This notice summarizes a federal solicitation for design-build construction services related to eight military construction projects at Marine Corps Base Camp Lejeune in North Carolina. The solicitation will result in a firm-fixed price contract to replace headquarters facilities and support buildings damaged by Hurricane Florence in 2018, including facilities for combat logistics battalions, a tank battalion, regimental headquarters, an infantry battalion, Marine expeditionary units, a transportation support battalion, and an environmental management division. The projects involve new construction of administrative, operational, and classroom buildings totaling over 300,000 square feet. The period of performance is 1,826 calendar days. The solicitation is unrestricted and will utilize a two-phase evaluation including technical, past performance, safety, project management, and price factors. The contracting office anticipates award by July 2020.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
8 Substation Impedance and Fault Currents
Point of Delivery Impedance and Faults Sub. 1 Sub. 2 Sub. FC Sub. Geiger Sub. Johnson
Z1R Resistance (pu @ 100 MVA) 0.0448 0.086 0.0171 .0844 X/R Ratio = 13 Z1X Reactance (pu @ 100 MVA) 0.3439 0.6583 0.4336 .6462 N/A Z0R Resistance (pu @ 100 MVA) 0.0408 0.083 0.0125 .0817 N/A Z0X Reactance (pu @ 100 MVA) 0.3103 0.6306 0.3958 .6206 N/A Fault Curr. 3 Ph (Amps) 12,907 6,789 10,315 6,825 2,722 Fault Curr. Ph-Gnd (Amps) 13,340 6,885 10,624 6,916 N/A 3 Ph Shrt Crkt (MVA) 297 155.1 237.3 156 N/A Trnsfmr ONAN Rating (MVA) 30 15 24 15 (3) x 1.667 Trnsfmr Impedance (%) 9.39 9.54 9.5 9.39 5.47,5.39,5.43 High Side Voltage (kV) 230 230 230 230 22.86 Bus Voltage (kV) 13.09 13.00 13.09 13.09 13.09
File details come from the government source that posted it. Updated .