A-Mechanical-Part 2.pdf

PDF 9 MB Posted

Attached to
36C10F24R50018 Balance of Work VAMC Manhattan, NY -- Y1DA
Solicitation number
QSE--36C10F24R50018
Issued by

About this file

This document appears to be a set of mechanical drawings and technical specifications for a construction project at the VA New York Healthcare System Manhattan Campus. The drawings and specifications detail the mechanical systems, including HVAC air handling units, terminal units, ductwork, piping, and associated controls. Key details include:

The project involves constructing the "Balance of Work" for the Manhattan Hurricane Sandy Recovery Program at the VA VAMC Manhattan Campus. The work includes installation of new mechanical systems to serve the building, including air handling units, terminal units, ductwork, piping, and controls. The drawings provide floor plans, mechanical equipment schedules, and control diagrams for the HVAC systems. Major mechanical equipment includes air handling units, return/exhaust fans, air terminal units, unit heaters, and air curtains. The control system utilizes a direct digital control system (DDCS) to monitor and control the HVAC equipment. The technical specifications detail the performance requirements, features, and installation requirements for the mechanical systems.

View the file

Other files

File Type Posted
SolicitationCancellation.pdf PDF
SolicitationAmendment0006.pdf PDF
Manhattan VA Asbestos Survey Report 05-2021final (5-24-21).pdf PDF
Manhattan VA Revised Asbestos Survey Report 05-2021Final (Appendix H - First Half).pdf PDF
QA - Balance of Work - 05.08.2024.pdf PDF
Manhattan VA Revised Asbestos Survey Report 05-2021Final (Appendix H - 2nd half).pdf PDF
QA - Balance of Work - 05.02.2024.pdf PDF
SolicitationAmendment0005.pdf PDF
SolicitationAmendment0004.pdf PDF
QA - Balance of Work - 04.16.2024.pdf PDF
C-Mechanical- Part 2.pdf PDF
C-Electrical- Part 5.pdf PDF
B-Mechanical-Part 1.pdf PDF
P03_CDR- Sole Source JA - Access Controls - 11-16-22.pdf PDF
B-Civil.pdf PDF
C-Plumbing- Part 2.pdf PDF
P03_CDR - Sole Source JA - Public Announcement System - 11-16-22.pdf PDF
C-Electrical- Part 4.pdf PDF
A-Architecture-Part 3.pdf PDF
A-ICRA.pdf PDF
C-Architecture- Part 5.pdf PDF
A-Fire Protection-Part 2.pdf PDF
C-Electrical- Part 10.pdf PDF
P03_CDR - Sole Source JA - Triplex Pump 11-16-22.pdf PDF
C-Life Safety.pdf PDF
A-Electrical-Part 1.pdf PDF
VHA Directive 1028_D_2020-02-24.pdf PDF
B-Electrical-Part 2.pdf PDF
B-Architecture-Part 4.pdf PDF
C-Electrical- Part 12.pdf PDF
A-Electrical-Part 3.pdf PDF
C-Electrical- Part 7.pdf PDF
C-Electrical- Part 8.pdf PDF
A-Civil.pdf PDF
A-Structural.pdf PDF
A-General.pdf PDF
QSE 36C10F24R50018.pdf PDF
Amendment 0001 - Missing and Replacement Documents.pdf PDF
B-Electrical-Part 1.pdf PDF
C-Fire Protection- Part 2.pdf PDF
C-Electrical- Part 11.pdf PDF
C-Telecom.pdf PDF
A-Plumbing-Part 2.pdf PDF
C-Architecture- Part 6.pdf PDF
B-Electrical-Part 3.pdf PDF
VAMC CD Refresh IFC Vol 1 Specifications REV 2_ 9-19-23 (Part 3).pdf PDF
C-Mechanical- Part 3.pdf PDF
Shutdown Request Form.pdf PDF
B-Architecture-Part 2.pdf PDF
P03_CD Refresh - Sole Source JA - Fire Alarm System - 11-16-22.pdf PDF
Show 40 more

Latest 50 of 281 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KEYED NOTES:#GENERAL NOTES:

U

V

W

2 3 4 5 7 9

U

Y

S

S S

S

S S

X

CU

H-

1STOP

UH-W-28

UH-W-30

UH-W-29

UH-W-31

UH-W-26

UH-W-27

GAS METER

G204ASG204AS

PAINT

SHOP

0203S0203S

PAINT SHOP

STOR.

0203S

CORR

G201S

MEN'S

LOCKERS

G204BS

WOMEN'S

LOCKERS

G205S

VEST.

G204CS

CORR.

G297S

VEST.

142A

REGULATED

MEDICAL

WASTE

G206S

INTERIM

STORAGE

G207S

EMPTY SHARPS

CONTAINERS

G204S

VEST.

G208S

CUH-1

T T

T

T

T

T

T

UH-W-32

MA

TC

H

LIN

E

- S

EE

A

-M P1

F

OR

C

ON

T.

PARTIAL GROUND FLOOR PLAN - PART C -

MECHANICAL PIPING

A-MP103

TM/BH IR

C2 1/8" = 1'-0"

PARTIAL GROUND FLOOR PLAN - PART C - MECHANICAL PIPING

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

VA NY Manhattan Campus

423 E 23RD Street, New York, NY 10010

630-600A

Project Director

Revisions: Date:

A/E:

AECOM

3101 WILSON BLVD, SUITE 900

ARLINGTON, VA. 22201

703-682-4900

WWW.AECOM.COM

Construction Document Refresh

Key Plan

Balance of Work

9/12/2022

AutoCAD SHX Text

1. HWS/HWR SERVE CUH-1. PIPES DROP DOWN ALONG WALL AND PENETRATE HWS/HWR SERVE CUH-1. PIPES DROP DOWN ALONG WALL AND PENETRATE WALL INTO BACK OF CUH-1 FOR CONNECTION TO UNIT. COORDINATE CONNECTION LOCATIONS WITH CUH-1 PURCHASED. 2. DIMENSION SHOWN IS TO CENTER LINE OF CUH-1 PURCHASED. COORDINATE DIMENSION SHOWN IS TO CENTER LINE OF CUH-1 PURCHASED. COORDINATE EQUIPMENT DIMENSIONS WITH CONTRACTOR INSTALLING WALL CRASH RAILS TO ELIMINATE CLEARANCE CONFLICTS.

AutoCAD SHX Text

1. SEE SHEET A-M001 FOR MECHANICAL SYMBOLS AND ABBREVIATIONS. SEE SHEET A-M001 FOR MECHANICAL SYMBOLS AND ABBREVIATIONS. 2. WHERE APPLICABLE, REFER TO DRAWING A-GI001 FOR FIRE AND SMOKE BARRIER WHERE APPLICABLE, REFER TO DRAWING A-GI001 FOR FIRE AND SMOKE BARRIER WALL LEGEND. 3. UPON COMPLETION OF INSTALLATIONS OF HVAC WORK, CALIBRATE ALL THERMOSTATS UPON COMPLETION OF INSTALLATIONS OF HVAC WORK, CALIBRATE ALL THERMOSTATS AND BALANCE WATER AND AIR FLOWS AT ALL FANS, AIR TERMINAL UNITS, UNIT HEATERS, AND AIR DEVICES AFFECTED BY THIS WORK TO THEIR SPECIFIED VALUES. ALL TEST AND BALANCE WORK TO BE ACCOMPLISHED BY AN AABC, NEMI, OR NEBB CERTIFIED BALANCING CONTRACTOR. 4. PROVIDE 2-WAY CONTROL VALVES FOR HEATING WATER COIL (UNLESS NOTED PROVIDE 2-WAY CONTROL VALVES FOR HEATING WATER COIL (UNLESS NOTED OTHERWISE).

AutoCAD SHX Text

ELEC

AutoCAD SHX Text 0165S

AutoCAD SHX Text

LOCKERS

AutoCAD SHX Text 0168S

AutoCAD SHX Text

ELEC

AutoCAD SHX Text 0167S

AutoCAD SHX Text G191S

AutoCAD SHX Text

SECURITY RM.

AutoCAD SHX Text 0202S

AutoCAD SHX Text 0171S

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

AutoCAD SHX Text

SHR

AutoCAD SHX Text G193S

AutoCAD SHX Text

TOILET

AutoCAD SHX Text G190S

AutoCAD SHX Text

VEST

AutoCAD SHX Text 0199S

AutoCAD SHX Text

ELEV.MACH. RM.

AutoCAD SHX Text

0203AS

AutoCAD SHX Text

STAFF TOILET

AutoCAD SHX Text

0202BS

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text 0202S

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

0202AS

AutoCAD SHX Text

IT (TR-D)

AutoCAD SHX Text

0209SA

AutoCAD SHX Text

LAUNDRY

AutoCAD SHX Text 0184S

AutoCAD SHX Text

PUMPS

AutoCAD SHX Text 0166S

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

STAIRS #3

AutoCAD SHX Text G2189S

AutoCAD SHX Text Open

AutoCAD SHX Text to Above

AutoCAD SHX Text to Above

AutoCAD SHX Text Open

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

SECURITY CONTROL

AutoCAD SHX Text

RM. (POST 7)

AutoCAD SHX Text 0200S

AutoCAD SHX Text

3-WAY

AutoCAD SHX Text

HWR

AutoCAD SHX Text

HWS

AutoCAD SHX Text

HWR

AutoCAD SHX Text

HWS

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

HWR

AutoCAD SHX Text

HWS

AutoCAD SHX Text 1"

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 1"

AutoCAD SHX Text F I R S T A V E N U E

AutoCAD SHX Text A S S E R L E V Y P L A C E

AutoCAD SHX Text E A S T 2 3 r d. S T R E E T

AutoCAD SHX Text

BLDG 3

AutoCAD SHX Text

BLDG 2

AutoCAD SHX Text

BLDG 4 / 5

AutoCAD SHX Text

E A S T 25 TH STREET

AutoCAD SHX Text

BLDG 1

AutoCAD SHX Text N

AutoCAD SHX Text

BLDG 6

# KEYED NOTES:

GENERAL NOTES:

22 2720

18161412

V

W

X

Z

AA

U

CC

DD

Z

AA

BB

Y

Y

EE

HH

DN

DN DN

FREEZER 1

3093E

FREEZER 2

3096E

REFRIGERATOR 1

3092E REFRIGERATOR 2

3095E

REFR 3

3070C

89 89

5 5 3 6 3 6

3 63 6

7 7

8 9

3 6

12 12

PARTIAL THIRD FLOOR PLAN -

MECHANICAL PIPING

1/8" = 1'-0"F5 PARTIAL THIRD FLOOR PLAN - MECHANICAL PIPING

A-MP130

BH IR

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

VA NY Manhattan Campus

423 E 23RD Street, New York, NY 10010

630-600A

Project Director

Revisions: Date:

A/E:

AECOM

3101 WILSON BLVD, SUITE 900

ARLINGTON, VA. 22201

703-682-4900

WWW.AECOM.COM

Construction Document Refresh

Key Plan

Balance of Work

9/12/2022

AutoCAD SHX Text

1. REFRIGERANT PIPES UP TO CONDENSER #1 LOCATED ON ROOF ABOVE. REFRIGERANT REFRIGERANT PIPES UP TO CONDENSER #1 LOCATED ON ROOF ABOVE. REFRIGERANT PIPES SIZED PER REFRIGERATOR/FREEZER MANUFACTURER'S RECOMMENDATIONS. S RECOMMENDATIONS. 2. EXACT QUANTITY AND SIZES OF PIPES TO BE DETEERMINED BY EXACT QUANTITY AND SIZES OF PIPES TO BE DETEERMINED BY REFRIGERATOR/FREEZER MANUFACTURER. REFRIGERANT PIPES RUN ABOVE REFRIGERATOR/FREEZER CEILINGS. CONTRACTOR TO CONFIRM FINAL ROUTING PATH BASED ON EXISTING CONDITIONS. 3. REFRIGERANT PIPES DOWN TO REFRIGERATOR/FREEZER EVAPORATOR. PROVIDE LOOP REFRIGERANT PIPES DOWN TO REFRIGERATOR/FREEZER EVAPORATOR. PROVIDE LOOP VENT ON REFRIGERANT SUCTION LINE PER MANUFACTURER'S RECOMMENDATIONS. S RECOMMENDATIONS. 4. CONDENSATE DRAIN PIPE RUNS ALONG WALL PITCHED TOWARD FLOOR DRAIN. PIPE CONDENSATE DRAIN PIPE RUNS ALONG WALL PITCHED TOWARD FLOOR DRAIN. PIPE FOR EACH REFRIGERATOR/FREEZER SHALL BE INDEPENDENT AND NOT COMBINED WITH DRAIN FROM ANOTHER REFRIGERATOR/FREEZER UNLESS OTHERWISE INDICATED BY THE MANUFACTURER. 5. CONDENSATE PIPE UTILIZES A PIPE UNION FITTING AT CONNECTION POINT BELOW CONDENSATE PIPE UTILIZES A PIPE UNION FITTING AT CONNECTION POINT BELOW EACH EVAPORATIVE BLOWER COIL'S DRAIN LINE FOR DISCONNECTING AND SERVICING S DRAIN LINE FOR DISCONNECTING AND SERVICING PURPOSES 6. ALL PIPE PENETRATIONS THROUGH REFRIGERATOR/FREEZER ENCLOSURE TO BE ALL PIPE PENETRATIONS THROUGH REFRIGERATOR/FREEZER ENCLOSURE TO BE SEALED AIR TIGHT (TYPICAL). 7. CONDENSATE DRAIN LINE IN FREEZER ENCLOSURE TO BE PROVIDED WITH HEAT CONDENSATE DRAIN LINE IN FREEZER ENCLOSURE TO BE PROVIDED WITH HEAT TRACING SPIRALED AND TAPED TO PIPE AND INSULATED WITH 1" THICK FLEXIBLE ELASTOMERIC CLOSED-CELL FOAM INSULATION PER FREEZER MANUFACTURER RECOMMENDATIONS INSULATION. 8. CONDENSATE DRAIN TO BE PROVIDED WITH ‘P' TRAP AND AIR GAP BETWEEN FLOOR CONDENSATE DRAIN TO BE PROVIDED WITH ‘P' TRAP AND AIR GAP BETWEEN FLOOR P' TRAP AND AIR GAP BETWEEN FLOOR TRAP AND AIR GAP BETWEEN FLOOR DRAIN AND DRAIN LINE. PIPE TRAP TO BE MOUNTED PARALLEL TO REFRIGERATOR WALL.. 9. CONDENSATE DRAIN PIPE DOWN ALONG OUTSIDE OF REFRIGERATOR ENCLOSURE CONDENSATE DRAIN PIPE DOWN ALONG OUTSIDE OF REFRIGERATOR ENCLOSURE CLAMPED AND SECURED IN PLACE WITH MINIMUM 3/4" SPACE CLEARANCE BETWEEN PIPE AND ENCLOSURE FOR CLEANING PURPOSES. 10. REFRIGERANT PIPES UP TO CONDENSER #2 LOCATED ON ROOF ABOVE. REFRIGERANT REFRIGERANT PIPES UP TO CONDENSER #2 LOCATED ON ROOF ABOVE. REFRIGERANT PIPES SIZED PER REFRIGERATOR/FREEZER MANUFACTURER'S RECOMMENDATIONS. S RECOMMENDATIONS. 11. ROUTE PIPING AROUND CEILING ACCESS DOOR OPENING. TO ALLOW FOR CEILING ROUTE PIPING AROUND CEILING ACCESS DOOR OPENING. TO ALLOW FOR CEILING ACCESS. 12. P-TRAPS TO BE MOUNTED ONE HIGHER THAN THE OTHER PARALLEL TO P-TRAPS TO BE MOUNTED ONE HIGHER THAN THE OTHER PARALLEL TO REFRIGERATOR WALL SO AS LIMIT PIPE PROTRUSION TOWARD KITCHEN SPACE.

AutoCAD SHX Text

1. SEE SHEET A-M001 FOR MECHANICAL SYMBOLS AND ABBREVIATIONS. SEE SHEET A-M001 FOR MECHANICAL SYMBOLS AND ABBREVIATIONS. 2. WHERE APPLICABLE, REFER TO DRAWING A-GI001 FOR FIRE AND SMOKE BARRIER WHERE APPLICABLE, REFER TO DRAWING A-GI001 FOR FIRE AND SMOKE BARRIER WALL LEGEND.

AutoCAD SHX Text

SALAD PREP

AutoCAD SHX Text 0380C

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text 3102E

AutoCAD SHX Text

PAPER

AutoCAD SHX Text

PRODUCTS

AutoCAD SHX Text 3097E

AutoCAD SHX Text 3081S

AutoCAD SHX Text

PATIENT SERVICES

AutoCAD SHX Text 3083E

AutoCAD SHX Text

SPECIAL DIET KITCH

AutoCAD SHX Text

3061AE

AutoCAD SHX Text

FILE STORAGE

AutoCAD SHX Text 3077C

AutoCAD SHX Text

DISTR

AutoCAD SHX Text 3076C

AutoCAD SHX Text

SERVICE LOBBY

AutoCAD SHX Text 3089E

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text 3090E

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text 3091E

AutoCAD SHX Text

STAIR 1-1

AutoCAD SHX Text 3098E

AutoCAD SHX Text

COOKS

AutoCAD SHX Text 3099E

AutoCAD SHX Text

P SUP ASST

AutoCAD SHX Text 3088E

AutoCAD SHX Text

SCULLERY

AutoCAD SHX Text 3086E

AutoCAD SHX Text

MAIN KITCHEN

AutoCAD SHX Text

3108CE

AutoCAD SHX Text

FOOD FOREMAN

AutoCAD SHX Text

3108AE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

3108BE

AutoCAD SHX Text

KITCHEN STOR

AutoCAD SHX Text

3110AN

AutoCAD SHX Text

DIET COMM CENTER

AutoCAD SHX Text 3100E

AutoCAD SHX Text

UTILITY

AutoCAD SHX Text 3101C

AutoCAD SHX Text

STORAGE ROOM

AutoCAD SHX Text 3102C

AutoCAD SHX Text

LC

AutoCAD SHX Text 3103C

AutoCAD SHX Text

JC

AutoCAD SHX Text 3105C

AutoCAD SHX Text

DISH WASHERS

AutoCAD SHX Text 3107N

AutoCAD SHX Text

KITCH & DISH WASHING

AutoCAD SHX Text 3075S

AutoCAD SHX Text

SEC ACNS

AutoCAD SHX Text

EDUCATION

AutoCAD SHX Text 3075S

AutoCAD SHX Text

NURSE RECRUITER

AutoCAD SHX Text 3044S

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

3044AS

AutoCAD SHX Text

NURSING

AutoCAD SHX Text 3043S

AutoCAD SHX Text

PATIENT SERVICES

AutoCAD SHX Text 3042S

AutoCAD SHX Text

PATIENT SERVICES

AutoCAD SHX Text 3040S

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

AutoCAD SHX Text

ELEV SHAFT

AutoCAD SHX Text

AutoCAD SHX Text

ELEV SHAFT

AutoCAD SHX Text

AutoCAD SHX Text

ELEV SHAFT

AutoCAD SHX Text

AutoCAD SHX Text

ELEV SHAFT

AutoCAD SHX Text 3039C

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text 3097E

AutoCAD SHX Text

PAPER PRODUCTS

AutoCAD SHX Text 3038C

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

ELEV SHAFT

AutoCAD SHX Text

AutoCAD SHX Text

ELEV SHAFT

AutoCAD SHX Text

AutoCAD SHX Text

ELEV SHAFT

AutoCAD SHX Text

AutoCAD SHX Text

ELEV SHAFT

AutoCAD SHX Text 3123N

AutoCAD SHX Text

SEC TO CHIEF

AutoCAD SHX Text

3123CN

AutoCAD SHX Text

PROG CLERK

AutoCAD SHX Text 3123N

AutoCAD SHX Text

SITE MANAGER

AutoCAD SHX Text

3123EN

AutoCAD SHX Text

TOILET

AutoCAD SHX Text

3123DN

AutoCAD SHX Text

TOILET

AutoCAD SHX Text 3120N

AutoCAD SHX Text

SEC/CLERK

AutoCAD SHX Text 3118E

AutoCAD SHX Text

DIETICIAN

AutoCAD SHX Text 3117N

AutoCAD SHX Text

TRAINING RM

AutoCAD SHX Text 3116N

AutoCAD SHX Text

MENS TLT

AutoCAD SHX Text 3115N

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text 3112N

AutoCAD SHX Text

EL CL

AutoCAD SHX Text 3124N

AutoCAD SHX Text

EL CL

AutoCAD SHX Text 3109N

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

3110AN

AutoCAD SHX Text

DIET COMM CENTER

AutoCAD SHX Text 3125N

AutoCAD SHX Text

STAIR #4

AutoCAD SHX Text 3097E

AutoCAD SHX Text

PAPER PRODUCTS

AutoCAD SHX Text 3110N

AutoCAD SHX Text

PATIENTS CLOTHING

AutoCAD SHX Text 3081E

AutoCAD SHX Text

DIET VOLUNTEER

AutoCAD SHX Text 3085E

AutoCAD SHX Text

DIETETICS OFFICE

AutoCAD SHX Text

3085AE

AutoCAD SHX Text

CHIEF DIETETICS

AutoCAD SHX Text

SE #13

AutoCAD SHX Text 3078C

AutoCAD SHX Text

CLOSET

AutoCAD SHX Text

REFRIGERATOR

AutoCAD SHX Text

CCD

AutoCAD SHX Text

CCD

AutoCAD SHX Text

CCD

AutoCAD SHX Text

CCD

AutoCAD SHX Text

CCD

AutoCAD SHX Text

CCD

AutoCAD SHX Text

RL/RS PIPE PAIR

AutoCAD SHX Text

RL/RS PIPE PAIR

AutoCAD SHX Text

CCD

AutoCAD SHX Text

CEILING ACCESS DOOR

AutoCAD SHX Text F I R S T A V E N U E

AutoCAD SHX Text A S S E R L E V Y P L A C E

AutoCAD SHX Text E A S T 2 3 r d. S T R E E T

AutoCAD SHX Text

BLDG 3

AutoCAD SHX Text

BLDG 2

AutoCAD SHX Text

BLDG 4 / 5

AutoCAD SHX Text

E A S T 25 TH STREET

AutoCAD SHX Text

BLDG 1

AutoCAD SHX Text N

22 2720

18161412

X

Z

AA

CC

DD

Z

AA

BB

Y

Y

EE

HH

262422 2720

18161412

X

Z

AA

CC

DD

Z

AA

BB

Y

Y

EE

HH

GENERAL NOTES:

# KEYED NOTES:

PARTIAL FOURTH FLOOR, ROOF PLAN -

MECHANICAL PIPING

A-MP140

TM/BH RC/IR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

VA NY Manhattan Campus

423 E 23RD Street, New York, NY 10010

630-600A

Project Director

Revisions: Date:

A/E:

AECOM

3101 WILSON BLVD, SUITE 900

ARLINGTON, VA. 22201

703-682-4900

WWW.AECOM.COM

Construction Document Refresh

1 & GEN PLTFRM

Key Plan

Balance of Work

9/12/2022

PLAN

NORTH

1/8" = 1'-0"F1 PARTIAL FOURTH FLOOR NEW WORK PLAN - MECHANICAL PIPING

0 4'-0" 8'-0" 16'-0"

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

ROOF

AutoCAD SHX Text

ROOF

AutoCAD SHX Text

STAIR 1-1

AutoCAD SHX Text

MECHANICAL ROOM

AutoCAD SHX Text

ELEVATOR MACHINE ROOM

AutoCAD SHX Text

RD (E)

AutoCAD SHX Text

ROOF

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text A. SEE SHEET A-GI001 FOR MECHANICAL SYMBOLS AND ABBREVIATIONS. SEE SHEET A-GI001 FOR MECHANICAL SYMBOLS AND ABBREVIATIONS. B. WHERE IA APPLICABLE, REFER TO DRAWING A-GI001 FOR FIRE AND SMOKE BARRIER WHERE IA APPLICABLE, REFER TO DRAWING A-GI001 FOR FIRE AND SMOKE BARRIER WALL LEGEND. C. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS (DRAWINGS AND PROJECT MANUALS INCLUDING ADDENDUMS) AND ALL APPLICABLE CODES AND STANDARDS. D. THESE PLANS ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL INCLUDE THESE PLANS ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL INCLUDE APPROPRIATE ALLOWANCES FOR OFFSETS AS REQUIRED TO ACCOMMODATE VERTICAL AND HORIZONTAL VARIATIONS IN THE LOCATIONS AND ELEVATIONS OF DUCTWORK, PIPING AND EXISTING CONDITIONS. E. PENETRATIONS OF WALLS OR FLOORS FOR PIPING, DUCTWORK AND/OR EQUIPMENT PENETRATIONS OF WALLS OR FLOORS FOR PIPING, DUCTWORK AND/OR EQUIPMENT SHALL BE PROPERLY SEALED AFTER INSTALLATIONS. FIELD VERIFY EXISTING WALL CONSTRUCTION AND SEAL PENETRATIONS AS REQUIRED TO MAINTAIN WALL OR FLOOR RATING. F. COORDINATE ALL BUILDING SYSTEMS SHUT-DOWN REQUIREMENTS WITH THE OWNER COORDINATE ALL BUILDING SYSTEMS SHUT-DOWN REQUIREMENTS WITH THE OWNER VA CFM. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE AND PROVIDE SYSTEM DRAIN DOWN AND FILL OF THE AFFECTED HVAC AND PLUMBING SYSTEMS PER THE OWNER'S/FACILITY ENGINEER'S REQUIREMENTS. G. EACH TRADE SHALL COORDINATE THE ROUTING AND INSTALLATION OF HIS WORK EACH TRADE SHALL COORDINATE THE ROUTING AND INSTALLATION OF HIS WORK WITH THAT OF ALL OTHER TRADES THROUGH THE GENERAL CONTRACTOR. IN ANY INSTANCES OF CONFLICT, SYSTEMS REQUIRING "GRADE" OR "SLOPE" FOR DRAINAGE (SANITARY SEWER, SANITARY VENT, EQUIPMENT/CONDENSATE DRAINS, ETC.) SHALL HAVE PRIORITY.

AutoCAD SHX Text

1. CONDENSER UNIT #2 TO SERVE REFRIGERATOR 3 ON THIRD FLOOR. CONDENSER UNIT #2 TO SERVE REFRIGERATOR 3 ON THIRD FLOOR. 2. REFRIGERANT LIQUID AND SUCTION PIPING DOWN TO THIRD FLOOR CEILING REFRIGERANT LIQUID AND SUCTION PIPING DOWN TO THIRD FLOOR CEILING THROUGH ROOF PENETRATION PIPE PORTAL FLASHING SYSTEM. 3. REFRIGERANT PIPES TO BE SIZED PER REFRIGERATOR /FREEZER REFRIGERANT PIPES TO BE SIZED PER REFRIGERATOR /FREEZER MANUFACTURER'S RECOMMENDATIONS. S RECOMMENDATIONS. 4. CONDENSER UNIT #1 TO SERVE REFRIGERATORS 1 AND 2, AND FREEZERS 1 CONDENSER UNIT #1 TO SERVE REFRIGERATORS 1 AND 2, AND FREEZERS 1 AND 2 ON THIRD FLOOR. 5. REFRIGERANT PIPING FROM CONDENSER DOWN THROUGH ROOF TO THIRD REFRIGERANT PIPING FROM CONDENSER DOWN THROUGH ROOF TO THIRD FLOOR CEILING.

AutoCAD SHX Text F I R S T A V E N U E

AutoCAD SHX Text A S S E R L E V Y P L A C E

AutoCAD SHX Text E A S T 2 3 r d. S T R E E T

AutoCAD SHX Text

BLDG 3

AutoCAD SHX Text

BLDG 2

AutoCAD SHX Text

BLDG 4 / 5

AutoCAD SHX Text

E A S T 25 TH STREET

AutoCAD SHX Text

BLDG 1

AutoCAD SHX Text N

KEYED NOTES:#

Y

W

X

HX-W-1

COPY

ROOM

MECH

ROOM

0272CN

MECH

ROOM

0270N

AHU-W-1

HWP-W-1

ET-W-1

FT-W-1 AS-W-1

GLYCOL TANK

GENERAL NOTES:

33 3533 35

Y

W

X

EF-W-1

RF-W-1 ET-W-1

VVR-W-1

COPY

MECH

ROOM

0272CN

OFFICE

0272BN

CD2

CD2

RG1

RG1

CD2 CD2 CD3

T

T

EF-W-6

SR

480ER

F1 1/8" = 1'-0"

ENLARGED FLOOR PLAN - MECHANICAL PIPING

ENLARGED FLOOR PLANS -

MECHANICAL

A-M301

TM/BH IR

PLAN

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

VA NY Manhattan Campus

423 E 23RD Street, New York, NY 10010

630-600A

Project Director

Revisions: Date:

A/E:

AECOM

3101 WILSON BLVD, SUITE 900

ARLINGTON, VA. 22201

703-682-4900

WWW.AECOM.COM

Construction Document Refresh

Key Plan

Balance of Work

9/12/2022

F1 1/4" = 1'-0"

ENLARGED FLOOR PLAN - MECHANICAL DUCTWORK

PLAN

NORTH

0 2'-0" 4'-0" 8'-0" 0 2'-0" 4'-0" 8'-0"

AutoCAD SHX Text

1. ROUTE 1"INSULATED COPPER CONDENSATE PIPING (TRAPPED) FROM AHU OR ACU TO ROUTE 1"INSULATED COPPER CONDENSATE PIPING (TRAPPED) FROM AHU OR ACU TO NEAREST FLOOR DRAIN. REFER TO PLUMBING DRAWINGS FOR MORE INFORMATION ON FLOOR DRAIN LOCATION IN THE ROOM. 2. AIR CURTAIN CONTROL PANEL MOUNTED ON WALL. BOTTOM OF PANEL AIR CURTAIN CONTROL PANEL MOUNTED ON WALL. BOTTOM OF PANEL APPROXIMATELY 48 INCHES ABOVE FINISHED FLOOR. 3. EQUIPMENT HUNG FROM CEILING. EQUIPMENT HUNG FROM CEILING. 4. REMOVE CAP FROM EXISTING SHUT OFF VALVE LOCATED ABOVE CEILING AND REMOVE CAP FROM EXISTING SHUT OFF VALVE LOCATED ABOVE CEILING AND CONNECT NEW PIPE. A BROADER SHUTDOWN MAY BE NEEDED TO TURN OFF THE STEAM PRIOR TO CONNECTING THE NEW PIPE. CONTRACTOR SHALL COORDINATE THIS SHUTDOWN WITH THE VA OFFICE. THE WORK SHALL BE DONE OUTSIDE OF THE WORK SHALL BE DONE OUTSIDE OF THE HEATING SEASON AND SHALL BE SCHEDULED TO MINIMIZE THE DURATION OF THE SHUTDOWN. 5. NEW STEAM PIPE DOWN TROUGH FLOOR TO STEAM TUNNEL BELOW. NEW STEAM PIPE DOWN TROUGH FLOOR TO STEAM TUNNEL BELOW. 6. APPROXIMATE BOUNDARY LOCATION OF STEAM TUNNEL BELOW FLOOR. APPROXIMATE BOUNDARY LOCATION OF STEAM TUNNEL BELOW FLOOR. 7. THERMAL EXPANSION LOOP FOR HWS/R. THERMAL EXPANSION LOOP FOR HWS/R. 8. PROVIDE A 12" MINIMUM CONCRETE CLEARANCE BETWEEN PIPE PENETRATION PROVIDE A 12" MINIMUM CONCRETE CLEARANCE BETWEEN PIPE PENETRATION OPENINGS (OPENING EDGE TO EDGE CLEARANCE) FOR PIPES PENETRATING THROUGH THE FLOOR TO CRAWL SPACE BELOW. 9. PIPE DOWN IN CHASE THROUGH FLOOR SLAB TO BASEMENT CRAWL SPACE. PIPE DOWN IN CHASE THROUGH FLOOR SLAB TO BASEMENT CRAWL SPACE. 10. SEE ARCHITECTURAL DRAWINGS FOR DETAIL OF MOUNTING LOCATION OF AIR CURTAIN SEE ARCHITECTURAL DRAWINGS FOR DETAIL OF MOUNTING LOCATION OF AIR CURTAIN SERVING ROLL-UP DOOR. 11. GLYCOL FEED SYSTEM PACKAGE WITH 55 GALLON STORAGE TANK AND ONE THIRD GLYCOL FEED SYSTEM PACKAGE WITH 55 GALLON STORAGE TANK AND ONE THIRD HP PUMP WITH 115 VOLT CORD FOR ELECTRICAL CONNECTION TO ELECTRICAL OUTLET. 12. FLASH TANK VENT PIPE THROUGH WALL. VENT EXTENDS MINIMUM OF 12 INCHES FLASH TANK VENT PIPE THROUGH WALL. VENT EXTENDS MINIMUM OF 12 INCHES OUT FROM FACE OF WALL EXTERIOR. 13. PRELIMINARY LOCATIONS OF THE DIFFERENTIAL PRESSURE SENSORS ARE AS SHOWN. PRELIMINARY LOCATIONS OF THE DIFFERENTIAL PRESSURE SENSORS ARE AS SHOWN. FINAL LOCATIONS OF THE SENSORS SHALL BE DETERMINED BY THE TAB AND CONTROLS CONTRACTORS. 14. CONTRACTOR SHALL PROVIDE TEMPORARY COOLING. CONTRACTOR IS RESPONSIBLE CONTRACTOR SHALL PROVIDE TEMPORARY COOLING. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE ELECTRICAL ROOMS AT 80°F UNTIL SUCH A TIME THAT THETEMPORARY COOLING IS NO LONGER NEEDED BY THE ELECTRICAL EQUIPMENT.

AutoCAD SHX Text

2 1/2" CHS/R DN

AutoCAD SHX Text 4"

AutoCAD SHX Text 2 1/2"

AutoCAD SHX Text v

AutoCAD SHX Text 3"

AutoCAD SHX Text 4"

AutoCAD SHX Text

HWR

AutoCAD SHX Text

HWS

AutoCAD SHX Text 4"

AutoCAD SHX Text 2 1/2"

AutoCAD SHX Text v

AutoCAD SHX Text 4"

AutoCAD SHX Text 4"

AutoCAD SHX Text

HWR

AutoCAD SHX Text

HWS

AutoCAD SHX Text 1 1/4"

AutoCAD SHX Text 1 1/4"

AutoCAD SHX Text 5"

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

MW

AutoCAD SHX Text

3/4" DOMESTIC WATER MAKE-UP. SEE PLUMBING DRAWINGS FOR CONTINUATION

AutoCAD SHX Text

LPR

AutoCAD SHX Text

LPS

AutoCAD SHX Text

LPS

AutoCAD SHX Text

1. SEE SHEET A-M001 FOR MECHANICAL SYMBOLS AND ABBREVIATIONS. SEE SHEET A-M001 FOR MECHANICAL SYMBOLS AND ABBREVIATIONS. 2. WHERE APPLICABLE, REFER TO DRAWING A-GI001 FOR FIRE AND SMOKE BARRIER WHERE APPLICABLE, REFER TO DRAWING A-GI001 FOR FIRE AND SMOKE BARRIER WALL LEGEND. 3. UPON COMPLETION OF INSTALLATIONS OF HVAC WORK, CALIBRATE ALL THERMOSTATS UPON COMPLETION OF INSTALLATIONS OF HVAC WORK, CALIBRATE ALL THERMOSTATS AND BALANCE WATER AND AIR FLOWS AT ALL FANS, AIR TERMINAL UNITS, UNIT HEATERS, AND AIR DEVICES AFFECTED BY THIS WORK TO THEIR SPECIFIED VALUES. ALL TEST AND BALANCE WORK TO BE ACCOMPLISHED BY AN AABC, NEMI, OR NEBB CERTIFIED BALANCING CONTRACTOR. 4. PROVIDE 2-WAY CONTROL VALVES FOR HEATING WATER COIL (UNLESS NOTED PROVIDE 2-WAY CONTROL VALVES FOR HEATING WATER COIL (UNLESS NOTED OTHERWISE).

AutoCAD SHX Text 46x12 OA

AutoCAD SHX Text

RELIEF AIR

AutoCAD SHX Text 16x14 EA

AutoCAD SHX Text 30x24 RA

AutoCAD SHX Text 6"

AutoCAD SHX Text 8x10 SA

AutoCAD SHX Text 8"

AutoCAD SHX Text 24x16 RA

AutoCAD SHX Text 10"

AutoCAD SHX Text 8"

AutoCAD SHX Text 8"

AutoCAD SHX Text D

AutoCAD SHX Text 34x20 RA

AutoCAD SHX Text

CONTROL PANEL

AutoCAD SHX Text

VFD

AutoCAD SHX Text 10x10 EA

AutoCAD SHX Text 14x8 EA

AutoCAD SHX Text 30x24 REA, BELOW

AutoCAD SHX Text

VFD

AutoCAD SHX Text

SD

AutoCAD SHX Text F I R S T A V E N U E

AutoCAD SHX Text A S S E R L E V Y P L A C E

AutoCAD SHX Text E A S T 2 3 r d. S T R E E T

AutoCAD SHX Text

BLDG 3

AutoCAD SHX Text

BLDG 2

AutoCAD SHX Text

BLDG 4 / 5

AutoCAD SHX Text

E A S T 25 TH STREET

AutoCAD SHX Text

BLDG 1

AutoCAD SHX Text N

C1

B9

C4 IN-LINE PUMPS - CONNECTIONS

F1

C6AIR HANDLING UNIT DRAIN TRAP DETAIL

UNIT HEATERS (HOT WATER) -PIPING

CONNECTIONS

TERMINAL UNIT WATER

COILS -PIPING CONNECTIONS

POWER ROOF VENTILATOR F4 INLINE FAN DETAIL F6 VAV BOX TAKEOFF DETAIL F8 CEILING DIFFUSER DETAIL

D9 MAKE UP WATER PIPING DETAIL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

VA NY Manhattan Campus

423 E 23RD Street, New York, NY 10010

630-600A

Project Director

Revisions: Date:

A/E:

AECOM

3101 WILSON BLVD, SUITE 900

ARLINGTON, VA. 22201

703-682-4900

WWW.AECOM.COM

Construction Document Refresh

Key Plan

Balance of Work

9/12/2022

DETAILS

TM/BH WY

A-M501

AutoCAD SHX Text

NTS

AutoCAD SHX Text

DRAW THRU

AutoCAD SHX Text

BLOW THRU

AutoCAD SHX Text

2" PLUS X

AutoCAD SHX Text

1" MINIMUM

AutoCAD SHX Text X

AutoCAD SHX Text 2X

AutoCAD SHX Text

UNIT TYPE

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

WHERE X = STATIC PRESSURE IN PAN

AutoCAD SHX Text DRAIN LINE SHALL BE AT LEAST THE SAME SIZE AS THE NIPPLE ON THE DRAIN PAN PIPING SHALL BE RIGID COPPER TYPE L OR TYPE M UNLESS NOTE BELOW IS MET

AutoCAD SHX Text

PITCH DOWN TOWARD DRAIN

AutoCAD SHX Text

CLEAN OUT

AutoCAD SHX Text

FLOOR SINK

AutoCAD SHX Text

DRAIN PAN

AutoCAD SHX Text NOTE: 1. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE TO BE CONNECTED.

AutoCAD SHX Text

DIELECTRIC FITTING

AutoCAD SHX Text

NTS

AutoCAD SHX Text

COIL

AutoCAD SHX Text

TEST PLUG (TYP.)

AutoCAD SHX Text

REDUCER, IF REQUIRED

AutoCAD SHX Text

WATER RETURN

AutoCAD SHX Text

MANUAL AIR VENT

AutoCAD SHX Text

UNION CONNECTIONS (TYP.)

AutoCAD SHX Text

WATER SUPPLY

AutoCAD SHX Text

SHUT OFF VALVE

AutoCAD SHX Text

DRAIN WITH HOSE CONNECTION

AutoCAD SHX Text

MV

AutoCAD SHX Text

MODULATION CONTROL VALVE

AutoCAD SHX Text

NTS

AutoCAD SHX Text PIPE HANGERS - PROVIDE DOUBLE DEFLECTION NEOPRENE (TYPE HN) FOR FIRST TWO ON EACH SIDE OF PUMP (SEE NOTE NO. 1)

AutoCAD SHX Text

PRESSURE GAGE

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

STRAINER

AutoCAD SHX Text

FLEXIBLE CONNECTION

AutoCAD SHX Text

BALL OR BUTTERFLY TYP.

AutoCAD SHX Text NOTES: 1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.

AutoCAD SHX Text

BALANCING DEVICE

AutoCAD SHX Text

NTS

AutoCAD SHX Text

NOTE: 1. 2. 3. 4.

AutoCAD SHX Text SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" CADMIUM PLATED LAG BOLTS NOT OVER 12" ON CENTER. SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS (CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF). RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER, THEN THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE. MINIMUM CURB HEIGHT SHALL BE 12 INCHES. INCREASE HEIGHT, IF REQUIRED, TO OVERCOME SNOW DRIFT.

AutoCAD SHX Text

MOTORIZED DAMPER

AutoCAD SHX Text

RIGID CONDUIT TO ACCOMMODATE ELECTRICAL WIRES

AutoCAD SHX Text

SEE NOTE 2

AutoCAD SHX Text

PREFABRICATED ROOF CURB SEE NOTE 4

AutoCAD SHX Text

WOOD NAILING STRIP

AutoCAD SHX Text

ELECTRICAL CONDUIT GUIDE

AutoCAD SHX Text

MOTOR HOUSING

AutoCAD SHX Text

DUCT

AutoCAD SHX Text

TRANSITION DUCT TO FULL SIZE OF DAMPER SUPPLIED WITH ROOF VENTILATOR

AutoCAD SHX Text

ROOF

AutoCAD SHX Text

SEE NOTE 2

AutoCAD SHX Text

SEE NOTE 1

AutoCAD SHX Text

CURB CAP

AutoCAD SHX Text

NTS

AutoCAD SHX Text

INLINE FAN

AutoCAD SHX Text

HANGER BRACKETS BY FAN MANUFACTURER (TYPICAL)

AutoCAD SHX Text MOTOR ACCESS COVER - COORDINATE POSITION WITH FIELD CONDITIONS TO PROVIDE SERVICE ACCESS

AutoCAD SHX Text SPRING AND RUBBER- IN-SHEAR ISOLATION HANGERS. MIN. 1.0" STATIC DEFLECTION (TYPICAL)

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

CONNECT DUCTWORK TO FAN W/ 1/8" THICK NEOPRENE GASKET W/ BOLTS.

AutoCAD SHX Text

FLEXIBLE CONNECTION (TYPICAL)

AutoCAD SHX Text

DUCTWORK- SIZE AS INDICATED ON PLANS (TYP). TRANSITION AS REQUIRED.

AutoCAD SHX Text SUPPORT RODS FROM BUILDING STRUCTURE, COORDINATE ROD SIZE W/ ISOLATORS AND ROD LENGTH W/ LOCATION.

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

NTS

AutoCAD SHX Text

CONTROL BOX

AutoCAD SHX Text

MAIN SUPPLY DUCT

AutoCAD SHX Text

DUCTWORK

AutoCAD SHX Text NOTES: 1. PROVIDE MINIMUM 3 FT SERVICE CLEARANCE AROUND VAV BOX TO PROVIDE MINIMUM 3 FT SERVICE CLEARANCE AROUND VAV BOX TO ACCESS CONTROL BOX AS WELL AS HOT WATER COIL COMPONENTS. 2. CONNECTION TO DIFFUSER SHALL BE DIRECT RUN WITH AS FEW CONNECTION TO DIFFUSER SHALL BE DIRECT RUN WITH AS FEW BENDS AS POSSIBLE.

AutoCAD SHX Text

3 INLET DIAMETER MINIMUM STRAIGHT DUCT TO INLET CONNECTION

AutoCAD SHX Text

ROUND DUCT SIZE BASED ON BOX INLET DIAMETER (SEE SCHEDULE)

AutoCAD SHX Text

CEILING TILE

AutoCAD SHX Text

LAY-IN TILE CEILING

AutoCAD SHX Text

ROUND NECK SEE SCHEDULE FOR SIZES

AutoCAD SHX Text

COLLAR WITH MANUAL VOLUME DAMPER

AutoCAD SHX Text

INSULATED FLEXIBLE DUCT (MAXIMUM 60" LENGTH)

AutoCAD SHX Text

NTS

AutoCAD SHX Text

NTS

AutoCAD SHX Text

SCREW TYPE CLAMP

AutoCAD SHX Text

SUPPLY DUCT

AutoCAD SHX Text

HOT WATER HEATING COIL

AutoCAD SHX Text

INSULATED FLEXIBLE DUCT TO DIFFUSER 5 FEET MAXIMUM LENGHT

AutoCAD SHX Text

DUCT SIZE REFER TO PLANS OR SCHEDULE

AutoCAD SHX Text

UNIT HEATER

AutoCAD SHX Text

HOT WATER

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

HOT WATER

AutoCAD SHX Text

RETURN

AutoCAD SHX Text

MV

AutoCAD SHX Text

2-WAY CONTROL VALVE UNLESS NOTED OTHERWISE

AutoCAD SHX Text

FLOW MEASURING AND BALANCING VALVE

AutoCAD SHX Text

UNIT HEATER

AutoCAD SHX Text

HOT WATER

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

HOT WATER

AutoCAD SHX Text

RETURN

AutoCAD SHX Text

MV

AutoCAD SHX Text

3-WAY CONTROL VALVE WHERE NOTED ON DRAWINGS

AutoCAD SHX Text

FLOW MEASURING AND BALANCING VALVE

AutoCAD SHX Text

SAME PIPE SIZE AS HOT WATER SUPPLY TO UNIT HEATER

AutoCAD SHX Text

PRESSURE REDUCING VALVE

AutoCAD SHX Text

CW

AutoCAD SHX Text

3/4" REDUCED PRESSURE ZONE BACKFLOW PREVENTER (PIPE TO NEAREST DRAIN)

AutoCAD SHX Text

PRESSURE GAUGE W/ GAUGE COCK (TYP)

AutoCAD SHX Text

GLOBE VALVE (NORMALLY CLOSED)

AutoCAD SHX Text

NTS

AutoCAD SHX Text

VOLUME DAMPER

AutoCAD SHX Text

CALIBRATED BALANCING VALVE

AutoCAD SHX Text F I R S T A V E N U E

AutoCAD SHX Text A S S E R L E V Y P L A C E

AutoCAD SHX Text E A S T 2 3 r d. S T R E E T

AutoCAD SHX Text

BLDG 3

AutoCAD SHX Text

BLDG 2

AutoCAD SHX Text

BLDG 4 / 5

AutoCAD SHX Text

E A S T 25 TH STREET

AutoCAD SHX Text

BLDG 1

AutoCAD SHX Text N

D1 HEAT EXCHANGER - STEAM TO HOT WATER

F4

STEAM LINE DRIP POCKET AND STEAM

TRAP ASSEMBLY

B8

FLOAT AND THERMOSTATIC STEAM TRAP

ASSEMBLY

D6 END OF STEAM LINE DRIP TRAP

F8

FT-W-2

HORIZONTAL FLASH TANK DETAIL

D4

FT-W-1

VERTICAL FLASH TANK DETAIL

B6

EXPANSION TANK AND AIR SEPARATOR

PIPING DETAIL

F6

AIR HANDLING UNIT

CHILLED WATER AND HOT WATER COIL PIPING DETAIL

F1 AIR HANDLING UNIT DETAIL

D8

MAKEUP AIR UNITS DUCT MOUNTED

CHILLED WATER COIL PIPING DETAIL

B4 FLEXIBLE EXPANSION LOOP DETAIL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

VA NY Manhattan Campus

423 E 23RD Street, New York, NY 10010

630-600A

Project Director

Revisions: Date:

A/E:

AECOM

3101 WILSON BLVD, SUITE 900

ARLINGTON, VA. 22201

703-682-4900

WWW.AECOM.COM

Construction Document Refresh

Key Plan

Balance of Work

9/12/2022

DETAILS

TM/BH WY

A-M502

AutoCAD SHX Text

NTS

AutoCAD SHX Text NOTES: 1. PROVIDE SADDLE SUPPORTS AND LEGS OR HANGERS FOR PROVIDE SADDLE SUPPORTS AND LEGS OR HANGERS FOR HEAT EXCHANGER. MOUNTING HEIGHT SHALL BE ADJUSTED TO FACILITATE GRAVITY RETURN OF STEAM CONDENSATE. 2. MAKE THE BYPASS THE SAME SIZE AS THE CONNECTIONS TO MAKE THE BYPASS THE SAME SIZE AS THE CONNECTIONS TO THE CONTROL VALVES. 3. CONTROL VALVES SHALL BE IN A AND SIZE CONTROL VALVES SHALL BE IN A AND SIZE 13 AND SIZE 23 SIZE ARRANGEMENT.

AutoCAD SHX Text

TEST PLUG (TYP.)

AutoCAD SHX Text

THERMOMETER (TYP.)

AutoCAD SHX Text

MPS STEAM SUPPLY

AutoCAD SHX Text

HEAT EXCHANGER

AutoCAD SHX Text D

AutoCAD SHX Text

[6"MIN.]

AutoCAD SHX Text

RUN DRAIN LINE FROM RELIEF VALVE TO NEAREST FLOOR DRAIN. (TYP.)

AutoCAD SHX Text

HWR

AutoCAD SHX Text

HWS

AutoCAD SHX Text

MPR TO FLASH TANK

AutoCAD SHX Text 15mm [1/2"] CHECK VALVE VACUUM BREAKER

AutoCAD SHX Text

SCALE POCKET

AutoCAD SHX Text

DDC TEMPERATURE SENSORS (TYP.)

AutoCAD SHX Text

SEE SCHEDULES FOR RELIEF VALVE SETTING

AutoCAD SHX Text

TT

AutoCAD SHX Text

AutoCAD SHX Text

PI

AutoCAD SHX Text

CONTROL VALVES IN 2/3 & 1/3

AutoCAD SHX Text

SIZE ARRANGEMENT.

AutoCAD SHX Text

BYPASS

AutoCAD SHX Text

IF INSTALLED LOWER THAN MAIN MPS LINE, PROVIDE ANOTHER SCALE POCKET/TRAP HERE.

AutoCAD SHX Text

TT

AutoCAD SHX Text

AutoCAD SHX Text

NC

AutoCAD SHX Text

DDC PRESSURE SENSOR

AutoCAD SHX Text

THERMOSTATIC AIR VENT

AutoCAD SHX Text

NTS

AutoCAD SHX Text

%%USTEAM TRAP ASSEMBLY

AutoCAD SHX Text

DRIP LEG (TYP.)

AutoCAD SHX Text

3/4" DRAIN (ALTERNATE LOCATIONS) (TYPICAL)

AutoCAD SHX Text

STEAM LINE (TYPICAL)

AutoCAD SHX Text

CAP (TYPICAL)

AutoCAD SHX Text

PIPE T0 STEAM TRAP (TYPICAL)

AutoCAD SHX Text

NOTE: DRIP POCKET PIPE SIZE SAME AS STEAM MAIN UNLESS OTHERWISE NOTED.

AutoCAD SHX Text

STEAM LINE DRIP POCKET

AutoCAD SHX Text

3/4" MIN.

AutoCAD SHX Text

FROM DRIP CONNECTION

AutoCAD SHX Text

DRIP RETURN

AutoCAD SHX Text

3/8" TEST CONNECTION

AutoCAD SHX Text

NTS

AutoCAD SHX Text

CONDENSATE

AutoCAD SHX Text

TO DRAIN

AutoCAD SHX Text

MV

AutoCAD SHX Text

MANUAL AIR VENT

AutoCAD SHX Text

TO BUILDING LOAD

AutoCAD SHX Text

INVERTED BUCKET TRAP ASSEMBLY

AutoCAD SHX Text

WELDED TEE

AutoCAD SHX Text

STEAM PIPE

AutoCAD SHX Text 12"

AutoCAD SHX Text 6"

AutoCAD SHX Text

SCHEDULE 80 STEEL PIPE

AutoCAD SHX Text

1" GATE VALVE

AutoCAD SHX Text

WELDED TEE

AutoCAD SHX Text

NTS

AutoCAD SHX Text 2.5"

AutoCAD SHX Text 30°-300°F

AutoCAD SHX Text

FLASH TANK

AutoCAD SHX Text

DIELECTRIC FITTING (WHEN RETURN IS COPPER)

AutoCAD SHX Text

RETURN

AutoCAD SHX Text

MPS DRIP RETURNS. (SEE FLOOR PLANS)

AutoCAD SHX Text

VENT TO OUTSIDE OF BUILDING

AutoCAD SHX Text

FLOOR

AutoCAD SHX Text

GRAVITY RETURN TO CONDENSATE PUMP

AutoCAD SHX Text SPARGE PIPE WITH 1/4" PERFORATIONS SHALL EXTEND INTO MIDDLE OF TANK AND SHALL BE SAME DIAMETER OF CONDENSATE RETURN CONNECTION TO TANK. TOTAL AREA OF ALL 1/4" PERFORATIONS SHALL BE EQUIVALENT TO THE TRANSVERSE AREA OF THE PIPE.

AutoCAD SHX Text 30°-300°F

AutoCAD SHX Text

NTS

AutoCAD SHX Text BLOW DOWN LINE. SAME SIZE AS AIR SEPARATOR CONNECTION. EXTEND TO NEAREST FLOOR DRAIN.

AutoCAD SHX Text

AIR SEPARATOR

AutoCAD SHX Text

FROM HEAT EXCHANGER

AutoCAD SHX Text

AUTOMATIC AIR VENT EXTEND TO NEAREST FLOOR DRAIN

AutoCAD SHX Text

PRESSURED EXPANSION TANK

AutoCAD SHX Text

VALVE W/ HOSE CONNECTION

AutoCAD SHX Text

TO HOT WATER PUMP

AutoCAD SHX Text

GLYCOL MAKE-UP WATER

AutoCAD SHX Text

ANTI-THERMO SYPHON LOOP 12" MIN DROP)

AutoCAD SHX Text

LOCK-SHIELD TYPE SHUT-OFF VALVE

AutoCAD SHX Text

PRE-CHARGING AIR CONNECTION

AutoCAD SHX Text

FLASH TANK

AutoCAD SHX Text

LPR

AutoCAD SHX Text

MPR

AutoCAD SHX Text

VENT TO ATMOSPHERE

AutoCAD SHX Text

PRESSURE GAUGE

AutoCAD SHX Text

STEAM TRAP

AutoCAD SHX Text

NTS

AutoCAD SHX Text

NTS

AutoCAD SHX Text

NTS

AutoCAD SHX Text

HIGH CAPACITY AUTOMATIC AIR VENT - EXTEND TO NEAREST FLOOR DRAIN

AutoCAD SHX Text HEIGHT OF UNIT INSTALLATION TO ALLOW GRAVITY PIPE RUN TO CONDENSATE PUMP RETURN CONNECTION POINT INDICATED ON DRAWINGS.

AutoCAD SHX Text

PROVIDE PIPE SUPPORT AND SADDLES.

AutoCAD SHX Text

%%UCOIL

AutoCAD SHX Text

MANUAL AIR VENT (TYP)

AutoCAD SHX Text

UNION (TYP)

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

STRAINER

AutoCAD SHX Text

RETURN

AutoCAD SHX Text

TEMPERATURE GAUGE (TYP)

AutoCAD SHX Text

PRESSURE GAUGE (TYP)

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

NC

AutoCAD SHX Text

FULL SIZE BY-PASS

AutoCAD SHX Text

2-WAY CONTROL VALVE (MODULATING)

AutoCAD SHX Text

ELBOW (TYP) (NOTE 1)

AutoCAD SHX Text

CALIBRATED BALANCING VALVE

AutoCAD SHX Text

BUTTERFLY VALVE (TYP) (NOTE 2)

AutoCAD SHX Text

BALL VALVE WITH HOSE END

AutoCAD SHX Text

2. BALL VALVE MAY BE USED INSTEAD OF BUTTERFLY VALVE WHERE PIPING IS 2" OR SMALLER.BALL VALVE MAY BE USED INSTEAD OF BUTTERFLY VALVE WHERE PIPING IS 2" OR SMALLER.

AutoCAD SHX Text

1. ARRANGE ALL HEADER CONNECTIONS SO AS NOT TO BLOCK COIL REMOVAL.ARRANGE ALL HEADER CONNECTIONS SO AS NOT TO BLOCK COIL REMOVAL.

AutoCAD SHX Text NOTE: ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 12" MINIMUM HIGH DRIP LEG FROM BOTTOM OF STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 6" SCALE POCKET BELOW TRAP INLET.

AutoCAD SHX Text

TO RETURN MAIN

AutoCAD SHX Text

PIPE SIZE SHALL BE SAME SIZE AS TRAP

AutoCAD SHX Text

FLOAT AND THERMOSTATIC TRAP. SEE PLANS, AND SCHEDULES

AutoCAD SHX Text

DIELECTRIC FITTING WHERE RETURN IS COPPER PIPE

AutoCAD SHX Text

FLOW

AutoCAD SHX Text

SCHEDULE 80 STEEL PIPE

AutoCAD SHX Text BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL WITH TRAP OR IN VERTICAL PLANE & BELOW TRAP PROVIDE BYPASS PIPING PROVIDE BYPASS PIPING FOR ALL TRAPS 1" AND LARGER.

AutoCAD SHX Text 300mm

AutoCAD SHX Text 150mm

AutoCAD SHX Text DRIP LEG OR EQUIPMENT CONNECTION. MAKE THE SAME SIZE AS THE SUPPLY MAIN OR EQUIPMENT CONNECTION. SEE NOTE 1

AutoCAD SHX Text

SCHEDULE 80 STEEL PIPE

AutoCAD SHX Text

SEE DRAWINGS FOR PIPE SIZES

AutoCAD SHX Text

1" GATE VALVE

AutoCAD SHX Text

USE 4-BOLT RAISED FACE FLANGES

AutoCAD SHX Text

SA

AutoCAD SHX Text

VFD

AutoCAD SHX Text

OA

AutoCAD SHX Text

RA

AutoCAD SHX Text

ELEVATION VIEW

AutoCAD SHX Text

VFD

AutoCAD SHX Text

RA

AutoCAD SHX Text

PLAN VIEW

AutoCAD SHX Text SA DISCHARGE SUPPLY FAN ACCESS COOLING COIL ACCESS HEATING COIL ACCESS FILTERS MIXING BOX OA INTAKE RA INTAKE

AutoCAD SHX Text

NTS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

%%UCOIL

AutoCAD SHX Text

MANUAL AIR VENT (TYP)

AutoCAD SHX Text

UNION (TYP)

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

STRAINER

AutoCAD SHX Text

RETURN

AutoCAD SHX Text

TEMPERATURE GAUGE (TYP)

AutoCAD SHX Text

PRESSURE GAUGE (TYP)

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

NC

AutoCAD SHX Text

FULL SIZE BY-PASS

AutoCAD SHX Text

3-WAY CONTROL VALVE (MODULATING)

AutoCAD SHX Text

ELBOW (TYP) (NOTE 1)

AutoCAD SHX Text

CALIBRATED BALANCING VALVE

AutoCAD SHX Text

BUTTERFLY VALVE (TYP) (NOTE 2)

AutoCAD SHX Text

BALL VALVE WITH HOSE END

AutoCAD SHX Text

2. BALL VALVE MAY BE USED INSTEAD OF BUTTERFLY VALVE WHERE PIPING IS 2 INCHES OR SMALLER.BALL VALVE MAY BE USED INSTEAD OF BUTTERFLY VALVE WHERE PIPING IS 2 INCHES OR SMALLER.

AutoCAD SHX Text

1. ARRANGE ALL HEADER CONNECTIONS SO AS NOT TO BLOCK COIL REMOVAL.ARRANGE ALL HEADER CONNECTIONS SO AS NOT TO BLOCK COIL REMOVAL.

AutoCAD SHX Text

PIPE SUPPORT (AXIAL AND LATERAL) AS NEEDED. (TYP)

AutoCAD SHX Text

PIPE ANCHOR (TYP)

AutoCAD SHX Text

PIPE GUIDE (TYP)

AutoCAD SHX Text

BRAIDED FLEXIBLE CORRUGATED HOSE (TYP)

AutoCAD SHX Text NOTES: 1. THE CONTRACTOR SHALL PROVIDE A DELEGATED DESIGN SUBMITTAL FOR THE DESIGN OF THERMAL EXPANSION COMPONENTS, INCLUDING PIPE GUIDES, ANCHORS, AND SUPPORTS. 2. INSTALL LOOP PER MANUFACTURERS INSTALLATION REQUIREMENTS.

AutoCAD SHX Text

NTS

AutoCAD SHX Text

PIPE INSULATION

AutoCAD SHX Text

LOOP CENTERLINE

AutoCAD SHX Text

HANGER BRACKET

AutoCAD SHX Text

PIPE GUIDES - EQUAL DISTANCE FROM CENTERLINE

AutoCAD SHX Text

LPR

AutoCAD SHX Text

STEAM TRAP

AutoCAD SHX Text

DRAIN PIPE WITH HOSE CONNECTION.

AutoCAD SHX Text

INTERNAL DROP LEG

AutoCAD SHX Text F I R S T A V E N U E

AutoCAD SHX Text A S S E R L E V Y P L A C E

AutoCAD SHX Text E A S T 2 3 r d. S T R E E T

AutoCAD SHX Text

BLDG 3

AutoCAD SHX Text

BLDG 2

AutoCAD SHX Text

BLDG 4 / 5

AutoCAD SHX Text

E A S T 25 TH STREET

AutoCAD SHX Text

BLDG 1

AutoCAD SHX Text N

C5 GLYCOL HEATING SYSTEM SCHEMATIC

F5

STEAM SYSTEM DIAGRAM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

VA NY Manhattan Campus

423 E 23RD Street, New York, NY 10010

630-600A

Project Director

Revisions: Date:

A/E:

AECOM

3101 WILSON BLVD, SUITE 900

ARLINGTON, VA. 22201

703-682-4900

WWW.AECOM.COM

Construction Document Refresh

Key Plan

Balance of Work

9/12/2022

FLOW DIAGRAMS

TM/BH WY

A-M503

AutoCAD SHX Text

HWS

AutoCAD SHX Text

HWP-W-1

AutoCAD SHX Text

HWR

AutoCAD SHX Text 4"

AutoCAD SHX Text 4"

AutoCAD SHX Text

ET-W-1

AutoCAD SHX Text

PRESSURE

AutoCAD SHX Text

SWITCH

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

HX-W-1

AutoCAD SHX Text

GLYCOL

AutoCAD SHX Text

TEST VALVE

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

DOMESTIC

AutoCAD SHX Text

WATER

AutoCAD SHX Text

MAKE-UP

AutoCAD SHX Text

GLYCOL MAKE-UP

AutoCAD SHX Text

SYSTEM PACKAGE

AutoCAD SHX Text

HB

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text 4"

AutoCAD SHX Text

MPS

AutoCAD SHX Text 1"

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 4"

AutoCAD SHX Text 4"

AutoCAD SHX Text

TO UNIT HEATERS, AIR CURTAINS, AHU-W-1

AutoCAD SHX Text

GLYCOL MAKE-UP PUMP

AutoCAD SHX Text

(PART OF GLYCOL MAKE-UP

AutoCAD SHX Text

SYSTEM PACKAGE)

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 4"

AutoCAD SHX Text

MPS

AutoCAD SHX Text

MPR

AutoCAD SHX Text 2"

AutoCAD SHX Text 5"

AutoCAD SHX Text 8"

AutoCAD SHX Text

BY-PASS

AutoCAD SHX Text 2"

AutoCAD SHX Text

MPS

AutoCAD SHX Text 5"

AutoCAD SHX Text 1"

AutoCAD SHX Text

AUTO AIR VENT

AutoCAD SHX Text

AIR SEPARATOR

AutoCAD SHX Text

TO UNIT HEATERS, AIR CURTAINS, AHU-W-1

AutoCAD SHX Text

TO FLASH TANK

AutoCAD SHX Text

CHEMICAL

AutoCAD SHX Text

POT FEEDER

AutoCAD SHX Text

NTS

AutoCAD SHX Text

NTS

AutoCAD SHX Text

HX-W-1

AutoCAD SHX Text

CRAWL SPACE

AutoCAD SHX Text

BASEMENT

AutoCAD SHX Text

GROUND FLOOR

AutoCAD SHX Text

FLASH TANK

AutoCAD SHX Text

EXISTING CONDENSER RECEIVER

AutoCAD SHX Text

FLASH TANK

AutoCAD SHX Text

MPS

AutoCAD SHX Text

MPS

AutoCAD SHX Text V

AutoCAD SHX Text V

AutoCAD SHX Text

MPR

AutoCAD SHX Text

MPR

AutoCAD SHX Text

LPR

AutoCAD SHX Text

LPR

AutoCAD SHX Text

LPR

AutoCAD SHX Text

LPR

AutoCAD SHX Text

MPS

AutoCAD SHX Text

MPS

AutoCAD SHX Text

NEW STEAM CONNECTION IN CORRIDOR BESIDE MECH RM G703

AutoCAD SHX Text

MPR

AutoCAD SHX Text 5"

AutoCAD SHX Text 5"

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 2"

AutoCAD SHX Text

MPS

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 1"

AutoCAD SHX Text

LPR

AutoCAD SHX Text 2"

AutoCAD SHX Text V

AutoCAD SHX Text V

AutoCAD SHX Text 4"

AutoCAD SHX Text

VENT THROUGH WALL TO EXTERIOR

AutoCAD SHX Text

HWR

AutoCAD SHX Text

FT-W-1

AutoCAD SHX Text

FT-W-2

AutoCAD SHX Text

AS-W-1

AutoCAD SHX Text 1"

AutoCAD SHX Text

1/3 AND 2/3 CAPACITY

AutoCAD SHX Text

CONTROL VALVES

AutoCAD SHX Text

HEAT EXCHANGER MPS SUPPLY

AutoCAD SHX Text

MPR

AutoCAD SHX Text 5"

AutoCAD SHX Text 5"

AutoCAD SHX Text 5"

AutoCAD SHX Text

PIPE DOWN THROUGH FLOOR OF MECHANICAL ROOM G703 TO UTILITY TUNNEL BELOW.

AutoCAD SHX Text

1/3 AND 2/3 CAPACITY

AutoCAD SHX Text

CONTROL VALVES

AutoCAD SHX Text

HEAT EXCHANGER MPS SUPPLY

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text

BALL VALVE (TYP.)

AutoCAD SHX Text

UNION (TYP.)

AutoCAD SHX Text

STRAINER W/BLOWDOWN

AutoCAD SHX Text

VALVE AND DRAIN CAP

AutoCAD SHX Text

REDUCED PRESSURE

AutoCAD SHX Text

BACKFLOW PREVENTER

AutoCAD SHX Text

(PIPE TO NEAREST DRAIN)

AutoCAD SHX Text

(SEE PLUMBING SHEETS FOR RPZ AND CONTINUATION OF PIPING)

AutoCAD SHX Text

PRESSURE REDUCING VALVE

AutoCAD SHX Text

(FIELD ESTABLISHED SET POINT)

AutoCAD SHX Text

BYPASS VALVE NORMALLY CLOSED

AutoCAD SHX Text

(GLOBE VALVE)

AutoCAD SHX Text F I R S T A V E N U E

AutoCAD SHX Text A S S E R L E V Y P L A C E

AutoCAD SHX Text E A S T 2 3 r d. S T R E E T

AutoCAD SHX Text

BLDG 3

AutoCAD SHX Text

BLDG 2

AutoCAD SHX Text

BLDG 4 / 5

AutoCAD SHX Text

E A S T 25 TH STREET

AutoCAD SHX Text

BLDG 1

AutoCAD SHX Text N

AIR HANDLING UNIT SCHEDULE

UNIT

NUMBER

SUPPLY FAN CHILLED WATER COIL HEATING WATER COIL AIR FILTER

VFD BASIS OF DESIGN (OR

EQUIVALENT) REMARKSMAXIMUM

SUPPLY AIR

(CFM)

MINIMUM

OUTSIDE AIR

(CFM)

MAXIMUM EXT

S.P. (IN. W.G.)

TOTAL S.P.

(IN. WG.) TYPE RPM

MOTOR

MAXIMUM FACE VELOCITY

(FPM)

AIRSIDE WATERSIDE

MAXIMUM FACE

VELOCITY (FPM)

AIRSIDE WATERSIDE

FILTER TYPE FILTER

EFFICIENCY DEPTH (W) MAX FACE

VELOCITY FPM

MAX BHP HP

ELECTRICAL @ 60 HZ ENTERING AIR LEAVING AIR MAX. S.P. LOSS (IN.

W.G.) FLOW (GPM) MAX PRESS.

DROP (FT. H20)

ENTERING

WATER (F)

LEAVING

WATER (F)

MIN. SENSIBLE

CAP. (MBH)

MIN. TOTAL

CAP. (MBH)

ENTERING AIR LEAVING AIR MAX S.P.

LOSS (IN.

W.G.)

FLOW (GPM) MAX PRESS. DROP

(FT. H20)

ENTERING

WATER (F)

LEAVING

WATER (F)

MIN. SENSIBLE

CAP. (MBH)

VOLTS PHASE DB DEG F WB DEG F DB DEG F WB DEG F DB DEG F DB DEG F

AHU-W-1 6,870 1,365 2.5 6.34 PLENUM 2183 9.23 15 208 3 464 78.2 65.2 52.3 52 0.78 41.4 2.3 44 56.7 197 269 464 59 82.8 0.12 8.8 0.6 180 140.1 169 ANGLE MERV 8 4 311.6 YES YORK SOLUTIONS XTI-

54X60 NOTES 1,2,3,4,5

NOTES:

I. UNIT LOCATED IN INDOOR MECHANICAL ROOM AT GROUND LEVEL.

2. PROVIDE MIN/MAX DAMPER ON OUTSIDE AIR INTAKE (NORMAL/ECONOMIZER).

3. PREHEAT COIL SELECTION BASED ON A 35% PROPYLENE GLYCOL SOLUTION.

4. MANUFACTURER TO PROVIDE VARIABLE FREQUENC DRIVE AND DISCONNECT SWITCH

5. IT IS THE CONTRACTORS RESPONSIBILITY TO ENSURE THAT THE PROPOSED AHU WILL FIT THROUGH EXISTING MECHANICAL ROOM DOOR AND FIT IN SPACE WITH ENOUGH ROOM FOR RECOMMENDED COIL-PULL CLEARANCES

DUCT CLASSIFICATION SCHEDULE

SYSTEM SERVING DESCRIPTION PRESSURE CLASS (INCHES) SEAL CLASS RECTANGULAR LEAK CLASS ROUND LEAK CLASS

SUPPLY ALL AHU-W-1 DISCHARGE TO AIR TERMINAL UNIT 4 A 6 3

SUPPLY ALL MAU-W-1, MAU-W-2 4 A 6 3

SUPPLY ALL DOWNSTREM OF AIR TERMINAL UNIT 1 A 6 3

SUPPLY ALL SF-W-1 2 A 6 3

RETURN ALL RF-W-1 4 A 6 3

EXHAUST ALL EF-W-1, EF-W-2, EF-W-3 4 A 6 3

EXHAUST ALL EF-W-4,EF-W-5 1 A 6 3

OUTSIDE AIR ALL ALL 4 A 6 3

RELIEF AIR ALL ALL 4 A 6 3

DUCT MOUNTED FILTER HOUSING

UNIT NUMBER LOCATION SERVES AIRFLOW (CFM)FACE VELOCITY (FPM)

FILTER DATA

HOUSING DIMENSIONS BASIS OF DESIGN

(OR EQUIVALENT) REMARKS

FILTER MERV INITIAL PD (INCHES

WG) FINAL PD (INCHES WG)

FILT-1 LOGISTICS 0236E MAU-W-1 10,975 457 8 0.25 0.7 52"Hx70"Wx13"D CAMFIL-BOST FILTREX GP-MT13-2H-3W NOTES 1,2,3,4,5,6,7

FILT-2 STOR 0218E MAU-W-2 9,280 387 8 0.17 0.7 76"Hx47"Wx13"D CAMFIL-BOST FILTREX GP-MT13-3H-2W NOTES 1,2,3,4,5,6,7

NOTES:

1. PROVIDE FULLY PACKAGED, MULTI-TRACK SYSTEM, DOUBLE WALL INSULATE HOUSINGS

2. INCLUDE, 1 (0-2) IWG MAGNEHELIC GAGE WITH KIT SHIPPED LOOSE FOR FIELD MOUNTING

3. HOUSING SIZES BASED ON USE OF 24"X24" FILTERS. INCLUDE ONE SET OF SPARE FILTERS

4. HOUSING SHALL BE DESIGNED TO HAVE A 2" AND 4" RACK SEPERATELY, AS WELL AS A HEADERED 1" RACK TO ALLOW FOR FUTURE MERV 13/14 ADDITION SHOULD THE CUSTOMER NEED TO ADD FOR FUTURE

5. PREFILTERS SHALL HAVE MINIMUM 200 GRAMS DUST HOLDING CAPACITY PER 24X24X2 FILTER AND SHALL BE ESTIMATED TO HAVE A 9-12 MONTH LIFE

6. PREFILTERS SHALL MEET ASHRAE 52.2 APPENDIX J AND ADDENDUM E STANDARDS.

7. MANUFACTURER MUST BE ISO CERTIFIED

VARIABLE/CONSTANT VOLUME BOX SCHEDULE

UNIT

NUMBER SERVICE

MAXIMUM

AIRFLOW

(CFM)

MINIMUM

AIRFLOW

(CFM)

HEATING

AIRFLOW (CFM)

INLET

CONN. SIZE

(IN)

MAXIMUM

TOTAL S.P.

(IN. W.G.)

MAXIMUM NC

LEVEL AT

MAXIMUM

FLOW

HOT WATER REHEAT COIL DATA

BASIS OF DESIGN

(OR EQUIVALENT) REMARKS

CAPACITY (MBH) FLOW

(GPM) LAT (F) WPD (FT. H20) ROWS PIPE CONN. (IN.)

VVR-W-1 EMS OFFICES 400 120 120 6 0.5 35 5.6 1 95 1 1 3/4 TITUS DESV NOTES 1,2,3,4

VVR-W-2 EMS OFFICES, COPY ROOM 1665 500 500 14 0.5 35 20.8 2 95 1 1 3/4 TITUS DESV NOTES 1,2,3,4

VVR-W-3 EMS OFFICES 455 390 390 8 0.5 35 16.9 1 95 1 2 3/4 TITUS DESV NOTES 1,2,3,4

VVR-W-4 LOGISTICS OFFICES 1235 495 495 12 0.5 35 21.4 1 95 1 2 3/4 TITUS DESV NOTES 1,2,3,4

VVR-W-5 LOGISTICS OFFICES 860 265 265 10 0.5 35 11.8 2 95 1 1 3/4 TITUS DESV NOTES 1,2,3,4

VVR-W-6 LOGISTICS OFFICES, COPY ROOM 580 100 190 8 0.5 35 8.1 1 95 1 1 3/4 TITUS DESV NOTES 1,2,3,4

CVR-W-7 TOILETS SHOWERS, LINEN CHUTE 1060 1060 1060 10 0.5 35 40.3 5 95 4 2 3/4 TITUS DESV NOTES 1,2,3,4

VVR-W-8 PROPERTY MANAGERS OFFICE 0230E 370 115 115 6 0.5 35 5.6 1 95 1 1 3/4 TITUS DESV NOTES 1,2,3,4

VVR-W-9 WAREHOUSE MANAGERS OFFICE 0215AE 240 115 115 6 0.5 35 5.6 1 95 1 1 3/4 TITUS DESV NOTES 1,2,3,4

VVR-W-10 OFFICE 0216AE 300 115 115 6 0.5 35 5.6 1 95 1 1 3/4 TITUS DESV NOTES 1,2,3,4

NOTES:

1. AIR TERMINAL UNIT PERFORMANCE EXCEEDING THE MAX NC SHOWN WILL NOT BE ACCEPTED.

2. PROVIDE MULTI-PORTAIR FLOW SENSOR WITH EACH ASSEMBLY.

3. DISCONNECT SWITCH PROVIDED BY VARIABLE/CONSTANT VOLUME BOX MANUFACTURER.

4. TERMINAL UNIT SELECTIONS BASED ON A 35% PROPYLENE GLYCOL SOLUTION.

5. TERMINAL COIL CAPACITIES BASED ON 180 DEG F EWT AND 55 DEG F SUPPLY AIR TEMPERATURE.

AIR DISTRIBUTION DEVICE SCHEDULE

UNIT TAG TYPE SERVICE MAX AIRFLOW

(CFM)

MIN AIRFLOW

(CFM) NECK SIZE (IN) NOMINAL FACE

SIZE (IN.) MAX N.C. AIRFLOW

PATTERN

BASIS OF DESIGN

(OR EQUIVALENT) NOTES

SG1 DOUBLE BLADE SUPPLY 470 230 18 x8 20x10 25 - TITUS 300FL NOTE 1

SG2 DOUBLE BLADE SUPPLY 720 360 24x10 26x12 25 - TITUS 300FL NOTE 1

SG3 DOUBLE BLADE SUPPLY 1220 600 48x6 50x8 30 - TITUS 300FL NOTE 1

SG4 DOUBLE BLADE SUPPLY 600 400 14x14 16x16 25 - TITUS 300FL NOTE 1

SG5 DOUBLE BLADE SUPPLY 1040 520 36x8 38x10 30 - TITUS 300FL NOTE 1

CD1 SQUARE PLAQUE SUPPLY 125 0 6Ø 24X24 25 4-WAY TITUS OMNI-AA

CD2 SQUARE PLAQUE SUPPLY 245 126 8Ø 24X24 25 4-WAY TITUS OMNI-AA

CD3 SQUARE PLAQUE SUPPLY 380 246 10Ø 24X24 25 4-WAY TITUS OMNI-AA

RG1 PERFORATED RETURN 210 0 8Ø 24X24 25 - TITUS PAR

RG2 PERFORATED RETURN 380 211 10Ø 24X24 25 - TITUS PAR

RG3 PERFORATED RETURN 900 600 18x18 24X24 25 - TITUS PAR

RG4 PERFORATED RETURN 810 550 16Ø 24X24 30 - TITUS PAR

EG1 SINGLE BLADE EXHAUST 190 0 8x8 10x10 25 - TITUS 350 FL NOTE 2

EG2 SINGLE BLADE EXHAUST 260 190 12X8 14X10 25 - TITUS 350 FL NOTE 2

EG3 SINGLE BLADE EXHAUST 590 260 18X10 20X12 25 - TITUS 350 FL NOTE 2

EG4 SINGLE BLADE EXHAUST 1270 500 36X12 38X14 25 - TITUS 350 FL NOTE 2

EG5 SINGLE BLADE EXHAUST 600 200 14X14 16X16 25 - TITUS 350 FL NOTE 2

EG6 SINGLE BLADE EXHAUST 470 230 12X12 14X14 25 - TITUS 350 FL NOTE 2

ER1 SINGLE BLADE EXHAUST 500 400 12X12 14X14 25 - TITUS 350 FL NOTE 2, 3

TG1 SINGLE BLADE TRANSFER 500 300 14X14 16X16 25 - TITUS 350 FL NOTE 2

NOTES:

1. ALUMINUM DOUBLE DEFLECTION WITH ADJUSTABLE FRONT AND BACK DEFLECTION BLADES SPACED AT 3/4 INCH. HORIZONTAL FACE BLADES WITH VERTICAL REAR BLADES.

2. ALUMINUM WITH SINGLE FIXED DEFLECTION BLADES AT 3/4 INCH SPACING. FACE BLADES PARALLEL TO LONG DIMENSION.

3. INCLUDE OPPOSED BLADE VOLUME DAMPER.

DUCT HEATER COIL SCHEDULE

UNIT NUMBER SERVES

HEATING WATER COIL

BASIS OF DESIGN

(OR EQUIVALENT) REMARKSHEATING

CFM

AIRSIDE WATERSIDE

EAT

DB (F)

LAT DB

(F)

MAX. S.P.

LOSS (IN.

W.G.)

VELOCITY

(FPM)

HEIGHT

(IN)

WIDTH

(IN)

VELOCITY

(FPM)

NO. OF

ROWS

FLOW

(GPM)

WPD

(FT. H20)

ENTERING

WATER (F)

LEAVING

WATER (F)

MIN.

SENSIBLE

CAP.

(MBH)

HC-W-1 MAU-W-1 5,490 10.0 84.6 0.07 351 45 50 351 2 22.9 5 180 140 440 JOHNSON CONTROLS BDW NOTES 1,2,3

HC-W-2 MAU-W-2 4,640 10.0 84 0.07 330 43 48 330 2 19.9 3 180 140 374 JOHNSON CONTROLS BDW NOTES 1,2,3

NOTES:

1. PROVIDE DISCHARGE AIR CONTROL TO MAINTAIN 68 DEGF IN WAREHOUSE DURING WINTER MONTHS

2. HEATING CFM IS BASED ON REDUCED VENTILATION AIR QUANTITIES (2 ACH) OF THE MAKE UP AIR FAN SERVED.

3. DUCT HEATER SELECTIONS BASED ON A 35% PROPYLENE GLYCOL SOLUTION.

FAN SCHEDULE

UNIT NUMBER LOCATION SERVES TYPE DESIGN AIR

(CFM)

TOTAL S.P.

(IN. W.G.)

SUPPLY FAN

VFD BASIS OF DESIGN

(OR EQUIVALENT) REMARKS

HP RPM

ELECTRICAL @ 60

Hz

VOLTS PHASE

RF-W-1 MECHANICAL ROOM AHU-W-1 RETURN/RELIEFMIXED FLOW 6,105 2.00 5 1699 208 3 YES GREENHECK MODEL QEID-20-70-A5 NOTES 1,3,6

EF-W-1 ROOF GENERAL EXHAUST DOWNBLAST 1,240 1.30 1 1363 208 3 YES GREENHECK MODEL G-160HP-7 NOTES 1,2,6,8

EF-W-2 ROOF VENTILATION WEST DOWNBLAST 12375/ 6185 1.50 7.5 787 208 3 YES GREENHECK MODEL GB-360HP-75 NOTES 1,2,5,6,8

EF-W-3 WAREHOUSE VENTILATION EAST MIXED FLOW 9670/ 4835 1.50 7.5 1680 208 3 YES GREENHECK MODEL QEID-22-75-A75NOTES 1,3,5.6

EF-W-4 EMPTY SHARPS GENERAL EXHAUST INLINE 200 0.30 1/10 1279 120 1 NO GREENHECK MODEL SQ-80-VG NOTE 3,4

EF-W-5 MEN'S LOCKER GENERAL EXHAUST INLINE 300 0.40 1/10 1390 120 1 NO GREENHECK MODEL SQ -90-VG NOTE 3,4

EF-W-6 MECHANICAL ROOM GENERAL EXHAUST INLINE 480 0.30 1/10 1490 120 1 NO GREENHECK MODEL SQ -90-VG NOTE 3,4

EF-W-7 CORRIDOR 0271N GENERAL EXHAUST INLINE 750 0.80 3/4 1891 208 1 NO GREENHECK MODEL SQ-99-VG NOTE 3,4

EF-W-8 MANIFOLD RM 1091S GENERAL EXHAUST PROPELLER 500 0.15 1/4 1225 120 1 NO COOK 12XW26D17EC NOTE 7

MUA-W-1 WAREHOUSE MAKE-UP AIR WEST MIXED FLOW 10975/ 5490 2.90 10 1278 208 3 YES GREENHECK MODEL QEID-27-75-B100NOTES 1,3,5,6

MUA-W-2 WAREHOUSE MAKE-UP AIR EAST MIXED FLOW 9280/ 4640 2.60 7.5 1387 208 3 YES GREENHECK MODEL…