PART 6 ATTACHMENT M9-M602 MECHANICAL CONTROLS.pdf

PDF 2 MB Posted

Attached to
Repair Nine Paradise Point BOQs
Solicitation number
N6247020R6019
Issued by

View the file

Other files

File Type Posted
20-0046 PART 3-- PPI RESPONSE 5_13AUG2020.pdf PDF
Amnd 0007 20R6019 FINAL.pdf PDF
Amnd 0006 20R6019 FINAL.pdf PDF
Amnd 0005 20R6019 FINAL.pdf PDF
20-0046 PART 3-- PPI RESPONSE 4_07AUG2020.pdf PDF
20-0046 PART 3-- PPI RESPONSE 3_06AUG2020.pdf PDF
Amnd 0004 20R6019 FINAL.pdf PDF
Amnd 0003 20R6019 FINAL.pdf PDF
Roof Louvers 2617.jpeg JPEG file
Amnd 0002 20R6019 FINAL.pdf PDF
PART 6 ATTACHMENT N-MCBCL Base-Wide MNS-FACP Construction Requirements 28 JAN 2015 Typical.pdf PDF
01 31 19.05 20 Post Award Meetings-Revised 20JUL2020.pdf PDF
20-0046 Paradise Point BOQs - REV SP1.pdf PDF
01 31 10.05 20 Design Submittal Procedure-Revised 20JUL2020.pdf PDF
23 73 33 HEATING VENTILATING AND COOLING SYSTEM.pdf PDF
20-0046 Paradise Point BOQs - REV A101.pdf PDF
20-0046 PART 3-- PPI RESPONSE 1_20JUL2020.pdf PDF
11 24 24 ROOF FALL PROTECTION 20 Nov 2019.pdf PDF
Amnd 0001 20R6006 FINAL.pdf PDF
PART 6 ATTACHMENT F-NPDES PERMIT NCS000290.pdf PDF
PART 5 FINAL-28MAY2020.pdf PDF
PART 6 ATTACHMENT I9-879291-2603-INT_EXT REPAIRS.pdf PDF
PART 6 TOC-20-0046.pdf PDF
PART 6 ATTACHMENT I3-85-6406 BOQ Improvements.pdf PDF
PART 6 ATTACHMENT H-BOQ FURNITURE INVENTORY.pdf PDF
PART 6 ATTACHMENT K- MCBCL Mech Design Guidance 7.17.pdf PDF
PART 6 ATTACHMENT M5-M105 BOQ 2603 THRU 2611 LEVEL 1.pdf PDF
PART 6 ATTACHMENT I5-91-7314 BOQs Sidewalks-2.pdf PDF
PART 3 FINAL-28MAY2020.pdf PDF
PART 6 ATTACHMENT A3-EXISTING BUILDING PICTURES PT2.pdf PDF
PART 6 ATTACHMENT E3-ES101 BOQ SITE PRIMARY O.H. POWER PLAN.pdf PDF
Master PPI Form Template.xls XLS spreadsheet
PART 6 ATTACHMENT M2-M102 BOQ 2617 LEVEL 2.pdf PDF
PART 6 ATTACHMENT A1-BOQ FLOOR PLAN REFERENCES.pdf PDF
PART 6 ATTACHMENT M10-M603 MECHANICAL CONTROLS.pdf PDF
PART 6 ATTACHMENT I6-95-1430 HVAC BOQs.pdf PDF
PART 6 ATTACHMENT L-EXAMPLE SCREEN WALL.pdf PDF
PART 6 ATTACHMENT M3-M103 BOQ 2602 LEVEL 1.pdf PDF
PART 6 ATTACHMENT D2- Appendix D for DEMO.pdf PDF
RFP N6247020R6019.pdf PDF
PART 6 ATTACHMENT M4-M104 BOQ 2602 LEVEL 2.pdf PDF
PART 6 ATTACHMENT M7-M107 BOQ 2613 LEVEL 1.pdf PDF
PART 6 ATTACHMENT E1-Electrical Policies 2020.pdf PDF
PART 6 ATTACHMENT I10-994214 - 2603_2609_2611_2613-REPL HVAC.pdf PDF
PART 6 ATTACHMENT A2-BOQ FRONT DESK FLOOR PLANS.pdf PDF
PART 6 ATTACHMENT D1-BASE ASBESTOS REPORTS-ALL BUILDINGS.pdf PDF
PART 6 ATTACHMENT E2-TS101 BOQ SITE TELECOMM PLAN.pdf PDF
PART 6 ATTACHMENT E4-ES102 BOQ SITE SECONDARY O.H. POWER PLAN.pdf PDF
PART 6 ATTACHMENT I8-1942 BOQs.pdf PDF
PART 6 ATTACHMENT M8-M601 MECHANICAL CONTROLS.pdf PDF
Show 40 more

Latest 50 of 66 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROGRESS

DRAWING - DO NOT

USE FOR

CONSTRUCTION

2246 Yaupon Drive

Wilmington, NC 28401

Phone: 910.791.4000

Fax: 910.791.5266 www.cbhfengineers.com

NC# P-0506

c

Copyright 2019 CBHF Engineers, PLLC

Engineers, PLLC

DISCLOSURE OF INFORMATION:

CONTRACTOR SHALL COMPLY AS FOLLOWS:

A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G. FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT

OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

1. THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF THE RELEASE.

B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING

OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.

C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT.

SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR

TO THE CONTRACTING OFFICER.

THE RFP-DOCUMENTS (RFPD), INCLUDING BUT NOT LIMITED TO: THE DRAWINGS, PLANS, DESIGNS, REPORTS, SURVEYS, CALCULATIONS, COMPUTER PRINT-OUTS, ETC. ARE MADE AVAILABLE TO THE CONTRACTOR'S FOR REFERENCE PURPOSES ONLY IN RELATION TO THIS DESIGN-BID PROJECT. THE RFPD ARE THE PROPERTY OF THE GOVERNMENT.

THE RFPD ARE PROVIDED "AS-IS" WITHOUT ANY GUARANTEE, REPRESENTATION, CONDITION, OR WARRANTY OF ANY KIND, EITHER EXPRESSED OR IMPLIED, OR STATUTORY.

THE GOVERNMENT ASSUMES NO LIABILITY WITH RESPECT TO ANY RELIANCE THE CONTRACTOR(S) PLACE ON THESE RFPD. IF THE CONTRACTOR(S) RELY ON THESE RFPD IN ANY WAY, THE CONTRACTOR(S) ASSUME THE ENTIRE RISK AS TO THE TRUTH, ACCURACY, CURRENCY, OR COMPLETENESS OF THE INFORMATION CONTAINED IN THESE RFPD.

NOT TO SCALE1 CONTROL DIAGRAM - CHILLER PLANT

M

CT

STARTER

BI - CHILLED WATER PUMP STATUS

BO - CHILLED WATER PUMP START/STOP

CWS

VFD

VFD

BI - CHILLED WATER PUMP 2 VFD FAULT

AO - CHILLED WATER PUMP 2 VFD SPEED

BI - CHILLED WATER PUMP 1 VFD FAULT

AO - CHILLED WATER PUMP 1 VFD SPEED

AI - CHILLED WATER

DIFFERENTIAL

PRESSURE

L

H

M

M

CT

CT

BI - CHILLED WATER PUMP 1 STATUS

BI - CHILLED WATER PUMP 2 STATUS

BO - CHILLED WATER PUMP 1 START/STOP

BO - CHILLED WATER PUMP 2 START/STOP

CWS

M

CT

STARTER

BI - CHILLED WATER PUMP STATUS

BO - CHILLED WATER PUMP START/STOP

T

AI - CHILLED WATER RETURN TEMP

BO - CHILLED WATER ISOLATION VALVE

BI - CHILLED WATER ISOLATION VALVE STATUSS

CWRCWR

BO - CHILLER ENABLE

BI - CHILLER STATUS

CH01

T

AI - CHILLED WATER

BRIDGE TEMP

T

AI - CHILLED WATER SUPPLY TEMP

T

AI - SECONDARY CHILLED

WATER SUPPLY TEMP

INTLK

CHILLER 1 CHWS

FLOW SWITCH

SA AI - ZONE TEMPT

DUCTLESS SPLIT SYSTEM UNITS

GENERAL:

1. A MICROPROCESSOR-BASED CONTROLLER (FURNISHED WITH THE UNIT) SHALL CONTROL THE SPLIT SYSTEM AIR

CONDITIONING UNIT.

2. THE INDOOR EVAPORATOR UNIT FAN AND DX COOLING SYSTEM SHALL BE STARTED AND STOPPED VIA THE

MICROPROCESSOR BASED CONTROLS.

3. A SPACE TEMPERATURE SENSOR WILL MONITOR THE ROOM CONDITIONS FOR TEMPERATURE ALARM

MONITORING THROUGH THE BUILDING AUTOMATION SYSTEM (BAS).

SYSTEM DESCRIPTION:

1. THE SYSTEM IS A DUCTLESS SPLIT SYSTEM HEAT PUMP UNIT.

2. THE OUTDOOR CONDENSING UNIT IS LOCATED REMOTELY.

SYSTEM CONTROL:

TEMPERATURE CONTROL:

A. INDOOR UNIT:

1) ON A RISE IN SPACE TEMPERATURE ABOVE THE ACTIVE SET POINT, THE MICROPROCESSOR CONTROLLER

SHALL INDEX THE INDOOR UNIT EVAPORATOR FAN TO RUN. THE FAN SHALL RUN INITIALLY AT A PREDETERMINED SPEED UPON STARTUP. IN AUTO MODE, THE INDOOR EVAPORATOR FAN SHALL CYCLE WITH A CALL FOR COOLING, AND THE FAN SHALL SWITCH VIA THE MICROPROCESSOR CONTROLS BETWEEN LOW SPEED AND HIGH SPEED BASED UPON THE ROOM TEMPERATURE DEVIATION FROM THE SET POINT.

2) THE MICROPROCESSOR CONTROLLER WILL ENERGIZE THE OUTDOOR COMPRESSOR TO RUN UPON A CALL FOR

COOLING, BASED UPON THE SET POINT ENTERED INTO THE MICROPROCESSOR CONTROLLER.

3) UPON A DROP IN SPACE TEMPERATURE, THE MICROPROCESSOR WILL DE-ENERGIZE THE COMPRESSOR. THE INDOOR UNIT FAN WILL CONTINUE TO RUN FOR A PRE-DETERMINED CYCLE LENGTH TO DISSIPATE REMAINING ENERGY FROM THE COIL. THE UNIT CONTROLS SHALL INCLUDE AN ANTI-CYCLE TIMER TO PREVENT MULTIPLE

STARTS ON THE COMPRESSOR.

BAS INTERFACE:

SEQUENCE OF OPERATION - DUCTLESS SPLIT SYSTEM

1. A TEMPERATURE SENSOR SHALL BE WIRED TO THE BAS TO MONITOR THE ACTIVE SPACE TEMPERATURE. THE BAS SHALL INITIATE AN ALARM WHENEVER THE SPACE TEMPERATURE RANGES BEYOND THE HIGH OR LOW LIMITS

DEFINED FOR THE SPACE (85F HIGH ALARM/65F LOW ALARM, ADJ.).

NOT TO SCALE2 CONTROL DIAGRAM - DUCTLESS SPLIT SYSTEM

CWHWP01A

CWHWP01B

CWHWP02A

CWHWP02B

SYSTEM GENERAL DESCRIPTION:

THE CHILLED WATER SYSTEM CONSISTS OF THE FOLLOWING:

ONE (1) CHILLER

TWO (2) MANIFOLDED PRIMARY CHILLED WATER PUMPS, CONFIGURED AS ONE (1) LEAD AND ONE (1) STANDBY TWO (2) MANIFOLDED SECONDARY CHILLED WATER PUMPS, CONFIGURED AS ONE (1) LEAD AND ONE (1) LAG

THE BUILDING AUTOMATION SYSTEM (BAS) CONTROLLER PROVIDES STAND-ALONE CONTROL OR CONTROL FROM A HIGHER-LEVEL BAS AND PROVIDES START/STOP CONTROL FOR THE CHILLED WATER PUMPS AND PROVIDES LEAD/STANDBY CONTROL OF THE SECONDARY CHILLED WATER PUMPS IN ORDER TO MAINTAIN THE SYSTEM

CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT (ADJ.).

CHILLED WATER SYSTEM ENABLE/DISABLE:

THE CHILLED WATER SYSTEM SHALL BE ENABLED VIA A POINT CONTROLLED BY A HIGHER-LEVEL BAS. THE BAS CONTROLLER SHALL THEN START THE LEAD SYSTEM PUMP. WHEN RUN STATUS FOR THAT PUMP IS PROVEN, THE BAS CONTROLLER SHALL REPORT THAT STATUS TO THE HIGHER-LEVEL BAS. THE HIGHER-LEVEL BAS SHALL THEN

REQUESTS A CHILLER TO RUN.

THE PRIMARY CHILLED WATER PUMP SHALL BE ENABLED ON A CONTACT CLOSURE FROM ANY SYSTEM CHILLER.

WHEN ENABLED, THE BAS CONTROLLER SHALL START PRIMARY CHILLED WATER PUMP.

THE CHILLED WATER SYSTEM SHALL BE DISABLED WHEN BUILDING IS UNOCCUPIED UNLESS THERE IS A CALL FOR COOLING FROM ANY ZONE. WHEN THE CHILLED WATER SYSTEM IS DISABLED, THE SECONDARY CHILLED WATER PUMP SHALL BE OFF AND THE PRIMARY PUMP SHALL BE OFF UNLESS REQUESTED BY THE CHILLER.

PRIMARY CHILLED WATER PUMP START/STOP:

THE BAS CONTROLLER SHALL START A CHILLED WATER PUMP THROUGH A CONTACT CLOSURE OF THE PUMPS

MOTOR STARTER ENABLE CONTACTS.

PRIMARY CHILLED WATER PUMP STATUS:

THE BAS CONTROLLER SHALL DETECT CHILLED WATER PUMP RUN STATUS BY A CURRENT SWITCH.

PRIMARY CHILLED WATER PUMP FAILURE:

IF THE PUMP START/STOP RELAY IS ENABLED AND THE CURRENT SWITCH STATUS IS OFF FOR MORE THAN 30 SECONDS (ADJ.), THE BAS CONTROLLER SHALL ANNUNCIATE A CHILLED WATER PUMP FAILURE ALARM TO THE BAS. ONCE THE PROBLEM HAS BEEN CORRECTED, THE OPERATOR SHALL BE ABLE TO CLEAR THE ALARM FAILURE FROM THE BAS CONTROLLER FROM A BAS OR BY MANUALLY OVERRIDING THE PUMP ON MOMENTARILY.

SECONDARY CHILLED WATER PUMP START/STOP:

THE BAS CONTROLLER SHALL START A SECONDARY CHILLED WATER PUMP THROUGH A CONTACT CLOSURE OF

THE PUMPS VFD RUN-ENABLE CONTACTS.

SECONDARY CHILLED WATER PUMP STATUS:

THE BAS CONTROLLER SHALL DETECT SECONDARY CHILLED WATER PUMP RUN STATUS BY A VFD CURRENT

SWITCH.

SECONDARY CHILLED WATER PUMP LEAD/LAG:

THE SECONDARY CHILLED WATER PUMP LEAD/LAG SEQUENCE: CHILLED WATER PUMPS SHALL ROTATE ON THE 1ST AND 15TH OF THE MONTH. FROM THE BAS CONTROLLER HUMAN-INTERFACE PANEL OR A BAS WORKSTATION, AN OPERATOR SHALL BE ABLE TO MANUALLY CHANGE THE LEAD/LAG SEQUENCE.

IF THE CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE FALLS 0.5 PSIG (ADJ.) BELOW SETPOINT AND THE LEAD PUMP IS AT 100% (ADJ.) FOR MORE THAN 5 MINUTES (ADJ.), THE NEXT PUMP IN THE SEQUENCE SHALL START. IF THE PUMP SPEED CONTROL OUTPUT IS BELOW 40% (ADJ.) FOR MORE THAN 5 MINUTES (ADJ.), THE LAST

OPERATING PUMP IN THE SEQUENCE SHALL BE DISABLED.

SECONDARY CHILLED WATER PUMP FAILURE:

IF THE LEAD START/STOP RELAY IS ENABLED AND THE CURRENT SWITCH STATUS IS OFF FOR MORE THAN 30 SECONDS (ADJ.), THE BAS CONTROLLER SHALL ANNUNCIATE A SECONDARY CHILLED WATER PUMP FAILURE ALARM TO THE BAS AND START THE LAG PUMP. WHEN A SECONDARY CHILLED WATER PUMP FAILURE EXISTS, LEAD/LAG AUTOMATION SHALL BE DISABLED AND THE CURRENTLY RUNNING PUMP BECOMES THE LEAD PUMP.

ONCE THE PROBLEM HAS BEEN CORRECTED, THE OPERATOR SHALL BE ABLE TO CLEAR THE ALARM FAILURE FROM THE BAS CONTROLLER OR BAS WORKSTATION. THIS SHALL RE-ENABLE THE LEAD/LAG SEQUENCE.

SECONDARY CHILLED WATER PUMP SPEED:

THE BAS CONTROLLER SHALL MONITOR THE CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SENSOR. WHEN THE PUMP VARIABLE FREQUENCY DRIVE IS ENABLED, THE BAS CONTROLLER SHALL CONTROL THE ANALOG SPEED SIGNAL THAT IS SENT TO THE VARIABLE FREQUENCY DRIVES OF OPERATING PUMPS TO MAINTAIN A

CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT OF 15.0 PSIG (ADJ.).

SECONDARY CHILLED WATER AHU PUMP PRESSURE SETPOINT OPTIMIZATION:

THE BAS SHALL CONTINUALLY MONITOR THE CHILLED WATER CONTROL VALVE POSITION OF ALL AHUS IN THE

CHILLED WATER SYSTEM.

AT CHILLED WATER SYSTEM STARTUP, THE CHILLED WATER SYSTEM PRESSURE SETPOINT SHALL BE 100% OF THE MAXIMUM PRESSURE SETPOINT. WHEN ALL CHILLED WATER VALVES ARE LESS THAN 85% OPEN, THE CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT SHALL BE LOWERED BY 0.1 PSIG (ADJ.) OF THE CURRENT CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT. THIS OCCURS EVERY 5 MINUTES UNTIL AT LEAST ONE VALVE IS MORE THAN 85% OPEN, OR IF THE SETPOINT IS EQUAL TO THE MINIMUM CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT, OR IF THE PUMP VARIABLE FREQUENCY DRIVES ARE AT A MINIMUM SPEED

SETTING (22 HZ).

WHEN ANY CHILLED WATER VALVE IS MORE THAN 95% OPEN, THE CHILLED WATER SYSTEM PRESSURE SETPOINT SHALL INCREASE BY 0.1 PSIG (ADJ.) OF THE CURRENT CHILLED WATER SYSTEM DIFFERENTIAL SETPOINT. THIS OCCURS EVERY 5 MINUTES UNTIL NO VALVE IS MORE THAN 95% OPEN, OR IF THE CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT HAS RISEN TO THE SYSTEMS MAXIMUM SETTING, OR IF THE PUMP VARIABLE

FREQUENCY DRIVES ARE AT THE MAXIMUM SETTING (60 HZ).

LOW TEMPERATURE FREEZE PROTECTION: ENABLE PRIMARY CHILLED WATER PUMPS IF DISABLED AND OUTSIDE

AIR TEMPERATURE DROPS BELOW 38F 9ADJ.).

SEQUENCE OF OPERATIONS - CHILLER PLANT

CHILLED WATER ENERGY

CHILLED WATER-COOLING DEMAND - ENERGY METER:

THE CONTROLLER SHALL MONITOR THE CHILLED WATER SUPPLY TEMPERATURE, CHILLED WATER RETURN TEMPERATURE AND CHILLED WATER FLOW TO THE BUILDING AND CALCULATE CURRENT ENERGY DEMAND ON A CONTINUAL BASIS. THESE VALUES SHALL BE MADE AVAILABLE TO THE SYSTEM AT ALL TIMES.

ALARM SHALL BE GENERATED AS FOLLOWS:

• INVALID READING: SENSOR READINGS INDICATE AN INVALID DEMAND VALUE.

PEAK DEMAND HISTORY:

THE CONTROLLER SHALL MONITOR AND RECORD THE PEAK (HIGH AND LOW) DEMAND READINGS FROM THE CHILLED WATER ENERGY METER. PEAK READINGS SHALL BE RECORDED ON A DAILY, MONTH-TO-DATE, AND

YEAR-TO-DATE BASIS.

USAGE HISTORY:

THE CONTROLLER SHALL MONITOR AND RECORD CHILLED WATER ENERGY METER READINGS SO AS TO PROVIDE AN ENERGY CONSUMPTION HISTORY. USAGE READINGS SHALL BE RECORDED ON A DAILY, MONTH-TO-DATE, AND

YEAR-TO-DATE BASIS.

CHILLED WATER FLOW METER SEQUENCE

AI - METER INPUT

T

AI - SECONDARY CHILLED

WATER RETURN TEMP

OUTSIDE AIR CONDITIONS:

THE CONTROLLER SHALL MONITOR THE OUTSIDE AIR TEMPERATURE AND HUMIDITY AND CALCULATE THE OUTSIDE AIR ENTHALPY ON A CONTINUAL BASIS. THESE VALUES SHALL BE MADE AVAILABLE TO THE SYSTEM AT

ALL TIMES.

ALARM SHALL BE GENERATED AS FOLLOWS:

• SENSOR FAILURE: SENSOR READING INDICATES SHORTED OR DISCONNECTED SENSOR. IN THE EVENT OF A

SENSOR FAILURE, AN ALTERNATE OUTSIDE AIR CONDITIONS SENSOR SHALL BE MADE AVAILABLE TO THE

SYSTEM WITHOUT INTERRUPTION IN SENSOR READINGS.

IF AN OA TEMP SENSOR CANNOT BE READ, A DEFAULT VALUE OF 65°F WILL BE USED.

IF AN OA HUMIDITY SENSOR CANNOT BE READ, A DEFAULT VALUE OF 50 % WILL BE USED.

OUTSIDE AIR TEMPERATURE HISTORY:

THE CONTROLLER SHALL MONITOR AND RECORD THE HIGH AND LOW TEMPERATURE READINGS FOR THE OUTSIDE AIR. THESE READINGS SHALL BE RECORDED ON A DAILY, MONTH-TO-DATE, AND YEAR-TO-DATE BASIS.

SEQUENCE OF OPERATION - OUTSIDE AIR MONITORING

AI - OUTSIDE AIR TEMP

AI - OUTSIDE AIR HUMIDITY

T

NOT TO SCALE3 CONTROL DIAGRAM - OUTSIDE AIR MONITORING

SENSORS SHALL BE PROVIDED BY EACH SEQUENCE OF OPERATION AND

ARE ALSO REQUIRED TO MEET THE SEQUENCE OF OPERATION. ALL SYSTEM

SAFETIES THAT SHUT DOWN AIR HANDLERS (I.E. FREEZESTAT, DUCT

DETECTOR, CONDENSATE LEVEL, HIGH DUCT PRESSURE, ETC.) MUST

BE “HARDWIRE INTERLOCKED” TO SHUT THE UNIT DOWN AND SHALL BE

MONITORED BY THE DDC SYSTEM.

POINTS LIST - CHILLER PLANT

HARDWARE POINTS SOFTWARE POINTS

POINT NAME AI AO BI BO AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC

SECONDARY CHILLED WATER RETURN TEMP X X X

SECONDARY CHILLED WATER SUPPLY TEMP X X X

CHILLED WATER DIFFERENTIAL PRESSURE X X X

PRIMARY CHILLED WATER RETURN TEMP X X X

PRIMARY CHILLED WATER SUPPLY TEMP X X X

CHILLED WATER BRIDGE TEMP X X X

CHILLED WATER SUPPLY TEMP SETPOINT RESET X X X

CHILLED WATER PUMP 1 VFD SPEED X X X

CHILLED WATER PUMP 2 VFD SPEED X X X

CHILLED WATER ISOLATION VALVE STATUS X X X

CHILLED 1 STATUS X X X

CIRCULATION PUMP 1 STATUS X X X

CIRCULATION PUMP 2 STATUS X X X

CHILLED WATER PUMP 1 STATUS X X X

CHILLED WATER PUMP 1 VFD FAULT X X X

CHILLED WATER PUMP 2 STATUS X X X

CHILLED WATER PUMP 2 VFD FAULT X X X

CHILLED WATER ISOLATION VALVE X X X

CHILLER 1 ENABLE X X

CIRCULATION PUMP 1 START/STOP X X X

CIRCULATION PUMP 2 START/STOP X X X

CHILLED WATER PUMP 1 START/STOP X X

CHILLED WATER PUMP 2 START/STOP X X

CHILLED WATER DIFFERENTIAL PRESSURE SETPOINT X X X

OUTSIDE AIR TEMP X X

CHILLER FAILURE X

CHILLER HIGH CHILLED WATER SUPPLY TEMP X

CHILLER LOW CHILLED WATER SUPPLY TEMP X

CHILLER RUNNING IN HAND X

CHILLER FAILURE X

CIRCULATION PUMP 1 RUNNING IN HAND X

CIRCULATION PUMP 1 RUNTIME EXCEEDED X

CIRCULATION PUMP 2 FAILURE X

CIRCULATION PUMP 2 RUNNING IN HAND X

CIRCULATION PUMP 2 RUNTIME EXCEEDED X

HIGH CHILLED WATER DIFFERENTIAL PRESSURE X

HIGH PRIMARY CHILLED WATER SUPPLY TEMP X

CHILLED WATER PUMP 1 FAILURE X

CHILLED WATER PUMP 1 RUNNING IN HAND X

CHILLED WATER PUMP 1 RUNTIME EXCEEDED X

CHILLED WATER PUMP 2 FAILURE X

CHILLED WATER PUMP 2 RUNNING IN HAND X

CHILLED WATER PUMP 2 RUNTIME EXCEEDED X

LOW CHILLED WATER DIFFERENTIAL PRESSURE X

LOW PRIMARY CHILLED WATER SUPPLY TEMP X

CHILLED WATER FLOW METER POINTS

HARDWARE POINTS SOFTWARE POINTS

POINT NAME AI AO BI BO AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC

CHILLED WATER FLOW X X X

CHILLED WATER RETURN TEMP X X X

CHILLED WATER SUPPLY TEMP X X X

DEMAND X X X

PEAK MONTH-TO-DATE X X

PEAK TODAY X X

PEAK YEAR-TO-DATE X X

USAGE MONTH-TO-DATE X X

USAGE TODAY X X

USAGE YEAR-TO-DATE X X

OUTSIDE AIR MONITORING POINTS

HARDWARE POINTS SOFTWARE POINTS

POINT NAME AI AO BI BO AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC

OUTSIDE AIR HUMIDITY X X X

OUTSIDE AIR TEMP X X X

OUTSIDE AIR ENTHALPY X X X

OUTSIDE AIR HUMIDITY (ALTERNATE) X X

OUTSIDE AIR TEMP (ALTERNATE) X X

HIGH TEMP MONTH-TO-DATE X X

HIGH TEMP TODAY X X

HIGH TEMP YEAR-TO-DATE X X

LOW TEMP MONTH-TO-DATE X X

LOW TEMP TODAY X X

LOW TEMP YEAR-TO-DATE X X

SENSOR FAILURE X

AutoCAD SHX Text

SYM

AutoCAD SHX Text

DATE

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

SATISFACTORY TO: DATE

AutoCAD SHX Text

APPROVED: PWO OR OICC DATE

AutoCAD SHX Text

DESIGN DIR.

AutoCAD SHX Text

SUBMITTED BY:

AutoCAD SHX Text

DR.

AutoCAD SHX Text

CHK.

AutoCAD SHX Text

DES.

AutoCAD SHX Text

CAMP LEJEUNE, NORTH CAROLINA

AutoCAD SHX Text

CONST. CONTR.

AutoCAD SHX Text

MARINE CORPS BASE

AutoCAD SHX Text

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text E1

AutoCAD SHX Text

SIZE

AutoCAD SHX Text 80091

AutoCAD SHX Text

SPEC.

AutoCAD SHX Text

CODE IDENT. NO

AutoCAD SHX Text

NAVFAC DRAWING NO.

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text 18168

AutoCAD SHX Text BOQs 2602, 2603, 2604, 2605

AutoCAD SHX Text 2607, 2609, 2611, 2613, 2617

AutoCAD SHX Text 20-0046

AutoCAD SHX Text

NA

AutoCAD SHX Text

NOTED

AutoCAD SHX Text

FINAL 21MAY 2020

AutoCAD SHX Text

T H BURTON, PE

AutoCAD SHX Text M-602

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text

CONTROLS

AutoCAD SHX Text

AutoCAD SHX Text

GRM

AutoCAD SHX Text

GRM

AutoCAD SHX Text

DMH

AutoCAD SHX Text

Sheets and Views
M602
OLE1

File details come from the government source that posted it. Updated .