SECTION 28 10 05: ELECTRONIC SECURITY SYSTEMS (ESS) SPECIFICATION
This is a federal technical specification document (NUWC P-084, Amendment 006) issued by Newport Naval Station for the design, installation, and integration of a complete Electronic Security System comprising intrusion detection, access control, video surveillance, security command center, communications, and security lighting subsystems. The specification mandates compliance with numerous industry standards including UL (Underwriters Laboratories), NFPA 70 (National Electrical Code), NIST encryption standards, TIA telecommunications cabling standards, and military grounding/bonding standards (MIL-HDBK-419, MIL-STD-188-124), with all materials and equipment manufactured more than one year prior to delivery deemed unacceptable. Government approval is required for shop drawings, product data, design calculations, certificates of qualifications, and operation/maintenance documentation submitted under the specified submittal procedures.
The Intrusion Detection System must detect intrusions within 300-foot zones along perimeters and individual assets with a probability of detection of 0.9-0.95 at 90-95 percent confidence levels, including both interior sensors (high security switches, microwave, dual technology, photoelectric) and exterior sensors (fence-mounted fiber optic/strain-sensitive cable, electrostatic field, taut-wire, dual technology, bistatic/monostatic microwave, passive infrared, active infrared, video motion, radar, and duress alarms) all conforming to UL 639. The Access Control System must support Common Access Cards (CAC) provided by the Government and be capable of controlling up to 16 card readers and keypads per controller with support for multiple authentication technologies (keypad, CAC, biometric, smart card combinations) and elevator floor control. Both systems require networked integration via TCP/IP or fiber-optic configurations with 128-bit AES encryption (NIST FIPS 197), continuous link supervision, backup battery capacity exceeding sensor/communications/alarm requirements plus 25 percent spare capacity, and on-site training for 10 designated personnel including administrator, operator, and five-day maintenance courses with two months of follow-up sessions. The specification emphasizes tamper protection, line supervision, fail-safe capabilities, environmental performance across temperature ranges of minus 25 to 140 degrees F for exterior equipment and 32 to 120 degrees F for interior equipment, and comprehensive bonding/grounding/shielding per military standards with ground rods not exceeding 10 ohms resistance for sensor locations.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NUWC P-084 AMENDMENT 006
NEWPORT NAVAL STATION, NEWPORT, RI OCTOBER 2026
SECTION 28 10 05
ELECTRONIC SECURITY SYSTEMS (ESS)
05/24
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ASC/X9 X9.52 (1998) Triple Data Encryption Algorithm Modes of Operation
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM B32 (2020) Standard Specification for Solder Metal
ASTM D709 (2017) Standard Specification for Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits
IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits
INTELLIGENCE COMMUNITY STANDARD (ICS)
ICS 705-1 (2010) Physical and Technical Security Standard for Sensitive Compartmented Information Facilities
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)
ANSI ISO/IEC 7816 (R 2009) Identification Cards - Integrated Circuit Cards
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2020) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA ICS 1 (2022) Standard for Industrial Control and Systems: General Requirements
SECTION 28 10 05 Page 1
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023) National Electrical Code
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY (NIST)
NIST FIPS 140-2 (2001) Security Requirements for Cryptographic Modules
NIST FIPS 197 (2001) Advance Encryption Standard
NIST FIPS 201-2 (2013) Personal Identity Verification (PIV) of Federal Employees and Contractors
NIST SP 800-116 (2018; Rev 1) Guidelines for the Use of PIV Credentials in Facility Access
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-568.2 (2018d) Balanced Twisted-Pair Telecommunications Cabling and Components Standards
TIA-606 (2021d) Administration Standard for Telecommunications Infrastructure
TIA-607 (2019d) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-HDBK-419 (1987; Rev A) Grounding, Bonding, and Shielding for Electronic Equipments and Facilities Volumes 1 of 2 Basic Theory
MIL-STD-188-124 (1998; Rev B; Notice 2 1998; Notice 3 2000; Notice 4 2013) Grounding, Bonding and Shielding for Common Long Haul/Tactical Communications Systems, Including Ground Based Communications - Electronics Facilities and Equipments
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
47 CFR 15 Radio Frequency Devices
UNDERWRITERS LABORATORIES (UL)
UL 50 (2024) UL Standard for Safety Enclosures for Electrical Equipment, Non-Environmental Considerations
UL 294 (2023) UL Standard for Safety Access Control System Units
UL 437 (2013; Reprint Jan 2022) UL Standard for Safety Key Locks
SECTION 28 10 05 Page 2
UL 634 (2007; Reprint Mar 2015) Connectors and Switches for Use with Burglar-Alarm Systems
UL 636 (2018) UL Standard for Safety Holdup Alarm Units and Systems
UL 639 (2007; Reprint Jun 2024) Standard for Intrusion Detection Units
UL 681 (2014; Reprint Jan 2021) UL Standard for Safety Installation and Classification of Burglar and Holdup Alarm Systems
UL 796 (2020; Reprint Oct 2023) UL Standard for Safety Printed Wiring Boards
UL 969 (2017; Reprint May 2023) UL Standard for Safety Marking and Labeling Systems
UL 1037 (2016; Reprint Aug 2023) UL Standard for Safety Antitheft Alarms and Devices
UL 1076 (2018; Reprint Feb 2021) UL Standard for Safety Proprietary Burglar Alarm Units and Systems
UL 2050 (2003; 4th Edition) Standard for National Industrial Security Systems for the Protection of Classified Materials (limited distribution publication, direct purchase request with justification to UL)
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government. Submit the following in accordance with Section
01 33 00 SUBMITTAL PROCEDURES:
The Project Officer will review and , Naval Facilities Engineering Command will approve submittals requiring special review in this section.
SD-02 Shop Drawings
ESS Components ; G, Access Control System (ACS) ; G, Security Hardware Door Schedule ; G, Overall System Schematic ; G, SD-03 Product Data
Premise Control Unit ; G, SECTION 28 10 05 Page 3
Detection Sensors ; G, Access Control Unit ; G, Access Control Devices ; G, Communications Interface Devices ; G, Radio Frequency Link ; G, Network Switch ; G, Video and ESS Transmission ; G, Uninterruptible Power Supply (UPS) ; G, Batteries ; G, Equipment Rack ; G, SD-05 Design Data
Backup Battery Capacity Calculations ; G, Video Surveillance System (VSS) Storage Calculations ; G, Error and Throughput Rates ; G, SD-07 Certificates
Contractor Qualifications ; G, Instructor Qualifications ; G, Contact Card Readers ; G, Contactless Card Readers ; G, Data Encryption ; G, Wire And Cable ; G, Bonding, Grounding, And Shielding ; G, SD-10 Operation and Maintenance Data
ESS Components ; G, ESS Software, Data Package 4 ; G, ESS Training ; G, ESS Training Outline ; G, Submit data package in accordance with Section 01 78 23
OPERATION AND MAINTENANCE DATA
SD-11 Closeout Submittals
SECTION 28 10 05 Page 4
As-Built Drawings ; G,
1.3 QUALITY ASSURANCE
1.3.1 Regulatory Requirements
The advisory provisions in each of the publications referred to in this specification are mandatory. Interpret these publications as though the word "must" has been substituted for "should" wherever it appears.
Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer.
Equipment, materials, installation, and workmanship must be in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.3.2 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening and have been utilized in applications of equipment and materials under similar circumstances and of similar size.
b. Have been available on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer.
d. Provide commercial off-the-shelf (COTS) products in which the manufacturer allows a network of qualified distributors to sell, install, integrate, maintain, and repair the hardware and software products that make up the system. All products are to be NDAA and FAR subpart 4.21 compliant.
1.3.2.1 Alternative Qualifications
Products having less than a 2 year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.3.2.2 Material and Equipment Manufacturing Date
Products manufactured more than one year prior to date of delivery to the site are not acceptable.
1.3.2.3 Product Safety
System components are to conform to applicable rules and requirements of NFPA 70 . Equip system components with instruction stickers including warnings and cautions describing physical safety, and special or important procedures to be followed in operating and servicing system equipment.
SECTION 28 10 05 Page 5
1.3.3 Shop Drawings
1.3.3.1 ESS Components
Submit the ESS Components, Data Package 4 with the ESS Software submittal package in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA. Submit drawings that clearly and completely indicate each ESS component function that includes:
a. Termination device points
b. Interconnections required for system operation
c. Interconnections between modules and devices
d. Component and device wiring diagrams.
e. Proposed wireway or conduit systems to be used including:
(1) Locations
(2) Sizes
(3) Types
f. Drawings showing:
(1) Device locations and spacing
(2) Mounting and positioning details
(3) Riser Diagrams with cable sizes and types
(4) Bill of Materials (Device make, model and quantities)
(5) Alarm and access control zones
(6) Video Surveillance System (VSS) and sensor coverage areas
(7) Spare capacity
(8) Tables with ( Security Hardware Door Schedule ) identifying security devices requirements per building, room, and door
(9) Overall system schematic diagram(s).
1.3.4 Evidence of Experience and Qualifications
1.3.4.1 Contractor Qualifications
Contractor or its subcontractor(s) must be a Value Added Resaler (VAR)/Authorized Dealer (AD) of the manufacturer line of products being installed. Provide manufacturer certificate showing current dealership status. Technicians working the project must provide certificates of training for the requirements of the manufacturer, and those certificates must be from the manufacturer or approved by the manufacturer.
Submit experience and certified qualifications data prior to
SECTION 28 10 05 Page 6 installation. Show that specific installers who will perform the work have a minimum of 2 years of experience successfully installing ESS of the same type and similar design as specified. Include the names, locations, and points of contact of at least two installations of similar type and design as specified in this document where the installer has installed such systems. Indicate the type of each system installed. Certify that each system has performed satisfactorily in the manner intended for a period of at least 12 months. Installation and maintenances of IDS for the protection of classified information to be performed by US citizens who have been subject to a trustworthiness determination.
1.3.4.2 Instructor Qualifications
Submit the instructor's experience and certified qualifications data prior to installation. Show that the instructor has received a minimum of 24 hours of ESS training from the manufacturer of the product being installed, and 2 years experience in installing the specified ESS type.
1.4 ENVIRONMENTAL CONDITIONS
1.4.1 Interior Conditions
Equipment installed in environmentally protected interior areas must meet performance requirements specified for the following ambient conditions:
1.4.1.1 Temperature
32 to 120 degrees F. Components installed in unheated security protected areas must meet performance requirements for temperatures as low as 0 degrees F
1.4.1.2 Pressure
Sea level to 15,000 feet above sea level
1.4.1.3 Relative Humidity
5 to 95 percent
1.4.1.4 Fungus
Components must be constructed of non-fungus nutrient materials or be treated to inhibit fungus growth
1.4.1.5 Acoustical Noise
Components must be suitable for use in high noise areas above 100 dB, without adversely affecting their performance
1.4.2 Exterior Conditions
Components in enclosures must meet performance requirements when exposed to the following ambient conditions:
1.4.2.1 Temperature
Minus 25 to 140 degrees F
SECTION 28 10 05 Page 7
1.4.2.2 Pressure
Sea level to 15,000 feet above sea level
1.4.2.3 Solar Radiation
Six hours of solar radiation per day at dry bulb temperature of 120 degrees F including 4 hours of solar radiation at 104 watts per square foot
1.4.2.4 Sand and Dust
Wind driven for up to 6 miles per hour (mph) in accordance with UL 294 and
UL 639 .
1.4.2.5 Rain
2 inches per hour and 5 inches per hour cyclic with wind plus one period of 12 inches per hour in accordance with UL 294 and UL 639 .
1.4.2.6 Humidity
5 to 95 percent
1.4.2.7 Fungus
Warm, humid atmosphere conducive to the growth of heterotrophic plants
1.4.2.8 Salt Fog
Salt atmosphere with 5 percent salinity
1.4.2.9 Snow
Snow loading of 48 (psf) per hour; blowing snow of 4.6 psf per hour.
Blowing snow from any angle (falling vertically to horizontal blowing from any azimuth) must not penetrate ESS equipment.
1.4.2.10 Ice Accretion
Up to 1/2 inches of radial ice
1.4.2.11 Wind
Continual velocity up to 50 mph with gusts to 66 mph, except that fence sensors must detect intrusions up to 35 mph
1.4.2.12 Acoustical Noise
Visual alert device and components should be used in high noise areas above 110 dB without adversely affecting their performance. Examples areas include flight lines, run-up pads, and generator sites.
1.5 SYSTEM CALCULATIONS AND ANALYSIS
1.5.1 Backup Battery Capacity Calculations
Submit calculations showing that backup battery capacity exceeds sensor operation, communications supervision, and alarm annunciation power
SECTION 28 10 05 Page 8 requirements for proposed equipment plus 25 percent spare capacity. In environments regularly exposed to conditions of 32 degrees F provide 50 percent spare capacity. In environments regularly exposed to conditions of 120 degrees F provide resistance to thermal runaway for lithium based batteries.
1.5.2 Video Surveillance System (VSS) Storage Calculations
Submit calculations showing the required storage capacity for each video storage device. Calculations must be based on the recording parameters specified by the end user/customers operational requirements.
1.6 ESS SOFTWARE, DATA PACKAGE 4
Submit the ESS software, Data Package 4 with the ESS Components submittal package in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA. Describe the functions of all software in the software manual and include:
a. All information necessary to enable proper loading, testing, and operation
b. Terms and functions definitions
c. Use of system and application software
d. Procedures for system initialization, start-up and shutdown
e. Alarm reports
f. Reports generation
g. Database format and data entry requirements
h. Directory of all files
i. All communication protocol descriptions, including data formats, command characters, and a sample of each type of data transfer
j. Interface definition
k. List of software keys
l. Backup and restore procedures and instructions on how to archive reports and video footage on DVD for forensics investigations.
1.7 AS-BUILT DRAWINGS
Maintain a separate set of drawings, elementary diagrams, and wiring diagrams of the system to be used for as-built drawings. Keep this set accurately and neatly up to date with all changes and additions. This set is not to be used for installation purposes.
Finish the final drawings submitted with the endurance test report in accordance with Section 01 78 00 CLOSEOUT SUBMITTALS for as-built requirements.
SECTION 28 10 05 Page 9
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide a complete and integrated electronic security system (ESS) that meets the requirements of . ESS must be compatible with the Installation's central monitoring system and monitored within the secure/protected area and at the Installation central monitoring station.
Installation's central monitoring system is manufactured by the government, model number by the government. ESS consisting of the following subsystems and features:
a. Intrusion Detection System (IDS)
b. Access Control System (ACS)
c. Video Surveillance System (VSS)
d. Security Command Center (SCC)
e. Communications System
f. Security Lighting Systems
Include materials not normally furnished by the manufacturer with the ESS equipment as specified in:
a. Section 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
b. Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM
2.2 PERFORMANCE REQUIREMENTS
Integrate the installed and operating subsystems into the overall ESS system to detect intrusion, control access, video surveillance, visual verification, and perform as an entity, as specified below. Provide electronic equipment that complies with 47 CFR 15 and are suitable for the environment where they will be installed.
2.2.1 Growth Capability
Provide capability for modular ESS expansion of inputs, outputs, card readers, and remote-control stations with minimal equipment modification.
Software must be able to handle design requirements plus 25 percent spare capacity. Growth capability is not to be limited by the provided products.
2.2.2 Hazardous Locations
When located in areas where fire or explosion hazards exist, provide system components rated and installed according to Chapter 5 of NFPA 70 .
2.2.3 Maintainability
Provide components that can be maintained using commercially available tools and equipment. Arrange and assemble components to be readily accessible to maintenance personnel without compromising system defeat resistance and with no degradation in tamper protection, structural integrity, EMI or RFI attenuation, or line supervision after maintenance when it is performed in accordance with manufacturer's instructions.
SECTION 28 10 05 Page 10
2.2.4 Availability
Provide components rated for continuous operation. Provide solid-state electronic components mounted on printed circuit boards, conforming to UL 796 . Provide boards that are plug-in, quick-disconnect type. Do not impede maintenance with densely packed circuitry. Provide power-dissipating components with safety margins of not less than 25 percent with respect to dissipation ratings, maximum voltages, and current-carrying capacity. Provide heat sinks or other heat dissipation devices on appropriate components and assemblies. Provide solid-state type or hermetically sealed electromechanical type light duty relays and similar switching devices.
2.2.5 Fail-Safe Capability
Provide fail-safe capability in critical elements of the ESS including, but not be limited to, the capability to monitor communication link integrity and to provide self-test. Provide fault annunciation when diminished functional capabilities are detected. Annunciate fail-safe alarms to clearly distinguish from other types of alarms.
2.2.6 Line Supervision
Provide the same geographic resolution for fault isolation at the systems level as provided for intrusion detection. Provide either a static or dynamic system with active mode for line supervision of communication links of the ESS.
a. The static system must represent "no-alarm" always by the same signal, which is different than the originally transmitted signal.
b. The dynamic system must represent "no-alarm" with a signal which continually changes with time.
2.2.7 Power Loss Detection
Detect AC and DC power loss and generate an alarm when a critical component of the system experiences temporary or permanent loss of power.
Annunciate the alarm in the Secured Area and the Security Command Center to clearly identify the component experiencing power loss.
2.2.8 Controls and Designations
Provide controls and designations in accordance with NEMA ICS 1 .
2.2.9 Special Test Equipment
Provide all special test equipment, special hardware, software, tools, instructions, and programming or initialization equipment needed to start or maintain any part of the system and its components. Special test equipment is defined as any test equipment not normally used in an electronics maintenance facility.
2.2.10 Electromagnetic Interference (EMI)
Configure and provide ESS components employing electromagnetic radiation constructed to provide minimal vulnerability to electronic countermeasures.
SECTION 28 10 05 Page 11
2.2.11 Electromagnetic Radiation (EMR)
Provide only ESS communication components which are Federal Communications Commission (FCC) licensed and approved. Provide system components which are electromagnetically compatible.
2.2.12 Interchangeability
Use off-the-shelf components which are physically, electrically, and functionally interchangeable with equivalent components as complete items. Equivalent, replacement components must not require new or other component modification. Do not use custom designed or one-of-a-kind items. Interchangeable components or modules must not require trial and error matching in order to meet integrated system requirements, system accuracy, or restore complete system functionality.
2.2.13 Date and Time Generator
The ESS system date and time are to originate from the ESS network time server GPS synchronization system with GPS satellite antenna.
2.3 INTRUSION DETECTION SYSTEM (IDS)
The IDS primary function is to detect intrusion into secured areas.
Utilize a single database for all IDS programming data that seamlessly integrates with the ESS under a single operating environment. The IDS events must be viewable as separate or as a combined list of all ESS events. Control the IDS alarm monitoring through software control from the ESS.
a. Provide both supervised and non-supervised alarm point monitoring.
b. Secure or access alarm points both manually and automatically by time of day, day of week or by operator command.
c. For classified assets, IDS installation related components and monitoring stations must comply with UL 2050 .
2.3.1 IDS Components
Provide components:
a. Premise Control Units (PCU)
b. Detection Sensors
c. Tamper Switches
d. Arm/Disarm Keypads
2.3.2 Detection Sensitivity
The sensitivity of the IDS must allow for the following:
a. Locating intrusions within 300 feet zones along a line or perimeter to one side of the facility
b. Locating intrusions at individually protected assets or at an individual portal
SECTION 28 10 05 Page 12
c. Locating intrusions within the coverage on a single volumetric sensor
d. Locating failures or tampering at individual sensors
2.3.3 Detection Alarm and Reporting Capacity
Collect, communicate, and display up to 256 sensor zone alarms and to enable control of card reader with integral keypad for arming and disarming.
Identify individual sensors in alarm if the sensor zone is a multiple alarm source combination. Annunciate a single alarm within 2 seconds maximum, after sensor transducer or other detection device activation except that alarms transmitted by radio frequency signaling must communicate in less than 3 seconds.
2.3.4 False Alarm Rate
The false alarm rate for each interior IDS zone must not exceed one false alarm per 30-day period. The false alarm rate for each exterior IDS zone must not exceed one false alarm per 24-hour period.
2.3.5 Nuisance Alarm Rate
The nuisance alarm rate for each interior IDS zone must not exceed three nuisance alarms per 30-day period. The nuisance alarm rate for each exterior IDS zone must not exceed three nuisance alarms per 24-hour period.
2.3.6 Premise Control Unit (PCU)
Install the PCU command processor in a tamper resistant enclosure that is specified in paragraph COMPONENT ENCLOSURE. Package the following with the PCU:
a. Power transformer
b. Battery(s)
c. Network connection cable
d. Keypad(s)
e. Keypad connection cable(s)
f. Additional components as required for full functionality
2.3.6.1 PCU Capabilities
Provide the PCU at a minimum but not limited to, the following capabilities;
a. Expansion to a total of at least 10,000 user codes with 99 user profile definitions.
b. Support 16 keypads with alphanumeric display. Each keypad must be capable of arming and disarming any system area based on a pass code or access control card and or key FOB authorization. Provide keypad alphanumeric display with complete prompt messages during all stages of operation and system programming and display all relevant operating
SECTION 28 10 05 Page 13 and test data.
c. Four 4 shift schedules per area.
d. A total of at least 100 programmable output relay schedules.
e. 64 individual reporting areas.
f. Data line supervision or two separate lines of communication.
g. Two-man access code or credentials.
h. Support programming to require the same or different access code entered within a programmed delay time of 1 to 15 minutes after disarming before activating a silent ambush alarm.
i. Support area programming that disables schedule and time-of-day changes while system is armed so that area can only be disarmed during scheduled times.
j. Provide a minimum of a 4,000 event log buffer per PCU. Record and hold alarm activity information in the log buffer until the ESS is connected and receives the information. Provide a software-configurable warning log buffer filling notification for PCU(s) configured with network switch capabilities.
k. Support a Network Interface Card (NIC) plug-in module with built in network router capable of 128 Bit AES Rijndael Encryption process certified by NIST (National Institute of Standards and Technology).
2.3.6.2 Overcurrent Protection and Indication
When overcurrent more than it is rated for is detected by the PCU, communication bus(es) and keypad(s) are to be shut down and an overcurrent notification LED lit to indicate the situation.
2.3.6.3 Manual and Self-Test
All alphanumeric keypad to include testing for: standby battery, alarm bell or siren, and communication to the Security Command Center (SCC).
Include provisions for an automatic, daily, weekly, 30 day, or up to 60 day communication link test from the PCU installation site to the SCC.
Include a provision for displaying the internal system power and wiring conditions.
Include the following for internal monitoring points:
a. The bell circuit
b. AC power
c. Battery voltage level
d. Charging voltage
e. Panel box tamper
f. Phone trouble line 1
SECTION 28 10 05 Page 14
g. Phone trouble line 2
h. Transmit trouble
i. Network trouble
A battery test must be automatically performed to test the integrity of the standby battery by disconnecting the standby battery from the charging circuit and placing a load on the battery. Perform this test at an interval no greater than 180 days.
2.3.7 Detection Sensors
a. Sensors are to detect facility perimeter or protected zone penetrations by unauthorized personnel or intruders and transmit an alarm signal to the alarm annunciation system upon change detection.
Accomplish this with a probability of detection (PD) of 0.9, 0.95 with a 90, 95 percent confidence level and conforming to UL 639 where applicable.
Probability of Detection 0.9 0.9 0.95 0.95 Number of Misses Allowed
Confidence Level 90 Percent
Percent
Percent
Percent
Number of Intrusion Attempts 22 29 45 59 0
38 46 77 93 1
52 61 105 124 2
65 76 132 153 3
78 89 158 181 4
91 103 184 208 5
b. Required sensor power is 12 VDC unless otherwise specified.
c. An interior IDS zone is a room or space within a building that can be armed and disarmed independently from all other zones.
d. Provide line supervision for all sensors with an end-of-line resistor at the sensor or within a tampered junction box with conduit from the junction box to the sensor.
d. Provide sensors and components rated for operation in the installed environment. The sensors must transmit an alarm signal to the alarm annunciation system upon change detection. Provide all sensors with a tamper switch and elements housed in a tamper-alarmed enclosure in accordance of paragraph COMPONENT ENCLOSURE.
SECTION 28 10 05 Page 15
2.3.7.1 Interior Sensors
2.3.7.1.1 High Security Switch (HSS)
Mount the HSS inside the secure location and on the opening side of the door. HSS sensors do not have the capability to incorporate an end-of-line (EOL) resistor.
2.3.7.1.1.1 Level 1 Switch
UL 634 . Level 1 High Security
2.3.7.1.1.2 Level 2 Switch
UL 634 . Level 2 High Security
2.3.7.1.2 Microwave Sensors
UL 639 .
2.3.7.1.3 Dual Technology Sensors
UL 639 . Provide sensor combining passive infrared (PIR) and microwave sensors configured and manufactured specifically to be mounted in a single tamper alarmed enclosure. The sensor must provide selectable "AND" logic or "OR" logic for alarm indication configured in the "OR" logic state.
Provide sensors that have a local means of indicating detection for use during installation and calibration with a means of disabling the indication.
The sensor is to have an LED walk test indicator which is not visible during normal operations. When visible, the walk test indicator will light when the sensor detects an intruder. Provide a sensor equipped with a manual control, located within the sensor's housing, to enable and disable the test indicator or with the test indicator located within the sensor housing so that it can only be seen when the housing is open or removed.
2.3.7.1.4 Photoelectric Sensors
UL 639 . The sensor is to detect opaque bodies and not allow an intruder to disable detection by shining another light source into the receiver.
Provide sensor with a local means of indicating detection for use during installation and calibration with a means of disabling the indication.
2.3.7.2 Exterior Sensors
2.3.7.2.1 Wide Gap High Security Switch (HSS)
Provide UL 634 approved wide gap HSS for all exterior applications (gates, etc.) that cannot operate within the close tolerances of standard HSS sensors. Ensure the application tolerances are within the HSS limitations set by the manufacturer for optimum operation.
2.3.7.2.2 Fence Mounted Sensors
Sensors are fiber optic or strain-sensitive cable sensors as indicated which initiate an alarm when an intruder attempts to scale, cut through, SECTION 28 10 05 Page 16 lift the fabric of, or lean climbing devices on to the entire length of a standard chain link fence or physical barrier. Provide sensors that are either tamper alarmed or self-protecting. House exterior components in rugged, corrosion-resistant enclosures, as specified in paragraph
COMPONENT ENCLOSURE.
Provide fence cable support hardware that is weather-resistant.
2.3.7.2.2.1 Fiber Optic Sensor
The sensor consists of an ultraviolet resistant fiber optic transducer cable with a microprocessor based dual zone signal processor that is capable of monitoring different styles of metal fabric fencing including chain-link, expanded-metal or welded-mesh fence. The sensor detects intruders by utilizing signals generated by the minute flexing of the fiber optic transducer cable, caused by attempting to cut, climb, or raise the fence fabric.
The signal processor analyzes the signals from the fiber optic transducer cable and detects minute vibrations in the fabric of the fence. The signal processor supports dual zones with each zone supporting a maximum 1640 feet of sensing cable. The processor utilizes adaptive algorithms, ambient signal compensation and selectable common-mode rejection, to discriminate between actual, false and nuisance alarms, without lowering the probability of detection. The processor identifies, by type, a cut intrusion and a climb intrusion. Provide sensors with independent adjustments and thresholds for each type of intrusion and have the capability to completely mask climb or cut alarms. Alarms caused by power failure, low input voltage, cable fault (cable cut or high loss due to physical stress), or internal electronic fault are to be identified as supervisory alarms. Equip the sensor with a test indicator if it is an integral sensor signal processor function.
2.3.7.2.2.2 Strain-Sensitive
a. Provide a complete fence line protection with no dead zones where an intruder can penetrate the fence. Through sensor electronics the fence line protection must be divided into zones. Sensing unit of sensor must achieve specified performance with transducer cable either by attachment directly to the fence fabric by plastic cable every 12 to 18 inches or by installation inside RGS conduit mounted on the fence. Provide sensing units with equal adjustable sensitivity throughout the entire length.
b. Use only conventional waterproof coaxial cable connectors for connections of the sensing unit to permit installation in extreme EMI environments with no loss of detection capability. Entire sensor system must be capable of detecting tampering within each system portion by sensor zone.
c. Provide capability for alarm threshold sensitivity adjustment to permit compensation by zone for winds up to 35 mph while maintaining the same level of detection performance as under ambient conditions.
d. Sensor zone control unit must provide an analog audio output for interface to an external audio amplifier to permit remote audio assessment regardless of sensor alarm status. Sensor zone control unit alarm output interface is to be a separately supervised relay contact normally open or normally closed, with an adjustable intrusion
SECTION 28 10 05 Page 17 alarm pulse width of 0.5 second adjustable and a continuous (until corrected) tamper alarm.
2.3.7.2.2.3 Gate Units
Provide gate units in accordance with specific fence sensor manufacturer's recommendations to ensure continuous fence sensor zone protection for the entire protected perimeter. Provide a gate unit for each fence portal.
Provide separately zoned HSS gate sensors when gate units are not provided by the fence sensor manufacturer. HSS sensors perform as specified in paragraph WIDE GAP BALANCED MAGNETIC SWITCH.
2.3.7.2.3 Electrostatic Field Sensors
a. Initiate an alarm when an intruder attempts to approach or scale a fence or physical barrier. Electrostatic field sensors generate an electric field around one or more horizontal wires and sense the induced signal in parallel sensing wires to detect human presence.
Provide sensors that monitor the induced signal for changes that result from the presence of a conductive body or a body with a high dielectric constant.
b. Use mounting and support hardware as provided by the equipment manufacturer.
c. Provide spring tension-mounted wire on end-of-line terminators to detect cutting, shorting, or breaking of the wires. Select sensor configuration such that an intruder cannot crawl under the bottom wire, through the wires, or over the top wire without being detected and be divided into sensor zones.
d. Sensors must be capable of following irregular contours and barrier bends without degrading sensitivity below the specified detection level. Adjacent zones must provide continuous coverage to avoid a dead zone and be configured to prevent crosstalk interference.
e. Provide filtering on signal processing circuitry to distinguish nuisance alarms. Sensor configuration is to incorporate balanced, opposed field construction to eliminate far field noise.
f. House exterior components in rugged corrosion-resistant enclosures, protected from environmental degradation and provided with tamper switches. Use underground cables to interface between exterior units. Use stainless steel or galvanized exterior support hardware.
Use stainless steel sensor and field wires.
g. Follow manufacturer's specifications for wire spacing of various configurations.
h. Provide adjustable sensor sensitivity which is inaccessible to operating personnel.
2.3.7.2.4 Taut-Wire Sensors
a. Incorporate perimeter intrusion detection sensors into a barbed or barbless wire security fence. Detect intrusion of cutting of any single wire or the deflecting, as by climbing, of any wire by more than
3.1 inches. A sensor zone includes one or more 200 feet maximum
SECTION 28 10 05 Page 18 sections of 7 foot high parallel fence with each sector consisting of 13 horizontal tensioned wires attached to the taut-wire fence posts, and three strands as outriggers, plus an "anti-ladder" trip wire supported by rods extending from the outriggers for a total vertical height of approximately 8 feet.
b. Mount displacement switches for each horizontal wire within a prewired channel fastened to the fence post at the midpoint of each section.
Outrigger barbed wire and tripwire may share the same switch. Mount each taut-wire fence post to the normal security fence (chain link) fabric posts or other barrier via standoffs to position the taut-wire approximately 6 inches from the fence fabric or other barrier.
c. Mount freestanding taut-wire fence posts in concrete to support the taut-wire fence system. Pretension and clamp each barbed or barbless wire strand to the lever arm of the displacement switch, such that the lever is in the neutral (off) position; therefore, the forces applied by the barbed or barbless wires are balanced equal in opposite directions. Pretension tripwires in a like manner. Line tripwires to the top switch in the sensor switch channel by a special subassembly that includes a rod which transfers tripwire movement as a lever to the end of the actuating sensor switch's lever arm.
d. Initiate an alarm upon abnormal switch lever displacement. This would result from cutting or deflecting its attached wire, as by climbing on or through fence strands. Provide sensor with a damping mechanism which reduces alarm threshold due to slowly changing phenomena including ground shifting, daily and seasonal temperature variations, and winds up to 35 mph.
e. Sensor switch must provide electrical contact closure as the means for initiating an alarm, whenever the wire clamped to the vertical center bolt is pulled laterally in any direction by an amount not over 0.75 inch.
f. Housing for switch assembly must be covered by a neoprene cap to retain the center bolt (lever arm). This bolt translates attached horizontal wire movement into the contact closure. The bolt functions as the fulcrum for the lever when the neoprene cap is firmly seated on the cup-shaped polycarbonate housing.
g. Provide threaded upper exposed end of the lever to accommodate clamping to the horizontal wire. The lower end of the lever, which is fashioned to serve as the movable electrical contact, must be held suspended in a small cup-shaped contact that floats in a plastic putty material. The plastic putty is to retain a degree of elasticity under varying temperature conditions and provide the sensor switch with a self-adjusting property. This provides the switch with a built-in compensating mechanism that ignores small, very slow changes in lever alignment (which may result from environmental changes including extreme temperature variations and ground creepage due to weather conditions) and to react to fast changes only, as caused by manual deflection or cutting of the wires.
h. Provide metal slider strips having slots through which the barbed wires pass with rivets that prevent the wires from leaving the slots.
The slider strip must translate horizontal displacement forces normal to the barbed wire to the sensor. Install one slider strip pair, upper and lower, on every fence post except where sensor posts or
SECTION 28 10 05 Page 19 anchor strips are installed. Provide maximum separation between slider elements along the fence of 10 feet.
i. Attach barbed or barbless wires to installed fence anchor posts, located equidistant on both sides of sensor posts and at ends of sensor zone run. Install fastening plates on an anchor strip. Weld strip or otherwise attach the strip to anchor post and ends of tensed barbed wires wrapped around the fastening plates. Fastening plates are to break off when climbed upon or on the attached barbed or barbless wires creating an alarm and making it impossible to defeat the system by climbing at the anchor post.
j. Use barbed or barbless wire suitable for installation under a preload of approximately 88 pounds tension and be flexible enough for convenient manipulation during tensioning. The minimum acceptable double-strand barbed wire gage is 15-1/2.
k. Sensor zone control unit must monitor up to 10 zones.
l. Provide sensor with relay outputs to interface alarm outputs with the overall ESS. Input power is 120 or 230 VAC.
2.3.7.2.5 Dual Technology Sensors
a. Provide dual technology sensor that combines Microwave and Dual PIR into one single all-weather detector. Use the sensor in extreme outdoor conditions to provide the maximum amount of coverage in a horizontal plane.
b. The sensor must come mounted in an industrial-grade housing as specified in paragraph COMPONENT ENCLOSURE. Provide pan-tilt swivel bracket with swivel within 100 degrees of range and tilt within 10 degrees. The swivel bracket is to allow for calibration into 1-degree segments for adjustment to any environment.
c. The sensor must provide either wide angle or long-range detection by change of optical mirrors. Wide angle coverage must detect intrusion out to 49 feet and long-range coverage out to 130 feet. Provide sensors that allow adjustment masks for wildlife immunity for animals up to 99 pounds.
2.3.7.2.6 Bistatic Microwave Sensor
a. Provide sensor equipped with circuitry that produces an alarm signal when the sensor's receiver is captured by another microwave transmitter. Multiple sensors must be able to operate in adjacent zones without interfering with each other. Provide sensors with adjustable sensitivity controls within the sensor that are not accessible when the sensor housing is in place. Provide sensors that can be adjusted in order to obtain the designed coverage pattern.
b. The bistatic microwave sensor is to consist of a separate transmitter and receiver. The sensor detects changes from a standard intruder's movement in the received microwave signal sensor's detection pattern.
The sensor transmits an alarm signal to the alarm annunciation system upon detecting such changes. The sensor must detect a standard intruder moving perpendicular through the sensor's detection pattern at a speed of 0.2 to 25 fps.
SECTION 28 10 05 Page 20
c. Equip the sensor with an LED walk test indicator which is not visible during normal operations. When visible, the walk test indicator is to light when the sensor detects an intruder. Provide sensors equipped with a manual control, located within the sensor's housing, to enable and disable the test indicator or with the test indicator located within the sensor housing so that it can only be seen when the housing is open or removed.
2.3.7.2.7 Monostatic Microwave Sensor
a. Multiple sensors must be able to operate in adjacent zones without interfering with each other. Provide sensors with adjustable sensitivity controls within the sensor that are not accessible when the sensor housing is in place. The sensor must be adjustable to obtain the coverage pattern shown and have range cut off capabilities of field selected distance 100 to 400 feet.
b. The monostatic microwave sensor must consist of an integrated transceiver. The sensor detects changes from a standard intruder in the received microwave signal sensor's detection pattern. The sensor must transmit an alarm signal to the alarm annunciation system upon detecting such changes. The sensor must detect a standard intruder moving perpendicular through the sensor's detection pattern at a speed of 0.2 to 25 fps.
c. The sensor is to be equipped with an LED walk test indicator which is not visible during normal operations. When visible, the walk test indicator is to light when the sensor detects an intruder. Provide sensors equipped with a manual control, located within the sensor's housing, to enable and disable the test indicator or with the test indicator located within the sensor housing so that it can only be seen when the housing is open or removed.
2.3.7.2.8 Passive Infrared Sensor (Exterior)
a. UL 639 . The passive infrared sensor must detect movement from a standard intruder in the ambient level of infrared emissions within the sensors' field of view.
b. The sensor is to detect a change in temperature of at least 2 degrees F and detect an intruder traveling within the sensor's detection pattern at a speed of 0.6 to 50 fps across 2 adjacent segments of the field of view. The sensor must have a detection range of at least 300 feet. Emissions monitored by the sensor must be in the 8 to 14 micron range.
c. Provide sensors that can be adjusted to obtain the designed coverage pattern. The sensor is to be equipped with a temperature compensation circuit.
d. The sensor is to be equipped with an LED walk test indicator which is not visible during normal operations. When visible, the walk test indicator is to light when the sensor detects an intruder. Provide sensors equipped with a manual control, located within the sensor's housing, to enable and disable the test indicator or with the test indicator located within the sensor housing so that it can only be seen when the housing is open or removed.
SECTION 28 10 05 Page 21
2.3.7.2.9 Buried Ported Cable
The buried ported cable to monitor for changes in the electromagnetic field between the leaky coax transmit and receive cables within the sensor's detection pattern to detect standard intruder movement. The sensor must transmit an alarm signal to the alarm annunciation system upon detecting such changes. Provide sensors that detect a standard intruder moving through the sensor detection pattern at a speed of 0.2 to 25 fps.
Provide ported coaxial transmission and receive cables rated for direct burial. Provide sensors to obtain the designed coverage pattern with adjustable sensitivity to 3 feet length by controls within the sensor signal processor. Controls must not be accessible when the sensor signal processor's housing is in place. Equip the sensor with a test indicator if it is an integral sensor signal processor function.
2.3.7.2.10 Active Infrared Sensor (Exterior)
a. The active infrared sensor detects a light beam interruption that links the transmitter and receiver caused by an intruder moving at a speed of less than 7.5 fps through the beam. The sensor must transmit an alarm signal to the alarm annunciation system upon detecting such an interruption.
b. The sensor must use a pulsed infrared light source. Multiple sensors must be able to operate within the same zone without interfering with each other. Provide sensors to obtain the designed coverage pattern with adjustable sensitivity with controls located within the sensor signal processor and not accessible when the sensor signal processor's housing is in place.
c. The sensor is to be equipped with an LED walk test indicator which is not visible during normal operations. When visible, the walk test indicator is to light when the sensor detects an intruder. Provide sensors equipped with a manual control, located within the sensor's housing, to enable and disable the test indicator or with the test indicator located within the sensor housing so that it can only be seen when the housing is open or removed.
d. The sensor may incorporate remote test if it is an integral sensor function .
2.3.7.2.11 Video Motion Sensor (Exterior)
Provide a video motion sensor to detect changes in the video signal within a user defined detection zone as described in paragraph VIDEO ANALYTICS (VA). The system must detect changes in the video signal corresponding to a standard intruder moving within the defined detection zone and wearing clothing with a reflectivity that differs from that of the background scene by a factor of 2. Provide signal processing techniques to eliminate non-alarm background motion including light changes, trees blowing, and birds. Provide sensor with controls and method needed by the operator to define and adjust the sensor detection zone within the video picture.
Video motion sensor system must operate using digital cameras. The number of detection zones, the size of the detection zones, and the sensitivity of the detection zones are to be user definable. Provide sensors that accommodate multiple video inputs and have the capability of modular growth. The video inputs must accept composite video. The sensor must
SECTION 28 10 05 Page 22 not require external sync for operation. Provide one alarm output for each video input. Provide number of video inputs and alarm outputs as required for an operable system. Rack-mount sensor equipment in a standard rack as described in paragraph EQUIPMENT RACK with hardware includes as required to mount the sensor components.
2.3.7.2.12 Radar
The radar system must provide intruder detection to 2300 feet. Provide monostatic type unit in which the transmitter and receiver are encased within a single housing unit (transceiver). The radar is to be equipped with a signal processor that is programmed to recognize reflected energy from the normal environmental surroundings and eliminate those objects relative to alarm. Provide unit with the capability of preprogramming specific parameters, size and speed, above which an alarm signal is generated.
The system is to provide alarm information to the ESS to identify specific zones of concern to include range and azimuth information, as a minimum.
The information must have the capability of integrating with VSS or video motion sensor systems, to "call" the cameras to a particular view for alarm verification. The system is to be able to retrofit with existing VSS or other detection systems. After radar system installation, post warning signs indicating radiation hazard as recommended by the manufacturer.
2.3.7.3 Duress Alarms (Hold Up Switch)
UL 636 . Duress alarm switches must provide the means for an individual to covertly notify the alarm annunciation system that a duress situation exists with no visible or audible signal in the secure area.
2.3.7.3.1 Hardwire Duress Alarms
Alarms must be capable of being secretly activated by the foot or hand of an average adult in both standing and seated positions. Upon activation the alarm signal is to lock-in until manually reset with a key or similar device and be readily identifiable by the ESS.
Provide sensors that are easy to operate and configured to minimize the possibility of accidental activation. Hardwire duress alarms must be rated for a minimum lifetime of 50,000 operations. Securely mount sensors in rugged, corrosion-resistant housing.
2.3.7.3.2 Wireless Duress Alarms
Wireless duress alarm switches to consist of portable alarm transmitters easily worn on the body or clothing. Alarm activation is to be by hand-operated switch protected from accidental activation, yet easily activated by hand when worn at the waist on body or clothing which transmits a unique identification code to one or more receivers located within a protected zone. The receivers, in-turn, are to transmit an alarm signal to the ESS system. Sensor activation is to be automatic when mounted on a body or clothing and the wearer is in a horizontal position for longer than 15 minutes, adjustable.