MIDDLE SCHOOL MS-T101-MS-T101F.pdf

PDF 566 KB Posted

Attached to
2025 E-Rate Network Cabling Additions
Solicitation number
RFP-SCC-250000001194-2
Issued by
Michigan

About this file

This is a technical structured cabling design document prepared by Convergent Technology Partners for the Swartz Creek Community Schools' Middle School natatorium (swimming pool facility). The drawing shows detailed specifications for Category 6A UTP cable installation in both the upper and first floor natatorium areas, including requirements for wall locations, ceiling locations, telecom cabinets, and bus bars. The design was completed in December 2024/January 2025 and includes specific installation requirements such as surface-mounted single-gang back boxes with white two-port faceplates, cable concealment in contractor-provided raceways, and proper termination on white 8P/8C (RJ45) jacks.

The technical specifications require all UTP cable to meet ANSI/TIA Category 6A standards, with specific installation heights centered below whiteboards or centered on walls at standard height where whiteboards are not present. The document includes requirements for service loops in ceiling locations, grounding for all cabinets, and bus block placement according to best practices. The drawing provides detailed floor plans for both levels of the natatorium, including adjacent spaces such as locker rooms, offices, storage areas, and a laundry facility.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U N

IT

A

U N

IT

F

0' 5' 10' 20' 30' 40' 50'

NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS

TGB

SYMBOL LEGEND

WALL UTP LOCATION, QTY AS

NOTED

CEILING UTP LOCATION, QTY AS

NOTED

TELECOM CABINET

TELECOM BUS-BAR

REPLACE CABINETR

B

A

C D

E

FF

0' 5' 10' 20' 30' 40' 50'

NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS

UNIT F

GENERAL NOTES

1. ALL UTP CABLE SHALL BE ANSI/TIA

CATEGORY 6A. PLACE WALL LOCATIONS IN

A SURFACE MOUNTED SINGLE-GANG BACK

BOX WITH A WHITE TWO PORT FACEPLATE.

2. THE UNUSED TOP PORT OF THE

FACEPLATE IS TO BE FILLED WITH A BLANK

KEYSTONE JACK INSERT.

3. PLACE WALL LOCATIONS CENTERED

BELOW WHITEBOARD AT STANDARD

HEIGHT.

4. LOCATIONS WITHOUT WHITEBOARDS,

CENTER THE INSTALLATION ON THE WALL

AT STANDARD HEIGHT.

5. ALL CABLE BELOW CEILING SHALL BE

CONCEALED IN RACEWAY PROVIDED BY

CONTRACTOR.

6. PROVIDE CEILING LOCATION WITH SERVICE

LOOP LONG ENOUGH TO REACH THE

FARTHEST LOCATION IN THE ASSOCIATED

ROOM. SECURELY FASTEN SERVICE LOOP

TO STRUCTURE.

7. TERMINATE ALL CATEGORY 6A CABLES ON

WHITE 8P/8C (RJ45) JACKS.

8. LOCATION OF BUS BLOCKS ARE

ESTIMATED, USE BEST PRACTICES FOR

INSTALLATION LOCATION.

9. FOR ESTIMATES ASSUME ALL CABINETS

NEED GROUNDING.

C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473

Phone: 810.720.3820 www.ctpartners.net

T E C H N O L O G Y P A R T N E R S

TECHNOLOGY DESIGN I CONSULTING I PLANNING

1/27/2025 DESIGN DLF

12/17/2024 DESIGN EGH

DATE ISSUE AUTHOR

SWARTZ CREEK

COMMUNITY SCHOOLS

STRUCTURED CABLING

SWARTZ CREEK

MIDDLE SCHOOL

MS-T101F

KEYMAP

T101F

NTS

UPPER NATATORIUM

T101F

NTS

1ST FLOOR NATATORIUM