, Void or Cavity Material* — Sealant — Nom 1/2 in. (13 mm) bead of fill material applied around the perimeter of the metal plate enclosure at the interface of the enclosure and steel deck. When ends of metal plate enclosure (Item 3) are not bent up to enclose packing material within flutes, min 1/4 in. (6 mm) thickness of fill material shall be applied to completely cover the surface of the mineral wool packing material within the flutes of the steel floor units, between the two ends of the metal enclosure plate and the steel floor units.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant
6. Firestop Device* — Firestop Collar — Firestop collar shall be installed in accordance with the accompanying installation instructions. Collar to be installed and latched around the pipe and secured to the valley of the steel deck and to the metal plate enclosure using the anchor hooks provided with the collar. Min of two anchor hooks required for 1-1/2 and 2 in. (38 and 51 mm) diam pipes, min of three anchor hooks required for 3 and 4 in. (76 and 102 mm) diam pipes, and min of four anchor hooks required for 6 in. (152 mm) diam pipes. Where the anchor hooks are beneath the valley of the steel floor unit, the anchor tabs are to be secured with 1/4 in. (6 mm) diam by min 1-1/2 in. (38 mm) long steel expansion bolts, or equivalent, in conjunction with steel nuts and min 3/4 in. (19 mm) diam steel washers with one anchor bolt in each anchor hook. Where the anchor hooks are beneath the crest of the steel deck, the anchor hooks are to be secured to the metal enclosure with No. 10 by min 1/2 in. (13 mm) long self-drilling, self-tapping steel screws and min 3/4 in. (19 mm) diam steel washers.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 643 50/1.5"N, CP 643 63/2"N, CP643 90/3"N, CP 643 110/4"N or CP 643 160/6"N Firestop Collar.
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
System No. F-A-2025
FA
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 15, 2015
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479
Hilti Firestop Systems
System No. F-A-2053
SECTION A-A
FA
1. Floor Assembly — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
1A. Floor Assembly - (Optional - Not Shown) — The fire rated unprotected concrete and steel floor assembly shall be constructed of the materials and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below:
A. Concrete — Min 2-1/2 in (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
B. Steel Floor and Form Units* — Composite or non-composite max 3 in. (76 mm) deep galv steel fluted units as specified in the individual
Floor-Ceiling Design.
2. Firestop Device* — Cast in place firestop device permanently embedded during concrete placement or grouted in concrete assembly in accordance with accompanying installation instructions. The 3, 4 and 6 in. devices may extend a max 2 in. (51 mm) above the top surface of the concrete. The max extension above the slab for the 2 and 2.5 in. devices is not restricted.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 680-75/2.5"N, CP 680-110/4"N, CP 680-160/6"N, CP 680-P 2", CP 680-P 3", CP 680-P 4", CP 680-P 6", CP 680-PX 2", CP 680-PX 3"
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
June 29, 2015
F Rating — 2 Hr T Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM/sq ft (See Item 3) L Rating At 400 F — Less Than 1 CFM/sq ft (See Item 3)
W Ratings — Class 1 (See Items 3, 4 and 4A)
A
Page: 1 of 2
2 3
CL
ASS I F IED
Classified by Underwriters Laboratories, Inc.
to UL 1479
Hilti Firestop Systems
System No. F-A-2058
SECTION A-A
FA
1. Floor Assembly — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Max diam of opening is 4 in. (102 mm).
1A. Floor Assembly — (Optional — Not Shown) — The fire-rated unprotected concrete and steel floor assembly shall be constructed of the materials and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below:
A. Concrete — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
B. Steel Floor and Form Units* — Composite or non-composite max 3 in. (76 mm) deep galv steel fluted units as specified in the individual
Floor-Ceiling Design. Max diam of opening is 4 in. (102 mm).
2. Through Penetrants — One nonmetallic pipe to be installed concentrically or eccentrically within the firestop system. Annular space between pipe or conduit and edge of opening to be min 3/8 in. and max 1 in. (9.5 to 25 mm). Pipe to be rigidly supported on both sides of floor-ceiling assembly.
The following types and sizes of nonmetallic pipes or conduits may be used:
A. Polyvinyl Chloride (PVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
3. Fill, Void or Cavity Materials*-Sealant — Min 2-1/2 in. (64 mm) thickness of sealant applied within annular space, flush with top surface of floor.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant.
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 15, 2015
F Rating — 2 Hr T Rating — 0 Hr
A
1 2
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479
Nom Pipe Diameter Firestop Device
1/2 in. to 2 in. (19 mm to 51 mm)
CP 680-75/2.5"N
CP 680-P 2" CP 680-PX 2"
3 in. (76 mm) CP 680-P 3" CP 680-PX 3"
3 in. to 4 in. (76 mm to 102 mm)
CP 680-110/4"N
CP 680-P 4"
6 in. (152 mm)
CP 680-160/6"N
CP 680-P 6"
Hilti Firestop Systems
System No. F-A-2053
FA
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
June 29, 2015 Page: 2 of 2
++ L Rating applies only to CP 680-P(X) devices and only when the nom diam of pipe equals size of device (2 in. diam pipe in 2" device etc.) L Rating does not apply to CP 680N devices.
4. Firestop Device* — (Not shown) -Top Seal Plug for use with CP 680-P(X) 2" device Installed in accordance with the manufacturer's instructions.
The Top Seal Plug is optional for nom 1-1/2 in. (38 mm) pipes and conduits. Top Seal Plugs are required for all pipes and conduits less than nom 1-1/2 in. (38 mm). W Rating applies only to the IPS Top Seal Plug and nom 2 in. diam penetrants, and to CPS Top Seal Plugs with nom 1/2 to 2
in. (13 to 51 mm) diam penetrants.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CPS and IPS Top Seal Plugs
4A. Firestop Device* - Water Barrier Module — (Optional, Not Shown) - Used as an alternate to the top seal plug (Item 4). Applies to nom 2", 3", 4" and 6" water barrier modules used in combination with the CP 680-P(X) 2", CP 680-P(X) 3", CP 680-P 4" CP 680-P 6" devices, respectively, and supplied by device manufacturer. Module is threaded onto top of device. W Rating applies only when water barrier module is used and nom diam of penetrant equals size of device.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — Water Barrier Module
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
+Bearing the UL Listing Mark
3. Through Penetrants — One nonmetallic pipe or conduit to be installed within the firestop system. Pipe or conduit to be rigidly supported on both sides of floor assembly. For W Rating with Water Barrier Module, pipe shall be installed from bottom of device. The following types and sizes of nonmetallic pipes or conduits may be used:
A. Polyvinyl Chloride (PVC) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 6 in. (152 mm) diam (or smaller) SDR11 or SDR13.5 CPVC pipe for use in closed (process or supply) piping systems.
C. Rigid Nonmetallic Conduit+ — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA No. 70).
The firestop devices and nonmetallic penetrants shall be sized as follows:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
ISSUED FOR
CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA NY Manhattan Campus
423 E 23RD Street, New York, NY 10010
630-600A
Project Director
Revisions: Date:
A/E:
AECOM
3101 WILSON BLVD, SUITE 900
ARLINGTON, VA. 22201
703-682-4900
WWW.AECOM.COM
Construction Document Refresh
1 & GEN PLTFRM
Key Plan
Balance of Work
9/12/2022
C-AE507
FIRESTOPPING DETAILS - 1
DZ JH / DZ
1. Refer to the following specifications for firestopping.
a. 07 84 00 Firestopping
b. 21 21 13 Wet-pipe Sprinkler Systems
c. 21 13 16 Dry-pipe Sprinkler Systems d.Division 22 00 00 Plumbing (all sections) e.Division 23 00 00 HVAC (all sections)
f. Division 26 00 00 Electrical (all sections)
g. 27 05 33 Raceways and Boxes for Communication Systems
h. 28 31 00 Fire Detection and Alarm
For Quality Control requirements, refer to the Quality Assurance portion of the specification.
2. Manufacturer's trade names and UL assembly used here-in are only to identify basis of design / level of performance requirements required.
Products of other manufacturer's equivalent to basis of design / performance requirements that meet requirements of the technical specification will be acceptable once submitted / approved as a shop drawing submittal.
3. Details shown are typical details and are not meant to be inclusive of all field conditions that may be present.
Contractor shall submit additional firestop system assemblies for penetrations through rated construction as required for review and approval.
4. Details shown are typical details.
Always refer to the listed system detail for complete system requirements. If field conditions do not match requirements of details, approved alternate details shall be utilized / submitted for review / approval. Design requirements, field conditions and dimensions need to be verified for compliance with the details, including but not limited to the following:
* Fire Rating (F-Rating)
* Leakage Rating (L-Rating)
* Water Rating (W-Rating)
* Annular Space
* Percent Fill
* Movement
* Type and thickness of fire-rated construction.
4. If alternate details matching the field conditions are not available, manufacturer's engineering judgment drawings are acceptable subject to approval by the Authority Having Jurisdiction (AHJ). Contact Hilti Inc. for alternative systems or Engineering Judgment (800-879-8000). Drawings shall follow the International Firestop Council (IFC) Guidelines for Evaluating Firestop Systems Engineering Judgments.
5. References:
* 2017 Underwriter's Laboratories
Fire Resistance Directory, Volumes 1 & 2.
* NFPA 101 Life Safety Code
* NFPA 70 – National Electric Code
* All governing local and regional building codes.
6. Systems C-AJ-3095, C-AJ-3216 and C-AJ-3283 are permitted for use at existing cables thru new construction only. All new cables passing thru new walls use system C-AJ-3285.
7. Firestop System installation must meet requirements of ASTM E-814 (UL 1479) tested assemblies that provide a fire rating equal or greater to that of construction being penetrated.
8. Systems W-L-5028, W-L-1054, W-L-1389, W-L-3396 and W-L-8079 are permitted for use at existing pipes and cables through new GWB construction only. All new pipes and cables through new GWB walls shall use W-L-2078, W-L-2128 and W-L-3334.
9. During construction all empty core holes through elevated floor slabs are required to be temporarily closed.
Provide Hilti CFS-PL Firestop Plug or Hilti CFS-BL Firestop Block /approved equal sized for core hole.