PART 6 ATTACHMENT M4-M104 BOQ 2602 LEVEL 2.pdf

PDF 5 MB Posted

Attached to
Repair Nine Paradise Point BOQs
Solicitation number
N6247020R6019
Issued by

View the file

Other files

File Type Posted
20-0046 PART 3-- PPI RESPONSE 5_13AUG2020.pdf PDF
Amnd 0007 20R6019 FINAL.pdf PDF
Amnd 0006 20R6019 FINAL.pdf PDF
Amnd 0005 20R6019 FINAL.pdf PDF
20-0046 PART 3-- PPI RESPONSE 4_07AUG2020.pdf PDF
20-0046 PART 3-- PPI RESPONSE 3_06AUG2020.pdf PDF
Amnd 0004 20R6019 FINAL.pdf PDF
Amnd 0003 20R6019 FINAL.pdf PDF
Roof Louvers 2617.jpeg JPEG file
Amnd 0002 20R6019 FINAL.pdf PDF
PART 6 ATTACHMENT N-MCBCL Base-Wide MNS-FACP Construction Requirements 28 JAN 2015 Typical.pdf PDF
01 31 19.05 20 Post Award Meetings-Revised 20JUL2020.pdf PDF
20-0046 Paradise Point BOQs - REV SP1.pdf PDF
01 31 10.05 20 Design Submittal Procedure-Revised 20JUL2020.pdf PDF
23 73 33 HEATING VENTILATING AND COOLING SYSTEM.pdf PDF
20-0046 Paradise Point BOQs - REV A101.pdf PDF
20-0046 PART 3-- PPI RESPONSE 1_20JUL2020.pdf PDF
11 24 24 ROOF FALL PROTECTION 20 Nov 2019.pdf PDF
Amnd 0001 20R6006 FINAL.pdf PDF
PART 6 ATTACHMENT F-NPDES PERMIT NCS000290.pdf PDF
PART 5 FINAL-28MAY2020.pdf PDF
PART 6 ATTACHMENT M9-M602 MECHANICAL CONTROLS.pdf PDF
PART 6 ATTACHMENT I9-879291-2603-INT_EXT REPAIRS.pdf PDF
PART 6 TOC-20-0046.pdf PDF
PART 6 ATTACHMENT I3-85-6406 BOQ Improvements.pdf PDF
PART 6 ATTACHMENT H-BOQ FURNITURE INVENTORY.pdf PDF
PART 6 ATTACHMENT K- MCBCL Mech Design Guidance 7.17.pdf PDF
PART 6 ATTACHMENT M5-M105 BOQ 2603 THRU 2611 LEVEL 1.pdf PDF
PART 6 ATTACHMENT I5-91-7314 BOQs Sidewalks-2.pdf PDF
PART 3 FINAL-28MAY2020.pdf PDF
PART 6 ATTACHMENT A3-EXISTING BUILDING PICTURES PT2.pdf PDF
PART 6 ATTACHMENT E3-ES101 BOQ SITE PRIMARY O.H. POWER PLAN.pdf PDF
Master PPI Form Template.xls XLS spreadsheet
PART 6 ATTACHMENT M2-M102 BOQ 2617 LEVEL 2.pdf PDF
PART 6 ATTACHMENT A1-BOQ FLOOR PLAN REFERENCES.pdf PDF
PART 6 ATTACHMENT M10-M603 MECHANICAL CONTROLS.pdf PDF
PART 6 ATTACHMENT I6-95-1430 HVAC BOQs.pdf PDF
PART 6 ATTACHMENT L-EXAMPLE SCREEN WALL.pdf PDF
PART 6 ATTACHMENT M3-M103 BOQ 2602 LEVEL 1.pdf PDF
PART 6 ATTACHMENT D2- Appendix D for DEMO.pdf PDF
RFP N6247020R6019.pdf PDF
PART 6 ATTACHMENT M7-M107 BOQ 2613 LEVEL 1.pdf PDF
PART 6 ATTACHMENT E1-Electrical Policies 2020.pdf PDF
PART 6 ATTACHMENT I10-994214 - 2603_2609_2611_2613-REPL HVAC.pdf PDF
PART 6 ATTACHMENT A2-BOQ FRONT DESK FLOOR PLANS.pdf PDF
PART 6 ATTACHMENT D1-BASE ASBESTOS REPORTS-ALL BUILDINGS.pdf PDF
PART 6 ATTACHMENT E2-TS101 BOQ SITE TELECOMM PLAN.pdf PDF
PART 6 ATTACHMENT E4-ES102 BOQ SITE SECONDARY O.H. POWER PLAN.pdf PDF
PART 6 ATTACHMENT I8-1942 BOQs.pdf PDF
PART 6 ATTACHMENT M8-M601 MECHANICAL CONTROLS.pdf PDF
Show 40 more

Latest 50 of 66 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROGRESS

DRAWING - DO NOT

USE FOR

CONSTRUCTION

2246 Yaupon Drive

Wilmington, NC 28401

Phone: 910.791.4000

Fax: 910.791.5266 www.cbhfengineers.com

NC# P-0506

c

Copyright 2019 CBHF Engineers, PLLC

Engineers, PLLC

DISCLOSURE OF INFORMATION:

CONTRACTOR SHALL COMPLY AS FOLLOWS:

A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G. FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT

OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

1. THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF THE RELEASE.

B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING

OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.

C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT.

SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR

TO THE CONTRACTING OFFICER.

THE RFP-DOCUMENTS (RFPD), INCLUDING BUT NOT LIMITED TO: THE DRAWINGS, PLANS, DESIGNS, REPORTS, SURVEYS, CALCULATIONS, COMPUTER PRINT-OUTS, ETC. ARE MADE AVAILABLE TO THE CONTRACTOR'S FOR REFERENCE PURPOSES ONLY IN RELATION TO THIS DESIGN-BID PROJECT. THE RFPD ARE THE PROPERTY OF THE GOVERNMENT.

THE RFPD ARE PROVIDED "AS-IS" WITHOUT ANY GUARANTEE, REPRESENTATION, CONDITION, OR WARRANTY OF ANY KIND, EITHER EXPRESSED OR IMPLIED, OR STATUTORY.

THE GOVERNMENT ASSUMES NO LIABILITY WITH RESPECT TO ANY RELIANCE THE CONTRACTOR(S) PLACE ON THESE RFPD. IF THE CONTRACTOR(S) RELY ON THESE RFPD IN ANY WAY, THE CONTRACTOR(S) ASSUME THE ENTIRE RISK AS TO THE TRUTH, ACCURACY, CURRENCY, OR COMPLETENESS OF THE INFORMATION CONTAINED IN THESE RFPD.

1/8" = 1'-0" 0 8' 16'4'1 2602 FLOOR PLAN LEVEL 2 - RENO

PLAN

NORTH

KEYED NOTES

NOTE: SELECT KEYED NOTES MAY NOT BE USED THIS DRAWING

REMOVE AND DISPOSE OF ENTIRE EXISTING HVAC SYSTEM INCLUDING, BUT NOT LIMITED

TO, PTACS, UNIT HEATERS, EXHAUST FANS, DUCTWORK, DUCT INSULATION, HANGERS

AND SUPPORTS. REMOVE AND DISPOSE OF ENTIRE EXISTING PLUMBING SYSTEM

INCLUDING, BUT NOT LIMITED TO, DOMESTIC HEATING WATER EQUIPMENT, PLUMBING

FIXTURES/TRIM, PUMPS, DOMESTIC WATER PIPING, INSULATION, SANITARY/VENT PIPING,

HANGERS AND SUPPORTS.

PROVIDE AIR-COOLED CHILLER ON CONCRETE HOUSEKEEPING PAD (TOP OF

PAD 10” ABOVE ADJACENT GRADE). PROVIDE INSULATED AND JACKETED CHILLED

WATER PIPING FROM CHILLER TO MECHANICAL ROOM FOR DISTRIBUTION THROUGHOUT

THE FACILITY. ALL PARTS OF THE EXTERIOR CHILLED WATER SYSTEM SUBJECT TO

FREEZING MUST BE HEAT TRACED TO PREVENT FREEZING DOWN TO 0 DEGREES F.

PROVIDE EXTERIOR PIPING WITH EMERGENCY CHILLER CONNECTIONS. A SET OF

EMERGENCY TEES MUST BE INSTALLED BEFORE ENTERING THE CHILLER ON SUPPLY

AND RETURN LINES. THE TEES MUST MATCH THE DIAMETER OF THE PIPE. A BUTTERFLY

VALVE AND A BOLTED COVER PLATE MUST BE INSTALLED.

PROVIDE BOILERS ON 6” HOUSEKEEPING PADS. PROVIDE IN-LINE CLOSE-COUPLED

CONSTANT VOLUME SOURCE SIDE PUMPS (ONE PER BOILER) AND LEAD-STANDBY

VARIABLE VOLUME LOAD SIDE HEATING WATER SYSTEM PUMPS DISTRIBUTING HEATING

WATER THROUGHOUT THE FACILITY.

PROVIDE IN-LINE CLOSE-COUPLED LEAD-STANDBY CONSTANT VOLUME SOURCE SIDE

PUMPS AND LEAD-STANDBY VARIABLE VOLUME LOAD SIDE CHILLED WATER SYSTEM

PUMPS DISTRIBUTING CHILLED WATER THROUGHOUT THE FACILITY.

PROVIDE A FOUR-PIPE DEDICATED OUTSIDE AIR SYSTEM (DOAS) WITH TOTAL ENERGY

CORE TO DISTRIBUTE FULLY CONDITIONED AIR THROUGHOUT THE FACILITY. ALL

FACILITY EXHAUST AIR MUST BE ROUTED BACK THROUGH THIS UNIT FOR ENERGY

RECOVERY. OFF COOLING COIL AIR MUST NOT EXCEED 50F. NEUTRAL AIR MUST BE

DELIVERED TO EACH AREA DECOUPLED FROM TERMINAL SYSTEMS. BUILDING

PRESSURE MUST BE POSITIVE.

PROVIDE DUCTLESS SPLIT SYSTEM HEAT PUMP FOR DATA/TEL ROOM. ONE SYSTEM PER

ROOM.

PROVIDE VERTICAL HIGH-RISE FOUR-PIPE FAN-COIL UNIT FURRED IN WALL FOR

TEMPERATURE AND HUMIDITY CONTROL IN EACH SUITE. POSITION THE FAN-COIL SUCH

THAT SIDEWALL SUPPLY DIFFUSERS CAN SERVE THE LIVING AREA AND THE SLEEPING

AREA FROM ONE UNIT. PROTOCOL SUITES MAY HAVE ONE FAN-COIL EACH FOR LIVING

AREA AND SLEEPING AREA. PROVIDE EXHAUST GRILLE IN HEAD AND VENTILATION

REGISTER IN BOTH THE LIVING AND SLEEPING AREAS FROM THE DOAS.

PROVIDE SEMI-CUSTOM FOUR-PIPE AIR HANDLING UNIT IN CLOSET FOR TEMPERATURE

AND HUMIDITY CONTROL IN COMMON AREA. PROVIDE EXHAUST GRILLE IN HEAD/

CUSTODIAL ROOM AND VENTILATION REGISTERS IN COMMON AREAS FROM THE DOAS.

PROVIDE GAS-FIRED WATER HEATER(S) AND DOMESTIC HOT WATER RECIRCULATION

PUMP TO DISTRIBUTE DOMESTIC HOT WATER THROUGHOUT THE FACILITY. PROVIDE

DOMESTIC COLD WATER BACKFLOW PREVENTER. DISTRIBUTE DOMESTIC COLD WATER

THROUGHOUT THE FACILITY. PROVIDE DOMESTIC WATER AND SANITARY/VENT UTILITIES

FOR EACH FIXTURE AND EQUIPMENT REQUIRING THESE UTILITIES THROUGHOUT THE

FACILITY.

AutoCAD SHX Text

SYM

AutoCAD SHX Text

DATE

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

SATISFACTORY TO: DATE

AutoCAD SHX Text

APPROVED: PWO OR OICC DATE

AutoCAD SHX Text

DESIGN DIR.

AutoCAD SHX Text

SUBMITTED BY:

AutoCAD SHX Text

DR.

AutoCAD SHX Text

CHK.

AutoCAD SHX Text

DES.

AutoCAD SHX Text

CAMP LEJEUNE, NORTH CAROLINA

AutoCAD SHX Text

CONST. CONTR.

AutoCAD SHX Text

MARINE CORPS BASE

AutoCAD SHX Text

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text E1

AutoCAD SHX Text

SIZE

AutoCAD SHX Text 80091

AutoCAD SHX Text

SPEC.

AutoCAD SHX Text

CODE IDENT. NO

AutoCAD SHX Text

NAVFAC DRAWING NO.

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text 18168

AutoCAD SHX Text BOQs 2602, 2603, 2604, 2605

AutoCAD SHX Text 2607, 2609, 2611, 2613, 2617

AutoCAD SHX Text 20-0046

AutoCAD SHX Text

NA

AutoCAD SHX Text

NOTED

AutoCAD SHX Text

FINAL 21MAY 2020

AutoCAD SHX Text

T H BURTON, PE

AutoCAD SHX Text M-104

AutoCAD SHX Text

BOQ 2602 LEVEL 2 FLOOR PLAN

AutoCAD SHX Text

AutoCAD SHX Text

DMH

AutoCAD SHX Text

GRM

AutoCAD SHX Text

DMH

AutoCAD SHX Text

Sheets and Views
M104
OLE1

File details come from the government source that posted it. Updated .