003 0101 Tk Vent Ref Scope - Response.docx

DOCX document 27 KB Posted

Attached to
USNS MERCY ROH/DD Federal contract opportunity
Solicitation number
N3220520R6500
Issued by
Department of the Navy Military Sealift Command

About this file

This document contains a contractor's response to a request for specification clarification from the Department of the Navy Military Sealift Command regarding solicitation N3220520R6500 for repair and deferred maintenance work aboard the USNS Mercy. The contractor requested additional drawings and sizing information for miscellaneous tank vent piping, overflow port vent repairs, and replacement of vent piping. The Navy provided the requested drawing and specified the vent valve and piping lengths needed.

View the file

Other files for this federal contract opportunity

Other files attached to USNS MERCY ROH/DD, newest first.
File Type Posted
Amendment 008.docx DOCX document
Amendment 7.docx DOCX document
Amendment 6.docx DOCX document
Revised J-3 Category B Items.xlsx XLSX spreadsheet
Revised J-2 Category A Item.xlsx XLSX spreadsheet
Amendment 5.docx DOCX document
020 NAG Marine Software 1_9_20.rtf RTF text file
020 NAG Marine Software.docx DOCX document
AMENDMENT 4.docx DOCX document
022 1001 Ceiling panel size.docx DOCX document
025 Nag Material Request.docx DOCX document
N3220520R6500 Amendment 0003.docx DOCX document
Copy of J-3 Category B Items.xlsx XLSX spreadsheet
RFCs 013 through 019.docx DOCX document
AMENDMENT 2 MERCY.docx DOCX document
006 0920 Stability Lightship-Response.docx DOCX document
012 0907 blast prep - Response.docx DOCX document
009 Extension Request.docx DOCX document
004 0102 Anti Roll Tk Ref and Scope - Response.docx DOCX document
007 0105 WT Door size and detail - Response.docx DOCX document
005 0103 Ladders Rails scope - Response.docx DOCX document
011 Missing TMs - Response.docx DOCX document
010 Ballast System Valve Actuator Repair - Response.docx DOCX document
008 Missing DWGs & TMs.docx DOCX document
Q&A #1.docx DOCX document
Q&A #2.docx DOCX document
J-13 Past Performance Questionnaire.docx DOCX document
DD Form 1423-1 SWI-022 Machinery Turnover, Dock and Sea Trials.pdf PDF
J-4 GFP Report.xlsx XLSX spreadsheet
DD Form 1423-1 SWI-019 Shipboard Access.pdf PDF
J-3 Category B Items.xlsx XLSX spreadsheet
DD Form 1423-1 SWI-012 Telephone Service.pdf PDF
DD Form 1423-1 SWI-001 General Requirements.pdf PDF
J-2 Category A Item.xlsx XLSX spreadsheet
DD Form 1423-1 SWI-015 ILS GFM Support.pdf PDF
DD Form 1423-1 SWI-014.pdf PDF
J-9 Disclosure of Lobbying Activities SF-LLL.docx DOCX document
SOLICITATION N3220520R6500.docx DOCX document
J-14 Technical Data Non-Disclosure.docx DOCX document
J-5 Subcontracting Plan.docx DOCX document
DD Form 1423-1 SWI-013 Project Planning.pdf PDF
DD Form 1423-1 SWI-004 Testing Quality Assurance.pdf PDF
DD Form 1423-1 SWI-018 Delivery and Redelivery.pdf PDF
DD Form 1423-1 SWI-020 Gas Free Certificates.pdf PDF
DD Form 1423-1 SWI-016 Fire Protection.pdf PDF
J-10 Interport Differential.docx DOCX document
DD Form 1423-1 SWI-017 Ships Stores.pdf PDF
J-7 MSC Ship Repair Facility Survey.docx DOCX document
DD Form 1423-1 SWI-003 Approach - Berth - Mooring.pdf PDF
J-12 Past Performance Data.docx DOCX document
Show all 50

USNS MERCY ROH/DD has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N3220520R6500

USNS MERCY (T-AH 19) ROH/DD

REQUEST FOR SPECIFICATION CLARIFICATION

Q#003 12/5/19

NAME OF CONTRACTOR:

SPECIFICATION ITEM NO.: 0101

PARAGRAPH / SECTION NO: 2.1.1 & 7.2

TITLE: MISCELLANEOUS TANK VENT PIPING

QUESTION:

Reference 2.1.1. NAVSEA Drawing 506-5980080 Rev C Tank Vents and Sounds was not provided in solicitation package and will be required to determine routes, penetrations, and sizes.

Additonally, the following paragraphs are missing sizes or scope to estimate pricing:

7.3.1. DFM 6-87-2 overflow port vent needs repair, cover threads are stripped, vent valve need replacement. Location 1-95-2 (Need vent valve size)

7.3.4. SSDG fuel tank vent pipe need replacement piping size 2.5" location 1-126-5 (Need lengh of piping to be renewed)

7.3.5. Steam plant engine room sea chest vent pipe 4" piping need piping replacement and new vent valve location 1-105-5 (Need lengh of piping to be renewed)

ANSWER:

7.3.1 10” vent valve

7.3.4 20 feet of pipe

7.3.5 58 feet of pipe

Drawing 5980080 will be provided.