This is a structured cabling technology design document for Morrish Elementary School in the Swartz Creek Community Schools system, created by Convergent Technology Partners. The document consists of a floor plan and technical specifications for Category 6A UTP cable installation throughout the school building, with work to be completed between December 2024 and January 2025. The scope includes installation requirements for wall-mounted single-gang back boxes with white two-port faceplates, ceiling cable runs, and telecom cabinets and bus-bars throughout the facility.

The technical specifications require all UTP cable to be ANSI/TIA Category 6A standard, with specific installation requirements including concealed raceway placement, service loops for ceiling locations, white 8P/8C (RJ45) jack terminations, and grounding for all cabinets. The floor plan shows multiple UTP locations and ceiling UTP locations distributed throughout the building, along with telecom cabinets and bus-bars. Installation heights and placement requirements are specified relative to whiteboards and wall locations, with precise requirements for cable concealment and service loop securing.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1 1 1

1 1

1 1

TGB

SYMBOL LEGEND

UTP LOCATION, QTY AS

NOTED

CEILING UTP LOCATION,

QTY AS NOTED

TELECOM CABINET

TELECOM BUS-BAR

REPLACE CABINETR

GENERAL NOTES

1. ALL UTP CABLE SHALL BE ANSI/TIA

CATEGORY 6A. PLACE WALL LOCATIONS

IN A SURFACE MOUNTED SINGLE-GANG

BACK BOX WITH A WHITE TWO PORT

FACEPLATE.

2. THE UNUSED TOP PORT OF THE

FACEPLATE IS TO BE FILLED WITH A

BLANK KEYSTONE JACK INSERT.

3. PLACE WALL LOCATIONS CENTERED

BELOW WHITEBOARD AT STANDARD

HEIGHT.

4. LOCATIONS WITHOUT WHITEBOARDS,

CENTER THE INSTALLATION ON THE WALL

AT STANDARD HEIGHT.

5. ALL CABLE BELOW CEILING SHALL BE

CONCEALED IN RACEWAY PROVIDED BY

CONTRACTOR.

6. PROVIDE CEILING LOCATION WITH

SERVICE LOOP LONG ENOUGH TO REACH

THE FARTHEST LOCATION IN THE

ASSOCIATED ROOM. SECURELY FASTEN

SERVICE LOOP TO STRUCTURE.

7. TERMINATE ALL CATEGORY 6A CABLES

ON WHITE 8P/8C (RJ45) JACKS.

8. LOCATION OF BUS BLOCKS ARE

ESTIMATED, USE BEST PRACTICES FOR

INSTALLATION LOCATION.

9. FOR ESTIMATES ASSUME ALL CABINETS

NEED GROUNDING.

C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473

Phone: 810.720.3820 www.ctpartners.net

T E C H N O L O G Y P A R T N E R S

TECHNOLOGY DESIGN I CONSULTING I PLANNING

1/23/2025 DESIGN DLF

12/17/2024 DESIGN EGH

DATE ISSUE AUTHOR

SWARTZ CREEK

COMMUNITY SCHOOLS

STRUCTURED CABLING

MORRISH ELEMENTARY

SCHOOL

ME-T101

T101

NTS

MOORISH FLOOR PLAN

Sheets and Views
ME-T101