This document is an Engineering Systems Requirements (ESR) specification for plumbing systems in a Battery Energy Storage System (BESS) project at 29 Palms, California. The plumbing system requirements cover domestic water supply, sanitary waste, emergency fixtures, and specialized systems specific to the battery installation. Key technical specifications include:
Plumbing system components must use copper tubing for above and below ground piping, with mineral fiber and cellular glass insulation with vapor barriers for hot and cold water lines. An emergency portable eyewash station meeting ANSI Z358.1 requirements is mandated, along with floor drains in the battery area. The system also requires a battery electrolyte waste collection system, and provisions for condensate drainage from AC units. All installations must comply with International Plumbing Code (IPC) and UFC 3-420-01 standards, with concrete equipment pads and proper working space around all equipment.
View the file
Other files
Show 40 more
Latest 50 of 76 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-1238 Construction of Grid Stability & Resiliency 10 MW Battery Energy Storage, Various Buildings.
Work Order Number 20190612 29 Palms/California
PART 3 - CHAPTER 6 / ESR D20 - Page 1
6. ENGINEERING SYSTEMS REQUIREMENTS
D20 PLUMBING
Refer to Part 4 Section D20 for performance requirements of the building elements included in the plumbing system.
SYSTEM DESCRIPTION
The plumbing system for Battery Energy Storage System (BESS) consists of all fixtures, potable cold and hot water piping and equipment, piping insulation, water heating equipment, sanitary waste and vent piping systems, and other specialty piping and equipment within 5 foot (1.5 meter) of the building.
Refer to Building Requirements, Space Tabulations Section of the Project Program for building occupancy levels.
GENERAL SYSTEM REQUIREMENTS
Provide working space around all equipment. Provide concrete pads under all equipment. Provide all required fittings, connections and accessories required for a complete and usable system. Install all equipment in accordance with the criteria of PTS section D20 and the manufacturer's recommendations. Design and install in accordance with International Plumbing Code (IPC) and UFC 3-420-01, Plumbing Systems. Where the word "should" is used in the manufacturer's recommendations, substitute the word "must".
D2010 PLUMBING FIXTURES
Not Used.
D201090 EMERGENCY FIXTURES
Provide emergency portable eyewash. A portable, standalone type emergency eyewash (EWS) is required and will meet ANSI Z 358.1 requirements. The system shall have tepid water tank with heater. An emergency alarm indicator light will be provided per UFC 3-420-01. Floor drains are not required for EWS per International Plumbing Code Section 411 and UFC 3-420-01.
D202001 PIPES AND FITTINGS
Provide Copper tubing and fittings for above ground and buried piping.
D202004 INSULATION & IDENTIFICATION
Provide mineral fiber insulation with vapor barrier on domestic hot water supply and recirculation piping. Provide cellular glass insulation with vapor barrier on domestic cold water supply. Provide identification for piping and equipment.
D202090 OTHER DOMESTIC WATER SUPPLY
Provide piping supports in accordance with the IPC. Provide inspections, disinfection, and testing in accordance with the IPC.
P-1238 Construction of Grid Stability & Resiliency 10 MW Battery Energy Storage, Various Buildings.
Work Order Number 20190612 29 Palms/California
PART 3 - CHAPTER 6 / ESR D20 - Page 2
D2030 SANITARY WASTE
D203001 WASTE PIPE & FITTINGS
Provide plastic PVC or ABS piping, fittings, and solvent cement for above and below ground installation.
D203002 VENT PIPE & FITTINGS
Not used.
D203003 FLOOR DRAINS
Provide floor drains in battery area, design them in accordance with UFC 3-420-01, Plumbing Systems.
Provide floor sinks to receive condensate from AC units.
D2040 RAIN WATER DRAINAGE
D204001 PIPE & FITTINGS
D204002 ROOF DRAINS
Provide roof drains that are compatible with the roofing system.
D204004 INSULATION & IDENTIFICATION
D2090 OTHER PLUMBING SYSTEMS
D209002 ACID WASTE SYSTEMS
Provide battery electrolyte waste collection system for the BESS.
--End of Section--