This is an architectural/engineering drawing for structured cabling at Swartz Creek High School's Unit E, created by Convergent Technology Partners, showing the layout and specifications for Category 6A cable installation. The drawing details the placement of UTP locations, ceiling UTP locations, telecom cabinets, and bus bars throughout Unit E of the high school, which includes a cafeteria, kitchen, main office area, and staff lounge. The design was completed in January 2025 with initial design work done in December 2024.
The technical specifications require all UTP cable to be ANSI/TIA Category 6A, installed in surface-mounted single-gang back boxes with white two-port faceplates, with unused top ports filled with blank keystone jack inserts. Wall locations must be centered below whiteboards at standard height, and all cabling below ceiling must be concealed in contractor-provided raceway. The plan requires ceiling locations to have service loops capable of reaching the farthest point in associated rooms, with all Category 6A cables terminating on white 8P/8C (RJ45) jacks. The project assumes all cabinets need grounding, and bus block locations are to be determined using best practices for installation.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNIT E
0' 5' 10' 20' 30' 40' 50'
NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS
TGB
TGB
SYMBOL LEGEND
UTP LOCATION, QTY AS
NOTED
CEILING UTP LOCATION,
QTY AS NOTED
TELECOM CABINET
NEW TELECOM BUS-BAR
EXISTING BUS-BAR
OLD COMPUTER LAB
TGB
B C
A D
E F
G
GENERAL NOTES
1. ALL UTP CABLE SHALL BE ANSI/TIA
CATEGORY 6A. PLACE WALL LOCATIONS IN A
SURFACE MOUNTED SINGLE-GANG BACK BOX
WITH A WHITE TWO PORT FACEPLATE.
2. THE UNUSED TOP PORT OF THE FACEPLATE
IS TO BE FILLED WITH A BLANK KEYSTONE
JACK INSERT.
3. PLACE WALL LOCATIONS CENTERED BELOW
WHITEBOARD AT STANDARD HEIGHT.
4. LOCATIONS WITHOUT WHITEBOARDS,
CENTER THE INSTALLATION ON THE WALL AT
STANDARD HEIGHT.
5. ALL CABLE BELOW CEILING SHALL BE
CONCEALED IN RACEWAY PROVIDED BY
CONTRACTOR.
6. PROVIDE CEILING LOCATION WITH SERVICE
LOOP LONG ENOUGH TO REACH THE
FARTHEST LOCATION IN THE ASSOCIATED
ROOM. SECURELY FASTEN SERVICE LOOP TO
STRUCTURE.
7. TERMINATE ALL CATEGORY 6A CABLES ON
WHITE 8P/8C (RJ45) JACKS.
8. LOCATION OF BUS BLOCKS ARE ESTIMATED,
USE BEST PRACTICES FOR INSTALLATION
LOCATION.
9. FOR ESTIMATES ASSUME ALL CABINETS
NEED GROUNDING.
C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473
Phone: 810.720.3820 www.ctpartners.net
T E C H N O L O G Y P A R T N E R S
TECHNOLOGY DESIGN I CONSULTING I PLANNING
1/24/2025 DESIGN DLF
12/17/2024 DESIGN EGH
DATE ISSUE AUTHOR
SWARTZ CREEK
COMMUNITY SCHOOLS
STRUCTURED CABLING
SWARTZ CREEK HIGH
SCHOOL
HS-T101E
T101E
NTS
HIGH SCHOOL UNIT E
KEYMAP