PART 6 ATTACHMENT M9-M602 MECHANICAL CONTROLS.pdf
PDF 2 MB Posted
- Attached to
- Repair Nine Paradise Point BOQs
- Solicitation number
- N6247020R6019
View the file
Other files
Show 40 more
Latest 50 of 66 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROGRESS
DRAWING - DO NOT
USE FOR
CONSTRUCTION
2246 Yaupon Drive
Wilmington, NC 28401
Phone: 910.791.4000
Fax: 910.791.5266 www.cbhfengineers.com
NC# P-0506
c
Copyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
DISCLOSURE OF INFORMATION:
CONTRACTOR SHALL COMPLY AS FOLLOWS:
A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G. FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT
OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
1. THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF THE RELEASE.
B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING
OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT.
SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR
TO THE CONTRACTING OFFICER.
THE RFP-DOCUMENTS (RFPD), INCLUDING BUT NOT LIMITED TO: THE DRAWINGS, PLANS, DESIGNS, REPORTS, SURVEYS, CALCULATIONS, COMPUTER PRINT-OUTS, ETC. ARE MADE AVAILABLE TO THE CONTRACTOR'S FOR REFERENCE PURPOSES ONLY IN RELATION TO THIS DESIGN-BID PROJECT. THE RFPD ARE THE PROPERTY OF THE GOVERNMENT.
THE RFPD ARE PROVIDED "AS-IS" WITHOUT ANY GUARANTEE, REPRESENTATION, CONDITION, OR WARRANTY OF ANY KIND, EITHER EXPRESSED OR IMPLIED, OR STATUTORY.
THE GOVERNMENT ASSUMES NO LIABILITY WITH RESPECT TO ANY RELIANCE THE CONTRACTOR(S) PLACE ON THESE RFPD. IF THE CONTRACTOR(S) RELY ON THESE RFPD IN ANY WAY, THE CONTRACTOR(S) ASSUME THE ENTIRE RISK AS TO THE TRUTH, ACCURACY, CURRENCY, OR COMPLETENESS OF THE INFORMATION CONTAINED IN THESE RFPD.
NOT TO SCALE1 CONTROL DIAGRAM - CHILLER PLANT
M
CT
STARTER
BI - CHILLED WATER PUMP STATUS
BO - CHILLED WATER PUMP START/STOP
CWS
VFD
VFD
BI - CHILLED WATER PUMP 2 VFD FAULT
AO - CHILLED WATER PUMP 2 VFD SPEED
BI - CHILLED WATER PUMP 1 VFD FAULT
AO - CHILLED WATER PUMP 1 VFD SPEED
AI - CHILLED WATER
DIFFERENTIAL
PRESSURE
L
H
M
M
CT
CT
BI - CHILLED WATER PUMP 1 STATUS
BI - CHILLED WATER PUMP 2 STATUS
BO - CHILLED WATER PUMP 1 START/STOP
BO - CHILLED WATER PUMP 2 START/STOP
CWS
M
CT
STARTER
BI - CHILLED WATER PUMP STATUS
BO - CHILLED WATER PUMP START/STOP
T
AI - CHILLED WATER RETURN TEMP
BO - CHILLED WATER ISOLATION VALVE
BI - CHILLED WATER ISOLATION VALVE STATUSS
CWRCWR
BO - CHILLER ENABLE
BI - CHILLER STATUS
CH01
T
AI - CHILLED WATER
BRIDGE TEMP
T
AI - CHILLED WATER SUPPLY TEMP
T
AI - SECONDARY CHILLED
WATER SUPPLY TEMP
INTLK
CHILLER 1 CHWS
FLOW SWITCH
SA AI - ZONE TEMPT
DUCTLESS SPLIT SYSTEM UNITS
GENERAL:
1. A MICROPROCESSOR-BASED CONTROLLER (FURNISHED WITH THE UNIT) SHALL CONTROL THE SPLIT SYSTEM AIR
CONDITIONING UNIT.
2. THE INDOOR EVAPORATOR UNIT FAN AND DX COOLING SYSTEM SHALL BE STARTED AND STOPPED VIA THE
MICROPROCESSOR BASED CONTROLS.
3. A SPACE TEMPERATURE SENSOR WILL MONITOR THE ROOM CONDITIONS FOR TEMPERATURE ALARM
MONITORING THROUGH THE BUILDING AUTOMATION SYSTEM (BAS).
SYSTEM DESCRIPTION:
1. THE SYSTEM IS A DUCTLESS SPLIT SYSTEM HEAT PUMP UNIT.
2. THE OUTDOOR CONDENSING UNIT IS LOCATED REMOTELY.
SYSTEM CONTROL:
TEMPERATURE CONTROL:
A. INDOOR UNIT:
1) ON A RISE IN SPACE TEMPERATURE ABOVE THE ACTIVE SET POINT, THE MICROPROCESSOR CONTROLLER
SHALL INDEX THE INDOOR UNIT EVAPORATOR FAN TO RUN. THE FAN SHALL RUN INITIALLY AT A PREDETERMINED SPEED UPON STARTUP. IN AUTO MODE, THE INDOOR EVAPORATOR FAN SHALL CYCLE WITH A CALL FOR COOLING, AND THE FAN SHALL SWITCH VIA THE MICROPROCESSOR CONTROLS BETWEEN LOW SPEED AND HIGH SPEED BASED UPON THE ROOM TEMPERATURE DEVIATION FROM THE SET POINT.
2) THE MICROPROCESSOR CONTROLLER WILL ENERGIZE THE OUTDOOR COMPRESSOR TO RUN UPON A CALL FOR
COOLING, BASED UPON THE SET POINT ENTERED INTO THE MICROPROCESSOR CONTROLLER.
3) UPON A DROP IN SPACE TEMPERATURE, THE MICROPROCESSOR WILL DE-ENERGIZE THE COMPRESSOR. THE INDOOR UNIT FAN WILL CONTINUE TO RUN FOR A PRE-DETERMINED CYCLE LENGTH TO DISSIPATE REMAINING ENERGY FROM THE COIL. THE UNIT CONTROLS SHALL INCLUDE AN ANTI-CYCLE TIMER TO PREVENT MULTIPLE
STARTS ON THE COMPRESSOR.
BAS INTERFACE:
SEQUENCE OF OPERATION - DUCTLESS SPLIT SYSTEM
1. A TEMPERATURE SENSOR SHALL BE WIRED TO THE BAS TO MONITOR THE ACTIVE SPACE TEMPERATURE. THE BAS SHALL INITIATE AN ALARM WHENEVER THE SPACE TEMPERATURE RANGES BEYOND THE HIGH OR LOW LIMITS
DEFINED FOR THE SPACE (85F HIGH ALARM/65F LOW ALARM, ADJ.).
NOT TO SCALE2 CONTROL DIAGRAM - DUCTLESS SPLIT SYSTEM
CWHWP01A
CWHWP01B
CWHWP02A
CWHWP02B
SYSTEM GENERAL DESCRIPTION:
THE CHILLED WATER SYSTEM CONSISTS OF THE FOLLOWING:
ONE (1) CHILLER
TWO (2) MANIFOLDED PRIMARY CHILLED WATER PUMPS, CONFIGURED AS ONE (1) LEAD AND ONE (1) STANDBY TWO (2) MANIFOLDED SECONDARY CHILLED WATER PUMPS, CONFIGURED AS ONE (1) LEAD AND ONE (1) LAG
THE BUILDING AUTOMATION SYSTEM (BAS) CONTROLLER PROVIDES STAND-ALONE CONTROL OR CONTROL FROM A HIGHER-LEVEL BAS AND PROVIDES START/STOP CONTROL FOR THE CHILLED WATER PUMPS AND PROVIDES LEAD/STANDBY CONTROL OF THE SECONDARY CHILLED WATER PUMPS IN ORDER TO MAINTAIN THE SYSTEM
CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT (ADJ.).
CHILLED WATER SYSTEM ENABLE/DISABLE:
THE CHILLED WATER SYSTEM SHALL BE ENABLED VIA A POINT CONTROLLED BY A HIGHER-LEVEL BAS. THE BAS CONTROLLER SHALL THEN START THE LEAD SYSTEM PUMP. WHEN RUN STATUS FOR THAT PUMP IS PROVEN, THE BAS CONTROLLER SHALL REPORT THAT STATUS TO THE HIGHER-LEVEL BAS. THE HIGHER-LEVEL BAS SHALL THEN
REQUESTS A CHILLER TO RUN.
THE PRIMARY CHILLED WATER PUMP SHALL BE ENABLED ON A CONTACT CLOSURE FROM ANY SYSTEM CHILLER.
WHEN ENABLED, THE BAS CONTROLLER SHALL START PRIMARY CHILLED WATER PUMP.
THE CHILLED WATER SYSTEM SHALL BE DISABLED WHEN BUILDING IS UNOCCUPIED UNLESS THERE IS A CALL FOR COOLING FROM ANY ZONE. WHEN THE CHILLED WATER SYSTEM IS DISABLED, THE SECONDARY CHILLED WATER PUMP SHALL BE OFF AND THE PRIMARY PUMP SHALL BE OFF UNLESS REQUESTED BY THE CHILLER.
PRIMARY CHILLED WATER PUMP START/STOP:
THE BAS CONTROLLER SHALL START A CHILLED WATER PUMP THROUGH A CONTACT CLOSURE OF THE PUMPS
MOTOR STARTER ENABLE CONTACTS.
PRIMARY CHILLED WATER PUMP STATUS:
THE BAS CONTROLLER SHALL DETECT CHILLED WATER PUMP RUN STATUS BY A CURRENT SWITCH.
PRIMARY CHILLED WATER PUMP FAILURE:
IF THE PUMP START/STOP RELAY IS ENABLED AND THE CURRENT SWITCH STATUS IS OFF FOR MORE THAN 30 SECONDS (ADJ.), THE BAS CONTROLLER SHALL ANNUNCIATE A CHILLED WATER PUMP FAILURE ALARM TO THE BAS. ONCE THE PROBLEM HAS BEEN CORRECTED, THE OPERATOR SHALL BE ABLE TO CLEAR THE ALARM FAILURE FROM THE BAS CONTROLLER FROM A BAS OR BY MANUALLY OVERRIDING THE PUMP ON MOMENTARILY.
SECONDARY CHILLED WATER PUMP START/STOP:
THE BAS CONTROLLER SHALL START A SECONDARY CHILLED WATER PUMP THROUGH A CONTACT CLOSURE OF
THE PUMPS VFD RUN-ENABLE CONTACTS.
SECONDARY CHILLED WATER PUMP STATUS:
THE BAS CONTROLLER SHALL DETECT SECONDARY CHILLED WATER PUMP RUN STATUS BY A VFD CURRENT
SWITCH.
SECONDARY CHILLED WATER PUMP LEAD/LAG:
THE SECONDARY CHILLED WATER PUMP LEAD/LAG SEQUENCE: CHILLED WATER PUMPS SHALL ROTATE ON THE 1ST AND 15TH OF THE MONTH. FROM THE BAS CONTROLLER HUMAN-INTERFACE PANEL OR A BAS WORKSTATION, AN OPERATOR SHALL BE ABLE TO MANUALLY CHANGE THE LEAD/LAG SEQUENCE.
IF THE CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE FALLS 0.5 PSIG (ADJ.) BELOW SETPOINT AND THE LEAD PUMP IS AT 100% (ADJ.) FOR MORE THAN 5 MINUTES (ADJ.), THE NEXT PUMP IN THE SEQUENCE SHALL START. IF THE PUMP SPEED CONTROL OUTPUT IS BELOW 40% (ADJ.) FOR MORE THAN 5 MINUTES (ADJ.), THE LAST
OPERATING PUMP IN THE SEQUENCE SHALL BE DISABLED.
SECONDARY CHILLED WATER PUMP FAILURE:
IF THE LEAD START/STOP RELAY IS ENABLED AND THE CURRENT SWITCH STATUS IS OFF FOR MORE THAN 30 SECONDS (ADJ.), THE BAS CONTROLLER SHALL ANNUNCIATE A SECONDARY CHILLED WATER PUMP FAILURE ALARM TO THE BAS AND START THE LAG PUMP. WHEN A SECONDARY CHILLED WATER PUMP FAILURE EXISTS, LEAD/LAG AUTOMATION SHALL BE DISABLED AND THE CURRENTLY RUNNING PUMP BECOMES THE LEAD PUMP.
ONCE THE PROBLEM HAS BEEN CORRECTED, THE OPERATOR SHALL BE ABLE TO CLEAR THE ALARM FAILURE FROM THE BAS CONTROLLER OR BAS WORKSTATION. THIS SHALL RE-ENABLE THE LEAD/LAG SEQUENCE.
SECONDARY CHILLED WATER PUMP SPEED:
THE BAS CONTROLLER SHALL MONITOR THE CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SENSOR. WHEN THE PUMP VARIABLE FREQUENCY DRIVE IS ENABLED, THE BAS CONTROLLER SHALL CONTROL THE ANALOG SPEED SIGNAL THAT IS SENT TO THE VARIABLE FREQUENCY DRIVES OF OPERATING PUMPS TO MAINTAIN A
CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT OF 15.0 PSIG (ADJ.).
SECONDARY CHILLED WATER AHU PUMP PRESSURE SETPOINT OPTIMIZATION:
THE BAS SHALL CONTINUALLY MONITOR THE CHILLED WATER CONTROL VALVE POSITION OF ALL AHUS IN THE
CHILLED WATER SYSTEM.
AT CHILLED WATER SYSTEM STARTUP, THE CHILLED WATER SYSTEM PRESSURE SETPOINT SHALL BE 100% OF THE MAXIMUM PRESSURE SETPOINT. WHEN ALL CHILLED WATER VALVES ARE LESS THAN 85% OPEN, THE CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT SHALL BE LOWERED BY 0.1 PSIG (ADJ.) OF THE CURRENT CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT. THIS OCCURS EVERY 5 MINUTES UNTIL AT LEAST ONE VALVE IS MORE THAN 85% OPEN, OR IF THE SETPOINT IS EQUAL TO THE MINIMUM CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT, OR IF THE PUMP VARIABLE FREQUENCY DRIVES ARE AT A MINIMUM SPEED
SETTING (22 HZ).
WHEN ANY CHILLED WATER VALVE IS MORE THAN 95% OPEN, THE CHILLED WATER SYSTEM PRESSURE SETPOINT SHALL INCREASE BY 0.1 PSIG (ADJ.) OF THE CURRENT CHILLED WATER SYSTEM DIFFERENTIAL SETPOINT. THIS OCCURS EVERY 5 MINUTES UNTIL NO VALVE IS MORE THAN 95% OPEN, OR IF THE CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT HAS RISEN TO THE SYSTEMS MAXIMUM SETTING, OR IF THE PUMP VARIABLE
FREQUENCY DRIVES ARE AT THE MAXIMUM SETTING (60 HZ).
LOW TEMPERATURE FREEZE PROTECTION: ENABLE PRIMARY CHILLED WATER PUMPS IF DISABLED AND OUTSIDE
AIR TEMPERATURE DROPS BELOW 38F 9ADJ.).
SEQUENCE OF OPERATIONS - CHILLER PLANT
CHILLED WATER ENERGY
CHILLED WATER-COOLING DEMAND - ENERGY METER:
THE CONTROLLER SHALL MONITOR THE CHILLED WATER SUPPLY TEMPERATURE, CHILLED WATER RETURN TEMPERATURE AND CHILLED WATER FLOW TO THE BUILDING AND CALCULATE CURRENT ENERGY DEMAND ON A CONTINUAL BASIS. THESE VALUES SHALL BE MADE AVAILABLE TO THE SYSTEM AT ALL TIMES.
ALARM SHALL BE GENERATED AS FOLLOWS:
• INVALID READING: SENSOR READINGS INDICATE AN INVALID DEMAND VALUE.
PEAK DEMAND HISTORY:
THE CONTROLLER SHALL MONITOR AND RECORD THE PEAK (HIGH AND LOW) DEMAND READINGS FROM THE CHILLED WATER ENERGY METER. PEAK READINGS SHALL BE RECORDED ON A DAILY, MONTH-TO-DATE, AND
YEAR-TO-DATE BASIS.
USAGE HISTORY:
THE CONTROLLER SHALL MONITOR AND RECORD CHILLED WATER ENERGY METER READINGS SO AS TO PROVIDE AN ENERGY CONSUMPTION HISTORY. USAGE READINGS SHALL BE RECORDED ON A DAILY, MONTH-TO-DATE, AND
YEAR-TO-DATE BASIS.
CHILLED WATER FLOW METER SEQUENCE
AI - METER INPUT
T
AI - SECONDARY CHILLED
WATER RETURN TEMP
OUTSIDE AIR CONDITIONS:
THE CONTROLLER SHALL MONITOR THE OUTSIDE AIR TEMPERATURE AND HUMIDITY AND CALCULATE THE OUTSIDE AIR ENTHALPY ON A CONTINUAL BASIS. THESE VALUES SHALL BE MADE AVAILABLE TO THE SYSTEM AT
ALL TIMES.
ALARM SHALL BE GENERATED AS FOLLOWS:
• SENSOR FAILURE: SENSOR READING INDICATES SHORTED OR DISCONNECTED SENSOR. IN THE EVENT OF A
SENSOR FAILURE, AN ALTERNATE OUTSIDE AIR CONDITIONS SENSOR SHALL BE MADE AVAILABLE TO THE
SYSTEM WITHOUT INTERRUPTION IN SENSOR READINGS.
IF AN OA TEMP SENSOR CANNOT BE READ, A DEFAULT VALUE OF 65°F WILL BE USED.
IF AN OA HUMIDITY SENSOR CANNOT BE READ, A DEFAULT VALUE OF 50 % WILL BE USED.
OUTSIDE AIR TEMPERATURE HISTORY:
THE CONTROLLER SHALL MONITOR AND RECORD THE HIGH AND LOW TEMPERATURE READINGS FOR THE OUTSIDE AIR. THESE READINGS SHALL BE RECORDED ON A DAILY, MONTH-TO-DATE, AND YEAR-TO-DATE BASIS.
SEQUENCE OF OPERATION - OUTSIDE AIR MONITORING
AI - OUTSIDE AIR TEMP
AI - OUTSIDE AIR HUMIDITY
T
NOT TO SCALE3 CONTROL DIAGRAM - OUTSIDE AIR MONITORING
SENSORS SHALL BE PROVIDED BY EACH SEQUENCE OF OPERATION AND
ARE ALSO REQUIRED TO MEET THE SEQUENCE OF OPERATION. ALL SYSTEM
SAFETIES THAT SHUT DOWN AIR HANDLERS (I.E. FREEZESTAT, DUCT
DETECTOR, CONDENSATE LEVEL, HIGH DUCT PRESSURE, ETC.) MUST
BE “HARDWIRE INTERLOCKED” TO SHUT THE UNIT DOWN AND SHALL BE
MONITORED BY THE DDC SYSTEM.
POINTS LIST - CHILLER PLANT
HARDWARE POINTS SOFTWARE POINTS
POINT NAME AI AO BI BO AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC
SECONDARY CHILLED WATER RETURN TEMP X X X
SECONDARY CHILLED WATER SUPPLY TEMP X X X
CHILLED WATER DIFFERENTIAL PRESSURE X X X
PRIMARY CHILLED WATER RETURN TEMP X X X
PRIMARY CHILLED WATER SUPPLY TEMP X X X
CHILLED WATER BRIDGE TEMP X X X
CHILLED WATER SUPPLY TEMP SETPOINT RESET X X X
CHILLED WATER PUMP 1 VFD SPEED X X X
CHILLED WATER PUMP 2 VFD SPEED X X X
CHILLED WATER ISOLATION VALVE STATUS X X X
CHILLED 1 STATUS X X X
CIRCULATION PUMP 1 STATUS X X X
CIRCULATION PUMP 2 STATUS X X X
CHILLED WATER PUMP 1 STATUS X X X
CHILLED WATER PUMP 1 VFD FAULT X X X
CHILLED WATER PUMP 2 STATUS X X X
CHILLED WATER PUMP 2 VFD FAULT X X X
CHILLED WATER ISOLATION VALVE X X X
CHILLER 1 ENABLE X X
CIRCULATION PUMP 1 START/STOP X X X
CIRCULATION PUMP 2 START/STOP X X X
CHILLED WATER PUMP 1 START/STOP X X
CHILLED WATER PUMP 2 START/STOP X X
CHILLED WATER DIFFERENTIAL PRESSURE SETPOINT X X X
OUTSIDE AIR TEMP X X
CHILLER FAILURE X
CHILLER HIGH CHILLED WATER SUPPLY TEMP X
CHILLER LOW CHILLED WATER SUPPLY TEMP X
CHILLER RUNNING IN HAND X
CHILLER FAILURE X
CIRCULATION PUMP 1 RUNNING IN HAND X
CIRCULATION PUMP 1 RUNTIME EXCEEDED X
CIRCULATION PUMP 2 FAILURE X
CIRCULATION PUMP 2 RUNNING IN HAND X
CIRCULATION PUMP 2 RUNTIME EXCEEDED X
HIGH CHILLED WATER DIFFERENTIAL PRESSURE X
HIGH PRIMARY CHILLED WATER SUPPLY TEMP X
CHILLED WATER PUMP 1 FAILURE X
CHILLED WATER PUMP 1 RUNNING IN HAND X
CHILLED WATER PUMP 1 RUNTIME EXCEEDED X
CHILLED WATER PUMP 2 FAILURE X
CHILLED WATER PUMP 2 RUNNING IN HAND X
CHILLED WATER PUMP 2 RUNTIME EXCEEDED X
LOW CHILLED WATER DIFFERENTIAL PRESSURE X
LOW PRIMARY CHILLED WATER SUPPLY TEMP X
CHILLED WATER FLOW METER POINTS
HARDWARE POINTS SOFTWARE POINTS
POINT NAME AI AO BI BO AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC
CHILLED WATER FLOW X X X
CHILLED WATER RETURN TEMP X X X
CHILLED WATER SUPPLY TEMP X X X
DEMAND X X X
PEAK MONTH-TO-DATE X X
PEAK TODAY X X
PEAK YEAR-TO-DATE X X
USAGE MONTH-TO-DATE X X
USAGE TODAY X X
USAGE YEAR-TO-DATE X X
OUTSIDE AIR MONITORING POINTS
HARDWARE POINTS SOFTWARE POINTS
POINT NAME AI AO BI BO AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC
OUTSIDE AIR HUMIDITY X X X
OUTSIDE AIR TEMP X X X
OUTSIDE AIR ENTHALPY X X X
OUTSIDE AIR HUMIDITY (ALTERNATE) X X
OUTSIDE AIR TEMP (ALTERNATE) X X
HIGH TEMP MONTH-TO-DATE X X
HIGH TEMP TODAY X X
HIGH TEMP YEAR-TO-DATE X X
LOW TEMP MONTH-TO-DATE X X
LOW TEMP TODAY X X
LOW TEMP YEAR-TO-DATE X X
SENSOR FAILURE X
AutoCAD SHX Text
SYM
AutoCAD SHX Text
DATE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
SATISFACTORY TO: DATE
AutoCAD SHX Text
APPROVED: PWO OR OICC DATE
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
CONST. CONTR.
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text E1
AutoCAD SHX Text
SIZE
AutoCAD SHX Text 80091
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text 18168
AutoCAD SHX Text BOQs 2602, 2603, 2604, 2605
AutoCAD SHX Text 2607, 2609, 2611, 2613, 2617
AutoCAD SHX Text 20-0046
AutoCAD SHX Text
NA
AutoCAD SHX Text
NOTED
AutoCAD SHX Text
FINAL 21MAY 2020
AutoCAD SHX Text
T H BURTON, PE
AutoCAD SHX Text M-602
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
CONTROLS
AutoCAD SHX Text
AutoCAD SHX Text
GRM
AutoCAD SHX Text
GRM
AutoCAD SHX Text
DMH
AutoCAD SHX Text
| Sheets and Views |
| M602 |
| OLE1 |
File details come from the government source that posted it. Updated .